DESIGN GUIDE FOR

EMERGENCY LIGHTING SYSTEMS

Y LIGHTING
GENC
EMER

Lighting Technology
2
CONTENTS

INTRODUCTION...............................................................................................5

SYSTEM DESIGN: THINGS TO CONSIDER................................................ 6

EMERGENCY LIGHTING SYSTEM FEATURES...........................................8

SYSTEM DESIGN: EMERGENCY AND EXIT LIGHTS............................... 9

MARKINGS.......................................................................................................10

TERMINOLOGY AND STANDARDS............................................................11

MANDATORY “POINTS OF EMPHASIS”................................................... 12

DURATION TIMES AND RESPONSE TIMES............................................. 13

VIEWING DISTANCE......................................................................................14

THE PERFORMANCE REQUIREMENTS FOR THE EXIT LIGHTS.......... 15

ILLUMINATION............................................................................................... 16

GLARE ZONE AND CONTRAST RATIO.................................................... 17

TESTING AND MAINTENANCE.................................................................. 18

AUTOMATIC TESTING AND MONITORING........................................... 19

3
4
INTRODUCTION

Emergency lighting is a vital and plan and implement an emergency


effective life safety tool, providing lighting installation, that satisfies
reassurance and guidance to all the legal requirements, and
people at critical times when they ensures safe evacuation in the
need to escape quickly and safely event of an emergency.
from a building.
This guide is based on common
European standards and practices.
Specific requirements for
emergency lighting are set out in
Also, check the specific guidelines
law, and international standards.
that refer to your own country.
This Guide is based on common
This design guide will help you to European regulations.

Teknoware
With more than 40 years of fullfill the relevant standards at
experience, Teknoware is one all times. Our customers benefit
of the leading emergency from our extensive expertise and
lighting manufacturers. We are a experience.
significant technological innovator
of emergency lighting systems As a baseline, Teknoware´s entire
for buildings, ships and other product range is designed to meet
locations. Our emergency lighting the requirements of the relevant
product range covers exit lights, European directives and standards.
emergency lights, central battery
systems, emergency lighting
monitoring systems and central
monitoring softwares, control
electronics, spare parts and much
more.

We design and manufacture


both the electronics and final
products ourselves, which
guarantees compatible and
non-compromised solutions.
We can even design and
build customized emergency
lighting products and systems
for challenging environments,
making sure that all our products

5
SYSTEM DESIGN: THINGS TO CONSIDER

Emergency lighting can be ►► the purpose of the building (e.g. ►► high risk lighting requirements
implemented by two different back up power source, and
ways: back up time requirements)
►► the acquisition cost (the
equipment and the cabling,
►► a centrally supplied emergency including the cost of installation)
lighting system
►► operating costs (maintenance
►► self-contained emergency and and energy costs)
exit lights.
►► control procedures of the
When determining the most system (automatic/manual
suitable emergency lighting testing)
system for a building, the possible
restrictions imposed by the ►► connecting to an existing
installation environment need to system (system expansion)
be taken into account.
►► use of existing cabling for
renovations
Things to consider when you
choose the emergency lighting
►► architectural aspects, design of
system: ►► construction type (new the luminaires
construction, renovation or
►► the size of the building/site and expansion)
the total number of emergency ►► fire zones
and exit lights
1~N/PE
IP 220-240
VAC
67 50HZ

►► technical performance level


of the emergency lighting
equipment ►► the possibility of area
monitoring

►► environmental factors
(recyclability, disposal of the
parts and components, e.g.
batteries)

►► anti-panic illumination of open


areas

6
Emergency lighting Emergency lighting ►► size of the batteries (required
specification generally includes specification can be back up operation time)
the following documents: summarized using the following
checklist: ►► choosing the type of the cables
►► electrical evaluation report, for the system cabling
which sets out a general
description for the system and ►► choosing the luminaire
types (viewing distance, ►► cross section of the cabling,
determines the equipment to
IP classification, mounting taking into account the loss of
be used
height etc.) voltage and the minimum short
►► drawing of the electrical plan, circuit current (electrotechnical
where the locations of the ►► placement of luminaires design).
luminaires and the central (luminaire technical design)
battery systems are presented
►► choosing the type of the
►► emergency lighting graph, system (central battery or self-
where the system cabling is laid contained)
out

►► table of luminaires, which


defines the type of the
emergency and exit lights

►► the addresses for the luminaires


(in addressable emergency
lighting systems)

►► maintenance plan and service


and operational manual.

