You are on page 1of 10

IET Generation, Transmission & Distribution

Research Article

ISSN 1751-8687
Kalman filter based incipient fault detection Received on 7th June 2014
Revised on 28th April 2015
method for underground cables Accepted on 8th June 2015
doi: 10.1049/iet-gtd.2015.0040
www.ietdl.org

Teymoor Ghanbari ✉
School of Advanced Technologies, Shiraz University, Shiraz, Iran
✉ E-mail: Ghanbarih@shirazu.ac.ir

Abstract: An incipient and self-clearing arcing fault can be utilised as a precursor of an imminent permanent failure for
monitoring of underground cables. Due to very short duration of the incipient faults, generally they cannot be detected
by conventional protection relays. This study presents a new method for detection of incipient cable failures by using
measured current and voltage at one end of the cable. The incipient faults are detected using an innovation signal
calculated from the measured fault current via a Kalman filter. Upon change detection by the innovation signal, the
change is checked for discriminating possible incipient fault from other similar conditions. The proposed method is
evaluated using several simulations and field data collected from a real network. The results confirm that the method
can achieve high accuracy and speed for detection of cables incipient faults.

1 Introduction arc voltage and/or current of the incipient faults such as positive
and negative sequences as well as current peaks are analysed in
Underground cables may experience incipient, self-clearing arcing the time domain based techniques [7, 8]. It should be noted that
faults before occurrence of imminent failure. The incipient faults due to sub-cycle duration of the incipient faults, some of these
typically occur near peak of voltage waveform and quench at the techniques have essential restrictions. Having a suitable arc model
first zero crossing of current waveform. These events may last a in such study is very important. Different arc models have been
sub-cycle or multi-cycle [1]. Root causes of the incipient cable proposed in literature, which can be used for detection and
faults are electrical overstress in conjunction because of location of cable incipient fault [18–20]. In [19] an incipient fault
mechanical defects and deterioration of the insulation due to aging detection and location algorithm has been proposed taking into
process, unsuitable environmental condition, and mechanical account the fault arc voltage. In [20] the model of self-clearing
damage to the cable [2]. faults is considered as simple as possible so that the proposed
The main cause of the incipient fault is penetration of water into incipient fault location algorithm can be applied to complex
the cable splices. In this condition, an insulation breakdown occurs circuits of centrally monitored substations. In [21] fault diagnosis,
by an arc. The arc leads to rapid water evaporation and hence the location, and characterisation in a typical power cable are
high vapour pressure inside the splice extinguishes the arc quickly investigated. The fault resistance is characterised and location of
[1, 2]. Typical duration of this process is about one-quarter cycle the defect determined using a combination of infra-red imaging
to multi-cycle [1]. The characteristics of the incipient faults and time-difference-of-arrival location.
depend on the location of the fault on the cable and incipient Generally incipient faults may occur as either sub-cycle or
angle of the fault on the voltage waveform [2]. Conventional multi-cycle faults. The sub-cycle type always occurs near the peak
over-current protections cannot detect incipient faults, due to the of voltage, at which the arc ignites and lasts until the arc current
short duration and low magnitude increment of these faults [2]. crosses zero. The multi-cycle type also occurs near the peak of
Generally, conversion of an incipient fault to a permanent failure voltage, at which the arc ignites but lasts 1–4 cycles. This fault
is a gradual phenomenon and may last several months. During type self-clears when the arc is quenched [1].
conversion of an incipient fault to a permanent failure, frequency The incipient faults commonly occur in cable splices following
of the incipient fault occurrence increases. An accurate and fast penetration of moisture into the splice. The moisture leads to the
algorithm is essential for developing the conventional protection to insulation break down and the generated arc evaporates the
detect the incipient faults and preventing the relevant catastrophic moisture. This phenomenon creates high pressure vapours which
failures [3, 4]. extinguishes the arc and self-clears the fault. Some of the unique
Several approaches have been presented in literature for detection characteristics of these faults are as follows:
and location of faults for underground cables [4–20]. However, the
techniques in which voltage and/or current are employed via
(i) Generally the incipient faults starts near the positive and
one-terminal monitoring are more attractive [4, 5]. In [13] a good
negative peaks of the voltage waveform and finishes when the arc
survey is presented regarding fault location techniques of electrical
cools off at zero crossing of the arc current
distribution networks. Some methods are based on the main
(ii) The arc voltage waveform resemble a distorted square wave
characteristics of voltage and current waveforms during incipient
with a blip occurred in each half cycle of the arc voltage. In
fault condition [14, 15]. The methods are based on voltage
addition, arc current and voltage are in phase
and current processing in the frequency domain, time domain, and
(iii) Fault duration may be less than one cycle (even 1/4 cycle) to
frequency-time domain. Some of well-known fault detection and
four cycles
location approaches are the methods based on travelling wave [6],
(iv) Frequency occurrence of the incipient faults increase over time
impedance [7, 8], and intelligent system [9, 16]. In the frequency
and it rapidly increases before converting to permanent fault
domain based approaches by using some tools such as wavelet and
(v) Due to low increment of current amplitude and duration of the
S-transform, the harmonic components of the arc current and/or
incipient fault, they cannot be detected by conventional over-current
voltage are utilised [10, 17]. The time varying characteristics of
relays

IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 14, pp. 1988–1997
1988 & The Institution of Engineering and Technology 2015
However, the other transients in power systems such as: lightening
stroke, switching action, load change, etc., may have similar
characteristics. Therefore, finding an accurate and reliable
technique for development of the conventional protections to
detect incipient cable faults are important.
In this paper, a new proficient incipient fault detection technique is
proposed for underground cables monitoring. In the proposed
method, the incipient faults are initially detected by using a
residual signal. The fundamental component of the current is
estimated using a Kalman filter (KF) with slow dynamic. The
wavelet transform as a suitable alternative for KF has some
restrictions, such as the impact of mother wavelet selection,
adequate detection thresholds on the results, the need for different
sampling frequencies for different frequency sub-bands, extreme
sensitivity of noise superimposed on the signal, and expensive
computational burden. Upon fault occurrence, the estimated signal
cannot track the fault current increment during the initial moments
after the incipient fault occurrence. Therefore, a residual signal
which is the difference between the measured current and its
estimated value is generated. Following the current estimation, arc
voltage is also estimated using another KF with fast dynamic. A
square wave is fitted to the estimated voltage using minimum least
square (MLS) method. Whenever a change is detected by the
residual signal, correlation of the estimated voltage and the fitted
one is calculated to confirm or cancel the initial decision.
Performance of the proposed method is evaluated by plenty of
simulations and using field data collected from a real network. The
results confirm the capabilities of the method.

2 Proposed incipient faults detection algorithm

In the proposed approach, incipient fault is detected using an


innovation signal generated by the estimated and measured fault
currents. A KF with slow dynamic is utilised to estimate
fundamental component of incipient fault current. Since the
estimated signal cannot swiftly track the measured current
increment during the initial moments after the fault occurrence, a
difference occurs between the measured and estimated currents’ Fig. 1 Proposed algorithm for incipient fault detection
values. This difference is used as current residual signal for
change detection and initial decision in the proposed method.
Parallel with the current estimation, fundamental component of where, cn denotes an additive zero-mean random term, considered to
arc voltage is also estimated using another KF with relatively fast represent the possible model errors, including slight amplitude,
dynamic. A square wave is fitted on the estimated arc voltage phase, or frequency deviations.
using MLS method. Furthermore, voltage residual signal is Current signal noise due to the measurement and other factors can
calculated by subtracting the estimated voltage signal and the fitted be superposed on the pure current signal, therefore:
square wave. After the initial decision by the current residual
signal, in the last step, variance of the voltage residual signal
yn = Sn + vn (3)
during each half-cycle of power frequency is calculated to confirm
or reject the initial decision. In Fig. 1 a schematic of the proposed
algorithm is presented. In this flowchart, Vn and In are the where, Sn is the fundamental component of the current signal and vn
monitored voltage and current in the beginning of the feeder, n is is a zero-mean random term, representing the noises.
time index, Vsn, and Isn are the estimated voltage and current, To construct a KF to estimate the fundamental component of the
Vfitted is the fitted square wave, Rn and Cn are the residual and current signal, the dynamic equation in (2) needs to be converted into
correlation signals as well as T1n and T2n are the selected a state space form. Therefore, (2) and (3) for the fundamental
thresholds for Rn and Cn, respectively. component can be rewritten as follows:
In the estimation process, the fundamental component of the
current is estimated in real time by a KF with slow dynamic. A Xn+1 = MXn + bcn
mathematical model of the current in state space variable form is (4)
used as KF model. A discrete sinusoid current signal with an yn = hT Xn + vn
arbitrary amplitude and phase is considered for the model. Let us
consider the current signal as: where,

