You are on page 1of 2883

Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report

Amman - Jordan NOVEMBER 2018

RCHR-G-FD-CLC-P4-ME-01 R01 Page 1 of 47

Mechanical Calculation Report


RCHR-G-FD-CLC-P4-ME-01 R01
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

Table of Contents 2.4 Fuel Tanks ........................................................................................................................................... 30


3 Water Features & Pools ............................................................................................................................. 31
1 Hotel Building .............................................................................................................................................. 4
3.1 Introduction ........................................................................................................................................ 31
1.1 Cooling and Heating Load ...................................................................................................................... 4
3.2 Scope of Work ..................................................................................................................................... 31
1.2 Smoke Management and Pressurization................................................................................................ 4
3.3 Standards & Code ............................................................................................................................... 31
1.2.1 Fireman Core (Staircase, elevator and lobby) Pressurization .......................................................... 4
3.4 Design Data ......................................................................................................................................... 32
1.2.2 Escape Core (Staircase and lobby) Pressurization ........................................................................... 8
3.5 Filtration & Treatment Systems Description ........................................................................................ 32
1.2.3 Refuge Area Pressurization .......................................................................................................... 11
3.6 Preliminary Calculation / Selection Notes ............................................................................................ 33
1.2.4 Parking Ventilation ...................................................................................................................... 12
1.2.5 Cellar-1 Floor Smoke Management .............................................................................................. 12
1.2.6 Ground Floor Smoke Management .............................................................................................. 14
1.2.7 First Floor Smoke Management ................................................................................................... 14
1.2.8 Third Floor (applicable for all floors from 2nd up to 17th) Smoke Management ............................. 15
1.2.9 18th Floor Smoke Management .................................................................................................... 15
1.3 Water Tanks ........................................................................................................................................ 15
1.3.1 Irrigation Tank ............................................................................................................................. 15
1.3.2 Combined Domestic and Firefighting Water Tank ........................................................................ 15
1.3.3 Cement Lined Domestic Hot Water Tanks .................................................................................... 16
1.3.4 Fuel Fired Water Heaters (Serving Laundry Hot Water) ................................................................ 17
1.4 LPG Tanks............................................................................................................................................ 17
1.5 Fuel Tanks ........................................................................................................................................... 18
1.5.1 Generator Fuel Tank .................................................................................................................... 18
1.5.2 Boilers Fuel Tank (Backup) ........................................................................................................... 18
2 Residence Building ..................................................................................................................................... 19
2.1 Heating, Ventilation and Air Conditioning............................................................................................ 19
2.2 Smoke extraction and Pressurization: .................................................................................................. 19
1.5.3 Elevators Pressurization............................................................................................................... 19
1.5.4 Fireman Core (Staircase, elevator and lobby) ............................................................................... 20
1.5.5 Escape Core (Staircase and lobby) ............................................................................................... 24
1.5.6 Refuge Areas ............................................................................................................................... 27
1.5.7 Corridors smoke extraction and Makeup Air: ............................................................................... 29
2.3 Water Tanks ........................................................................................................................................ 30
RCHR-G-FD-CLC-P4-ME-01 R01 Page 2 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

List of Tables Table 2-20: Irrigation Tank Capacity .................................................................................................................... 30


Table 2-21: Fuel Tank Capacity ........................................................................................................................... 30
Table 1-1: Cooling Load ........................................................................................................................................ 4 Table 3-1: Heating Calculation (Swimming Pool-Hotel-Type 1) ............................................................................ 41
Table 1-2: Heating Load ........................................................................................................................................ 4 Table 3-2: Heating Calculation (Swimming Pool-Hotel-Type 2) ............................................................................ 42
Table 1-3: Fireman Core Pressurization................................................................................................................. 5 Table 3-3: Heating Calculation (Swimming Pool-Hotel-Type 3) ............................................................................ 42
Table 1-4: Fireman Core Pressurization................................................................................................................. 5 Table 3-4: Heating Calculation (Jacuzzi-Hotel)..................................................................................................... 43
Table 1-5: Fireman Core Pressurization................................................................................................................. 6 Table 3-5: Heating Calculation (Swimming Pool-Residences-Type 1) ................................................................... 43
Table 1-6: Fireman Core Pressurization................................................................................................................. 7 Table 3-6: Heating Calculation (Swimming Pool-Residences-Type 2) ................................................................... 44
Table 1-7: Escape Core Pressurization................................................................................................................... 9 Table 3-7: Heating Calculation (Swimming Pool-Residences-Type 3) ................................................................... 44
Table 1-8: Escape Core Pressurization................................................................................................................... 9 Table 3-8: Heating Calculation (Swimming Pool-Residences-Type 4) ................................................................... 45
Table 1-9: Escape Core Pressurization................................................................................................................. 10 Table 3-9: Heating Calculation (Jacuzzi- Residences) ........................................................................................... 45
Table 1-10: Escape Core Pressurization ............................................................................................................... 10
Table 1-11: Parking Ventilation ........................................................................................................................... 12
Table 1-12: Irrigation Water Tanks ...................................................................................................................... 15
Table 1-13: Combined Domestic and Firefighting Water Tank ............................................................................. 15
Table 1-14: Cement Lined Domestic Hot Water Tanks (Low Pressure Zone) ........................................................ 16
List of Figures
Table 1-15: Cement Lined Domestic Hot Water Tanks (Medium Pressure Zone) ................................................. 16 Figure 2-1: Elevators Pressurization .................................................................................................................... 19
Table 1-16: Cement Lined Domestic Hot Water Tanks (High Pressure Zone) ....................................................... 17 Figure 2-2: Second Floor Refuge Area Pressurization .......................................................................................... 27
Table 1-17: Fuel Fired Water Heaters (Serving Laundry Water) ........................................................................... 17 Figure 2-3: Eighth Floor Refuge Area Pressurization ............................................................................................ 28
Table 1-18: LPG Tanks......................................................................................................................................... 17 Figure 2-4: Fourteenth Floor Refuge Area Pressurization .................................................................................... 28
Table 1-19: Generator Fuel Tank ......................................................................................................................... 18
Table 1-20: Boilers Fuel Tanks (Backup) .............................................................................................................. 18
Table 2-1: Elevator-02 Pressurization.................................................................................................................. 19
Table 2-2: Elevator-02 Pressurization.................................................................................................................. 19
Table 2-3: Elevator-02 Pressurization.................................................................................................................. 19
Table 2-4: Elevator-03 Pressurization.................................................................................................................. 20
Table 2-5: Elevator-03 Pressurization.................................................................................................................. 20
Table 2-6: Elevator-03 Pressurization.................................................................................................................. 20
Table 2-7: Elevator-04 Pressurization.................................................................................................................. 20
Table 2-8: Elevator-04 Pressurization.................................................................................................................. 20
Table 2-9: Elevator-04 Pressurization.................................................................................................................. 20
Table 2-10: Fireman core- Leakage across 50 Pa pressure difference .................................................................. 21
Table 2-11: Fireman core- Leakage across 5 Pa pressure difference .................................................................... 21
Table 2-12: Fireman core-Lobby Total Flow ........................................................................................................ 22
Table 2-13: Fireman core-Flow from Other Leakages .......................................................................................... 23
Table 2-14: Escape core- Leakage across 50 Pa pressure difference .................................................................... 24
Table 2-15: Escape core-Leakage across 5 Pa pressure difference ....................................................................... 25
Table 2-16: Escape core-Lobby Total Flow .......................................................................................................... 25
Table 2-17: Leakage Area through Floors ............................................................................................................ 26
Table 2-18: Car Park Ventilation. ........................................................................................................................ 30
Table 2-19: Domestic Water Tank Cpacity ........................................................................................................... 30

RCHR-G-FD-CLC-P4-ME-01 R01 Page 3 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

1 Hotel Building
1.1 Cooling and Heating Load 1.2 Smoke Management and Pressurization

1.2.1 Fireman Core (Staircase, elevator and lobby) Pressurization


Cooling Load
This arrangement shall comply with a Class B System (For means of escape and firefighting) and based on BS EN
Sum-of-peak cooling load* 1401.7 TR 12101-6.
Block cooling load* 1187.5 TR
Total air conditioned area 24,752.5 m2 Mode-1 (Pressure difference Criterion – Closed door scenario):
Load density 20.84 m2 / TR
* For detailed calculation refer to appendix-A - Staircase:

Table 1-1: Cooling Load In this mode, the air flow is calculated assuming all doors are closed as below:

Q = 0.83 x A x P1/n
Three chillers with 385 TR and one chiller with 160 TR have been selected to handle 110% of the total load
calculated considering 37oC ambient temperature as requested by JEA. However, same chillers will handle 130% Where: Q: The leakage flowrate via gaps around closed doors (m3/s)
of building block load (1001 TR) calculated considering ASHRAE weather data (35.2 oC ambient temperature) to
comply with RC standard. A: Total crack area (m2)

P: Pressure difference criterion (Pa)

Heating Load The pressure difference is calculated considering the following pressure relation, Staircase and elevator are
pressurized at 50Pa while the lobby to be pressurized at 45Pa.
Sum-of-peak heating load* 3211.5 kW
Block heating load* 2511.9 kW Total leakage area is calculated as shown in below table:
Space Heating 22,036.6
Total heated area Leakage across 50 Pa pressure difference
m2
Load density 114 W/m2 Floor Internal walls Exterior walls Single-leaf door Single-leaf Total leakage
domestic water heating load ** 760 kW area (m2) 1 area (m2) 2 opening into 3 door opening area x 10-3 (m2) 6
Indoor swimming pool heating load *** 50 kW outward 4
Total heating load 3321.9 kW C4 48.62 0 0.681
* For detailed calculation refer to appendix-A C3 48.62 0 0.681
C2 48.62 0 0.681
** For detailed calculation refer to plumbing calculations of this report.
C1 68.64 0 0.961
*** For detailed calculation refer to swimming pools & water features calculation of this report.
GF 85.8 0 1 25.201
Table 1-2: Heating Load F1 58 15.5 1.897
F2 40.6 10.85 1.328
Selected boilers are comprised of four boilers adequate to handle 120% of the total load, with 1000 kW each. F3 40.6 10.85 1.328
F4 40.6 10.85 1.328
F5 40.6 10.85 1.328
F6 40.6 10.85 1.328
F7 40.6 10.85 1.328
F8 40.6 10.85 1.328
F9 40.6 10.85 1.328
F10 40.6 10.85 1.328
F11 40.6 10.85 1.328
RCHR-G-FD-CLC-P4-ME-01 R01 Page 4 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

F12 40.6 10.85 1.328 Table 1-4: Fireman Core Pressurization


F13 40.6 10.85 1.328
F14 40.6 10.85 1.328
F15 40.6 10.85 1.328 Required Pressurization Flow is:
F16 41.76 11.16 1.366
F17 46.4 12.4 1.518 Q = 0.83 x 71.420x 10-3 x 501/2 + 0.83 x 333.802 x 10-3 x 51/2 = 1.039
F18 58 15.5 1.897
RF 42.64 76.44 1 17.948 Applying 50% Safety factor,
Total 71.420
Table 1-3: Fireman Core Pressurization Q = 1.039 x 1.5 = 1.559 m3/s

Leakage across 5 Pa pressure difference


Floor Internal walls area Single-leaf door Double-leaf Door 5 Total leakage area
2 1 3
(m ) opening into x 10-3 (m2) 6 - Elevator Shaft:
C4 10.54 1 12.148
C3 10.54 1 12.148 Elevator shaft height = 87.6 m
C2 10.54 1 12.148
C1 14.88 1 12.208 Leakage across 5 Pa pressure difference:
GF 18.6 1 12.260
Internal wall length = 2.6 m (Area = 2.6 x 87.6 =227.76 m2)
F1 15.5 1 30.217
F2 10.85 1 30.152 Number of doors = 23 doors
F3 10.85 1 12.152
F4 10.85 1 12.152 Leakage are = (227.76 x 0.14 x 10-4) + (23 x 0.06) = 1.383 m2
F5 10.85 1 12.152
F6 10.85 1 12.152 Flow rate = 0.83 x 1.383 x 51/2 = 2.567 m3/s
F7 10.85 1 12.152
F8 10.85 1 12.152 Leakage across 50 Pa pressure difference:
F9 10.85 1 12.152
Internal wall length = 7.2 m (Area = 7.2 x 87.6 = 630.72 m2)
F10 10.85 1 12.152
F11 10.85 1 12.152
Lift well walls length = 2.5 m (Area = 2.5 x 87.6 = 219 m2)
F12 10.85 1 12.152
F13 10.85 1 12.152 Lift vent area = 0.1 m2
F14 10.85 1 12.152
F15 10.85 1 12.152 Total leakage are = (630.72 x 0.14 x 10-4) + (219 x 0.18 x 10-3) + 0.1 = 0.148 m2
F16 11.16 1 12.156
F17 12.4 1 12.174 Flow rate = 0.83 x 0.148 x 501/2 = 0.869 m3/s
F18 15.5 1 30.217
Total 333.802 Applying 50% safety factor:
(1) Leakage area for indoor wall calculated based on ALW/AWall = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
Q = (2.567 + 0.869) x 1.5 = 5.154 m3/s
(2) Leakage area for exterior wall calculated based on ALW/Awall = 0.7 x 10-4 (Table A.5, BS EN 12101-6)
(3) Leakage area for single-leaf door opening into pressurized space = 0.012 m2 (1mm from side and above,
7mm from bottom)
(4) Leakage area for single-leaf door opening outward pressurized space = 0.024 m2
(5) Leakage area for double-lead door = 0.03 m2 (Table A.3, BS EN 12101-6)
(6) Total leakage area consider all leakage area as series (ATotal = A1 + A2 + A3 …..).

RCHR-G-FD-CLC-P4-ME-01 R01 Page 5 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

- Lobby: Mode-3 (Airflow Criterion – Open door scenario):

Floor Internal Exterior Number of Number of Number Total Pressure Flow Total - Staircase:
Wall Wall Single-leaf Single-leaf of Leakage Difference from Flow
Area Area door door Double- Area x (Pa) leakage applying Flow through fire storey:
(m2)1 (m2)2 opening opening leaf 10-3 areas 50%
into a outwards a Door 5 2 6
(m ) safety  Number of opened door = 1
pressurized pressurized factor  Open door area = 2 m2
space3 space4 (m3/s)  Assumed velocity across opened door = 2 m/s
C4 22.61 1 12.317 45 0.069 0.103  Air flow through opened door = 2 x 2 = 4 m3/s
C3 22.78 1 12.319 45 0.069 0.103
C2 22.78 1 12.319 45 0.069 0.103
C1 32.16 1 12.450 45 0.069 0.104
GF 39.6 1 12.554 45 0.070 0.105 Resulted pressure within the stair case:
F1 40.5 1 30.567 45 0.170 0.255
 Assumed velocity across air exit = 2.5 m/s
F2 32.55 1 1 54.456 45 0.303 0.455
 Flow across air exit = 4 m3/s
F3 31.5 1 12.441 45 0.069 0.104
 Air exit area = 4 / 2.5 = 1.6 m2
F4 31.5 1 12.441 45 0.069 0.104
F5 31.5 1 12.441 45 0.069 0.104  Leakage effective area:
F6 31.5 1 12.441 45 0.069 0.104 1 1 1
−1/2
1 1 1 −1/2
F7 31.5 1 12.441 45 0.069 0.104 Aeff = [𝐴2 + 𝐴2𝑙𝑜𝑏𝑏𝑦 𝑑𝑜𝑜𝑟
+ 𝐴2𝑎𝑖𝑟 𝑒𝑥𝑖𝑡
] = [22 + 22
+ 1.62
] = 1.06 m2
𝑠𝑡𝑎𝑖𝑟 𝑑𝑜𝑜𝑟
F8 31.5 1 12.441 45 0.069 0.104
𝑄 𝑛 4 2
F9 31.5 1 12.441 45 0.069 0.104  Pressure within staircase = ( ) =( ) = 20.67 Pa
0.83 𝐴 0.83 𝑥 1.06
F10 31.5 1 12.441 45 0.069 0.104
F11 31.5 1 12.441 45 0.069 0.104
F12 31.5 1 12.441 45 0.069 0.104
F13 31.5 1 12.441 45 0.069 0.104 Flow through opened door at ground floor:
F14 31.5 1 12.441 45 0.069 0.104  Door area = 2 m2
F15 31.5 1 12.441 45 0.069 0.104
 Air flow through opened door = 0.83 x 2 x 20.671/2 = 7.55 m3/s
F16 32.4 1 12.454 45 0.069 0.104
F17 36 1 12.504 45 0.070 0.104
F18 25 19.5 1 1 43.715 45 0.243 0.365
Total 3.152 Flow through opened door at adjacent storey:
-4
(1) Leakage area for indoor wall calculated based on ALW/AWall = 0.14 x 10 (Table A.5, BS EN 12101-6)  Assumption: stair door of adjacent storey is opened while lobby door to accommodation is closed.
(2) Leakage area for exterior wall calculated based on ALW/Awall = 0.7 x 10-4 (Table A.5, BS EN 12101-6)  Leakage effective area:
(3) Leakage area for single-leaf door opening into pressurized space = 0.012 m2 (1mm from side and above, 1 1
−1/2
1 1 −1/2
7mm from bottom) Aeff = [𝐴2 + 𝐴2𝑙𝑜𝑏𝑏𝑦 𝑑𝑜𝑜𝑟 𝑙𝑒𝑎𝑘𝑎𝑔𝑒 𝑎𝑟𝑒𝑎
] = [22 + 0.012 2
] = 0.012 m2
𝑠𝑡𝑎𝑖𝑟 𝑑𝑜𝑜𝑟
(4) Leakage area for single-leaf door opening outward pressurized space = 0.024 m2  Air flow = 0.83 x 0.012 x 20.671/2 = 0.045 m3/s
(5) Leakage area for double-lead door = 0.03 m2 (Table A.3, BS EN 12101-6)
(6) Total leakage area consider all leakage area as series (ATotal = A1 + A2 + A3 …..)

Table 1-5: Fireman Core Pressurization

Total air flow for mode-1 = 1.559 + 3.152 + 5.154 = 9.865 m3/s

RCHR-G-FD-CLC-P4-ME-01 R01 Page 6 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

Flow from other leakages:

Floor Internal walls area Exterior walls area Single-leaf door Total leakage area - Elevator Shaft:
2 1 2 2 3
(m ) (m ) opening into x 10-3 (m2) 6
C4 48.62 0 0.681 Calculation to be done considering one door opened in the adjacent storey:
C3 48.62 0 0.681
C2 48.62 0 0.681 Flow from opened door:
C1 68.64 0 0.961
 Door lift dimension is 1.7 m x 2.0 m.
GF 85.8 0 1.201
F1 58 15.5 1.897  Open door leakage = ((1.7 + 2.0) x 2) x 0.025 = 0.185 m2
F2 40.6 10.85 1.328  Leakage from open door = 0.83 x 0.185 x 501/2 = 1.086 m3/s
F3 40.6 10.85 1.328
F4 40.6 10.85 1.328 Flow from other leakages:
F5 40.6 10.85 1.328
 Elevator shaft height = 87.6 m
F6 40.6 10.85 1.328
F7 40.6 10.85 1.328
F8 40.6 10.85 1.328  Leakage across 5 Pa pressure difference:
F9 40.6 10.85 1.328 o Internal wall length = 2.6 m (Area = 2.6 x 87.6 =227.76 m2)
F10 40.6 10.85 1.328 o Number of doors = 22 doors
F11 40.6 10.85 1.328 o Leakage area = (227.76 x 0.14 x 10-4) + (22 x 0.06) = 1.323 m2
F12 40.6 10.85 1.328 o Flow rate = 0.83 x 1.323 x 51/2 = 2.455
F13 40.6 10.85 1.328  Leakage across 50 Pa pressure difference:
F14 40.6 10.85 1.328
o Internal wall length = 7.2 m (Area = 7.2 x 87.6 = 630.72 m2)
F15 40.6 10.85 1.328
F16 41.76 11.16 1.366 o Lift well walls length = 2.5 m (Area = 2.5 x 87.6 = 219 m2)
F17 46.4 12.4 1.518 o Lift vent area = 0.1 m2
F18 58 15.5 1.897 o Total leakage are = (630.72 x 0.14 x 10-4) + (219 x 0.18 x 10-3) + 0.1 = 0.148 m2
RF 42.64 76.44 1 17.948 o Flow rate = 0.83 x 0.148 x 501/2 = 0.869 m3/s
Total leakage area 47.420
(1) Leakage area for indoor wall calculated based on ALW/AWall = 0.14 x 10-4 (Table A.5, BS EN 12101-6)  Total flow from leakages applying 50% safety factor
(2) Leakage area for exterior wall calculated based on ALW/Awall = 0.7 x 10-4 (Table A.5, BS EN 12101-6) = 2.455 + 0.869 = 3.324 m3/s
(3) Leakage area for single-leaf door opening into pressurized space = 0.012 m2 (1mm from side and above,
7mm from bottom) Total required flow, applying 50% safety factor:

Q = (1.086 + 3.324) x 1.5 = 6.615 m3/s


Table 1-6: Fireman Core Pressurization

 Air flow through leakage area = 0.83 x 47.42 x 10-3 x 20.671/2 = 0.179 m3/s - Lobby:
 Applying 50% safety factor, 0.179 x 1.5 = 0.269 m3/s Same as mode-1

Total Pressurization flow

Q = 4 + 7.55 + 0.045 + 0.269 = 11.864 m3/s

RCHR-G-FD-CLC-P4-ME-01 R01 Page 7 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

Calculated total airflow for mode-3 1.2.2 Escape Core (Staircase and lobby) Pressurization
This arrangement shall comply with a Class E System (For means of escape only) and based on BS EN 12101-6.
 Air flow to fire floor = 4 m3/s
 Air flow to exit door (ground floor) = 7.55 m3/s Mode-1 (All doors closed):
 Air flow for lift shaft = 6.615 m3/s
 Air flow through all other leakages = 3.466 m3/s - Staircase:

Total = 4 + 7.55 + 6.615 + 3.466 = 21.631 m3/s In this mode, the air flow is calculated assuming all doors are closed as below:

Select two fans (1 duty & 1 standby) each capable to handle 21.631 m3/s minimum. Q = 0.83 x A x P1/n

Calculated area for air/smoke relief vent Where: Q: The leakage flowrate via gaps around closed doors (m3/s)

 Air flow to fire floor = 4 m3/s A: Total crack area (m2)


 Velocity through relief vent = 2.5 m/s P: Pressure difference criterion (Pa)
 Area of air/smoke relief vent = 4 / 2.5 = 1.6 m2

The pressure difference is calculated considering the following pressure relation, Staircase is pressurized at 50Pa
Calculated area of pressure relief while the lobby to be pressurized at 45Pa.
𝑄 (21.631−9.865)
 Area of pressure relief = = = 2 m2
0.83 𝑥 𝑃 0.5 0.83 𝑥 500.5

However, Variable speed fans with dampers controlled by pressure sensors will be used instead of providing the Total leakage area is calculated as shown in below table:
pressure relief. Highlighting that the system shall be able to achieve over 90% of the new air supply requirements
Leakage across 50 Pa pressure difference
within 3 second of a door being opened or closed. (as per BS EN 12101-6, paragraph 5.4.2.5).
Floor Internal walls area Exterior walls area Single-leaf door Total leakage area x
(m2) 1 (m2) 2 opening into 3 10-3 (m2) 6
C4 46.75 0 0.655
C3 46.75 0 0.655
C2 46.75 0 0.655
C1 69.36 0 0.971
GF 86.7 0 1.214
F1 44 0 0.616
F2 39.9 10.85 1.318
F3 39.9 10.85 1.318
F4 39.9 10.85 1.318
F5 39.9 10.85 1.318
F6 39.9 10.85 1.318
F7 39.9 10.85 1.318
F8 39.9 10.85 1.318
F9 39.9 10.85 1.318
F10 39.9 10.85 1.318
F11 39.9 10.85 1.318
F12 22.05 28.7 2.318
F13 22.05 28.7 2.318

RCHR-G-FD-CLC-P4-ME-01 R01 Page 8 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

F14 22.05 28.7 2.318 Required Pressurization Flow is:


F15 22.225 28.525 2.308
F16 20.52 31.68 2.505 Q = 0.83 x 53.273 x 10-3 x 501/2 + 0.83 x 346.286 x 10-3x51/2 = 0.955 m3/s
F17 24.4 36.8 2.918
F18 31.75 47.25 3.752 Applying 50% Safety factor,
RF 45.24 60.84 1 16.892
Q = 0.955 x 1.5 = 1.433 m3/s
Total 53.273
Table 1-7: Escape Core Pressurization

Leakage across 5 Pa pressure difference - Lobby:


Floor Internal walls Single-leaf door Single-leaf door Double-leaf Total leakage
area (m2) 1 opening into 3 opening Door 5 area x 10-3 (m2 )
outward4 6

C4 12.75 1 12.179 Floor Internal Exterior Number of Number of Number Total Pressure Flow Total
C3 12.75 1 12.179 Wall Wall Single-leaf Single-leaf of Leakage Difference from Flow
C2 12.75 1 12.179 Area Area door door Double- Area x (Pa) leakage applying
C1 14.64 1 12.205 (m2)1 (m2)2 opening opening leaf 10-3 areas 50%
5 2 6
GF 18.3 1 24.256 into a outwards a Door (m ) safety
F1 44 1 30.616 pressurized pressurized factor
F2 10.85 1 30.152 space3 space4 (m3/s)
F3 10.85 1 12.152 C4 40.12 0 1 12.562 45 0.070 0.105
F4 10.85 1 12.152 C3 40.12 0 1 12.562 45 0.070 0.105
F5 10.85 1 12.152 C2 43.69 0 1 12.612 45 0.070 0.105
F6 10.85 1 12.152 C1 54.24 0 2 24.759 45 0.138 0.207
F7 10.85 1 12.152 GF 161.7 7.8 1 26.810 45 0.149 0.224
F8 10.85 1 12.152 F1 80.5 9 1 1 43.757 45 0.244 0.365
F9 10.85 1 12.152 F2 40.075 0 2 24.561 45 0.137 0.205
F10 10.85 1 12.152 F3 40.25 0 1 12.564 45 0.070 0.105
F11 10.85 1 12.152 F4 40.25 0 1 12.564 45 0.070 0.105
F12 10.85 1 12.152 F5 40.25 0 1 12.564 45 0.070 0.105
F13 10.85 1 12.152 F6 40.25 0 1 12.564 45 0.070 0.105
F14 10.85 1 12.152 F7 40.25 0 1 12.564 45 0.070 0.105
F15 10.85 1 12.152 F8 40.25 0 1 12.564 45 0.070 0.105
F16 11.16 1 12.156 F9 40.25 0 1 12.564 45 0.070 0.105
F17 12.4 1 12.174 F10 40.25 0 1 12.564 45 0.070 0.105
F18 15.5 1 30.217 F11 39.9 0 1 12.559 45 0.070 0.105
Total 346.286 F12 40.6 0 1 12.568 45 0.070 0.105
(1) Leakage area for indoor wall calculated based on ALW/AWall = 0.14 x 10-4 (Table A.5, BS EN 12101-6) F13 28.7 0 1 12.402 45 0.069 0.104
(2) Leakage area for exterior wall calculated based on ALW/Awall = 0.7 x 10-4 (Table A.5, BS EN 12101-6) F14 40.425 0 1 12.566 45 0.070 0.105
F15 40.25 0 1 12.564 45 0.070 0.105
(3) Leakage area for single-leaf door opening into pressurized space = 0.012 m2 (1mm from side and above,
F16 80.28 14.94 2 1 50.170 45 0.279 0.419
7mm from bottom)
F17 28.6 15.4 1 13.478 45 0.075 0.113
(4) Leakage area for single-leaf door opening outward pressurized space = 0.024 m2 F18 25.5 9 1 30.987 45 0.173 0.259
(5) Leakage area for double-lead door = 0.03 m2 (Table A.3, BS EN 12101-6) Total 3.469
(6) Total leakage area consider all leakage area as series (ATotal = A1 + A2 + A3 …..). (1) -4
Leakage area for indoor wall calculated based on ALW/AWall = 0.14 x 10 (Table A.5, BS EN 12101-6)
(2) Leakage area for exterior wall calculated based on ALW/Awall = 0.7 x 10-4 (Table A.5, BS EN 12101-6)
Table 1-8: Escape Core Pressurization

RCHR-G-FD-CLC-P4-ME-01 R01 Page 9 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

(3) Leakage area for single-leaf door opening into pressurized space = 0.012 m2 (1mm from side and above, Mode-2 (Velocity criterion):
7mm from bottom)
In this mode, the calculation is performed assuming one open door at fire floor, one open exit door and open
(4) Leakage area for single-leaf door opening outward pressurized space = 0.024 m2
(5) Leakage area for double-lead door = 0.03 m2 (Table A.3, BS EN 12101-6) accommodation door other than fire floor.
(6) Total leakage area consider all leakage area as series (ATotal = A1 + A2 + A3 …..) Air flow through open fire door:
Table 1-9: Escape Core Pressurization
 Door area = 2 m2
Total air flow for mode-1 = 1.433 + 3.469 = 4.902 m3/s  Velocity = 0.75 m/s
 Flow = 2 x 0.75 = 1.5 m3/s
Mode-2 (Pressure criterion):
Resulted pressure within the stair case:
In this mode, the calculation is performed assuming open exit door in addition to two open accommodation
doors other than fire floor (maintaining 10Pa pressure):  Assumed velocity across air exit = 2.5 m/s
 Flow across air exit = 1.5 m3/s
Air flow through open exit door:  Air exit area = 1.5 / 2.5 = 0.6 m2
 Leakage effective area:
 Door Area = 2 m2
−1/2
 Flow rate = 0.83 x 2 x 101/2 = 5.249 m3/s 1 1 1 1 1 1 −1/2
Aeff = [𝐴2 + 𝐴2𝑙𝑜𝑏𝑏𝑦 𝑑𝑜𝑜𝑟
+ 𝐴2𝑎𝑖𝑟 𝑒𝑥𝑖𝑡
] = [22 + 22
+ 0.6 2
] = 0.55 m2
𝑠𝑡𝑎𝑖𝑟 𝑑𝑜𝑜𝑟
Air flow through opened accommodation doors: 𝑛 2
𝑄 1.5
 Pressure within staircase = (0.83 𝐴) = (0.83 𝑥 0.55) = 10.8 Pa
 Assume the below floors as the worst case:
o First floor, area = 2101.7 m2. Airflow through open exit door:
o Second floor, area = 1556.8 m2.
 Door area = 2 m2
 Leakage area through floors:  Air flow through opened door = 0.83 x 2 x 10.81/2 = 5.455 m3/s
Floor Floor Leakage area ratio Exterior walls area (m2) Leakage area Total leakage
Area area (ALF/AFloor)1 ratio area (m2) Airflow through open accommodation door:
2
(m ) (ALW/Awall)2
First 2101.7 0.52 x 10-4 1075 (215 L x 5 H) 0.42 x 10-3 0.670  Assume first floor as the worst case.
Floor x2  Airflow = 0.83 x 0.670 x 10.81/2 = 1.828 m3/s
Second 1556.8 0.52 x 10-4 665 (190 L x 3.5 H) 0.42 x 10-3 0.441
Floor x2
(1) Assuming average tightness (table A.6, BS EN 12101-6).
Adding mode-1, total air flow for mode-3 = 1.5 + 5.455 + 1.828 + 4.902 = 13.685 m3/s
(2) Assuming loose tightness (table A.5, BS EN 12101-6).

Table 1-10: Escape Core Pressurization

 Air flow = 0.83 x (0.670 + 0.441) x 101/2 = 2.916 m3/s

Adding mode-1, total air flow for mode-2 = 5.249 + 2.916 +4.902 = 13.067 m3/s

RCHR-G-FD-CLC-P4-ME-01 R01 Page 10 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

Summery: 1.2.3 Refuge Area Pressurization

 Mode-1: 1.2.3.1 7th floor refuge area


o Airflow required to stair = 1.433 m3/s
Leakage through floors
o Air flow required to lobby = 3.469 m3/s
o Total airflow = 4.902 m3/s  Floor area = 140 m2
 Mode-2 (Pressure criterion):  Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
o Airflow through open exit door = 5.249 m3/s  Leakage area = 0.00728 m2
o Airflow through two open accommodation doors = 2.916 m3/s  Multiplied by two to cater leakage from below and above slab floor = 0.01456 m2
o Total air flow = 13.067 m3/s
 Airflow through leakage =0.83 x 0.01456 x 501/2 = 0.085 m3/s
o Airflow to stair = 9.598 m3/s
o Air flow to lobby = 3.469 m3/s Leakage through walls
 Mode-2 (Velocity criterion):
o Airflow through open fire floor door = 1.5 m3/s  Length = 147 m2
o Airflow through open exit door = 5.455 m3/s  Height = 3.5 m
o Airflow through open accommodation door = 1.828 m3/s  Area = 514.5 m2
o Total airflow = 13.685 m3/s  Leakage factor (ALW/AWall) = 0.14 x 10-4
o Airflow to stair = 10.216 m3/s  Leakage area = 0.007203 m2
o Airflow to lobby = 3.469 m3/s  Airflow through leakage = 0.83 x 0.007203 x 501/2 = 0.042 m3/s

Leakage through doors


 Calculated area of air / smoke relief vent:
o Airflow to fire floor = 1.5 m3/s  Number of single-leaf doors opened outward pressurized space = 20
o Area of air/relief smoke vent = 1.5 / 2.5 = 0.6 m2  Number of double-leaf doors = 1
 Leakage area for single-leaf door opening outward pressurized space = 0.024 m2
 Calculated area of pressure relief:  Leakage area for double-leaf door opening into pressurized space = 0.03 m2
𝑄 (13.685−4.902)
o = = 1.5 m2  Total leakage area = 20 x 0.024 + 1 x 0.03 = 0.51 m2
0.83 𝑥 𝑃 0.5 0.83 𝑥 500.5
 Airflow through leakage = 0.83 x 0.51 x 501/2 = 2.993 m3/s
However, Variable speed fans with dampers controlled by pressure sensors will be used instead of
providing the pressure relief. Highlighting that the system shall be able to achieve over 90% of the new air
supply requirements within 3 second of a door being opened or closed. (as per BS EN 12101-6, paragraph Total Airflow
5.4.2.5).
 Total airflow = 0.085 + 0.042 + 2.993 = 3.12 m3/s
 Applying 50% safety factor = 3.12 x 1.5 = 4.68 m3/s

RCHR-G-FD-CLC-P4-ME-01 R01 Page 11 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

1.2.3.2 13th floor refuge area 1.2.4 Parking Ventilation


Leakage through floors Parking Normal
Normal Smoke
Area (m2) Ventilation
 Floor area = 130 m2 Total Floor Floor Height Ventilation Extraction
Floor Flow (7.5
Area (m2) (m) Flow (6 ACH) – Flow (10 ACH)
 Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6) L/s
l/s/m2) –
– L/s
 Leakage area = 0.00676 m2 L/s*
Cellar – 4 7,089 5,002 3.05 36,036 37,515 60,060
 Multiplied by two to cater leakage from below and above slab floor = 0.01352 m2
Cellar – 3 7,432 5,543 3.05 37,779 41,572.5 62,966
 Airflow through leakage = 0.83 x 0.01352 x 501/2 = 0.079 m3/s
Cellar – 2 7,402 5,484 3.05 37,627 41,130 62,711
Leakage through walls * 7.5 l/s/m2 is considered for normal flow based on RC standard.

Table 1-11: Parking Ventilation


 Length = 121 m2
 Height = 3.5 m 1.2.5 Cellar-1 Floor Smoke Management
 Area = 423.5 m2 Part-1 (Ballroom area)
 Leakage factor (ALW/AWall) = 0.14 x 10-4
 Leakage area = 0.005929 m2 Leakage area through floors:
 Airflow through leakage = 0.83 x 0.005929 x 501/2 = 0.035 m3/s
 Floors across 12.5 Pa:
Leakage through doors o Floor area = 1010 m2
o Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
 Number of single-leaf doors opened outward pressurized space = 15 o Leakage area = 2 x 1010 x 0.52 x 10-4 = 0.105 m2
 Number of double-leaf doors = 1
 Leakage area for single-leaf door opening outward pressurized space = 0.024 m2 Leakage area through walls:
 Leakage area for double-leaf door opening into pressurized space = 0.03 m2
 Walls across 25 Pa:
 Total leakage area = 15 x 0.024 + 1 x 0.03 = 0.39 m2
o Internal walls area = 156 x 10 = 1560 m2
 Airflow through leakage = 2.289 m3/s
o Leakage factor (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
Total Airflow o Leakage area = 1560 x 0.14 x 10-4 = 0.02184 m2
 Wall across 12.5 Pa:
 3
Total airflow = 0.079 + 0.035 + 2.289 = 2.403 m /s o Internal walls area = 17 x 10 = 170 m2
 Applying 50% safety factor = 2.403 x 1.5 = 3.605 m3/s o Leakage factor (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
o Leakage area = 170 x 0.14 x 10-4 = 0.00238 m2

Leakage area through doors:

 Doors across 25 Pa:


1.2.3.3 Total for both refuge area o Number of single leaf door opening outward = 6
Total fan flow rate = 4.680 + 3.605 = 8.285 m3/s o Number of double door = 7
o large double door: 3.5 m width, 2.0 m height
o Leakage area = (6 x 0.02) + (7 x 0.03) + (7.5 x 0.001 + 3.5 x 0.007) = 0.362 m2

Required flowrate through leakages:

Q = 0.83 x (0.02184 + 0.362) x 251/2 + 0.83 x (0.105 + 0.00238) x 12.51/2 = 1.908 m3/s

RCHR-G-FD-CLC-P4-ME-01 R01 Page 12 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

Assume Additional one open door (for smoke mode only): Assume Additional one open door (for smoke mode only):

Q = A x V = 2 x 0.75 = 1.5 m3/s Q = A x V = 2 x 0.75 = 1.5 m3/s

Summery: Summery:

For Pressurization Supply Mode = 1.908 m3/s For Pressurization Supply Mode = 2.810 m3/s

For Smoke Extraction Mode = 1.908 + 1.5 = 3.408 m3/s For Smoke Extraction Mode = 2.810 + 1.5 = 4.31 m3/s

Part-2 (Pre-function area) Part-3 (service corridor)

Leakage area through floors: Leakage area through floors:

 Floor across 12.5 Pa:  Floor across 12.5 Pa:


o Floor area = 895 m2 o Floor area = 736 m2
o Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6) o Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
o Leakage area = 2 x 895 x 0.52 x 10-4 = 0.093 m2 o Leakage area = 2 x 736 x 0.52 x 10-4 = 0.077 m2

Leakage area through walls: Leakage area through walls:

 Walls across 25 Pa:


o Internal walls area = 71 x 4.45 = 315.95 m2  Walls across 25 Pa:
o Leakage factor (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6) o Wall area = 60 x 4.45 = 267 m2
o Leakage area = 315.95 x 0.14 x 10-4 = 0.0044233 m2 o Leakage factor (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
 Wall across 12.5 Pa: o Leakage area = 267 x 0.14 x 10-4 = 0.003738 m2
o Internal walls area = 209 x 4.45 = 930.05 m2
o Leakage factor (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)  Walls across 12.5 Pa:
o Leakage area = 930.05 x 0.14 x 10-4 = 0.0130207 m2 o Wall area = 550 x 4.45 = 2447.5 m2
o Leakage factor (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
Leakage area through doors: o Leakage area = 2447.5 x 0.14 x 10-4 = 0.034265 m2

 Doors across 25 Pa: Leakage area through doors:


o Number of single leaf door opening outward = 1
o Number of double door = 7  Doors across 25 Pa:
o Leakage area = (1 x 0.02) + (7 x 0.03) = 0.23 m2 o Number of single leaf door opening into = 7
 Doors across 12.5 Pa: o Number of double door = 2
o Number of single leaf door opening into = 4 o Ballroom large double door: 3.5 m width, 2.0 m height
o Number of single leaf door opening outward = 9 o Leakage area = (7 x 0.01) + (2 x 0.03) + (7.5 x 0.001 + 3.5 x 0.007) = 0.162 m2
o Number of double door = 6
o Number of lift doors = 2  Doors across 12.5 Pa:
o Leakage area = (4 x 0.01) + (9 x 0.02) + (6 x 0.03) + (2 x 0.06) = 0.52 m2 o Number of single leaf door opening into = 18
o Number of single leaf door opening outward = 18
Required flowrate through leakages: o Number of double door = 16
o Number of lift doors = 1
Q = 0.83 x (0.0044233 + 0.23) x 251/2 + 0.83 x (0.093 + 0.0130207 + 0.52) x 12.51/2 = 2.810 m3/s
RCHR-G-FD-CLC-P4-ME-01 R01 Page 13 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

o Shutter door – 1 : 5.0 m length x 2.0 m height Q = 0.83 x (0.083 + 0.037 + 0.53) x 12.51/2 = 1.907 m3/s
o Shutter door – 2 : 4.0 m length x 2.0 m height
Restaurant:
o Shutter door – 3 : 3.5 m length x 2.0 m height
o Leakage area = (18 x 0.01) + (18 x 0.02) + (16 x 0.03) + (1 x 0.06) + (9 x 0.001 + 5 x 0.007) + (8 x Leakage area through floors:
0.001 + 4 x 0.007) + (7.5 x 0.001 + 3.5 x 0.007) = 1.192 m2
 Floor across 12.5 Pa:
Required flowrate through leakages:
o Floor area = 390 m2
Q = 0.83 x (0.003738 + 0.162) x 251/2 + 0.83 x (0.077 + 0.034265 + 1.192) x 12.51/2 = 4.512 m3/s o Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
o Leakage area = 390 x 0.52 x 10-4 = 0.02028 m2
Assume Additional one open door (for smoke mode only):
Leakage area through walls:
Q = A x V = 2 x 0.75 = 1.5 m3/s

Summery:  Walls across 25 Pa:


o Wall area = 27 x 6 = 162 m2
For Pressurization Supply Mode = 4.512 m3/s o Leakage factor (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
o Leakage area = 162 x 0.14 x 10-4 = 0.002268 m2
For Smoke Extraction Mode = 4.512 + 1.5 = 6.012 m3/s
 Walls across 12.5 Pa:
1.2.6 Ground Floor Smoke Management o Wall area = 81 x 6 = 486 m2
o Leakage factor (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
Corridor and Lobby:
o Leakage area = 486 x 0.14 x 10-4 = 0.006804 m2
Leakage area through floors:
Leakage area through doors:
 Floor area = 795 m2
 Doors across 25 Pa:
 Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
o Number of double doors = 2
 Leakage area = 2 x 795 x 0.52 x 10-4 = 0.083 m2
o Leakage area = 2 x 0.03 = 0.06 m2
Leakage area through walls:
 Doors across 12.5 Pa:
 Internal walls area = (189 x 6) + (30 x 11) = 1464 m 2
o Number of single doors opening outward = 1
 External walls area = (25 x 6) + (7.5 x 11) = 232.5 m2 o Number of double doors = 2
 Leakage factor for internal walls (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6) o Leakage area = 1 x 0.02 + 2 x 0.03 = 0.08 m2
 Leakage factor for external walls (ALW/AWall) = 0.7 x 10-4 (Table A.5, BS EN 12101-6)
 Leakage area = (1464 x 0.14 x 10-4) + (232.5 x 0.7 x 10-4) = 0.037 m2 Required flowrate:

Leakage area through doors:  Q = 0.83 x (0.002268 + 0.06) x 251/2 + 0.83 x (0.02028 + 0.006804 + 0.08) x 12.51/2 = 0.573 m3/s

 Number of single leaf door opening into = 1 1.2.7 First Floor Smoke Management
 Number of single leaf door opening outward = 8 Leakage area through floors:
 Number of double door = 8
 Number of lift doors = 2  Floor area = 305 m2
 Leakage area = (1 x 0.01) + (8 x 0.02) + (8 x 0.03) + (2 x 0.06) = 0.53 m2  Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
 Leakage area = 2 x 305 x 0.52 x 10-4 = 0.032 m2
Required flowrate:
RCHR-G-FD-CLC-P4-ME-01 R01 Page 14 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

Leakage area through walls:  Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
 Leakage area = 2 x 458 x 0.52 x 10-4 = 0.048 m2
 Internal walls area = 197 x 5 = 985 m2
 External walls area = 11 x 5 = 55 m2 Leakage area through walls:
 Leakage factor for internal walls (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
 Internal walls area = 80 x 5 = 400 m2
 Leakage factor for external walls (ALW/AWall) = 0.7 x 10-4 (Table A.5, BS EN 12101-6)
 External walls area = 55 x 5 = 275 m2
 Leakage area = (985 x 0.14 x 10-4) + (55 x 0.7 x 10-4) = 0.018 m2
 Leakage factor for internal walls (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
Leakage area through doors:  Leakage factor for external walls (ALW/AWall) = 0.7 x 10-4 (Table A.5, BS EN 12101-6)
 Leakage area = (400 x 0.14 x 10-4) + (275 x 0.7 x 10-4) = 0.025 m2
 Number of single leaf door opening into = 4
 Number of single leaf door opening outward = 13 Leakage area through doors:
 Number of double door = 5
 Number of single leaf door opening into = 2
 Leakage area = (4 x 0.01) + (13 x 0.02) + (5 x 0.03) = 0.45 m2
 Number of single leaf door opening outward = 8
Required flowrate:  Number of double door = 1
 Leakage area = (2 x 0.01) + (8 x 0.02) + (1 x 0.03) = 0.21 m2
Q = 0.83 x (0.032 + 0.018 + 0.45) x 12.51/2 = 1.467 m3/s
Required flowrate:
1.2.8 Third Floor (applicable for all floors from 2nd up to 17th) Smoke Management
Q = 0.83 x (0.048 + 0.025 + 0.21) x 12.51/2 = 0.830 m3/s
 Floor area = 132 m2
 Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6) 1.3 Water Tanks
 Leakage area = 2 x 132 x 0.52 x 10-4 = 0.014 m2
1.3.1 Irrigation Tank
Leakage area through walls:
Daily irrigation demand (m3) Number of storage day Required Tank Volume (m3)
 Internal walls area = 143 x 3.5 = 500.5 m2
47* 3 141
 Leakage factor for internal walls (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
* Based on latest data received from cracknell
 Leakage area = 500.5 x 0.14 x 10-4 = 0.007 m2
Table 1-12: Irrigation Water Tanks
Leakage area through doors:
1.3.2 Combined Domestic and Firefighting Water Tank
 Number of single leaf door opening outward = 21
 Number of double door = 1 Domestic Water Demand
 Leakage area = (21 x 0.02) + (1 x 0.03) = 0.45 m2 Number of Daily Consumption per Total Daily Number of Required Volume
guestroom guestroom (L/day)* Consumption (L) storage days (m3)
Required flowrate: 228 570 129,960 3 390
Firefighting Water Demand
Q = 0.83 x (0.014 + 0.007 + 0.45) x 12.51/2 = 1.382 m3/s Required Volume
Flow Rate Duration Required Volume (gallons)
(m3)
1.2.9 18th Floor Smoke Management 1,250 60 75,000 284
Leakage area through floors: Total Tank Volume 674
* As per RC standard.
 Floor area = 458 m2
Table 1-13: Combined Domestic and Firefighting Water Tank
RCHR-G-FD-CLC-P4-ME-01 R01 Page 15 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

1.3.3 Cement Lined Domestic Hot Water Tanks Medium Pressure Zone (2nd floor up to 10th floor)

Low Pressure Zone (B4 floor up to 1st Floor)


Foodservice Facilities Number of meals per day 75 meals
(Club Lounge) 25 meals
Foodservices (Lobby Number of meals per day 3,218 meals
Number of meals per hour (assuming 3 meals
Lounge Bar, ADD
per day & 1 hour per meal)
restaurants, Pool Bar,
Number of meals per hour (assuming 3 meals Maximum hourly demand 5.7 l/h per meal
Employee cafeteria,
per day & 1 hour per meal) 1,073 meals Recovery heating 0.0012 l/s per meal
Ballroom & pre-
function and main Maximum hourly demand 5.7 L/h per meal Useable storage 143 liters
kitchen) recovery heating 0.0012 L/s per meal Storage 204 liters
useable storage 6,114 L Recovery 0.03 l/s
Storage 8,735 L Guestrooms Number of guestrooms 146 Room
Recovery 1.29 l/s 38* liters per
Other public areas Number of Lavatory 99 Storage rate guestroom
Number of showers 31 15* l/h per
Demand per lavatory 30 L/h recovery rate guestroom
Demand per shower 284 L/h useable storage 5,548 liters
Demand Factor 0.25 Storage 7,926 liters
Storage Factor 0.8 Recovery 0.61 l/s
total demand 2943.5 L/h Other public areas Number of Lavatory 8
useable storage 2354.8 L Number of showers 0
Storage 3364 Liters Demand per lavatory 30 L/h
Recovery 0.82 L/s Demand per shower 284 L/h
Total Storage 12,099 L Demand Factor 0.25
Storage Factor 0.8
Total Recovery (at 55 oC rise) 485 kW
Table 1-14: Cement Lined Domestic Hot Water Tanks (Low Pressure Zone) total demand 60 L/h
useable storage 48 L
Storage 69 Liters
Two Tanks (6,050 Liters each) are selected to serve the low pressure zone. L/s
Recovery 0.02
Total Storage 8,198 liters
Total Recovery (at 55 oC rise) 151 kW
* As per RC Standard.

