Professional Documents
Culture Documents
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Eurocode 2: Design of
concrete structures —
Part 1.2 General rules —
Structural fire design —
Contents
Page
Committees responsible Inside front cover
National foreword ii
Foreword 2
Text of National Application Document v
Text of ENV 1992-1-2 7
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
© BSI 03-2000 i
DD ENV 1992-1-2:1996
National foreword
This Draft for Development was prepared by Subcommittee B/525/2 and is the
English language version of ENV 1992-1-2:1995 Eurocode 2: Design of concrete
structures — Part 1.2: General rules — Structural fire design, as published by the
European Committee for Standardization (CEN). This Draft for Development
also includes the United Kingdom (UK) National Application Document (NAD)
to be used with the ENV in the design of buildings to be constructed in the UK.
ENV 1992-1-2 results from a programme of work sponsored by the European
commission to make available a common set of rules for the structural and
geotechnical design of building and civil engineering works.
This publication should not be regarded as a British Standard.
An ENV is made available for provisional application, but does not have the
status of a European Standard. The aim is to use the experience gained to modify
the ENV so that it can be adopted as a European Standard. The publication of this
ENV and its National Application Document should be considered to supersede
any reference to a British Standard in previous DD ENV Eurocodes concerning
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Summary of pages
This document comprises a front cover, an inside front cover, pages i to x,
the ENV title page, pages 2 to 63 and a back cover.
This standard has been updated (see copyright date) and may have had
amendments incorporated. This will be indicated in the amendment table on the
inside front cover.
ii © BSI 03-2000
DD ENV 1992-1-2:1996
National Application
Document
for use in the UK with
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Contents of
National Application Document
Page
Introduction v
1 Scope v
2 Partial factors, combination factors and other values v
3 Tabulated data v
4 Reference standards x
5 Additional recommendations x
Table 1 — Values to be used in referenced clauses instead of boxed values v
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
iv © BSI 03-2000
DD ENV 1992-1-2:1996
Introduction
This National Application Document (NAD) has been prepared by Subcommittee B/525/2. It has been
developed from the following.
a) A textual examination of ENV 1992-1-2.
b) A parametric calibration against BS 8110, supporting standards and test data.
c) Trial calculations.
1 Scope
This NAD provides information to enable ENV 1992-1-2 (hereafter referred to as EC2-1.2) to be used for
the design of buildings to be constructed in the UK. It is assumed that it will be used in conjunction with
DD ENV 1992-1-1, the NAD of which refers to BSI publications for values of actions. Since publication of
ENV 1992-1-1 (hereafter referred to as EC2-1.1), ENVs for actions (Parts of Eurocode 1) have been
published. Where appropriate this NAD refers to them. It should be borne in mind that designs should be
consistent in their use of UK and CEN standards for all parameters.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
4.2.3 (4) Limit to fire resistance for distribution bars along sides of columns 120 min.
4.2.7.4 (2) Minimum top reinforcement over span in column strip 10 %
3 Tabulated data
Tables 4.1 to 4.11 of EC2-1.2:1995 are replaced with Table N4.1 to Table N4.11 respectively as given below.
All the tables in 4.2 of EC2-1.2:1995 have been reproduced, regardless of whether changes have been made,
to avoid unnecessary cross referencing. Changes in values from those given in EC2-1.2 are shown in bold.
These changes largely reflect the current values in BS 8110.
Table N4.1 — Minimum dimensions and axis distances for reinforced concrete
columns; rectangular and circular section
Minimum dimensions
mm
Column width bmin/axis distance a
Standard fire resistance
Column exposed on more than one side Exposed on one side
Èfi = 0.2 Èfi = 0.5 Èfi = 0.7 Èfi = 0.7
1 2 3 4 5
R 30 150/10a 150/10a 150/10a 100/10a
R 60 150/10a 180/10a 200/10a 120/10a
R 90 180/10a 210/10a 240/35 140/10a
R 120 200/40 250/40 280/40 160/45
R 180 240/50 320/50 360/50 200/60
R 240 300/50 400/50 450/50 300/60
a Normally the cover required by ENV 1992-1-1 will control.
© BSI 03-2000 v
DD ENV 1992-1-2:1996
EI 30 60
EI 60 80
EI 90 100
EI 120 120
EI 180 150
EI 240 175
Minimum dimensions
mm
Wall thickness/axis distance for
Standard fire
resistance Èf = 0.35 Èf = 0.7
Wall exposed on one Wall exposed on two Wall exposed on one Wall exposed on two
side sides side sides
1 2 3 4 5
REI 30 100/10 a
120/10 a
120/10 a
120/10a
1 2 3
R 30 80/25 200/10 a
R 60 120/40 300/25
R 90 150/55 400/45
R 120 200/65 500/45
R 180 240/80 600/60
R 240 280/90 700/70
NOTE For prestressed members the increase of axis distance according
to 4.2.2(4) should be noted.
a Normally the cover required by ENV 1992-1-1 will control.
vi © BSI 03-2000
DD ENV 1992-1-2:1996
Table N4.5 — Minimum dimensions and axis distances for simply supported beams
made with reinforced and prestressed concrete
Minimum dimensions
Standard fire mm
resistance Possible combinations of a and bmin where a is the average axis
Web thickness bw
distance and bmin is the width of beam
1 2 3 4 5 6
R 30 bmin 80 120 160 200 80
a 25 15a 10a 10a
R 60 bmin 120 160 200 300 100
a 40 35 30 25
R 90 bmin 150 200 250 400 100
a 55 45 40 35
R 120 bmin 200 240 300 500 120
a 65 55 50 45
R 180 bmin 240 300 400 600 140
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
a 80 70 65 60
R 240 bmin 280 350 500 500 160
a 90 80 75 70
asd = a + 10 mm
(see note 2.)
NOTE 1 For prestressed beams the increase of axis distance according to 4.2.2(4) of this Part 1-2 should be noted.
NOTE 2 asd is the axis distance to the side of beam for the corner bars (tendon or wire) of beams with only one layer of
reinforcement. For values of bmin greater than that given in column 4 no increase of a is required.
a
Normally the cover required by ENV 1992-1-1 will control.
Table N4.6 — Minimum dimensions and axis distances for continuous beams
made with reinforced and prestressed concrete
Minimum dimensions
mm
Standard fire resistance
Possible combinations of a and bmin where a is the average
axis distance and bmin is the width of beam Web thickness bw
1 2 3 4 5
R 30 bmin 80 160 200 80
a 12a 12a 12a
R 60 bmin 120 200 300 100
a 25 12a 12a
R 90 bmin150 250 400 100
a 35 25 25
R 120 bmin 180 300 450 120
a 55 45 35
R 180 bmin 225 350 550 140
a 70 60 50
R 240 bmin 275 450 650 160
a 80 70 60
asd = a + 10 mm
(see note 2.)
NOTE 1 For prestressed beams the increase of axis distance according to 4.2.2(4) should be noted.
NOTE 2 asd is the axis distance to the side of beam for the corner bars (tendon or wire) of beams with only one layer of
reinforcement. For values of bmin greater than that given in column 3 no increase of a is required.
a
Normally the cover required by ENV 1992-1-1 will control.
1 2 3 4 5
REI 30 60 10a 10a 10a
REI 60 80 20 10a 15a
REI 90 100 30 15a 20
REI 120 120 40 20 25
REI 180 150 55 30 40
REI 240 175 65 40 50
NOTE 1 lx and ly are the spans of a two-way slab (two directions at right angles) where ly is the longer span
NOTE 2 The minimum cover of any bar should not be less than half of required average axis distance, am’ defined in 4.2.2.
NOTE 3 For prestressed slabs the increase of axis distance according to 4.2.2(4) should be noted.
NOTE 4 The axis distance, a, in columns 4 and 5 for two way slabs relate to slabs supported at all four edges. Otherwise, they
should be treated as one-way spanning slab.
a
Normally the cover required by ENV 1992-1-1 will control.
1 2 3
REI 30 75 10 a
REI 60 95 15a
REI 90 110 25
REI 120 125 35
REI 180 150 45
REI 240 170 50
a Normally the cover required by ENV 1992-1-1 will control.
Table N4.10 — Minimum dimensions and axis distance for two-way spanning, simply
supported ribbed slabs in reinforced or prestressed concrete
Minimum dimensions
mm
Standard fire resistance
Possible combinations of width of Slab thickness hs and axis
ribs bmin and axis distance a distance a, in span
1 2 3 4 5
REI 30 bmin W 80 hs 80
a 15 a
a 10a
REI 60 bmin 100 120 W 200 hs 80
a 35 25 15a a 10a
REI 90 bmin 120 160 W 250 hs 100
a 45 40 30 a 15a
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Table N4.11 — Minimum dimensions and axis distances for two way spanning ribbed
slabs in reinforced or prestressed concrete with at least one restrained edge
Minimum dimensions
mm
Standard fire resistance
Possible combinations of width of ribs bmin and Slab thickness hs and axis distance
axis distance a a, in span
1 2 3 4 5
REI 30 bmin W 80 hs 80
a 10a a 10a
REI 60 bmin 100 120 W 200 hs 80
a 25 15a 10a a 10a
REI 90 bmin 120 160 W 250 hs 100
a 35 25 15a a 15a
REI 120 bmin 140 190 W 300 hs 120
a 45 40 30 a 20
REI 180 bmin 175 300 W 400 hs 150
a 60 50 40 a 30
REI 240 bmin 200 400 W 500 hs 175
a 70 60 50 a 40
asd = a + 10 mm
NOTE 1 For prestressed ribbed slabs, the axis-distance a should be increased in accordance with 4.2.2(4).
