Professional Documents
Culture Documents
Abstract—According to the special working condition in real time the deviation of related transformer parameters be-
in the commutation region of the traction grid, a novel tween measured values and nominal values. Therefore, in terms
technique of online core-loss measurement for the electric of optimization of maintenance, avoidance of unplanned fail-
locomotive onboard traction transformer is proposed to
noninvasively monitor the status of the magnetic core in real ures, and extension of service lives of transformers, advanced
time. Meanwhile, a new modeling approach is also put for- condition monitoring techniques are highly desirable in practice.
ward for the equivalent nonlinear magnetizing inductance The electric locomotive onboard traction transformer is a
LM of the magnetic core. First, a no-load test under 31 kV single-phase transformer with multiple split windings. As one of
is implemented on a healthy traction transformer, and the
the foremost electrical devices, its operation state directly affects
measured transient terminal voltages and currents are then
filtered and downsampled by the comprehensive test and the safety and stability of trains. However, related condition
fault diagnosis system of electric locomotive traction trans- monitoring technologies are still under developed.
former. Next, the magnetizing inductance LM is modeled According to CIGRÉ WG A2.37 [1] and surveys from some
as the ratio of “the derivative of main flux linkage λp with locomotive maintenance departments in China, the incipient
respect to time” over “the derivative of magnetizing current faults of transformer cores, which include multipoint ground
im with respect to time.” After that the proposed LM model
is verified by comparing with the experimental results and faults and interlaminar faults, are one of the main causes of
two other models. Finally, the proposed technique for on- transformer failures and, respectively, ranked the fourth and the
line estimation of core loss is applied on a normal onboard third for power transformers and traction transformers among all
traction transformer and a downscaled testing transformer internal faults. The deteriorated and damaged insulation coat-
with different severity of interlaminar fault. The experimen-
ings of lamination layers (often caused by winding interturn
tal results approximately match the theoretical calculation,
and the online estimated values of core loss show sharply arcing faults, manufacturing defects, and mechanical damages
rising trend under incipient fault. due to assemblage, regular maintaining, and abnormal vibration,
etc.), as well as edge burrs (always produced in the processes
Index Terms—Condition monitoring, loss measurement,
magnetic cores, onboard traction transformers.
of slitting, punching, and cutting) are the main origins of multi-
point ground faults and interlaminar faults.
These faults often start as potential local overheating faults,
I. INTRODUCTION which if left undetected at the incipient stage, may deteriorate
OMPARED to fault diagnosis, appropriate condition mon- rapidly under terrible working conditions such as higher order
C itoring methods can timely issue warnings by observing harmonics from loads, vibrations from locomotive bogies, and
unstable supply voltages from the traction power system (nor-
Manuscript received December 26, 2016; revised May 26, 2017, July mally fluctuates between 19 and 31 kV). Therefore, it is urgent
22, 2017, and August 23, 2017; accepted September 14, 2017. Date of to develop an effective online method for condition monitoring
publication October 2, 2017; date of current version January 5, 2018.
This work was supported in part by the National Natural Science Foun-
of magnetic cores of onboard traction transformers.
dation of China under Grant 61603062 and in part by the Hunan Province There have been various conventional methods employed for
2011 Collaborative Innovation Center of Clean Energy and Smart Grid. detection of magnetic core faults during manufacturing and
(Corresponding author: Jiaojiao Zhu.)
Q. Fu is with the School of Energy and Power Engineering, Changsha
scheduled maintenance of onboard traction transformers, e.g.,
University of Science and Technology, Changsha 410076, China (e-mail: the conventional and most commonly used noninvasive methods
fuqiang-0812@163.com). [2]: the dissolved-gas-analysis (DGA)-based method, the clamp
J. Zhu is with the School of Basic Medical Science, Central South
University, Changsha 410083, China (e-mail: jiaoer868@163.com).
ammeter method, and the recently proposed flux-injection probe
Z.-H. Mao is with the Department of Electrical and Computer En- (FIP) method [3]. However, major limitations still exist in the
gineering and Department of Bioengineering, University of Pittsburgh, above methods. For example, the clamp ammeter method is sus-
Pittsburgh, PA 15261 USA (e-mail: zhm4@pitt.edu).