Table 1-15: Cement Lined Domestic Hot Water Tanks (Medium Pressure Zone)

Two Tanks (4,100 Liters each) are selected to serve the medium pressure zone.

RCHR-G-FD-CLC-P4-ME-01 R01 Page 16 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

1.3.4 Fuel Fired Water Heaters (Serving Laundry Hot Water)


th
High Pressure Zone (11 floor up to Roof Floor)

Washing Capacity 188.6* kg/hr


Foodservice Facilities Number of meals per day 404 meals
(Specialty Restaurant) Estimated maximum hourly demand 16.56 L/h per kg
135 meals
Estimated recovery heating 0.0046 L/s per kg
Number of meals per hour (assuming 3 meals
Useable storage 3123 Liters
per day & 1 hour per meal)
Total Storage 4,462** Liters
Maximum hourly demand 5.7 l/h per meal
0.0012 l/s per meal Total Recovery 0.87 L/s
recovery heating
* Based on RC standard, 8.2 kg per day per guestroom, 80% utilizing. Assuming 8 hours full operation per day.
useable storage 767.6 liters
** Assume 70% useable factor.
Storage 1097 liters
0.16 l/s Table 1-17: Fuel Fired Water Heaters (Serving Laundry Water)
Recovery
Guestrooms Number of guestrooms 83 Room Three fuel fired water with 1,500 liters each are selected to Laundry domestic hot water.
Storage rate 38 liters per
guestroom
recovery rate 15 l/h per
guestroom 1.4 LPG Tanks
useable storage 3154 liters
Storage 4506 liters
Input Capacity LPG Consumption Number of operation Daily Consumption
Recovery 0.35 l/s Application
(kW) (Gal/hr)* hours per day Gal m3
Other public areas Number of Lavatory 15 Water Boiler 3315 113.2 8 906 3.43
Number of showers 0 Steam Boiler 1532 52 8 416 1.57
Demand per lavatory 30 L/h Laundry Fuel Fired
Demand per shower 284 L/h 527 18 8 144 0.55
Heaters
Demand Factor 0.25 Kitchen Equipment
199 7 8 54 0.21
Storage Factor 0.8 (Cooking)**
total demand 112.5 L/h Total Required LPG Volume per Day 1,520 5.76
useable storage 90 L * LPG Consumption is calculated based on 99,926 Btu/gal (considering 80% Butane, 20% Propane Mixer).
Storage 129 Liters ** For kitchens cooking equipment, diversity of 35% is taken into consideration as per CKP report
Recovery 0.031 L/s recommendation (Construction guidelines report).
Total Storage 5,731 liters Table 1-18: LPG Tanks
Total Recovery (at 55 oC rise) 124 kW
Table 1-16: Cement Lined Domestic Hot Water Tanks (High Pressure Zone)

Seven tanks (5 m3 capacity each) are provided which are adequate for approximately 6 days full operation
Two Tanks (2,900 Liters each) are selected to serve the high pressure zone. (considering 0.9 tank filling factor).

RCHR-G-FD-CLC-P4-ME-01 R01 Page 17 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

1.5 Fuel Tanks

1.5.1 Generator Fuel Tank


Generator Number of Fuel Consumption per Required Tank
Storage Period (hr)
Size generators generator (L/hr) Volume (L)

2,750 kVA 1 572.3* 24** 13,735

* Based on generator selection.


** Assuming 3 days operation, 8 hours per day.
Table 1-19: Generator Fuel Tank

1.5.2 Boilers Fuel Tank (Backup)

Input Capacity Fuel Consumption Number of Required Tank


Application Volume (m3)
(kW) per Unit (L/hr)* operation hours**
Water Boilers 3315 335 16 5.36

Steam Boilers 1532 155 16 2.50

Fuel Fired Water 53 16 0.85


527
Heaters
Total Tank Volume 8.71

* Fuel consumption is calculated based on 43,400 kJ/kg heating value and 820 kg/m 3 density.
** 8 hours operation per day for two days.
Table 1-20: Boilers Fuel Tanks (Backup)

RCHR-G-FD-CLC-P4-ME-01 R01 Page 18 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

2 Residence Building Pressure difference between lift and lobby (pressurized area) (Pa)
Air flow when all doors are closed [0.83 A P1/n] (m3/s)*
5
9
2.1 Heating, Ventilation and Air Conditioning *Assumed leakage factor is 2.
Table 2-1: Elevator-02 Pressurization
Refer to Appendix-B for detailed calculation

2.2 Smoke extraction and Pressurization:


Flow from opened door in adjacent story:

1.5.3 Elevators Pressurization Number of door openings 1


Leakage area of door openings (m2) 0.12
Pressure difference between lift/lobby and accommodation (Pa) 50
Flow from opened doors [0.83 A P1/n] (m3/s)* 0.7
*Assumed leakage factor is 2.
Table 2-2: Elevator-02 Pressurization

Total required pressurization flow:

Air flow when all doors are closed (m3/s) 9


Air flow when lift door is open on one floor 0.7
Total flow (m3/s) 9.7
Total required pressurization flow (m3/s) 11.2
(including 15% allowance for ducts leakage)
Table 2-3: Elevator-02 Pressurization

Figure 2-1: Elevators Pressurization


Elevator-03
Flow from closed doors:
Elevator -01

Refer to Fireman core calculation. Lift top vent 1


Lift top vent leakage area (m2) 0.1
Elevator-02
Shaft height (m) 78
Flow from closed doors: Shaft leakage area (m2) 0.15
Lift top vent 1 Number of lift doors open to stair lobby 4
Lift top vent leakage area (m2) 0.1 Leakage area per lift door into stair lobby area (m2) 0.06
Shaft height (m) 90 Number of lift doors open to unpressurised area 17
Shaft leakage area (m2) 0.15 Leakage area per lift door into unpressurised area (m2) 0.06
Number of lift doors open to stair lobby 4 Pressure difference between lift and unpressurised area (Pa) 50
Leakage area per lift door into stair lobby area (m2) 0.06 Pressure difference between lift and lobby (pressurized area) (Pa) 5
Number of lift doors open to unpressurised area 20 Air flow when all doors are closed [0.83 A P1/n] (m3/s)* 7.9
Leakage area per lift door into unpressurised area (m2) 0.06 *Assumed leakage factor is 2.
Pressure difference between lift and unpressurised area (Pa) 50
RCHR-G-FD-CLC-P4-ME-01 R01 Page 19 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

Table 2-4: Elevator-03 Pressurization

Flow from opened door in adjacent story: Flow from opened door in adjacent story:

Number of door openings 1


Leakage area of door openings (m2) 0.12
Number of door openings 1
Pressure difference between lift/lobby and accommodation (Pa) 50
Leakage area of door openings (m2) 0.12
Flow from opened doors [0.83 A P1/n] (m3/s) 0.7
Pressure difference between lift/lobby and accommodation (Pa) 50
Flow from opened doors [0.83 A P1/n] (m3/s)* 0.7 *Assumed leakage factor is 2.
*Assumed leakage factor is 2. Table 2-8: Elevator-04 Pressurization

Table 2-5: Elevator-03 Pressurization

Total required pressurization flow:


Total required pressurization flow:
Air flow when all doors are closed (m3/s) 9.0
Air flow when lift door is open on one floor 0.7
Air flow when all doors are closed (m3/s) 7.9
Total flow (m3/s) 9.7
Air flow when lift door is open on one floor 0.7
Total required pressurization flow (m3/s) 11.2
Total flow (m3/s) 8.6
(including 15% allowance for ducts leakage)
Total required pressurization flow (m3/s) 9.9
(including 15% allowance for ducts leakage) *Assumed leakage factor is 2.
Table 2-6: Elevator-03 Pressurization Table 2-9: Elevator-04 Pressurization

Elevator-04

Flow from closed doors: 1.5.4 Fireman Core (Staircase, elevator and lobby)
This arrangement shall comply with a Class B System (For means of escape and firefighting) and based on BS EN
12101-6.
Lift top vent 1
Lift top vent leakage area (m2) 0.1 Mode-1 (Pressure difference Criterion – Closed door scenario):
Shaft height (m) 90
Shaft leakage area (m2) 0.15 Left-Side Staircase
Number of lift doors open to stair lobby 4
All Doors Closed Scenario:
Leakage area per lift door into stair lobby area (m2) 0.06
Number of lift doors open to unpressurised area 20 Q = 0.83 x A x P1/n
Leakage area per lift door into unpressurised area (m2) 0.06
Pressure difference between lift and unpressurised area (Pa) 50 Where: Q: The leakage flowrate via gaps around closed doors (m3/s)
Pressure difference between lift and lobby (pressurized area) (Pa) 5
Air flow when all doors are closed [0.83 A P1/n] (m3/s)* 9.0 A: Total crack area (m2)
*Assumed leakage factor is 2.
P: Pressure difference criterion (Pa)
Table 2-7: Elevator-04 Pressurization
The pressure difference is calculated considering the following pressure relation, Staircase and elevator are
pressurized at 50Pa while the lobby to be pressurized at 45Pa.

RCHR-G-FD-CLC-P4-ME-01 R01 Page 20 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

F3 8.875 1 12.124
F4 9.0525 1 12.127
Total leakage area is calculated as shown in below table: F5 9.0525 1 12.127
F6 9.0525 1 12.127
Leakage across 50 Pa pressure difference F7 9.3075 1 12.130
Floor Internal walls Exterior walls Single-leaf door Single-leaf Total leakage F8 9.0525 1 12.127
area (m2) 1 area (m2) 2 opening into 3 door opening area x 10-3 (m2) 6 F9 9.23 1 12.129
outward 4
F10 9.23 1 12.129
C4 42.56 0.596
F11 9.23 1 12.129
C3 42.56 0.596
F12 9.49 1 12.133
C2 42.56 0.596
F13 9.23 1 12.129
C1 51.205 0.717
F14 10.295 1 12.144
GF 76.255 1 25.068
F15 10.295 1 12.144
F1 47.215 0.661
F16 10.295 1 12.144
F2 47.215 0.661
F17 10.585 1 12.148
F3 47.215 0.661
F18 11.89 1 12.166
F4 47.7475 0.668
F19 19.74 1 12.276
F5 47.7475 0.668
F6 47.7475 0.668 RF 0 0
F7 49.0925 0.687 Total 291.458
Table 2-11: Fireman core- Leakage across 5 Pa pressure difference
F8 47.7475 0.668
F9 48.28 0.676 (7) Leakage area for indoor wall calculated based on ALW/AWall = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
F10 48.28 0.676 (8) Leakage area for exterior wall calculated based on ALW/Awall = 0.7 x 10-4 (Table A.5, BS EN 12101-6)
F11 48.28 0.676
(9) Leakage area for single-leaf door opening into pressurized space = 0.012 m2 (1mm from side and above,
F12 49.64 0.695
7mm from bottom)
F13 74.0175 1.036
F14 53.25 0.746 (10)Leakage area for single-leaf door opening outward pressurized space = 0.024 m2
F15 53.25 0.746 (11)Leakage area for double-lead door = 0.03 m2 (Table A.3, BS EN 12101-6)
F16 53.25 0.746 (12)Total leakage area consider all leakage area as series (ATotal = A1 + A2 + A3 …..).
F17 54.75 0.767
F18 61.5 0.861
F19 54.6 0.764 Required Pressurization Flow is:
RF 64.75 1 16.533
Total 57.837 Q = 0.83 x 57.837x 10-3 x 501/2 + 0.83 x 291.458 x 10-3 x 51/2 = 0.880 m3/s
Table 2-10: Fireman core- Leakage across 50 Pa pressure difference
Applying 50% Safety factor,
Leakage across 5 Pa pressure difference
Floor Internal walls Exterior walls Single-leaf door Single-leaf Total leakage Q = 0.88x 1.5 = 1.32 m3/s
area (m2) 1 area (m2) 2 opening into 3 door opening area x 10-3 (m2) 6
outward 4 - Elevator-1 Shaft:
C4 8 1 12.112
C3 8 1 12.112 Elevator shaft height = 87.9 m
C2 8 1 12.112
C1 9.625 1 12.135 Leakage across 5 Pa pressure difference:
GF 21.715 1 12.304
F1 8.875 1 12.124 Internal wall length = 2.75 m (Area = 2.75 x 87.9 =241.7m2)
F2 8.875 1 12.124
RCHR-G-FD-CLC-P4-ME-01 R01 Page 21 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

Number of doors = 24 doors F15 25.03 1 12.350 45 0.069 0.103


F16 25.03 1 12.350 45 0.069 0.103
Leakage are = (241.7x 0.14 x 10-4) + (24 x 0.06) = 1.443 m2 F17 25.73 1 12.360 45 0.069 0.103
F18 28.91 1 12.405 45 0.069 0.104
Flow rate = 0.83 x 1.443 x 51/2 = 2.679 m3/s F19 36.75 2 24.515 45 0.136 0.205
Total 3.974
Leakage across 50 Pa pressure difference:
Table 2-12: Fireman core-Lobby Total Flow

Internal wall length = 3.45x2+2.75 = 9.65 m (Area = 9.65 x 87.9 = 848.235 m2) (7) Leakage area for indoor wall calculated based on ALW/AWall = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
(8) Leakage area for exterior wall calculated based on ALW/Awall = 0.7 x 10-4 (Table A.5, BS EN 12101-6)
Lift vent area = 0.1 m2
(9) Leakage area for single-leaf door opening into pressurized space = 0.012 m2 (1mm from side and above,
Total leakage are = (848.235 x 0.14 x 10-4)+ 0.1 = 0.1119 m2 7mm from bottom)
(10)Leakage area for single-leaf door opening outward pressurized space = 0.024 m2
Flow rate = 0.83 x 0.1119 x 501/2 = 0.657 m3/s (11)Leakage area for double-lead door = 0.03 m2 (Table A.3, BS EN 12101-6)
Applying 50% safety factor: (12)Total leakage area consider all leakage area as series (ATotal = A1 + A2 + A3 …..)

Q = (2.679 + 0.657) x 1.5 = 5.004 m3/s Total air flow for mode-1 = 1.32+ 5.004 + 3.974 = 10.298 m3/s

- Lobby: Mode-3 (Airflow Criterion – Open door scenario):

Floor Internal Exterior Number of Number of Number Total Pressure Flow Total - Staircase:
Wall Wall Single-leaf Single-leaf of Leakage Difference from Flow
Flow through fire story:
Area Area door door Double- Area x (Pa) leakage applying
(m2)1 (m2)2 opening opening leaf 10-3 areas 50%  Number of opened door = 1
into a outwards a Door5 (m2)6 safety
pressurized pressurized factor  Open door area = 2 m2
space3 space4 (m3/s)  Assumed velocity across opened door = 2 m/s
C4 19.20 2 24.269 45 0.135 0.203  Air flow through opened door = 2 x 2 = 4 m3/s
C3 19.20 2 24.269 45 0.135 0.203
C2 19.20 2 24.269 45 0.135 0.203 Resulted pressure within the stair case:
C1 23.10 2 24.323 45 0.135 0.203  Assumed velocity across air exit = 2.5 m/s
GF 26.26 2 24.368 45 0.136 0.204
 Flow across air exit = 4 m3/s
F1 21.30 1 12.298 45 0.068 0.103
 Air exit area = 4 / 2.5 = 1.6 m2
F2 21.30 1 12.298 45 0.068 0.103
 Leakage effective area:
F3 21.30 1 12.298 45 0.068 0.103
F4 21.30 2 24.298 45 0.135 0.203 1 1 1
−1/2
1 1 1 −1/2
F5 21.30 2 24.298 45 0.135 0.203 Aeff = [ + + ] =[ + + ] = 1.06 m2
𝐴2𝑠𝑡𝑎𝑖𝑟 𝑑𝑜𝑜𝑟 𝐴2𝑙𝑜𝑏𝑏𝑦 𝑑𝑜𝑜𝑟 𝐴2𝑎𝑖𝑟 𝑒𝑥𝑖𝑡 22 22 1.62
F6 21.30 2 24.298 45 0.135 0.203
𝑄 𝑛 4 2
F7 21.90 2 24.307 45 0.135 0.203  Pressure within staircase = (0.83 𝐴) = (0.83 𝑥 1.06 ) = 20.69 Pa
F8 21.30 2 24.298 45 0.135 0.203
F9 21.30 2 24.298 45 0.135 0.203
F10 21.30 2 24.298 45 0.135 0.203
F11 21.30 2 24.298 45 0.135 0.203 Flow through opened door at ground floor:
F12 21.90 2 24.307 45 0.135 0.203  Door area = 2 m2
F13 25.03 1 12.350 45 0.069 0.103  Air flow through opened door = 0.83 x 2 x 20.69/2 = 7.55 m3/s
F14 25.03 1 12.350 45 0.069 0.103
RCHR-G-FD-CLC-P4-ME-01 R01 Page 22 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 Air flow through leakage area = 0.83 x 48.894 x 10-3 x 20.69/2 = 0.185 m3/s
 Applying 50% safety factor, 0.185 x 1.5 = 0.278m3/s
Flow through opened door at adjacent story:

 Assumption: stair door of adjacent story is opened while lobby door to accommodation is closed.
 Leakage effective area:
−1/2 −1/2
Total Pressurization flow
1 1 1 1
Aeff = [ + ] =[ 2 +
] = 0.012 m2
𝐴2𝑠𝑡𝑎𝑖𝑟 𝑑𝑜𝑜𝑟 𝐴2𝑙𝑜𝑏𝑏𝑦 𝑑𝑜𝑜𝑟 𝑙𝑒𝑎𝑘𝑎𝑔𝑒 𝑎𝑟𝑒𝑎 2 0.012 2
Q = 4 + 7.55 + 0.045 + 0.278 = 11.823m3/s
 Air flow = 0.83 x 0.012 x 20.69 = 0.045 m /s /2 3

- Elevator Shaft:
Flow from other leakages:
Calculation to be done considering one door opened in the adjacent story:
Floor Internal walls area Exterior walls area Single-leaf door Total leakage area
(m2) 1 (m2) 2 opening into 3 x 10-3 (m2) 6 Flow from opened door:
C4 42.560 0.59584
C3 42.560 0.59584  Door lift dimension is 1.3m x 2.4 m.
C2 42.560 0.59584  Open door leakage = ((1.3 + 2.4) x 2) x 0.025 = 0.185 m2
C1 51.205 0.71687
 Leakage from open door = 0.83 x 0.185 x 501/2 = 1.086 m3/s
GF 76.255 1.06757
F1 47.215 0.66101 Flow from other leakages:
F2 47.215 0.66101
F3 47.215 0.66101  Elevator shaft height = 87.9 m
F4 47.748 0.668465
F5 47.748 0.668465  Leakage across 5 Pa pressure difference:
F6 47.748 0.668465
o Internal wall length = 2.75 m (Area = 2.75 x 87.9 =241.7m2)
F7 49.093 0.687295
o Number of doors = 24 doors
F8 47.748 0.668465
F9 48.280 0.67592 o Leakage area = (241.7 x 0.14 x 10-4) + (24 x 0.06) = 1.443 m2
F10 48.280 0.67592 o Flow rate = 0.83 x 1.443 x 51/2 = 2.679
F11 48.280 0.67592  Leakage across 50 Pa pressure difference:
F12 49.640 0.69496 o Internal wall length = 3.45x2+2.75 = 9.65 m (Area = 9.65 x 87.9 = 848.235 m 2)
F13 74.018 1.036245 o Lift vent area = 0.1 m2
F14 53.250 0.7455 o Total leakage are = (848.235 x 0.14 x 10-4)+ 0.1 = 0.1119 m2
F15 53.250 0.7455 o Flow rate = 0.83 x 0.1119 x 501/2 = 0.657 m3/s
F16 53.250 0.7455
F17 54.750 0.7665
F18 61.500 0.861  Total flow from leakages applying 50% safety factor
F19 54.600 15.822 = 2.678 + 0.657 = 3.335 m3/s
RF 64.758 54.600 1 16.53304
Total required flow:
Total leakage area 48.894
Table 2-13: Fireman core-Flow from Other Leakages
Q = 1.086+3.335= 4.421 m3/s
(4) Leakage area for indoor wall calculated based on ALW/AWall = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
(5) Leakage area for exterior wall calculated based on ALW/Awall = 0.7 x 10-4 (Table A.5, BS EN 12101-6)
(6) Leakage area for single-leaf door opening into pressurized space = 0.012 m2 (1mm from side and above, - Lobby:
7mm from bottom)
Same as mode-1
RCHR-G-FD-CLC-P4-ME-01 R01 Page 23 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

SUMMARY Where: Q: The leakage flowrate via gaps around closed doors (m3/s)

Calculated total airflow for mode-3 A: Total crack area (m2)

 Air flow to fire floor = 4 m3/s P: Pressure difference criterion (Pa)


 Air flow to exit door (ground floor) = 7.55 m3/s
 Air flow for lift shaft = 4.421 m3/s
 Air flow through all other leakages = 0.045+0.278+3.974= 4.297 m3/s The pressure difference is calculated considering the following pressure relation, Staircase is pressurized at 50Pa
 Total = 4 + 7.55 + 4.421 + 4.297= 20.268 m3/s while the lobby to be pressurized at 45Pa.

Total flow of staircase pressurization = 11.823 m³/s

Total flow of fire lobby and lift pressurization = 4.421+ 3.974 = 8.395 m³/s Total leakage area is calculated as shown in below table:

Select two fans (1 duty & 1 standby) each capable to handle 8.395 m3/s minimum to serve the fire lobby and lift. Leakage across 50 Pa pressure difference
Floor Internal walls area Exterior walls area Single-leaf door Total leakage area x
Select two fans (1 duty & 1 standby) each capable to handle 11.823 m3/s minimum to serve the staircase. (m2) 1 (m2) 2 opening into 3 10-3 (m2) 6
C4 46.42 0.650
Calculated area for air/smoke relief vent
C3 46.42 0.650
C2 46.42 0.650
 Air flow to fire floor = 4 m3/s
C1 55.84 0.782
 Velocity through relief vent = 2.5 m/s
GF 68.18 0.954
 Area of air/smoke relief vent = 4 / 2.5 = 1.6 m2 F1 31.88 0.446
F2 31.74 0.444
F3 31.74 0.444
Calculated area of pressure relief F4 31.74 0.444
F5 31.88 0.446
𝑄 (20.218−10.298) F6 31.88 0.446
 Area of pressure relief = = = 1.69 m2
0.83 𝑥 𝑃 0.5 0.83 𝑥 500.5 F7 32.78 0.459
F8 32.84 0.460
However, Variable speed fans with dampers controlled by pressure sensors will be used instead of providing the
F9 32.77 0.459
pressure relief. Highlighting that the system shall be able to achieve over 90% of the new air supply requirements F10 32.77 0.459
within 3 second of a door being opened or closed. (as per BS EN 12101-6, paragraph 5.4.2.5) F11 32.77 0.459
F12 33.69 0.472
F13 32.77 0.459
F14 32.77 0.459
1.5.5 Escape Core (Staircase and lobby)
F15 32.77 0.459
This arrangement shall comply with a Class E System (For means of escape only) and based on BS EN 12101-6. F16 32.77 0.459
F17 33.69 0.472
Mode-1 (All doors closed): F18 37.84 0.530
F19 38.77 0.543
- Staircase:
RF 49.58 1 15.471
In this mode, the air flow is calculated assuming all doors are closed as below: Total 27.974
Table 2-14: Escape core- Leakage across 50 Pa pressure difference
1/n
Q = 0.83 x A x P

RCHR-G-FD-CLC-P4-ME-01 R01 Page 24 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

Leakage across 5 Pa pressure difference


Floor Internal walls Single-leaf door Single-leaf door Double-leaf Total leakage - Lobby:
2 1
area (m ) opening into 3 opening Door 5 area x 10-3 (m2 )
outward4 6

C4 4.8 1 12.067 Floo Intern Exterior Lift Number Number Numbe Total Pressure Flow Total
C3 4.8 1 12.067 r al Wall well of Single- of Single- r of Lift Leakag Differenc from Flow
C2 4.8 1 12.067 Wall Area wall leaf door leaf door Landin e Area e (Pa) leakag applyin
C1 5.775 1 12.081 Area (m2)2 s opening opening g Door6 x 10-3 e g 50%
GF 12.625 1 24.177 (m2)1 Area into a outwards (m2)7 areas safety
F1 5.325 1 12.075 (m²) pressurize a factor
F2 5.538 1 12.078 ³ d space4 pressurize (m3/s)
F3 5.538 1 12.078 d space5
F4 5.538 1 12.078 C4 34.88 2 24.488 45 0.136 0.205
F5 5.5735 1 12.078 C3 34.88 2 24.488 45 0.136 0.205
F6 5.5735 1 12.078 C2 34.88 2 24.488 45 0.136 0.205
F7 5.7305 1 12.080 C1 41.97 2 24.588 45 0.137 0.205
F8 5.68 1 12.080 GF 13.6 111.69
F9 5.751 1 12.081 88.63 35 2 1 1 5 45 0.622 0.933
F10 5.751 1 12.081 F1 38.70 2 12.542 45 0.070 0.105
F11 5.751 1 12.081 F2 38.70 2 12.542 45 0.070 0.105
F12 5.913 1 12.083 F3 38.70 2 12.542 45 0.070 0.105
F13 5.751 1 12.081 F4 38.70 2 24.542 45 0.137 0.205
F14 5.751 1 12.081 F5 38.70 2 24.542 45 0.137 0.205
F15 5.751 1 12.081 F6 38.70 2 24.542 45 0.137 0.205
F16 5.751 1 12.081 F7 39.79 2 24.557 45 0.137 0.205
F17 5.913 1 12.083 F8 39.05 2 24.547 45 0.137 0.205
F18 6.642 1 1 12.093 F9 39.05 2 24.547 45 0.137 0.205
F19 6.804 1 12.095 F10 39.05 2 24.547 45 0.137 0.205
Total 302.00 F11 39.05 2 24.547 45 0.137 0.205
Table 2-15: Escape core-Leakage across 5 Pa pressure difference F12 40.15 2 24.562 45 0.137 0.205
F13 39.05 2 12.547 45 0.070 0.105
(1) Leakage area for indoor wall calculated based on ALW/AWall = 0.14 x 10-4 (Table A.5, BS EN 12101-6) F14 39.05 2 12.547 45 0.070 0.105
(2) Leakage area for exterior wall calculated based on ALW/Awall = 0.7 x 10-4 (Table A.5, BS EN 12101-6) F15 39.05 2 12.547 45 0.070 0.105
(3) Leakage area for single-leaf door opening into pressurized space = 0.012 m2 (1mm from side and above, F16 39.05 2 12.547 45 0.070 0.105
7mm from bottom) F17 40.15 2 12.562 45 0.070 0.105
(4) Leakage area for single-leaf door opening outward pressurized space = 0.024 m2 F18 71.34 2 12.999 45 0.072 0.109
(5) Leakage area for double-lead door = 0.03 m2 (Table A.3, BS EN 12101-6) F19 46.20 2 24.647 0.137 0.206
(6) Total leakage area consider all leakage area as series (ATotal = A1 + A2 + A3 …..). Total 4.750
Table 2-16: Escape core-Lobby Total Flow

Required Pressurization Flow is: (1) Leakage area for indoor wall calculated based on ALW/AWall = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
Q = 0.83 x 27.974 x 10-3 x 501/2 + 0.83 x 302.00 x 10-3x51/2 = 0.725 m3/s (2) Leakage area for exterior wall calculated based on ALW/Awall = 0.7 x 10-4 (Table A.5, BS EN 12101-6)
(3) Leakage area for Lift well wall calculated based on ALW/Awall = 0.18 x 10-3 (Table A.5, BS EN 12101-6)
Applying 50% Safety factor, (4) Leakage area for single-leaf door opening into pressurized space = 0.012 m2 (1mm from side and above,
7mm from bottom)
Q = 0.725 x 1.5 = 1.09 m3/s
(5) Leakage area for single-leaf door opening outward pressurized space = 0.024 m2
RCHR-G-FD-CLC-P4-ME-01 R01 Page 25 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

(6) Leakage area for Lift landing door = 0.06 m2 (Table A.3, BS EN 12101-6) In this mode, the calculation is performed assuming one open door at fire floor, one open exit door and open
(7) Total leakage area consider all leakage area as series (ATotal = A1 + A2 + A3 …..) accommodation door other than fire floor.

Air flow through open fire door:

Total air flow for mode-1 = 1.09 + 4.750 = 5.84 m3/s  Door area = 2 m2
 Velocity = 0.75 m/s
 Flow = 2 x 0.75 = 1.5 m3/s
Mode-2 (Pressure criterion):
Resulted pressure within the stair case:
In this mode, the calculation is performed assuming open exit door in addition to two open accommodation  Assumed velocity across air exit = 2.5 m/s
doors other than fire floor (maintaining 10Pa pressure):  Flow across air exit = 1.5 m3/s
 Air exit area = 1.5 / 2.5 = 0.6 m2
Air flow through open exit door:
 Leakage effective area:
 Door Area = 2 m2 −1/2 −1/2
1 1 1 1 1 1
 Flow rate = 0.83 x 2 x 101/2 = 5.249 m3/s Aeff = [𝐴2 + 𝐴2𝑙𝑜𝑏𝑏𝑦 𝑑𝑜𝑜𝑟
+ 𝐴2𝑎𝑖𝑟 𝑒𝑥𝑖𝑡
] = [22 + 22
+ 0.62
] = 0.55 m2
𝑠𝑡𝑎𝑖𝑟 𝑑𝑜𝑜𝑟

Air flow through opened accommodation doors: 𝑄 𝑛 1.5 2


 Pressure within staircase = (0.83 𝐴) = (0.83 𝑥 0.55) = 10.8 Pa
 Assume the below floors as the worst case:
Airflow through open exit door:
o First floor, area = 2016.07 m2.
o Second floor, area = 2296.17 m2.  Door area = 2 m2
 Leakage area through floors:  Air flow through opened door = 0.83 x 2 x 10.81/2 = 5.455 m3/s

Floor Floor Leakage area ratio Exterior walls area (m2) Leakage area Total leakage
Airflow through open accommodation door:
Area area (ALF/AFloor)1 ratio area (m2)
(m2) (ALW/Awall)2  Assume second floor as the worst case.
First 2016.07 0.52 x 10-4 869.75 (245 L x 3.55H) 0.42 x 10-3 0.575  Airflow = 0.83 x 0.577 x 10.81/2 = 1.57 m3/s
Floor x2
Second 2296.17 0.52 x 10-4 805.85 (227 L x 3.55 H) 0.42 x 10-3 0.577
Floor x2
Table 2-17: Leakage Area through Floors Adding mode-1, total air flow for mode-3 = 1.5 + 5.455 + 1.57 + 5.84 = 14.365 m3/s

(3) Assuming average tightness (table A.6, BS EN 12101-6). Summery:


(4) Assuming loose tightness (table A.5, BS EN 12101-6).
 Mode-1:
 Air flow = 0.83 x (0.575 + 0.577) x 101/2 = 3.02 m3/s o Airflow required to stair = 1.09 m3/s
o Air flow required to lobby = 4.750 m3/s
o Total airflow = 5.84 m3/s
 Mode-2 (Pressure criterion):
Adding mode-1, total air flow for mode-2 = 5.249 + 3.02 +5.84 = 14.109 m3/s
o Airflow through open exit door = 5.249 m3/s
Mode-2 (Velocity criterion): o Airflow through two open accommodation doors = 3.02 m3/s
o Total air flow = 14.109 m3/s
o Airflow to stair = 9.359 m3/s

RCHR-G-FD-CLC-P4-ME-01 R01 Page 26 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

o Air flow to lobby = 4.750 m3/s


 Mode-2 (Velocity criterion): Leakage through floors
o Airflow through open fire floor door = 1.5 m3/s
 Floor area = 116 m2
o Airflow through open exit door = 5.455 m3/s
 Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
o Airflow through open accommodation door = 1.57 m3/s
 Leakage area = 0.006032 m2
o Total airflow = 14.365 m3/s
 Multiplied by two to cater leakage from below and above slab floor = 0.012064 m2
o Airflow to stair = 9.615 m3/s
o Airflow to lobby = 4.750 m3/s  Airflow through leakage =0.83 x 0.012064 x 501/2 = 0.0708 m3/s

Select two fans (1 duty & 1 standby) each capable to handle 14.365 m3/s minimum to serve the escape stair Leakage through walls
and lobby.  Length = 108 m2
 Calculated area of air / smoke relief vent:  Height = 3.55 m
o Airflow to fire floor = 1.5 m3/s  Area = 383.4 m2
o Area of air/relief smoke vent = 1.5 / 2.5 = 0.6 m2  Leakage factor (ALW/AWall) = 0.11 x 10-3
 Leakage area = 0.042174 m2
 Calculated area of pressure relief:  Airflow through leakage = 0.83 x 0.042174 x 501/2 = 0.2475 m3/s
𝑄 (14.365−5.84)
o = = 1.45 m2 Leakage through doors
0.83 𝑥 𝑃 0.5 0.83 𝑥 500.5

However, Variable speed fans with dampers controlled by pressure sensors will be used instead of providing  Number of single-leaf doors opened outward pressurized space = 9
the pressure relief. Highlighting that the system shall be able to achieve over 90% of the new air supply  Number of lift doors = 3
requirements within 3 second of a door being opened or closed. (As per BS EN 12101-6, paragraph 5.4.2.5).  Leakage area for single-leaf door opening outward pressurized space = 0.024 m2
 Leakage area for lift door opening into pressurized space = 0.06 m2
1.5.6 Refuge Areas
 Total leakage area = 9 x 0.024 + 3 x 0.06 = 0.396 m2
Refuge Area (2nd floor) Pressurization  Airflow through leakage = 0.83 x 0.396 x 501/2 = 2.324 m3/s

Total Airflow

 Total airflow = 0.0708 + 0.2475 + 2.324 = 2.6423 m3/s

Applying 50% safety factor = 2.6423 x 1.5 = 3.96 m3/s

Figure 2-2: Second Floor Refuge Area Pressurization

RCHR-G-FD-CLC-P4-ME-01 R01 Page 27 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 Number of single-leaf doors opened outward pressurized space = 3


 Number of double-leaf doors = 1
Refuge Area (8th floor) Pressurization
 Number of lift doors = 3
 Leakage area for single-leaf door opening outward pressurized space = 0.024 m2
 Leakage area for double-leaf door opening into pressurized space = 0.03 m2
 Leakage area for lift door opening into pressurized space = 0.06 m2
 Total leakage area = 3 x 0.024 + 1 x 0.03 + 3 x 0.06= 0.282 m2
 Airflow through leakage = 0.83 x 0.282 x 501/2 = 1.655 m3/s

Total Airflow

 Total airflow = 0.06653 + 0.2384 + 1.655 = 1.96 m3/s


 Applying 50% safety factor = 1.96 x 1.5 = 2.94 m3/s

Refuge area (14th floor) Pressurization

Figure 2-3: Eighth Floor Refuge Area Pressurization

Leakage through floors

 Floor area = 109 m2


 Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
 Leakage area = 0.005668 m2
 Multiplied by two to cater leakage from below and above slab floor = 0.011336 m2
 Airflow through leakage = 0.83 x 0.011336 x 501/2 = 0.06653 m3/s

Leakage through walls

 Length = 104 m2
 Height = 3.55 m
 Area = 369.2 m2
 Leakage factor (ALW/AWall) = 0.11 x 10-3 Figure 2-4: Fourteenth Floor Refuge Area Pressurization

 Leakage area = 0.040612m2 Leakage through floors


 Airflow through leakage = 0.83 x 0.040612 x 501/2 = 0.2384 m3/s
 Floor area = 94 m2
Leakage through doors  Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
 Leakage area = 0.004888 m2
RCHR-G-FD-CLC-P4-ME-01 R01 Page 28 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 Multiplied by two to cater leakage from below and above slab floor = 0.009776 m2 Leakage area through walls:
 Airflow through leakage = 0.83 x 0.009776 x 501/2 = 0.05738 m3/s
 Internal walls area = 110 x 3.55 = 390.5 m2
Leakage through walls  Leakage factor (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
 Leakage area = 390.5 x 0.14 x 10-4 = 0.005467 m2
 Length = 85 m2
 Height = 3.55 m Leakage area through doors:
 Area = 301.75 m2
 Number of single leaf door opening outward = 9
 Leakage factor (ALW/AWall) = 0.11 x 10-3
 Number of lift doors = 3
 Leakage area = 0.0331925 m2
 Leakage area for single-leaf door opening outward pressurized space = 0.024 m2
 Airflow through leakage = 0.83 x 0.0331925 x 501/2 = 0.1948 m3/s
 Leakage area for lift door opening into pressurized space = 0.06 m2
Leakage through doors  Leakage area = (9 x 0.024) + (3 x 0.06) = 0.396 m2

 Number of single-leaf doors opened outward pressurized space = 4 Required flowrate:


 Number of lift doors = 3
Q = 0.83 x (0.0121 + 0.005467 + 0.396) x 12.51/2 = 1.214 m3/s
 Leakage area for single-leaf door opening outward pressurized space = 0.024 m2
 Leakage area for lift door opening into pressurized space = 0.06 m2 Required smoke extraction flowrate:
 Total leakage area = 4 x 0.024 + 3 x 0.06 = 0.276 m2
 Airflow through leakage = 0.83 x 0.276 x 501/2 = 1.62 m3/s Q = 0.83 x (0.008164 + 0.00441 + 0.228) x 12.51/2 = 0.706 m3/s

Required fan flow to cover the stairs air smoke relief vent and corridor smoke extraction will be equal to

Total Airflow 1.214 m³/s + 4 m³/s + 1.5 m³/s = 6.714 m³/s minimum to serve the apartments floors corridors smoke extraction.

 Total airflow = 0.05738 + 0.1948 + 1.62 = 1.872 m3/s Required pressurization flowrate:
 Applying 50% safety factor = 1.872 x 1.5 = 2.81 m3/s Q = 2 x 1.214 = 2.428 m3/s

Flowrate of 2.428 m3/s minimum to serve the apartments floors corridors pressurization.

Ground Floor
Total for all refuge areas: Leakage area through floors:
Total fan flow rate = 3.96 + 2.94 + 2.81 = 9.71 m3/s
 Floor area = 247 m2
1.5.7 Corridors smoke extraction and Makeup Air:  Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)
 Leakage area = 2 x 247 x 0.52 x 10-4 = 0.0257 m2
Apartment floors
Leakage area through walls:
 Assume 2nd floor:

Leakage area through floors:  Internal walls area = 142 x 4.750 = 674.5 m2
 Internal double volume walls area = 32 x 8.300 = 265.6 m2
 Floor area = 116 m2  Leakage factor (ALW/AWall) = 0.14 x 10-4 (Table A.5, BS EN 12101-6)
 Leakage area ratio (ALF/AFloor) = 0.52 x 10-4 (Table A.6, BS EN 12101-6)  Leakage area = (647.5 + 265.6) x 0.14 x 10-4 = 0.0132 m2
 Leakage area = 2 x 116 x 0.52 x 10-4 = 0.0121 m2
RCHR-G-FD-CLC-P4-ME-01 R01 Page 29 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

Leakage area through doors:


Domestic Water Demand
 Number of single leaf door opening outward = 6 Daily Total Weekly
Number of Total Daily
 Number of single leaf door opening into = 3 Unit Consumption Consumption
Units Consumption (L)
 Number of double leaf doors = 5 (L/day) (m3)
 Number of lift doors = 3 Apartments 90 800 72,000 216
 Leakage area for single-leaf door opening outward pressurized space = 0.024 m2 Fire Fighting Demand
 Leakage area for single-leaf door opening into pressurized space = 0.012 m2 Tank Volume Tank Volume (m3)
Flow Rate (gpm) Duration (min)
(gallons)
 Leakage area for double-leaf door = 0.03 m2
1,250 60 75,000 284
 Leakage area for lift door opening into pressurized space = 0.06 m2 Total Water Tank Demand (m³) 500
 Leakage area = (6 x 0.024)+ (3 x 0.012) + (5 x 0.03) + (3 x 0.06) = 0.51 m2 Table 2-19: Domestic Water Tank Cpacity

Required flowrate: Irrigation Tank Capacity

Q = 0.83 x (0.0257 + 0.0132 + 0.51) x 12.51/2 = 1.611 m3/s


Daily Peak Demand (m³/day) Storage (days) Storage Capacity (m3)
3
Flowrate of 1.611 m /s minimum to serve the ground floor corridors smoke extraction. 5 16 80
Table 2-20: Irrigation Tank Capacity
Required pressurization flowrate:
2.4 Fuel Tanks
Q = 1.614 m3/s

Flowrate of 1.611 m3/s minimum to serve the ground floor corridors pressurization. Fuel Tank Capacity

Car Park Ventilation: Storage Capacity


Application Capacity (kW)
(m3)*
Smoke Normal Generator 1,280 9.5
10 ACH 6 ACH Table 2-21: Fuel Tank Capacity
Area
Floor Height (m)* Smoke Extraction & Smoke Extraction &
(m2) * Storage capacity is based on 24 hours generators run.
Make-up Air Flow Make-up Air Flow
(l/s) (l/s)
Cellar-1 3370 3.85 38382 23029

Cellar-2 3723 3.2 33093 19856

Cellar-3 3723 3.2 33093 19856

Cellar-4 3370 3.2 29956 17973

Table 2-18: Car Park Ventilation.

