Feed water Auto Logic for Start up

Startup to be done with MDBFP


Seperator overflow control valve opening to be maintained 70%
FRS 30% control valve will follow seperator overflow control valve opening ( it will try to maintain overflow cv op
70%)
MDBFP will maintain 2.0Mpa DP across FRS 30% conrtol valve (Press.diff. before FRS and eco. Inlet)
FRS 30% control valve locking to be done such that total feed water flow should not go less then 150 TPH

HP LP Bypass charging
For HP bypass charging, HP bypass force close logic on feed water pressure low to be changed from 6.0 Mpa to 3
Mpa

1st Mill Start up


For first mill start up coal fire permit on feed water flow to be changed to FW Flow> 450 TPH

FRS 30 % to 100 % line change over


This line changeover should be done in auto with one command at unit load >150 MW
During this changeover current feed water flow will become setpoint for feed water flow demand during line
changeover
FRS 30%CV will open slowly and MDBFP will maintain total feedwater flow.
After opening FRS 30% CV, opening command to 100% Line MOV. MDBFP will maintain total feedwater flow.

Wet to dry Mode changeover


Heaters charging should be completed
During wet to dry mode changeover feed water flow should to constant at 800 TPH
Slowly increase the boiler loading (Mill loading to 240 TPH)
Overflow valve opening will reduce to zero.
OHDR will raise and it is to be maintained 5-10 degree C.

Wet to dry mode Change Condition


Feed water temp.> 180 Deg. C
OHDR > 5 Deg. C
Seperator Level Zero
Seperator overflow valve position Zero
MS Flow > 750 TPH