G. Zhang and T. Chen are with the School of Information Science and
ceptible to interference and its measurement accuracy is often
Engineering, Central South University, Changsha 410083, China (e-mail: not satisfactory. Also, it is difficult to achieve continuous moni-
zhanggx@csu.edu.cn; ctfcyt@163.com). toring. Moreover, it can only be applied to the transformer with
Color versions of one or more of the figures in this paper are available
online at http://ieeexplore.ieee.org.
earthing bushing (there is no earthing bushing on the onboard
Digital Object Identifier 10.1109/TIE.2017.2758721 traction transformer). For the DGA-based method, the offline
0278-0046 © 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on September 09,2021 at 16:45:52 UTC from IEEE Xplore. Restrictions apply.
3500 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 65, NO. 4, APRIL 2018
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on September 09,2021 at 16:45:52 UTC from IEEE Xplore. Restrictions apply.
FU et al.: ONLINE CONDITION MONITORING OF ONBOARD TRACTION TRANSFORMER CORE BASED ON CORE-LOSS CALCULATION MODEL 3501
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on September 09,2021 at 16:45:52 UTC from IEEE Xplore. Restrictions apply.
3502 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 65, NO. 4, APRIL 2018
Fig. 3. Structure of the comprehensive test and fault diagnosis system. generator, 10-kV transformer, 100-kV transformer, and other
electrical equipments, and can provide appropriate power sup-
ply for test items. The intelligent acquisition system is made up
III. MODELING TECHNIQUE FOR THE MAGNETIZING of the sensors, smart meters, high-speed data acquisition cards,
INDUCTANCE LM and other components.
Regardless of no-load condition, load condition or with in- The central control system includes the console, pro-
cipient faults, the anhysteretic magnetization characteristic of grammable logic controller (PLC) system, inverter, etc., and
magnetic core remains unchanged. For simplicity, the λp −im is designed to monitor and manage the entire test process. Here,
curve is acquired through the no-load test. However, the trans- the console consists of the industrial computer, manual operation
former core just works within the linear range when supplied buttons, etc., and mainly functions as human–machine interface
with the rated voltage. In order to obtain the integrated magne- and data preservation and processing. The PLC system incorpo-
tization curve that covers both the linear and nonlinear areas, rates SIEMENS S7-200 PLC system, MM440 inverter, etc., and
the no-load test is carried out under the supply voltage of 31 kV, is used to control and monitor the power system, consequently
which is nearly the upper limit of the traction power system. providing a secure and reliable environment for testing.
Special function instrument group, which is used to accom-
plish some specific tests, mainly comprises the digital megohm
A. System of Data Acquisition and Processing meter, dc resistance tester, insulation oil tester, gases analyzer,
Our research team has developed a comprehensive test and etc. Additionally, data transmission between subsystems is ac-
fault diagnosis system, which is a hierarchical control system, complished based on the RS485, RS232, PCI, and other field
for the electric locomotive onboard traction transformer. It can buses.
implement various types of tests for the traction transformer In this paper, the transient terminal voltage and current infor-
and can also acquire and process data such as dissolved gases, mation is needed, so the sensors in Fig. 4 have been selected.
vibration signals, and terminal voltages and currents to analyze For example, CV 3-500/1000 together with HOP 2000-SB/SP1
transformer faults (see Fig. 3). is a closed-loop voltage/current Hall sensor that can acquire
The hierarchical control system is comprised of four sub- high harmonic components of up to 200 kHz. Meanwhile, the
systems: the power system, intelligent acquisition system, cen- wavelet packet transform is adopted to filter and downsample
tral control system, and special function instrument group. The these transient signals. Fig. 5 shows the circuit schematic of the
power system consists of the power distribution cabinets, in- no-load/load test. When the no-load test is carried out, through
duction voltage regulator, testing transformer, triple frequency the 380-/600-V step-up transformer, 600/0–2000-V induction
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on September 09,2021 at 16:45:52 UTC from IEEE Xplore. Restrictions apply.