* Floor height measured from slab to slab.

2.3 Water Tanks


Water and Fire Tank Capacity
RCHR-G-FD-CLC-P4-ME-01 R01 Page 30 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

3 Water Features & Pools a) Hotel Floor 1 Outdoor Pool: One overflow type outdoor pool (Swimming Pool-Hotel-Type 1) is to be
conceived in the floor 1 of the hotel. This pool will be the public main pool of the hotel.
b) Hotel Floor 1 Jacuzzi: One skimmer type outdoor Jacuzzi (Jacuzzi-Hotel) adjacent to the Swimming
3.1 Introduction
Pool-Hotel-Type 1 is to be conceived in the floor 1 of the hotel. This Jacuzzi will include hydrojets and
The Ritz Carlton Hotel and Residences project will be run by the luxury hotel chain Ritz Carlton Hotels (the seat bubblers.
Operator) and is expected to set a new benchmark for hospitality in Jordan and the region. The project is located c) Hotel Floor 16 Pool: One skimmer type outdoor swimming pool (Swimming Pool-Hotel-Type 2) is to
in the already prestigious area of the 5th circle in proximity to the Four Seasons Hotel, The Sheraton Hotel, and be conceived in the floor 16 of the hotel. This pool will include hydrojets and seat bubblers.
d) Hotel Floor 1 Indoor Pool: One Overflow type indoor pool (swimming Pool-Hotel-Type 3) is to be
the upcoming Fairmont Hotel along the main Zahran Street and Kindi Street. An elegantly proportioned hotel
conceived in the floor 1 of the hotel. This pool will be the public indoor pool pf the hotel accessed
tower and residence accommodations tower, inspired by classical ornamentation, will add a level of sophistication from the Spa / Gym.
to the city and act as a primary gathering space for friends, family and meetings. e) Residences Floor 13 Pool: One skimmer type outdoor swimming pool (Swimming Pool-Residences-
Type 3) is to be conceived in the floor 13 of the Residences. This pool will include hydrojets and seat
The project will have two components: The first is the Ritz Carlton Hotel with a built-up area of approximately bubblers.
28,100sqm, 19 floors (+72m. high), adding around 233 keys, a 1000sqm. Banquet Hall, two specialty restaurants, f) Residences Floor 18 Pool A: One skimmer type outdoor swimming pool (Swimming Pool-Residences-
spa, external gardens and pools. The second component is the branded Ritz Carlton Residences with an estimated Type 1) is to be conceived in the floor 18 of the Residences. This pool will include hydrojets and seat
built-up area of 36,600sqm, 20 floors (+73.40m. high), offering around 90 luxurious apartments with all supporting bubblers.
services and amenities. Four basement levels with approximately 43,240sqm of built-up area are expected to g) Residences Floor 18 Pool B: One skimmer type outdoor swimming pool (Swimming Pool-Residences-
Type 2) is to be conceived in the floor 18 of the Residences. This pool will include hydrojets and seat
include services, parking and BOH areas.
bubblers.
The project will include several water features to enhance the landscape scenery and several swimming pools as h) Residences Floor GF Indoor Pool: One Overflow type indoor pool (Swimming Pool-Residences-Type
4) is to be conceived in the ground floor of the Residences. This pool will be the public main pool of
a part of the recreational policy of the chain.
the Residences.
i) Residences Floor GF Jacuzzi: One skimmer type indoor Jacuzzi (Jacuzzi-Residences) adjacent to
These water features and swimming pools will be studied in this report.
swimming pool-residences-type 4 is to be conceived in the GF floor of the residences. This Jacuzzi will
include hydrojets and seat bubblers.
3.2 Scope of Work
The project includes as a part of its landscape scenery, five water features with various water effects giving life to This report will give a general description for all the mechanical systems used in the design of all the water
the external and internal landscape: features and pools. For this, it will include the standards and codes and the design data used for the design
elaboration along with the schematic flow diagrams of all the water features and pools.
a) Gateway Entrance of the project: Two similar water features (Water Feature-General) are to be
installed at the Gateway entrance of the project, one at each side of the gateway. This water feature 3.3 Standards & Code
is a wall mounted fountain with double bowls and a lion face sculpture.
b) Hotel Drop-Off: One water feature (Water Feature-Hotel-Type 1) is to be installed at the drop-off The standards and codes used and followed to elaborate the design of the water features and swimming
zone of the hotel. This water feature includes three concentric elliptical basins cascading one on the pools are:
other with 5 fountain nozzles in the upper basin.
c) Hotel Garden: One water feature (Water Feature-Hotel-Type 2) is to be installed in the garden of the a) The Virginia Graeme Baker Pool and Spa Safety Act
hotel. This water feature includes two concentric semi-elliptical basins with a waterfall from the upper b) The Ritz Carlton Hotel Design Standards-Module 4-Recreation (January 2013)
basin to the lower basin while having a scattered white water wall effect. c) The Ritz Carlton Residences Design Standards-Module 4-Recreation (June 2015)
d) Residences Executive Terrace: One water feature (Water Feature-Residences) is to be installed in the d) International swimming pool and spa code (ISPSC code by ICC)
residences executive terrace. This water feature includes 2 half rectangular basins with the upper e) American Society of Heating, Refrigerating and Air-conditioning Engineers Standards (Ashrae)
basin cascading on the lower basin. f) British Standards (BS)
e) Colonnade Extension: One water feature (Water Feature-Hotel-Type 3) is to be installed in the hotel g) WORLD HEALTH ORGANIZATION (WHO) Guidelines for safe recreational water environments
extension. This water feature includes 2 concentric circular basins with 1 basin overflowing to the h) Recommended Standards for Swimming Pool Design and Operation Policies for the Review and
lower basin. Approval of Plans and Specifications for Public Pools by "Great Lakes--Upper Mississippi River Board
Additionally, this project includes as a part of its recreational policy, nine swimming pools/Jacuzzi at various of State and Provincial Public Health and Environmental Managers"
locations in the hotel and residences:

RCHR-G-FD-CLC-P4-ME-01 R01 Page 31 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

3.4 Design Data 3.5 Filtration & Treatment Systems Description


In this paragraph, the basic design parameters used in the design, calculations and sizing of the equipment will a) Filtration:
be listed.
The raw water is pumped from its storage tank using the filter feed pumps and enters the sand filter
a) Design Temperatures: where the suspended matters are removed down to 30 microns.
 Summer Outdoor Temperature: 35°C
 Winter Outdoor Temperature: 10°C The Sand Filter is fitted with collector arms and diffuser made in UPVC to increase the filtering surface
 Swimming Pool Desired Temperature when Heating is on: 29°C and improves efficiency. As well as pressure gauge, manual air and water purges and a multiport valve
 Swimming Pool Maximum Temperature in Summer when Heating is off: 33°C (No cooling will with six positions filter, backwash, rinse, recirculate, waste & closed.
be conceived)
 Jacuzzi/Whirl pools Desired Temperature: 40°C A predetermined pressure drop or a reduction of flow rate means that sufficient solids have been
 Maximum Temperature Rise: 0.25°C per hour collected in the filter to reduce the flow through the filter to an unacceptable degree. Consequently,
the filters should be daily and manually rinsed at low pressure and backwashed. During backwash,
b) Water Filtration: water flows down through the riser tube and up through the filter bed to drain; the filter bed is fully
 A turn-over rate of 4 hours for Pools expanded and all foreign materials are thoroughly washed from the medium. Whenever, backwashing
 A turn-over rate of 20 minutes for whirl pools/Jacuzzis the filter becomes useless then it should be replaced.
 A turn-over rate of 2 hours for Water features
b) Water Treatment-Ultra-Violet Sterilizer:
 Filter loading Rate of 20 gpm/ft2
Water, after filtration and before getting to the point of use, will pass by the Ultraviolet sterilizer to
c) Desired Pool Water Quality:
purify water from the excess of Chloramine.
 A pH of water between 7.2-7.6 to be kept for Pools and Jacuzzis
 A free residual chlorine of 1 to 1.5 PPM for Pools and Jacuzzis Whenever the water contains any hardness minerals (calcium or magnesium), iron or manganese, the
 A free residual chlorine of 3 PPM for Water Features quartz sleeve will require periodic cleaning and if the system indicates that the UV intensity is low, UV
sensor/ and or quartz sleeve may need to be cleaned or replaced.
d) Bathers Load:
 For pools less than 1m depth, the bathing load is 2.2 m2/bather. Replacing the UV lamp should be done regularly to ensure maximum disinfection.
 For pools of depth between 1m & 1.5m, the bathing load is 2.7 m2/bather.
 For pools of depth higher than 1.5m, the bathing load is 4 m2/bather. c) Water Treatment-Salt Chlorine Generator:

e) Velocities in Pipes: In our design, Salt chlorinators are used as they introduce enough disinfectants in water to destroy
 Water Velocity in suction lines around 1.5 m/s any micro-organisms that may be floating in it.
 Water Velocity in discharge lines around 2 m/s
 Water Velocity in gravity lines around 0.5 m/s The purpose of disinfection is to kill the germs, bacteria and viruses and to keep the water free from
any bacteriological growth and synthesis.
f) Redundancy:
 Only public swimming pools filtration pumps will be backed-up by stand-by pumps. Salt chlorinators increase the quality of the water as they do not need chemical products and make
 Plunge pools will not be backed-up by stand-by pumps. maintenance work easier. Salt is added to the water and then once dissolved, an electric current is
passed through the water via an electrode and the salt turns into chlorine.
g) Water thickness:
 All water features will be designed with a spill water thickness of 7-15mm. The salt chlorinators should be controlled automatically to maintain the required free residual chlorine
 All overflow type pool will be designed with a spill water thickness of 3mm for cascades and levels.
1mm for standard overflow channel.
d) Water Treatment-pH adjustment:
h) Classification:
 The Swimming Pool-Hotel-Type 1, Type 3 and Residence Pool Type 4 are standard pool. In this project, as it is very important to keep the water always neutral, pH dosing pumps with
 All the remaining pools will be considered as whirl pools. controlled automatically to maintain the pH within the acceptable range are conceived for the pools.
RCHR-G-FD-CLC-P4-ME-01 R01 Page 32 of 47
Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

3.6 Preliminary Calculation / Selection Notes  SWIMMING POOL – Residence Type 1

The following pages contain the preliminary calculation notes for the water features and swimming pools design, Total Calculated Volume (based on the drawings) = 7 m³
taking into consideration that these calculations may change after final design submittal.
𝟕 𝐦𝟑
𝐅= = 𝟐𝟏. 𝟐𝟏
a) Sand Filters and Filtration Pumps 𝟎. 𝟑𝟑 𝐡𝐫

*Theoretical turnover : 𝟐𝟏. 𝟐𝟏 𝐱 𝟒. 𝟒


Swimming Pools : 4 hrs 𝐃= √ 𝝿 ≈ 𝟐. 𝟒𝟒 𝐟𝐭 ≈ 𝟕𝟒. 𝟑𝟕 𝐜𝐦
𝟒 𝐱 𝟐𝟎
Whirl Pools : 0.33 hrs ≈ 20 min

Jacuzzis : 0.33 hrs ≈ 20 min Therefore, a 75 cm Sand Filter (SF-SP-R-Type 1) and a 2 HP pump (P-SP-R-Type 1-1) with 21 m³/hr flow are
needed.
Water Features : 2 hrs
 SWIMMING POOL – Residence Type 2

Swimming Pools Total Calculated Volume (based on the drawings) = 6.5 m³


Whirl Pools
𝟔. 𝟓
*Theoretical loading rate : : 20 gpm/ft² 𝐅= = 𝟏𝟗. 𝟕 𝐦³/𝐡𝐫
Jacuzzis 𝟎. 𝟑𝟑

Water Features 𝟏𝟗. 𝟕 𝐱 𝟒. 𝟒


𝐃= √ 𝝿 ≈ 𝟐. 𝟑𝟓 𝐟𝐭 ≈ 𝟕𝟏. 𝟔𝟑 𝐜𝐦
Turnover: 𝟒 𝐱 𝟐𝟎

Therefore, a 75 cm Sand Filter (SF-SP-R-Type 2) and a 2 HP pump (P-SP-R-Type 2-1) with 21 m³/hr flow are
𝐕 where: T.O. in hr needed.
𝐓. 𝐎. =
𝐅 V in m³
 SWIMMING POOL – Residence Type 3
F in m³/hr
𝐕
Flow: 𝐅 = Total Calculated Volume (based on the drawings) = 7 m³
𝐓. 𝐎.

𝟕 𝐦𝟑
𝐅= = 𝟐𝟏. 𝟐𝟏
𝟎. 𝟑𝟑 𝐡𝐫
Loading Rate:

𝐅 where: F in gpm
𝟐𝟏. 𝟐𝟏 𝐱 𝟒. 𝟒
𝐋. 𝐑. = 𝐃= √ 𝝿 ≈ 𝟐. 𝟒𝟒 𝐟𝐭 ≈ 𝟕𝟒. 𝟑𝟕 𝐜𝐦
𝐀 A in ft²
𝟒 𝐱 𝟐𝟎

Diameter: Therefore, a 75 cm Sand Filter (SF-SP-R-Type 3) and a 2 HP pump (P-SP-R-Type 3-1) with 21 m³/hr flow are
𝐅 𝞹 𝐅 𝑭 needed.
𝐀 = 𝑫² = 𝑫 = √𝞹
𝐋. 𝐑. 𝟒 𝐋. 𝐑.
𝟒 𝑳. 𝑹.

RCHR-G-FD-CLC-P4-ME-01 R01 Page 33 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 SWIMMING POOL – Residence Type 4  SWIMMING POOL – Hotel Type 2

Total Calculated Volume (based on the drawings) = 135 m3 Total Calculated Volume (based on the drawings) = 2.8 m³

𝟏𝟑𝟓 𝐦𝟑 𝟐. 𝟖 𝐦𝟑
𝑭= = 𝟑𝟑. 𝟕𝟓 𝐅= = 𝟖. 𝟓
𝟒 𝐡𝐫 𝟎. 𝟑𝟑 𝐡𝐫

𝟑𝟑. 𝟕𝟓 𝐱 𝟒. 𝟒 𝟖. 𝟓 𝐱 𝟒. 𝟒
𝐃= √ 𝝿 ≈ 𝟑. 𝟎𝟕 𝐟𝐭 ≈ 𝟗𝟑. 𝟓𝟕 𝐜𝐦 𝐃= √ 𝝿 ≈ 𝟏. 𝟓𝟓 𝐟𝐭 ≈ 𝟒𝟕. 𝟐𝟒 𝐜𝐦
𝐱 𝟐𝟎
𝟒 𝐱 𝟐𝟎 𝟒
Therefore, a 50 cm Sand Filter (SF-SP-H-Type 2) and a 1 HP pump (P-SP-H-Type 2-1) with 9 m³/hr flow are
Therefore, a 94 cm Sand Filter (SF-SP-R-type 4) and a 2 HP pump (P-SP-R-Type 4-1) with 34 m³/hr flow are needed.
needed.
 SWIMMING POOL – Hotel Type 3
 SWIMMING POOL-Residence Jacuzzi
Total Calculated Volume (based on the drawings) = 60 m3
Total Calculated Volume (based on the drawings) = 5.25 m³
𝟔𝟎 𝐦𝟑
𝟑 𝑭= = 𝟏𝟓
𝟓. 𝟐𝟓 𝐦 𝟒 𝐡𝐫
𝐅= = 𝟏𝟓. 𝟗𝟏
𝟎. 𝟑𝟑 𝐡𝐫
𝟏𝟓 𝐱 𝟒. 𝟒
𝐃= √ 𝝿 ≈ 𝟐. 𝟎𝟓 𝐟𝐭 ≈ 𝟔𝟐. 𝟒𝟖𝟒 𝐜𝐦
𝟏𝟓. 𝟗𝟏 𝒙 𝟒. 𝟒 𝟒 𝐱 𝟐𝟎
𝑫= √ 𝞹 ≈ 𝟐. 𝟏𝟏 𝒇𝒕 ≈ 𝟔𝟒. 𝟑 𝒄𝒎
𝟒 𝒙 𝟐𝟎
Therefore, a 63 cm Sand Filter (SF-SP-H-Type 3) and a 2 HP pump (P-SP-H-Type 3-1) with 15 m³/hr flow are
Therefore, a 65 cm Sand Filter (SF-JC-R) and a 2 HP pump (P-JC-R-1) with 16 m³/hr flow are needed. needed.

 SWIMMING POOL – Hotel Type 1  SWIMMING POOL – Hotel Jacuzzi

Total Calculated Volume (based on the drawings) = 300 m³ Total Calculated Volume (based on the drawings) = 6.1 m³

𝟑𝟎𝟎 𝐦𝟑 𝟔. 𝟏 𝐦𝟑
𝐅= = 𝟕𝟓 𝐅= = 𝟏𝟖. 𝟓
𝟒 𝐡𝐫 𝟎. 𝟑𝟑 𝐡𝐫

𝟕𝟓 𝒙 𝟒. 𝟒 𝟏𝟖. 𝟓 𝒙 𝟒. 𝟒
𝑫= √ 𝞹 ≈ 𝟒. 𝟓𝟗 𝒇𝒕 ≈ 𝟏𝟒𝟎 𝒄𝒎 𝑫= √ 𝞹 ≈ 𝟐. 𝟐𝟖 𝒇𝒕 ≈ 𝟔𝟗. 𝟓 𝒄𝒎
𝟒 𝒙 𝟐𝟎 𝒙 𝟐𝟎
𝟒

Therefore, THREE 90 cm Sand Filters (SF-SP-H-Type 1) and THREE 10.5 HP pumps (P-SP-H-Type 1) with 30 Therefore, a 80 cm Sand Filter (SF-JC-H) and a 5.5 HP pump (P-JC-H-1) with 21 m³/hr flow are needed.
m³/hr flow each are needed.

RCHR-G-FD-CLC-P4-ME-01 R01 Page 34 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 WATER FEATURE – General WF 601  WATER FEATURE – Residence 601

Total Calculated Volume (based on the drawings) = 2 * 1.05 m³ Total Calculated Volume (based on the drawings) = 3.7 m³

𝟑. 𝟕 𝒎𝟑
𝟐 ∗ 𝟏. 𝟎𝟓 𝒎𝟑 𝑭= = 𝟏. 𝟖𝟓
𝑭= = 𝟏. 𝟎𝟓 𝟐 𝒉𝒓
𝟐 𝒉𝒓
𝟏. 𝟖𝟓 𝒙 𝟒. 𝟒
𝟏. 𝟎𝟓 𝒙 𝟒. 𝟒 𝑫= √ 𝞹 ≈ 𝟎. 𝟕𝟐 𝒇𝒕 ≈ 𝟐𝟏. 𝟗𝟓 𝒄𝒎
𝑫= √ 𝞹 ≈ 𝟎. 𝟓𝟓 𝒇𝒕 ≈ 𝟏𝟔. 𝟕𝟔 𝒄𝒎 𝒙 𝟐𝟎
𝟒
𝟒 𝒙 𝟐𝟎
Therefore, a 40 cm Sand Filter (SF-WF-R) and a 0.5 HP pump (P-WF-R-1) with 6 m³/hr flow are needed.
Therefore, a 40 cm Sand Filter (SF-WF-G) and a 0.5 HP pump (P-WF-G-1) with 6 m³/hr flow are needed.
 WATER FEATURE – Hotel Type 3

 WATER FEATURE – Hotel Type 1 Total Calculated Volume (based on the drawings) = 3.7 m³

Total Calculated Volume (based on the drawings) = 6.7 m³ 𝟑. 𝟕 𝒎𝟑


𝑭= = 𝟏. 𝟖𝟓
𝟐 𝒉𝒓
𝟔. 𝟕 𝒎𝟑
𝑭= = 𝟑. 𝟑𝟓 𝟏. 𝟖𝟓 𝒙 𝟒. 𝟒
𝟐 𝒉𝒓 𝑫= √ 𝞹 ≈ 𝟎. 𝟕𝟐 𝒇𝒕 ≈ 𝟐𝟏. 𝟗𝟓 𝒄𝒎
𝟒 𝒙 𝟐𝟎
𝟑. 𝟑𝟓 𝒙 𝟒. 𝟒
𝑫= √ 𝞹 ≈ 𝟎. 𝟗𝟕 𝒇𝒕 ≈ 𝟐𝟗. 𝟔 𝒄𝒎 Therefore, a 40 cm Sand Filter (SF-WF-H-Type 3) and a 0.5 HP pump (P-WF-H-Type 3-1) with 6 m³/hr flow
𝟒 𝒙 𝟐𝟎
are needed.

Therefore, a 48 cm Sand Filter (SF-WF-H-Type 1) and a 4 HP pump (P-WF-H-Type 1-1) with 6 m³/hr flow are
b) Hydrojets Pumps
needed.

 WATER FEATURE – Hotel Type 2 The total flow of the pumps serving hydrojets (in whirl pools and Jacuzzi) should have a flow covering the
demand of all the hydrojets of the pool simultaneously.
Total Calculated Volume (based on the drawings) = 17.5 m³
For standard hydrojets fittings, a flow of 5m3/hr is required for each fitting to give the required massage effect.
𝟏𝟕. 𝟓 𝒎𝟑
𝑭= = 𝟖. 𝟕𝟓 F= F(H) x N(H)
𝟐 𝒉𝒓
Where F=Flow in m³/hr
𝟖. 𝟕𝟓 𝒙 𝟒. 𝟒
𝑫= √ 𝞹 ≈ 𝟏. 𝟓𝟕 𝒇𝒕 ≈ 𝟒𝟕. 𝟖𝟓 𝒄𝒎 F(H)=Hydrojet Flow demand in m³/hr=5 m³/hr Per hydrojet
𝟒 𝒙 𝟐𝟎
N(H)=Number of Hydrojets in the pool
Therefore, a 50 cm Sand Filter (SF-WF-H-Type 2) and a 1 HP pump (P-WF-H-Type 2-1) with 9 m³/hr flow are
Thus, F= 5 x N(H)
needed.

RCHR-G-FD-CLC-P4-ME-01 R01 Page 35 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 Swimming Pool-Hotel-Type 2: Additionally, the required effect of each nozzle and outlet defines the required flow of the pump supplying the
N(H)= 8 Hydrojets nozzle.
F= 5 x N(H)
F= 5 x 8 = 40 m³/hr F= F(N) x N(N)
Thus, the hydrojets pump flow (P-SP-H-Type 2-2) is 40 m³/hr. Where F=Flow in m³/hr
F(N)=Nozzle Flow demand in m³/hr
 Jacuzzi-Hotel: N(N)=Number of Nozzles supplied by the pump
N(H)= 12 Hydrojets
F= 5 x N(H)  Water Feature-General:
F= 5 x 12 = 60 m³/hr This water feature is a wall mounted fountain with double bowls and a lion face sculpture. Water is to fall
Thus, two hydrojets pump flow (P-JC-H-2) of 30 m³/hr each will be needed. from the lion face to the high bowl where it will overflow all around the weir.
E=7 mm
 Swimming Pool-Residences-Type 1: L=0.8 m
N(H)= 8 Hydrojets F=1440 x 0.8 x 0.007= 8 m³/hr
F= 5 x N(H) Thus, the overflow pump total flow for each feature (P-WF-G- 2) is 8 m³/hr.
F= 5 x 8 = 40 m³/hr As, we have two water features of this type, 2 pumps P-WF-G-2 with 8 m3/hr are required.
Thus, the hydrojets pump flow (P-SP-R-Type 1-2) is 40 m³/hr.
 Water Feature-Hotel-Type 1:
 Swimming Pool-Residences-Type 2: This water feature includes three concentric elliptical basins cascading one on the other with 5 fountain
N(H)= 8 Hydrojets nozzles in the upper basin.
F= 5 x N(H)
F= 5 x 8 = 40 m³/hr a) Nozzle Effect Pump:
Thus, the hydrojets pump flow (P-SP-R-Type 2-2) is 40 m³/hr. N(N)= 5 Nozzles
F(N)= 2.8 m³/hr
 Swimming Pool-Residences-Type 3: F= 5 x 2.8 = 14 m³/hr
N(H)= 8 Hydrojets Thus, the nozzles pump flow (P-WF-H-Type 1-4) is 14 m³/hr.
F= 5 x N(H)
F= 5 x 8 = 40 m³/hr b) High Basin overflow Effect Pump:
Thus, the hydrojets pump flow (P-SP-R-Type 3-2) is 40 m³/hr. E=7 mm
L=8.15 m
c) Effects Pumps F=1440 x 8.15 x 0.007= 82.4 m³/hr
However, the nozzles are contributing in the overflow over the basin edge, for this the required flow is:
F=82.4-14=68.4 m³/hr
The water effect required for each water feature defines the thickness of spill of water required to cascade all Thus, two overflow pumps (P-WF-H-Type 1-2) of 34.2m3/hr each are required for the overflow of the
over the edge. high basin.

F= L x V x E
c) Mid Basin overflow Effect Pump:
Where F=Flow in m³/hr
E=7 mm
L=Length of cascade in m L=12.2m
V=Velocity of water required to have a fine effect= 1440 m/hr
F=1440 x 12.20 x 0.007= 122.9 m³/hr
E=Water Spill thickness in m
However, the water overflowing from the high basin will contribute in the water overflowing from the
Thus, F= 1440 x L x E mid basin, for this the required flow is:

RCHR-G-FD-CLC-P4-ME-01 R01 Page 36 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

F=122.9-82.4=40.5 m³/hr
Thus, one overflow pump (P-WF-H-Type 1-3) of 40.5m3/hr is required for the overflow of the mid basin. 2. Delay return volume during ON-OFF of pumps (V2):

 Water Feature-Hotel-Type 2: The total flow of the pumps is equal to:


This water feature includes two concentric semi-elliptical basins with a waterfall from the upper basin to the F(total) = total filtration flow rate (m³/hr)
lower basin while having a scattered white water wall effect.
E=15 mm The delay return volume when the pumps are ON is calculated by estimating the travel time spent until
L=12.02 m water starts to reach back the compensation tank after overflowing into the overflow channel.
F=1440 x 12.02 x 0.015= 259.6 m³/hr
Thus, 4 overflow pumps (P-WF-H-Type 2-2) of 64.9m3/hr each are required for the overflow of the high When the pumps are ON: V(ON) = F(total) x 1 min (travel time assumption) x [1/60] (hr/min)
basin.
The delay return volume when the pumps are OFF is equal to the delay return volume when the pumps are
 Water Feature-Residences: ON ≡ V(OFF) = V(ON)
This water feature includes 2 half rectangular basins with the upper basin cascading on the lower basin with
5 spouts in the upper basin. Thus, V2 = V(ON) + V(OFF)

a) Spouts Effect Pump:


N(N)= 5 Nozzles 3. Displacement of water due to swimmers (V3): (IF APPLICABLE)
F(N)= 2.8 m³/hr
F= 5 x 2.8 = 14 m³/hr This Volume is equal to volume of water displaced out of the pool when the pool is at full load.
Thus, the spouts pump flow (P-WF-R- 3) is 14 m³/hr. The bathing load depends on the pool depth.

b) Basin overflow Effect Pump: For pools less than 1m depth, the bathing load is 2.2 m²/bather.
E=10 mm For pools of depth between 1m & 1.5m, the bathing load is 2.7 m²/bather.
L=11 m For pools of depth higher than 1.5m, the bathing load is 4 m²/bather.
F=1440 x 11 x 0.01= 158.4 m³/hr
However, the spouts are contributing in the overflow over the basin edge, for this the required flow is: Each bather shall displace 20 gallons (0.075 m³) of water
F=158.4-14=144.4 m³/hr
Thus, three overflow pumps (P-WF-R-2) of 48.2m3/hr each are required for the overflow of the basin. Therefore, V3 = 0.075 m³/swimmer x nb of swimmers

 Water Feature- Hotel-Type 3:


This water feature includes 2 circular basins with the upper basin cascading on the lower basin. 4. Dead Volume (V4):
E=7 mm
L=7.34 m V4 = volume of water below pump’s suction lines (m³)
F=1440 x 7.34 x 0.007= 74 m³/hr
Thus, 2 overflow pumps (P-WF-H-Type 3-2) of 37m3/hr each are required for the overflow of the high basin.

d) Compensation Tanks

1. Filter Backwash Water Volume (V1):


During one cycle,
V1 = filtration flow rate (m³/hr) x 10 min (duration of the backwash and rinse cycle) x [1/60] (hr/min)

RCHR-G-FD-CLC-P4-ME-01 R01 Page 37 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 SWIMMIMG POOL – HOTEL – TYPE 1


 SWIMMING POOL-HOTEL-TYPE3
1. Filter Backwash Water Volume (V1):
1. Filter Backwash Water Volume (V1):
Filtration flow rate = 30 m³/hr
Filtration flow rate = 15 m³/hr
V1 = 30 m³/hr x 10 min x [1/60] (hr/min)
V1 = 5 m³ V1 = 15m³/hr x 10 min x [1/60] (hr/min)
V1 = 2.5 m³
2. Delay return volume during ON-OFF of pumps (V2):
2. Delay return volume during ON-OFF of pumps (V2):
F(total) = 90 m³/hr
F(total) = 15 m³/hr
V(ON) = V(OFF) = 90 m³/hr x 1 min x [1/60] (hr/min) = 1.5 m³
V(ON) = V(OFF) = 15 m³/hr x 1 min x [1/60] (hr/min) = 0.25 m³
V2 = 1.5 m³ + 1.5 m³
V2 = 3 m³ V2 = 0.25 m³ + 0.25 m³
V2 = 0.5 m³
3. Displacement of water due to swimmers (V3):
3. Displacement of water due to swimmers (V3):
For the depth between 1m & 1.5m, the total area is 196 m², giving 73 bathers.
For the depth less than 1m depth, the total area is 15.3 m², giving 7 bathers For the depth between 1m & 1.5m, the total area is 50 m², giving 19 bathers.

Total number of bathers at full load is 80 bathers. Total number of bathers at full load is 19 bathers.

V3 = 0.075 m³/swimmer x 80 swimmers V3 = 0.075 m³/swimmer x 19 swimmers


V3 = 6 m³ V3 = 1.425 m³

4. Dead Volume (V4): 4. Dead Volume (V4):

V4 = 0.36 m³ V4 = 0.52 m³

5. The total required Volume of the Compensation tank Vt is equal to: 5. The total required Volume of the Compensation tank Vt is equal to:

Vt = V1+V2+V3+V4 Vt = V1+V2+V3+V4
Vt = 5+3+6+0.36 Vt = 2.5+0.5+1.425+0.52
Vt = 14.36 m³ Vt = 4.945 m³

RCHR-G-FD-CLC-P4-ME-01 R01 Page 38 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 WATER FEATURE – GENERAL


 SWIMMING POOL-RESIDENCE-TYPE 4
1. Filter Backwash Water Volume (V1):
1. Filter Backwash Water Volume (V1):
Filtration flow rate = 6 m³/hr
Filtration flow rate = 34 m³/hr
V1 = 6 m³/hr x 10 min x [1/60] (hr/min)
V1 = 34 m³/hr x 10 min x [1/60] (hr/min) V1 = 1 m³
V1 = 5.67 m³
2. Delay return volume during ON-OFF of pumps (V2):
2. Delay return volume during ON-OFF of pumps (V2):
F(total) = 22 m³/hr
F(total) = 34 m³/hr
V(ON) = V(OFF) = 22 m³/hr x 1 min x [1/60] (hr/min) = 0.37 m³
V(ON) = V(OFF) = 34 m³/hr x 1 min x [1/60] (hr/min) = 0.57 m³
V2 = 0.37 m³ + 0.37 m³
V2 = 0.57 m³ + 0.57 m³ V2 = 0.74 m³
V2 = 1.14 m³
3. Displacement of water due to swimmers (V3):
3. Displacement of water due to swimmers (V3):
Not Applicable
For the depth between 1m & 1.5m, the total area is 90 m², giving 34 bathers.
4. Dead Volume (V4):
Total number of bathers at full load is 34 bathers.
V4 = 0.58 m³
V3 = 0.075 m³/swimmer x 34 swimmers
V3 = 2.55 m³ 5. The total required Volume of the Compensation tank Vt is equal to:

4. Dead Volume (V4): Vt = V1+V2+V3+V4


Vt = 1+0.74+0.58
V4 = 0.72 m³ Vt = 2.32 m³

5. The total required Volume of the Compensation tank Vt is equal to:


 WATER FEATURE – HOTEL – TYPE 1
Vt = V1+V2+V3+V4
1. Filter Backwash Water Volume (V1):
Vt = 5.67+1.14+2.55+0.72
Filtration flow rate = 6 m³/hr
Vt = 10.08 m³
V1 = 6 m³/hr x 10 min x [1/60] (hr/min)
V1 = 1 m³

RCHR-G-FD-CLC-P4-ME-01 R01 Page 39 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

3. Displacement of water due to swimmers (V3):


2. Delay return volume during ON-OFF of pumps (V2):
Not Applicable
F(total) = 182.2 m³/hr
4. Dead Volume (V4):
V(ON) = V(OFF) = 182.2 m³/hr x 1 min x [1/60] (hr/min) = 3.0 m³ V4 = 1.91 m³

V2 = 3.0 m³ + 3.0 m³ 5. The total required Volume of the Compensation tank Vt is equal to:
V2 = 6.0 m³
Vt = V1+V2+V3+V4
3. Displacement of water due to swimmers (V3): Vt = 1.5+8.94+1.91
Vt = 12.35 m³
Not Applicable
 WATER FEATURE – RESIDENCE
4. Dead Volume (V4):
1. Filter Backwash Water Volume (V1):

V4 = 1.8 m³ Filtration flow rate = 6 m³/hr

5. The total required Volume of the Compensation tank Vt is equal to: V1 = 6 m³/hr x 10 min x [1/60] (hr/min)
V1 = 1 m³
Vt = V1+V2+V3+V4
Vt = 1+6+1.8 2. Delay return volume during ON-OFF of pumps (V2):
Vt = 8.8 m³
F(total) = 164.6 m³/hr

 WATER FEATURE – HOTEL – TYPE 2 V(ON) = V(OFF) = 164.6 m³/hr x 1 min x [1/60] (hr/min) = 2.75 m³

V2 = 2.75 m³ + 2.75 m³
1. Filter Backwash Water Volume (V1):
V2 = 5.5 m³

Filtration flow rate = 9 m³/hr 3. Displacement of water due to swimmers (V3):

V1 = 9 m³/hr x 10 min x [1/60] (hr/min) Not Applicable


V1 = 1.5 m³
4. Dead Volume (V4):
2. Delay return volume during ON-OFF of pumps (V2):
V4 = 1.6 m³

F(total) = 268.6 m³/hr


5. The total required Volume of the Compensation tank Vt is equal to:

V(ON) = V(OFF) = 268.6 m³/hr x 1 min x [1/60] (hr/min) = 4.47 m³ Vt = V1+V2+V3+V4


Vt = 1+5.5+1.6
V2 = 4.47 m³ + 4.47 m³ Vt = 8.1 m³
V2 = 8.94 m³

RCHR-G-FD-CLC-P4-ME-01 R01 Page 40 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 WATER FEATURE – HOTEL – TYPE 3  Swimming Pool-Hotel-Type 1:

1. Filter Backwash Water Volume (V1):


Initial Values
Filtration flow rate = 6 m³/hr Ambient temperature Tamb 10.00 °C
Pool Water desired temperature Tpool 29.00 °C
V1 = 6 m³/hr x 10 min x [1/60] (hr/min) Pool Water Initial temperature Tini 8.00 °C
V1 = 1 m³ Pool Water Final desired temperature Tfin 29.00 °C
density of water d 998.00 kg/m3
Specific heat of water Cp 4.19 KJ/kg.C
2. Delay return volume during ON-OFF of pumps (V2): 0.045 Kw/m2.K ------> wind velocity
below 5 Km/hr
F(total) = 75 m³/hr 0.06 Kw/m2.K ------> wind velocity
between 5 to 8 Km/hr
Water Surface heat transfer coefficient Usurf 0.120 kw/m2.k
V(ON) = V(OFF) = 75 m³/hr x 1 min x [1/60] (hr/min) = 1.25 m³ 0.075 Kw/m2.K ------> wind velocity
around 8 Km/hr
0.12 Kw/m2.K ------> wind velocity
V2 = 1.25 m³ + 1.25 m³ around 16 Km/hr
V2 = 2.5 m³ Pool heat-up time t 84.00 Hours
Pool surface Area A 211.30 m2
3. Displacement of water due to swimmers (V3): Pool Volume V 300.00 m3
1.15 ------> Coast
Safety factor SF 1.20
Not Applicable 1.2 ------> Mountain
Fill Only When Having Above Ground Or Suspended Pool Case
4. Dead Volume (V4): Pool total wall surface Awall 79.75 m2
Pool total floor surface Afloor 196.00 m2
V4 = 1.9 m³ Temperature of Area behind wall T1 17.00 °C
Temperature of media below pool T2 10.00 °C
5. The total required Volume of the Compensation tank Vt is equal to: Heat transfer coefficient through pool wall Uwall 0.004 kw/m2.K
Heat transfer coefficient through pool Floor Ufloor 0.004 kw/m2.K
Waterfall total Area Awfall 0.00 m2
Vt = V1+V2+V3+V4 Waterfall Surface heat transfer coefficient Uwfall 0.24 kw/m2.k
Vt = 1+2.5+1.9 OUTPUT DATA (HEATING LOAD)
Vt = 5.4 m³ Pool Heat-Up Rate Q1 87.05 Kw Q1=d*Cp*V*(Tfin - Tini)/(t*3600)
Pool Surface Heat Loss Q2 481.76 Kw Q2=Usurf*A*(Tpool - Tamb)
Q3=Uwall*Awall*(Tpool-T1) +
Q3
6. Heat Exchangers and Electric Heaters Pool Wall/Floor Heat Loss 16.38 Kw Ufloor*Afloor*(Tpool-T2)
Waterfall Surface Heat Loss Q4 0.00 Kw Q4=Uwfall*Awfall*(Tpool - Tamb)
The required heat exchanger/electric heater for each pool will be calculated as per “2007 ASHRAE Handbook - Total Required Heater Capacity QT 702.24 Kw QT=SF*(Q1+Q2+Q3+Q4)
Table 3-1: Heating Calculation (Swimming Pool-Hotel-Type 1)
HVAC Applications (49.22-49.23)” method.

However, only the Jacuzzi-Hotel, the Swimming Pool-Hotel-Type 1 and the swimming pool-Hotel-Type 2 will be
equipped with heat exchangers connected to heating water coming from the heat recovery chiller with a back-up
boiler and the remaining pools will be equipped with electrical heaters as the Residences don’t have a chiller
system and the Swimming Pool-Hotel-Type 2 equipment will be installed under deck, where no space is allowed
for the installation of the heat exchanger and its connections.