IP
65 65 m

7
EMERGENCY LIGHTING SYSTEM FEATURES

Emergency lighting can be ►► Addressable 230 V central Teknoware Advanced Central


implemented by two different battery systems Monitoring system (ACM), uses a
methods: either with self-contained separate network for addressable
emergency luminaires, or with ►► Non-addressable 230 V central (Tapsa Control compatible) central
a centrally supplied emergency battery systems. cattery units. ACM contains a
lighting system. map view, and a variety of options
and functions for monitoring both
Central Monitoring Options for
Self-contained means, that the the central battery units and the
Central Battery Systems
emergency lights contain their own emergency and exit lights.
backup power source, such as a A central monitoring system
battery. Centrally supplied means, monitors all individual components
Self-Contained Systems
that the back up power source is a of an emergency lighting system,
central battery unit. and gathers all collected information In the self-contained systems, each
to a single location. This makes emergency and exit light has its own
Teknoware offers emergency monitoring the system fast and easy, backup power source, traditionally a
lighting products from both no matter how complicated the battery. This kind of a system is the
categories. From individually location is. The system also records most applicable in such buildings,
packed, self-contained luminaires, data about performed tests. where the maintenance of the
to centrally supplied and monitored batteries, located in each luminaire,
systems, consisting of several Teknoware offers several different can be arranged with reasonable
thousand emergency lighting options for monitoring of the costs.
components. Product designs vary addressable, centrally supplied
from stylish, high-end luminaires to luminaires. In ESCAP emergency and exit
robust emergency lighting products lights, the adaptability of the self-
designed to withstand even the For web-based central monitoring contained luminaires is combined
harshest and most challenging there is Web Central Monitoring with environmental friendliness,
environments. (WebCM), which enables the and freedom from maintenance.
monitoring of the state of the Instead of a battery, in the luminaire
addressable Tapsa Control central there is a maintenance-free Super
Central Battery Systems battery system via internet. WebCM capacitor, the life-time of which
also indicates test log information, exceeds 10 years.
In short, central battery system
and has the option of remotely
for emergency lighting means,
run luminaire and battery tests.
that the backup power source for Central Monitoring for Self-
WebACM adds a map view to the
the emergency and exit lights is Contained Systems
system, which makes locating the
provided centrally.
luminaires fast and easy. WebACM
For the self-contained luminaires,
Teknoware´s central battery system is a user-based PC software, with
there is a wireless monitoring
product portfolio include several user levels, for locations,
system, Aalto Control. Aalto Control
where there might be several people
is a wireless system containing, user-
►► 24 V central battery systems using the system.
based functionalities, reporting,
system logs and much more.

8
SYSTEM DESIGN: EMERGENCY AND EXIT LIGHTS

EXAMPLE OF SYSTEM DESIGN

Stage 1 Stage 3

Position the emergency and exit Other areas, which require


lights at points of emphasis on emergency lighting, but are not on
escape routes the escape route area

►► at each exit door ►► lift cars

►► to illuminate exit and safety ►► toilets and changing rooms etc.


signs (larger than 8 m2)

►► near call points ►► escalators and moving


walkways
►► near each staircase
►► motor and plant room

►► change of direction
►► pedestrian routes within
covered car parks
►► near fire fighting equipment

►► change of floor level Stage 4

Check the minimum illuminance


►► near intersection of escape levels on the escape routes.
routes

►► outside final exits Stage 5

Anti-panic open areas apply to


►► near first aid points any areas over 60 m2 floor area, or
that have an escape route passing
through them.
Stage 2

Check that the maximum viewing


distances are not exceeded. Even Stage 6
if the normal lighting is dimmed, High risk lighting requirements
e.g. in cinemas, the exit lights must
still be permanently illuminated
(maintained lighting).

