Professional Documents
Culture Documents
+++design of Hydropower Plants 2014
+++design of Hydropower Plants 2014
D := 2.112 m;
Q := 22.5 m3/s;
36 7
L := 2189 m; 34
U := Q/A(d) = 6.42 m/s; 32
Re := U*d/ν =13430041;
6
30
ε = 0.6*0.001 m; (n = 0.012sm-1/3); 28
26 5
J = 0.015; 24
∆H := J*L = 32.3 m; 22
∆H /1418=0.023 20
4
U [m/s]
H [m]
18
16
If Q = 6.75, ∆H := J*L = 2.93 m; ∆H /1418=0.0021
3
14
12
10 2
8
6
1
4
2
0 0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Q [mc/s]
weir
Pressure pipe or
penstock
intake
Ecological
flow release Power house
Tunnel
(galleria)
dam
Powerhouse
(centrale)
surge chamber
(pozzo piezometrico)
penstock
powerhouse
Head :1211-1290 m;
Q: 9.16-10.35 mc/s;
P: 140 MW
•Depending on the type of turbine, H0 can be totally converted into kinetic energy (turbina ad azione) or partitioned
between pressure related energy and kinetic energy (turbina a reazione)
•However, in S.Fiorano, the turbine max output is MW 2x140 = 280, with Q =22.5 cm/s. Accordingly the operative
condition (LJ = 35 m; 2.5% of 1418 m !) is far away from the theoretical condition (LJ = 472 m !). The same happens
in other hydropower plants where LJ is usually below 10%. Why ?
•A first hydraulic observation could be that in S.Fiorano, due to the plant layout, such an high Q would imply
underpressures in the penstock, but this is not a general explanation for other cases.
( )
yearly production for 1000 hours of
C = L ω0 + ω1 D 2
both the amount of material needed
peak functioning as a
to produce the pipe and the volume
function of D
of the trench rise with D2
Other constraints for D comes from:
•upper constraint: resistence to pressure in steady state condition (e.g., Mariotte’s equation) s = pD / 2σ
•Lower constraint: constraint on max V, according to water hammer theory
In a Pelton turbine, used in most high head run of river plants, H0 is totally converted into kinetic energy. In the range
of variation of Q, V is slightly affected by the adjustable noozle regulation.
Considering S. Fiorano:
Yu -JL <H0 <Yu
1385.7 m <H0 <1418 m
The nozzle (iniettore) area, a, at full opening condition is set on the basis of the maximum discharge
• Depending on the availability of the resource and the purpose of the exploitation, different
water capturing structures may be present
• In all this cases spillways (sfioratori, luci) are present in order to controll overflow (dams)
and guarantee unaltered tailwater levels during floods.
• The weir in itself can be regarded as a spillway so that the two terms are often
interchangeable.
• Often spillways have mobile devices (gated spillways) by which they can actively control
the water level upstream.
• with the exception of the simplest cases, the stage - discharge relationship should be
determined experimentally or by a physical models
Weir / Spillways
Purpose: to divert the required amount of water into a power canal or into a penstock
Constraint: minimum possible head losses and environmental impact. Sometimes a fish ladder is required; always
an ecological-flow release device.
Challenges: handling debris and sediment transport. Minimize the effects of ice formation
Position: The best disposition of the intake is with the screen at right angles to the spillway so that the flow pushes
away the debris. If sediment transport is present, the intake should not be located in an area of still water as well as
on a river bend, in order to prevent sedimentation related problems.
Additional equipment:the intake should be equipped with a trashrack and a settling basin where the flow velocity is
reduced, to remove all particles over 0.2 mm (when possible). There must be a sluicing system to flush the
deposited silt, sand, gravel and pebbles with a minimum of water loss; and a spillway to divert the excess water with
respect to the maximum discharge that can be handled downstream.
Types of intakes
Power intake: supplies water directly to the turbine via a penstock. These intakes
are usually encountered in lakes and reservoirs, i.e., where sediment and debris are not a problem
Conveyance intake (lateral, frontal and drop intakes) The intake supplies water to other waterways (power canal,
flume, tunnel, etc.) that usually end in a power intake.These are most frequently encountered along waterways and
generally transfer the water as free surface flow.
It is important to
prevent the risk of
vortex formation
at their entrance
and thus the
formation of air
pockets within the
flow
Lateral intake
Saviore
dell’Adamello
(2)
πD 3 1 wD πD 2 2
= g (ρ s − ρ )
dw
m − ρC D ( ) w
dt 6 2 υ 4
8 g (ρ s − ρ ) wD 2
D = CD ( )w
6 ρ υ
D and Q are given;
L and U are design
parameters to be found,
as a function of w;
w is found by solving
the equation above.