RCHR-G-FD-CLC-P4-ME-01 R01 Page 41 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 Swimming Pool-Hotel-Type 2:  Swimming Pool-Hotel-Type 3:

Initial Values
Initial Values Indoor temperature Tamb 27.00 °C
Ambient temperature Tamb 22.00 °C Pool Water desired temperature Tpool 29.00 °C
Pool Water desired temperature Tpool 40.00 °C Pool Water Initial temperature Tini 8.00 °C
Pool Water Initial temperature Tini 20.00 °C Pool Water Final desired temperature Tfin 29.00 °C
Pool Water Final desired temperature Tfin 40.00 °C density of water d 998.00 kg/m3
density of water d 998.00 kg/m3 Specific heat of water Cp 4.19 KJ/kg.C
Specific heat of water Cp 4.19 KJ/kg.C 0.045 Kw/m2.K ------> wind velocity
2
0.045 Kw/m .K ------> wind velocity below 5 Km/hr
below 5 Km/hr 0.06 Kw/m2.K ------> wind velocity
0.06 Kw/m2.K ------> wind velocity between 5 to 8 Km/hr
Water Surface heat transfer coefficient Usurf 0.120 kw/m2.k
2 between 5 to 8 Km/hr 0.075 Kw/m2.K ------> wind velocity
Water Surface heat transfer coefficient Usurf 0.120 kw/m .k
0.075 Kw/m2.K ------> wind velocity around 8 Km/hr
around 8 Km/hr 0.12 Kw/m2.K ------> wind velocity
0.12 Kw/m2.K ------> wind velocity around 16 Km/hr
around 16 Km/hr Pool heat-up time t 84.00 Hours
Pool heat-up time t 80.00 Hours Pool surface Area A 50.00 m2
Pool surface Area A 6.66 m2 Pool Volume V 60.00 m3
Pool Volume V 2.80 m3 1.15 ------> Coast
Safety factor SF 1.20
1.15 ------> Coast 1.2 ------> Mountain
Safety factor SF 1.20
1.2 ------> Mountain Fill Only When Having Above Ground Or Suspended Pool Case
Fill Only When Having Above Ground Or Suspended Pool Case Pool total wall surface Awall 38.3 m2
Pool total wall surface Awall 7.67 m2 Pool total floor surface Afloor 50.00 m2
Pool total floor surface Afloor 2.00 m2 Temperature of Area behind wall T1 21.00 °C
Temperature of Area behind wall T1 22.00 °C Temperature of media below pool T2 21.00 °C
Temperature of media below pool T2 22.00 °C Heat transfer coefficient through pool wall Uwall 0.004 kw/m2.K
Heat transfer coefficient through pool wall Uwall 0.004 kw/m2.K Heat transfer coefficient through pool Floor Ufloor 0.004 kw/m2.K
Heat transfer coefficient through pool Floor Ufloor 0.004 kw/m2.K Waterfall total Area Awfall 0.00 m2
Waterfall total Area Awfall 0.00 m2 Waterfall Surface heat transfer coefficient Uwfall 0.24 kw/m2.k
Waterfall Surface heat transfer coefficient Uwfall 0.24 kw/m2.k OUTPUT DATA (HEATING LOAD)
OUTPUT DATA (HEATING LOAD) Pool Heat-Up Rate Q1 17.423 Kw Q1=d*Cp*V*(Tfin - Tini)/(t*3600)
Pool Heat-Up Rate Q1 0.81 Kw Q1=d*Cp*V*(Tfin - Tini)/(t*3600) Pool Surface Heat Loss Q2 12.000 Kw Q2=Usurf*A*(Tpool - Tamb)
Pool Surface Heat Loss Q2 14.39 Kw Q2=Usurf*A*(Tpool - Tamb) Q3=Uwall*Awall*(Tpool-T1) +
Q3
Q3=Uwall*Awall*(Tpool-T1) + Pool Wall/Floor Heat Loss 2.826 Kw Ufloor*Afloor*(Tpool-T2)
Q3
Pool Wall/Floor Heat Loss 0.61 Kw Ufloor*Afloor*(Tpool-T2) Waterfall Surface Heat Loss Q4 0.00 Kw Q4=Uwfall*Awfall*(Tpool - Tamb)
Waterfall Surface Heat Loss Q4 0.00 Kw Q4=Uwfall*Awfall*(Tpool - Tamb) Total Required Heater Capacity QT 32.249 Kw QT=SF*(Q1+Q2+Q3+Q4)
Total Required Heater Capacity QT 18.97 Kw QT=SF*(Q1+Q2+Q3+Q4) Table 3-3: Heating Calculation (Swimming Pool-Hotel-Type 3)
Table 3-2: Heating Calculation (Swimming Pool-Hotel-Type 2)

RCHR-G-FD-CLC-P4-ME-01 R01 Page 42 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 Jacuzzi-Hotel:  Swimming Pool-Residences-Type 1:

Initial Values Initial Values


Ambient temperature Tamb 10.00 °C Ambient temperature Tamb 22.00 °C
Pool Water desired temperature Tpool 40.00 °C Pool Water desired temperature Tpool 40.00 °C
Pool Water Initial temperature Tini 8.00 °C Pool Water Initial temperature Tini 20.00 °C
Pool Water Final desired temperature Tfin 40.00 °C Pool Water Final desired temperature Tfin 40.00 °C
density of water d 998.00 kg/m3 density of water d 998.00 kg/m3
Specific heat of water Cp 4.19 KJ/kg.C Specific heat of water Cp 4.19 KJ/kg.C
0.045 Kw/m2.K ------> wind velocity 0.045 Kw/m2.K ------> wind velocity
below 5 Km/hr below 5 Km/hr
0.06 Kw/m2.K ------> wind velocity 0.06 Kw/m2.K ------> wind velocity
between 5 to 8 Km/hr between 5 to 8 Km/hr
Water Surface heat transfer coefficient Usurf 0.120 kw/m2.k Water Surface heat transfer coefficient Usurf 0.120 kw/m2.k
0.075 Kw/m2.K ------> wind velocity 0.075 Kw/m2.K ------> wind velocity
around 8 Km/hr around 8 Km/hr
0.12 Kw/m2.K ------> wind velocity 0.12 Kw/m2.K ------> wind velocity
around 16 Km/hr around 16 Km/hr
Pool heat-up time t 128.00 Hours Pool heat-up time t 80.00 Hours
Pool surface Area A 12.22 m2 Pool surface Area A 12.96 m2
Pool Volume V 6.10 m3 Pool Volume V 7.00 m3
1.15 ------> Coast 1.15 ------> Coast
Safety factor SF 1.20 Safety factor SF 1.20
1.2 ------> Mountain 1.2 ------> Mountain
Fill Only When Having Above Ground Or Suspended Pool Case Fill Only When Having Above Ground Or Suspended Pool Case
Pool total wall surface Awall 8.23 m2 Pool total wall surface Awall 6.23 m2
Pool total floor surface Afloor 9.97 m2 Pool total floor surface Afloor 7.40 m2
Temperature of Area behind wall T1 21.00 °C Temperature of Area behind wall T1 22.00 °C
Temperature of media below pool T2 11.00 °C Temperature of media below pool T2 22.00 °C
Heat transfer coefficient through pool wall Uwall 0.004 kw/m2.K Heat transfer coefficient through pool wall Uwall 0.004 kw/m2.K
Heat transfer coefficient through pool Floor Ufloor 0.004 kw/m2.K Heat transfer coefficient through pool Floor Ufloor 0.004 kw/m2.K
Waterfall total Area Awfall 0.00 m2 Waterfall total Area Awfall 0.00 m2
Waterfall Surface heat transfer coefficient Uwfall 0.24 kw/m2.k Waterfall Surface heat transfer coefficient Uwfall 0.24 kw/m2.k
OUTPUT DATA (HEATING LOAD) OUTPUT DATA (HEATING LOAD)
Pool Heat-Up Rate Q1 1.77 Kw Q1=d*Cp*V*(Tfin - Tini)/(t*3600) Pool Heat-Up Rate Q1 2.03 Kw Q1=d*Cp*V*(Tfin - Tini)/(t*3600)
Pool Surface Heat Loss Q2 43.99 Kw Q2=Usurf*A*(Tpool - Tamb) Pool Surface Heat Loss Q2 27.99 Kw Q2=Usurf*A*(Tpool - Tamb)
Q3=Uwall*Awall*(Tpool-T1) + Q3=Uwall*Awall*(Tpool-T1) +
Q3 Q3
Pool Wall/Floor Heat Loss 1.78 Kw Ufloor*Afloor*(Tpool-T2) Pool Wall/Floor Heat Loss 0.86 Kw Ufloor*Afloor*(Tpool-T2)
Waterfall Surface Heat Loss Q4 0.00 Kw Q4=Uwfall*Awfall*(Tpool - Tamb) Waterfall Surface Heat Loss Q4 0.00 Kw Q4=Uwfall*Awfall*(Tpool - Tamb)
Total Required Heater Capacity QT 57.05 Kw QT=SF*(Q1+Q2+Q3+Q4) Total Required Heater Capacity QT 37.06 Kw QT=SF*(Q1+Q2+Q3+Q4)
Table 3-4: Heating Calculation (Jacuzzi-Hotel) Table 3-5: Heating Calculation (Swimming Pool-Residences-Type 1)

RCHR-G-FD-CLC-P4-ME-01 R01 Page 43 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 Swimming Pool-Residences-Type 2:  Swimming Pool-Residences-Type 3:

Initial Values Initial Values


Ambient temperature Tamb 22.00 °C Ambient temperature Tamb 22.00 °C
Pool Water desired temperature Tpool 40.00 °C Pool Water desired temperature Tpool 40.00 °C
Pool Water Initial temperature Tini 20.00 °C Pool Water Initial temperature Tini 20.00 °C
Pool Water Final desired temperature Tfin 40.00 °C Pool Water Final desired temperature Tfin 40.00 °C
density of water d 998.00 kg/m3 density of water d 998.00 kg/m3
Specific heat of water Cp 4.19 KJ/kg.C Specific heat of water Cp 4.19 KJ/kg.C
0.045 Kw/m2.K ------> wind velocity 0.045 Kw/m2.K ------> wind velocity
below 5 Km/hr below 5 Km/hr
0.06 Kw/m2.K ------> wind velocity 0.06 Kw/m2.K ------> wind velocity
between 5 to 8 Km/hr between 5 to 8 Km/hr
Water Surface heat transfer coefficient Usurf 0.120 kw/m2.k Water Surface heat transfer coefficient Usurf 0.120 kw/m2.k
0.075 Kw/m2.K ------> wind velocity 0.075 Kw/m2.K ------> wind velocity
around 8 Km/hr around 8 Km/hr
0.12 Kw/m2.K ------> wind velocity 0.12 Kw/m2.K ------> wind velocity
around 16 Km/hr around 16 Km/hr
Pool heat-up time t 80.00 Hours Pool heat-up time t 80.00 Hours
Pool surface Area A 12.12 m2 Pool surface Area A 13.90 m2
Pool Volume V 6.50 m3 Pool Volume V 7.00 m3
1.15 ------> Coast 1.15 ------> Coast
Safety factor SF 1.20 Safety factor SF 1.20
1.2 ------> Mountain 1.2 ------> Mountain
Fill Only When Having Above Ground Or Suspended Pool Case Fill Only When Having Above Ground Or Suspended Pool Case
Pool total wall surface Awall 7.88 m2 Pool total wall surface Awall 8.63 m2
Pool total floor surface Afloor 6.95 m2 Pool total floor surface Afloor 8.44 m2
Temperature of Area behind wall T1 22.00 °C Temperature of Area behind wall T1 22.00 °C
Temperature of media below pool T2 22.00 °C Temperature of media below pool T2 22.00 °C
Heat transfer coefficient through pool wall Uwall 0.004 kw/m2.K Heat transfer coefficient through pool wall Uwall 0.004 kw/m2.K
Heat transfer coefficient through pool Floor Ufloor 0.004 kw/m2.K Heat transfer coefficient through pool Floor Ufloor 0.004 kw/m2.K
Waterfall total Area Awfall 0.00 m2 Waterfall total Area Awfall 0.00 m2
Waterfall Surface heat transfer coefficient Uwfall 0.24 kw/m2.k Waterfall Surface heat transfer coefficient Uwfall 0.24 kw/m2.k
OUTPUT DATA (HEATING LOAD) OUTPUT DATA (HEATING LOAD)
Pool Heat-Up Rate Q1 1.89 Kw Q1=d*Cp*V*(Tfin - Tini)/(t*3600) Pool Heat-Up Rate Q1 2.03 Kw Q1=d*Cp*V*(Tfin - Tini)/(t*3600)
Pool Surface Heat Loss Q2 26.18 Kw Q2=Usurf*A*(Tpool - Tamb) Pool Surface Heat Loss Q2 30.02 Kw Q2=Usurf*A*(Tpool - Tamb)
Q3=Uwall*Awall*(Tpool-T1) + Q3=Uwall*Awall*(Tpool-T1) +
Q3 Q3
Pool Wall/Floor Heat Loss 0.93 Kw Ufloor*Afloor*(Tpool-T2) Pool Wall/Floor Heat Loss 1.08 Kw Ufloor*Afloor*(Tpool-T2)
Waterfall Surface Heat Loss Q4 0.00 Kw Q4=Uwfall*Awfall*(Tpool - Tamb) Waterfall Surface Heat Loss Q4 0.00 Kw Q4=Uwfall*Awfall*(Tpool - Tamb)
Total Required Heater Capacity QT 34.80 Kw QT=SF*(Q1+Q2+Q3+Q4) Total Required Heater Capacity QT 39.76 Kw QT=SF*(Q1+Q2+Q3+Q4)
Table 3-6: Heating Calculation (Swimming Pool-Residences-Type 2) Table 3-7: Heating Calculation (Swimming Pool-Residences-Type 3)

RCHR-G-FD-CLC-P4-ME-01 R01 Page 44 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 Swimming Pool-Residences-Type 4:  Jacuzzi- Residences:

Initial Values Initial Values


Indoor temperature Tamb 27.00 °C Ambient temperature Tamb 22.00 °C
Pool Water desired temperature Tpool 29.00 °C Pool Water desired temperature Tpool 40.00 °C
Pool Water Initial temperature Tini 8.00 °C Pool Water Initial temperature Tini 10.00 °C
Pool Water Final desired temperature Tfin 29.00 °C Pool Water Final desired temperature Tfin 40.00 °C
density of water d 998.00 kg/m3 density of water d 998.00 kg/m3
Specific heat of water Cp 4.19 KJ/kg.C Specific heat of water Cp 4.19 KJ/kg.C
0.045 Kw/m2.K ------> wind velocity 0.045 Kw/m2.K ------> wind velocity
below 5 Km/hr below 5 Km/hr
0.06 Kw/m2.K ------> wind velocity 0.06 Kw/m2.K ------> wind velocity
between 5 to 8 Km/hr between 5 to 8 Km/hr
Water Surface heat transfer coefficient Usurf 0.120 kw/m2.k Water Surface heat transfer coefficient Usurf 0.120 kw/m2.k
0.075 Kw/m2.K ------> wind velocity 0.075 Kw/m2.K ------> wind velocity
around 8 Km/hr around 8 Km/hr
0.12 Kw/m2.K ------> wind velocity 0.12 Kw/m2.K ------> wind velocity
around 16 Km/hr around 16 Km/hr
Pool heat-up time t 84.00 Hours Pool heat-up time t 128.00 Hours
Pool surface Area A 90.00 m2 Pool surface Area A 8 m2
Pool Volume V 135.00 m3 Pool Volume V 5.8 m3
1.15 ------> Coast 1.15 ------> Coast
Safety factor SF 1.20 Safety factor SF 1.20
1.2 ------> Mountain 1.2 ------> Mountain
Fill Only When Having Above Ground Or Suspended Pool Case Fill Only When Having Above Ground Or Suspended Pool Case
Pool total wall surface Awall 63.00 Pool total wall surface Pool total wall surface Awall 8 m2
Pool total floor surface Afloor 90.00 Pool total floor surface Pool total floor surface Afloor 3.9 m2
Temperature of Area behind wall T1 21.00 Temperature of Area behind wall Temperature of Area behind wall T1 21.00 °C
Temperature of media below pool T2 21.00 Temperature of media below pool Temperature of media below pool T2 11.00 °C
Heat transfer coefficient through pool Heat transfer coefficient through pool wall Uwall 0.004 kw/m2.K
Uwall Heat transfer coefficient through pool Floor Ufloor 0.004 kw/m2.K
Heat transfer coefficient through pool wall 0.004 wall
Heat transfer coefficient through pool Waterfall total Area Awfall 0.00 m2
Ufloor
Heat transfer coefficient through pool Floor 0.004 Floor Waterfall Surface heat transfer coefficient Uwfall 0.24 kw/m2.k
Waterfall total Area Awfall 0.00 Waterfall total Area OUTPUT DATA (HEATING LOAD)
Waterfall Surface heat transfer Pool Heat-Up Rate Q1 1.68 Kw Q1=d*Cp*V*(Tfin - Tini)/(t*3600)
Waterfall Surface heat transfer coefficient Uwfall
0.24 coefficient Pool Surface Heat Loss Q2 28.8 Kw Q2=Usurf*A*(Tpool - Tamb)
OUTPUT DATA (HEATING LOAD) Q3
Q3=Uwall*Awall*(Tpool-T1) +
Pool Heat-Up Rate Q1 39.20 Kw Q1=d*Cp*V*(Tfin - Tini)/(t*3600) Pool Wall/Floor Heat Loss 1.06 Kw Ufloor*Afloor*(Tpool-T2)
Pool Surface Heat Loss Q2 21.6 Kw Q2=Usurf*A*(Tpool - Tamb) Waterfall Surface Heat Loss Q4 0.00 Kw Q4=Uwfall*Awfall*(Tpool - Tamb)
Q3=Uwall*Awall*(Tpool-T1) + Total Required Heater Capacity QT 35.69 Kw QT=SF*(Q1+Q2+Q3+Q4)
Q3 Table 3-9: Heating Calculation (Jacuzzi- Residences)
Pool Wall/Floor Heat Loss 4.90 Kw Ufloor*Afloor*(Tpool-T2)
Waterfall Surface Heat Loss Q4 0.00 Kw Q4=Uwfall*Awfall*(Tpool - Tamb)
Total Required Heater Capacity QT 65.7 Kw QT=SF*(Q1+Q2+Q3+Q4)
Table 3-8: Heating Calculation (Swimming Pool-Residences-Type 4)

RCHR-G-FD-CLC-P4-ME-01 R01 Page 45 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

7. Air Blowers  Jacuzzi-Residences:


N(H) = 8 Air Blow Nozzels
The total flow of the air blower serving the air blowers nozzles (seat nozzles) (in whirl pools and Jacuzzi) F(H) = 7.5 x N(H)
should have a flow covering the demand of all the air nozzles of the pool simultaneously. F = 7.5 x 8 = 60 m3/hr
Thus, the Air blower flow (AB-JC-R) is 60 m3/hr
For standard air blower nozzles, a flow of 7.5m3/hr is required for each fitting to give the required effect.

F= F(H) x N(H) 8. Salt Chlorine Generators


Where F=Air Flow in m³/hr
The salt chlorine generator is selected depending on the pool volume:
F(H)=Nozzle Air Flow demand in m³/hr=7.5 m³/hr Per Nozzle
N(H)=Number of Nozzles in the pool For pools below 60m3, a chlorine production of max 16.2 g/hr is required.
Thus, F= 7.5 x N(H) For pools below 100m3, a chlorine production of max 24.7 g/hr is required.
For pools below 160m3, a chlorine production of max 30.4 g/hr is required.
 Swimming Pool-Hotel-Type 2:
For this,
N(H)= 10 Air Blower Nozzles  The Swimming Pool-Hotel-Type 1 should have two salt chlorine generators, each having a maximum
F= 7.5 x N(H) chlorine production of 30.4 g/hr.
F= 7.5 x 10= 75 m³/hr  The Swimming Pool-Hotel-Type 3 should have one salt chlorine generator of 24.7 g/hr is required.
Thus, the Air blower flow (AB-SP-H-Type 2) is 75 m³/hr.  The Swimming Pool-Residence –Type 4 should have one salt chlorine generator of 30.4 g/hr is
required.
 Jacuzzi-Hotel:  The salt chlorine generators of the 5 water features and the 5 whirl pools should have a maximum
chlorine production of 16.2 g/hr.
N(H)= 12 Air Blower Nozzles
F= 7.5 x N(H)
F= 7.5 x 12= 90 m³/hr 9. Ultra-Violet Treatment Modules
Thus, the Air blower flow (AB-JC-H) is 90 m³/hr.
The Ultra-Violet treatment module is selected depending on the filtration flow for a dosing rate of 30mj/cm 2.
 Swimming Pool-Residences-Type 1:
N(H)= 11 Air Blower Nozzles For a flow up to 12m3/hr, a single tube module (55w) is required.
F= 7.5 x N(H) For a flow up to 24m3/hr, a double tube module (110w) is required.
F= 7.5 x 11= 82.5 m³/hr
Thus, the Air blower flow (AB-SP-R-Type 1) is 82.5 m³/hr.  Swimming Pool-Hotel-Type 1:
Total filtration flow= 3 x 30m3/hr=90m3/hr
 Swimming Pool-Residences-Type 2: Thus, 4 double tube (110w) ultra-violet treatment modules are required.
N(H)= 8 Air Blower Nozzles
F= 7.5 x N(H)  Swimming Pool-Hotel-Type 2:
F= 7.5 x 8= 60 m³/hr Total filtration flow= 9m3/hr
Thus, the Air blower flow (AB-SP-R-Type 2) is 60 m³/hr. Thus, 1 single tube (55w) ultra-violet treatment module is required.

 Swimming Pool-Residences-Type 3:  Swimming Pool-Hotel-Type 3:


N(H)= 8 Air Blower Nozzles Total filtration flow = 15 m3/hr
F= 7.5 x N(H) Thus, 1 single tube (110w) ultra-violet treatment module is required.
F= 7.5 x 8= 60 m³/hr
Thus, the Air blower flow (AB-SP-R-Type 3) is 60 m³/hr.  Jacuzzi-Hotel:
Total filtration flow= 21m3/hr
Thus, 1 double tube (110w) ultra-violet treatment module is required

RCHR-G-FD-CLC-P4-ME-01 R01 Page 46 of 47


Ritz Carlton Hotel and Residences J17006-0100D –Calculation Report
Amman - Jordan NOVEMBER 2018

 Swimming Pool-Residences-Type 1: 10. Fittings


Total filtration flow= 21m3/hr
Thus, 1 double tube (110w) ultra-violet treatment module is required.  Drains:
All the pools will have multiple drains separated at least by 90cm.
 Swimming Pool-Residences-Type 2: The drains grilles will be selected to have their holes less than 8mm width and the size of the drain grilles
Total filtration flow= 21m3/hr should be defined by having the water velocity less than 0.5m/s.
Thus, 1 double tube (110w) ultra-violet treatment module is required. No different size pumps can have their suction from same drain grille.

 Swimming Pool-Residences-Type 3:  Skimmers:


Total filtration flow= 21m3/hr Each skimmer will take up to 7 m3/hr and maximum area coverage of 25m2.
Thus, 1 double tube (110w) ultra-violet treatment module is required. However, for a better coverage, the number of inlets may be increased to cover all the pool space
(depending on the pool geometry and the wind direction).
 Swimming Poll-Residences-Type 4:
Total filtration flow = 34 m3/hr  Floor Inlet:
Thus, 2 double tube (110w) ulta-violet treatment module are required. Each standard floor inlet (63mm) can supply up to 14m3/hr.
However, for a better water filtration, the number of inlets may be increased to cover all the pool space
 Jacuzzi-Residences: (depending on the pool geometry).
Total filtration flow = 16 m3/hr
Thus, 1 single tube (110w) ultra-violet treatment module is required.  Wall Inlet:
Each standard wall inlet (50mm) can supply up to 5m3/hr.
 Water Feature-General: However, for a better water filtration, the number of inlets may be increased to cover all the pool space
Total filtration flow= 6m3/hr (depending on the pool geometry).
Thus, 1 single tube (55w) ultra-violet treatment module is required.
 Vacuum Fitting:
 Water Feature-Hotel-Type 1: Each vacuum fitting will cover around 80 m2 depending on vacuum hose length (A 10 m hose covers 80
Total filtration flow= 6m3/hr m2). However, this number may increase/ decrease depending on the pool geometry.
Thus, 1 single tube (55w) ultra-violet treatment module is required.

 Water Feature-Hotel-Type 2:
Total filtration flow= 9m3/hr
Thus, 1 single tube (55w) ultra-violet treatment module is required.

 Water Feature-Residences:
Total filtration flow= 6m3/hr
Thus, 1 single tube (55w) ultra-violet treatment module is required.

 Water Feature-Hotel-Type 3:
Total filtration flow= 6m3/hr
Thus, 1 single tube (55w) ultra-violet treatment module is required.

RCHR-G-FD-CLC-P4-ME-01 R01 Page 47 of 47


Appendix – A

Hotel Building
Cooling & Heating Load Calculations
Design Weather Parameters & MSHGs
J17006-0100D FD REV2 11/21/2018
dar 10:16AM

Design Parameters:

City Name Amman


Location Jordan
Latitude 32.0 Deg.
Longitude -36.0 Deg.
Elevation 773.0 m
Summer Design Dry-Bulb 37.0 °C
Summer Coincident Wet-Bulb 22.0 °C
Summer Daily Range 11.3 °K
Winter Design Dry-Bulb -0.8 °C
Winter Design Wet-Bulb -2.5 °C
Atmospheric Clearness Number 1.00
Average Ground Reflectance 0.20
Soil Conductivity 1.385 W/(m-°K)
Local Time Zone (GMT +/- N hours) -2.0 hours
Consider Daylight Savings Time No
Simulation Weather Data noneN/A
Current Data is User Modified
Design Cooling Months January to December

Design Day Maximum Solar Heat Gains

(The MSHG values are expressed in W/m² )

Month N NNE NE ENE E ESE SE SSE S


January 74.0 74.0 95.4 318.4 563.3 711.9 793.4 792.2 775.1
February 86.0 86.0 220.1 450.4 652.2 769.1 777.9 729.5 692.9
March 99.3 108.4 356.1 578.1 706.0 757.8 713.1 612.2 552.6
April 112.1 252.6 458.9 635.3 715.3 686.2 591.2 444.5 362.5
May 120.8 350.2 532.6 657.0 694.6 627.9 488.3 313.2 232.7
June 151.3 383.2 548.5 661.8 678.3 594.1 442.0 261.3 190.4
July 126.0 345.1 527.0 651.7 680.2 606.9 476.6 303.2 225.4
August 117.3 247.2 455.0 617.8 688.3 656.6 570.0 428.2 349.6
September 102.9 109.3 321.9 545.8 679.6 715.1 688.7 596.7 540.1
October 88.8 88.8 187.4 450.8 628.7 731.4 759.1 712.9 676.0
November 75.3 75.3 88.6 331.5 536.8 708.5 769.3 778.8 765.8
December 68.8 68.8 68.8 252.8 515.0 683.1 779.7 797.4 794.1
Month SSW SW WSW W WNW NW NNW HOR Mult
January 794.0 790.6 716.1 547.0 340.8 79.5 74.0 553.5 1.00
February 734.8 785.9 756.1 660.3 460.3 209.1 86.0 680.6 1.00
March 615.0 714.5 759.1 717.0 564.5 356.7 112.2 793.5 1.00
April 444.2 589.6 691.9 714.3 628.0 468.2 252.0 854.1 1.00
May 312.7 486.7 629.5 693.0 652.9 537.3 350.1 872.7 1.00
June 260.2 436.7 597.8 673.1 653.7 560.9 383.6 870.7 1.00
July 301.4 469.7 615.6 674.2 640.6 535.0 347.3 859.8 1.00
August 428.0 568.1 667.0 689.0 607.5 455.6 249.9 836.2 1.00
September 596.1 688.1 718.5 677.3 546.7 326.8 108.2 769.1 1.00
October 706.7 747.8 741.5 620.6 443.2 209.0 88.8 670.6 1.00
November 776.7 776.9 706.2 550.1 310.0 95.6 75.3 552.2 1.00
December 794.8 774.1 688.2 508.6 273.9 68.8 68.8 499.4 1.00
Mult. = User-defined solar multiplier factor.

Hourly Analysis Program v4.80 Page 1 of 7


Cooling Design Temperature Profiles
J17006-0100D FD REV2 11/21/2018
dar 10:16AM

Location: Amman, Jordan

( Dry and Wet Bulb temperatures are expressed in °C )

Hr January February March April May June


DB WB DB WB DB WB DB WB DB WB DB WB
0000 16.4 11.9 17.8 13.2 20.9 15.7 23.0 16.9 25.5 18.2 27.2 19.4
0100 15.8 11.7 17.3 13.0 20.4 15.5 22.4 16.7 24.9 18.0 26.6 19.2
0200 15.3 11.5 16.7 12.8 19.8 15.3 21.8 16.5 24.4 17.8 26.0 19.0
0300 14.8 11.3 16.2 12.6 19.4 15.1 21.4 16.4 23.9 17.7 25.6 18.9
0400 14.5 11.2 15.9 12.4 19.0 15.0 21.0 16.3 23.6 17.5 25.3 18.8
0500 14.3 11.1 15.8 12.4 18.9 15.0 20.9 16.2 23.5 17.5 25.1 18.8
0600 14.6 11.2 16.0 12.5 19.1 15.1 21.1 16.3 23.7 17.6 25.4 18.8
0700 15.1 11.4 16.6 12.7 19.7 15.2 21.7 16.5 24.3 17.8 25.9 19.0
0800 16.2 11.8 17.6 13.1 20.7 15.6 22.7 16.8 25.3 18.1 27.0 19.3
0900 17.6 12.4 19.1 13.6 22.2 16.1 24.2 17.3 26.8 18.5 28.4 19.8
1000 19.3 13.0 20.8 14.3 23.9 16.7 25.9 17.9 28.4 19.1 30.1 20.2
1100 21.2 13.8 22.7 14.9 25.8 17.3 27.8 18.5 30.4 19.6 32.0 20.8
1200 23.0 14.4 24.5 15.6 27.6 17.9 29.6 19.0 32.2 20.2 33.8 21.3
1300 24.4 14.9 25.9 16.0 29.0 18.3 31.0 19.4 33.5 20.5 35.2 21.7
1400 25.3 15.2 26.8 16.3 29.9 18.6 31.9 19.7 34.4 20.8 36.1 21.9
1500 25.6 15.3 27.1 16.4 30.2 18.7 32.2 19.8 34.8 20.9 36.4 22.0
1600 25.3 15.2 26.8 16.3 29.9 18.6 31.9 19.7 34.4 20.8 36.1 21.9
1700 24.5 14.9 26.0 16.1 29.1 18.3 31.1 19.4 33.6 20.6 35.3 21.7
1800 23.3 14.5 24.7 15.7 27.8 17.9 29.8 19.1 32.4 20.2 34.1 21.4
1900 21.8 14.0 23.3 15.1 26.4 17.5 28.4 18.6 30.9 19.8 32.6 20.9
2000 20.3 13.4 21.8 14.6 24.9 17.0 26.9 18.2 29.5 19.4 31.1 20.5
2100 19.1 13.0 20.5 14.2 23.7 16.6 25.7 17.8 28.2 19.0 29.9 20.2
2200 18.0 12.5 19.4 13.8 22.5 16.2 24.5 17.4 27.1 18.6 28.8 19.9
2300 17.1 12.2 18.5 13.4 21.6 15.9 23.6 17.1 26.2 18.4 27.9 19.6

Hr July August September October November December


DB WB DB WB DB WB DB WB DB WB DB WB
0000 27.7 19.4 27.7 19.4 26.6 18.8 24.1 17.2 20.4 15.7 17.3 13.2
0100 27.2 19.2 27.2 19.2 26.1 18.6 23.5 17.0 19.8 15.5 16.7 13.0
0200 26.6 19.0 26.6 19.0 25.5 18.4 22.9 16.8 19.3 15.3 16.1 12.7
0300 26.2 18.9 26.2 18.9 25.0 18.3 22.5 16.6 18.8 15.1 15.7 12.6
0400 25.8 18.8 25.8 18.8 24.7 18.2 22.1 16.5 18.5 15.0 15.4 12.4
0500 25.7 18.8 25.7 18.8 24.6 18.1 22.0 16.5 18.4 15.0 15.2 12.4
0600 25.9 18.8 25.9 18.8 24.8 18.2 22.3 16.6 18.6 15.0 15.5 12.5
0700 26.5 19.0 26.5 19.0 25.4 18.4 22.8 16.7 19.1 15.2 16.0 12.7
0800 27.5 19.3 27.5 19.3 26.4 18.7 23.8 17.1 20.2 15.6 17.1 13.1
0900 29.0 19.8 29.0 19.8 27.9 19.2 25.3 17.6 21.6 16.1 18.5 13.6
1000 30.7 20.2 30.7 20.2 29.6 19.6 27.0 18.1 23.3 16.7 20.2 14.3
1100 32.6 20.8 32.6 20.8 31.5 20.2 28.9 18.7 25.3 17.3 22.1 14.9
1200 34.4 21.3 34.4 21.3 33.3 20.7 30.7 19.2 27.1 17.9 23.9 15.6
1300 35.8 21.7 35.8 21.7 34.6 21.1 32.1 19.6 28.4 18.3 25.3 16.0
1400 36.7 21.9 36.7 21.9 35.5 21.4 33.0 19.9 29.3 18.6 26.2 16.3
1500 37.0 22.0 37.0 22.0 35.9 21.4 33.3 20.0 29.7 18.7 26.5 16.4
1600 36.7 21.9 36.7 21.9 35.5 21.4 33.0 19.9 29.3 18.6 26.2 16.3
1700 35.9 21.7 35.9 21.7 34.8 21.1 32.2 19.7 28.5 18.3 25.4 16.1
1800 34.6 21.4 34.6 21.4 33.5 20.8 31.0 19.3 27.3 17.9 24.2 15.6
1900 33.2 20.9 33.2 20.9 32.0 20.4 29.5 18.9 25.8 17.5 22.7 15.1
2000 31.7 20.5 31.7 20.5 30.6 19.9 28.0 18.4 24.3 17.0 21.2 14.6
2100 30.4 20.2 30.4 20.2 29.3 19.6 26.8 18.0 23.1 16.6 20.0 14.2
2200 29.3 19.9 29.3 19.9 28.2 19.3 25.6 17.7 22.0 16.2 18.9 13.8
2300 28.4 19.6 28.4 19.6 27.3 19.0 24.7 17.4 21.1 15.9 18.0 13.4

Hourly Analysis Program v4.80 Page 2 of 7


Design Temperature Profile
J17006-0100D FD REV2 11/21/2018
dar 10:16AM

Location: Amman, Jordan

Design Temperature Profiles for July

Dry Bulb Wet Bulb


38

36

34

32
Temperature ( °C )

30

28

26

24

22

20

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour

Hourly Analysis Program v4.80 Page 3 of 7


Design Solar Flux and Heat Gain Profiles
J17006-0100D FD REV2 11/21/2018
dar 10:16AM

Location: Amman, Jordan

Design Solar Fluxes for July


( Values for each exposure are expressed in W/m² )

Hour N NNE NE ENE E ESE SE SSE


0000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 117.1 212.2 280.2 309.0 293.3 236.0 147.4 42.7
0600 199.9 420.2 591.2 683.3 679.8 581.4 405.8 183.4
0700 164.2 415.7 624.5 755.3 785.0 708.4 539.0 306.3
0800 128.7 334.9 541.3 686.8 746.5 710.0 583.7 389.3
0900 142.3 226.1 400.8 538.7 617.1 622.9 555.1 425.0
1000 151.1 156.5 235.0 346.1 429.2 471.1 464.9 411.7
1100 154.8 156.1 158.6 162.1 209.6 276.7 326.8 352.1
1200 153.2 149.8 149.8 149.8 153.0 156.5 161.4 253.1
1300 146.5 141.3 141.3 141.3 141.3 141.3 144.3 151.6
1400 134.7 126.7 126.7 126.7 126.7 126.7 126.7 130.5
1500 139.9 106.2 106.2 106.2 106.2 106.2 106.2 106.2
1600 192.2 79.3 79.3 79.3 79.3 79.3 79.3 79.3
1700 176.5 46.2 42.8 42.8 42.8 42.8 42.8 42.8
1800 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Hour S SSW SW WSW W WNW NW NNW HOR
0000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 23.2 23.2 23.2 23.2 23.2 23.2 23.2 25.8 72.8
0600 68.3 66.2 66.2 66.2 66.2 66.2 66.2 69.0 293.3
0700 103.2 96.2 96.2 96.2 96.2 96.2 96.2 96.2 507.3
0800 159.1 119.2 119.2 119.2 119.2 119.2 119.2 119.2 694.0
0900 254.3 143.7 136.2 136.2 136.2 136.2 136.2 136.2 841.0
1000 320.0 204.6 155.0 147.1 147.1 147.1 147.1 147.1 938.3
1100 348.4 316.5 261.3 191.5 161.2 157.9 155.7 151.7 979.6
1200 336.2 393.0 414.3 396.8 343.3 262.3 166.6 156.9 961.9
1300 284.8 425.5 525.5 568.4 547.0 464.9 335.7 180.3 886.5
1400 200.2 409.6 580.3 684.1 703.3 634.5 489.6 292.9 758.5
1500 115.5 345.0 566.6 721.5 783.0 740.2 600.7 388.8 586.4
1600 83.2 236.8 471.5 651.3 744.9 735.5 624.9 432.8 381.7
1700 42.8 98.2 270.3 412.0 498.9 515.4 458.5 338.4 159.6
1800 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.0
1900 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 4 of 7


Design Solar Flux and Heat Gain Profiles
J17006-0100D FD REV2 11/21/2018
dar 10:16AM

Location: Amman, Jordan

Design Beam Solar Heat Gains for July


( Values for each exposure are expressed in W/m² )

Hour N NNE NE ENE E ESE SE SSE


0000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 56.8 146.1 204.7 227.0 215.4 166.7 86.5 2.4
0600 55.9 263.3 413.7 492.1 489.3 405.2 249.9 43.4
0700 10.8 212.2 406.9 520.2 545.9 479.6 330.4 107.2
0800 0.0 104.7 302.9 436.0 488.0 456.3 342.9 154.7
0900 0.0 17.1 144.8 278.9 354.0 359.4 294.9 167.7
1000 0.0 0.0 15.8 85.2 158.8 199.1 193.1 142.4
1100 0.0 0.0 0.0 0.0 5.8 33.5 66.2 85.7
1200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5
1300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 1.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 72.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Hour S SSW SW WSW W WNW NW NNW HOR
0000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 13.9
0600 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 148.8
0700 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 336.9
0800 2.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 505.0
0900 30.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 640.1
1000 65.1 5.7 0.0 0.0 0.0 0.0 0.0 0.0 728.3
1100 82.7 58.8 25.4 2.1 0.0 0.0 0.0 0.0 762.6
1200 75.0 122.4 141.8 125.9 80.5 27.0 0.0 0.0 748.3
1300 45.5 162.0 259.7 301.5 280.7 200.1 82.4 2.0 682.1
1400 11.1 164.5 330.6 425.6 442.5 381.0 242.8 63.0 563.9
1500 0.0 129.7 343.0 480.0 533.2 496.2 374.2 171.4 408.0
1600 0.0 69.0 291.2 449.6 530.1 522.2 426.8 254.7 224.4
1700 0.0 13.0 163.2 289.9 363.8 376.3 330.1 226.0 53.5
1800 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.0 0.0
1900 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 5 of 7


Design Solar Flux and Heat Gain Profiles
J17006-0100D FD REV2 11/21/2018
dar 10:16AM

Location: Amman, Jordan

Design Diffuse Solar Heat Gains for July


( Values for each exposure are expressed in W/m² )

Hour N NNE NE ENE E ESE SE SSE


0000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 26.7 33.8 40.0 42.9 41.3 35.9 28.8 22.5
0600 67.0 81.8 96.2 105.0 104.6 95.3 80.7 66.0
0700 89.3 104.2 120.1 131.6 134.4 127.4 113.3 97.1
0800 104.7 116.8 130.5 141.9 146.9 143.8 133.7 120.1
0900 115.8 124.0 133.9 143.1 148.9 149.3 144.3 135.4
1000 122.9 127.3 133.0 139.0 144.1 146.8 146.3 143.0
1100 126.0 127.0 129.0 131.9 135.3 138.7 141.5 142.9
1200 124.7 121.8 121.8 121.8 124.4 127.3 131.3 136.0
1300 119.1 115.0 115.0 115.0 115.0 115.0 117.4 123.3
1400 109.6 103.1 103.1 103.1 103.1 103.1 103.1 106.1
1500 96.0 86.4 86.4 86.4 86.4 86.4 86.4 86.4
1600 77.1 64.5 64.5 64.5 64.5 64.5 64.5 64.5
1700 46.5 37.6 34.8 34.8 34.8 34.8 34.8 34.8
1800 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Hour S SSW SW WSW W WNW NW NNW HOR
0000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 18.8 18.8 18.8 18.8 18.8 18.8 18.8 21.0 28.7
0600 55.6 53.8 53.8 53.8 53.8 53.8 53.8 56.1 66.6
0700 84.0 78.3 78.3 78.3 78.3 78.3 78.3 78.3 82.2
0800 107.3 96.9 96.9 96.9 96.9 96.9 96.9 96.9 90.0
0900 125.5 116.9 110.8 110.8 110.8 110.8 110.8 110.8 94.2
1000 137.5 131.5 126.1 119.7 119.7 119.7 119.7 119.7 96.4
1100 142.7 140.9 137.9 134.4 131.1 128.5 126.7 123.4 97.2
1200 140.5 143.8 145.1 144.0 140.9 136.4 131.7 127.6 96.8
1300 131.1 139.4 146.0 149.1 147.6 141.9 134.0 125.8 95.2
1400 115.3 127.2 139.1 147.2 148.7 143.2 132.5 120.2 92.0
1500 93.9 107.3 122.8 135.5 141.0 137.2 125.4 110.1 85.9
1600 67.7 79.7 95.5 110.6 119.3 118.4 108.2 92.6 74.4
1700 34.8 42.1 52.9 64.5 72.7 74.4 68.8 58.2 48.5
1800 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 6 of 7


Design Solar Flux and Heat Gain Profiles
J17006-0100D FD REV2 11/21/2018
dar 10:16AM

Location: Amman, Jordan

Design Total Solar Heat Gains for July


( Values for each exposure are expressed in W/m² )

Hour N NNE NE ENE E ESE SE SSE


0000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 83.5 179.9 244.8 269.9 256.7 202.6 115.3 24.8
0600 122.9 345.1 509.9 597.1 593.9 500.6 330.6 109.4
0700 100.0 316.4 527.0 651.8 680.2 606.9 443.6 204.3
0800 104.7 221.5 433.4 577.9 634.9 600.1 476.6 274.8
0900 115.8 141.1 278.7 422.0 502.9 508.7 439.1 303.2
1000 122.9 127.3 148.8 224.2 302.8 345.9 339.5 285.3
1100 126.0 127.0 129.0 131.9 141.1 172.3 207.7 228.6
1200 124.7 121.8 121.8 121.8 124.4 127.3 131.3 158.4
1300 119.1 115.0 115.0 115.0 115.0 115.0 117.4 123.3
1400 109.6 103.1 103.1 103.1 103.1 103.1 103.1 106.2
1500 97.7 86.4 86.4 86.4 86.4 86.4 86.4 86.4
1600 113.3 64.5 64.5 64.5 64.5 64.5 64.5 64.5
1700 118.7 37.6 34.8 34.8 34.8 34.8 34.8 34.8
1800 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Hour S SSW SW WSW W WNW NW NNW HOR
0000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 18.8 18.8 18.8 18.8 18.8 18.8 18.8 21.0 42.6
0600 55.6 53.8 53.8 53.8 53.8 53.8 53.8 56.2 215.4
0700 84.0 78.3 78.3 78.3 78.3 78.3 78.3 78.3 419.1
0800 109.7 97.0 97.0 97.0 97.0 97.0 97.0 97.0 595.0
0900 156.3 116.9 110.8 110.8 110.8 110.8 110.8 110.8 734.3
1000 202.7 137.2 126.1 119.7 119.7 119.7 119.7 119.7 824.7
1100 225.4 199.7 163.3 136.5 131.1 128.5 126.7 123.4 859.8
1200 215.5 266.3 287.0 269.9 221.4 163.4 131.8 127.7 845.1
1300 176.6 301.4 405.7 450.6 428.3 342.1 216.4 127.8 777.3
1400 126.4 291.7 469.7 572.8 591.3 524.2 375.3 183.2 655.8
1500 93.9 237.0 465.8 615.6 674.2 633.4 499.6 281.5 494.0
1600 67.7 148.6 386.7 560.1 649.4 640.6 535.0 347.3 298.7
1700 34.8 55.1 216.1 354.4 436.5 450.7 398.9 284.2 102.0
1800 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.0
1900 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 7 of 7


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-06 Purch & Rec St

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 10.79 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 750.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 10.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 46.9 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 1 of312 1


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-07 Purch. Manager

1. General Details:
Floor Area 5.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 8.60 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 5.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -8.0 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 29.3 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 2 of312 2


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-09 Monitoring Statio

1. General Details:
Floor Area 19.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 12.37 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 19.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.8 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 47.5 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 3 of312 3


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-10 Security Supervis

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 12.91 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 9.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.8 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 11.8 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 4 of312 4


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-100 HK Manager

1. General Details:
Floor Area 12.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 13.72 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 12.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 5.1 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 5 of312 5


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-101 Assistance HK

1. General Details:
Floor Area 12.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 18.42 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 12.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 11.7 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 6 of312 6


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-102 Housekeeping

1. General Details:
Floor Area 41.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 16.50 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 41.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 41.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 23.4 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 7 of312 7


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-109 Nurse

1. General Details:
Floor Area 17.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Multi-purpose assembly
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 9.59 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 16.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 16.4 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 8 of312 8


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-112 HR Reception

1. General Details:
Floor Area 27.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 5.83 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 23.4 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 9 of312 9


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-113 HR Clerk

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 12.39 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 10 of312 10


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-114 DR of HR

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.90 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 10.0 m² Area 12.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 11 of312 11


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-115 Training Rm

1. General Details:
Floor Area 35.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage EDUCATION: Classroom (age 9+)
OA Requirement 1 5.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 31.0 People
Wattage 9.84 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 600.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 35.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 5.2 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 12 of312 12


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-116 Dr. of Training

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 13.85 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 13 of312 13


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-117 ENG Reception

1. General Details:
Floor Area 27.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8.0 People
Wattage 8.69 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 12.9 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 14 of312 14


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-119 Dirc of Eng

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 12.65 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 12.6 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 15 of312 15


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-121 Carpenter Shop

1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage EDUCATION: Wood/metal shop
OA Requirement 1 5.0 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 10.52 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 500 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 18.3 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 16 of312 16


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-122 M+E Workshop

1. General Details:
Floor Area 23.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage EDUCATION: Wood/metal shop
OA Requirement 1 5.0 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 8.69 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 500 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 4.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 17 of312 17


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-124 Paint Shop

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Multi-purpose assembly
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 9.81 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 500 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 37.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 18 of312 18


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-125 Electric Rep.