9
MARKINGS

= CE marking

= SGS Finland marking (a 3rd party certification)

= International standard IEC 60364-5-56, 560.9.15: Emergency lighting luminaires and


associated circuit equipment shall be identified by a red label of at least 30 mm diameter.
A=central battery unit, B= circuit, C=luminaire

= Luminaire classification label. According to the requirements of the standard


EN 60598-2-22, the emergency luminaires shall be classified and marked according to
their function and construction. Therefore, a sticker with four squares must be attached on
the luminaire, in a visible place. The first square is already filled in at the factory, the rest of
the squares are to be filled in after the installation.

a) First segment containing one position: TYPE (marked already in the factory)
X self-contained luminaire
Z centrally supplied luminaire

b) Second segment containing one position: MODE OF OPERATION:


0 non-maintained emergency luminaire
1 maintained emergency luminaire
2 combined non-maintained luminaire
3 combined maintained luminaire
4 compound non-maintained luminaire
5 compound maintained luminaire
6 satellite emergency luminaire

c) Third segment containing four positions: FACILITIES.


A including test device
B including remote rest mode
C including inhibiting mode
D high-risk task-area luminaire
E with non-replacable lamp(s) and/or battery
F automatic test gear complying with IEC 61347-2-7 denoted EL-T
G internally illuminated safety sign.

d) Fourth segment containing three positions: FOR SELF-CONTAINED LUMINAIRES to


indicate the minimum DURATION of the emergency mode, expressed in minutes:
*10 10 min duration
*60 1 h duration
120 2 h duration
180 3 h duration

10
TERMINOLOGY AND STANDARDS

Emergency lighting is one of the power fails. (=emergency light). emergency lights to be marked
most important safety systems in with information relevant to type,
a building. Emergency lighting A maintained luminaire operates performance and manufacture.
makes it possible to safely stop at all times, both when the mains
The CE mark is a mandatory
working and to evacuate the fails, and when it is present light.
requirement for all luminaires
building, by following the exit (=exit light).
for sale in Europe. This marking
lights, in case of an emergency.
is placed on the product by the
Emergency lighting is a standalone High risk task areas of high
manufacturer and proves that the
backup system, which does not physical risk, or the control rooms
product conforms to all relevant
rely on the functionality of the of dangerous plant and production
safety standards.
general electrical distribution lines, need emergency lighting
system in the building. It must to enable them to be shut down Response time is a time that
always be operational and ready safely. elapses between the failure of
for use.
the normal power supply, and the
EN 1838 is an European Standard auxiliary power supply energizing
Emergency exit route is a that specifies the luminous the equipment.
continuous and unobstructed requirements for emergency
path of exit, from any point escape lighting and standby
of the building, in the case of lighting systems, installed in
an emergency. This route isn’t premises or locations, where such
necessarily used everyday, but systems are required.
must be lit up by the appropriate
warning and directional signs. EN 50171 is the standard relevant
to central power supply units and
Open (anti-panic) area lighting systems, controlling their design,
is necessary to reduce confusion construction and performance
and panic, whilst ensuring visibility requirements.
of the nearest exit route.
EN 50172 standard includes the
requirements for illumination lux
Emergency light is a luminaire
levels for additional areas, and
which may or may not be provided
the requirements for service and
with its own electrical source for
maintenance.
safety services and which is used
for safety or emergency lighting. EN 60598-2-22 is the product
standard for emergency lights.
Exit Light is a luminaire,
The standard ensures that the
that indicates and assists the
products are safe to use, and have
identification of escape routes.
been designed and manufactured
for correct performance
A non-maintained luminaire under emergency conditions.
operates only, when the mains EN 60598 -2-22 also requires all

11
MANDATORY “POINTS OF EMPHASIS”

Any point on an escape route, or leading to it, must have an exit sign, so that the direction of travel is not in
doubt. Exit signs should clearly identify the full extent of the escape route, including any changes of direction.
Emergency Lighting must be provided along escape routes, and in the open areas leading to them, to enable
people to move quickly and safely to an exit.