FU et al.: ONLINE CONDITION MONITORING OF ONBOARD TRACTION TRANSFORMER CORE BASED ON CORE-LOSS CALCULATION MODEL 3503
modeled as
im = −0.6065 cos(ωt) − 0.4636 cos(3ωt) − 0.3547 cos(5ωt)
− 0.2334 cos(7ωt) − 0.135 cos(9ωt) − 0.0667 cos(11ωt)
− 0.028 cos(13ωt) − 0.0094 cos(15ωt). (7)
In addition, the equivalent impedances of the supply power
and transformer winding are far less than that of the transformer
core. Moreover, in the no-load test, the no-load current is so low
that it will cause very small voltage harmonics on the equivalent
Fig. 7. Two cycles of the steady-state magnetizing current in Fig. 6 impedances of the supply power and transformer winding. For
(2.6–3.0 s).
that reason, the supply power voltage waveform can be approxi-
mated by the fundamental frequency of the voltage, and the volt-
age drop on the equivalent impedance of the supply power and
voltage regulator, and 2000-V/35-kV step-up transformer, the transformer winding can be neglected. The relationship among
power supply voltage is transformed to 0–35 kV. Similarly, when the main flux linkage λp , main flux φ0 , induced electromotive
the load test is carried out, through the 380-/600-V step-up force e1 , supply voltage u1 , magnetizing current im , and equiv-
transformer and 600/0–2000-V induction voltage regulator, the alent nonlinear magnetizing inductance LM is summarized in
power supply voltage is transformed to 0–2000 V. (8). It can be found that λp changes with im at the same phase
and frequency, but lags behind the supply voltage u1 by nearly
90°. If the supply voltage u1 is described as (9), the main flux
B. Acquisition of the Magnetization Curve λp −im linkage λp can be derived as (10), where Vm is the peak value
The magnetizing current is acquired by applying the exciting of the supply voltage
current measured from the comprehensive test and fault diag- dφ0 dλp dim
nosis system to (3) and shown in Figs. 6 and 7. u1 ≈ −e1 = N1 = = LM = λp (8)
dt dt dt
From Fig. 6, we can see high transient inrush current peaks √
before the magnetizing current reaches its steady state. We can u1 = Vm sin(ωt) = 31000 × 2 sin(ωt) (9)
derive a more accurate anhysteretic curve λp −im especially Vm
for the deep saturation region by considering the initial inrush λp = − cos(ωt) = −140 cos(ωt). (10)
ω
current peaks, although the modeling complexity would greatly
increase [30], [31]. However, the peak value of the supply volt- Then, the magnetization characteristic curve λp − im of the
age often does not drive the transformer into deep saturation. magnetic core is obtained by (7) and (10) and presented in Fig. 8.
Moreover, it makes sense to use the change of core loss esti-
mated under the steady state to monitor the transformer core’s C. Model of Magnetizing Inductance LM
condition. Therefore, to compromise between complexity and According to (6), the magnetizing inductance LM can be
accuracy, this paper models Lm by just considering the steady- defined as the quotient of “the derivative of λp with respect to
state magnetizing current im . time” over “the derivative of im with respect to time” in
Here, 20 cycles of the steady magnetizing current shown
dλp dt λ p
in Fig. 6 in red (2.6–3.0 s) are analyzed by FFT, and the LM = (λp (im )) = = . (11)
magnetizing current under a supply voltage of 31 kV is dt dim im
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on September 09,2021 at 16:45:52 UTC from IEEE Xplore. Restrictions apply.
3504 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 65, NO. 4, APRIL 2018
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on September 09,2021 at 16:45:52 UTC from IEEE Xplore. Restrictions apply.