Sn = a cos (v0 n + w) (1)  


2 cos (v0 ) −1
Xn =[S
˙ n Sn−1 ]−1 , M=
˙ ,
1 0
where, ω0 = 2πf0/fs, in which f0 and fs are the current signal and
sampling frequencies, respectively, and n is the time index. b=[1
˙ 0]T , and h=[1
˙ 0]T
Using basic trigonometric identities, Sn can be recursively
computed as follows:
The dynamical current is now completed. The fundamental
component of the current signal could be estimated using classical
Sn+1 + Sn−1 = 2 cos (v0 )Sn + cn (2) iterative KF equations presented in the Appendix. The residual

IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 14, pp. 1988–1997
& The Institution of Engineering and Technology 2015 1989
signal is calculated as: As a result, k0 and k1 are calculated by the following equation:
 N    N 
RCn = Sn − yn (5) N nDt k0 Varc,s (n)
n=1
N N n=1
= N (8)
n=1 nDt n=1 (nDt)2 k1
n=1 (nDt)Varc,s (n)
The same formulation is required for calculation of the voltage
residual signal. Consequently, depending on incipient angle of the
fault occurrence, the residual signal has positive or negative Average of the fitted signal without DC component for each
variation. Consider stationary process models (qn = q) and half-cycle drives the fitted square wave on the arc voltage as follow:
stationary observations (rn = r) in steady state condition of the filter
(see Appendix). Noise covariance matrixes q and r act as tunable 1 m
parameters to balance the dynamic response of the filter. Ratio q/r x(n) = (g(n) − k0 ) (9)
m n=1
rather than their actual values determines the dynamic response. It
can tune a balance between sensitivity to noise and dynamic
response of the filter. The second residual signal, which is calculated by subtracting the
In the MLS fitting, suppose that the original signal has N samples. estimated voltage signal and the fitted square wave, is used for
Amplitude and phase of the fitted square wave to the arc voltage is calculation of the second criterion. The second criterion is defined
such that estimated the most resemblance to the signal is achieved. as variance of square of the voltage residual signal during each
The squared error is defined as follows: half-cycle of power frequency and calculated by:


N Cm = Var[(Varc,s − x)2 ] (10)
SS = [Varc,s (n) − g(n)]2 (6)
n=1
in which m denotes number of the half-cycle.
Different simulations show that for the incipient fault conditions,
in which, Varc,s(n) is the voltage signal and g(n) is the fitted one
criterion Cm increases considerably more than the other conditions
such as load variation, capacitor switching, etc. It should be noted
g(n) = k0 + k1 (nDt), v = 2 p f0 (7) that, the estimated arc voltage has more resemblance with a square
wave than the measured arc voltage. Therefore, it is used to
where f0 is the power system frequency and Δt is the sampling time. compare with the square wave in this research. Based on this fact
The ki coefficients are determined in such a way that the error is that the arc voltage waveform resembles a distorted square wave,
minimised. similarity between the estimated arc voltage and the fitted square

Fig. 2
a The network, in which the field data have been measured
b Location of the voltage and current sensors

IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 14, pp. 1988–1997
1990 & The Institution of Engineering and Technology 2015
Fig. 3 Typical sub-cycle incipient fault
a Upper: measured current and its estimation lower: the residual signal
b Measured voltage and its estimation, fitted square wave, and the variance signal (simulation)

wave essentially increases during the incipient faults. This similarity The recorded voltage and currents are logged using a data logger,
is used as the second criterion for confirming or cancelling the initial which has sampling time 128 µs and it can be set to log voltages and
decisions. currents of the system in abnormal condition. In this research, the
field data are recorded by the data logger, and then the gathered
data are processed in MATLAB software using a program which
is based on the proposed algorithm.
3 Considerations relevant to implementation of However, the proposed algorithm of the monitoring system for
the method in the under study system detection of incipient fault can also be implemented on a DSP or
even dsPIC (16-bit or 32-bit) processor as an incipient fault
In Fig. 2a single line diagram of a part of the network, in which the detector relay. Since the intervals relevant to process of the
field data have been measured are presented. In this figure, measured voltage and current are about one cycle of power
information of the network and some feeders are presented. The frequency, conventional voltage and current sensors can be utilised
measured data are recorded from F2, which has 6 km underground in this application. Therefore, the already installed CT and PT in
cable (type XLPE). the substation’s feeder can also be used for this relay.
In the under study system, several reports have been recorded by Selection of the voltage and current sensors and their locations
the operators regarding anomaly operation of some power electronic have essential role in the monitoring system. Some of the
devices such as uninterruptable power supply systems. Following important factors for selection of the sensors are as follows:
these complaints, it is cleared that they are relevant to strike out of
their protection system. A power quality monitoring instrument
was installed in the system. The logged current and voltage (i) Suitable frequency response
waveforms clear that the origin is similar to fault occurrence, but it (ii) Cost-effectiveness
has not lead to trip the breakers. The acquired information raised (iii) Size
suspicions about the possibility of an incipient fault in an (iv) Noise and interference immunity
underground cable feeder (F2), which has several splices. By
inspecting the splices, an anomaly sound is heard near one of
them and more investigation appeared some signs of insulation One can select more suitable sensors based on the above
burning. mentioned factors.
In the experiment, the voltage and current sensors are installed at Of course, more details regarding implementation of the proposed
the substation in the beginning of the feeder. In Fig. 2b location of protection in real applications need more investigations, which are
the voltage and current sensors are illustrated. out of concern of this research.

IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 14, pp. 1988–1997
& The Institution of Engineering and Technology 2015 1991
Fig. 4 Typical multi-cycle incipient fault
a Upper: measured current and its estimation lower: the residual signal
b Measured voltage and its estimation, fitted square wave, and the variance signal (simulation)

Fig. 5 Typical load change


a Upper: measured current and its estimation lower: the residual signal
b Measured voltage and its estimation, fitted square wave, and the variance signal (simulation)

IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 14, pp. 1988–1997
1992 & The Institution of Engineering and Technology 2015
Fig. 6 Typical capacitor bank switching
a Upper: measured current and its estimation lower: the residual signal
b Measured voltage and its estimation, fitted square wave, and the variance signal (simulation)

4 Results and discussion signal, which leads to the second peak for the current residual
signal. In Fig. 3b the monitored voltage, estimated voltage, fitted
The network shown in Fig. 2 is simulated in electro-magnetic signal, and variance signal for such case are presented. It can be
transient program (EMTP) including combination of an overhead observed that Cm dramatically increases in the fault condition.
line and an underground cable. The cable is considered as 9 Thus, by selection of a suitable threshold one can confirm the
pi-sections with detailed model including capacitors. Different previews decision half-cycle of power frequency after the initial
scenarios, which are considered to evaluate the proposed decision. It should be noted that, inherent delay of the Cm criterion
algorithm, are as follows: is about half-cycle of power frequency.
Fig. 4 shows the results for a typical multi-cycle incipient fault. In
this case, fault occurs at 0.1 s and last for 25 ms, as well. The current
(i) Different fault distances from the monitoring location in the residual signal in Fig. 4a straightforwardly determines instances of
cable incipient fault occurrence and clearance. Moreover, using the Cm,
(ii) Different fault resistances one can confirm the initial decision, too. As shown in Figs. 3 and
(iii) Different fault types including balanced, unbalanced, grounded, 4, the current residual signals vary about 4 units. Moreover, the
and ungrounded variance signal increases in three steps in case of the
(iv) Different fault inception angles multi-incipient fault, because the resemblance of each half-cycle
(v) Different unbalanced/balanced load variations more than the previews one after the fault occurrence. In Fig. 5
(vi) Different loads and capacitors switching the results in case of a load change are presented. Using the
current residual signal, one can detect a change in condition of the
system. Due to low amplitude of the current residual signal
4.1 Simulation results variation, the initial decision is that the change is not an incipient
fault and may refer to a normal condition of the system. From
The real network in which the field data have been logged is relatively low variation of the Cm, one can confirm the initial
simulated in EMTP with the same specifications. In the following decision.
some typical simulations from the abovementioned scenarios are One of the other similar conditions is capacitor bank switching,
presented. In Fig. 3 a typical sub-cycle incipient fault is which can also be discriminated by the proposed method. Fig. 6
considered. As shown in this figure, fault occurs at 0.1 s and last shows the results in case of a capacitor bank switching. As shown
for 4 ms. By use of the current residual signal shown in Fig. 3a in this figure, peak of the current residual signal is lower than the
and a suitable threshold, fault can be detected <3 ms. Meanwhile, residuals relevant to the incipient faults. If T1 is set at the possible
the instance of fault clearance can also be determined by this minimum value (for having more sensitivity), this condition is

IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 14, pp. 1988–1997
& The Institution of Engineering and Technology 2015 1993
Fig. 7 Typical sub-cycle incipient fault
a Upper: measured current and its estimation lower: the residual signal
b Measured voltage and its estimation, fitted square wave, and the variance signal (recorded field data)

Fig. 8 Typical sub-cycle incipient fault


a Upper: measured current and its estimation lower: the residual signal
b Measured voltage and its estimation, fitted square wave, and the variance signal (recorded field data)

IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 14, pp. 1988–1997
1994 & The Institution of Engineering and Technology 2015
Fig. 9 Typical load change
a Upper: measured current and its estimation lower: the residual signal
b Measured voltage and its estimation, fitted square wave, and the variance signal (recorded field data)

Fig. 10 Typical capacitor bank switching


a Upper: measured current and its estimation lower: the residual signal
b Measured voltage and its estimation, fitted square wave, and the variance signal (recorded field data)

IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 14, pp. 1988–1997
& The Institution of Engineering and Technology 2015 1995
detected as an incipient fault. However, considering Fig. 6b, the 5 Conclusion
initial decision is straightforwardly rejected because variation of
Cm is negligible. Due to importance of utilising high and medium voltage cables in the
It is observed that, the variance signals vary slightly in case of load modern electrical networks, underground cable monitoring is essential.
change or capacitor switching, while it increases dramatically in case In this paper, a new incipient fault detection method based on KF for
of the incipient faults. Hence, the second criterion can reliably underground cables is proposed. In the method, first the incipient fault
confirm or reject the initial decision about half-cycle of power is detected by using current residual signal calculated by the measured
frequency after fault occurrence. current and its estimated signal. Then, the initial decision is confirmed
or rejected by calculation of the variance signal. Performance of the
4.2 Experimental results proposed technique is evaluated using different simulations and
experiments. The simulation and experimental results show that
In the following, the algorithm is evaluated with some recorded field the proposed method can reliably detect incipient faults and
data from a real network. Figs. 7 and 8 show two typical sub-cycle discriminate these faults from other similar transients. The main
incipient faults. The incipient faults occur around positive and outlets of the results are (a) capability of the method for detection
negative peaks in Figs. 7 and 8, respectively. As shown in Fig. 7, of incipient fault in <5 ms (b) confirm or reject the initial detection
by using the residual signals, one can detect the incipient fault in in less than half-cycle of power frequency (c) high reliability of
<3 ms. Furthermore, the initial detection can be confirmed about the method due to its detection is rely on two criteria based on
half-cycle of power frequency after the fault occurrence. Fig. 8 current and voltage signals (d) the experimental results agree well
also confirms capabilities of the proposed method in case of with the corresponding simulation results, which not only confirms
another incipient fault occurring around negative peak. It can be the simulations, but verifies the high performance of the method in
observed that when the incipient fault occurs around positive and practice (e) reliability of the method from the sensitivity and
negative peaks, the current residual signal will be increased to accuracy points of view are also concluded considering the
positive and negative values, respectively. However, Cm increases simulation results of different similar scenarios.
in both the cases.
Fig. 9 shows the results for a typical load change. Based on
remarkable change in the current residual signal, this case is 6 References
detected as incipient fault in the initial decision. However,
considering variation of the Cm, the initial decision is rejected and 1 Sidhu, T.S., Xu, Z.: ‘Detection of incipient faults in distribution underground
cables’, IEEE Trans. Power Deliv., 2010, 25, (3), pp. 1363–1371
this condition is recognised as a normal condition of the system. 2 Kojovic, L., Williams, C.W.J.: ‘Sub-cycle detection of incipient cable splice faults
In Fig. 10, recorded data from a typical capacitor switching is to prevent cable damage’. Proc. IEEE Power Engineering Society Summer
utilised to evaluate performance of the proposed method. As Meeting, 2000, pp. 1175–1180
shown in this figure, one can detect the change by the current 3 Kim, C., Bialek, T.: ‘Sub-cycle ground fault location-formulation and preliminary
results’. Proc. IEEE/PES Power System Conf. Expo. (PSCE), March 2011, pp. 1–8
residual signal, but possibility of incipient fault occurrence can be 4 Jia, K., Thomas, D., Sumner, M.: ‘A new single-ended fault-location scheme for