Specific locations where emergency lighting must be provided are:

Exit door Stairs Change of direction

Change of floor level Open areas At each intersection of corridors

Highlighting fire fighting and first aid High Risk task areas Outside and near each final exit
equipment

12
DURATION TIMES AND RESPONSE TIMES

In emergency conditions, light


must be provided for a certain
minimum amount of time, to
effectively achieve evacuation,
and/or complete certain essential
tasks. “Duration” is the minimum
period of time that the emergency
luminaire remains lit, after a
mains failure. Various premises
require different durations, from
1 to up to 8 hours, depending
on the requirements of the local
authorities.

Response times

The requirement for escape routes


and open areas is, that 50% of
the illuminance must be available
within 5 seconds, and the full
value within 60 seconds of supply
failure.

The requirement for high risk task


areas is more critical, because
a distribution may endager life,
while someone is working on a
hazardous machine or process.
Full emergency illuminance should
therefore be provided within 0.5
seconds through to the end of the
required duration.

13
VIEWING DISTANCE

For all formats of exit lights and The viewing distance is the pictogram in mm. For example a
signs, the maximum viewing distance, from which the sign can 100 mm high pictogram gives a
distances and luminance be clearly seen and understood. viewing distance of 20 m.
conditions are given in EN 1838:
2013. The minimum height of the
internally illuminated pictogram is
Exit lights must be placed at any
calculated with the formula:
change in direction, to indicate the
d = 200 x h, where d = viewing
route to the final exit door.
distance, h = height of the

h 200
xh

14
THE PERFORMANCE REQUIREMENTS FOR THE EXIT LIGHTS

Exit lights need to fulfil the Within the same colour, the emergency lighting system to
performance requirements contrast must be less than 1:10. be according to the relevant
of the European standard EN emergency lighting standards.
1838. This standard determines These will guarantee the minimum
observability for the pictogram. Since 2011, the pictogram format
the requirements both for the
This is the most important feature adopted both by BSI and EN
luminance and the contrasts.
of an exit light, and it cannot be standards, is ISO 7010.

The minimum luminance in the neglected e.g. due to the quest for
green area is 2 cd/m2. a lower energy consumption, or
the product costs.
The contrast between the white 1996 2011
and the green area must be In the end, the owner of the
between 1:5 and 1:15. building is responsible for the

min luminance = 2cd/m2

contrast of the colours must be


between 5:1 and 15:1

ratio of luminance shall be less than


10:1 for either colour

15
ILLUMINATION

Emergency lighting must be


provided along escape routes, and
in the open areas leading to them,
to enable people to move quickly
and safely to an exit.

50 % of the illuminance must be


available within 5 seconds and
the full value within 60 seconds of
supply failure in escape routes and
open area.

Escape route
illumination Escape Route Illumination

The illuminance required on the


floor of a corridor-like escape 1 lux
route, up to 2 m wide, should be a 2m 1m

minimun of 1 lux along the centre


line, and a minimum of 0.5 lux in 0.5 lux
the 1 m wide central band.
=Emergency Light

Open area illumination Open Area Illumination

Any area larger than 60 m2, where


people could find themselves
in a emergency, is an open area
requiring emergency lighting.

In open areas, illumination of 0,5 0.5 lux minimum in core area

lux minimum should be provided.


=Emergency Light

High risk task area


illumination
For high risk task areas the
illuminance should generally
be 10% of the normal mains
illuminance or at least 15 Lux. This
output must be fully achieved
within 0.5 seconds.