1. General Details:
Floor Area 6.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage EDUCATION: Wood/metal shop
OA Requirement 1 5.0 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 12.37 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 6.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 11.7 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 19 of312 19


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-20 Linen Collection

1. General Details:
Floor Area 14.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 11.51 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 14.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 14.0 m² Area 15.4 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 20 of312 20


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-25 Corridor 1

1. General Details:
Floor Area 381.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 39.0 People
Wattage 3.23 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 191.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 381.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. 0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 369.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 21 of312 21


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-52 Closing Room

1. General Details:
Floor Area 30.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 30.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 30.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 35.1 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 22 of312 22


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-90-Lobby

1. General Details:
Floor Area 25.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 24.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 68.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 23 of312 23


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1A-93 Bridal Suite

1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Bedroom/living room
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 31.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 32.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 68.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 24 of312 24


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1E-70 Pantry

1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.94 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 380 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 18.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 18.0 m² Area 51.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 25 of312 25


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1E-71 Employee Cafe

1. General Details:
Floor Area 152.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Restaurant dining room
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 70.0 People
Wattage 7.44 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4075 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 152.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 62.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 26 of312 26


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1F-34 Chef Office

1. General Details:
Floor Area 5.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 12.50 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 5.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 27 of312 27


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1F-37 Banquet Services

1. General Details:
Floor Area 14.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 12.50 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 14.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 39.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 28 of312 28


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1F-44 Meeting Room 3

1. General Details:
Floor Area 50.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 14.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 50.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 50.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 29 of312 29


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1F-45 Meeting Room 2

1. General Details:
Floor Area 50.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 14.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 50.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 50.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 30 of312 30


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1F-47 Prayer Rm F

1. General Details:
Floor Area 39.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 35.0 People
Wattage 34.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 39.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 39.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 58.5 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 31 of312 31


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1F-48 Prayer Rm M

1. General Details:
Floor Area 28.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 30.0 People
Wattage 34.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 28.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 28.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 80.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 32 of312 32


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1F-50 Meeting Room

1. General Details:
Floor Area 80.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 14.0 People
Wattage 12.50 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 80.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 80.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 80.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 33 of312 33


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1F-53 Executive Chef Of

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 11.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 26.7 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 34 of312 34


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1F-54 Executive Chef Of

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 9.0 m² Area 25.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 35 of312 35


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1G-25 Corridor 4

1. General Details:
Floor Area 88.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 3.23 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1160 W
Schedule None Schedule ELECTRICAL EQUIPMENT 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 88.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 88.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. 0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 50.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 36 of312 36


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1G-74 Prayer Room

1. General Details:
Floor Area 20.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 10.56 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 20.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 20.0 m² Area 8.7 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 37 of312 37


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1G-75 F WC

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 7.29 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 9.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 38 of312 38


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1G-77 F Locker

1. General Details:
Floor Area 26.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 7.29 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 26.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 26.0 m² Area 8.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 39 of312 39


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1G-81 M Locker Room

1. General Details:
Floor Area 130.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 19.0 People
Wattage 5.76 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 130.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 130.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 110.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 40 of312 40


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1G-83 WC

1. General Details:
Floor Area 37.5 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 22.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 37.5 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 77.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 41 of312 41


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1G-87 WC

1. General Details:
Floor Area 39.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 22.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 39.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. 0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 54.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 42 of312 42


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1 - Refrigration Rm

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 1.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 210.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 43 of312 43


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1-25 Corridor 2

1. General Details:
Floor Area 259.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 26.0 People
Wattage 3.23 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 279.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 259.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 188.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 44 of312 44


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1-27 Oven Room

1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 12.21 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 3272 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.4 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 18.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 10.7 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 45 of312 45


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1-30 Regeneration Ar

1. General Details:
Floor Area 75.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 10.17 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 18855 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 75.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 75.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 95.6 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 46 of312 46


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1-32 Service Station

1. General Details:
Floor Area 21.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 14.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 3939 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 47 of312 47


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1-33 Central Dishwash

1. General Details:
Floor Area 47.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 14.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2303 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 47.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 47.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 71.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 48 of312 48


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1-35 Service Station

1. General Details:
Floor Area 16.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 14.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 760 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 16.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 33.6 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 49 of312 49


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1-FA 37 Banquet Servi

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 15.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 50 of312 50


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1-FA 53 Executive Che

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 51 of312 51


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1-FA 54 Executive Che

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 52 of312 52


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K1-FA-34 Chef Office

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 15.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 53 of312 53


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2 - Refrigration RM 1

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 1.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 694.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 54 of312 54


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2 - Refrigration RM 2

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 1.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 630.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 55 of312 55


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-02 Waste Handling

1. General Details:
Floor Area 31.0 m²
Avg. Ceiling Height 3.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 8.24 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1452 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 31.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 14.8 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 56 of312 56


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-04 Waste Chiller

1. General Details:
Floor Area 19.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 19.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 10.5 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 24.0 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 57 of312 57


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-05 Flower Room

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 2.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.0 L/s/person
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 3.57 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 504 W
Schedule None Schedule ELECTRICAL EQUIPMENT 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 22.0 m² Area 30.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 58 of312 58


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-13 F&V Sanitation

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 12.21 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 224 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 6.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 59 of312 59


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-14 Cold Kitchen

1. General Details:
Floor Area 28.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 12.21 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 948 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 28.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 60 of312 60


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-15 Sea Food Prep

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 22.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 23 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 7.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. -0.8 °C
Ambient at Space Min Temp. 11.0 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 61 of312 61


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-16 Meat Prep

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 22.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 521 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 11.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 62 of312 62


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-17 Pork Prep

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 22.00 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 170 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 7.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 63 of312 63


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-22 Dry Storage

1. General Details:
Floor Area 15.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 12.14 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 15.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. -0.8 °C
Ambient at Space Min Temp. 11.0 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 64 of312 64


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-23 Mini Bar Stor

1. General Details:
Floor Area 5.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 32.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 5.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 65 of312 65


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-24 Beverage Storage

1. General Details:
Floor Area 27.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 12.14 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 336 W
Schedule None Schedule ELECTRICAL EQUIPMENT 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. -0.8 °C
Ambient at Space Min Temp. 11.0 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 66 of312 66


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-25 Kitchen Corridor

1. General Details:
Floor Area 39.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 10.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 39.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 67 of312 67


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-26 Bakery

1. General Details:
Floor Area 63.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 13.0 People
Wattage 12.14 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 3061 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 42.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 63.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 39.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 68 of312 68


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1K2-26 Chocolate Room

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 12.21 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 870 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 7.8 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 24.0 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 69 of312 69


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1L-94-Laundry Area

1. General Details:
Floor Area 196.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Laundry room, central
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 66.0 People
Wattage 7.17 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 12775 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 9300 W
Schedule MISC LATENT 100 %
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 168.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 196.0 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 76.6 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 70 of312 70


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1L-95-Laundry Office

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 7.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 7.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 71 of312 71


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1L-96 Uniform Issunace

1. General Details:
Floor Area 33.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Laundry room, central
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 11.0 People
Wattage 10.09 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 355.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 33.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 5.5 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 17.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 72 of312 72


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1L-97-Clean Linen

1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 18.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 25.5 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 73 of312 73


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1P-43 Pre Function 1

1. General Details:
Floor Area 488.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 450.0 People
Wattage 9.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 488.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 488.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.2 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 127.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 74 of312 74


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1P-43 Pre Function 2

1. General Details:
Floor Area 206.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 200.0 People
Wattage 9.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 206.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 112.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 75 of312 75


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1P-85 CRC

1. General Details:
Floor Area 73.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 10.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 73.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. 0.6 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 100.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 76 of312 76


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1P-FA39 AV Control

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 15.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 77 of312 77


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1P-FA44 Meeting Room 3

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 50.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 78 of312 78


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1P-FA45 Meeting Room 2

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 50.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 79 of312 79


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1P-FA47 Prayer/F

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0 % of supply air
OA Requirement 2 105.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 80 of312 80


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1P-FA48 Prayer Room M

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0 % of supply air
OA Requirement 2 85.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 81 of312 81


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C1P-FA50 Meeting Room

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 60.0 L/s
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 82 of312 82


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C2F-10 IT Store

1. General Details:
Floor Area 16.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 7.40 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 16.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 16.0 m² Area 54.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 83 of312 83


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

C2F-11 IT Director

1. General Details:
Floor Area 19.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 7.40 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 19.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 19.0 m² Area 60.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 84 of312 84


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C1-108 Security CC

1. General Details:
Floor Area 34.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 14.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 8500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 34.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 34.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 18.8 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 85 of312 85


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C1-135 IDF

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule ELECTRICAL EQUIPMENT 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 690.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 11.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 48.0 m²
U-Value 1.600 W/(m²-°K)
Uncondit. Space Max Temp 28.0 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 86 of312 86


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C1-36 El Room

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 14.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 3000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 7.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 8.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 25.2 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 87 of312 87


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C1-38 IDF

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule ELECTRICAL EQUIPMENT 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 690.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 10.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 88 of312 88


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C1-39 AV Control

1. General Details:
Floor Area 19.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 14.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 18.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 19.0 m² Area 28.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 89 of312 89


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C1-40 AV Equipment

1. General Details:
Floor Area 37.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 14.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 11900.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 37.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 37.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 52.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 90 of312 90


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C1-56 El Room

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 14.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 3000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 9.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 10.2 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 91 of312 91


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C1-92 IDF

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule ELECTRICAL EQUIPMENT 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 8455.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 10.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 15.4 m²
U-Value 1.600 W/(m²-°K)
Uncondit. Space Max Temp 28.0 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 92 of312 92


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C2-12 Server Room

1. General Details:
Floor Area 65.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 43.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule TASK LIGHTING 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 60000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 65.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 120.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 93 of312 93


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C2-21 EMDB

1. General Details:
Floor Area 49.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 5300.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 74.1 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 94 of312 94


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C2-25 GSM

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 30000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 9.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 37.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 95 of312 95


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C2-27 UPS

1. General Details:
Floor Area 43.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 10000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 43.0 m² Area 51.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 96 of312 96


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C2-30 Demarcation

1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 10000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 13.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 36.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 97 of312 97


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C2-31 Substation

1. General Details:
Floor Area 135.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 45500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 135.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 66.0 m² Area 158.2 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 98 of312 98


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C2-32 MDB Room

1. General Details:
Floor Area 151.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 29600.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 151.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 17.0 m² Area 182.7 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 99 of312 99


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-C3-33 UPS Room

1. General Details:
Floor Area 42.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 23000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 42.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 42.0 m² Area 82.8 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 100 of312 100


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-F19-03 TV Room

1. General Details:
Floor Area 6.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 6000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 8.4 0 0 0
SW 8.4 0 0 0
SE 8.4 0 0 0
NE 8.4 0 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure SW


Wall Type Default Wall Assembly

3.3. Construction Types for Exposure SE


Wall Type Default Wall Assembly

3.4. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 6.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

Hourly Analysis Program v4.80 Page 101 of312 101


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 102 of312 102


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

EL-GF-38 Fire CC

1. General Details:
Floor Area 20.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 14.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule ELECTRICAL EQUIPMENT 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule ELECTRICAL EQUIPMENT 100 %
2.3. Electrical Equipment:
Wattage 2500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 33.0 8 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 20.0 m² Area 40.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 103 of312 103


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-01 Reserv Manager

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 7.7 3 0 0
SW 9.5 0 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure SW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 7.0 m² Area 9.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 104 of312 104


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-02 Reservation

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 11.7 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 9.0 m² Area 7.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 105 of312 105


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-03 Call Center

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 12.8 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 10.0 m² Area 7.7 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 106 of312 106


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-04 Drc of Catr/Conf

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 8.8 3 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 9.0 m² Area 10.7 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 107 of312 107


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-05 Drc of Public Rel

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 8.0 3 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 11.0 m² Area 12.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 108 of312 108


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-06 Drc of Revenue

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 8.2 3 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 11.0 m² Area 12.3 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 109 of312 109


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-07 Meeting Room

1. General Details:
Floor Area 26.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Conference/meeting
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 21.2 6 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 26.0 m² Area 10.7 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 110 of312 110


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-08 General Manager

1. General Details:
Floor Area 20.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.8 0 0 0
SE 11.3 6 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 20.0 m² Area 11.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 111 of312 111


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-09 EAM Room

1. General Details:
Floor Area 12.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 9.0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 12.0 m² Area 12.7 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 112 of312 112


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-10 Quality Manager

1. General Details:
Floor Area 12.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 9.0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 11.0 m² Area 12.7 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 113 of312 113


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-11 Admin Support

1. General Details:
Floor Area 129.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 14.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2800.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 126.0 m² Area 24.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 114 of312 114


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-12 Drc of M&S

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 9.0 3 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 10.0 m² Area 11.1 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 115 of312 115


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-13 Reception Area

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 22.0 m² Area 7.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 116 of312 116


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-14 Chief Account

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 11.0 m² Area 12.9 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 117 of312 117


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-15 Assistance Cn

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 11.0 m² Area 15.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 118 of312 118


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-16 Accountant Support

1. General Details:
Floor Area 52.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 28.0 9 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 52.0 m² Area 16.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 119 of312 119


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-18 Director of Fin

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 9.0 3 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 9.0 m² Area 18.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 120 of312 120


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-20 Cashier

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 7.0 m² Area 18.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 121 of312 121


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-21 Counting Room

1. General Details:
Floor Area 4.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 4.0 m² Area 13.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 122 of312 122


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-34 Meeting Room 2

1. General Details:
Floor Area 54.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Conference/meeting
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12.0 People
Wattage 54.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 18.0 9 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 54.0 m² Area 28.4 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 123 of312 123


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-35 Prefunction

1. General Details:
Floor Area 40.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 15.50 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 18.9 9 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 40.0 m² Area 16.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 124 of312 124


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-36 Boardroom

1. General Details:
Floor Area 54.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Conference/meeting
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12.0 People
Wattage 9.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 18.0 9 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 54.0 m² Area 41.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 125 of312 125


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-37 Boardroom

1. General Details:
Floor Area 54.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Conference/meeting
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 16.0 People
Wattage 9.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 18.0 9 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 54.0 m² Area 41.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 126 of312 126


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-38 Business Centre

1. General Details:
Floor Area 26.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 15.50 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 18.0 9 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 26.0 m² Area 14.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 127 of312 127


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-39 Club Lounge 1

1. General Details:
Floor Area 24.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.50 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 24.0 m² Area 12.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 128 of312 128


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-39 Club Lounge 2

1. General Details:
Floor Area 56.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 15.50 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3384.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 34.6 0 0 0
NW 17.0 9 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 56.0 m² Area 16.4 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 129 of312 129


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-39 Club Lounge 3

1. General Details:
Floor Area 55.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 20.0 People
Wattage 15.50 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 34.0 9 0 0
NW 17.5 9 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 55.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 130 of312 130


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-39 Club Lounge 4

1. General Details:
Floor Area 60.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 18.0 People
Wattage 15.50 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 17.0 9 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 60.0 m² Area 10.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 131 of312 131


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-39 Club Lounge 5

1. General Details:
Floor Area 43.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 18.0 People
Wattage 15.50 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 17.0 9 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 43.0 m² Area 10.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 132 of312 132


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-39 Pantry

1. General Details:
Floor Area 15.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.50 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1735 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 15.0 m² Area 18.3 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 133 of312 133


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-47 Boardroom

1. General Details:
Floor Area 54.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Conference/meeting
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 16.0 People
Wattage 9.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 18.0 9 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 54.0 m² Area 41.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 134 of312 134


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F1-51 Drc of FB

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 8.0 3 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 10.0 m² Area 11.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 135 of312 135


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F18K-07 Dishwash

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 10.17 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 900 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 14.4 0 0 0
SE 29.0 17 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 22.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 2.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 136 of312 136


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F18K-08 Chiller

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.17 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.5 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 137 of312 137


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F18K-09 Hot and Dessert

1. General Details:
Floor Area 39.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8.0 People
Wattage 10.17 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 11549 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 25.3 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 39.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 1.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 138 of312 138


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F18K-11 Sushi + Robata

1. General Details:
Floor Area 38.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8.0 People
Wattage 10.17 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2250 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 25.0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 38.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 1.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 139 of312 139


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F18K-170 Prep Station

1. General Details:
Floor Area 14.0 m²
Avg. Ceiling Height 4.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 10.17 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 525 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 10.0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 1.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 140 of312 140


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

F18R-12 Spec Restaurant

1. General Details:
Floor Area 417.0 m²
Avg. Ceiling Height 4.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 18.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 105.0 People
Wattage 30.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 7700 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 131.2 101 0 0
NW 54.5 33 0 0
NE 45.0 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.3. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 437.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 1.00 ACH
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 123.0 m²
U-Value 1.900 W/(m²-°K)

Hourly Analysis Program v4.80 Page 141 of312 141


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

Uncondit. Space Max Temp 31.5 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 142 of312 142


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

FP-TYP. Pantry

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 850.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 8.0 m² Area 25.2 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 143 of312 143


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA 40 Lobby

1. General Details:
Floor Area 182.0 m²
Avg. Ceiling Height 5.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 40.0 People
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 182.0 m² Area 114.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 144 of312 144


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-11 Service Lobby

1. General Details:
Floor Area 21.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Sedentary Work
Ballast Multiplier 1.00 Sensible 82.1 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 79.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 16.0 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 21.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 21.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 145 of312 145


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-13 Female inspect

1. General Details:
Floor Area 5.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 5.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 146 of312 146


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-15 Vestibule

1. General Details:
Floor Area 62.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 30.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 43.0 21 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 62.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 147 of312 147


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-16 Corridor

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 5.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 54.0 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 22.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 148 of312 148


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-17 Pantry/WSTN

1. General Details:
Floor Area 34.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Cafeteria/fast food
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 8.21 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 41.6 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 34.0 m² Area 18.2 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 149 of312 149


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-18 WC

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 22.0 m² Area 46.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 150 of312 150


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-19 WC

1. General Details:
Floor Area 28.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 28.0 m² Area 25.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 151 of312 151


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-20 Tea Lounge

1. General Details:
Floor Area 215.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 71.0 People
Wattage 7.00 W/m² Activity Level Sedentary Work
Ballast Multiplier 1.00 Sensible 82.1 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 79.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 58.0 34 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 215.0 m² Area 165.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 152 of312 152


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-21 Reception Area 1

1. General Details:
Floor Area 121.2 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 13.0 People
Wattage 11.00 W/m² Activity Level Sedentary Work
Ballast Multiplier 1.00 Sensible 82.1 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 79.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 20.0 20 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 121.2 m² Area 47.8 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 153 of312 153


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-21 Reception Area 2

1. General Details:
Floor Area 181.0 m²
Avg. Ceiling Height 10.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 38.0 People
Wattage 11.00 W/m² Activity Level Sedentary Work
Ballast Multiplier 1.00 Sensible 82.1 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 79.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 80.0 80 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 85.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 181.0 m² Area 193.8 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 154 of312 154


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-22 Viewing Room

1. General Details:
Floor Area 6.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 22.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 17.0 0 0 0
NE 8.0 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 6.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 155 of312 155


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-23 Safe Deposit

1. General Details:
Floor Area 5.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 25.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 20.0 0 0 0
NW 9.0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 5.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 156 of312 156


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-24 Guest Relation

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 9.72 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 750.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 46.8 36 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 22.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 157 of312 157


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-25 Front Desk M

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 18.70 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 9.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 158 of312 158


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-26 Guest Relation M

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 19.95 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 8.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 159 of312 159


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-27 - Female Ins.

1. General Details:
Floor Area 5.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 5.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 160 of312 160


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-28 FOH Manager

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.15 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 12.8 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 8.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 161 of312 161


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-29 Vestibule

1. General Details:
Floor Area 49.0 m²
Avg. Ceiling Height 10.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 10.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 97.0 64 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 49.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 162 of312 162


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-30 Lug

1. General Details:
Floor Area 26.0 m²
Avg. Ceiling Height 5.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 43.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 25.0 2 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 26.0 m² Area 49.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 163 of312 163


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-32 Lobby

1. General Details:
Floor Area 26.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 26.0 m² Area 88.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 164 of312 164


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-34 Valet Elevator

1. General Details:
Floor Area 6.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Laundry room within dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 12.8 0 0 0
NE 13.7 9 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 6.0 m² Area 13.1 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 165 of312 165


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-37 Service Lobby 2

1. General Details:
Floor Area 44.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 3.91 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 48.0 0 0 0
E 14.5 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure E


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 44.0 m² Area 88.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 166 of312 166


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFA-39 Lugg

1. General Details:
Floor Area 24.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 20.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 24.0 m² Area 16.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 167 of312 167


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFB-51 Ball Room 1

1. General Details:
Floor Area 315.0 m²
Avg. Ceiling Height 10.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Multi-purpose assembly
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.00 m²/person
Wattage 12.00 W/m² Activity Level Sedentary Work
Ballast Multiplier 1.00 Sensible 82.1 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 79.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 10000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 315.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 315.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 168 of312 168


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFB-51 Ball Room 2

1. General Details:
Floor Area 315.0 m²
Avg. Ceiling Height 10.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Multi-purpose assembly
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.00 m²/person
Wattage 12.00 W/m² Activity Level Sedentary Work
Ballast Multiplier 1.00 Sensible 82.1 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 79.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 10000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 315.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 315.0 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 169 of312 169


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFB-51 Ball Room 3

1. General Details:
Floor Area 315.0 m²
Avg. Ceiling Height 10.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Multi-purpose assembly
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.00 m²/person
Wattage 12.00 W/m² Activity Level Sedentary Work
Ballast Multiplier 1.00 Sensible 82.1 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 79.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 10000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 164.0 0 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 315.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 315.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 170 of312 170


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFC-45 Cafe

1. General Details:
Floor Area 146.0 m²
Avg. Ceiling Height 5.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 18.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 135.0 People
Wattage 54.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4000 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 48.0 24 0 0
SE 88.0 50 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 146.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 108.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 171 of312 171


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFF-49 Garden Pantry

1. General Details:
Floor Area 20.0 m²
Avg. Ceiling Height 4.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 4500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 9.2 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 20.0 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 20.0 m² Area 124.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 172 of312 172


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFK-01 - Refrigration Rm

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 1.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 125.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 173 of312 173


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFK-02 Cold Kitchen

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 9.42 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1428 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 13.0 4 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 1.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 10.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 10.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 174 of312 174


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFK-03 Dishwash

1. General Details:
Floor Area 16.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 9.42 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1754 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 16.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 16.0 m² Area 15.3 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 175 of312 175


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFK-04 Corridor

1. General Details:
Floor Area 25.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 9.42 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2137 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 6.5 0 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 1.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 25.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 25.0 m² Area 34.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 176 of312 176


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFK-05 Room Service

1. General Details:
Floor Area 21.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 9.42 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4948 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 1.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 21.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 21.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 177 of312 177


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFK-06 Order Taker

1. General Details:
Floor Area 4.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 10.17 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 1.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.8 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 4.0 m² Area 22.8 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 178 of312 178


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFK-07 Dry Storage

1. General Details:
Floor Area 5.4 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 10.17 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 4.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.8 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 4.0 m² Area 18.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 179 of312 179


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFK-08 Hot Kitchen

1. General Details:
Floor Area 24.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 9.42 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 133.3 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 5970 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 24.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 25.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 180 of312 180


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFL-42 Retail 3

1. General Details:
Floor Area 120.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RETAIL: Sales
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.00 m²/person
Wattage 75.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 74.1 74 0 0
SE 12.3 6 0 0
SE 58.0 58 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.3. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 122.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

Hourly Analysis Program v4.80 Page 181 of312 181


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 120.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 120.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 182 of312 182


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFL-43 Retail 4

1. General Details:
Floor Area 140.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RETAIL: Sales
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.00 m²/person
Wattage 75.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 71.5 71 0 0
SE 12.3 6 0 0
NW 67.5 67 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.3. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 136.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

Hourly Analysis Program v4.80 Page 183 of312 183


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 140.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 95.2 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 184 of312 184


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFL-44 Retail 5

1. General Details:
Floor Area 99.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RETAIL: Sales
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.00 m²/person
Wattage 75.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 62.0 62 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 121.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 99.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 50.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 185 of312 185


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFL-46 Retail 1

1. General Details:
Floor Area 122.0 m²
Avg. Ceiling Height 5.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RETAIL: Sales
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.00 m²/person
Wattage 75.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 64.0 64 0 0
SE 48.0 48 0 0
NE 74.7 74 0 0
NW 12.1 6 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.3. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.4. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 122.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

Hourly Analysis Program v4.80 Page 186 of312 186


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 122.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 43.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 187 of312 187


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFL-47 Retail 2

1. General Details:
Floor Area 125.0 m²
Avg. Ceiling Height 5.3 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RETAIL: Sales
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.00 m²/person
Wattage 75.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 68.0 68 0 0
NW 58.8 58 0 0
NE 71.2 71 0 0
SE 12.0 6 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.3. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.4. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 121.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

Hourly Analysis Program v4.80 Page 188 of312 188


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 125.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 43.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 189 of312 189


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFR-14 Humidor

1. General Details:
Floor Area 6.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 18.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1000 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 7.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 190 of312 190


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFR-14 RestA

1. General Details:
Floor Area 225.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 18.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 52.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 6402 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 103.0 35 0 0
SE 85.5 50 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 95.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 227.0 m² Area 45.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 191 of312 191


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFR-14 RestB

1. General Details:
Floor Area 43.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 18.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 200 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 26.5 18 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 43.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 192 of312 192


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

GFR-14 RestC

1. General Details:
Floor Area 75.0 m²
Avg. Ceiling Height 5.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 18.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 21.0 People
Wattage 20.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1065 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 62.2 36 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 75.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 193 of312 193


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C1-132 Mech. Room

1. General Details:
Floor Area 102.0 m²
Avg. Ceiling Height 3.9 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 81.6 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 102.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 124.8 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 194 of312 194


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C1-134 Water Feature

1. General Details:
Floor Area 26.0 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2000 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 26.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 26.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 46.4 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 195 of312 195


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-01 Mech Room

1. General Details:
Floor Area 71.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1984 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 52.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 13.0 m² Area 116.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 196 of312 196


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-04 AHU room

1. General Details:
Floor Area 69.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 69.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 90.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 197 of312 197


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-05 Water Feature P

1. General Details:
Floor Area 37.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2000 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 37.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 37.0 m² Area 60.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 198 of312 198


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-07 Ventilation Rm

1. General Details:
Floor Area 27.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2759 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 63.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 199 of312 199


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-08 Indoor Swimming

1. General Details:
Floor Area 52.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2500 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 52.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 91.5 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 200 of312 200


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-15 Pump Room

1. General Details:
Floor Area 77.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4000 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 107.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 201 of312 201


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-19 Water Feature P

1. General Details:
Floor Area 35.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2000 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 50.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 202 of312 202


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-20 Mech. Room

1. General Details:
Floor Area 71.4 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 65.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 203 of312 203


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-28 Mech Room

1. General Details:
Floor Area 39.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 39.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 57.5 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 204 of312 204


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-34 Ventilation

1. General Details:
Floor Area 60.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1511 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 40.0 m² Area 115.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 205 of312 205


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C2-42 AHU room

1. General Details:
Floor Area 186.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1981 W
Schedule None Schedule ELECTRICAL EQUIPMENT 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 102.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 215.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 206 of312 206


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-01 Ventilation Rm

1. General Details:
Floor Area 42.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2488 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 78.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 207 of312 207


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-04 Outdoor Pool

1. General Details:
Floor Area 39.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 3000 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 39.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 92.4 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 208 of312 208


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-05 Ventilation Rm

1. General Details:
Floor Area 39.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2488 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 77.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 209 of312 209


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-09 Ventilation Rm

1. General Details:
Floor Area 26.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2460 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 63.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 210 of312 210


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-12 Mech Room

1. General Details:
Floor Area 35.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 35.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 35.0 m² Area 72.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 211 of312 211


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-15 Pump Room

1. General Details:
Floor Area 78.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4400 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Slab Floor On Grade
Floor Area 78.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 107.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 212 of312 212


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-18 AHU Room

1. General Details:
Floor Area 151.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 151.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 183.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 213 of312 213


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-25 AHU Room

1. General Details:
Floor Area 38.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 38.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 79.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 214 of312 214


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-26 AHU Room

1. General Details:
Floor Area 50.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 50.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 50.0 m² Area 103.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 215 of312 215


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-28 Ventilation Rm

1. General Details:
Floor Area 69.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1611 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 111.6 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 216 of312 216


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-29 Mech. Room

1. General Details:
Floor Area 73.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 73.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 52.0 m² Area 105.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 217 of312 217


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C3-31 AHU Room

1. General Details:
Floor Area 60.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 36.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 60.0 m² Area 94.8 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 218 of312 218


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C4-01 Ventilation Rm

1. General Details:
Floor Area 34.5 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2352 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Slab Floor On Grade
Floor Area 34.5 m²
Total Floor U-Value 0.600 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 63.3 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 219 of312 219


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C4-06 Ventilation Rm

1. General Details:
Floor Area 36.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2352 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Slab Floor On Grade
Floor Area 36.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 72.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 220 of312 220


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C4-10 Irrigation Pump

1. General Details:
Floor Area 26.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1500 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Slab Floor On Grade
Floor Area 26.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 26.0 m² Area 44.1 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 221 of312 221


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C4-12 Ventilation Rm

1. General Details:
Floor Area 25.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 2526 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Slab Floor On Grade
Floor Area 25.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 63.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 222 of312 222


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-C4-26 Ventilation Rm

1. General Details:
Floor Area 77.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1611 W
Schedule None Schedule MISC SENSIBLE 100 %
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Slab Floor On Grade
Floor Area 77.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 106.8 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 223 of312 223


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

M-GF-48 Mech Room

1. General Details:
Floor Area 38.0 m²
Avg. Ceiling Height 5.4 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.40 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 27.5 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 38.0 m²
Total Floor U-Value 0.600 W/(m²-°K)
Unconditioned Space Max Temp. 31.5 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 11.0 °C
Ambient at Space Min Temp. -0.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 135.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 224 of312 224


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTP14 Bedroom

1. General Details:
Floor Area 38.6 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 18.3 6 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 38.6 m² Area 71.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 225 of312 225


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTP14 Dining

1. General Details:
Floor Area 30.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 16.5 6 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 30.0 m² Area 32.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 226 of312 226


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTP14 Kitchenette

1. General Details:
Floor Area 6.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Cafeteria/fast food
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 6.0 m² Area 21.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 227 of312 227


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTP14 Living

1. General Details:
Floor Area 36.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 20.5 6 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 36.0 m² Area 61.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 228 of312 228


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTP15 Bedroom

1. General Details:
Floor Area 42.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 18.3 6 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 42.0 m² Area 58.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 229 of312 229


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTP15 Dining

1. General Details:
Floor Area 30.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 16.0 6 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 30.0 m² Area 18.9 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 230 of312 230


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTP15 Kitchenette

1. General Details:
Floor Area 14.5 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Cafeteria/fast food
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 14.5 m² Area 23.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 231 of312 231


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTP15 Living

1. General Details:
Floor Area 36.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 20.5 6 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 36.0 m² Area 38.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 232 of312 232


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTR16 - Gym

1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage SPORTS: Gym, stadium (play area)
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 5.0 0 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 18.0 m² Area 81.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 233 of312 233


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTR16 - Hairdressing

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage SPORTS: Gym, stadium (play area)
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 7.2 0 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 8.0 m² Area 19.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 234 of312 234


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTR16 Bedroom

1. General Details:
Floor Area 21.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 13.5 6 0 0
SE 16.5 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 21.0 m² Area 30.3 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 235 of312 235


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTR16 Bedroom 2

1. General Details:
Floor Area 26.5 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 16.5 6 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 26.5 m² Area 44.4 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 236 of312 236


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTR16 Dining

1. General Details:
Floor Area 20.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 18.5 6 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 20.0 m² Area 24.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 237 of312 237


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTR16 Living Room

1. General Details:
Floor Area 53.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 11.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 32.5 12 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 53.0 m² Area 49.4 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 238 of312 238


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTR16 Pantry

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Cafeteria/fast food
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 300.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 11.0 m² Area 32.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 239 of312 239


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTR16 Study

1. General Details:
Floor Area 12.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 12.0 m² Area 18.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 240 of312 240


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTYP. Junior Suit B

1. General Details:
Floor Area 56.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 27.0 14 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 56.0 m² Area 61.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 28.0 °C Uncondit. Space Max Temp 28.0 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 241 of312 241


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTYP. Junior Suit T

1. General Details:
Floor Area 56.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 27.0 14 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 56.0 m² Area 61.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 28.0 °C Uncondit. Space Max Temp 28.0 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 242 of312 242


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTYP. King Room Bot

1. General Details:
Floor Area 41.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 18.0 7 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 41.0 m² Area 58.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 243 of312 243


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTYP. King Room L

1. General Details:
Floor Area 36.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 16.5 7 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 36.0 m² Area 55.8 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 244 of312 244


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTYP. King Room L.B

1. General Details:
Floor Area 38.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.5 0 0 0
SE 16.0 7 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 38.0 m² Area 66.2 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 245 of312 245


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTYP. King Room L.T

1. General Details:
Floor Area 38.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 15.5 0 0 0
SE 16.0 7 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 38.0 m² Area 66.2 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 246 of312 246


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTYP. King Room R

1. General Details:
Floor Area 36.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 16.5 7 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 36.0 m² Area 55.8 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 247 of312 247


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTYP. King Room R.B

1. General Details:
Floor Area 38.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.5 0 0 0
NW 16.0 7 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 38.0 m² Area 66.2 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 248 of312 248


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTYP. King Room R.T

1. General Details:
Floor Area 38.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 15.5 0 0 0
NW 16.0 7 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 38.0 m² Area 66.2 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 249 of312 249


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

NTYP. King Room Top

1. General Details:
Floor Area 41.0 m²
Avg. Ceiling Height 3.1 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 17.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 18.0 7 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 41.0 m² Area 58.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 250 of312 250


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP Floor Electrical Rm

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 7.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule ELECTRICAL EQUIPMENT 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 28.0 m²
U-Value 1.600 W/(m²-°K)
Uncondit. Space Max Temp 28.0 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 251 of312 251


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP IDF Closet

1. General Details:
Floor Area 6.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 13.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule ELECTRICAL EQUIPMENT 100 % Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2290.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 23.0 m²
U-Value 1.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 252 of312 252


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP. CRC

1. General Details:
Floor Area 139.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 900.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 111.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 28.0 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 253 of312 253


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP. Lobby

1. General Details:
Floor Area 27.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 10.7 6 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 254 of312 254


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP.25 - Executive - BD

1. General Details:
Floor Area 38.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 13.5 7 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 38.0 m² Area 57.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 255 of312 255


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP.25 Executive - LR

1. General Details:
Floor Area 41.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 14.8 7 0 0

3.1. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 41.0 m² Area 36.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 256 of312 256


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP.25 Executive - OFF

1. General Details:
Floor Area 3.5 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 3.5 m² Area 12.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 257 of312 257


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP.26 Executive - BD

1. General Details:
Floor Area 38.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 22.5 7 0 0
NW 13.5 7 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 38.0 m² Area 57.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 258 of312 258


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP.26 Executive - LR

1. General Details:
Floor Area 41.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 28.5 7 0 0
NW 14.8 7 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 41.0 m² Area 36.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 259 of312 259


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP.26 Executive - OF

1. General Details:
Floor Area 3.5 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 7.0 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 3.5 m² Area 12.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 260 of312 260


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP.31 Executive - BD

1. General Details:
Floor Area 38.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 22.5 7 0 0
SE 13.5 7 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 38.0 m² Area 57.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 261 of312 261


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP.31 Executive - LR

1. General Details:
Floor Area 41.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RESIDENTIAL: Dwelling unit
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 100.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 28.5 7 0 0
SE 14.8 7 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 41.0 m² Area 36.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 262 of312 262


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

TYP.31 Executive - OFF

1. General Details:
Floor Area 3.5 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 14.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 7.0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 3.5 m² Area 12.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 263 of312 263


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA- Corridor

1. General Details:
Floor Area 39.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 81.0 20 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 38.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 264 of312 264


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA- F Heat Experience

1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 75.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 25.0 10 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 18.0 m² Area 13.3 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 265 of312 265


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA- Fitness Center

1. General Details:
Floor Area 117.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage SPORTS: Health club/weight room
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 29.0 People
Wattage 15.00 W/m² Activity Level Athletics
Ballast Multiplier 1.00 Sensible 208.1 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 319.4 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 5000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 117.0 m² Area 40.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 266 of312 266


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA- Plant 1

1. General Details:
Floor Area 2.6 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 5.7 0 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 2.6 m² Area 18.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 267 of312 267


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA- Plant 2

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 35.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 7.0 m² Area 7.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 268 of312 268


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA- Plant 3

1. General Details:
Floor Area 2.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100.0 L/s
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 2.0 m² Area 4.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 269 of312 269


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-01 Treatment Room

1. General Details:
Floor Area 23.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1185.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 16.8 10 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 23.0 m² Area 16.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 270 of312 270


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-02 Lounge

1. General Details:
Floor Area 17.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 17.0 m² Area 20.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 271 of312 271


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-03 Male Treatment R

1. General Details:
Floor Area 17.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 765.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 17.5 10 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 17.0 m² Area 27.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 272 of312 272


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-04 Corridor

1. General Details:
Floor Area 11.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 11.0 m² Area 5.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 273 of312 273


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-05 Shower

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 10.0 m² Area 12.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 274 of312 274


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-06 Soaking Changing

1. General Details:
Floor Area 6.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 45.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 6.0 m² Area 18.6 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 275 of312 275


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-08 Male Treatment R

1. General Details:
Floor Area 19.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 765.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 19.0 10 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 19.0 m² Area 16.8 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 276 of312 276


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-09 Male Treatment R

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 765.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 16.0 0 0 0
SE 23.0 10 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure SE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 22.0 m² Area 14.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 277 of312 277


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-10 Male Co-ED Lounge

1. General Details:
Floor Area 25.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 29.0 10 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 25.4 m² Area 7.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 278 of312 278


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-11 Staff Lounge

1. General Details:
Floor Area 10.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Break room
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 150.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 10.0 m² Area 9.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 279 of312 279


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-13 Pantry

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Cafeteria/fast food
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 8.0 m² Area 8.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 280 of312 280


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-15 Laundry

1. General Details:
Floor Area 7.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Laundry room, central
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 7.0 m² Area 7.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 281 of312 281


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-16 Female Treatment

1. General Details:
Floor Area 20.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 765.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 20.0 m² Area 50.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 282 of312 282


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-17 Corridor

1. General Details:
Floor Area 102.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 185.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 102.0 m² Area 100.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 283 of312 283


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-20 Male Spa

1. General Details:
Floor Area 42.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 11.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 42.0 10 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 42.0 m² Area 44.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 284 of312 284


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-21 Male Treatment R

1. General Details:
Floor Area 20.5 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 765.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 20.5 m² Area 13.3 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 285 of312 285


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-27 Male Changing /WC

1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 175.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 25.1 10 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition (No partition data).
Area 24.0 m²
U-Value 0.600 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 286 of312 286


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-29 Timeless Capsule

1. General Details:
Floor Area 13.5 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 13.5 m² Area 35.4 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 287 of312 287


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA30 - Spa Retail 2

1. General Details:
Floor Area 30.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 31.0 m² Area 16.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 288 of312 288


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-30 Spa Retail 1

1. General Details:
Floor Area 40.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 40.0 m² Area 25.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 289 of312 289


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-31 F Changing Room

1. General Details:
Floor Area 9.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 70.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 9.0 m² Area 28.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 290 of312 290


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

UL-A32 Female CO-ED L

1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 25.0 10 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 32.0 m² Area 23.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 291 of312 291


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-36 Female Changing

1. General Details:
Floor Area 22.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 55.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 22.0 m² Area 51.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 292 of312 292


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-37 Hair/Nail Saloon

1. General Details:
Floor Area 75.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage RETAIL: Beauty/nail salon
OA Requirement 1 10.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 22.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 47.0 21 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 75.0 m² Area 58.1 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 293 of312 293


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-39 Retail Store

1. General Details:
Floor Area 5.5 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 5.5 m² Area 14.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 294 of312 294


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-41 Tech Store

1. General Details:
Floor Area 5.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 5.0 m² Area 16.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 295 of312 295


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-42 Spa Manager

1. General Details:
Floor Area 15.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 20.0 10 0 0

3.1. Construction Types for Exposure NE


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 15.0 m² Area 36.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 296 of312 296


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-47 Lobby

1. General Details:
Floor Area 26.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage HOTEL: Lobby/prefunction
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 26.0 m² Area 16.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 297 of312 297


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-49 Threshold & Lobby

1. General Details:
Floor Area 103.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 95.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 11.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 500.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 24.5 9 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 103.0 m² Area 54.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 298 of312 298


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-51 Female WC

1. General Details:
Floor Area 17.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 130.0 L/s
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 11.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 17.0 m² Area 41.0 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 299 of312 299


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-52 M Washroom

1. General Details:
Floor Area 21.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 160.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 14.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 21.0 m² Area 43.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 300 of312 300


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-54 Managing office

1. General Details:
Floor Area 8.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 8.0 m² Area 7.5 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 301 of312 301


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-55 Linen Room

1. General Details:
Floor Area 4.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Storage room
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 4.0 m² Area 11.1 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 302 of312 302


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-57 Pantry

1. General Details:
Floor Area 51.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Cafeteria/fast food
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 11.0 People
Wattage 8.21 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 60.1 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 5250.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 34.7 0 0 0
NW 26.0 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 52.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 303 of312 303


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-58 Female Toilets

1. General Details:
Floor Area 14.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 12.0 0 0 0
SW 7.7 0 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure SW


Wall Type Default Wall Assembly

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 1.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 45.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 304 of312 304


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-59 Male Toilets

1. General Details:
Floor Area 15.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 17.6 0 0 0
NW 11.6 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 61.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 305 of312 305


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULA-66 ADA Toilet

1. General Details:
Floor Area 4.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 40.0 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 9.0 0 0 0

3.1. Construction Types for Exposure SE


Wall Type Default Wall Assembly

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type Wall Partition
Area 61.0 m²
U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 306 of312 306


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULB-55 Indoor Pool

1. General Details:
Floor Area 162.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 50.0 People
Wattage 34.00 W/m² Activity Level Athletics
Ballast Multiplier 1.00 Sensible 208.1 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 319.4 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 48.6 9 0 0
NW 63.0 51 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly
1st Window Type WINDOW 1x1

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 162.0 0 0

4.1. Construction Types for Exposure H


Roof Type Default Roof Assembly

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 2.00 ACH
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 307 of312 307


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ULF-62Pantry

1. General Details:
Floor Area 41.0 m²
Avg. Ceiling Height 4.7 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 1.50 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 15.00 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule LIGHTING SCHEDULE 100 % Latent 35.2 W/person
Schedule PEOPLE 100 %

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3000.0 Watts
Schedule ELECTRICAL EQUIPMENT 100 %

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 35.0 0 0 0
NW 27.0 0 0 0

3.1. Construction Types for Exposure SW


Wall Type Default Wall Assembly

3.2. Construction Types for Exposure NW


Wall Type Default Wall Assembly

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Ceiling Partition Partition Type Wall Partition
Area 8.0 m² Area 8.2 m²
U-Value 0.600 W/(m²-°K) U-Value 1.900 W/(m²-°K)
Uncondit. Space Max Temp 31.5 °C Uncondit. Space Max Temp 31.5 °C
Ambient at Space Max Temp 35.2 °C Ambient at Space Max Temp 35.2 °C
Uncondit. Space Min Temp 11.0 °C Uncondit. Space Min Temp 11.0 °C
Ambient at Space Min Temp -0.8 °C Ambient at Space Min Temp -0.8 °C

Hourly Analysis Program v4.80 Page 308 of312 308


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ZAHU-H-C1-01

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 1.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 4205.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 309 of312 309


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ZAHU-H-C1-03

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 1.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 920.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 310 of312 310


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ZRAHU-H-RF-01

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 1.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 8201.0 L/s
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 311 of312 311


Space Input Data
J17006-0100D FD REV2 11/19/2018
dar 05:28PM

ZRAHU-H-RF-02

1. General Details:
Floor Area 1.0 m²
Avg. Ceiling Height 1.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 7148.0 L/s
OA Requirement 2 100 % of supply air
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 0.00 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule None Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program v4.80 Page 312 of312 312


AHU-H-C1-01 Spa Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C1-01 Spa
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 23.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 22.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: ZAHU-H-C1-01
ZAHU-H-C1-01 x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH

Hourly Analysis Program v4.80 Page 1 of 126


AHU-H-C1-01 Spa Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Minimum Airflow 100 % of supply air

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 22.0 °C
Supply Fan Airflow 4205.0 L/s
Ventilation Airflow 4205.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 12.2 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 4205.0 - 0.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 2 of 126


AHU-H-C1-02 Cafe Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C1-02 Cafe
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method ASHRAE Std 62.1-2007
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: GF-45 Cafe


GFC-45 Cafe x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 2360.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Hourly Analysis Program v4.80 Page 3 of 126


AHU-H-C1-02 Cafe Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 30 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 3037.5 L/s
Ventilation Airflow 3037.5 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 3037.5 - 34.6

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 4 of 126


AHU-H-C1-03 Retails Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C1-03 Retails
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
ZAHU-H-C1-03 x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH

Hourly Analysis Program v4.80 Page 5 of 126


AHU-H-C1-03 Retails Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Minimum Airflow 100 % of supply air

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 920.0 L/s
Ventilation Airflow 920.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 12.2 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 920.0 - 8.3

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 6 of 126


AHU-H-C2-01- Bulk Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C2-01- Bulk Kitchen
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 11

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C1-35 Service Station


C1K1-35 Service Station x1
Zone 2: C1-25 Corridor
C1K1-25 Corridor 2 x1
Zone 3: C1-27 Oven Room
C1K1-27 Oven Room x1
Zone 4: C1-30 Regeneration Area
C1K1-30 Regeneration Ar x1
Zone 5: C1-32 Service Station
C1K1-32 Service Station x1
Zone 6: C1-33 Central Dishwash
C1K1-33 Central Dishwash x1
Zone 7: C1-37 Banquet Service FA
C1K1-FA 37 Banquet Servi x1
Zone 8: C1-53 Executive Chef FA
C1K1-FA 53 Executive Che x1
Zone 9: C1-54 Executive Chef FA

