INTRODUCTION
Teknoware
With more than 40 years of fullfill the relevant standards at
experience, Teknoware is one all times. Our customers benefit
of the leading emergency from our extensive expertise and
lighting manufacturers. We are a experience.
significant technological innovator
of emergency lighting systems As a baseline, Teknoware´s entire
for buildings, ships and other product range is designed to meet
locations. Our emergency lighting the requirements of the relevant
product range covers exit lights, European directives and standards.
emergency lights, central battery
systems, emergency lighting
monitoring systems and central
monitoring softwares, control
electronics, spare parts and much
more.
5
SYSTEM DESIGN: THINGS TO CONSIDER
Emergency lighting can be ►► the purpose of the building (e.g. ►► high risk lighting requirements
implemented by two different back up power source, and
ways: back up time requirements)
►► the acquisition cost (the
equipment and the cabling,
►► a centrally supplied emergency including the cost of installation)
lighting system
►► operating costs (maintenance
►► self-contained emergency and and energy costs)
exit lights.
►► control procedures of the
When determining the most system (automatic/manual
suitable emergency lighting testing)
system for a building, the possible
restrictions imposed by the ►► connecting to an existing
installation environment need to system (system expansion)
be taken into account.
►► use of existing cabling for
renovations
Things to consider when you
choose the emergency lighting
►► architectural aspects, design of
system: ►► construction type (new the luminaires
construction, renovation or
►► the size of the building/site and expansion)
the total number of emergency ►► fire zones
and exit lights
1~N/PE
IP 220-240
VAC
67 50HZ
►► environmental factors
(recyclability, disposal of the
parts and components, e.g.
batteries)
6
Emergency lighting Emergency lighting ►► size of the batteries (required
specification generally includes specification can be back up operation time)
the following documents: summarized using the following
checklist: ►► choosing the type of the cables
►► electrical evaluation report, for the system cabling
which sets out a general
description for the system and ►► choosing the luminaire
types (viewing distance, ►► cross section of the cabling,
determines the equipment to
IP classification, mounting taking into account the loss of
be used
height etc.) voltage and the minimum short
►► drawing of the electrical plan, circuit current (electrotechnical
where the locations of the ►► placement of luminaires design).
luminaires and the central (luminaire technical design)
battery systems are presented
►► choosing the type of the
►► emergency lighting graph, system (central battery or self-
where the system cabling is laid contained)
out
IP
65 65 m
7
EMERGENCY LIGHTING SYSTEM FEATURES
8
SYSTEM DESIGN: EMERGENCY AND EXIT LIGHTS
Stage 1 Stage 3
►► change of direction
►► pedestrian routes within
covered car parks
►► near fire fighting equipment
9
MARKINGS
= CE marking
a) First segment containing one position: TYPE (marked already in the factory)
X self-contained luminaire
Z centrally supplied luminaire
10
TERMINOLOGY AND STANDARDS
Emergency lighting is one of the power fails. (=emergency light). emergency lights to be marked
most important safety systems in with information relevant to type,
a building. Emergency lighting A maintained luminaire operates performance and manufacture.
makes it possible to safely stop at all times, both when the mains
The CE mark is a mandatory
working and to evacuate the fails, and when it is present light.
requirement for all luminaires
building, by following the exit (=exit light).
for sale in Europe. This marking
lights, in case of an emergency.
is placed on the product by the
Emergency lighting is a standalone High risk task areas of high
manufacturer and proves that the
backup system, which does not physical risk, or the control rooms
product conforms to all relevant
rely on the functionality of the of dangerous plant and production
safety standards.
general electrical distribution lines, need emergency lighting
system in the building. It must to enable them to be shut down Response time is a time that
always be operational and ready safely. elapses between the failure of
for use.
the normal power supply, and the
EN 1838 is an European Standard auxiliary power supply energizing
Emergency exit route is a that specifies the luminous the equipment.
continuous and unobstructed requirements for emergency
path of exit, from any point escape lighting and standby
of the building, in the case of lighting systems, installed in
an emergency. This route isn’t premises or locations, where such
necessarily used everyday, but systems are required.
must be lit up by the appropriate
warning and directional signs. EN 50171 is the standard relevant
to central power supply units and
Open (anti-panic) area lighting systems, controlling their design,
is necessary to reduce confusion construction and performance
and panic, whilst ensuring visibility requirements.
of the nearest exit route.
EN 50172 standard includes the
requirements for illumination lux
Emergency light is a luminaire
levels for additional areas, and
which may or may not be provided
the requirements for service and
with its own electrical source for
maintenance.
safety services and which is used
for safety or emergency lighting. EN 60598-2-22 is the product
standard for emergency lights.