FU et al.: ONLINE CONDITION MONITORING OF ONBOARD TRACTION TRANSFORMER CORE BASED ON CORE-LOSS CALCULATION MODEL 3505
TABLE II
RATIO OF RMSD BETWEEN THE MODELS IN [28] AND THIS PAPER
31 kV 25 kV 19 kV
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on September 09,2021 at 16:45:52 UTC from IEEE Xplore. Restrictions apply.
3506 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 65, NO. 4, APRIL 2018
TABLE VI
RATED PARAMETERS OF THE DOWNSCALED TEST TRANSFORMER
Capacity 2 kVA
Voltage of primary winding/traction winding 380/15 V
Current of primary winding/traction winding 5.4/21.7 A
Number of traction winding 6
Silicon steel 30P105
TABLE VII
INCREMENT OF THE CORE EDDY-CURRENT LOSS UNDER
DIFFERENT DEGREES OF INTERLAMINAR FAULT
1 2 3 4 5 6 7 8 9 10 the allowed deviation range and obtain the most accurate results
under 25 kV.
31 kV 4.2 4.32 4 4.4 4.31 4.22 4.08 3.87 3.66 3.96
25 kV 2.54 2.59 2.62 2.65 2.69 2.6 2.62 2.58 2.54 2.62
19 kV 1.48 1.63 1.57 1.7 1.62 1.35 1.48 1.57 1.5 1.62 B. Interlaminar Fault
In Section V-A, it has been verified that the online method
TABLE IV
for core-loss measurement is effective and unaffected by the
ONLINE MEASURED CORE LOSS UNDER RATED CONDITION frequently fluctuating supply voltage and loads. In this section,
taking interlaminar fault as example, we verify whether the on-
The online measured core loss under rated condition (kW) line core-loss measurement technique can monitor the statue of
the transformer core. The theoretical calculation and fault exper-
1 2 3 4 5 6 7 8 9 10 iments are implemented on a downscaled testing transformer,
31 kV 4.33 4.45 4 4.39 4.28 4.12 3.94 3.86 3.93 4 and Table VI presents the related parameters.
25 kV 2.6 2.54 2.45 2.65 2.69 2.6 2.62 2.59 2.6 2.63 1) Theoretical Analysis: When different severities of an
19 kV 1.67 1.66 1.54 1.5 1.29 1.38 1.46 1.5 1.59 1.63
interlaminar fault (represented by the proportion of laminations
that is short circuited in one core limb) occurred, according to
TABLE V
the commonly used engineering calculation formula in [6] and
ONLINE MEASURED CORE LOSS UNDER UNDERLOAD CONDITION [7] as shown in (17), A1 (the increment of core eddy-current loss
compared to the total eddy-current loss) and A2 (the increment
The online measured core loss under underload condition (kW) of core eddy-current loss compared to the total core loss) are
calculated, and the results are showed in Table VII
1 2 3 4 5 6 7 8 9 10
π 2 f 2 Bs 2 whδ 3 4na 2na 2na
31 kV 4.12 4.38 4.24 4.08 3.88 4.2 4.15 4.09 3.99 4.23 pef = cos − cosh
25 kV 2.63 2.58 2.49 2.69 2.71 2.64 2.62 2.55 2.6 2.65 2ρ cosh 2nδ a + cos 2nδ a δ δ δ
19 kV 1.55 1.63 1.7 1.64 1.53 1.49 1.42 1.34 1.5 1.57 2
2na 2na
+ sinh +2
δ δ
1) The overload core loss was measured when the locomotive 2
was climbing with full loads. 2na 2na
+sin −2 (17)
2) The rated core loss was measured when the locomotive was δ δ
running on a relatively flat road with full loads.
3) The underload core loss was measured when the train was where Bs is the saturate magnetic flux density, δ is the skin
nearly empty. depth, n is the number of short-circuited silicon steel sheet, w,
h, and a are the width, height, and thickness of silicon steel
Fig. 15 shows the online measurements of core loss of the sheet, respectively, and pef is the eddy-current loss caused by
testing transformer under different supply voltages and differ- the interlaminar fault.
ent load levels in Tables III–V. Note that the online measure- 2) Experimental Validation: Starting from the central lo-
ments of core loss under different load levels fluctuate within cation of one limb of the downscaled testing transformer, the
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on September 09,2021 at 16:45:52 UTC from IEEE Xplore. Restrictions apply.