NOTE 2 asd denotes the distance measured between the axis of the reinforcement and the lateral surface of the
rib exposed to fire.
a Normally the cover required by ENV 1992-1-1 will control.
© BSI 03-2000 ix
DD ENV 1992-1-2:1996
4 Reference standards
Supporting standards including materials specifications and standards for construction are listed in
Table 2 of this NAD.
Table 2 — Reference in EC2 Part 1.2 to other codes and standards
Document
Reference in EC2-1.2 Subject area Status
referred to
Various ENV 1992-1-1 Design of concrete structures. General rules Published 1991
and rules for buildings
Various ENV 1991-2-1 Thermal and mechanical actions Published 1995
1.1(1)P 2.4.3(4) ENV 1991-2-2 Design for accidental situation of fire exposure Published 1995
1.3(1) ISO 834 Standards for fire tests Published 1975
1.4.12 ENV 1991-1 Fundamental combination of actions Published 1994
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
4.2.4.2(2) ENV 1992-1-6 Minimum thickness of plain concrete walls Published 1994
5 Additional recommendations
5.1 Chapter 4. Structural fire design
a) Clause 4.2.2(4)
Current British practice assumes a less conservative increase in axis distance, a, from that given in
this clause. The second sentence onwards of this clause may be replaced with the following:
If no special check according to (4) is made in prestressed tensile members and beams the required axis
distance, a, should be increased by:
10 mm for prestressing bars, corresponding to Ûcr = 400 °C;
15 mm for prestressing wires and strands, corresponding to Ûcr = 350 °C.
If no special check according to (4) is made in prestressed simply supported slabs (including simply
supported ribbed slabs) the required axis distance, a, may be increased by 5 mm for prestressing bars,
wires and strands.
If no special check according to (4) is made in prestressed continuous slabs (including continuous ribbed
slabs) the required axis distance, a, should be increased by:
5 mm for prestressing bars;
10 mm for prestressing wires and strands.
b) Clause 4.2.2(14)
Current British practice assumes a less conservative increase in axis distance, a, from that given in
this clause. The value of %ap in equation (4.6) may be assumed as follows:
%ap = 5 mm for prestressing bars;
= 15 mm for prestressing wires and strands.
c) Clause 4.2.7.1(4) — addition
The effective thickness, he, of hollow concrete slabs should be obtained by considering the total solid
part of the cross-section area as follows:
he = h1. M0.7 (4.12A)
where
h1 is the total thickness of concrete slab (See Figure 4.7 of EC2-1.2);
M is the proportion of concrete cross section area to the total cross section area of
concrete slab including voids.
x © BSI 03-2000
EUROPEAN PRESTANDARD ENV 1992-1-2:1995
PRÉNORME EUROPÉENNE
November 1995
EUROPÄISCHE VORNORM
English version
Eurocode 2: Calcul des structures en béton — Eurocode 2: Planung von Stahlbeton- und
Partie 1-2: Règles générales — Calcul du Spannbetontragwerken — Teil 1-2: Allgemeine
comportement au feu Regeln — Tragwerksbemessung für den
Brandfall
CEN
European Committee for Standardization
Comité Européen de Normalisation
Europäisches Komitee für Normung
Central Secretariat: rue de Stassart 36, B-1050 Brussels
© 1995 All rights of reproduction and communication in any form and by any means reserved in all
countries to CEN and its members
Ref. No. ENV 1992-1-2:1995 E
ENV 1992-1-2:1995
2 © BSI 03-2000
ENV 1992-1-2:1995
© BSI 03-2000 3
ENV 1992-1-2:1995
Contents Page
4.6 Anchorage 36
Page
5 Protective layers 37
Foreword 2
Annex A (informative) Additional
1 General 7 information on material properties 38
1.1 Scope 7 Annex B (informative) Temperature
1.2 Distinction between principles profiles and reduced cross section 54
and application rules 7 Annex C (informative) Simplified method
1.3 Normative References 7 of calculation for beams and slabs 58
1.4 Definitions 7 Annex D (informative) A procedure for
1.5 Symbols 10 assessing the structural response of
reinforced concrete elements under fire 59
1.6 Units 10
Figure 2.1 — Variation of ½fi as a function
2 Basic principles 11
of ß = Qk1/Gk for different values of Ó1,1 13
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
4 © BSI 03-2000
ENV 1992-1-2:1995
Page Page
Figure A.1 — Coefficient kct(G) allowing Figure A.14 — Thermal elongation of concrete 50
for decrease of tensile strength, (fctk) of Figure A.15 — Specific heat of concrete 51
concrete at elevated temperature 38
Figure A.16 — Thermal conductivity of concrete 51
Figure A.2 — Model for compression
Figure A.17 — Thermal elongation of steel 53
stress-strain relationships of siliceous
and calcareous concrete at elevated Figure A.18 — Relationship between Öc,fi
temperatures 39 and h (or b) for risk of explosive spalling
for normal weight concrete members 54
Figure A.3 — Parameters for stress-strain
relationships of concrete at elevated Figure B.1 — Temperature profiles for beams 55
temperatures, according to Figure A.2 Figure B.2 — Temperature profiles for slabs 56
and Table A.1 40 Figure B.3 — Reduction in cross section and
Figure A.4 — Stress-strain relationships concrete strength assuming a standard fire 57
of siliceous concrete under uniaxial Figure C.1 — Positioning the free bending
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
© BSI 03-2000 5
ENV 1992-1-2:1995
Page
Table 4.9 — Minimum dimensions and
axis distances for reinforced and
prestressed concrete flat slabs 29
Table 4.10 — Minimum dimensions and
axis distance for two-way spanning, simply
supported ribbed slabs in reinforced or
prestressed concrete 30
Table 4.11 — Minimum dimensions and
axis distances for two-way spanning ribbed
slabs in reinforced or prestressed concrete
with at least one restrained edge 31
Table A.1 — Values for the main parameters
of the stress-strain relationships in
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
6 © BSI 03-2000
ENV 1992-1-2:1995
1 General
1.1 Scope
(1)P ENV 1992-1-2 deals with the design of concrete structures for the accidental situation of fire exposure
and shall be used in conjunction with ENV 1992-1-1 and ENV 1991-2-2. It provides additions to and
identifies differences from the design of structures at normal temperatures.
(2)P Part 1-2 applies only to passive methods of fire protection. Active methods are not included.
(3)P Part 1-2 applies to structures which for reasons of general fire safety, are required to fulfil the
following criteria when exposed to fire:
— avoid premature collapse of the structure (load-bearing function)
— limit fire spread (flames, hot gases, excessive heat) beyond designated areas (separation function)
(4)P Part 1-2 gives Principles and Application Rules (see 1.2 in ENV 1992-1-1) in respect to the design of
structures to fulfil the criteria given in (3)P (e.g. in terms of required standard fire resistance).
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
(5)P Part 1-2 applies to those structures or parts of structures which are within the scope of Part 1-1, 1-3
to 1-6. However, it does not cover:
— structures with prestressing by external tendons
— shell structures.
(6) For structures using unbonded tendons reference should be made to 4.1(6) and 4.2.2(6).
1.4 Definitions
1.4.1
critical temperature of reinforcement
the temperature at which failure is expected to occur in reinforcement at a given load level
1.4.2
design fire
a specified fire development assumed for design purposes
1.4.3
effects of actions E (as described in ENV 1992-1-1, 2.2.2.5)
the effects of actions (E) are responses (for example internal forces and moments, stresses, strains) of the
structure to the actions
© BSI 03-2000 7
ENV 1992-1-2:1995
1.4.4
fire compartment
a space within a building extending over one or several floors which is enclosed by separating members
such, that fire spread beyond the compartment is prevented during the relevant fire exposure
1.4.5
fire resistance
the ability of a structure or part of it to fulfil its required functions (load-bearing and/or separating
function) for a specified fire exposure, for a specified period of time
1.4.6
global structural analysis (for fire)
the analysis of the entire structure, when either the entire structure or only parts of it are exposed to fire.