Electricity prices at peak hours can be substantially higher than in off-peak hours, hence the interest in providing an
extended pound, large enough to store the water necessary to operate, at maximum during peak hours. To evaluate
this volume:
V = 3600t p (Q p − Qr )
Provided that this volume must be refilled in off-peak hours, we have the constraint:
In the design of small hydro plants care must be taken to minimise head losses because they can be of great importance
to the feasibility of the project. For large plants, although small in relative terms, can be economically very significative.
Accordingly in any case care must be taken in order to:
· minimise flow separation
· distribute flow uniformly on the cross section
· suppress vortex generation
· choose an appropriate trashrack design
Rule of thumb: at the trashrack 0.8 < U < 1 m/s (this dictates
the dimensions of the rectangular section upstream).
In the penstock 3 < U < 5 m/s (this dictates the penstock
diameter).
For a well designed low head intake structure like the one
on the right the head loss can be as low as
U2
∆H = 0.19
2g
where U is the velocity in the penstock
Where D is the penstock diameter in m, U the velocity within it and g the acceleration due to gravity.
Alternatively
ht ≥ 1,474 U 0,48 D 0,76 [Rohan]
ht ≥ c U D0,50 [Gordon]
Where c is a factor that takes into account the simmetry of the approaching flow
c=0,7245 for asymettric flow
c=0,5434 for symmetric flow
According to experience the velocity V at the entrance of the rack should be between 0.25 m/s and 1.0
m/s. In order to obtain this velocity, the required trash rack area S is estimated by the formula derived by the continuity
equation
b
K1( Vsen( α ))φS = Q ; φ=
b+t
where S is the area of the trash rack in m2, t the bar thickness, b the distance between bars, Q the
discharge (m3/s) and K1 is a trash cleaning coefficient which, if the trash rack
has an automatic cleaner, is equal to 0.80. α = angle of bar inclination (°).
The head loss caused by the trash rack can be calculated by a formula developed by Kirschmer:
4/3
t V 2
∆H = K S sen(α )
b 2g
Where Ks = screen loss coefficient (see on the right)
For instance:
Let us consider a trash rack inclined 60° with the horizontal,
made of stainless steel flat bars 12 mm thick and the width
between bars is 70 mm. Q is 3 m3/s
First we estimate the area S; if we ask for V = 1 m/s, we get S = 5.07 m2; rounding to 6 m2 we get V = 0.84 m/s. Accordingly,
if we use Ks = 2.4 we get ∆h := 0.007 m.
If the grill is not perpendicular but makes an angle β with the water flow (β will have a maximum value of 90° for a grill
located in the sidewall of a canal), there will be an additional head loss. The result of previous head loss should be
multiplied by a correction factor provided in the following table (according to Mosonyi)
Sudden Contraction in the transition between two pipes where d downstream < D upstream
d 2 V22 d
∆H = 0.421 − 2 < 0.76
D 2g D
Sudden Expansion in the transition between two pipes (Borda’s loss; where D downstream > d upstream)
2
V22 D22
∆H =
1
(V1 − V2 ) = 2 − 1
2
2g 2 g d1
M. Pilotti - lectures of Environmental Hydraulics
HYDROPOWER PLANTS: Head loss in a bend
ε V
2
r
∆H = ξ ( , θ , )
D D 2g
In a bend, pipe flow experiences increase of
pressure along the outer wall and a decrease
of pressure along the inner wall. This
pressure unbalance causes a secondary
current. Both movements together - the
longitudinal flow and the secondary current -
produces a spiral flow that, at a length of
around 100 diameters, is dissipated by
viscous friction. The head loss produced in
these circumstances depends on the radius of
the bend and on the diameter of the pipe.
Furthermore, in view of the secondary
circulation, there is a secondary friction loss,
dependent of the relative roughness e/D.