FU et al.: ONLINE CONDITION MONITORING OF ONBOARD TRACTION TRANSFORMER CORE BASED ON CORE-LOSS CALCULATION MODEL 3507
TABLE VIII no-load experimental results and two other models, it is shown
INCREMENT OF CORE LOSS UNDER DIFFERENT DEGREES OF THE
FAULT CONDITION COMPARED TO THE NORMAL CONDITION
that our proposed method of modeling LM is simpler in calcu-
lation but easier to implement and obtains better applicability
as well as higher accuracy. Finally, a normal onboard traction
Increment Degree of the interlaminar fault(%)
transformer and a downscaled testing transformer with different
3 5 10 15 20 degrees of interlaminar fault are used to verify that the method
A3 0.29 0.65 2.62 6.18 10.76
for status monitoring of magnetic core based on online measured
core loss is feasible and effective even for incipient faults.
REFERENCES
[1] CIGRÉ, WG A2.37 transformer reliability survey, Brochure 642, Paris,
France, 2015.
[2] W. Feng, Z. Zheng, X. Y. Chen, and Z. W. Huang, “Quantitative analysis
and comparison of offline and online methods used to detect the core multi-
point grounding fault,” in Proc. IEEE Power Modulator High Voltage
Conf., 2014, pp. 241–244, doi: 10.1109/IPMHVC.2014.7287253.
[3] H. Hamzehbahmani, P. Anderson, and K. Jenkins, “Interlaminar insula-
tion faults detection and quality assessment of magnetic cores using flux
injection probe,” IEEE Trans. Power Del., vol. 30, no. 5, pp. 2205–2214,
Oct. 2015, doi: 10.1109/TPWRD.2015.2413900.
[4] Y. X. Yun, W. G. Chen, and Y. Y. Wang, “Photoacoustic detection of
dissolved gases in transformer oil,” Eur. Trans. Electr. Power, vol. 18,
no. 6, pp. 562–576, Sep. 2008, doi: 10.1002/etep.191.
[5] D. S. Lin and E. F. Fuchs, “Real-time monitoring of iron-core and cop-
Fig. 16. Increment of core loss under different degrees of interlaminar per losses of transformers under (non) sinusoidal operation,” IEEE Trans.
fault. Power Del., vol. 21, no. 3, pp. 1333–1341, Jul. 2006, doi: 10.1109/TP-
WRD.2006.874118.
[6] H. Hamzehbahmani, P. Anderson, J. Hall, and D. Fox, “Eddy current loss
3%, 5%, 10%, 15%, and 20% laminations (the percentage is estimation of edge burr-affected magnetic laminations based on equiva-
relative to the total number of laminations of the core limb) lent electrical network—Part I: Fundamental concepts and FEM model-
ing,” IEEE Trans. Power Del., vol. 29, no. 2, pp. 642–650, Apr. 2014,
are artificially welded together, respectively, to simulate differ- doi: 10.1109/TPWRD.2013.2272663.
ent degrees of the interlaminar fault. Then, the proposed online [7] H. Hamzehbahmani, P. Anderson, J. Hall, and D. Fox, “Eddy current loss
core-loss estimation method is applied to calculate A3 (the in- estimation of edge burr-affected magnetic laminations based on equiv-
alent electrical network—Part II: Analytical modeling and experimental
crement of core loss under the fault condition compared to the results,” IEEE Trans. Power Del., vol. 29, no. 2, pp. 651–659, Apr. 2014,
normal condition). For enhancing the test effectiveness, the av- doi: 10.1109/TPWRD.2013.2279634.
erage of 50 sets of data is taken under each fault condition, and [8] A. Lotfi, H. K. Høidalen, E. Agheb, and A. Nysveen, “Characterization of
magnetic losses in the transformer tank steel,” IEEE Trans. Magn., vol. 52,
the results are showed in Table VIII. no. 5, May 2016, Art. no. 6301104, doi: 10.1109/TMAG.2015.2512929.