Indirect fire actions are considered throughout the structure
1.4.7
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
8 © BSI 03-2000
ENV 1992-1-2:1995
1.4.16
standard fire resistance
the ability of a structure or part of it (usually only members) to fulfil required functions (load-bearing
function and/or separating function) for exposure to heating according to the standard temperature-time
curve, for a stated period of time
1.4.17
structural members
the load-bearing members of a structure including bracings
1.4.18
sub-assembly analysis (for fire)
the structural analysis of parts of the structure exposed to fire in which the respective part of the structure
is considered as isolated with appropriate support and boundary conditions. Indirect fire actions within the
sub-assembly are considered, but time-dependent interaction with other parts of the structure is not
considered
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
NOTE 1 Where the effects of indirect fire actions within the sub-assembly are negligible, sub-assembly analysis is equivalent to
member analysis.
NOTE 2 Where the effects of indirect fire actions between sub-assemblies are negligible, sub-assembly analysis is equivalent to
global structural analysis.
1.4.19
support and boundary conditions
description of restraints at supports and boundaries for structural modelling
1.4.20
temperature analysis
the procedure to determine the temperature development in members on the basis of thermal actions and
the thermal material properties of the members and of the protective layers, where relevant
1.4.21
temperature-time curves
gas temperatures in the environment of member surfaces as a function of time. They may be either
— Nominal: Conventional curves, adopted for classification or verification of fire resistance, e.g. the
standard temperature-time curve.
— Parametric: Determined on the basis of fire models and the specific physical parameters defining the
conditions in the fire compartment.
1.4.22
thermal actions
actions on the structure described by the net heat flux to the members
1.4.23
thermal insulation criterion “I”
a criterion by which the ability of a separating member to prevent excessive transmission of heat is
assessed
© BSI 03-2000 9
ENV 1992-1-2:1995
1.5 Symbols
The following symbols supplement those given in ENV 1992-1-1:
Ed,fi design effect of actions in the fire situation
Ed design effect of actions for normal temperature design
Rd,fi design load bearing capacity (resistance) in the fire situation Rd,fi(t) at a given time t.
R 30 or R 60,... a member meeting the load-bearing criterion for 30, or 60... minutes in standard fire
exposure
E 30 or E 60,... a member meeting the integrity criterion for 30, or 60... minutes in standard fire
exposure
I 30 or I 60,... a member meeting the thermal insulation criterion for 30, or 60... minutes in standard
fire exposure
Xk characteristic value of a strength or deformation property for normal temperature design
Xd,fi design strength or deformation property in the fire situation
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
1.6 Units
(1) Temperature G in degrees Celsius (°C)
Temperature difference in kelvins (K)
Specific heat c in joule per kilogramme per kelvin (J/kgK)
Coefficient of thermal conductivity Æ in watts per metre per kelvin (W/mK)
10 © BSI 03-2000
ENV 1992-1-2:1995
2 Basic principles
2.1 Performance requirements
(1)P Where structures are required to have mechanical resistance under fire conditions, they shall be
designed and constructed in such a way that they maintain their load bearing function during the relevant
fire exposure — Criterion “R”.
(2)P Where compartmentation is required, the members forming the compartment, including joints, shall
be designed and constructed in such a way that they maintain their separating function during the relevant
fire exposure, i.e.
— no integrity failure due to cracks, holes or other openings, which are large enough to cause fire
penetration by hot gases or flame — Criterion “E”
— no insulation failure due to temperatures of the non-exposed surface exceeding ignition temperatures
— Criterion “I”.
(3) Criterion “I” may be assumed to be met where the average temperature rise over the whole of the
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
non-exposed surface during the standard fire exposure does not exceed 140K and the maximum
temperature rise of that surface does not exceed 180K.
(4)P Members shall comply with criteria R, E and I as follows:
separating only: E and I
loadbearing only: R
separating and loadbearing: R, E and I
(5) When using general calculation methods (see 4.4) the deformation criteria should be used where
separating members or protective measures are affected by the deformation of the load bearing structure.
Reference should be made to the relevant product specifications.
2.2 Actions
(1)P Thermal and mechanical actions shall be obtained from ENV 1991-2-2.
(2) Where rules given in this Part 1-2 are only valid for the standard fire exposure, this is identified in the
relevant clauses.
© BSI 03-2000 11
ENV 1992-1-2:1995
YM,fi =|1,0|
Ed,fi(t) is the design effect of actions in the fire situation, determined from the general rule given in
ENV 1991-2-2, including indirect fire actions
Rd,fi(t) is the corresponding design resistance at elevated temperatures
t is the relevant duration of fire exposure
(2)P The structural model adopted for design to this ENV 1992-1-2 shall reflect the expected performance
of the structure in fire exposure.
(3) The global structural analysis should take into account the relevant failure mode in fire exposure, the
temperature-dependent material properties including stiffness, and effects of thermal expansions and
deformations (indirect fire actions).
(4) General calculation methods given in 4.4 are suitable for global structural analysis. They are based on
models which determine the temperature development within the structure and the mechanical behaviour
of the structure.
2.4.3 Analysis of parts of the structure
(1) As an alternative to the global structural analysis of the entire structure for various fire situations, a
structural analysis of parts of the structure (sub-assemblies) may be performed, where the sub-assemblies
are exposed to fire and analyzed in accordance with 2.4.2
(2) Sub-assemblies should be specified on the basis of the potential thermal expansions and deformations
such, that their interaction with other parts of the structure can be approximated by time-independent
support and boundary conditions during fire exposure.
(3) Effects of (permanent and variable) actions at supports and boundaries may be assumed to correspond
to those in ENV 1992-1-1.
(4) As an approximation to performing a global structural analysis for t = 0, effects of (permanent and
variable) actions at supports and boundaries may be obtained from the normal temperature design by
using
Ed,fi = ½fi.Ed (2.5)
where
Ed is the design effect of actions from ultimate limit state design to ENV 1992-1-1 using the
fundamental combination
½fi is a reduction factor, depending on ß = Qk1/Gk, which is the ratio between the main variable and
permanent actions applied to the structure, see ENV 1991-2-2:
½fi = ([1,0] + Ó1,1,ß)/(YG + YQ.ß) (2.6)
Values of Ó1,i are given in ENV 1991-1. Equation (2.6) is graphically represented presented in Figure 2.1.
(5) As a simplification ½fi =|0,6|may be used, except for load category E as given in ENV 1991-2-1 (areas
susceptible to accumulation of goods, including access areas) for which a value of|0,7|should be used.
12 © BSI 03-2000
ENV 1992-1-2:1995
(6) Simplified and general methods given in 4.3 and 4.4 respectively are suitable for analysis of parts of the
structure.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Figure 2.1 — Variation of ½fi as a function of ß = Qk1/Gk for different values of Ó1,1
2.4.4 Member analysis
(1) The support and boundary conditions of members corresponding to those in ENV 1992-1-1 may be used.
Where different conditions apply, they are identified in the relevant clauses.
(2) 2.4.3 (4) also applies to member analysis.
(3) The effects of thermal expansion need not, in general, be taken into account for member analysis.
(4) For verifying standard fire resistance requirements, member analysis is sufficient.
(5) Tabulated data, simplified or general methods given in 4.2, 4.3 and 4.4 respectively are suitable for
verifying members under fire conditions.
The tabulated data method consists of simple checks of dimensions of cross-sections and of axis distances
of the reinforcement. In some cases simple checks of the load level and additional detailing rules are also
required. When the actual steel stress and temperature are known more accurately, the values in the tables
may be modified.
2.4.5 Testing
(1) As an alternative to the use of calculation methods, fire design may be based on the results of tests.
(2) Combinations of testing and calculations may also be used.
© BSI 03-2000 13
ENV 1992-1-2:1995
3 Material properties
3.1 General
(1)P In fire conditions the temperature dependent properties shall be taken into account.
(2) The material properties at 20 °C should be assessed according to ENV 1992-1-1.
(3) Values for the reduction of the characteristic compressive strength of concrete, and of the characteristic
strength of reinforcing and prestressing steels are given in this section. They may be used with the
simplified calculation methods. These values may also be used for the evaluation of the critical temperature
of reinforcement when adapting tabulated data for critical temperatures other than 500 °C (see 4.2.2).
(4) Additional information on thermo-mechanical properties for general calculation methods is given in
Informative Annex A. Reference may also be made to appropriate documents.
(5) The material models given in 3.2 and 3.3 below should only be applied for heating rates similar to those
appearing under standard fire exposure until the time of the maximum temperature.
(6) Alternative formulations of material laws (e.g. for parametric fires) may be applied, provided solutions
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
3.2 Concrete
(1) The reduction of the characteristic compressive strength of concrete as a function of the temperature G
is allowed for by the coefficient kc(G) for which:
fck(G) = kc(G) fck(20 °C) (3.1)
(2) In the absence of more accurate information the following kc(G) values, applicable to concretes with
siliceous aggregates, should be used (see Figure 3.1).