Hourly Analysis Program v4.80 Page 7 of 126


AHU-H-C2-01- Bulk Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

C1K1-FA 54 Executive Che x1


Zone 10: C1-34 Chef Office FA
C1K1-FA-34 Chef Office x1
Zone 11: Refrigration Room
C1K1 - Refrigration Rm x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
2 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
3 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
4 24.0 24.0 21.0 21.0 1.00 100 3255.0 0.0
5 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
6 24.0 24.0 21.0 21.0 1.00 100 720.0 0.0
7 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
8 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
9 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
10 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
11 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 30 % - - -
2 VAV box with RH 30 % - - -
3 VAV box with RH 30 % - - -
4 VAV box with RH 30 % - - -
5 VAV box with RH 30 % - - -
6 VAV box with RH 30 % - - -
7 VAV box with RH 30 % - - -
8 VAV box with RH 30 % - - -
9 VAV box with RH 30 % - - -
10 VAV box with RH 30 % - - -
11 VAV box 30 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 5991.4 L/s
Ventilation Airflow 5991.4 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K

Hourly Analysis Program v4.80 Page 8 of 126


AHU-H-C2-01- Bulk Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 170.2 - 2.3 -
2 770.8 - 14.1 -
3 371.5 - 3.8 -
4 3255.0 - 32.3 -
5 434.0 - 4.0 -
6 720.0 - 8.6 -
7 15.0 - 0.1 -
8 15.0 - 0.1 -
9 15.0 - 0.1 -
10 15.0 - 0.1
11 210.0 - -

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 9 of 126


AHU-H-C2-02 Prefunction Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C2-02 Prefunction
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 9

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 100 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C1-43 Pre Function 1


C1P-43 Pre Function 1 x1
Zone 2: C1-43 Pre Function 2
C1P-43 Pre Function 2 x1
Zone 3: C1-50 Meeting room
C1P-FA50 Meeting Room x1
Zone 4: C1-47 Prayer/F FA
C1P-FA47 Prayer/F x1
Zone 5: C1-39 AV Control Room
C1P-FA39 AV Control x1
Zone 6: C1-48 Prayer Room M FA
C1P-FA48 Prayer Room M x1
Zone 7: C1-45 Meeting Room 2
C1P-FA45 Meeting Room 2 x1
Zone 8: C1-44 Meeting Room 1
C1P-FA44 Meeting Room 3 x1
Zone 9: C1-85 Corridor

Hourly Analysis Program v4.80 Page 10 of 126


AHU-H-C2-02 Prefunction Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

C1P-85 CRC x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 24.0 24.0 21.0 21.0 1.00 100 35.0 0.0
2 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
3 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
4 24.0 24.0 21.0 21.0 1.00 100 75.0 0.0
5 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
6 24.0 24.0 21.0 21.0 1.00 100 75.0 0.0
7 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
8 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
9 24.0 24.0 21.0 21.0 1.00 100 60.0 0.0

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 30 % - - -
2 VAV box with RH 30 % - - -
3 VAV box with RH 30 % - - -
4 VAV box with RH 40 % - - -
5 VAV box with RH 30 % - - -
6 VAV box with RH 40 % - - -
7 VAV box with RH 30 % - - -
8 VAV box with RH 30 % - - -
9 VAV box with RH 30 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 6131.4 L/s
Ventilation Airflow 6131.4 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Hourly Analysis Program v4.80 Page 11 of 126


AHU-H-C2-02 Prefunction Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 3914.9 - 43.9 -
2 1615.6 - 18.3 -
3 60.0 - 0.5 -
4 105.0 - 0.9 -
5 15.0 - 0.1 -
6 85.0 - 0.8 -
7 50.0 - 0.5 -
8 50.0 - 0.5
9 235.8 - 4.7

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 12 of 126


AHU-H-C2-03 Indoor Pool Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C2-03 Indoor Pool
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 10.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 14.4 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: UL-55 Indoor Pool


ULB-55 Indoor Pool x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 27.0 °C
Cooling T-stat: Unocc. 27.0 °C
Heating T-stat: Occ. 26.0 °C
Heating T-stat: Unocc. 26.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH
Minimum Airflow 0.00 L/s/person

Hourly Analysis Program v4.80 Page 13 of 126


AHU-H-C2-03 Indoor Pool Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 14.4 °C
Supply Fan Airflow 1900.1 L/s
Ventilation Airflow 1900.1 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 1900.1 - 29.4

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 14 of 126


AHU-H-C2-04 - Laundry Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C2-04 - Laundry
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 4

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method ASHRAE Std 62.1-2007
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 16.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C1-95 Laundry Office


C1L-95-Laundry Office x1
Zone 2: C1-94 Laundry Area
C1L-94-Laundry Area x1
Zone 3: C1-96 Uniform issuance
C1L-96 Uniform Issunace x1
Zone 4: C1-97 Clean Linen
C1L-97-Clean Linen x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
2 27.0 27.0 21.0 21.0 1.00 100 900.0 0.0

Hourly Analysis Program v4.80 Page 15 of 126


AHU-H-C2-04 - Laundry Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
3 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
4 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH
Minimum Airflow 30 % of supply air

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 16.0 °C
Supply Fan Airflow 2438.7 L/s
Ventilation Airflow 900.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 78.4 - 0.2 -
2 1937.8 - 7.0 -
3 253.0 - 1.0
4 169.4 - 1.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 16 of 126


AHU-H-C2-05 Ball Room Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C2-05 Ball Room
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: GF-51 Ball Room 1


GFB-51 Ball Room 1 x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH

Hourly Analysis Program v4.80 Page 17 of 126


AHU-H-C2-05 Ball Room Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Minimum Airflow 0.00 L/s/person

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 3906.5 L/s
Ventilation Airflow 882.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 3906.5 - 11.8

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 18 of 126


AHU-H-C2-06 Ball Room Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C2-06 Ball Room
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 10.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: GF-51 Ball Room 2


GFB-51 Ball Room 2 x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH

Hourly Analysis Program v4.80 Page 19 of 126


AHU-H-C2-06 Ball Room Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Minimum Airflow 0.00 L/s/person

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 3900.4 L/s
Ventilation Airflow 882.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 3900.4 - 11.7

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 20 of 126


AHU-H-C2-07 Ball Room Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C2-07 Ball Room
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 10.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: GF-51 Ball Room 3


GFB-51 Ball Room 3 x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH

Hourly Analysis Program v4.80 Page 21 of 126


AHU-H-C2-07 Ball Room Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Minimum Airflow 0.00 L/s/person

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 4100.0 L/s
Ventilation Airflow 882.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 4100.0 - 13.3

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 22 of 126


AHU-H-C2-08 GSM Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C2-08 GSM
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 10.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C2-25 GSM Room


EL-C2-25 GSM x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box

Hourly Analysis Program v4.80 Page 23 of 126


AHU-H-C2-08 GSM Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Minimum Airflow 0.00 L/s/person

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 2723.1 L/s
Ventilation Airflow 0.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 2723.1 - -

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 24 of 126


AHU-H-C3-01 - Reception & Tea L Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C3-01 - Reception & Tea L
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 22

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method ASHRAE Std 62.1-2007
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: GF-30 Lug


GFA-30 Lug x1
Zone 2: GF-40 Lobby
GFA 40 Lobby x1
Zone 3: GF-34 Valet Elevator Lob
GFA-34 Valet Elevator x1
Zone 4: GF-15 Vestibule
GFA-15 Vestibule x1
Zone 5: GF-18 WC
GFA-18 WC x1
Zone 6: GF-16 Corridor
GFA-16 Corridor x1
Zone 7: GF-17 Pantry/WSTN
GFA-17 Pantry/WSTN x1
Zone 8: GF-20 Tea Lounge/Bar
GFA-20 Tea Lounge x1
Zone 9: GF-21 Reception 1

Hourly Analysis Program v4.80 Page 25 of 126


AHU-H-C3-01 - Reception & Tea L Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

GFA-21 Reception Area 1 x1


Zone 10: GF-21 Reception 2
GFA-21 Reception Area 2 x1
Zone 11: GF-24 Guest Relation
GFA-24 Guest Relation x1
Zone 12: GF-25 Front Desk Manager
GFA-25 Front Desk M x1
Zone 13: GF-26 Guest Relation MGR
GFA-26 Guest Relation M x1
Zone 14: GF-28 FOH Manager
GFA-28 FOH Manager x1
Zone 15: GF-27 Female Inspection
GFA-27 - Female Ins. x1
Zone 16: GF-22 Viewing Room
GFA-22 Viewing Room x1
Zone 17: GF13/GF11 Inspect/Lobby
GFA-13 Female inspect x1
GFA-11 Service Lobby x1
Zone 18: GF-29 Vestibule
GFA-29 Vestibule x1
Zone 19: GF-33 Service Lobby 2 Cr
GFA-37 Service Lobby 2 x1
Zone 20: GF-39 Luggage
GFA-39 Lugg x1
Zone 21: GF-32 Lobby
GFA-32 Lobby x1
Zone 22: GF-19 WC
GFA-19 WC x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
2 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
3 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
4 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
5 24.0 24.0 21.0 21.0 1.00 100 150.0 0.0
6 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
7 24.0 24.0 21.0 21.0 1.00 100 290.0 0.0
8 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
9 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
10 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
11 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
12 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
13 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
14 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
15 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
16 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
17 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
18 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
19 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
20 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
21 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
22 24.0 24.0 21.0 21.0 1.00 100 250.0 0.0

Hourly Analysis Program v4.80 Page 26 of 126


AHU-H-C3-01 - Reception & Tea L Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 30 % - - -
2 VAV box with RH 30 % - - -
3 VAV box with RH 30 % - - -
4 VAV box with RH 30 % - - -
5 VAV box with RH 100 % - - -
6 VAV box with RH 30 % - - -
7 VAV box with RH 100 % - - -
8 VAV box with RH 45 % - - -
9 VAV box with RH 30 % - - -
10 VAV box with RH 30 % - - -
11 VAV box with RH 30 % - - -
12 VAV box with RH 30 % - - -
13 VAV box with RH 30 % - - -
14 VAV box with RH 30 % - - -
15 VAV box with RH 30 % - - -
16 VAV box with RH 30 % - - -
17 VAV box with RH 30 % - - -
18 VAV box with RH 30 % - - -
19 VAV box with RH 30 % - - -
20 VAV box with RH 30 % - - -
21 VAV box with RH 30 % - - -
22 VAV box with RH 100 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 7683.7 L/s
Ventilation Airflow 1438.9 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -

Hourly Analysis Program v4.80 Page 27 of 126


AHU-H-C3-01 - Reception & Tea L Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

(L/s) (kW) (kW) -


1 198.3 - 2.0 -
2 785.7 - 5.7 -
3 99.2 - 1.2 -
4 505.8 - 3.0 -
5 150.0 - 2.5 -
6 116.7 - 0.9 -
7 297.2 - 3.7 -
8 1399.3 - 12.4 -
9 652.8 - 4.5 -
10 1641.5 - 14.0 -
11 339.7 - 2.9 -
12 53.4 - 0.2 -
13 52.3 - 0.2 -
14 53.4 - 0.3 -
15 50.3 - 0.2 -
16 56.3 - 0.4 -
17 138.7 - 0.8 -
18 548.6 - 5.2 -
19 208.5 - 3.2 -
20 76.2 - 0.7 -
21 174.4 - 2.5
22 250.0 - 3.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 28 of 126


AHU-H-C3-02 - C1 Areas Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C3-02 - C1 Areas
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 24

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method ASHRAE Std 62.1-2007
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C1-06 Purch & Receive ST


C1A-06 Purch & Rec St x1
Zone 2: C1-07 Purchasing Manager
C1A-07 Purch. Manager x1
Zone 3: C1-09 Monitoring Station
C1A-09 Monitoring Statio x1
Zone 4: C1-10 SecuritySupervisor
C1A-10 Security Supervis x1
Zone 5: C1-20 Linen Collection
C1A-20 Linen Collection x1
Zone 6: C1-52 Closing Room
C1A-52 Closing Room x1
Zone 7: C1-90 Lobby
C1A-90-Lobby x1
Zone 8: C1-93 Bridal Suite
C1A-93 Bridal Suite x1
Zone 9: C1-101 Assistance HK

Hourly Analysis Program v4.80 Page 29 of 126


AHU-H-C3-02 - C1 Areas Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

C1A-101 Assistance HK x1
Zone 10: C1-100 HK Manager
C1A-100 HK Manager x1
Zone 11: C1-102 Houskeepking
C1A-102 Housekeeping x1
Zone 12: C1-109 Nurse
C1A-109 Nurse x1
Zone 13: C1-112 HR Reception
C1A-112 HR Reception x1
Zone 14: C1-113 HR Clerk
C1A-113 HR Clerk x1
Zone 15: C1-114 DR of HR
C1A-114 DR of HR x1
Zone 16: C1-116 DR of Training
C1A-116 Dr. of Training x1
Zone 17: C1-115 Training Room
C1A-115 Training Rm x1
Zone 18: C1-117 ENG. Reception
C1A-117 ENG Reception x1
Zone 19: C1-119 DIR of Engineerin
C1A-119 Dirc of Eng x1
Zone 20: C1-122 M+E Workshop
C1A-122 M+E Workshop x1
Zone 21: C1-121 Carpenter Shop
C1A-121 Carpenter Shop x1
Zone 22: C1-125 Electric Repair
C1A-125 Electric Rep. x1
Zone 23: C1-124 Paint Shop
C1A-124 Paint Shop x1
Zone 24: C1-25 Corridor 1
C1A-25 Corridor 1 x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
2 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
3 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
4 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
5 24.0 24.0 21.0 21.0 1.00 100 45.0 0.0
6 24.0 24.0 21.0 21.0 1.00 100 35.0 0.0
7 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
8 24.0 24.0 21.0 21.0 1.00 100 35.0 0.0
9 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
10 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
11 24.0 24.0 21.0 21.0 1.00 100 210.0 0.0
12 24.0 24.0 21.0 21.0 1.00 100 50.0 0.0
13 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
14 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
15 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
16 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
17 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
18 24.0 24.0 21.0 21.0 1.00 100 15.0 0.0
19 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0

Hourly Analysis Program v4.80 Page 30 of 126


AHU-H-C3-02 - C1 Areas Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
20 24.0 24.0 21.0 21.0 1.00 100 110.0 0.0
21 24.0 24.0 21.0 21.0 1.00 100 110.0 0.0
22 24.0 24.0 21.0 21.0 1.00 100 80.0 0.0
23 24.0 24.0 21.0 21.0 1.00 100 110.0 0.0
24 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 30 % - - -
2 VAV box with RH 30 % - - -
3 VAV box with RH 30 % - - -
4 VAV box with RH 30 % - - -
5 VAV box with RH 100 % - - -
6 VAV box with RH 30 % - - -
7 VAV box with RH 30 % - - -
8 VAV box with RH 30 % - - -
9 VAV box with RH 30 % - - -
10 VAV box with RH 30 % - - -
11 VAV box with RH 30 % - - -
12 VAV box with RH 30 % - - -
13 VAV box with RH 30 % - - -
14 VAV box with RH 30 % - - -
15 VAV box with RH 30 % - - -
16 VAV box with RH 30 % - - -
17 VAV box with RH 30 % - - -
18 VAV box with RH 30 % - - -
19 VAV box with RH 30 % - - -
20 VAV box with RH 100 % - - -
21 VAV box with RH 100 % - - -
22 VAV box with RH 100 % - - -
23 VAV box with RH 100 % - - -
24 VAV box with RH 30 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 3873.7 L/s
Ventilation Airflow 1610.0 L/s

Hydronic Sizing Specifications:

Hourly Analysis Program v4.80 Page 31 of 126


AHU-H-C3-02 - C1 Areas Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Chilled Water Delta-T 6.7 °K


Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 153.0 - 1.5 -
2 67.9 - 0.8 -
3 139.6 - 1.5 -
4 68.7 - 0.5 -
5 45.0 - 0.9 -
6 171.3 - 1.6 -
7 137.9 - 2.0 -
8 242.3 - 2.3 -
9 82.5 - 0.6 -
10 76.4 - 0.5 -
11 212.6 - 1.6 -
12 93.5 - 0.8 -
13 139.8 - 1.0 -
14 61.0 - 0.2 -
15 81.8 - 0.6 -
16 62.3 - 0.2 -
17 306.0 - 2.3 -
18 198.7 - 1.0 -
19 67.1 - 0.5 -
20 110.0 - 1.2 -
21 110.1 - 1.5 -
22 80.0 - 1.0 -
23 110.3 - 1.8
24 1058.9 - 14.2

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 32 of 126


AHU-H-C3-03 Employee Cafeteria Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C3-03 Employee Cafeteria
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 2

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C1-71 Employee Cafeteria


C1E-71 Employee Cafe x1
Zone 2: C1-70 Pantry
C1E-70 Pantry x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
2 24.0 24.0 21.0 21.0 1.00 100 50.0 0.0

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Hourly Analysis Program v4.80 Page 33 of 126


AHU-H-C3-03 Employee Cafeteria Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 50 % - - -
2 VAV box with RH 30 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 1153.3 L/s
Ventilation Airflow 402.8 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 1011.5 - 6.9
2 141.8 - 1.7

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 34 of 126


AHU-H-C3-04 GF Restaurant Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C3-04 GF Restaurant
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 4

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method ASHRAE Std 62.1-2007
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: GF-14 Restaurant Area 1


GFR-14 RestA x1
Zone 2: GF-14 Restaurant Area 2
GFR-14 RestB x1
Zone 3: GF-14 Restaurant Area 3
GFR-14 RestC x1
Zone 4: GF-14 Humidor
GFR-14 Humidor x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
2 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0

Hourly Analysis Program v4.80 Page 35 of 126


AHU-H-C3-04 GF Restaurant Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
3 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
4 21.0 21.0 20.0 20.0 1.00 100 0.0 0.0

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 40 % - - -
2 VAV box with RH 40 % - - -
3 VAV box with RH 40 % - - -
4 VAV box with RH 40 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 3093.3 L/s
Ventilation Airflow 2002.5 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 2025.9 - 18.6 -
2 292.2 - 3.7 -
3 611.6 - 6.7
4 174.4 - 0.8

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 36 of 126


AHU-H-C3-05 GF Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C3-05 GF Kitchen
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 8

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: GF-03 Dishwash


GFK-03 Dishwash x1
Zone 2: GF-04 Corridor
GFK-04 Corridor x1
Zone 3: GF-05 Room Service
GFK-05 Room Service x1
Zone 4: GF-06 Order Taker
GFK-06 Order Taker x1
Zone 5: GF-07 Dry Storage
GFK-07 Dry Storage x1
Zone 6: GF-02 Cold Kitchen
GFK-02 Cold Kitchen x1
Zone 7: GF-08 Hot Kitchen
GFK-08 Hot Kitchen x1
Zone 8: GF-01 Refrigration Room
GFK-01 - Refrigration Rm x1

Hourly Analysis Program v4.80 Page 37 of 126


AHU-H-C3-05 GF Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
2 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
3 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
4 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
5 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
6 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
7 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
8 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 30 % - - -
2 VAV box with RH 30 % - - -
3 VAV box with RH 30 % - - -
4 VAV box with RH 30 % - - -
5 VAV box with RH 30 % - - -
6 VAV box with RH 30 % - - -
7 VAV box with RH 30 % - - -
8 VAV box with RH 30 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 2050.1 L/s
Ventilation Airflow 2050.1 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 229.9 - 2.6 -

Hourly Analysis Program v4.80 Page 38 of 126


AHU-H-C3-05 GF Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
2 288.9 - 3.7 -
3 513.0 - 4.9 -
4 39.0 - 0.9 -
5 35.4 - 0.8 -
6 209.8 - 2.3 -
7 609.2 - 5.8
8 125.0 - 1.1

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 39 of 126


AHU-H-C3-06 C1 Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C3-06 C1 Kitchen
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 16

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C1-02 Waste Handling


C1K2-02 Waste Handling x1
Zone 2: C1-05 Flower Room
C1K2-05 Flower Room x1
Zone 3: C1-13 F&V Sanitization
C1K2-13 F&V Sanitation x1
Zone 4: C1-14 - Cold Kitchen
C1K2-14 Cold Kitchen x1
Zone 5: C1-15 Sea Food Prep
C1K2-15 Sea Food Prep x1
Zone 6: C1-16 Meat Prep
C1K2-16 Meat Prep x1
Zone 7: C1-26 Chocolate Room
C1K2-26 Chocolate Room x1
Zone 8: C1-17 Pork Prep
C1K2-17 Pork Prep x1
Zone 9: C1-22 Dry Storage

Hourly Analysis Program v4.80 Page 40 of 126


AHU-H-C3-06 C1 Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

C1K2-22 Dry Storage x1


Zone 10: C1-23 Mini Bar Storage
C1K2-23 Mini Bar Stor x1
Zone 11: C1-24 Beverage Storage
C1K2-24 Beverage Storage x1
Zone 12: C1-26 Bakery
C1K2-26 Bakery x1
Zone 13: C1-18 Kitchen Corridor
C1K2-25 Kitchen Corridor x1
Zone 14: Refrigration Comp 1
C1K2 - Refrigration RM 1 x1
Zone 15: Refrigeration RM 2
C1K2 - Refrigration RM 2 x1
Zone 16: C1-04 Waste Chiller
C1K2-04 Waste Chiller x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 24.0 24.0 21.0 21.0 1.00 100 530.0 0.0
2 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
3 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
4 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
5 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
6 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
7 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
8 24.0 24.0 21.0 21.0 1.00 100 80.0 0.0
9 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
10 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
11 21.0 21.0 18.0 18.0 1.00 100 0.0 0.0
12 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
13 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
14 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
15 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
16 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 30 % - - -
2 VAV box with RH 30 % - - -
3 VAV box with RH 30 % - - -
4 VAV box with RH 30 % - - -
5 VAV box with RH 30 % - - -
6 VAV box with RH 30 % - - -
7 VAV box with RH 30 % - - -
8 VAV box with RH 30 % - - -
9 VAV box with RH 30 % - - -
10 VAV box with RH 30 % - - -
11 VAV box with RH 30 % - - -

Hourly Analysis Program v4.80 Page 41 of 126


AHU-H-C3-06 C1 Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
12 VAV box with RH 30 % - - -
13 VAV box with RH 30 % - - -
14 VAV box 30 % - - -
15 VAV box 30 % - - -
16 VAV box with RH 30 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 3340.0 L/s
Ventilation Airflow 3340.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 530.0 - 5.3 -
2 132.8 - 2.0 -
3 45.2 - 0.4 -
4 171.6 - 1.7 -
5 33.4 - 0.4 -
6 95.2 - 0.9 -
7 110.7 - 1.3 -
8 80.0 - 0.8 -
9 40.1 - 0.6 -
10 22.5 - 0.2 -
11 150.7 - 1.2 -
12 543.8 - 6.4 -
13 73.0 - 0.5 -
14 694.0 - - -
15 630.0 - -
16 48.3 - 0.8

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 42 of 126


AHU-H-C3-07 EL Substation Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C3-07 EL Substation
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 10.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C3-31 EL Substation


EL-C2-31 Substation x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 29.0 °C
Cooling T-stat: Unocc. 29.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box
Minimum Airflow 0.00 L/s/person

Hourly Analysis Program v4.80 Page 43 of 126


AHU-H-C3-07 EL Substation Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 2910.0 L/s
Ventilation Airflow 0.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 2910.0 - -

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 44 of 126


AHU-H-C3-08 MDB Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C3-08 MDB
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 10.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C2-32 MDB Room


EL-C2-32 MDB Room x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 28.0 °C
Cooling T-stat: Unocc. 28.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box

Hourly Analysis Program v4.80 Page 45 of 126


AHU-H-C3-08 MDB Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Minimum Airflow 0.00 L/s/person

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 2097.5 L/s
Ventilation Airflow 0.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 2097.5 - -

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 46 of 126


AHU-H-C3-09 C1 Fresh AHU Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-C3-09 C1 Fresh AHU
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 7

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C1-25 Corridor


C1G-25 Corridor 4 x1
Zone 2: C1-81 M Locker room
C1G-81 M Locker Room x1
Zone 3: C1-75 F WC
C1G-75 F WC x1
Zone 4: C1-87 WC
C1G-87 WC x1
Zone 5: C1-83 WC
C1G-83 WC x1
Zone 6: C1-74 Prayer Room
C1G-74 Prayer Room x1
Zone 7: C1-77 F Locker
C1G-77 F Locker x1

Thermostats and Zone Data:

Hourly Analysis Program v4.80 Page 47 of 126


AHU-H-C3-09 C1 Fresh AHU Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
2 24.0 24.0 21.0 21.0 1.00 100 575.0 0.0
3 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
4 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
5 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
6 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
7 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH
Minimum Airflow 100 % of supply air

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 1633.4 L/s
Ventilation Airflow 1633.4 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 344.8 - 5.2 -
2 575.0 - 9.1 -
3 40.7 - 0.5 -
4 242.6 - 3.6 -
5 235.4 - 4.0 -
6 107.3 - 1.4
7 87.6 - 1.3

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 48 of 126


AHU-H-C3-09 C1 Fresh AHU Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Hourly Analysis Program v4.80 Page 49 of 126


AHU-H-RF-01 RF Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-RF-01 RF Kitchen
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 5

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 14.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: F18-07 Dishwash & Pot.


F18K-07 Dishwash x1
Zone 2: F18-09 Hot and Dessert
F18K-09 Hot and Dessert x1
Zone 3: Prep Station
F18K-170 Prep Station x1
Zone 4: F18-11 Sushi and robata
F18K-11 Sushi + Robata x1
Zone 5: F18-08 Chiller
F18K-08 Chiller x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

Hourly Analysis Program v4.80 Page 50 of 126


AHU-H-RF-01 RF Kitchen Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0


2 24.0 24.0 21.0 21.0 1.00 100 1400.0 0.0
3 24.0 24.0 21.0 21.0 1.00 100 0.0 0.0
4 24.0 24.0 21.0 21.0 1.00 100 1600.0 0.0
5 27.0 27.0 21.0 21.0 1.00 100 200.0 0.0

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 30 % - - -
2 VAV box with RH 30 % - - -
3 VAV box with RH 30 % - - -
4 VAV box with RH 30 % - - -
5 VAV box with RH 30 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 14.0 °C
Supply Fan Airflow 3657.8 L/s
Ventilation Airflow 3657.8 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) -
1 343.9 - 3.8 -
2 1400.0 - 11.2 -
3 113.9 - 1.0 -
4 1600.0 - 12.8
5 200.0 - 1.6

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 51 of 126


AHU-H-RF-02 F18 Restaurant Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name AHU-H-RF-02 F18 Restaurant
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method ASHRAE Std 62.1-2007
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 12.8 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1000 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: F18-12 Speciality Rest.


F18R-12 Spec Restaurant x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 2400.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:

Hourly Analysis Program v4.80 Page 52 of 126


AHU-H-RF-02 F18 Restaurant Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 VAV box with RH 30 % - - -

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Supply Fan Airflow 4108.6 L/s
Ventilation Airflow 2400.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 4108.6 - 33.6

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 53 of 126


FCU - C1 Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - C1
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 9
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: C1-44 Meeting Room 3


C1F-44 Meeting Room 3 x1
Zone 2: C1-45 Meeting Room 2
C1F-45 Meeting Room 2 x1
Zone 3: C1-47 Prayer Room F
C1F-47 Prayer Rm F x1
Zone 4: C1-48 Prayer Room M
C1F-48 Prayer Rm M x1
Zone 5: C1-50 Meeting Room
C1F-50 Meeting Room x1
Zone 6: C1-53 Executive Chef Off
C1F-53 Executive Chef Of x1
Zone 7: C1-54 Executive Chef Off
C1F-54 Executive Chef Of x1
Zone 8: C1-34 Chef Office
C1F-34 Chef Office x1
Zone 9: C1-37 Banquet Services
C1F-37 Banquet Services x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)

Hourly Analysis Program v4.80 Page 54 of 126


FCU - C1 Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1 24.0 24.0 21.0 21.0 1.00


2 24.0 24.0 21.0 21.0 1.00
3 24.0 24.0 21.0 21.0 1.00
4 24.0 24.0 21.0 21.0 1.00
5 24.0 24.0 21.0 21.0 1.00
6 24.0 24.0 21.0 21.0 1.00
7 24.0 24.0 21.0 21.0 1.00
8 24.0 24.0 21.0 21.0 1.00
9 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 372.6 - - 0.0
2 372.6 - - 0.0
3 455.6 - - 0.0
4 401.4 - - 0.0
5 499.2 - - 0.0
6 103.0 - - 10.8
7 108.6 - - 7.7
8 40.3 - - 4.0

Hourly Analysis Program v4.80 Page 55 of 126


FCU - C1 Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
9 124.5 - - 14.2

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 56 of 126


FCU - Club Lounge Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Club Lounge
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 12
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: F1-39 Club Lounge 1


F1-39 Club Lounge 1 x1
Zone 2: F1-38 Business Center
F1-38 Business Centre x1
Zone 3: F1-39 Club Lounge 3
F1-39 Club Lounge 3 x1
Zone 4: F1-39 Club Lounge 4
F1-39 Club Lounge 4 x1
Zone 5: F1-39 Club Lounge 5
F1-39 Club Lounge 5 x1
Zone 6: F1-39 Club Lounge 6
F1-39 Club Lounge 2 x1
Zone 7: F1-39 Club Lounge 7
F1-35 Prefunction x1
Zone 8: Boardroom Bot
F1-47 Boardroom x1
Zone 9: Boardroom Top 1
F1-36 Boardroom x1
Zone 10: Boardroom Top 2
F1-37 Boardroom x1
Zone 11: Boardroom Top 3
F1-36 Boardroom x1
Zone 12: Pantry
F1-39 Pantry x1

Hourly Analysis Program v4.80 Page 57 of 126


FCU - Club Lounge Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00
2 24.0 24.0 21.0 21.0 1.00
3 24.0 24.0 21.0 21.0 1.00
4 24.0 24.0 21.0 21.0 1.00
5 24.0 24.0 21.0 21.0 1.00
6 24.0 24.0 21.0 21.0 1.00
7 24.0 24.0 21.0 21.0 1.00
8 24.0 24.0 21.0 21.0 1.00
9 24.0 24.0 21.0 21.0 1.00
10 24.0 24.0 21.0 21.0 1.00
11 24.0 24.0 21.0 21.0 1.00
12 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.5 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

Hourly Analysis Program v4.80 Page 58 of 126


FCU - Club Lounge Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1 80.3 - - 22.4
2 203.2 - - 34.4
3 397.9 - - 92.5
4 306.9 - - 86.4
5 277.4 - - 81.3
6 584.8 - - 54.8
7 269.7 - - 46.2
8 402.2 - - 56.2
9 418.0 - - 46.2
10 443.6 - - 56.2
11 418.0 - - 46.2
12 226.0 - - 22.5

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 59 of 126


FCU - Executive (25) Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Executive (25)
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 2
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Executive
TYP.25 - Executive - BD x1
Zone 2: Living Room + Office
TYP.25 Executive - LR x1
TYP.25 Executive - OFF x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00
2 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water

Hourly Analysis Program v4.80 Page 60 of 126


FCU - Executive (25) Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.5 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 210.4 - - 16.4
2 261.3 - - 38.4

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 61 of 126


FCU - Executive (26) Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Executive (26)
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 2
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Bedroom
TYP.26 Executive - BD x1
Zone 2: Living Room + Office
TYP.26 Executive - LR x1
TYP.26 Executive - OF x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00
2 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water

Hourly Analysis Program v4.80 Page 62 of 126


FCU - Executive (26) Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.5 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 259.5 - - 16.4
2 351.1 - - 38.4

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 63 of 126


FCU - Executive (31) Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Executive (31)
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 2
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Bedroom
TYP.31 Executive - BD x1
Zone 2: Living Room + Office
TYP.31 Executive - LR x1
TYP.31 Executive - OFF x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00
2 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water

Hourly Analysis Program v4.80 Page 64 of 126


FCU - Executive (31) Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.5 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 285.7 - - 16.4
2 303.2 - - 38.4

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 65 of 126


FCU - F2 - Administrative Areas Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - F2 - Administrative Areas
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 20
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Heating Coil Data:


Setpoint 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: F1-11 Admin Support


F1-11 Admin Support x1
Zone 2: F1-09 EAM Room
F1-09 EAM Room x1
Zone 3: F1-51 Director of F&B
F1-51 Drc of FB x1
Zone 4: F1-06 DIR of Revenue
F1-06 Drc of Revenue x1
Zone 5: F1-05 DIR of Public Rel
F1-05 Drc of Public Rel x1
Zone 6: F1-04 DIR Cater & Confe
F1-04 Drc of Catr/Conf x1
Zone 7: F1-14 Chief Accountant
F1-14 Chief Account x1
Zone 8: F1-12 Director of M&S
F1-12 Drc of M&S x1
Zone 9: F1-20 Cashier
F1-20 Cashier x1
Zone 10: F18- DIR of Finance
F1-18 Director of Fin x1
Zone 11: F1-15 Assitant Control
F1-15 Assistance Cn x1
Zone 12: F1-13 Reception Area
F1-13 Reception Area x1
Zone 13: F1-08 General Manager

Hourly Analysis Program v4.80 Page 66 of 126


FCU - F2 - Administrative Areas Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

F1-08 General Manager x1


Zone 14: F1-10 Quality Manager
F1-10 Quality Manager x1
Zone 15: F1-03 Call Center
F1-03 Call Center x1
Zone 16: F1-01 Reservation Mngr
F1-01 Reserv Manager x1
Zone 17: F1-02 Reservation
F1-02 Reservation x1
Zone 18: F1-21 Counting Room
F1-21 Counting Room x1
Zone 19: F1-16 Chief Accountant
F1-16 Accountant Support x1
Zone 20: F1-07 Meeting Room
F1-07 Meeting Room x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.1 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 0 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Hourly Analysis Program v4.80 Page 67 of 126


FCU - F2 - Administrative Areas Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 639.1 - - 73.7
2 86.5 - - 11.1
3 93.7 - - 10.5
4 100.5 - - 10.8
5 100.4 - - 10.8
6 96.2 - - 10.2
7 78.8 - - 10.8
8 94.4 - - 10.5
9 63.0 - - 4.6
10 99.7 - - 10.2
11 81.0 - - 10.8
12 121.4 - - 24.1
13 173.0 - - 23.5
14 86.2 - - 11.1
15 161.2 - - 13.0
16 100.6 - - 9.6
17 61.8 - - 10.2
18 29.5 - - 3.7
19 474.6 - - 0.0
20 275.8 - - 32.8

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 68 of 126


FCU - Junior Suit B Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Junior Suit B
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Junior Suit


NTYP. Junior Suit B x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Hourly Analysis Program v4.80 Page 69 of 126


FCU - Junior Suit B Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 223.6 - - 0.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 70 of 126


FCU - Junior Suit T Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Junior Suit T
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Junior Suit


NTYP. Junior Suit T x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Hourly Analysis Program v4.80 Page 71 of 126


FCU - Junior Suit T Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 287.4 - - 0.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 72 of 126


FCU - Mechanical Rooms Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Mechanical Rooms
Equipment Type Terminal Units
Air System Type 2-Pipe Fan Coil
Number of zones 31
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: C1-132 Mech Room


M-C1-132 Mech. Room x1
Zone 2: C2-34 Ventilation Room
M-C2-34 Ventilation x1
Zone 3: C2-01 Mech Room
M-C2-01 Mech Room x1
Zone 4: C2-42 AHU Room
M-C2-42 AHU room x1
Zone 5: C2-04 AHU Room
M-C2-04 AHU room x1
Zone 6: C2-07 Ventilation Room
M-C2-07 Ventilation Rm x1
Zone 7: C2-08 Indoor Swimming
M-C2-08 Indoor Swimming x1
Zone 8: C2-20 Mech Room
M-C2-20 Mech. Room x1
Zone 9: C2-15 Pump Room
M-C2-15 Pump Room x1
Zone 10: C2-28 Mech Room
M-C2-28 Mech Room x1
Zone 11: C2-19 Water Feature Pump
M-C2-19 Water Feature P x1
Zone 12: C3-28 Ventilation Room
M-C3-28 Ventilation Rm x1
Zone 13: C3-01 Ventilation Room
M-C3-01 Ventilation Rm x1
Zone 14: C3-04 Outdoor Pool
M-C3-04 Outdoor Pool x1
Zone 15: C3-05 Ventilation Room
M-C3-05 Ventilation Rm x1
Zone 16: C3-09 Ventilation Room
M-C3-09 Ventilation Rm x1
Zone 17: C3-15 Pump Room
M-C3-15 Pump Room x1
Zone 18: C3-18 AHU Room
M-C3-18 AHU Room x1
Zone 19: C3-26 Mech Room
M-C3-26 AHU Room x1
Zone 20: C3-31 AHU Room
M-C3-31 AHU Room x1
Zone 21: C3-29 Mech Room
M-C3-29 Mech. Room x1
Zone 22: C3-25 AHURoom
M-C3-25 AHU Room x1
Zone 23: C3-12 Mech Room
M-C3-12 Mech Room x1
Zone 24: C4-26 Ventilation Room
M-C4-26 Ventilation Rm x1
Zone 25: C4-06 Ventilation Room

Hourly Analysis Program v4.80 Page 73 of 126


FCU - Mechanical Rooms Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

M-C4-06 Ventilation Rm x1
Zone 26: C4-10 Irrigation Pump
M-C4-10 Irrigation Pump x1
Zone 27: C4-12 Ventilation Room
M-C4-12 Ventilation Rm x1
Zone 28: GF-48 Mech Room
M-GF-48 Mech Room x1
Zone 29: C4-01 Ventilation Room
M-C4-01 Ventilation Rm x1
Zone 30: C2-05 Water Feature BP
M-C2-05 Water Feature P x1
Zone 31: C1-134 - Water Feature
M-C1-134 Water Feature x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 0 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation

Hourly Analysis Program v4.80 Page 74 of 126


FCU - Mechanical Rooms Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

(L/s) (kW) (kW) (L/s)


1 313.8 - - 0.0
2 320.9 - - 0.0
3 380.1 - - 0.0
4 582.3 - - 0.0
5 173.4 - - 0.0
6 336.1 - - 0.0
7 380.9 - - 0.0
8 121.5 - - 0.0
9 530.1 - - 0.0
10 105.6 - - 0.0
11 258.7 - - 0.0
12 316.9 - - 0.0
13 338.9 - - 0.0
14 413.2 - - 0.0
15 335.8 - - 0.0
16 308.7 - - 0.0
17 566.5 - - 0.0
18 363.6 - - 0.0
19 187.6 - - 0.0
20 182.7 - - 0.0
21 213.4 - - 0.0
22 129.2 - - 0.0
23 130.7 - - 0.0
24 316.7 - - 0.0
25 316.0 - - 0.0
26 210.8 - - 0.0
27 313.9 - - 0.0
28 230.2 - - 0.0
29 305.0 - - 0.0
30 298.3 - - 0.0
31 279.4 - - 0.0

5. Equipment Data
Changeover Controller:
Used Yes
Trigger OAT Threshold
Threshold Value 14.0 °C
Deadband 3.9 °K
Minimum Cycle Time 4 hours

Hourly Analysis Program v4.80 Page 75 of 126


FCU - Pantries Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Pantries
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: GF-49
GFF-49 Garden Pantry x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation

Hourly Analysis Program v4.80 Page 76 of 126


FCU - Pantries Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

(L/s) (kW) (kW) (L/s)


1 607.6 - - 30.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 77 of 126


FCU - Presidential P14 Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Presidential P14
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 4
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Bedroom
NTP14 Bedroom x1
Zone 2: Living Room
NTP14 Living x1
Zone 3: Dining
NTP14 Dining x1
Zone 4: Kitchenette
NTP14 Kitchenette x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00
2 24.0 24.0 21.0 21.0 1.00
3 24.0 24.0 21.0 21.0 1.00
4 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C

Hourly Analysis Program v4.80 Page 78 of 126


FCU - Presidential P14 Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Coil Bypass Factor 0.100


Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 236.5 - - 17.0
2 248.0 - - 25.8
3 213.1 - - 29.0
4 62.0 - - 9.2

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 79 of 126


FCU - Presidential P15 Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Presidential P15
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 4
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Bedroom
NTP15 Bedroom x1
Zone 2: Dining
NTP15 Dining x1
Zone 3: Kitchenette
NTP15 Kitchenette x1
Zone 4: Living Room
NTP15 Living x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00
2 24.0 24.0 21.0 21.0 1.00
3 24.0 24.0 21.0 21.0 1.00
4 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C

Hourly Analysis Program v4.80 Page 80 of 126


FCU - Presidential P15 Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Coil Bypass Factor 0.100


Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 227.2 - - 17.0
2 198.0 - - 29.0
3 78.5 - - 16.9
4 222.8 - - 25.8

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 81 of 126


FCU - Retails Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Retails
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 5
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: GF-46 Retail 1


GFL-46 Retail 1 x1
Zone 2: GF-47 Retail 2
GFL-47 Retail 2 x1
Zone 3: GF-44 Retail 3
GFL-44 Retail 5 x1
Zone 4: GF-43 Retail 4
GFL-43 Retail 4 x1
Zone 5: GF-42 Retail 5
GFL-42 Retail 3 x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00
2 24.0 24.0 21.0 21.0 1.00
3 24.0 24.0 21.0 21.0 1.00
4 24.0 24.0 21.0 21.0 1.00
5 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Hourly Analysis Program v4.80 Page 82 of 126


FCU - Retails Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 2553.3 - - 189.1
2 2718.1 - - 193.8
3 1526.8 - - 153.5
4 2633.5 - - 217.0
5 2493.5 - - 186.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 83 of 126


FCU - Royal Suite Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Royal Suite
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 7
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Bedroom
NTR16 Bedroom x1
Zone 2: Bedroom 2
NTR16 Bedroom 2 x1
Zone 3: Dining + Kitchen
NTR16 Dining x1
NTR16 Pantry x1
Zone 4: Living Room
NTR16 Living Room x1
Zone 5: Study
NTR16 Study x1
Zone 6: Gym
NTR16 - Gym x1
Zone 7: Hairdressing
NTR16 - Hairdressing x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00
2 24.0 24.0 21.0 21.0 1.00
3 24.0 24.0 21.0 21.0 1.00

Hourly Analysis Program v4.80 Page 84 of 126


FCU - Royal Suite Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
4 24.0 24.0 21.0 21.0 1.00
5 24.0 24.0 21.0 21.0 1.00
6 24.0 24.0 21.0 21.0 1.00
7 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 142.0 - - 17.0
2 154.5 - - 17.0
3 258.8 - - 44.7
4 316.1 - - 43.4
5 72.9 - - 13.6
6 181.9 - - 27.0
7 79.7 - - 12.0

5. Equipment Data

Hourly Analysis Program v4.80 Page 85 of 126


FCU - Royal Suite Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 86 of 126


FCU - SPA Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - SPA
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 43
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Heating Coil Data:


Setpoint 23.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: ULA-09 Male Treatment R


ULA-09 Male Treatment R x1
Zone 2: ULA-08 Male Treatment R
ULA-08 Male Treatment R x1
Zone 3: ULA-03 Male Treatment R
ULA-03 Male Treatment R x1
Zone 4: ULA-01 Treatment Room
ULA-01 Treatment Room x1
Zone 5: ULA-02 Lounge
ULA-02 Lounge x1
Zone 6: ULA-05 Shower
ULA-05 Shower x1
Zone 7: ULA-06 Soaking Tub Chang
ULA-06 Soaking Changing x1
Zone 8: ULA-11 Staff Lounge
ULA-11 Staff Lounge x1
Zone 9: ULA-13- Pantry
ULA-13 Pantry x1
Zone 10: ULA-10- Male Co-ED
ULA-10 Male Co-ED Lounge x1
Zone 11: ULA-55- Linen Room
ULA-55 Linen Room x1
Zone 12: ULA-21 Male Treatment R
ULA-21 Male Treatment R x1
Zone 13: ULA-16 Female Treatment