rejected by considering variation of the Cm in this case. utilization in an integrated power system’, IEEE Trans. Power Deliv., 2013, 28,
The method is evaluated by different other simulations and (1), pp. 38–46
experiments in the abovementioned scenarios. The results confirm 5 Xu, Z., Sidhu, T.: ‘Fault location method based on single-end measurements for
underground cables’, IEEE Trans. Power Deliv., 2011, 26, (4), pp. 2845–2854
the performance of the proposed method. It is revealed that the 6 Gilany, M., Ibrahim, D., Tag Eldin, E.S.: ‘Traveling-wave-based fault-location
method can detect incipient faults <5 ms and confidently confirm scheme for multiend-aged underground cable system’, IEEE Trans. Power
the decision in less than half-cycle of power frequency. Deliv., 2007, 22, (1), pp. 82–89
7 Filomena, A.D., Resener, M., Salim, R.H., Bretas, A.S.: ‘Fault location for
underground distribution feeders: an extended impedance based formulation with
4.3 Comparison with some other similar methods capacitive current compensation’, Elect. Power Energy Syst., 2009, 31, pp. 489–496
8 Salim, R., Salim, K., Bretas, A.: ‘Further improvements on impedance-based fault
location for power distribution systems’, IET Gener., Transm., Distrib., 2011, 5,
Many of the reports for incipient fault phenomenon of underground (4), pp. 467–478
cables have been dedicated to location rather than just detection of 9 Sadeh, J., Afradi, H.: ‘A new and accurate fault location algorithm for combined
incipient faults. However, most probable locations of incipient transmission lines using adaptive network-based fuzzy inference system’, Electr.
faults such as splices are distinct. Therefore, this paper deals with Power Syst. Res., 2009, 79, pp. 1538–1545
10 Butler-Purry, K.L., Cardoso, J.: ‘Characterization of underground cable incipient
incipient fault detection topic and the proposed algorithm is only behavior using time-frequency multi-resolution analysis and artificial neural
compared with some reported incipient fault detection methods. networks’. IEEE Power and Energy Society General Meeting – Conversion and
The accuracy of the proposed incipient fault detection method is Delivery of Electrical Energy in the 21st Century, 2008, pp. 186–201
compared with other voltage and current based methods by 11 Borghetti, A., Bosetti, M., Silvestro, M.D., Nucci, C.A., Paolone, M.:
‘Continuous-wavelet transform for fault location in distribution power networks:
evaluating the methods using gathered voltages and currents from definition of mother wavelets inferred from fault originated transients’, IEEE
150 different simulated cases of the mentioned scenarios and 16 Trans. Power Syst., 2008, 23, (2), pp. 380–388
recorded incipient faults in practice. To have a fair judgment, the 12 Su, Q., Li, H.J., Tan, K.C.: ‘Hotspot location and mitigation for underground
methods which are only based on measured current are not power cables’, IET Gener. Transm. Distrib., 2005, 152, (6), pp. 934–938
13 Diaz, H., López, M.: ‘Fault location techniques for electrical distribution networks:
considered. The first method is a simple algorithm based on the a literature survey’. Proc. Fifth IASTED Int. Conf., 15–17 June 2005, pp. 311–318
five main characteristics of cable incipient fault listed in the 14 Stringer, N.T., Kojovic, L.A.: ‘Prevention of underground cable splice failures’,
introduction [14]. The second method is based on artificial neural IEEE Trans. Ind. Appl., 2001, 37, (1), pp. 230–239
network [16]. The third method is based on S-transform and 15 Kasztenny, B., Voloh, I., Jones, C.G.: ‘Detection of incipient faults in underground
medium voltage cables’. Annual Conf. for Protective Relay Engineers, 2008,
support vector regression [17]. The detection accuracies of pp. 349–366
the methods are tabulated in Table 1. It can be observed that the 16 Kumar, A.: ‘A neural network approach to the detection of incipient faults on
proposed algorithm has the maximum accuracy compared with the power distribution feeders’, Middle-East J. Sci. Res., 2014, 20, (7), pp. 799–803
rest of the methods. 17 Faisal, M.F., Mohamed, A., Shareef, H.: ‘Prediction of incipient faults in
underground power cables utilizing S-transform and support vector regression’,
Int. J. Electr. Eng. Inf., 2012, 4, (2), pp. 186–201
18 Dong, X., Yanling, Y., Zhongqiang, G., et al.: ‘Analysis of cable failure modes and
Table 1 Compression of the incipient fault detection methods cable joint failure detection via sheath circulating current’. Proc. Electrical
Insulation Conf. (EIC), 2014, pp. 294–298
Methods Detection accuracy, % 19 Kulkarni, S., Santoso, S., Short, T.A.: ‘Incipient fault location algorithm for
underground cables’, IEEE Trans. Smart Grid, 2014, 5, (3), pp. 1165–1174
first method 89.2 20 Kim, C., Bialek, T., Awiylika, J.: ‘An initial investigation for locating self clearing
second method 80.6 faults in distribution systems’, IEEE Trans. Smart Grid, 2013, 4, (2), pp. 1105–1112
third method 83.5 21 Reid, A.J., Zhou, C., Hepburn, D.M., Judd, M.D., Siew, W.H., Withers, P.: ‘Fault
the proposed method 91.5 location and diagnosis in a medium voltage EPR power cable’, IEEE Trans.
Dielectr. Electr. Insul., 2013, 20, (1), pp. 10–18

IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 14, pp. 1988–1997
1996 & The Institution of Engineering and Technology 2015
7 Appendix Xn in the nth stage using the observations y1 to yn−1, and
X̂n+ =
˙ Ê{Xn |yn , . . . , y1 }is the a posteriori estimate of this state
KF process: vector after using the nth observation yn. Pn− and Pn+ are the state
vector covariance matrices before and after using the nth
(i) Set initial estimate of the state vector and its error covariance observation, respectively and are defined similarly.
matrix (X̂n− and Pn− ) (iv) Compute the error covariance for the update estimate using:
(ii) Compute the filter gain at instant n by: Pn+ = Pn− − Kn hT Pn−
Kn = (Pn− h/(hT Pn− h + rn )) (v) Project the filter ahead as: Pn+ = Pn− − Kn hT Pn− X̂n+1 = An X̂n ,
(iii) Update the estimate using the measurement at instant n by: P̂n+1 = An Pn+ ATn + qn bbT
X̂n+ = X̂n− + Kn (yn − hT X̂n− ) where, ˙ c2n },
q=E{ rn =E{v
˙ 2
n }, (vi) Start from 2

X̂n =˙ Ê{Xn |yn−1 , . . . , yn } is the a priori estimate of the state vector

IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 14, pp. 1988–1997
& The Institution of Engineering and Technology 2015 1997

You might also like