They may be considered as conservative values for other types of concrete.
kc(G) = 1,0 for 20 °C u G u 100 °C
kc(G) = (1 600 – G)/1 500 for 100 °C u G u 400 °C
kc(G) = (900 – G)/625 for 400 °C u G u 900 °C
kc(G) = 0 for 900 °C u G u 1 200 °C
3.3 Steel
(1) The reduction of the characteristic strength of a reinforcing steel as a function of the temperature G is
allowed for by the coefficient ks(G) for which:
fsk(G) = ks(G)fyk(20 °C) (3.2)
(2) The reduction of the characteristic strength of a prestressing steel as a function of the temperature G
is allowed for by the coefficient kp(G) for which:
fpk(G) = kp(G)fpk(20 °C) (3.3)
(3) Where ks(G) and kp(G) are taken from documented data they should be derived from tests performed
under constant stress and variable temperature (transient tests).
(4)In the absence of more accurate information the following ks(G) values should be used for reinforcement
(see Figure 3.2).
14 © BSI 03-2000
ENV 1992-1-2:1995
For tension reinforcement in beams and slabs where ºs,fi W 2 %, the strength reduction may be used as given
below (see Figure 3.2, Curve 1). This corresponds to the values given in the tables in 4.2.
ks(G) = 1,0 for 20 °C u G u 350 °C
ks(G) = (6 650 – 9G)/3 500 for 350 °C u G u 700 °C
ks(G) = (1 200 – G)/5 000 for 700 °C u G u 1 200 °C
For compression reinforcement in columns and compressive zones of beams and slabs the strength
reduction at 0,2 % proof strain should be used as given below (see Figure 3.2, Curve 2). This also applies
for tension reinforcement where ºs,fi < 2 % when using the simplified or general calculation methods.
ks(G) = 1,0 for 20 °C u G u 100 °C
ks(G) = (1 100 – G)/1 000 for 100 °C u G u 400 °C
ks(G) = (8 300 – 12 G)/5 000 for 400 °C u G u 650 °C
ks(G) = (1 200 – G)/5 500 for 650 °C u G u 1 200 °C
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
(5) In the absence of more accurate information the following kp(G) values should be used for prestressing
steel (see Figure 3.3).
For prestressing steel bars:
kp(G) = 1,0 for 20 °C u G u 100 °C
kp(G) = (1 600 – G)/1 500 for 100 °C u G u 250 °C
kp(G) = (700 – G)/500 for 250 °C u G u 650 °C
kp(G) = (1 000 – G)/3 500 for 650 °C u G u 1 000 °C
kp(G) = 0 for 1 000 °C u G u 1 200 °C
Figure 3.1 — Coefficient kc(G) allowing for decrease of compressive strength (fck) of
silicious concrete at elevated temperature
© BSI 03-2000 15
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Figure 3.2 — Coefficient ks(G) allowing for decrease of characteristic strength (fyk) of reinforcing
steels at elevated temperature
Figure 3.3 — Coefficient kp(G) allowing for decrease of characteristic strength (fpk) of
prestressing steels at elevated temperature
16 © BSI 03-2000
ENV 1992-1-2:1995
© BSI 03-2000 17
ENV 1992-1-2:1995
and Ys = 1,15 [see Equation (4.2)] where Ed denotes the design effect of actions according to ENV 1992-1-1.
(4) For prestressing tendons the critical temperature for bars is assumed to be 400 °C and for strands and
wires to be 350 °C. If no special check according to (5) is made in prestressed tensile members, beams and
slabs the required axis distance, a, should be increased by
10 mm for prestressing bars, corresponding to Gcr = 400 °C
15 mm for prestressing wires and strands, corresponding to Gcr = 350 °C.
(5) For tensile and simply supported bending members, except for those with unbonded tendons,
modification of the required axis distance a, given in the Table 4.4, Table 4.5 and Table 4.8, Column 3, for
critical temperatures of reinforcement other than 500 °C may be carried out as follows:
a) evaluate the steel stress Ös,fi for the actions in a fire situation (Ed,fi) using Equation (4.2).
(4.2)
where:
Ys is the partial safety factor for reinforcing steel;
Ys = 1,15 (see 2.3.3.2 of ENV 1992-1-1)
As,req is the area of reinforcement required for ultimate limit
state according to ENV 1992-1-1
As,prov is the area of reinforcement provided
Ed,fi/Ed may be assessed using 2.4.3 (4) and (5).
(6) The above approximation is valid for 350 °C < Gcr < 700 °C. For prestressing steel, Equation (4.2) may
be applied analogously.
For unbonded tendons critical temperatures greater than 350 °C should only be used where more accurate
methods are used to determine the effects of deflections.
(7) For tensile members or beams where the design requires Gcr to be below 400 °C the cross sectional
dimensions should be increased by increasing the minimum width of the tensile member or beam according
to Equation (4.4).
bmod W bmin + 0,8 (400 – Gcr) (mm) (4.4)
18 © BSI 03-2000
ENV 1992-1-2:1995
where bmin is the minimum dimension b given in the Tables, related to the required standard fire
resistance.
An alternative to increasing the width according to Equation (4.4) may be to adjust the axis distance of the
reinforcement in order to obtain the temperature required for the actual stress. This requires using a more
accurate method such as that given in Annex B.
(8) Values given in the Tables provide minimum dimensions for fire resistance in addition to the detailing
rules required by ENV 1992-1-1. Some values of the axis distance of the steel, used in the Tables are less
than that required by ENV 1992-1-1 and should be considered for interpolation only.
(9) Linear interpolation between the values given in the Tables is allowed.
(10) In situations for which the Tables do not apply, reference should be made to appropriate documents.
(11) Symbols used in the tables are defined in Figure 4.1.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Figure 4.1 — Sections through structural members, showing nominal axis distance a,
and nominal concrete cover c to reinforcement
(12) The nominal values of axis distance a to a steel bar, wire or tendon, should not be less than the
minimum values given in the Tables below.
(13) When reinforcement is arranged in several layers similar to Figure 4.2, and where it consists of either
reinforcing or prestressing steel with the same characteristic strength fyk and fpk respectively, the average
axis distance am should not be less than the axis distance a given in the Tables. The average axis distance
may be determined by Equation (4.5).
(4.5)
where:
Asi is the cross sectional area of steel bar (tendon, wire) “i”
ai is the axis distance of steel bar (tendon, wire) “i” from the nearest exposed surface.
When reinforcement consists of steels with different characteristic strength Asi should be replaced
by Asi fyki (or Asi fpki) in Equation (4.5).
© BSI 03-2000 19
ENV 1992-1-2:1995
(14) Where reinforcing and prestressing steel is used simultaneously (e.g. in a partially prestressed
member), the axis distances of the prestressing steel should be introduced in Equation (4.5) as a nominal
value given by:
ai,nom = ai – %ap (4.6)
where:
ai is the actual axis distance of the tendon considered
%ap is an allowance for the different critical temperatures of reinforcing and prestressing steel.
%ap may be assumed as follows:
%ap = 10 mm for prestressing bars
= 15 mm for prestressing wires and strands
(15) The minimum axis distance for any individual bar should not be less than that required for R 30 and
not less than half the average axis distance [see Equation (4.5)].
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
(16) In tensile members, beams and slabs with concrete covers c W|50|mm to the main longitudinal
reinforcement, surface reinforcement should be provided in order to prevent the fall off of the concrete
unless it can be justified, generally by tests, that falling off does not occur within the period of fire
resistance. Where necessary, for the cover to surface reinforcement reference should be made to
ENV 1992-1-1, 4.1.3.3 (6) and (7).
4.2.3 Columns
(1) Fire resistance of reinforced concrete columns may be satisfied by the use of Table 4.1 and the following
rules.
(2) In Table 4.1 a load level in the fire situation Èfi has been introduced accounting for load combinations
and the design column resistance to compression and, possibly, bending, including second order effects.
The effective length lo, is assumed to be equal to the actual column length lcol (notation as in
ENV 1992-1-1, 4.3.5).
Èfi may be taken as|0,7|in all cases. However, a more accurate value may be obtained using Equation (4.7):
Èfi = Ed,fi/Rd,fi(0) = ½fi Ed/Rd,fi(0) (4.7)
where:
½fi = Ed,fi/Ed [see 2.4.3 (4)];
Rd,fi(0) denotes the design resistance calculated according to ENV 1992-1-1 with lo = lcol, YM = 1 and t = 0
(3) For concrete made with calcareous or lightweight aggregate, no reduction of the minimum column
width b [see 4.2.1 (3)] given in Table 4.1 is permitted.
(4) In columns where As W|0,02|Ac, distribution of the bars along the sides of the cross-section is required
for a fire resistance higher than|90|minutes. However, this rule does not apply to lapping zones.
(5) The dimension b in Table 4.1 for columns exposed to fire on one side only (Column 5), applies to columns
which lie flush with wall of the same standard fire resistance or to protruding columns if that part of the
cross-section embedded in the wall is able to carry the whole load. Any opening in the wall should not be
nearer to the column than the minimum dimension b given in Table 4.1, Column 5 for the standard fire
resistance required (see Figure 4.3). Otherwise it should be treated as a column exposed to fire on more
than one side.