From Tables VII and VIII and Fig. 16, it can be seen that: [9] X. Peng, “Analysis and calculation about eddy current filed and its loss in
1) with the increase of fault severity, the core loss increases the oil tank of main transformer installed in O’Z-Y electric locomotive,”
Electr. Driv. Locom., no. 4, pp. 36–38, Jul. 2013.
sharply; 2) the increment is very obvious even with only [10] T. D. Kefalas and A. G. Kladas, “Harmonic impact on distribution
5% short-circuited silicon steel sheets; and 3) the increment transformer no-load loss,” IEEE Trans. Ind. Electron., vol. 57, no. 1,
A3 calculated based on the proposed technique for online pp. 193–200, Jan. 2010, doi: 10.1109/TIE.2009.2030207.
[11] I. Villar, U. Viscarret, I. Etxeberria-Otadui, and A. Rufer, “Global loss eval-
estimation of core loss approximately matches the theoretical uation methods for nonsinusoidally fed medium-frequency power trans-
calculation A2 . In conclusion, the online core-loss estimation formers,” IEEE Trans. Ind. Electron., vol. 56, no. 10, pp. 4132–4140,
method is feasible and effective to monitor the status of Oct. 2009, doi: 10.1109/TIE.2009.2021174.
[12] J. Reinert, A. Brockmeyer, and R. W. A. A. De Doncker, “Calculation
magnetic core in the electric locomotive onboard traction of losses in ferro- and ferrimagnetic materials based on the modified
transformer. Steinmetz equation,” IEEE Trans. Ind. Appl., vol. 37, no. 4, pp. 1055–1060,
Jul./Aug. 2001, doi: 10.1109/28.936396.
[13] E. Dallago and G. Venchi, “Analytical and experimental approach to high-
VI. CONCLUSION frequency transformer simulation,” IEEE Trans. Power Electron., vol. 14,
no. 3, pp. 415–421, May 1999, doi: 10.1109/63.761684.
This paper presented a noninvasive online technique for mea- [14] J. D. Liu and V. Dinavahi, “Detailed magnetic equivalent circuit based
surement of core loss of the electric locomotive onboard traction real-time nonlinear power transformer model on FPGA for electro-
transformer using the transient terminal voltages and currents magnetic transient studies,” IEEE Trans. Ind. Electron., vol. 63, no. 2,
pp. 1191–1201, Feb. 2016, doi: 10.1109/TIE.2015.2477487.
measured from terminations. The magnetizing current, as the [15] A. Wilk, J. Nieznanski, and I. Moson, “Nonlinear model of a wound iron
only parameter that cannot be measured directly in the online core traction transformer with the account of magnetic,” in Proc. Int. Conf.
measurement technique, is calculated based on the model of Electr. Mach., 2010, pp. 1–7, doi: 10.1109/ICELMACH.2010.5607873.
[16] W. A. Roshen, “A practical, accurate and very general core loss model for
equivalent nonlinear magnetizing inductance LM . First, the in- nonsinusoidal waveforms,” IEEE Trans. Power Electron., vol. 22, no. 1,
tegrated magnetization characteristic curve λp −im that covers pp. 30–40, Jan. 2007, doi: 10.1109/TPEL.2006.886608.
both linear and nonlinear areas is acquired through the no-load [17] T. Hatakeyama and K. Onda, “Core loss estimation of various materi-
als magnetized with the symmetrical/asymmetrical rectangular voltage,”
test under the supply voltage of 31 kV and then LM is modeled IEEE Trans. Power Electron., vol. 29, no. 12, pp. 6628–6635, Dec. 2014,
as the slope of the λp −im curve. Next, by comparing with the doi: 10.1109/TPEL.2014.2306755.
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on September 09,2021 at 16:45:52 UTC from IEEE Xplore. Restrictions apply.