Hourly Analysis Program v4.80 Page 87 of 126


FCU - SPA Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

ULA-16 Female Treatment x1


Zone 14: UL30 - Spa Retail 2
ULA30 - Spa Retail 2 x1
Zone 15: ULA-29 Timeless Capsule
ULA-29 Timeless Capsule x1
Zone 16: ULA-20 Male Spa
ULA-20 Male Spa x1
Zone 17: ULA-27 Male Changing/WC
ULA-27 Male Changing /WC x1
Zone 18: ULA- Plant 1
ULA- Plant 1 x1
Zone 19: ULA- Plant 2
ULA- Plant 2 x1
Zone 20: ULA-32 Female Co-ED
UL-A32 Female CO-ED L x1
Zone 21: ULA-31 F Changing Room
ULA-31 F Changing Room x1
Zone 22: ULA-36 Female Changing
ULA-36 Female Changing x1
Zone 23: ULA-F Heat Experience
ULA- F Heat Experience x1
Zone 24: ULA- Plant 3
ULA- Plant 3 x1
Zone 25: ULA-04 Corridor
ULA-04 Corridor x1
Zone 26: ULA-17 Corridor
ULA-17 Corridor x1
Zone 27: ULA-15 Laundry
ULA-15 Laundry x1
Zone 28: ULA-37 Hair/Nail Saloon
ULA-37 Hair/Nail Saloon x1
Zone 29: ULA-42 Spa Manager
ULA-42 Spa Manager x1
Zone 30: ULA-41Tech Store
ULA-41 Tech Store x1
Zone 31: ULA-39 Retail Stock
ULA-39 Retail Store x1
Zone 32: ULA-49 Threshold & Lobby
ULA-49 Threshold & Lobby x1
Zone 33: ULA-51 Female WC
ULA-51 Female WC x1
Zone 34: ULA-52 Male Washroom
ULA-52 M Washroom x1
Zone 35: ULA-47 Lobby
ULA-47 Lobby x1
Zone 36: ULA- Fitness Center
ULA- Fitness Center x1
Zone 37: ULA-54 Managing Office
ULA-54 Managing office x1
Zone 38: ULA- Corridor
ULA- Corridor x1
Zone 39: ULA-57 Pantry
ULA-57 Pantry x1
Zone 40: ULA-58 Toilets
ULA-58 Female Toilets x1
Zone 41: ULA-59 Toilets
ULA-59 Male Toilets x1
Zone 42: ULA-66 Male ADA
ULA-66 ADA Toilet x1
Zone 43: ULA-30 Spa Retail

Hourly Analysis Program v4.80 Page 88 of 126


FCU - SPA Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

ULA-30 Spa Retail 1 x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00
2 24.0 24.0 21.0 21.0 1.00
3 24.0 24.0 21.0 21.0 1.00
4 24.0 24.0 21.0 21.0 1.00
5 24.0 24.0 21.0 21.0 1.00
6 24.0 24.0 21.0 21.0 1.00
7 24.0 24.0 21.0 21.0 1.00
8 24.0 24.0 21.0 21.0 1.00
9 22.0 22.0 21.0 21.0 1.00
10 24.0 24.0 21.0 21.0 1.00
11 22.0 22.0 21.0 21.0 1.00
12 24.0 24.0 21.0 21.0 1.00
13 24.0 24.0 21.0 21.0 1.00
14 24.0 24.0 21.0 21.0 1.00
15 24.0 24.0 21.0 21.0 1.00
16 24.0 24.0 21.0 21.0 1.00
17 24.0 24.0 21.0 21.0 1.00
18 24.0 24.0 21.0 21.0 1.00
19 24.0 24.0 21.0 21.0 1.00
20 24.0 24.0 21.0 21.0 1.00
21 24.0 24.0 21.0 21.0 1.00
22 24.0 24.0 21.0 21.0 1.00
23 24.0 24.0 21.0 21.0 1.00
24 24.0 24.0 21.0 21.0 1.00
25 24.0 24.0 21.0 21.0 1.00
26 24.0 24.0 21.0 21.0 1.00
27 19.0 19.0 17.0 17.0 1.00
28 24.0 24.0 21.0 21.0 1.00
29 24.0 24.0 21.0 21.0 1.00
30 24.0 24.0 21.0 21.0 1.00
31 19.0 19.0 15.0 15.0 1.00
32 24.0 24.0 21.0 21.0 1.00
33 24.0 24.0 21.0 21.0 1.00
34 24.0 24.0 21.0 21.0 1.00
35 24.0 24.0 21.0 21.0 1.00
36 24.0 24.0 21.0 21.0 1.00
37 24.0 24.0 21.0 21.0 1.00
38 24.0 24.0 21.0 21.0 1.00
39 24.0 24.0 21.0 21.0 1.00
40 24.0 24.0 21.0 21.0 1.00
41 24.0 24.0 21.0 21.0 1.00
42 24.0 24.0 21.0 21.0 1.00
43 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat

Hourly Analysis Program v4.80 Page 89 of 126


FCU - SPA Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
1 Fan Coil 10.00 ACH 100 Pa 50 % -
2 Fan Coil 10.00 ACH 100 Pa 50 % -
3 Fan Coil 10.00 ACH 100 Pa 50 % -
4 Fan Coil 10.00 ACH 100 Pa 50 % -
5 Fan Coil 0.00 ACH 100 Pa 50 % -
6 Fan Coil 7.00 ACH 100 Pa 50 % -
7 Fan Coil 7.00 ACH 100 Pa 50 % -
8 Fan Coil 0.00 ACH 100 Pa 50 % -
9 Fan Coil 7.00 ACH 100 Pa 50 % -
10 Fan Coil 7.00 ACH 100 Pa 50 % -
11 Fan Coil 0.00 ACH 100 Pa 50 % -
12 Fan Coil 10.00 ACH 100 Pa 50 % -
13 Fan Coil 10.00 ACH 100 Pa 50 % -
14 Fan Coil 0.00 ACH 100 Pa 50 % -
15 Fan Coil 7.00 ACH 100 Pa 50 % -
16 Fan Coil 7.00 ACH 100 Pa 50 % -
17 Fan Coil 0.00 ACH 100 Pa 50 % -
18 Fan Coil 4.00 ACH 100 Pa 50 % -
19 Fan Coil 4.00 ACH 100 Pa 50 % -
20 Fan Coil 7.00 ACH 100 Pa 50 % -
21 Fan Coil 7.00 ACH 100 Pa 50 % -
22 Fan Coil 0.00 ACH 100 Pa 50 % -
23 Fan Coil 7.00 ACH 100 Pa 50 % -
24 Fan Coil 4.00 ACH 100 Pa 50 % -
25 Fan Coil 0.00 ACH 100 Pa 50 % -
26 Fan Coil 0.00 ACH 100 Pa 50 % -
27 Fan Coil 0.00 ACH 100 Pa 50 % -
28 Fan Coil 0.00 ACH 100 Pa 50 % -
29 Fan Coil 0.00 ACH 100 Pa 50 % -
30 Fan Coil 0.00 ACH 100 Pa 50 % -
31 Fan Coil 0.00 ACH 100 Pa 50 % -
32 Fan Coil 0.00 ACH 100 Pa 50 % -
33 Fan Coil 0.00 ACH 100 Pa 50 % -
34 Fan Coil 0.00 ACH 100 Pa 50 % -
35 Fan Coil 0.00 ACH 100 Pa 50 % -
36 Fan Coil 0.00 ACH 100 Pa 50 % -
37 Fan Coil 0.00 ACH 100 Pa 50 % -

Hourly Analysis Program v4.80 Page 90 of 126


FCU - SPA Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Fan Design Supply


Zone Terminal Type Min. Airflow Fan Performance Efficiency Temperature
38 Fan Coil 0.00 ACH 100 Pa 50 % -
39 Fan Coil 0.00 ACH 100 Pa 50 % -
40 Fan Coil 0.00 ACH 100 Pa 50 % -
41 Fan Coil 0.00 ACH 100 Pa 50 % -
42 Fan Coil 0.00 ACH 100 Pa 50 % -
43 Fan Coil 0.00 ACH 100 Pa 50 % -

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 237.1 - - 36.6
2 221.9 - - 35.7
3 225.1 - - 35.1
4 280.4 - - 66.9
5 81.8 - - 55.1
6 58.3 - - 33.0
7 45.0 - - 45.0
8 71.3 - - 15.5
9 156.2 - - 14.8
10 297.7 - - 77.5
11 36.6 - - 2.4
12 170.8 - - 36.2
13 178.0 - - 36.0
14 182.9 - - 49.0
15 221.3 - - 44.1
16 355.5 - - 122.6
17 205.4 - - 175.0
18 118.9 - - 100.0
19 109.7 - - 35.0
20 330.5 - - 89.6
21 101.4 - - 70.0
22 131.8 - - 55.0
23 282.6 - - 75.0
24 100.0 - - 100.0
25 37.1 - - 3.3

Hourly Analysis Program v4.80 Page 91 of 126


FCU - SPA Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
26 392.4 - - 185.0
27 141.5 - - 6.7
28 831.0 - - 265.0
29 170.4 - - 12.0
30 116.0 - - 3.0
31 71.7 - - 3.3
32 453.4 - - 95.0
33 141.9 - - 130.0
34 169.6 - - 160.0
35 80.5 - - 19.2
36 1229.3 - - 325.1
37 62.5 - - 9.9
38 371.2 - - 11.7
39 692.7 - - 87.7
40 136.8 - - 0.0
41 198.0 - - 0.0
42 90.8 - - 40.0
43 311.1 - - 72.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 92 of 126


FCU - Standard Guestroom B Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Standard Guestroom B
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: King Room


NTYP. King Room Bot x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Hourly Analysis Program v4.80 Page 93 of 126


FCU - Standard Guestroom B Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 199.7 - - 17.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 94 of 126


FCU - Standard Guestroom L Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Standard Guestroom L
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: King Room


NTYP. King Room L x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Hourly Analysis Program v4.80 Page 95 of 126


FCU - Standard Guestroom L Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 195.9 - - 17.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 96 of 126


FCU - Standard Guestroom L.B Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Standard Guestroom L.B
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: King Room


NTYP. King Room L.B x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Hourly Analysis Program v4.80 Page 97 of 126


FCU - Standard Guestroom L.B Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 219.4 - - 17.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 98 of 126


FCU - Standard Guestroom L.T Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Standard Guestroom L.T
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: King Room


NTYP. King Room L.T x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Hourly Analysis Program v4.80 Page 99 of 126 99


FCU - Standard Guestroom L.T Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 229.7 - - 17.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 100 of 126 100


FCU - Standard Guestroom R Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Standard Guestroom R
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: King Room


NTYP. King Room R x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Hourly Analysis Program v4.80 Page 101 of 126


FCU - Standard Guestroom R Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 209.4 - - 17.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 102 of 126


FCU - Standard Guestroom R.B Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Standard Guestroom R.B
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: King Room


NTYP. King Room R.B x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Hourly Analysis Program v4.80 Page 103 of 126


FCU - Standard Guestroom R.B Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 234.5 - - 17.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 104 of 126


FCU - Standard Guestroom R.T Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Standard Guestroom R.T
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: King Room


NTYP. King Room R.T x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Hourly Analysis Program v4.80 Page 105 of 126


FCU - Standard Guestroom R.T Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 241.9 - - 17.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 106 of 126


FCU - Standard Guestroom T Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - Standard Guestroom T
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Cooling Coil Data:


Setpoint 20.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: King Room


NTYP. King Room Top x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On

Terminal Units Data:

Hourly Analysis Program v4.80 Page 107 of 126


FCU - Standard Guestroom T Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 234.2 - - 17.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 108 of 126


FCU - TYP Pantry Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU - TYP Pantry
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: F1 Pantry
FP-TYP. Pantry x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation

Hourly Analysis Program v4.80 Page 109 of 126


FCU - TYP Pantry Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

(L/s) (kW) (kW) (L/s)


1 124.3 - - 12.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 110 of 126


FCU-EL - Cellars Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU-EL - Cellars
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 16
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: C1-39 AV Control Room


EL-C1-39 AV Control x1
Zone 2: C1-40 AV Equipment Room
EL-C1-40 AV Equipment x1
Zone 3: C1-108 Security Command
EL-C1-108 Security CC x1
Zone 4: GF-38 Fire Command Cen.
EL-GF-38 Fire CC x1
Zone 5: C2-30 Demarcation
EL-C2-30 Demarcation x1
Zone 6: C2-21 EMDB
EL-C2-21 EMDB x1
Zone 7: C2-27 UPS
EL-C2-27 UPS x1
Zone 8: C3-33 UPS
EL-C3-33 UPS Room x1
Zone 9: C2-11- IT Director
C2F-11 IT Director x1
Zone 10: C2-10 IT Store
C2F-10 IT Store x1
Zone 11: C1-38 IDF
EL-C1-38 IDF x1
Zone 12: C1-56
EL-C1-56 El Room x1
Zone 13: C1-36 EL Room
EL-C1-36 El Room x1
Zone 14: C1-92 IDF
EL-C1-92 IDF x1
Zone 15: C1-38 IDF
EL-C1-38 IDF x1
Zone 16: C1-135 IDF
EL-C1-135 IDF x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C

Hourly Analysis Program v4.80 Page 111 of 126


FCU-EL - Cellars Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Heating Source Hot Water


Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.5 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 158.4 - - 0.0
2 1211.3 - - 0.0
3 888.6 - - 0.0
4 395.5 - - 0.0
5 946.8 - - 0.0
6 590.0 - - 0.0
7 995.2 - - 0.0
8 2205.1 - - 0.0
9 157.5 - - 13.2
10 147.2 - - 12.3
11 79.8 - - 0.0
12 301.3 - - 0.0
13 315.0 - - 0.0
14 780.0 - - 0.0
15 79.8 - - 0.0
16 104.4 - - 0.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 112 of 126


FCU-EL - Floors Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name FCU-EL - Floors
Equipment Type Terminal Units
Air System Type 4-Pipe Fan Coil
Number of zones 2
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Typ. Electrical Room


TYP Floor Electrical Rm x23
Zone 2: IDF Room
TYP IDF Closet x23

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 24.0 24.0 21.0 21.0 1.00
2 22.0 22.0 18.0 18.0 1.00

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 100 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.5 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates

Hourly Analysis Program v4.80 Page 113 of 126


FCU-EL - Floors Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 6567.8 - - 0.0
2 6720.4 - - 0.0

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 114 of 126


RAHU-H-RF-01 Right Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name RAHU-H-RF-01 Right
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 16.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 15.5 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Recovery
ZRAHU-H-RF-01 x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 0.83 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH

Hourly Analysis Program v4.80 Page 115 of 126


RAHU-H-RF-01 Right Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Minimum Airflow 0.00 L/s/person

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 15.5 °C
Supply Fan Airflow 8201.0 L/s
Ventilation Airflow 8201.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 8201.0 - 49.6

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 116 of 126


RAHU-H-RF-02 Left Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name RAHU-H-RF-02 Left
Equipment Type Chilled Water AHU
Air System Type VAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Proportional
Ventilation Sizing Method Sum of Space OA Airflows
Minimum Airflow 0 %
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Preheat Coil Data:


Setpoint 10.0 °C
Heating Source Hot Water
Schedule JFMAMJJASOND
Coil position Downstream of Mixing Point

Central Cooling Data:


Supply Air Temperature 15.5 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Constant Temperature - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Recovery
ZRAHU-H-RF-02 x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type VAV box with RH

Hourly Analysis Program v4.80 Page 117 of 126


RAHU-H-RF-02 Left Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

Minimum Airflow 0.00 L/s/person

Reheat Coil Source Hot Water


Reheat Coil Schedule JFMAMJJASOND

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 15.5 °C
Supply Fan Airflow 7148.0 L/s
Ventilation Airflow 7148.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.0 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 7148.0 - 43.3

5. Equipment Data
Changeover Controller:
Used No

Hourly Analysis Program v4.80 Page 118 of 126


Server Room - CRAC Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name Server Room - CRAC
Equipment Type Chilled Water AHU
Air System Type Single Zone CAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Humidification Data:
Minimum RH Setpoint 50 %
Humidifier Type Heated Pan - Steam HX

Central Cooling Data:


Supply Air Temperature 12.0 °C
Coil Bypass Factor 0.100
Cooling Source Chilled Water
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
EL-C2-12 Server Room x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 20.0 °C
Cooling T-stat: Unocc. 20.0 °C
Heating T-stat: Occ. 18.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type Diffuser
Minimum Airflow 0.00 L/s/person

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Hot Water


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):

Hourly Analysis Program v4.80 Page 119 of 126


Server Room - CRAC Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

System Sizing Data:


Sizing Data:
Cooling Supply Temperature 12.0 °C
Supply Fan Airflow 8200.6 L/s
Ventilation Airflow 0.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 8200.6 - -

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v4.80 Page 120 of 126


SRAC -EL - TV Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name SRAC -EL - TV
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: TV Room
EL-F19-03 TV Room x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 12.8 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temperature 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 0 Pa
Fan Overall Efficiency 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.8 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 6.7 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation

Hourly Analysis Program v4.80 Page 121 of 126


SRAC -EL - TV Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

(L/s) (kW) (kW) (L/s)


1 574.0 - - 0.0

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity


Maximum Design Cooling Oversizing Compressor + ARI Conventional
Load OAT Equipment Capacity Factor OD Fan Power Performance Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) Rating Units (°C)
1 n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.80 Page 122 of 126


TYP. CRC Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name TYP. CRC
Equipment Type Undefined
Air System Type Single Zone CAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 12.0 °C
Coil Bypass Factor 0.100
Cooling Source Any
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:


Supply Temperature 35.0 °C
Heating Source Any
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
TYP. CRC x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type Diffuser
Minimum Airflow 370.0 L/s

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Any


Zone Heating Unit Schedule JFMAMJJASOND

Hourly Analysis Program v4.80 Page 123 of 126


TYP. CRC Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.0 °C
Supply Fan Airflow 370.0 L/s
Ventilation Airflow 370.0 L/s
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 370.0 - -

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v4.80 Page 124 of 126


TYP. Lobby Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

1. General Details:
Air System Name TYP. Lobby
Equipment Type Undefined
Air System Type Single Zone CAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 12.0 °C
Coil Bypass Factor 0.100
Cooling Source Any
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:


Supply Temperature 35.0 °C
Heating Source Any
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0 Pa
Overall Efficiency 54 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
TYP. Lobby x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 24.0 °C
Cooling T-stat: Unocc. 24.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 21.0 °C
T-stat Throttling Range 1.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type Diffuser
Minimum Airflow 85.0 L/s

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Any


Zone Heating Unit Schedule JFMAMJJASOND

Hourly Analysis Program v4.80 Page 125 of 126


TYP. Lobby Input Data
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:41PM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 12.0 °C
Supply Fan Airflow 85.0 L/s
Ventilation Airflow 85.0 L/s
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 85.0 - -

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v4.80 Page 126 of 126


Air System Sizing Summary for AHU-H-C1-01 Spa
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Air System Information


Air System Name AHU-H-C1-01 Spa Number of zones 1
Equipment Class CW AHU Floor Area 1.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 69.4 kW Load occurs at Jul 1500
Sensible coil load 69.4 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 4205 L/s Entering DB / WB 37.0 / 22.0 °C
Max block L/s at Des Htg 4205 L/s Leaving DB / WB 22.0 / 17.6 °C
Sum of peak zone L/s 4205 L/s Coil ADP 20.3 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 0.0 Resulting RH 66 %
W/m² 69419.4 Design supply temp. 22.0 °C
Water flow @ 6.7 °K rise 2.48 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 110.1 kW Load occurs at Des Htg
Coil L/s at Des Htg 4205 L/s Ent. DB / Lvg DB -0.8 / 23.0 °C
Max coil L/s 4205 L/s
Water flow @ 12.2 °K drop 2.16 L/s

Supply Fan Sizing Data


Actual max L/s at Des Htg 4205 L/s Fan motor BHP 0.00 BHP
Standard L/s 3834 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 4205.00 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 4205 L/s L/s/person 0.00 L/s/person
L/(s-m²) 4205.00 L/(s-m²)

Hourly Analysis Program v4.80 Page 1 of 142


Zone Sizing Summary for AHU-H-C1-01 Spa
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Air System Information


Air System Name AHU-H-C1-01 Spa Number of zones 1
Equipment Class CW AHU Floor Area 1.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
ZAHU-H-C1-01 0.0 4205 4205 Des Htg 0.0 1.0 4205.00

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
ZAHU-H-C1-01
ZAHU-H-C1-01 1 0.0 Jan 0000 4205 0.0 1.0 4205.00

Hourly Analysis Program v4.80 Page 2 of 142


Ventilation Sizing Summary for AHU-H-C1-01 Spa
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 4205 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
ZAHU-H-C1-01
ZAHU-H-C1-01 1 1.0 0.0 4205.0 0.00 0.00 4205.0 0.0 4205.0
Totals (incl. Space Multipliers) 4205.0 4205.0

Hourly Analysis Program v4.80 Page 3 of 142


Air System Design Load Summary for AHU-H-C1-01 Spa
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0
Zone Conditioning - 0 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 4205 L/s 0 - 4205 L/s 0 -
Ventilation Load 4205 L/s 69419 0 4205 L/s 105518 0
Supply Fan Load 4205 L/s 0 - 4205 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 69419 0 - 105518 0
Central Cooling Coil - 69419 0 - -4628 0
Preheat Coil - 0 - - 110146 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 69419 0 - 105518 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 4 of 142


Zone Design Load Summary for AHU-H-C1-01 Spa
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZAHU-H-C1-01 DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

Hourly Analysis Program v4.80 Page 5 of 142


Space Design Load Summary for AHU-H-C1-01 Spa
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' ZAHU-H-C1-01 '' IN ZONE '' ZAHU-H-C1-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' ZAHU-H-C1-01 '' IN ZONE '' ZAHU-H-C1-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 6 of 142


Hourly Air System Design Day Loads for AHU-H-C1-01 Spa
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 4205 26.5 26.5 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 4205 23.9 23.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 4205 21.3 21.3 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 4205 19.2 19.2 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 4205 17.6 17.6 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 4205 17.1 17.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 4205 18.2 18.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 4205 20.8 20.8 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 4205 25.5 25.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 4205 32.3 32.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 4205 40.1 40.1 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 4205 49.0 49.0 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 4205 57.4 57.4 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 4205 63.7 63.7 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 4205 67.9 67.9 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 4205 69.4 69.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 4205 67.9 67.9 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 4205 64.2 64.2 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 4205 58.4 58.4 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 4205 51.6 51.6 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 4205 44.8 44.8 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 4205 39.1 39.1 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 4205 33.9 33.9 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 4205 29.7 29.7 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 7 of 142


Hourly Zone Loads for AHU-H-C1-01 Spa
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: ZAHU-H-C1-01
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 22.0 66 4205.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 8 of 142


System Psychrometrics for AHU-H-C1-01 Spa
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 4205 400 69419 0
Vent - Return Mixing Outlet 37.0 0.01203 4205 400 - -
Preheat Coil Outlet 37.0 0.01203 4205 400 0 -
Central Cooling Coil Outlet 22.0 0.01203 4205 400 69419 0
Supply Fan Outlet 22.0 0.01203 4205 400 0 -
Cold Supply Duct Outlet 22.0 0.01203 4205 400 - -
Zone Air - 22.0 0.01203 4205 400 0 0
Return Plenum Outlet 22.0 0.01203 4205 400 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
ZAHU-H-C1-01 0 Deadband 0 22.0 4205 400 0 0

Hourly Analysis Program v4.80 Page 9 of 142


Air System Sizing Summary for AHU-H-C1-02 Cafe
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Air System Information


Air System Name AHU-H-C1-02 Cafe Number of zones 1
Equipment Class CW AHU Floor Area 146.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 120.4 kW Load occurs at Jul 1500
Sensible coil load 86.5 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 3038 L/s Entering DB / WB 37.0 / 22.0 °C
Max block L/s at Sep 1500 3038 L/s Leaving DB / WB 11.1 / 10.0 °C
Sum of peak zone L/s 3038 L/s Coil ADP 8.2 °C
Sensible heat ratio 0.719 Bypass Factor 0.100
m²/kW 1.2 Resulting RH 46 %
W/m² 824.4 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 4.30 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 45.5 kW Load occurs at Des Htg
Coil L/s at Des Htg 3038 L/s Ent. DB / Lvg DB -0.8 / 12.8 °C
Max coil L/s 3038 L/s
Water flow @ 11.0 °K drop 0.99 L/s

Supply Fan Sizing Data


Actual max L/s at Sep 1500 3038 L/s Fan motor BHP 7.09 BHP
Standard L/s 2769 L/s Fan motor kW 5.63 kW
Actual max L/(s-m²) 20.80 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 3038 L/s L/s/person 22.50 L/s/person
L/(s-m²) 20.80 L/(s-m²)

Hourly Analysis Program v4.80 Page 10 of 142


Zone Sizing Summary for AHU-H-C1-02 Cafe
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Air System Information


Air System Name AHU-H-C1-02 Cafe Number of zones 1
Equipment Class CW AHU Floor Area 146.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
GF-45 Cafe 33.6 3038 3038 Sep 1500 7.1 146.0 20.80

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
GF-45 Cafe 34.6 0.75 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
GF-45 Cafe
GFC-45 Cafe 1 33.6 Sep 1500 3038 7.1 146.0 20.80

Hourly Analysis Program v4.80 Page 11 of 142


Ventilation Sizing Summary for AHU-H-C1-02 Cafe
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

1. Summary
Ventilation Sizing Method ASHRAE Std 62.1-2007
Design Condition Minimum flow (heating)
Occupant Diversity 1.000
Uncorrected Ventilation Airflow Rate 2430 L/s
System Ventilation Efficiency 1.000
Design Ventilation Airflow Rate 3038 L/s

2. Space Ventilation Analysis Table


Minimum Floor Required Time Required Air Required Uncorrected Space
Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation
Zone Name / Space Name Mult. (L/s) (m²) (L/(s-m²)) Occupancy (L/s/person) Effectiveness (L/s) (L/s) Efficiency
GF-45 Cafe
GFC-45 Cafe 1 3038 146.0 0.00 135.0 18.00 0.80 3038 2430 1.000
Totals (incl. Space Multipliers) 3038 2430 1.000

Hourly Analysis Program v4.80 Page 12 of 142


Air System Design Load Summary for AHU-H-C1-02 Cafe
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 74 m² 3699 - 74 m² - -
Wall Transmission 62 m² 630 - 62 m² 493 -
Roof Transmission 146 m² 1373 - 146 m² 740 -
Window Transmission 74 m² 1616 - 74 m² 3210 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 108 m² 1361 - 108 m² 2052 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 7884 W 7884 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 135 9099 4752 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4000 0 - 0 0
Safety Factor 10% / 10% 2966 475 10% 650 0
>> Total Zone Loads - 32626 5227 - 7145 0
Zone Conditioning - 32424 5227 - 6776 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 678 L/s 0 - 678 L/s 0 -
Ventilation Load 3038 L/s 48478 28613 3038 L/s 69862 0
Supply Fan Load 3038 L/s 5625 - 3038 L/s -5625 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 86526 33841 - 71013 0
Central Cooling Coil - 86526 33841 - -5625 0
Preheat Coil - 0 - - 45465 -
Terminal Reheat Coils - 0 - - 31173 -
>> Total Conditioning - 86526 33841 - 71013 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 13 of 142


Zone Design Load Summary for AHU-H-C1-02 Cafe
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

GF-45 Cafe DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 74 m² 4877 - 74 m² - -
Wall Transmission 62 m² 732 - 62 m² 493 -
Roof Transmission 146 m² 1151 - 146 m² 740 -
Window Transmission 74 m² 1453 - 74 m² 3210 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 108 m² 1326 - 108 m² 2052 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 7884 W 7884 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 135 9099 4752 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4000 0 - 0 0
Safety Factor 10% / 10% 3052 475 10% 650 0
>> Total Zone Loads - 33573 5227 - 7145 0

Hourly Analysis Program v4.80 Page 14 of 142


Space Design Load Summary for AHU-H-C1-02 Cafe
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GFC-45 Cafe '' IN ZONE '' GF-45 Cafe ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 74 m² 4877 - 74 m² - -
Wall Transmission 62 m² 732 - 62 m² 493 -
Roof Transmission 146 m² 1151 - 146 m² 740 -
Window Transmission 74 m² 1453 - 74 m² 3210 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 108 m² 1326 - 108 m² 2052 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 7884 W 7884 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 135 9099 4752 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4000 0 - 0 0
Safety Factor 10% / 10% 3052 475 10% 650 0
>> Total Zone Loads - 33573 5227 - 7145 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GFC-45 Cafe '' IN ZONE '' GF-45 Cafe ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 24 0.365 - 376 - 191
WINDOW 1 24 1.990 0.300 471 2149 1041
SE EXPOSURE
WALL 38 0.365 - 356 - 302
WINDOW 1 50 1.990 0.300 982 2728 2169
H EXPOSURE
ROOF 146 0.232 - 1151 - 740

Hourly Analysis Program v4.80 Page 15 of 142


Hourly Air System Design Day Loads for AHU-H-C1-02 Cafe
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 3038 55.5 85.4 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 3038 53.7 83.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 3038 51.8 81.1 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 3038 50.3 79.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 3038 49.1 78.1 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 3038 48.8 77.7 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 3038 49.5 78.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 3038 51.4 80.7 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 3038 54.8 84.6 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 3038 59.7 90.2 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 3038 65.4 96.5 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 3038 71.8 103.8 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 3038 77.8 110.6 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 3038 82.4 115.7 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 3038 85.4 119.1 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 3038 86.5 120.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 3038 85.4 119.1 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 3038 82.7 116.1 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 3038 78.6 111.4 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 3038 73.7 105.9 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 3038 68.8 100.3 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 3038 64.6 95.6 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 3038 60.8 91.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 3038 57.8 88.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 16 of 142


Hourly Zone Loads for AHU-H-C1-02 Cafe
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: GF-45 Cafe


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 21.5 51 3037.5 27503.0 29165.1 0.0 0.0 0.0
0100 27.2 21.4 52 3037.5 27143.4 28878.6 0.0 0.0 0.0
0200 26.6 21.4 52 3037.5 26805.6 28603.1 0.0 0.0 0.0
0300 26.2 21.3 53 3037.5 26507.3 28350.5 0.0 0.0 0.0
0400 25.8 21.2 53 3037.5 26246.3 28120.8 0.0 0.0 0.0
0500 25.7 21.2 53 3037.5 26471.7 28200.6 0.0 0.0 0.0
0600 25.9 21.4 52 3037.5 27300.1 28679.3 0.0 0.0 0.0
0700 26.5 21.5 52 3037.5 28146.0 29198.4 0.0 0.0 0.0
0800 27.5 21.7 51 3037.5 28996.9 29742.8 0.0 0.0 0.0
0900 29.0 21.8 50 3037.5 29761.7 30252.7 0.0 0.0 0.0
1000 30.7 22.0 49 3037.5 30336.7 30657.2 0.0 0.0 0.0
1100 32.6 22.1 48 3037.5 30777.7 30985.2 0.0 0.0 0.0
1200 34.4 22.2 47 3037.5 31377.9 31419.5 0.0 0.0 0.0
1300 35.8 22.3 47 3037.5 32004.0 31881.0 0.0 0.0 0.0
1400 36.7 22.4 46 3037.5 32427.3 32222.7 0.0 0.0 0.0
1500 37.0 22.5 46 3037.5 32626.5 32423.5 0.0 0.0 0.0
1600 36.7 22.5 46 3037.5 32505.9 32417.0 0.0 0.0 0.0
1700 35.9 22.4 46 3037.5 31999.2 32152.6 0.0 0.0 0.0
1800 34.6 22.3 47 3037.5 31088.5 31610.5 0.0 0.0 0.0
1900 33.2 22.1 48 3037.5 30336.2 31140.7 0.0 0.0 0.0
2000 31.7 22.0 49 3037.5 29595.4 30660.5 0.0 0.0 0.0
2100 30.4 21.8 50 3037.5 28958.1 30229.3 0.0 0.0 0.0
2200 29.3 21.7 50 3037.5 28393.7 29832.5 0.0 0.0 0.0
2300 28.4 21.6 51 3037.5 27911.5 29478.6 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 17 of 142


System Psychrometrics for AHU-H-C1-02 Cafe
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 3038 400 48478 28613
Vent - Return Mixing Outlet 37.0 0.01203 3038 400 - -
Preheat Coil Outlet 37.0 0.01203 3038 400 0 -
Central Cooling Coil Outlet 11.1 0.00789 3038 400 86526 33841
Supply Fan Outlet 12.8 0.00789 3038 400 5625 -
Cold Supply Duct Outlet 12.8 0.00789 3038 400 - -
Zone Air - 22.5 0.00853 3038 596 32424 5227
Zone Direct Exhaust Outlet 22.5 0.00853 2360 596 - -
Return Plenum Outlet 22.5 0.00853 678 596 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
GF-45 Cafe 32626 Deadband 32424 22.5 3038 596 0 0

Hourly Analysis Program v4.80 Page 18 of 142


Air System Sizing Summary for AHU-H-C1-03 Retails
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Air System Information


Air System Name AHU-H-C1-03 Retails Number of zones 1
Equipment Class CW AHU Floor Area 1.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 32.6 kW Load occurs at Jul 1500
Sensible coil load 24.5 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 920 L/s Entering DB / WB 37.0 / 22.0 °C
Max block L/s at Des Htg 920 L/s Leaving DB / WB 12.8 / 11.5 °C
Sum of peak zone L/s 920 L/s Coil ADP 10.1 °C
Sensible heat ratio 0.753 Bypass Factor 0.100
m²/kW 0.0 Resulting RH 55 %
W/m² 32556.3 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 1.16 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 13.8 kW Load occurs at Des Htg
Coil L/s at Des Htg 920 L/s Ent. DB / Lvg DB -0.8 / 12.8 °C
Max coil L/s 920 L/s
Water flow @ 12.2 °K drop 0.27 L/s

Supply Fan Sizing Data


Actual max L/s at Des Htg 920 L/s Fan motor BHP 0.00 BHP
Standard L/s 839 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 920.00 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 920 L/s L/s/person 0.00 L/s/person
L/(s-m²) 920.00 L/(s-m²)

Hourly Analysis Program v4.80 Page 19 of 142


Zone Sizing Summary for AHU-H-C1-03 Retails
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Air System Information


Air System Name AHU-H-C1-03 Retails Number of zones 1
Equipment Class CW AHU Floor Area 1.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 0.0 920 920 Des Htg 0.0 1.0 920.00

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 12.2 °K (kW) @ 12.2 °K (L/s)
Zone 1 8.3 0.16 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
ZAHU-H-C1-03 1 0.0 Jan 0000 920 0.0 1.0 920.00

Hourly Analysis Program v4.80 Page 20 of 142


Ventilation Sizing Summary for AHU-H-C1-03 Retails
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 920 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
ZAHU-H-C1-03 1 1.0 0.0 920.0 0.00 0.00 920.0 0.0 920.0
Totals (incl. Space Multipliers) 920.0 920.0

Hourly Analysis Program v4.80 Page 21 of 142


Air System Design Load Summary for AHU-H-C1-03 Retails
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0
Zone Conditioning - 0 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 920 L/s 0 - 920 L/s 0 -
Ventilation Load 920 L/s 17103 8030 920 L/s 21171 0
Supply Fan Load 920 L/s 0 - 920 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 17103 8030 - 21171 0
Central Cooling Coil - 24526 8030 - 0 0
Preheat Coil - 0 - - 13771 -
Terminal Reheat Coils - -7423 - - 7423 -
>> Total Conditioning - 17103 8030 - 21193 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 22 of 142


Zone Design Load Summary for AHU-H-C1-03 Retails
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Zone 1 DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

Hourly Analysis Program v4.80 Page 23 of 142


Space Design Load Summary for AHU-H-C1-03 Retails
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' ZAHU-H-C1-03 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' ZAHU-H-C1-03 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 24 of 142


Hourly Air System Design Day Loads for AHU-H-C1-03 Retails
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 920 15.1 21.8 0.0 0.0 0.0 0.0 7.4 0.0
0100 27.2 920 14.6 21.2 0.0 0.0 0.0 0.0 7.4 0.0
0200 26.6 920 14.0 20.5 0.0 0.0 0.0 0.0 7.4 0.0
0300 26.2 920 13.5 20.0 0.0 0.0 0.0 0.0 7.4 0.0
0400 25.8 920 13.2 19.6 0.0 0.0 0.0 0.0 7.4 0.0
0500 25.7 920 13.1 19.5 0.0 0.0 0.0 0.0 7.4 0.0
0600 25.9 920 13.3 19.7 0.0 0.0 0.0 0.0 7.4 0.0
0700 26.5 920 13.9 20.4 0.0 0.0 0.0 0.0 7.4 0.0
0800 27.5 920 14.9 21.6 0.0 0.0 0.0 0.0 7.4 0.0
0900 29.0 920 16.4 23.3 0.0 0.0 0.0 0.0 7.4 0.0
1000 30.7 920 18.1 25.2 0.0 0.0 0.0 0.0 7.4 0.0
1100 32.6 920 20.1 27.5 0.0 0.0 0.0 0.0 7.4 0.0
1200 34.4 920 21.9 29.6 0.0 0.0 0.0 0.0 7.4 0.0
1300 35.8 920 23.3 31.1 0.0 0.0 0.0 0.0 7.4 0.0
1400 36.7 920 24.2 32.2 0.0 0.0 0.0 0.0 7.4 0.0
1500 37.0 920 24.5 32.6 0.0 0.0 0.0 0.0 7.4 0.0
1600 36.7 920 24.2 32.2 0.0 0.0 0.0 0.0 7.4 0.0
1700 35.9 920 23.4 31.2 0.0 0.0 0.0 0.0 7.4 0.0
1800 34.6 920 22.1 29.8 0.0 0.0 0.0 0.0 7.4 0.0
1900 33.2 920 20.6 28.1 0.0 0.0 0.0 0.0 7.4 0.0
2000 31.7 920 19.1 26.4 0.0 0.0 0.0 0.0 7.4 0.0
2100 30.4 920 17.9 25.0 0.0 0.0 0.0 0.0 7.4 0.0
2200 29.3 920 16.7 23.7 0.0 0.0 0.0 0.0 7.4 0.0
2300 28.4 920 15.8 22.6 0.0 0.0 0.0 0.0 7.4 0.0

Hourly Analysis Program v4.80 Page 25 of 142


Hourly Zone Loads for AHU-H-C1-03 Retails
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 58 920.0 0.0 0.0 0.0 7422.6 0.0
0100 27.2 20.1 58 920.0 0.0 0.0 0.0 7422.6 0.0
0200 26.6 20.1 58 920.0 0.0 0.0 0.0 7422.6 0.0
0300 26.2 20.1 59 920.0 0.0 0.0 0.0 7422.6 0.0
0400 25.8 20.1 59 920.0 0.0 0.0 0.0 7422.6 0.0
0500 25.7 20.1 59 920.0 0.0 0.0 0.0 7422.6 0.0
0600 25.9 20.1 59 920.0 0.0 0.0 0.0 7422.6 0.0
0700 26.5 20.1 58 920.0 0.0 0.0 0.0 7422.6 0.0
0800 27.5 20.1 58 920.0 0.0 0.0 0.0 7422.6 0.0
0900 29.0 20.1 58 920.0 0.0 0.0 0.0 7422.6 0.0
1000 30.7 20.1 57 920.0 0.0 0.0 0.0 7422.6 0.0
1100 32.6 20.1 56 920.0 0.0 0.0 0.0 7422.6 0.0
1200 34.4 20.1 56 920.0 0.0 0.0 0.0 7422.6 0.0
1300 35.8 20.1 55 920.0 0.0 0.0 0.0 7422.6 0.0
1400 36.7 20.1 55 920.0 0.0 0.0 0.0 7422.6 0.0
1500 37.0 20.1 55 920.0 0.0 0.0 0.0 7422.6 0.0
1600 36.7 20.1 55 920.0 0.0 0.0 0.0 7422.6 0.0
1700 35.9 20.1 55 920.0 0.0 0.0 0.0 7422.6 0.0
1800 34.6 20.1 56 920.0 0.0 0.0 0.0 7422.6 0.0
1900 33.2 20.1 56 920.0 0.0 0.0 0.0 7422.6 0.0
2000 31.7 20.1 57 920.0 0.0 0.0 0.0 7422.6 0.0
2100 30.4 20.1 57 920.0 0.0 0.0 0.0 7422.6 0.0
2200 29.3 20.1 57 920.0 0.0 0.0 0.0 7422.6 0.0
2300 28.4 20.1 58 920.0 0.0 0.0 0.0 7422.6 0.0

Hourly Analysis Program v4.80 Page 26 of 142


System Psychrometrics for AHU-H-C1-03 Retails
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 920 400 17103 8030
Vent - Return Mixing Outlet 37.0 0.01203 920 400 - -
Preheat Coil Outlet 37.0 0.01203 920 400 0 -
Central Cooling Coil Outlet 12.8 0.00878 920 400 24526 8030
Supply Fan Outlet 12.8 0.00878 920 400 0 -
Cold Supply Duct Outlet 12.8 0.00878 920 400 - -
Zone Air - 20.1 0.00878 920 400 0 0
Return Plenum Outlet 20.1 0.00878 920 400 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 0 20.1 920 400 7423 0

Hourly Analysis Program v4.80 Page 27 of 142


Air System Sizing Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Air System Information


Air System Name AHU-H-C2-01- Bulk Kitchen Number of zones 11
Equipment Class CW AHU Floor Area 441.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 237.4 kW Load occurs at Jul 1500
Sensible coil load 170.7 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 5991 L/s Entering DB / WB 37.0 / 22.0 °C
Max block L/s at Jul 1600 5991 L/s Leaving DB / WB 11.1 / 10.0 °C
Sum of peak zone L/s 5991 L/s Coil ADP 8.2 °C
Sensible heat ratio 0.719 Bypass Factor 0.100
m²/kW 1.9 Resulting RH 45 %
W/m² 538.4 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 8.48 L/s Zone T-stat Check 11 of 11 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 89.7 kW Load occurs at Des Htg
Coil L/s at Des Htg 5991 L/s Ent. DB / Lvg DB -0.8 / 12.8 °C
Max coil L/s 5991 L/s
Water flow @ 11.0 °K drop 1.95 L/s

Supply Fan Sizing Data


Actual max L/s at Jul 1600 5991 L/s Fan motor BHP 13.99 BHP
Standard L/s 5462 L/s Fan motor kW 11.10 kW
Actual max L/(s-m²) 13.59 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 5991 L/s L/s/person 101.55 L/s/person
L/(s-m²) 13.59 L/(s-m²)

Hourly Analysis Program v4.80 Page 28 of 142


Zone Sizing Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Air System Information


Air System Name AHU-H-C2-01- Bulk Kitchen Number of zones 11
Equipment Class CW AHU Floor Area 441.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C1-35 Service Station 2.1 170 170 Jul 1600 0.8 16.0 10.64
C1-25 Corridor 9.5 771 771 Jul 1600 7.2 259.0 2.98
C1-27 Oven Room 4.6 371 371 Jul 1600 0.4 18.0 20.64
C1-30 Regeneration Area 25.4 3255 3255 Jul 1600 2.9 75.0 43.40
C1-32 Service Station 5.3 434 434 Jun 1500 0.1 21.0 20.67
C1-33 Central Dishwash 5.4 720 720 Jul 1600 2.1 47.0 15.32
C1-37 Banquet Service FA 0.0 15 15 Des Htg 0.0 1.0 15.00
C1-53 Executive Chef FA 0.0 15 15 Des Htg 0.0 1.0 15.00
C1-54 Executive Chef FA 0.0 15 15 Des Htg 0.0 1.0 15.00
C1-34 Chef Office FA 0.0 15 15 Des Htg 0.0 1.0 15.00
Refrigration Room 0.0 210 210 Des Htg 0.0 1.0 210.00

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
C1-35 Service Station 2.3 0.05 0.0 0.00 0
C1-25 Corridor 14.1 0.31 0.0 0.00 0
C1-27 Oven Room 3.8 0.08 0.0 0.00 0
C1-30 Regeneration Area 32.3 0.70 0.0 0.00 0
C1-32 Service Station 4.0 0.09 0.0 0.00 0
C1-33 Central Dishwash 8.6 0.19 0.0 0.00 0
C1-37 Banquet Service FA 0.1 0.00 0.0 0.00 0
C1-53 Executive Chef FA 0.1 0.00 0.0 0.00 0
C1-54 Executive Chef FA 0.1 0.00 0.0 0.00 0
C1-34 Chef Office FA 0.1 0.00 0.0 0.00 0
Refrigration Room 0.0 0.00 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-35 Service Station
C1K1-35 Service Station 1 2.1 Jul 1600 170 0.8 16.0 10.64
C1-25 Corridor
C1K1-25 Corridor 2 1 9.5 Jul 1600 771 7.2 259.0 2.98
C1-27 Oven Room
C1K1-27 Oven Room 1 4.6 Jul 1600 371 0.4 18.0 20.64
C1-30 Regeneration Area
C1K1-30 Regeneration Ar 1 25.4 Jul 1600 3255 2.9 75.0 43.40
C1-32 Service Station
C1K1-32 Service Station 1 5.3 Jun 1500 434 0.1 21.0 20.67