20 © BSI 03-2000
ENV 1992-1-2:1995
(6) Where the actual width or diameter b of column is at least 1,2 times the minimum value bmin given
in Table 4.1 the axis distance a may be reduced to a value not less than the nominal cover required by
ENV 1992-1-1. Linear interpolation of the axis distance may be used for values b/bmin between 1 and 1,2.
For such situation 4.2.3 (4) does not apply.
Table 4.1 — Minimum dimensions and axis distances for reinforced
concrete columns; rectangular and circular section
Minimum dimensions (mm)
Column width bmin/axis distance a
Standard fire
resistance Exposed on one
Column exposed on more than one side
side
Èfi = 0,2 Èfi = 0,5 Èfi = 0,7 Èfi = 0,7
1 2 3 4 5
R 30 |150/10| a
|150/10| a
|150/10| a
|100/10|a
R 60 |150/10|a |180/10|a |200/10|a |120/10|a
R 90 |180/10|a |210/10|a |240/35| |140/10|a
R 120 |200/40| |250/40| |280/40| |160/45|
R 180 |240/50| |320/50| |360/50| |200/60|
R 240 |300/50| |400/50| |450/50| |300/60|
a Normally the cover required by ENV 1992-1-1 will control.
4.2.4 Walls
4.2.4.1 Non load-bearing walls (partitions)
(1) Where the fire resistance of a partition is only required to meet the thermal insulation criterion I and
integrity criterion E, the minimum wall thickness should not be less than that given in Table 4.2 below.
Requirements of axis distance may be disregarded.
(2) If calcareous or lightweight aggregates are used the minimum wall thickness given in Table 4.2 may
be reduced by|10 %|.
(3) To avoid excessive thermal deformation and subsequent failure of integrity between wall and slab, the
ratio of clear height of wall lw to wall thickness t should not exceed|40|.
© BSI 03-2000 21
ENV 1992-1-2:1995
1 2
EI 30 |60|
EI 60 |80|
EI 90 |100|
EI 120 |120|
EI 180 |150|
EI 240 |175|
(1) Adequate fire resistance of load-bearing reinforced concrete walls may be assumed if the data given
in Table 4.3 and the following rules are applied.
(2) For plain concrete walls (see ENV 1992-1-6) the minimum wall thickness values given in Table 4.3
may be used.
(3) 4.2.3 (2), (3) and (6) also apply for load-bearing solid walls.
Table 4.3 — Minimum dimensions and axis distances for load-bearing
reinforced concrete walls
Minimum dimensions (mm)
Wall thickness/axis distance for
Standard fire
resistance Èf = 0,35 Èf = 0,7
wall exposed on one wall exposed on two wall exposed on one wall exposed on two
side sides side sides
1 2 3 4 5
REI 30 |100/10|a |120/10|a |120/10|a |120/10|a
REI 60 |110/10|a |120/10|a |130/10|a |140/10|a
REI 90 |120/20|a |140/10|a |140/25| |170/25|
REI 120 |150/25| |160/25| |160/35| |220/35|
REI 180 |180/45| |200/45| |210/55| |300/55|
REI 240 |230/60| |250/60| |270/70| |360/70|
a Normally the cover required by ENV 1992-1-1 will control.
22 © BSI 03-2000
ENV 1992-1-2:1995
a
Normally the cover required by ENV 1992-1-1 will control.
4.2.6 Beams
4.2.6.1 General
(1) Adequate fire resistance of reinforced and prestressed concrete beams may be assumed if the data
given in Table 4.5 to Table 4.7 together with the following rules are used.
(2) The Tables apply to beams which can be exposed to fire on three sides, i.e. the upper side is insulated
by slabs or other elements which continue their insulating function during the whole fire resistance period.
For beams, exposed to fire on all sides, 4.2.6.4 applies.
(3) Values in the Tables are valid for the cross-sections shown in Figure 4.4. Rules (5) to (8) ensure adequate
cross-sectional dimensions to protect the reinforcement.
© BSI 03-2000 23
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Figure 4.5 — I-shaped beam with increasing web width bw satisfying the
requirements of an imaginary cross-section
(6) Where the actual width of the bottom flange b exceeds the limit 1,4 bw, [bw denotes the actual width of
web, see Figure 4.4 (c)], the axis distance to the reinforcing or prestressing steel should be increased to:
(4.9)
where:
deff is given by Equation (4.8)
bmin is the minimum beam width given in Table 4.5.
(7) For flanges with b > 3,5 bw [see (6) above for definitions] 4.2.6.4 applies.
(8) Holes through the webs of beams do not affect the fire resistance provided that the remaining
cross-sectional area of the member in the tensile zone is not less than Ac = 2b2min where bmin is given
by Table 4.5 below.
(9) Higher temperature concentrations occur at the bottom corners of beams. For this reason the axis
distance asd to the side of beam for corner bar (tendon or wire) in the bottom of beams with only one layer
of reinforcement, should be increased by|10| mm for widths of beam up to that given in Column 4 of
Table 4.5 for simply supported beams, and Column 3 of Table 4.6 for continuous beams, for the relevant
standard fire resistance.
4.2.6.2 Simply supported beams
(1) Table 4.5 provides minimum values of axis distance to the soffit and sides of simply supported beams
together with minimum values of the width of beam, for standard fire resistances of R 30 to R 240.
4.2.6.3 Continuous beams
(1) Table 4.6 provides minimum values of axis distance to the soffit and sides of continuous beams together
with minimum values of the width of beam, for standard fire resistance of R 30 to R 240.
(2) Table 4.6 and the following rules apply for beams where the moment redistribution according to
ENV-1992-1-1, 2.5.3.4.2 does not exceed|15 %|. In the absence of a more rigorous calculation and where
the redistribution exceeds|15 %|, or the detailing rules of this Part 1-2 are not followed, each span of a
continuous beam should be assessed using Table 4.5 for simple supported beams.
24 © BSI 03-2000
ENV 1992-1-2:1995
(3) The area of top reinforcement over each intermediate support for standard fire resistance of|R90|and
above, for up to a distance of|0,3|/eff (as defined in ENV 1992-1-1, 2.5.2.2.2) from the centre line of support
should not be less than (see Figure 4.6):
As,req(x) = As,req(0) × (1 – 2,5x/leff) (4.10)
where:
x is the distance from the section considered to the centre line of the support (x u 0,3/eff)
As,req(0) is the area of top reinforcement required over the support, according to ENV 1992-1-1
As,req(x) is the minimum area of top reinforcement required in the section considered but not less than
As(x) required by ENV 1992-1-1.
Where leff varies in the adjacent spans it should be taken as the greater value.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Explanation:
(1) Diagram of bending moments for the actions in a fire situation at t = 0
(2) Envelope line of acting bending moments to be resisted by tensile reinforcement according to ENV 1992-1-1
(3) Diagram of bending moments in fire conditions
(4) Envelope line of resisting bending moments according to Equation (4.10)
Figure 4.6 — Envelope of resisting bending moments over supports in fire conditions
© BSI 03-2000 25
ENV 1992-1-2:1995
Table 4.5 — Minimum dimensions and axis distances for simply supported
beams made with reinforced and prestressed concrete
Minimum dimensions (mm)
Standard fire
resistance Possible combinations of a and bmin where a is the average axis Web thickness
distance and bmin is the width of beam bw
1 2 3 4 5 6
R 30 bmin = |80| |120| |160| |200| |80|
a = |25| |15|a |10|a |10|a
R 60 bmin = |120| |160| |200| |300| |100|
a = |40| |35| |30| |25|
R 90 bmin = |150| |200| |250| |400| |100|
a = |55| |45| |40| |35|
R 120 bmin = |200| |240| |300| |500| |120|
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Table 4.6 — Minimum dimensions and axis distances for continuous beams
made with reinforced and prestressed concrete
Minimum dimensions (mm)
Standard fire
resistance Possible combinations of a and bmin where a is the average axis distance
Web thickness bw
and bmin is the width of beam
1 2 3 4 5
R 30 bmin = |80| |160| |200| |80|
a = |12|a |12|a |12|a
R 60 bmin = |120| |200| |300| |100|
a = |25| |12|a |12|a
R 90 bmin = |150| |250| |400| |100|
a = |35| |25| |25|
R 120 bmin = |220| |300| |500| |120|
a = |45| |35| |35|
R 180 bmin = |380| |400| |600| |140|
a = |60| |60| |50|
R 240 bmin = |480| |500| |700| |160|
a = |70| |70| |60|
asd = a + 10 mm (see note below)
For prestressed beams the increase of axis distance according to 4.2.2(4) should be noted.
asd is the axis distance to the side of beam for the corner bars (tendon or wire) of beams with only one layer of reinforcement.
For values of bmin greater than that given in Column 3 no increase of a is required.
a Normally the cover required by ENV 1992-1-1 will control.
(4) Table 4.6 applies to continuous beams using unbonded tendons only, where additional bonded top
reinforcement over intermediate supports is provided to ensure static equilibrium under fire conditions.