3508 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 65, NO. 4, APRIL 2018
[18] Y. Han and Y. F. Liu, “A practical transformer core loss measurement Jiaojiao Zhu was born in Aksu, Xinjiang, China,
scheme for high-frequency power converter,” IEEE Trans. Ind. Electron., in 1986. She received the B.Eng. degree in au-
vol. 55, no. 2, pp. 941–948, Feb. 2008, doi: 10.1109/TIE.2007.896154. tomation, the M.Eng. degree in transportation in-
[19] D. Ribbenfjard, “Electromagnetic transformer modeling including the fer- formation engineering and control, and the Ph.D.
romagnetic core,” Ph.D. dissertation, Dept. Elect. Eng., KTH Roy. Inst. degree in transportation equipments and control
Technol., Stockholm, Sweden, p. 47, 2010. from the Central South University, Changsha,
[20] P. Langevin, “Magnetism and electron theory,” Ann. Chem. Phys., vol. 5, China, in 2008, 2011, and 2017, respectively.
pp. 70–127, 1905. From 2014 to 2015, she was with the Uni-
[21] J. Krah, “Modeling of losses in power transformer from dc to the low versity of Pittsburgh, Pittsburgh, PA, USA, as a
kilohertz range,” Ph.D. dissertation, Dept. Elect. Eng., KTH Roy. Inst. joint-training Ph.D. student. She is currently with
Technol., Stockholm, Sweden, 2010. the School of Basic Medical Science, Central
[22] D. C. Jiles and D. L. Atherton, “Theory of magnetic hysteresis,” South University, as a Postdoctoral Fellow. Her research interests in-
J. Magn. Magn. Mater., vol. 19, no. 5, pp. 2183–2185, Sep. 1983, clude condition monitoring, fault diagnosis, service-life assessment and
doi: 10.1016/0304-8853(86)90066-1. management of large-scale electrical equipments, and the application of
[23] G. W. Swift, “An analytical approach to ferroresonance,” IEEE machine learning methods.
Trans. Power App. Syst., vol. PAS-88, no. 1, pp. 42–46, Jan. 1969,
doi: 10.1109/TPAS.1973.293584.
[24] W. L. A. Neves and H. W. Dommel, “On modeling iron core nonlinear-
Zhi-Hong Mao (S’96–M’05–SM’09) received
ities,” IEEE Trans. Power Syst., vol. 8, no. 2, pp. 417–425, May 1993,
the dual Bachelor’s degrees in automatic con-
doi: 10.1109/59.260845.
trol and mathematics and the M.Eng. degree in
[25] M. G. Vanti, S. L. Bertoli, S. H. L. Cabral, A. G. Gerent, and P. Kuo-Peng,
intelligent control and pattern recognition from
“Semianalytic solution for a simple model of inrush currents in transform-
Tsinghua University, Beijing, China, in 1995 and
ers,” IEEE Trans. Magn., vol. 44, no. 6, pp. 1270–1273, Jun. 2008, doi:
1998, respectively, the S.M. degree in aeronau-
10.1109/TMAG.2007.916245.
[26] B. Khalkhali and J. Sadeh, “Transformer differential protection by on- tics and astronautics from Massachusetts Insti-
tute of Technology, Cambridge, MA, USA, in
line core modeling and orthogonal polynomials,” IEEE Trans. Power
2000, and the Ph.D. degree in medical engi-
Del., vol. 30, no. 5, pp. 2146–2153, Oct. 2015, doi: 10.1109/TP-
neering and medical physics from the Harvard-
WRD.2014.2380452.
[27] B. M. Ge, A. T. de Almeida, Q. L. Zheng, and X. H. Wang, “An equiva- MIT Division of Health Sciences and Technology,
Cambridge, in 2006.
lent instantaneous inductance-based technique for discrimination between
He joined the University of Pittsburgh, Pittsburgh, PA, USA, as an As-
inrush current and internal faults in power transformers,” IEEE Trans.
sistant Professor in 2005 and became an Associate Professor in 2011
Power Del., vol. 20, no. 4, pp. 2473–2482, Oct. 2005, doi: 10.1109/TP-
WRD.2005.855443. and a William Kepler Whiteford Faculty Fellow in 2012.