16
GLARE ZONE AND CONTRAST RATIO

Glare zone of emergency lightings


is regarded as angles above 60°
from the vertical line. Typically, the Glare zone
emergency lights are mounted as
high as possible. As the mounting
height increases, so does the glare 60°
zone limit.

Contrast ratio

Both for escape routes and open


areas, the contrast ratio should
not exceed 40:1, meaning that,
if the minimum value is 1 lux, the
maximum cannot exceed 40 lux.

Teknoware provides Eulumdat


files for all its emergency lightings,
for designing calculating and
visualizing their photometric data,
eg. in DIAlux lighting design 1 lux 40 lux 1 lux 40 lux 1 lux 40 lux 1 lux
software.

17
TESTING AND MAINTENANCE

Central battery unit and be carried out according to the Automatic testing systems
emergency exit lights shall be standard EN 50172.
Teknoware provides automatic
maintained regularly, to secure
testing for both centrally supplied
trouble-free operation. ►► the indicators of the emergency
lighting central battery system and self-contained emergency
must be visually inspected on a lighting systems.
Teknoware recommends, that the
daily basis
central battery system should be
Teknoware’s central monitoring
tested and maintained according ►► the emergency mode of each and self-testing systems take care
to the standard EN 50172, as luminaire is tested monthly,
of the required light source and
follows: by switching the luminaire to
battery feed, either manually, or duration tests automatically.
automatically
Testing
►► once per year, the full duration
The operation of the luminaire test of 1 h, or a determined
shall be verified according to the longer time, is to be made, by
requirements of the authorities. switching the system to battery
feed, for the entire duration
time
The battery mode duration of the
self-contained types can be tested
►► all the tests and results shall
by be recorded in the logbook of
the emergency lighting system
►► switching off the mains supply
and when asked, it shall be
voltage
presented to the authorities for
inspection
►► using self-testing feature such
as Lumi Test, or
►► in addition, a daily visual
inspection of the maintained
►► using a central monitoring exit lights is recommended.
software, such as Aalto Control,
which also record the test
results.

Periodical checks and


maintenance

The condition of the emergency


lighting system shall be ensured by
regular maintenance, according to
the regulations of local authorities.

The maintenance of the


emergency lighting system is to

18
AUTOMATIC TESTING AND MONITORING

Teknoware Tapsa Control - Teknoware Aalto Control - Teknoware Lumi Test -


central monitoring for the wireless central monitoring for automatic self-testing for the
addressable, centrally supplied the self-contained emergency self-contained emergency and
emergency and exit lights and exit lights exit lights

Tapsa Control central battery unit Aalto Control provides a wireless Lumi Test self-diagnosis, which
includes the following monitoring, central monitoring for self- is available for self-contained
testing and reporting functions: contained emergency and exit luminaires, automatically tracks
lights. There is no need to connect and tests the reliable operation
►► testing the luminaires
the luminaires with data cables. of the luminaires. LED indicators
either through addressable
monitoring, or by measuring The only requirement is, that each (one green and one red) display
the circuit current individual luminaire has a local the status of the luminaires. Red
power supply, like any standard LED indicates fault. The luminaire´s
►► monitoring the condition of the self-contained luminaires. All the functionality and light source are
batteries benefits of the self-contained tested daily. Full emergency mode
luminairess are preserved, duration is tested every 6 months.
►► testing the capacity of the and each luminaire functions
batteries
independently. All Aalto Control emergency and
exit lights also include Lumi Test.
►► indicating the address of the
faulty circuit and luminaire Installation is simple, and
the luminaires can be easily
►► a short operation test time can positioned, even during
be set to take place after each renovations. Each luminaire is a
1…7 days node, receiving and transmitting
the signal to other luminaires. The
►► battery test every 6 months signal penetrates normal walls,
doors and floors easily, and climbs
stairways. The network is used
only for collecting information
and does not affect the operation
of the luminaires. For this reason,
Aalto Control is as robust and
resistant to failures as any other
self-contained system.

Aalto Control PC system can


include up to 5000 self-contained
emergency and exit lights.

19