26 © BSI 03-2000
ENV 1992-1-2:1995
(5) The web thickness of I-shaped continuous beams bw [see Figure 4.4 (c)] should not be less than the
minimum value bmin in Table 4.6, Columns 2 to 4, for a distance of 2h from an intermediate support unless
it can be shown that explosive spalling will not occur using Figure A.18.
(6) In order to prevent a concrete compression or shear failure of a continuous beam at the first
intermediate support, the beam width and web thickness should be increased for standard fire
resistances |R 120 – R 240|in accordance with Table 4.7, if both the following conditions exist:
a) no bending resistance is provided at the end support, either by the joint or beam (for the purposes
of this clause ENV 1992-1-1, 5.4.2.1.2 (1) does provide moment resistance when incorporated in a
joint which can transfer moment), and
b) Vsd > 2/3 VRd2 at the first intermediate support, where VRd2 is the design shear resistance of the
compression struts according to ENV 1992-1-1, 4.3.2.
Table 4.7 — Reinforced and prestressed concrete
continuous I-beams; increased beam width and web
thickness for conditions according to 4.2.6.3 (6)
Standard fire Minimum beam width bmin (mm) and web
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Explanation:
(1) Concrete slab
(2) Flooring (non-combustible)
(3) Sound insulation (possibly combustible)
h1 + h2 = hs as given in Table 4.8
Figure 4.7 — Concrete slab with floor finishes
(3) The rules given in 4.2.7.2 and 4.2.7.3 also apply for the flanges of T- or TT-shaped beams.
© BSI 03-2000 27
ENV 1992-1-2:1995
1 2 3 4 5
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
28 © BSI 03-2000
ENV 1992-1-2:1995
Explanation:
(a) Span direction of slab
(b) Large extent of system without cross walls
(c) No rotational restraint provided
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
1 2 3
© BSI 03-2000 29
ENV 1992-1-2:1995
(3) The values in Table 4.10 and Table 4.11 are valid for ribbed slabs subjected to uniformly distributed
loading.
(4) For ribbed slabs with reinforcement placed in several layers, 4.2.6.1 (4) applies.
(5) In continuous ribbed slabs, the top reinforcement should be placed in the upper half of the flange.
(6) Table 4.10 is valid for simply supported, two-way spanning ribbed slabs. It is also valid for two-way
spanning ribbed slabs with at least one restrained edge and standard fire resistances lower than REI 180
where the detailing of the upper reinforcement does not meet the requirements in 4.2.6.3 (3).
Table 4.11 is valid for two-way spanning ribbed slabs with at least one restrained edge. For the detailing
of the upper reinforcement, 4.2.6.3 (3) applies for all standard fire resistances.
Table 4.10 — Minimum dimensions and axis distance for two-way
spanning, simply supported ribbed slabs in reinforced or prestressed
concrete
Minimum dimensions (mm)
Standard Fire
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Resistance Possible combinations of width of ribs bmin and slab thickness hs and
axis distance a axis distance a in span
1 2 3 4 5
REI 30 bmin = |W 80| hs = |80|
a = |15|a a = |10|a
30 © BSI 03-2000
ENV 1992-1-2:1995
Table 4.11 — Minimum dimensions and axis distances for two-way spanning ribbed slabs in
reinforced or prestressed concrete with at least one restrained edge
Minimum dimensions (mm)
Standard Fire
Resistance possible combinations of width of ribs bmin and axis slab thickness hs and axis distance
distance a a in span
1 2 3 4 5
REI 30 bmin = |W 80| hs = |80|
a = |10|a a = |10|a
© BSI 03-2000 31
ENV 1992-1-2:1995
[see Figure 4.9 a), Figure 4.9 b), Figure 4.9 d), Figure 4.9 e) and the web of Figure 4.9 f)]. For any
rectangular part of a member an equivalent wall of thickness 2w is considered for which the thickness az
is calculated. For example the slab in Figure 4.9 c) is related to the equivalent wall in Figure 4.9 d), and
the flange of Figure 4.9 f) is also related to the equivalent wall in Figure 4.9 d), but the web of Figure 4.9 f)
is related to the equivalent wall of Figure 4.9 a).
(4) For the bottom and ends of rectangular members exposed to fire, where the width is less than the height,
the value of az is assumed to be the same as that calculated for the sides [see Figure 4.9 b), Figure 4.9 e)
and Figure 4.9 f)].
(5) The compressive strength and the modulus of elasticity of the reduced concrete cross section are
assumed to be constant and equal to that calculated for the point M. M corresponds to any point in the
middle plane of the equivalent wall.
The thickness az of the damaged zone and the reduced properties of the concrete should be determined
separately for each rectangular part of a cross section. This means that az may be different for the flange
of a T shaped, cross section, from that of the web of the same cross section [see Figure 4.9 f)].
32 © BSI 03-2000
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
The short term value of modulus of elasticity does not take account of the effect of creep or transient strain
(that part of the thermal expansion resisted by compressive stresses). Where second order effects for
columns and walls need to be considered the method given in ENV 1992-1-1 should be used with this value
of the modulus of elasticity and the reduced cross section of this clause. (The value of Ecd(GM) cannot be
derived from Annex A where creep and transient strain are included in the data).
(7) The damaged zone az is estimated for an equivalent wall exposed on both sides as follows:
a) The half thickness of the wall w is divided into n parallel zones of equal thickness, where n W 3
(see Figure 4.10).
b) The temperature is calculated for the middle of each zone.
c) The corresponding reductions kc(Gi) of the compressive strength of the concrete are determined.
© BSI 03-2000 33
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Figure 4.10 — Divisions of a wall, exposed on both sides, into zones for use in calculation of
strength reduction and az values
The reduced compressive strength and the damaged zone z may be estimated by means of Annex B for
a standard fire exposure until the time of maximum gas temperature or by means of the following
procedure.
d) The mean reduction coefficient incorporating a factor (1 – 0,2/n) which allows for the variation in
temperature within each zone, may be calculated using Equation (4.15):
(4.15)
e) The width of damaged zone for beams, slabs and members subjected to in-plane shear may be
calculated using Equation (4.16):
(4.16)
(4.17)
(8) The reinforcement is taken into account with reduced strength and modulus of elasticity according to
the temperature of each bar, even if it is placed outside the reduced cross section, see Annex B.
(9) For compression bars a strain of 0,2 % with the corresponding stress reductions should be applied. For
bars in tension an increased stress as an effect of a larger strain may be taken into account. The reduction
of the modulus of elasticity of a bar may be assessed as equal to the reduction of the 0,2 % stress of the bar.
(10) Beams and slabs might become over-reinforced. For the analysis of this, the short term value of ¼cu,max
may be assessed as
¼cu,max = 0,0035/kc(GM) (4.18)
34 © BSI 03-2000
ENV 1992-1-2:1995
where
ºth is the thermal strain,
ºload is the instantaneous stress-dependent strain
ºcreep is the creep strain and
ºtr is the transient strain
© BSI 03-2000 35
ENV 1992-1-2:1995
During fire exposure the creep strain may be disregarded; its contribution may only be significant for
calculation of deflections after a fire.
(6) For practical calculations, deformations and indirect actions in hyperstatic structures during fire may
be assessed by means of imposed strains (mean axis elongation and curvature) estimated on the basis of
appropriate documents (see for example Annex D).
(7) The load bearing capacity of individual members, sub-assemblies or entire structures exposed to fire
may be assessed by plastic methods of analysis (ref. ENV 1992-1-1, 2.5.3).
(8) The plastic rotation capacity of reinforced concrete sections should be estimated in account of the
increased ultimate strains ºcu and ºsu in hot condition. ºcu will also be affected by the confinement
reinforcement provided.
(9) The compressed zone of a section, especially if directly exposed to fire (e.g. negative bending in
continuous beams), should be checked and detailed with particular regard to spalling or falling-off of
concrete cover.
(10) In the analysis of individual members or sub-assemblies the boundary conditions should be checked
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
and detailed in order to avoid failure due to the loss of adequate support to the members.
4.4.4 Validation of general calculation methods
(1)P The validity of the general calculation methods shall be verified by the following procedures:
a) justification of the design assumptions shall be made on basis of relevant test results.
b) sensitivity analysis of the effect of the critical parameters shall be performed.
4.6 Anchorage
(1) Where necessary for fire purposes the anchorage capacity may be calculated according to
ENV 1992-1-1 using reduced temperature related material properties [see 3.1 (4)].
36 © BSI 03-2000
ENV 1992-1-2:1995
5 Protective layers
(1)P Required fire resistance can be obtained by the application of protective layers.
(2) The properties and performance of the insulation material to be used for protective layers should be
assessed using appropriate test procedure.
(3) The test procedure should confirm that the material remains coherent and cohesive for all foreseen
temperatures and deformations. It should provide information concerning
— temperature at the relevant depths of the concrete cross-section related to the fire duration, protective
material and layer thickness, or
— where possible equivalent concrete thickness, related to the fire duration, or
— thermal material properties related to the temperature.