Dr. Mao received the CAREER Award of the National Science Foun-
[28] S. Bhowmick and S. Nandi, “Online detection of an interturn winding fault
dation in 2010, the Andrew P. Sage Best Transactions Paper Award of the
in single-phase distribution transformers using a terminal measurement-
IEEE Systems, Man and Cybernetics Society in 2010, the Outstanding
based modeling technique,” IEEE Trans. Power Del., vol. 30, no. 2,
pp. 1007–1015, Apr. 2015, doi: 10.1109/TPWRD.2014.2347320. Service Award of the IEEE TRANSACTIONS ON INTELLIGENT TRANSPORTA-
TION SYSTEMS in 2013, and the Pitt Chancellor’s Distinguished Teaching
[29] N. Chiesa, “Power transformer modelling advanced core model,” M.S.
thesis, Dept. Elect. Eng., Polytechnic Univ. Milan, Milan, Italy, pp. 32– Award in 2016.
33, Jun. 2005.
[30] S. G. Abdulsalam, W. Xu, W. L. A. Neves, and X. Liu, “Estimation of
transformer saturation characteristics from inrush current waveforms,” Guixin Zhang was born in Beiliu, Guangxi,
IEEE Trans. Power Del., vol. 21, no. 1, pp. 170–177, Jan. 2006, doi: China, in 1965. She received the B.Eng. degree
10.1109/PES.2006.1708912. in automatic control and the M.Eng. degree in
[31] F. D. Leon, S. Jazebi, and A. Farazmand, “Accurate measurement of the transportation information engineering and con-
air-core inductance of iron-core transformers with a non-ideal low-power trol from the Central South University (the for-
rectifier,” IEEE Trans. Power Del., vol. 29, no. 1, pp. 294–296, Feb. 2014, mer Changsha Railway University), Changsha,
doi: 10.1109/TPWRD.2013.2288023. Hunan, China, in 1986 and 2000, respectively.
[32] U. C. Merzbach and C. B. Boyer, A History of Mathematics, 3rd ed. Since 1986, she has been a permanent Re-
New York, NY, USA: Wiley, Jan. 2011, ch. 13, p. 278. searcher with the Institute of Rail Transport and
Electric Traction Technology, and she is currently
an Associate Professor with the School of Infor-
mation Science and Engineering, Central South University. Her research
interests include fault diagnosis and electrical drivers and electric trac-
tion control systems.
Qiang Fu was born in Hengyang, Hunan, China, Tefang Chen was born in Lianyuan, China, in
in 1982. He received the B.Eng. degree in au- 1957. He received the B.Eng. degree in au-
tomation, the M.Eng. degree in control science tomation from Dalian University of Technology,
and engineering, and the Ph.D. degree in trans- Dalian, China, in 1981, and the M.Eng. degree
portation equipments and control from the Cen- in electrical engineering and the Ph.D. degree
tral South University, Changsha, China, in 2005, in electrical engineering from the Central South
2008, and 2013, respectively. University (the former Changsha Railway Uni-
Since 2014, he has been with the School of versity), Changsha, China, in 1991 and 2005,
Energy and Power Engineering, Changsha Uni- respectively.
versity of Science and Technology, Changsha, Since 1982, he has been a permanent Re-
Hunan, where he is currently a Lecturer. His re- searcher with the Institute of Rail Transport and
search interests include condition monitoring, fault diagnosis, service-life Electric Traction Technology, and he is currently a Professor with the
assessment and management of transformers and converters, electrical School of Information Science and Engineering, Central South Univer-
drivers and electric traction control systems, and the application of ma- sity. His main research interests include fault diagnosis and fault-tolerant
chine learning methods. technology of electrical drivers and electric traction control system.
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on September 09,2021 at 16:45:52 UTC from IEEE Xplore. Restrictions apply.