Exit Light is a luminaire,
The standard ensures that the
that indicates and assists the
products are safe to use, and have
identification of escape routes.
been designed and manufactured
for correct performance
A non-maintained luminaire under emergency conditions.
operates only, when the mains EN 60598 -2-22 also requires all
11
MANDATORY “POINTS OF EMPHASIS”
Any point on an escape route, or leading to it, must have an exit sign, so that the direction of travel is not in
doubt. Exit signs should clearly identify the full extent of the escape route, including any changes of direction.
Emergency Lighting must be provided along escape routes, and in the open areas leading to them, to enable
people to move quickly and safely to an exit.
Highlighting fire fighting and first aid High Risk task areas Outside and near each final exit
equipment
12
DURATION TIMES AND RESPONSE TIMES
Response times
13
VIEWING DISTANCE
For all formats of exit lights and The viewing distance is the pictogram in mm. For example a
signs, the maximum viewing distance, from which the sign can 100 mm high pictogram gives a
distances and luminance be clearly seen and understood. viewing distance of 20 m.
conditions are given in EN 1838:
2013. The minimum height of the
internally illuminated pictogram is
Exit lights must be placed at any
calculated with the formula:
change in direction, to indicate the
d = 200 x h, where d = viewing
route to the final exit door.
distance, h = height of the
h 200
xh
14
THE PERFORMANCE REQUIREMENTS FOR THE EXIT LIGHTS
Exit lights need to fulfil the Within the same colour, the emergency lighting system to
performance requirements contrast must be less than 1:10. be according to the relevant
of the European standard EN emergency lighting standards.
1838. This standard determines These will guarantee the minimum
observability for the pictogram. Since 2011, the pictogram format
the requirements both for the
This is the most important feature adopted both by BSI and EN
luminance and the contrasts.
of an exit light, and it cannot be standards, is ISO 7010.
The minimum luminance in the neglected e.g. due to the quest for
green area is 2 cd/m2. a lower energy consumption, or
the product costs.
The contrast between the white 1996 2011
and the green area must be In the end, the owner of the
between 1:5 and 1:15. building is responsible for the
15
ILLUMINATION
Escape route
illumination Escape Route Illumination
16
GLARE ZONE AND CONTRAST RATIO
Contrast ratio
17
TESTING AND MAINTENANCE
Central battery unit and be carried out according to the Automatic testing systems
emergency exit lights shall be standard EN 50172.
Teknoware provides automatic
maintained regularly, to secure
testing for both centrally supplied
trouble-free operation. ►► the indicators of the emergency
lighting central battery system and self-contained emergency
must be visually inspected on a lighting systems.
Teknoware recommends, that the
daily basis
central battery system should be
Teknoware’s central monitoring
tested and maintained according ►► the emergency mode of each and self-testing systems take care
to the standard EN 50172, as luminaire is tested monthly,
of the required light source and
follows: by switching the luminaire to
battery feed, either manually, or duration tests automatically.
automatically
Testing
►► once per year, the full duration
The operation of the luminaire test of 1 h, or a determined
shall be verified according to the longer time, is to be made, by
requirements of the authorities. switching the system to battery
feed, for the entire duration
time
The battery mode duration of the
self-contained types can be tested
►► all the tests and results shall
by be recorded in the logbook of
the emergency lighting system
►► switching off the mains supply
and when asked, it shall be
voltage
presented to the authorities for
inspection
►► using self-testing feature such
as Lumi Test, or
►► in addition, a daily visual
inspection of the maintained
►► using a central monitoring exit lights is recommended.
software, such as Aalto Control,
which also record the test
results.
18
AUTOMATIC TESTING AND MONITORING
Tapsa Control central battery unit Aalto Control provides a wireless Lumi Test self-diagnosis, which
includes the following monitoring, central monitoring for self- is available for self-contained
testing and reporting functions: contained emergency and exit luminaires, automatically tracks
lights. There is no need to connect and tests the reliable operation
►► testing the luminaires
the luminaires with data cables. of the luminaires. LED indicators
either through addressable
monitoring, or by measuring The only requirement is, that each (one green and one red) display
the circuit current individual luminaire has a local the status of the luminaires. Red
power supply, like any standard LED indicates fault. The luminaire´s
►► monitoring the condition of the self-contained luminaires. All the functionality and light source are
batteries benefits of the self-contained tested daily. Full emergency mode
luminairess are preserved, duration is tested every 6 months.
►► testing the capacity of the and each luminaire functions
batteries
independently. All Aalto Control emergency and
exit lights also include Lumi Test.
►► indicating the address of the
faulty circuit and luminaire Installation is simple, and
the luminaires can be easily
►► a short operation test time can positioned, even during
be set to take place after each renovations. Each luminaire is a
1…7 days node, receiving and transmitting
the signal to other luminaires. The
►► battery test every 6 months signal penetrates normal walls,
doors and floors easily, and climbs
stairways. The network is used
only for collecting information
and does not affect the operation
of the luminaires. For this reason,
Aalto Control is as robust and
resistant to failures as any other
self-contained system.