A further alternative is to provide a thermal analyses in accordance with the general calculation method
given in 4.4.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
© BSI 03-2000 37
ENV 1992-1-2:1995
Annex A (informative)
Additional information on material properties
A.1 Strength and deformation properties of concrete
(1) The strength and deformation properties of uniaxial stressed concrete at elevated temperatures are
characterized by a set of stress-strain relationships with a shape as specified in Figure A.2.
(2) For a given concrete temperature, the stress-strain curves are defined by two parameters:
— the compressive strength fc(G)
— the strain ºc1(G) corresponding to fc(G).
(3) Values for each of these parameters are given in Table A.1 as a function of the concrete temperatures.
For intermediate values of the temperature, linear interpolation is permitted.
(4) A graphical display of the two parameters of Table A.1 is given as a function of the concrete
temperatures in Figure A.3. Further illustration of the stress-strain relationships at various temperatures
is given in Figure A.4.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
(5) The values given in Table A.1 are recommended values. Due to various ways of testing specimens, ºc1(G)
shows considerable scatter, which is presented in Table A.2. Recommended values for ºcu(G) defining the
range of the descending branch are also presented.
(6) The stress-s train relationships include in an approximate way the effect of high temperature creep.
(7) In case of natural fire simulation, particularly when considering the decreasing temperature branch,
the material model given here has to be modified.
(8) In all situations the ultimate tensile strength of concrete may be assumed to be zero, which is on the
safe side. If it is necessary to take account of the tensile strength, when using the simplified or general
method of calculation, Figure A.1 may be used.
Figure A.1 — Coefficient kct(G) allowing for decrease of tensile strength, (fctk) of
concrete at elevated temperature
38 © BSI 03-2000
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Range I
© BSI 03-2000 39
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
40 © BSI 03-2000
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
© BSI 03-2000 41
ENV 1992-1-2:1995
Range I elastic
Range II
non-linear
Figure A.5 — Model for stress-strain relationships of reinforcing and prestressing steels
at elevated temperatures (notations for prestressing steels “p” instead of “s”)
42 © BSI 03-2000
ENV 1992-1-2:1995
(2) For a given steel temperature, the stress-strain curves of Figure A.5 are defined by three parameters:
— the slope of the linear elastic range E s ( G ) , Ep ( G ) for reinforcement and prestressing steels
respectively,
— the proportional limit Öspr(G), Öppr(G) respectively and
— the maximum stress level fy(G), fpy(G) respectively.
Values for each of the above parameters are given as a function of the steel temperature for various types
of reinforcing and prestressing steels in Table A.3 – Table A.6.
Table A.3 — Values for the parameters of the
stress-strain relationship of hot rolled reinforcing steel
E (G)
s Ö spr (G) f (G)
y
Steel Temperature (°C) ----------------------
- ------------------------
- ------------------------
-
E s ( 20 °C ) f 0,2 ( 20 °C ) f 0,2 ( 20 °C )
© BSI 03-2000 43
ENV 1992-1-2:1995
(3) A graphical display of the parameters of Table A.3 – Table A.6 is given in Figure A.7, Figure A.9,
Figure A.11 and Figure A.13. Further illustration of the stress-strain relationships at various
temperatures is given in Figure A.6, Figure A.8, Figure A.10 and Figure A.12.
44 © BSI 03-2000
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
© BSI 03-2000 45
ENV 1992-1-2:1995
46 © BSI 03-2000
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
© BSI 03-2000 47
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
48 © BSI 03-2000
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
© BSI 03-2000 49
ENV 1992-1-2:1995
where:
lc is the length at room temperature
%lc is the temperature induced elongation
G is the concrete temperature (°C)
The above equations are presented graphically in Figure A.14 below.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
50 © BSI 03-2000
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
(3) The thermal conductivity Æc of concrete may be calculated according to Equations (A.8) to (A.11):
Concrete with siliceous aggregates:
for 20 °C < G u 1 200 °C
Æc = 2 – 0,24 G/120 + 0,012(G/120)2 (W/Mk) (A.8)
Concrete with calcareous aggregates:
for 20 °C < Gc u 1 200 °C
2c = 1,6 – 0,16 G/120 + 0,008(G/120)2 (W/Mk) (A.9)
Concrete with lightweight aggregates:
for 20 °C < G u 800 °C
2c = 1,0 – G/1 600 (W/Mk) (A.10)
for 800 °C < G u 1 200°
2c = 0,5 (W/Mk) (A.11)
© BSI 03-2000 51
ENV 1992-1-2:1995
If only an approximate answer is required (simple calculation, estimation), the thermal conductivity may
be considered as independent of the concrete temperature:
Æc = 1,60 W/Mk for concrete with siliceous aggregates
Æc = 1,30 W/Mk for concrete with calcareous aggregates
Æc = 0,80 W/Mk for concrete with lightweight aggregates
(4) The density Ôc of unreinforced concrete may be considered as independent of the concrete temperature
and may be evaluated according to ENV 1992-1-2.
For thermal response models the value Ôc = 2 300 kg/m3 may be adopted for normal dense concrete
(siliceous or calcareous).
The density may also be reduced by 100 kg/m3 after having reached 100 °C, due to the evaporation of free
water.
(5) The moisture content of concrete may be taken equal to the equilibrium moisture content. If these data
are not available, moisture content may be considered u 2 % of the concrete weight.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
A high moisture content delays the heating up of concrete, but increases the risk of spalling.
(6) If only an approximate answer is required (simple calculation, estimation), the thermal diffusivity of
concrete ac (m2/s) may be used.
It may be considered as independent of the concrete temperature:
ac = 0,69 × 10– 6 m2/s for concrete with siliceous aggregates
ac = 0,56 × 10– 6 m2/s for concrete with calcareous aggregates
dependent on the density for lightweight concrete.
A.3.2 Steel (reinforcing and prestressing)
(1) The thermal elongation %l/l of steel may be adopted according to Equations (A.11) – (A.15).
reinforcing steel:
for 20 °C < G u 750 °C
(%l/l)s = (– 2,416 × 10–4) + (1,2 × 10–5G) + (0,4 × 10–8 G2) (A.12)
for 750 °C < G u 860 °C
(%l/l)s = 11 × 10–3 (A.13)
for G W 860 °C
(%l/l)s = (– 6,2 × 10–3) + (2 × 10–5 G) (A.14)
prestressing steel:
for 20 °C < G u 1 200 °C
(%l/l)p = (– 2,016 × 10–4) + 10–5 G + (0,4 × 10–8 G2) (A.15)
where:
ls, lp is the length at room temperature
%ls, %lp is the temperature induced elongation (see Figure A.17)
G is the steel temperature (°C)
52 © BSI 03-2000
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
If only an approximate answer is required (simple calculation, estimation), the coefficient of thermal
elongation may be used and considered as independent of the steel temperature:
(%l/l)s = 14 × 10–6 G for reinforcing steels
(%l/l)p = 12 × 10 G
–6
for prestressing steels
(2) The density Ôs of reinforcing and prestressing steel should be considered as independent from the steel
temperature:
Ôs = 7 850 kg/m3
(3) Normally in both reinforced and prestressed concrete members, the thermal properties Æs, cs, and as, of
steel may be ignored since the influence of the reinforcement on the temperature rise of the cross-section
is of little importance.
A.4 Spalling
(1) Normally explosive spalling is unlikely to occur where the smaller of the cross section dimensions h or
b in the compressive zones of beams, slabs, walls and columns satisfy the conditions given in Figure A.18.
The compressive stress Öc,fi may be calculated for the combination of actions in the fire situation using the
cross section required by ENV 1992-1-1.
© BSI 03-2000 53
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Annex B (informative)
Temperature profiles and reduced cross section
B.1 Temperature profiles
(1) Figure B.1 and Figure B.2 provide temperature profiles for beams and slabs. These are conservative
values and are intended for use in determining the temperature of reinforcing bars and prestressing
tendons.
B.2 Cross section and concrete strength
(1) Figure B.3 provides curves which give values of the reduction in concrete compressive strength and
cross section with respect to the thickness of section.
(2) The thickness of section w is assessed as follows:
— For slabs: w = h
— For beams: w = " bw
— For columns or walls exposed on one side only: w = width of wall or column
— For columns or walls exposed on two sides: w = " × width of wall or column
— For columns exposed on four sides: w = " × the smaller section dimension
(3) The reduction in cross section az is described in 4.3.3, see Figure 4.9.
(4) The reduction in strength kc(GM) is defined in 3.2.
54 © BSI 03-2000
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
© BSI 03-2000
Figure B.1 — Temperature profiles for beams
55
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
56
ENV 1992-1-2:1995
© BSI 03-2000
ENV 1992-1-2:1995
w is assessed as:
© BSI 03-2000 57
ENV 1992-1-2:1995
Annex C (informative)
Simplified method of calculation for beams and slabs
C.1 General
(1) This simplified method of calculation provides an extension to the use of the tabular method for beams
exposed on three sides and slabs, Table 4.4 to Table 4.8. It determines the affect on bending resistance for
situations where the axis distance, a, to bottom reinforcement is less than that required by the tables.