V2
∆H = k
2g
Z3 20 1.0985
pipe
D ε ε/ D A L L/D Q U Re λ U 2 /(2g) J JL
[m]
1.5 0.0005 0.000333 1.767146 108 72 3 1.698 2521266 0.01561 0.146945 0.0015 0.1652
1.2 0.0005 0.000417 1.130973 65 54.17 3 2.653 3151583 0.01627 0.358752 0.0049 0.3162
Total 0.4813
Head loss in trashrack 0.007 m
pipe entrance 0.073 m
I bend (ξ=0.06) 0.009 m
D contraction 0.054 m
II bend (ξ=0.1) 0.036 m
III bend (ξ=0.13) 0.047 m
Conclusions:
•The percentage head loss is reasonable and rather small (1% of the gross head)
•In relative terms, if the pipe length is small, local head losses may be significative
•For instance, supposing 7200 hours/year of functioning, the head loss at the trashrack implies an
yearly energy loss of 1483 kWh (9806*3*0.007/1000*7200) ≅ 190 euro/year (if 1kWh = 0.13 euro)
D r r r r r r r r r
( ∫ ( x − x0 ) ∧ ρVdW ) = ∫ ( x − x0 ) ∧ ρgdW + ∫ ( x − x0 ) ∧ σ n dS
Dt W W S
∂ r r r r r r r r r r r r r r
( ∫ ( x − x0 ) ∧ ρVdW ) − ∫ ( x − x0 ) ∧ ( ρV )V ⋅ ndS = ∫ ( x − x0 ) ∧ ρgdW + ∫ ( x − x0 ) ∧ σ n dS
∂t W S W S
r r r r r r r r
− ∫ ( x − x0 ) ∧ ( ρV )V ⋅ ndS = ∫ ( x − x0 ) ∧ σ n dS
S S
RρQV at position 1
r r r r r
∫ ( x − x0 ) ∧ (ρV )V ⋅ ndS
S
Torque of Momentum Rρ
Q
[ωR − (V − ωR) cosϑ ]
of entering jets (at 1, 2
2
and 3) at position 2 and 3
M = RρQV − 2Rρ
Q
[ωR − (V − ωR) cosϑ ]
2
M = RρQ(V − ωR)(1 + cosϑ )
P = Mω = RρQ(V − ωR)(1 + cosϑ )ω
V V
ω1 = 0; ω2 = ; ωmax =
R 2R
nominal speed V2
Accordingly, if θ =0 Pmax = γQH = ρQ
2
V2 V2
Which actually corresponds to the power of the entering jet P = γQH = γQ = ρQ
2g 2
P V2
Which is, per unit weight: =
γQ 2 g
And to the exit velocity V V
va = [ωmax R − (V − ωmax R)] = − (V − ) = 0
r
2 2
The runaway speed of a Pelton turbine is about 1.8 to 1.9 times the nominal speed. At runaway speed the
runner turns at almost the speed of the water jet, the water is no more able to transfer energy to the rotor.
U U 2π
ω= = →ω = n →n
2R D 60
4) And eventually one chooses the number of poles Zp on the generator
nZ p
50 =
60
That must be an integer value.
Note that ωD is a constant for a given head.
The desired value of ω can be obtained by changing the number of jets, that modify d and then B and D.
The desired D can be obtained by changing ω
Another possibility is not to run the turbine at the optimal speed. for a given D the speed of the runner may be
considerably different from the optimal speed, without having a too large influence on the efficiency of the
turbine and thus allowing the manufacturer to have a series of standardised sizes of diameters D.
100
90
80
60
50
40
30
20
10
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Frazioni della portata m assim a
The efficiency is high for a very wide range of discharge variation. However The efficiency of small Pelton turbines is
normally not as high as with larger turbines. In such a case, it is recommended to calculate the turbine parameters
with an efficiency of 0.70 to 0.85. This may result in an efficiency of 0.5 to 0.6 for an installation with an electrical
generator
M. Pilotti - lectures of Environmental Hydraulics
SMALL HYDROPOWER PLANTS: range of application of micro-Pelton turbines
limit set by
dynamic and
hydraulic forces on
the buckets, torque
on the shaft
10 m, limit set by
small discharge and
power output, large
dimensions of
wheel and low ω
noozle
counter-jet
deflector
(tegolo deviatore)
3 4
7 8
5) channel for cobbles and gravel settling, looking downstream 6) flat gates at junction between 6) and 8)
7) junction between 5) and 8). On the right the 2 sediment flushing gates 8) power channel to the powerhouse
9 10
11
Francis Turbine
In reaction turbines the pressure of water
exerts a force on the face of the runner
blades, and pressure decreases as it
proceeds through the turbine.
The turbine casing or housing (called
“scroll”), with the runner fully immersed in
water, must be strong enough to withstand
the operating pressure. Francis and Kaplan
turbines belong to this category.
In the following we shall present some
fundamentals of the functioning of a Francis
turbine
r r r r r
∫ ( x − x0 ) ∧ (ρV )V ⋅ ndS
S
Torque of Momentum
of entering flow (at 1 and flowing out at 2)
M = ρQR1 ∧ V1 − ρQR2 ∧ V2
= ρQR1V1 cosα1 − ρQR2V2 cosα 2
P = Mω = ρQR1ωV1 cosα1 − ρQR2ωV2 cosα 2
= ρQ(u1V1 cosα1 − u2V2 cosα 2 )
Ideal situation: α1=0 (but Q=0 !) α2=90° which can be obtained only for
the nominal discharge by suitable shaping of the runner blades.
M. Pilotti - lectures of Environmental Hydraulics
SMALL HYDROPOWER PLANTS: Francis turbines
Approximating efficiency curve for a Francis turbine
The maximum efficiency is higher than the one of a Pelton turbine, but only for a very narrow range of discharges