The minimum cross-section dimensions (b, bw, hs) given in Table 4.4 to Table 4.7 should not be reduced.
This method uses strength reduction factors based on Curve 1 of Figure 3.2 for reinforcing steels
and Figure 3.3 for prestressing steels.
(2) This simplified method may be used to justify reducing the axis distance a. Otherwise the rules given
in 4.2.6.1 to 4.2.6.3 should be followed. This method is not valid for continuous beams where, in the areas
of negative moment, the width b or bw is less than 200 mm and the height hs is less than 2b, where b is the
value given in Column 3 of Table 4.4.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
(2) The loading under fire conditions Fd,fi (kN) may be determined using Equation (2.5).
(3) The maximum fire design moment MSd,fi for predominantly uniformly distributed load may be calculated
using Equation (C.2).
MSd,fi = Fd,fileff/8 (C.2)
where:
Ys is the partial material factor for steel used in ENV 1992-1-1, (normally taken to be 1,15)
Ys,fi is the partial material factor for steel under fire conditions (normally taken to be 1,0)
ks(G) is the strength reduction factor of the steel for the given temperature G under the required fire
resistance. G may be taken from Figure B.1 and Figure B.2 for the chosen axis distance
MSd is the applied moment for cold design to ENV 1992-1-1
As,prov is the area of tensile steel provided
As,req is the area of tensile steel required for cold design by ENV 1992-1-1
As,prov/As,req should not be taken as greater than 1,3.
C.3 Continuous beams and slabs
(1) Static equilibrium of flexural moments and shear forces should be ensured for the full length of
continuous beams and slabs under the design fire conditions.
(2) In order to satisfy equilibrium of fire design, moment redistribution from the span to the supports is
permitted where sufficient area of reinforcement is provided over the supports to take the design fire
loading. This reinforcement should extend a sufficient distance into the span to ensure a safe bending
moment envelope.
(3) The moment of resistance MRdSpan,fi of the section at the position of maximum sagging moment should
be calculated for fire conditions in accordance with C.2 (4). The maximum free bending moment for applied
loads in the fire situation (Fd,fi leff/8 for uniformly distributed load) should be fitted to this moment of
resistance MRdSpan,fi such that the support moments MRd1,fi and MRd2,fi provide equilibrium as shown
in Figure C.1. This may be carried out by choosing the moment to be supported at one end as equal to or
less than the moment of resistance at that support [calculated using Equation (C.4)], and then calculating
the moment required at the other support.
58 © BSI 03-2000
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Figure C.1 — Positioning the free bending moment diagram MSd,fi to establish equilibrium
(4) In the absence of more rigorous calculations, the moment of resistance at supports for design for the fire
situation may be calculated using Equation (C.4).
MRd,fi = (Ys/Ys,fi) MSd (As,prov/As,req) (d – a)/d (C.4)
where
Ys, MSd, Ys, Ys,fi, As,prov and As,req are defined in C.2
a is the required average axis distance given in Table 4.5 for beams and Table 4.8, Column 3 for slabs,
d is the effective depth of section
As,prov/As,req should not be taken as greater than 1,3.
(5) Equation (C.4) is valid where the temperature of the top steel over the supports does not exceed 350 °C
for reinforcing bars nor 100 °C for prestressing tendons.
For higher temperatures MRd,fi should be reduced by ks(G) according to Figure 3.2, curve 1, for reinforcing
bars, and by kp(G) according to Figure 3.3 for prestressing tendons.
(6) The curtailment length lbnet,fi required under fire conditions should be checked. This may be calculated
using Equation (C.5).
lbnet,fi = (Ys/Ys,fi) (Yc,fi/Yc) lbnet (C.5)
Annex D (informative)
A procedure for assessing the structural response of reinforced concrete
elements under fire
D.1 General
(1) This step by step procedure describes a method for assessing the structural response of reinforced
concrete structures composed of typical elements (beams, columns, slabs and walls) under fire condition,
by means of simple methods of statics.
(2) The effective thermal strain profiles and the consequent behaviour under fire may be estimated with
good approximation, in spite of the uncertainties and the inaccuracy of the physical model used.
D.2 Rules for application
(1) For appropriately chosen durations of the given fire, or corresponding steps of %G (eg. 50 °C or
even 100 °C), the development of surface temperatures on the exposed surfaces and the “temperatures
profiles” of the concrete elements should be determined (see Figure D.1).
© BSI 03-2000 59
ENV 1992-1-2:1995
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
(2) For each temperature level, determine the modified elastic modulus Ec(Gm) and elongation (%/(Gm/l)c of
concrete (see Annex A).
(3) Assume that the structural element is composed of independent longitudinal fibres (layers), known as
thermo-elements, which are free to move axially. Under fire conditions the temperature profiles induce
thermal elongations which are not distributed linearly, so that sections do not remain plane
(see Figure D.2).
60 © BSI 03-2000
ENV 1992-1-2:1995
(4) The equivalent action effects N(G) and M(G) are then determined by applying a hypothetical stress Ö(G)
to each layer, sufficient to cause an equal and opposite strain to its thermal strain. The forces from each
layer are summed over the height of the section to give N(G), e and hence M(G) (see Figure D.3).
(D.1)
(D.2)
where:
Ec(G) and (%l(G)/l)c are defined in D.2 (see also Annex A),
h is the height of the cross section,
y is the distance of a thermo-element from the element axis and
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
y1, and y2 are the distances of the upper and lower thermo-elements from the member axis.
(5) The residual internal stresses are found by combining the hypothetical stresses Ö(G) and the stresses
due to N(G) and M(G), as shown in Figure D.4.
(6) The effective imposed strains are equal to the sum of the thermal strains of the thermo-elements
(see Figure D.2) and the mechanical strains due to the final internal stresses (see Figure D.4).
Hence:
a) The mean axial strain imposed on the cross-section is given by the expression:
(D.3)
© BSI 03-2000 61
ENV 1992-1-2:1995
b) The curvature, i.e. the mean strain gradient imposed on the cross-section is given by the expression:
(D.4)
where:
Ac is the area of the cross-section,
lc is the moment of inertia of the cross-section, subscripts 1 and 2 refer respectively to the upper and
lower fibre of the cross-section.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
(7) If the member is axially unrestrained (i.e. free to expand) the mean axial strain imposed on the
cross-section [Equation (D.3)] will result in an overall axial deformation.
If the member is free to rotate the mean strain gradient imposed on the cross-section [Equation (D.4)]
will result in an overall curvature of the section.
The resulting axial elongations, rotations and deflections of such unrestrained building elements do not
produce any further external forces.
(8) In the general case of statically indeterminate structural elements or sub-assemblies, the mean strains
and curvatures developed under elevated temperatures, lead to a modification of axial deformations,
deflections and rotations, as well as to redistribution of action-effects.
The relevant analysis can be carried out by means of conventional methods of statics, based on
moment/curvature and axial-force/elongation diagrams of selected cross-sections for a given temperature
profile. Such diagrams provide all the necessary values of (variable) stiffness for every situation and
corresponding level of action-effects.
(9) It is also possible to evaluate the safety margin (against flexural or shear failure) and the ductility at
critical sections of structural elements. In order to do this, the properties of concrete, steel and their bond
characteristics should be modified to take account of the corresponding internal temperature levels.
D.3 Possible further simplifications
(1) In order to overcome the laborious procedure of setting up thermo-elements and calculating the internal
stresses, practical diagrams may be used to obtain an approximate estimation of the effective thermal
deformations (mean elongation and curvature) assuming sections remain plane under fire conditions.
62 © BSI 03-2000
ENV 1992-1-2:1995
(2) For certain shapes and dimensions of typical cross-sections, practical diagrams may be prepared using
an equivalent linear temperature distribution Geff at the exposed faces of the considered cross-section,
instead of the actual temperature distribution Gact. An example of such a practical diagram is given
in Figure D.5. This is only valid for cross-sections similar to those shown. Using such diagrams, the
redistribution of action-effects and the modification of deformations of reinforced concrete elements during
fire may be analyzed using normal loads with effective imposed deformations.
(D.5)
(D.6)
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Figure D.5 — Equivalent temperature values Geff for typical reinforced concrete
sections exposed to a standard fire
© BSI 03-2000 63
DD ENV
1992-1-2:1996
BSI — British Standards Institution
BSI is the independent national body responsible for preparing
British Standards. It presents the UK view on standards in Europe and at the
international level. It is incorporated by Royal Charter.
Revisions
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: 020 8996 9000. Fax: 020 8996 7400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Licensed Copy: Sheffield University, University of Sheffield, 17 July 2003, Uncontrolled Copy, (c) BSI
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001.
Information on standards
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means – electronic, photocopying, recording or otherwise – without prior written
permission from BSI.
This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.