Hourly Analysis Program v4.80 Page 29 of 142


Zone Sizing Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-33 Central Dishwash
C1K1-33 Central Dishwash 1 5.4 Jul 1600 720 2.1 47.0 15.32
C1-37 Banquet Service FA
C1K1-FA 37 Banquet Servi 1 0.0 Jan 0000 15 0.0 1.0 15.00
C1-53 Executive Chef FA
C1K1-FA 53 Executive Che 1 0.0 Jan 0000 15 0.0 1.0 15.00
C1-54 Executive Chef FA
C1K1-FA 54 Executive Che 1 0.0 Jan 0000 15 0.0 1.0 15.00
C1-34 Chef Office FA
C1K1-FA-34 Chef Office 1 0.0 Jan 0000 15 0.0 1.0 15.00
Refrigration Room
C1K1 - Refrigration Rm 1 0.0 Jan 0000 210 0.0 1.0 210.00

Hourly Analysis Program v4.80 Page 30 of 142


Ventilation Sizing Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 5991 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
C1-35 Service Station
C1K1-35 Service Station 1 16.0 4.0 170.2 0.00 0.00 0.0 100.0 170.2
C1-25 Corridor
C1K1-25 Corridor 2 1 259.0 26.0 770.8 0.00 0.00 0.0 100.0 770.8
C1-27 Oven Room
C1K1-27 Oven Room 1 18.0 4.0 371.5 0.00 0.00 0.0 100.0 371.5
C1-30 Regeneration Area
C1K1-30 Regeneration Ar 1 75.0 15.0 3255.0 0.00 0.00 0.0 100.0 3255.0
C1-32 Service Station
C1K1-32 Service Station 1 21.0 5.0 434.0 0.00 0.00 0.0 100.0 434.0
C1-33 Central Dishwash
C1K1-33 Central Dishwash 1 47.0 5.0 720.0 0.00 0.00 0.0 100.0 720.0
C1-37 Banquet Service FA
C1K1-FA 37 Banquet Servi 1 1.0 0.0 15.0 0.00 0.00 15.0 0.0 15.0
C1-53 Executive Chef FA
C1K1-FA 53 Executive Che 1 1.0 0.0 15.0 0.00 0.00 15.0 0.0 15.0
C1-54 Executive Chef FA
C1K1-FA 54 Executive Che 1 1.0 0.0 15.0 0.00 0.00 15.0 0.0 15.0
C1-34 Chef Office FA
C1K1-FA-34 Chef Office 1 1.0 0.0 15.0 0.00 0.00 15.0 0.0 15.0
Refrigration Room
C1K1 - Refrigration Rm 1 1.0 0.0 210.0 0.00 0.00 210.0 100.0 420.0
Totals (incl. Space Multipliers) 5991.4 5991.4

Hourly Analysis Program v4.80 Page 31 of 142


Air System Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 450 m² 4234 - 450 m² 2282 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 399 m² 1593 - 399 m² 2394 -
Partitions 399 m² 5026 - 399 m² 7579 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2995 W 2995 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 59 4607 5314 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 29129 0 - 0 0
Safety Factor 10% / 10% 4758 531 10% 1226 0
>> Total Zone Loads - 52343 5846 - 13481 0
Zone Conditioning - 52513 5846 - 12485 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2016 L/s 0 - 2016 L/s 0 -
Ventilation Load 5991 L/s 103169 60905 5991 L/s 136151 0
Supply Fan Load 5991 L/s 11096 - 5991 L/s -11096 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 166778 66750 - 137541 0
Central Cooling Coil - 170673 66750 - -11096 0
Preheat Coil - 0 - - 89680 -
Terminal Reheat Coils - -3895 - - 58956 -
>> Total Conditioning - 166778 66750 - 137541 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 32 of 142


Zone Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

C1-35 Service Station DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 16 m² 150 - 16 m² 81 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 34 m² 427 - 34 m² 638 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 224 W 224 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 760 0 - 0 0
Safety Factor 10% / 10% 191 53 10% 72 0
>> Total Zone Loads - 2098 587 - 791 0

C1-25 Corridor DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 279 m² 2616 - 279 m² 1414 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 259 m² 1043 - 259 m² 1554 -
Partitions 188 m² 2389 - 188 m² 3572 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 837 W 837 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 26 1752 915 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 864 92 10% 654 0
>> Total Zone Loads - 9501 1007 - 7194 0

Hourly Analysis Program v4.80 Page 33 of 142


Zone Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

C1-27 Oven Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 12 m² 116 - 12 m² 63 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 18 m² 72 - 18 m² 108 -
Partitions 11 m² 136 - 11 m² 203 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 220 W 220 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3272 0 - 0 0
Safety Factor 10% / 10% 416 53 10% 37 0
>> Total Zone Loads - 4579 587 - 412 0

C1-30 Regeneration Area DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 75 m² 703 - 75 m² 380 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 75 m² 302 - 75 m² 450 -
Partitions 96 m² 1215 - 96 m² 1816 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 763 W 763 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 15 1297 2000 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 18855 0 - 0 0
Safety Factor 10% / 10% 2314 200 10% 265 0
>> Total Zone Loads - 25449 2199 - 2911 0

Hourly Analysis Program v4.80 Page 34 of 142


Zone Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

C1-32 Service Station DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 21 m² 198 - 21 m² 106 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 294 W 294 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3939 0 - 0 0
Safety Factor 10% / 10% 486 67 10% 11 0
>> Total Zone Loads - 5350 733 - 117 0

C1-33 Central Dishwash DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 47 m² 441 - 47 m² 238 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 47 m² 189 - 47 m² 282 -
Partitions 71 m² 902 - 71 m² 1349 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 658 W 658 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2303 0 - 0 0
Safety Factor 10% / 10% 493 67 10% 187 0
>> Total Zone Loads - 5418 733 - 2056 0

Hourly Analysis Program v4.80 Page 35 of 142


Zone Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

C1-37 Banquet Service FA DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

C1-53 Executive Chef FA DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

Hourly Analysis Program v4.80 Page 36 of 142


Zone Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

C1-54 Executive Chef FA DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

C1-34 Chef Office FA DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

Hourly Analysis Program v4.80 Page 37 of 142


Zone Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Refrigration Room DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

Hourly Analysis Program v4.80 Page 38 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1K1-35 Service Station '' IN ZONE '' C1-35 Service Station ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 16 m² 150 - 16 m² 81 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 34 m² 427 - 34 m² 638 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 224 W 224 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 760 0 - 0 0
Safety Factor 10% / 10% 191 53 10% 72 0
>> Total Zone Loads - 2098 587 - 791 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1K1-35 Service Station '' IN ZONE '' C1-35 Service Station ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 16 0.232 - 150 - 81

Hourly Analysis Program v4.80 Page 39 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' C1K1-25 Corridor 2 '' IN ZONE '' C1-25 Corridor ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 279 m² 2616 - 279 m² 1414 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 259 m² 1043 - 259 m² 1554 -
Partitions 188 m² 2389 - 188 m² 3572 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 837 W 837 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 26 1752 915 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 864 92 10% 654 0
>> Total Zone Loads - 9501 1007 - 7194 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' C1K1-25 Corridor 2 '' IN ZONE '' C1-25 Corridor ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 279 0.232 - 2616 - 1414

Hourly Analysis Program v4.80 Page 40 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' C1K1-27 Oven Room '' IN ZONE '' C1-27 Oven Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 12 m² 116 - 12 m² 63 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 18 m² 72 - 18 m² 108 -
Partitions 11 m² 136 - 11 m² 203 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 220 W 220 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3272 0 - 0 0
Safety Factor 10% / 10% 416 53 10% 37 0
>> Total Zone Loads - 4579 587 - 412 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' C1K1-27 Oven Room '' IN ZONE '' C1-27 Oven Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 12 0.232 - 116 - 63

Hourly Analysis Program v4.80 Page 41 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' C1K1-30 Regeneration Ar '' IN ZONE '' C1-30 Regeneration Area ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 75 m² 703 - 75 m² 380 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 75 m² 302 - 75 m² 450 -
Partitions 96 m² 1215 - 96 m² 1816 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 763 W 763 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 15 1297 2000 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 18855 0 - 0 0
Safety Factor 10% / 10% 2314 200 10% 265 0
>> Total Zone Loads - 25449 2199 - 2911 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' C1K1-30 Regeneration Ar '' IN ZONE '' C1-30 Regeneration Area ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 75 0.232 - 703 - 380

Hourly Analysis Program v4.80 Page 42 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' C1K1-32 Service Station '' IN ZONE '' C1-32 Service Station ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 21 m² 198 - 21 m² 106 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 294 W 294 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3939 0 - 0 0
Safety Factor 10% / 10% 486 67 10% 11 0
>> Total Zone Loads - 5350 733 - 117 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' C1K1-32 Service Station '' IN ZONE '' C1-32 Service Station ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 21 0.232 - 198 - 106

Hourly Analysis Program v4.80 Page 43 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' C1K1-33 Central Dishwash '' IN ZONE '' C1-33 Central Dishwash ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 47 m² 441 - 47 m² 238 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 47 m² 189 - 47 m² 282 -
Partitions 71 m² 902 - 71 m² 1349 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 658 W 658 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2303 0 - 0 0
Safety Factor 10% / 10% 493 67 10% 187 0
>> Total Zone Loads - 5418 733 - 2056 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' C1K1-33 Central Dishwash '' IN ZONE '' C1-33 Central Dishwash ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 47 0.232 - 441 - 238

Hourly Analysis Program v4.80 Page 44 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' C1K1-FA 37 Banquet Servi '' IN ZONE '' C1-37 Banquet Service FA ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' C1K1-FA 37 Banquet Servi '' IN ZONE '' C1-37 Banquet Service FA ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 45 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' C1K1-FA 53 Executive Che '' IN ZONE '' C1-53 Executive Chef FA ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' C1K1-FA 53 Executive Che '' IN ZONE '' C1-53 Executive Chef FA ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 46 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' C1K1-FA 54 Executive Che '' IN ZONE '' C1-54 Executive Chef FA ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' C1K1-FA 54 Executive Che '' IN ZONE '' C1-54 Executive Chef FA ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 47 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 10.1.A. COMPONENT LOADS FOR SPACE '' C1K1-FA-34 Chef Office '' IN ZONE '' C1-34 Chef Office FA ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 10.1.B. ENVELOPE LOADS FOR SPACE '' C1K1-FA-34 Chef Office '' IN ZONE '' C1-34 Chef Office FA ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 48 of 142


Space Design Load Summary for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 11.1.A. COMPONENT LOADS FOR SPACE '' C1K1 - Refrigration Rm '' IN ZONE '' Refrigration Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 11.1.B. ENVELOPE LOADS FOR SPACE '' C1K1 - Refrigration Rm '' IN ZONE '' Refrigration Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 49 of 142


Hourly Air System Design Day Loads for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 5991 109.6 168.5 0.0 0.0 0.0 0.0 5.7 0.0
0100 27.2 5991 105.8 164.3 0.0 0.0 0.0 0.0 5.8 0.0
0200 26.6 5991 102.1 160.0 0.0 0.0 0.0 0.0 6.0 0.0
0300 26.2 5991 99.1 156.6 0.0 0.0 0.0 0.0 6.1 0.0
0400 25.8 5991 96.9 154.1 0.0 0.0 0.0 0.0 6.2 0.0
0500 25.7 5991 96.2 153.2 0.0 0.0 0.0 0.0 6.2 0.0
0600 25.9 5991 97.6 154.9 0.0 0.0 0.0 0.0 6.2 0.0
0700 26.5 5991 101.4 159.2 0.0 0.0 0.0 0.0 6.2 0.0
0800 27.5 5991 108.1 166.8 0.0 0.0 0.0 0.0 5.9 0.0
0900 29.0 5991 117.8 177.8 0.0 0.0 0.0 0.0 5.6 0.0
1000 30.7 5991 128.9 190.3 0.0 0.0 0.0 0.0 5.2 0.0
1100 32.6 5991 141.6 204.7 0.0 0.0 0.0 0.0 4.8 0.0
1200 34.4 5991 153.5 218.1 0.0 0.0 0.0 0.0 4.4 0.0
1300 35.8 5991 162.5 228.2 0.0 0.0 0.0 0.0 4.1 0.0
1400 36.7 5991 168.4 234.9 0.0 0.0 0.0 0.0 4.0 0.0
1500 37.0 5991 170.7 237.4 0.0 0.0 0.0 0.0 3.9 0.0
1600 36.7 5991 168.4 234.9 0.0 0.0 0.0 0.0 3.9 0.0
1700 35.9 5991 163.2 229.0 0.0 0.0 0.0 0.0 3.9 0.0
1800 34.6 5991 155.0 219.8 0.0 0.0 0.0 0.0 4.1 0.0
1900 33.2 5991 145.3 208.9 0.0 0.0 0.0 0.0 4.4 0.0
2000 31.7 5991 135.7 197.9 0.0 0.0 0.0 0.0 4.7 0.0
2100 30.4 5991 127.5 188.7 0.0 0.0 0.0 0.0 5.0 0.0
2200 29.3 5991 120.0 180.4 0.0 0.0 0.0 0.0 5.3 0.0
2300 28.4 5991 114.0 173.6 0.0 0.0 0.0 0.0 5.5 0.0

Hourly Analysis Program v4.80 Page 50 of 142


Hourly Zone Loads for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: C1-35 Service Station


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.0 49 170.2 1785.7 1907.5 0.0 0.0 0.0
0100 27.2 22.9 49 170.2 1760.2 1892.7 0.0 0.0 0.0
0200 26.6 22.8 50 170.2 1735.7 1878.1 0.0 0.0 0.0
0300 26.2 22.8 50 170.2 1714.8 1864.9 0.0 0.0 0.0
0400 25.8 22.7 50 170.2 1697.5 1853.1 0.0 0.0 0.0
0500 25.7 22.6 50 170.2 1687.0 1844.3 0.0 0.0 0.0
0600 25.9 22.6 50 170.2 1687.8 1840.6 0.0 0.0 0.0
0700 26.5 22.6 50 170.2 1704.1 1844.4 0.0 0.0 0.0
0800 27.5 22.7 50 170.2 1741.7 1858.4 0.0 0.0 0.0
0900 29.0 22.9 49 170.2 1799.1 1882.5 0.0 0.0 0.0
1000 30.7 23.0 48 170.2 1867.7 1913.2 0.0 0.0 0.0
1100 32.6 23.2 47 170.2 1945.0 1949.5 0.0 0.0 0.0
1200 34.4 23.4 46 170.2 2019.5 1986.3 0.0 0.0 0.0
1300 35.8 23.5 46 170.2 2064.4 2011.3 0.0 0.0 0.0
1400 36.7 23.6 45 170.2 2082.8 2024.8 0.0 0.0 0.0
1500 37.0 23.7 45 170.2 2094.2 2035.0 0.0 0.0 0.0
1600 36.7 23.7 45 170.2 2097.8 2041.5 0.0 0.0 0.0
1700 35.9 23.7 45 170.2 2093.3 2044.1 0.0 0.0 0.0
1800 34.6 23.7 46 170.2 2065.6 2035.7 0.0 0.0 0.0
1900 33.2 23.5 46 170.2 2007.6 2012.7 0.0 0.0 0.0
2000 31.7 23.4 47 170.2 1948.3 1987.3 0.0 0.0 0.0
2100 30.4 23.3 48 170.2 1897.6 1964.3 0.0 0.0 0.0
2200 29.3 23.2 48 170.2 1852.5 1942.7 0.0 0.0 0.0
2300 28.4 23.1 49 170.2 1815.4 1923.7 0.0 0.0 0.0

ZONE: C1-25 Corridor


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.1 49 770.8 5926.5 7912.8 0.0 0.0 0.0
0100 27.2 22.0 49 770.8 5654.4 7829.4 0.0 0.0 0.0
0200 26.6 21.9 50 770.8 5400.7 7746.3 0.0 0.0 0.0
0300 26.2 21.8 50 770.8 5185.3 7668.2 0.0 0.0 0.0
0400 25.8 21.8 50 770.8 5005.0 7595.2 0.0 0.0 0.0
0500 25.7 21.7 50 770.8 4884.6 7533.2 0.0 0.0 0.0
0600 25.9 21.6 50 770.8 4873.4 7493.8 0.0 0.0 0.0
0700 26.5 21.6 50 770.8 5043.0 7494.0 0.0 0.0 0.0
0800 27.5 21.7 50 770.8 5460.9 7551.5 0.0 0.0 0.0
0900 29.0 21.8 49 770.8 6098.8 7665.0 0.0 0.0 0.0
1000 30.7 22.0 48 770.8 6862.5 7818.2 0.0 0.0 0.0
1100 32.6 22.2 47 770.8 7706.5 8002.9 0.0 0.0 0.0
1200 34.4 22.5 46 770.8 8515.8 8195.7 0.0 0.0 0.0
1300 35.8 22.6 46 770.8 9042.3 8343.1 0.0 0.0 0.0
1400 36.7 22.8 45 770.8 9318.7 8444.8 0.0 0.0 0.0
1500 37.0 22.8 45 770.8 9476.5 8523.5 0.0 0.0 0.0
1600 36.7 22.9 45 770.8 9501.3 8574.6 0.0 0.0 0.0
1700 35.9 22.9 45 770.8 9388.1 8594.6 0.0 0.0 0.0
1800 34.6 22.9 46 770.8 9031.9 8559.3 0.0 0.0 0.0
1900 33.2 22.8 46 770.8 8370.7 8451.1 0.0 0.0 0.0
2000 31.7 22.6 47 770.8 7698.9 8325.7 0.0 0.0 0.0
2100 30.4 22.5 48 770.8 7132.8 8209.3 0.0 0.0 0.0
2200 29.3 22.3 48 770.8 6645.3 8099.4 0.0 0.0 0.0
2300 28.4 22.2 49 770.8 6246.8 8000.1 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 51 of 142


Hourly Zone Loads for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: C1-27 Oven Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.6 49 371.5 4394.4 4430.5 0.0 0.0 0.0
0100 27.2 23.6 49 371.5 4379.9 4418.9 0.0 0.0 0.0
0200 26.6 23.6 50 371.5 4366.2 4407.7 0.0 0.0 0.0
0300 26.2 23.6 50 371.5 4354.5 4397.6 0.0 0.0 0.0
0400 25.8 23.5 50 371.5 4344.8 4388.8 0.0 0.0 0.0
0500 25.7 23.5 50 371.5 4338.6 4382.3 0.0 0.0 0.0
0600 25.9 23.5 50 371.5 4338.4 4379.8 0.0 0.0 0.0
0700 26.5 23.5 50 371.5 4347.6 4383.6 0.0 0.0 0.0
0800 27.5 23.6 50 371.5 4369.5 4396.2 0.0 0.0 0.0
0900 29.0 23.6 49 371.5 4402.9 4417.2 0.0 0.0 0.0
1000 30.7 23.7 48 371.5 4442.9 4443.4 0.0 0.0 0.0
1100 32.6 23.7 47 371.5 4487.4 4473.7 0.0 0.0 0.0
1200 34.4 23.8 46 371.5 4530.2 4503.8 0.0 0.0 0.0
1300 35.8 23.9 46 371.5 4556.7 4524.2 0.0 0.0 0.0
1400 36.7 23.9 45 371.5 4569.6 4536.0 0.0 0.0 0.0
1500 37.0 23.9 45 371.5 4577.1 4544.2 0.0 0.0 0.0
1600 36.7 23.9 45 371.5 4578.8 4548.4 0.0 0.0 0.0
1700 35.9 23.9 45 371.5 4574.2 4548.3 0.0 0.0 0.0
1800 34.6 23.9 46 371.5 4557.1 4539.6 0.0 0.0 0.0
1900 33.2 23.9 46 371.5 4522.9 4518.9 0.0 0.0 0.0
2000 31.7 23.8 47 371.5 4488.0 4496.7 0.0 0.0 0.0
2100 30.4 23.8 48 371.5 4458.4 4477.0 0.0 0.0 0.0
2200 29.3 23.7 48 371.5 4432.5 4459.0 0.0 0.0 0.0
2300 28.4 23.7 49 371.5 4411.4 4443.6 0.0 0.0 0.0

ZONE: C1-30 Regeneration Area


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.9 49 3255.0 24213.8 24987.5 0.0 3949.9 0.0
0100 27.2 20.9 49 3255.0 24115.1 24890.0 0.0 4037.7 0.0
0200 26.6 20.9 50 3255.0 24021.1 24797.0 0.0 4121.5 0.0
0300 26.2 20.9 50 3255.0 23941.2 24717.6 0.0 4192.9 0.0
0400 25.8 20.9 50 3255.0 23874.9 24651.5 0.0 4252.4 0.0
0500 25.7 20.9 50 3255.0 23833.2 24609.3 0.0 4290.4 0.0
0600 25.9 20.9 50 3255.0 23833.8 24608.5 0.0 4291.2 0.0
0700 26.5 20.9 50 3255.0 23896.6 24668.2 0.0 4237.4 0.0
0800 27.5 20.9 50 3255.0 24044.1 24810.8 0.0 4109.0 0.0
0900 29.0 20.9 49 3255.0 24269.3 25029.5 0.0 3912.2 0.0
1000 30.7 20.9 48 3255.0 24538.7 25291.9 0.0 3676.0 0.0
1100 32.6 20.9 47 3255.0 24840.3 25586.3 0.0 3411.0 0.0
1200 34.4 20.9 46 3255.0 25130.4 25870.2 0.0 3155.5 0.0
1300 35.8 20.9 46 3255.0 25307.8 26045.0 0.0 2998.1 0.0
1400 36.7 20.9 45 3255.0 25388.5 26125.9 0.0 2925.3 0.0
1500 37.0 20.9 45 3255.0 25436.8 26175.1 0.0 2881.0 0.0
1600 36.7 20.9 45 3255.0 25449.1 26189.1 0.0 2868.4 0.0
1700 35.9 20.9 45 3255.0 25423.8 26166.3 0.0 2888.9 0.0
1800 34.6 20.9 46 3255.0 25311.5 26058.5 0.0 2985.9 0.0
1900 33.2 20.9 46 3255.0 25082.0 25836.2 0.0 3186.1 0.0
2000 31.7 20.9 47 3255.0 24847.6 25608.3 0.0 3391.1 0.0
2100 30.4 20.9 48 3255.0 24648.4 25414.0 0.0 3566.1 0.0
2200 29.3 20.9 48 3255.0 24473.1 25242.6 0.0 3720.4 0.0
2300 28.4 20.9 49 3255.0 24329.1 25101.2 0.0 3847.6 0.0

Hourly Analysis Program v4.80 Page 52 of 142


Hourly Zone Loads for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: C1-32 Service Station


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.7 49 434.0 5198.0 5218.3 0.0 0.0 0.0
0100 27.2 23.7 49 434.0 5188.6 5210.1 0.0 0.0 0.0
0200 26.6 23.7 50 434.0 5180.7 5202.8 0.0 0.0 0.0
0300 26.2 23.7 50 434.0 5174.0 5196.3 0.0 0.0 0.0
0400 25.8 23.7 50 434.0 5168.2 5190.4 0.0 0.0 0.0
0500 25.7 23.7 50 434.0 5163.2 5185.1 0.0 0.0 0.0
0600 25.9 23.6 50 434.0 5160.8 5181.6 0.0 0.0 0.0
0700 26.5 23.7 50 434.0 5166.1 5183.5 0.0 0.0 0.0
0800 27.5 23.7 50 434.0 5182.3 5193.1 0.0 0.0 0.0
0900 29.0 23.7 49 434.0 5206.9 5209.3 0.0 0.0 0.0
1000 30.7 23.7 48 434.0 5236.5 5229.7 0.0 0.0 0.0
1100 32.6 23.8 47 434.0 5267.5 5251.9 0.0 0.0 0.0
1200 34.4 23.8 46 434.0 5296.9 5273.8 0.0 0.0 0.0
1300 35.8 23.9 46 434.0 5321.8 5293.2 0.0 0.0 0.0
1400 36.7 23.9 45 434.0 5339.9 5308.4 0.0 0.0 0.0
1500 37.0 23.9 45 434.0 5349.2 5317.9 0.0 0.0 0.0
1600 36.7 23.9 45 434.0 5348.6 5320.4 0.0 0.0 0.0
1700 35.9 23.9 45 434.0 5337.9 5315.6 0.0 0.0 0.0
1800 34.6 23.9 46 434.0 5317.4 5303.6 0.0 0.0 0.0
1900 33.2 23.9 46 434.0 5290.2 5286.1 0.0 0.0 0.0
2000 31.7 23.8 47 434.0 5263.0 5267.7 0.0 0.0 0.0
2100 30.4 23.8 48 434.0 5240.8 5251.9 0.0 0.0 0.0
2200 29.3 23.8 48 434.0 5223.4 5238.8 0.0 0.0 0.0
2300 28.4 23.7 49 434.0 5209.4 5227.8 0.0 0.0 0.0

ZONE: C1-33 Central Dishwash


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.9 49 720.0 4579.2 5144.9 0.0 1238.3 0.0
0100 27.2 20.8 49 720.0 4511.3 5079.1 0.0 1298.5 0.0
0200 26.6 20.8 50 720.0 4446.2 5015.8 0.0 1356.4 0.0
0300 26.2 20.8 50 720.0 4391.0 4961.6 0.0 1406.0 0.0
0400 25.8 20.8 50 720.0 4345.2 4916.3 0.0 1447.5 0.0
0500 25.7 20.8 50 720.0 4316.8 4887.3 0.0 1474.0 0.0
0600 25.9 20.8 50 720.0 4318.1 4886.2 0.0 1475.0 0.0
0700 26.5 20.8 50 720.0 4361.5 4924.8 0.0 1439.7 0.0
0800 27.5 20.8 50 720.0 4462.3 5017.6 0.0 1354.8 0.0
0900 29.0 20.9 49 720.0 4616.1 5160.9 0.0 1223.6 0.0
1000 30.7 20.9 48 720.0 4800.2 5333.4 0.0 1065.7 0.0
1100 32.6 20.9 47 720.0 5006.9 5528.2 0.0 887.5 0.0
1200 34.4 20.9 46 720.0 5205.9 5716.8 0.0 714.9 0.0
1300 35.8 20.9 46 720.0 5325.6 5832.2 0.0 609.2 0.0
1400 36.7 20.9 45 720.0 5377.7 5884.5 0.0 561.4 0.0
1500 37.0 20.9 45 720.0 5409.4 5917.5 0.0 531.2 0.0
1600 36.7 20.9 45 720.0 5418.4 5928.9 0.0 520.7 0.0
1700 35.9 20.9 45 720.0 5403.8 5918.0 0.0 530.7 0.0
1800 34.6 20.9 46 720.0 5329.4 5850.8 0.0 592.2 0.0
1900 33.2 20.9 46 720.0 5173.3 5706.3 0.0 724.4 0.0
2000 31.7 20.9 47 720.0 5013.7 5557.3 0.0 860.8 0.0
2100 30.4 20.9 48 720.0 4877.7 5429.5 0.0 977.8 0.0
2200 29.3 20.9 48 720.0 4757.4 5315.6 0.0 1082.0 0.0
2300 28.4 20.9 49 720.0 4658.4 5221.1 0.0 1168.5 0.0

Hourly Analysis Program v4.80 Page 53 of 142


Hourly Zone Loads for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: C1-37 Banquet Service FA


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
0100 27.2 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
0200 26.6 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0300 26.2 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0400 25.8 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0500 25.7 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0600 25.9 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0700 26.5 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0800 27.5 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0900 29.0 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
1000 30.7 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
1100 32.6 20.1 47 15.0 0.0 0.0 0.0 120.7 0.0
1200 34.4 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1300 35.8 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1400 36.7 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1500 37.0 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1600 36.7 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1700 35.9 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1800 34.6 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1900 33.2 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
2000 31.7 20.1 47 15.0 0.0 0.0 0.0 120.7 0.0
2100 30.4 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
2200 29.3 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
2300 28.4 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0

ZONE: C1-53 Executive Chef FA


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
0100 27.2 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
0200 26.6 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0300 26.2 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0400 25.8 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0500 25.7 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0600 25.9 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0700 26.5 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0800 27.5 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0900 29.0 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
1000 30.7 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
1100 32.6 20.1 47 15.0 0.0 0.0 0.0 120.7 0.0
1200 34.4 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1300 35.8 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1400 36.7 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1500 37.0 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1600 36.7 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1700 35.9 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1800 34.6 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1900 33.2 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
2000 31.7 20.1 47 15.0 0.0 0.0 0.0 120.7 0.0
2100 30.4 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
2200 29.3 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
2300 28.4 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0

Hourly Analysis Program v4.80 Page 54 of 142


Hourly Zone Loads for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: C1-54 Executive Chef FA


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
0100 27.2 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
0200 26.6 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0300 26.2 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0400 25.8 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0500 25.7 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0600 25.9 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0700 26.5 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0800 27.5 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0900 29.0 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
1000 30.7 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
1100 32.6 20.1 47 15.0 0.0 0.0 0.0 120.7 0.0
1200 34.4 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1300 35.8 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1400 36.7 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1500 37.0 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1600 36.7 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1700 35.9 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1800 34.6 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1900 33.2 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
2000 31.7 20.1 47 15.0 0.0 0.0 0.0 120.7 0.0
2100 30.4 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
2200 29.3 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
2300 28.4 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0

ZONE: C1-34 Chef Office FA


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
0100 27.2 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
0200 26.6 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0300 26.2 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0400 25.8 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0500 25.7 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0600 25.9 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0700 26.5 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0800 27.5 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
0900 29.0 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
1000 30.7 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
1100 32.6 20.1 47 15.0 0.0 0.0 0.0 120.7 0.0
1200 34.4 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1300 35.8 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1400 36.7 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1500 37.0 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1600 36.7 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1700 35.9 20.1 45 15.0 0.0 0.0 0.0 120.7 0.0
1800 34.6 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
1900 33.2 20.1 46 15.0 0.0 0.0 0.0 120.7 0.0
2000 31.7 20.1 47 15.0 0.0 0.0 0.0 120.7 0.0
2100 30.4 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
2200 29.3 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
2300 28.4 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0

Hourly Analysis Program v4.80 Page 55 of 142


Hourly Zone Loads for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: Refrigration Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 12.8 49 210.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 12.8 49 210.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 12.8 50 210.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 12.8 50 210.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 12.8 50 210.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 12.8 50 210.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 12.8 50 210.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 12.8 50 210.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 12.8 50 210.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 12.8 49 210.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 12.8 48 210.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 12.8 47 210.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 12.8 46 210.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 12.8 46 210.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 12.8 45 210.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 12.8 45 210.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 12.8 45 210.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 12.8 45 210.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 12.8 46 210.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 12.8 46 210.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 12.8 47 210.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 12.8 48 210.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 12.8 48 210.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 12.8 49 210.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 56 of 142


System Psychrometrics for AHU-H-C2-01- Bulk Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 5991 400 103169 60905
Vent - Return Mixing Outlet 37.0 0.01203 5991 400 - -
Preheat Coil Outlet 37.0 0.01203 5991 400 0 -
Central Cooling Coil Outlet 11.1 0.00789 5991 400 170673 66750
Supply Fan Outlet 12.8 0.00789 5991 400 11096 -
Cold Supply Duct Outlet 12.8 0.00789 5991 400 - -
Zone Air - 22.2 0.00825 5991 471 52513 5846
Zone Direct Exhaust Outlet 22.2 0.00825 3975 471 - -
Return Plenum Outlet 22.2 0.00825 2016 471 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
C1-35 Service Station 2094 Deadband 2035 23.7 170 622 0 0
C1-25 Corridor 9476 Deadband 8523 22.8 771 549 0 0
C1-27 Oven Room 4577 Deadband 4544 23.9 371 502 0 0
C1-30 Regeneration Area 25437 Heating 26175 20.9 3255 443 2881 0
C1-32 Service Station 5349 Deadband 5318 23.9 434 509 0 0
C1-33 Central Dishwash 5409 Heating 5917 20.9 720 466 531 0
C1-37 Banquet Service FA 0 Heating 0 20.1 15 400 121 0
C1-53 Executive Chef FA 0 Heating 0 20.1 15 400 121 0
C1-54 Executive Chef FA 0 Heating 0 20.1 15 400 121 0
C1-34 Chef Office FA 0 Heating 0 20.1 15 400 121 0
Refrigration Room 0 Deadband 0 12.8 210 400 0 0

Hourly Analysis Program v4.80 Page 57 of 142


Air System Sizing Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Air System Information


Air System Name AHU-H-C2-02 Prefunction Number of zones 9
Equipment Class CW AHU Floor Area 773.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 243.0 kW Load occurs at Jul 1500
Sensible coil load 174.7 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 6131 L/s Entering DB / WB 37.0 / 22.0 °C
Max block L/s at Jul 1600 6131 L/s Leaving DB / WB 11.1 / 10.0 °C
Sum of peak zone L/s 6131 L/s Coil ADP 8.2 °C
Sensible heat ratio 0.719 Bypass Factor 0.100
m²/kW 3.2 Resulting RH 48 %
W/m² 314.3 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 8.68 L/s Zone T-stat Check 9 of 9 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 91.8 kW Load occurs at Des Htg
Coil L/s at Des Htg 6131 L/s Ent. DB / Lvg DB -0.8 / 12.8 °C
Max coil L/s 6131 L/s
Water flow @ 11.0 °K drop 2.00 L/s

Supply Fan Sizing Data


Actual max L/s at Jul 1600 6131 L/s Fan motor BHP 14.31 BHP
Standard L/s 5590 L/s Fan motor kW 11.35 kW
Actual max L/(s-m²) 7.93 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 6131 L/s L/s/person 9.36 L/s/person
L/(s-m²) 7.93 L/(s-m²)

Hourly Analysis Program v4.80 Page 58 of 142


Zone Sizing Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Air System Information


Air System Name AHU-H-C2-02 Prefunction Number of zones 9
Equipment Class CW AHU Floor Area 773.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C1-43 Pre Function 1 48.3 3915 3915 Jul 1600 8.6 488.0 8.02
C1-43 Pre Function 2 19.9 1616 1616 Jul 1700 3.7 206.0 7.84
C1-50 Meeting room 0.0 60 60 Des Htg 0.0 1.0 60.00
C1-47 Prayer/F FA 0.0 105 105 Des Htg 0.0 1.0 105.00
C1-39 AV Control Room 0.0 15 15 Des Htg 0.0 1.0 15.00
C1-48 Prayer Room M FA 0.0 85 85 Des Htg 0.0 1.0 85.00
C1-45 Meeting Room 2 0.0 50 50 Des Htg 0.0 1.0 50.00
C1-44 Meeting Room 1 0.0 50 50 Des Htg 0.0 1.0 50.00
C1-85 Corridor 2.9 236 236 Jul 1700 2.6 73.0 3.23

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
C1-43 Pre Function 1 43.9 0.96 0.0 0.00 0
C1-43 Pre Function 2 18.3 0.40 0.0 0.00 0
C1-50 Meeting room 0.5 0.01 0.0 0.00 0
C1-47 Prayer/F FA 0.9 0.02 0.0 0.00 0
C1-39 AV Control Room 0.1 0.00 0.0 0.00 0
C1-48 Prayer Room M FA 0.8 0.02 0.0 0.00 0
C1-45 Meeting Room 2 0.5 0.01 0.0 0.00 0
C1-44 Meeting Room 1 0.5 0.01 0.0 0.00 0
C1-85 Corridor 4.7 0.10 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-43 Pre Function 1
C1P-43 Pre Function 1 1 48.3 Jul 1600 3915 8.6 488.0 8.02
C1-43 Pre Function 2
C1P-43 Pre Function 2 1 19.9 Jul 1700 1616 3.7 206.0 7.84
C1-50 Meeting room
C1P-FA50 Meeting Room 1 0.0 Jan 0000 60 0.0 1.0 60.00
C1-47 Prayer/F FA
C1P-FA47 Prayer/F 1 0.0 Jan 0000 105 0.0 1.0 105.00
C1-39 AV Control Room
C1P-FA39 AV Control 1 0.0 Jan 0000 15 0.0 1.0 15.00
C1-48 Prayer Room M FA
C1P-FA48 Prayer Room M 1 0.0 Jan 0000 85 0.0 1.0 85.00
C1-45 Meeting Room 2
C1P-FA45 Meeting Room 2 1 0.0 Jan 0000 50 0.0 1.0 50.00

Hourly Analysis Program v4.80 Page 59 of 142


Zone Sizing Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-44 Meeting Room 1
C1P-FA44 Meeting Room 3 1 0.0 Jan 0000 50 0.0 1.0 50.00
C1-85 Corridor
C1P-85 CRC 1 2.9 Jul 1700 236 2.6 73.0 3.23

Hourly Analysis Program v4.80 Page 60 of 142


Ventilation Sizing Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 6131 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
C1-43 Pre Function 1
C1P-43 Pre Function 1 1 488.0 450.0 3914.9 0.00 0.00 0.0 100.0 3914.9
C1-43 Pre Function 2
C1P-43 Pre Function 2 1 206.0 200.0 1615.6 0.00 0.00 0.0 100.0 1615.6
C1-50 Meeting room
C1P-FA50 Meeting Room 1 1.0 0.0 60.0 0.00 0.00 60.0 0.0 60.0
C1-47 Prayer/F FA
C1P-FA47 Prayer/F 1 1.0 0.0 105.0 0.00 0.00 105.0 0.0 105.0
C1-39 AV Control Room
C1P-FA39 AV Control 1 1.0 0.0 15.0 0.00 0.00 15.0 0.0 15.0
C1-48 Prayer Room M FA
C1P-FA48 Prayer Room M 1 1.0 0.0 85.0 0.00 0.00 85.0 0.0 85.0
C1-45 Meeting Room 2
C1P-FA45 Meeting Room 2 1 1.0 0.0 50.0 0.00 0.00 50.0 0.0 50.0
C1-44 Meeting Room 1
C1P-FA44 Meeting Room 3 1 1.0 0.0 50.0 0.00 0.00 50.0 0.0 50.0
C1-85 Corridor
C1P-85 CRC 1 73.0 5.0 235.8 0.00 0.00 0.0 100.0 235.8
Totals (incl. Space Multipliers) 6131.4 6131.4

Hourly Analysis Program v4.80 Page 61 of 142


Air System Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 488 m² 4588 - 488 m² 2473 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 767 m² 3055 - 767 m² 4602 -
Partitions 339 m² 4272 - 339 m² 6441 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 6976 W 6976 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 655 44146 23056 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 6454 2306 10% 1352 0
>> Total Zone Loads - 70989 25362 - 14867 0
Zone Conditioning - 69011 25362 - 13772 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 5886 L/s 0 - 5886 L/s 0 -
Ventilation Load 6131 L/s 91356 42947 6131 L/s 141050 0
Supply Fan Load 6131 L/s 11355 - 6131 L/s -11355 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 171722 68309 - 143467 0
Central Cooling Coil - 174658 68309 - -11355 0
Preheat Coil - 0 - - 91774 -
Terminal Reheat Coils - -2936 - - 63047 -
>> Total Conditioning - 171722 68309 - 143467 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 62 of 142


Zone Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

C1-43 Pre Function 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 488 m² 4576 - 488 m² 2473 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 488 m² 1959 - 488 m² 2928 -
Partitions 127 m² 1614 - 127 m² 2413 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4392 W 4392 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 450 30330 15840 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4387 1584 10% 781 0
>> Total Zone Loads - 48257 17424 - 8595 0

C1-43 Pre Function 2 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 206 m² 836 - 206 m² 1236 -
Partitions 112 m² 1435 - 112 m² 2128 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1854 W 1854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 200 13480 7040 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1810 704 10% 336 0
>> Total Zone Loads - 19915 7744 - 3700 0

Hourly Analysis Program v4.80 Page 63 of 142


Zone Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

C1-50 Meeting room DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

C1-47 Prayer/F FA DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

Hourly Analysis Program v4.80 Page 64 of 142


Zone Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

C1-39 AV Control Room DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

C1-48 Prayer Room M FA DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

Hourly Analysis Program v4.80 Page 65 of 142


Zone Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

C1-45 Meeting Room 2 DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

C1-44 Meeting Room 1 DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

Hourly Analysis Program v4.80 Page 66 of 142


Zone Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

C1-85 Corridor DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 73 m² 295 - 73 m² 438 -
Partitions 100 m² 1281 - 100 m² 1900 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 730 W 730 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 264 18 10% 234 0
>> Total Zone Loads - 2907 194 - 2572 0

Hourly Analysis Program v4.80 Page 67 of 142


Space Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1P-43 Pre Function 1 '' IN ZONE '' C1-43 Pre Function 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 488 m² 4576 - 488 m² 2473 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 488 m² 1959 - 488 m² 2928 -
Partitions 127 m² 1614 - 127 m² 2413 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4392 W 4392 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 450 30330 15840 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4387 1584 10% 781 0
>> Total Zone Loads - 48257 17424 - 8595 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1P-43 Pre Function 1 '' IN ZONE '' C1-43 Pre Function 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 488 0.232 - 4576 - 2473

Hourly Analysis Program v4.80 Page 68 of 142


Space Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' C1P-43 Pre Function 2 '' IN ZONE '' C1-43 Pre Function 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 206 m² 836 - 206 m² 1236 -
Partitions 112 m² 1435 - 112 m² 2128 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1854 W 1854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 200 13480 7040 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1810 704 10% 336 0
>> Total Zone Loads - 19915 7744 - 3700 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' C1P-43 Pre Function 2 '' IN ZONE '' C1-43 Pre Function 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 69 of 142


Space Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' C1P-FA50 Meeting Room '' IN ZONE '' C1-50 Meeting room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' C1P-FA50 Meeting Room '' IN ZONE '' C1-50 Meeting room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 70 of 142


Space Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' C1P-FA47 Prayer/F '' IN ZONE '' C1-47 Prayer/F FA ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' C1P-FA47 Prayer/F '' IN ZONE '' C1-47 Prayer/F FA ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 71 of 142


Space Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' C1P-FA39 AV Control '' IN ZONE '' C1-39 AV Control Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' C1P-FA39 AV Control '' IN ZONE '' C1-39 AV Control Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 72 of 142


Space Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' C1P-FA48 Prayer Room M '' IN ZONE '' C1-48 Prayer Room M FA ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' C1P-FA48 Prayer Room M '' IN ZONE '' C1-48 Prayer Room M FA ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 73 of 142


Space Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' C1P-FA45 Meeting Room 2 '' IN ZONE '' C1-45 Meeting Room 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' C1P-FA45 Meeting Room 2 '' IN ZONE '' C1-45 Meeting Room 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 74 of 142


Space Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' C1P-FA44 Meeting Room 3 '' IN ZONE '' C1-44 Meeting Room 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' C1P-FA44 Meeting Room 3 '' IN ZONE '' C1-44 Meeting Room 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 75 of 142


Space Design Load Summary for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' C1P-85 CRC '' IN ZONE '' C1-85 Corridor ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 73 m² 295 - 73 m² 438 -
Partitions 100 m² 1281 - 100 m² 1900 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 730 W 730 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 264 18 10% 234 0
>> Total Zone Loads - 2907 194 - 2572 0

TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' C1P-85 CRC '' IN ZONE '' C1-85 Corridor ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 76 of 142


Hourly Air System Design Day Loads for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 6131 112.1 172.4 0.0 0.0 0.0 0.0 2.9 0.0
0100 27.2 6131 108.3 168.1 0.0 0.0 0.0 0.0 2.9 0.0
0200 26.6 6131 104.5 163.8 0.0 0.0 0.0 0.0 2.9 0.0
0300 26.2 6131 101.5 160.3 0.0 0.0 0.0 0.0 2.9 0.0
0400 25.8 6131 99.2 157.7 0.0 0.0 0.0 0.0 2.9 0.0
0500 25.7 6131 98.4 156.8 0.0 0.0 0.0 0.0 2.9 0.0
0600 25.9 6131 99.9 158.6 0.0 0.0 0.0 0.0 2.9 0.0
0700 26.5 6131 103.7 162.9 0.0 0.0 0.0 0.0 2.9 0.0
0800 27.5 6131 110.6 170.7 0.0 0.0 0.0 0.0 2.9 0.0
0900 29.0 6131 120.5 182.0 0.0 0.0 0.0 0.0 2.9 0.0
1000 30.7 6131 132.0 194.8 0.0 0.0 0.0 0.0 2.9 0.0
1100 32.6 6131 144.9 209.4 0.0 0.0 0.0 0.0 2.9 0.0
1200 34.4 6131 157.1 223.2 0.0 0.0 0.0 0.0 2.9 0.0
1300 35.8 6131 166.3 233.5 0.0 0.0 0.0 0.0 2.9 0.0
1400 36.7 6131 172.4 240.4 0.0 0.0 0.0 0.0 2.9 0.0
1500 37.0 6131 174.7 243.0 0.0 0.0 0.0 0.0 2.9 0.0
1600 36.7 6131 172.4 240.4 0.0 0.0 0.0 0.0 2.9 0.0
1700 35.9 6131 167.0 234.4 0.0 0.0 0.0 0.0 2.9 0.0
1800 34.6 6131 158.6 224.9 0.0 0.0 0.0 0.0 2.9 0.0
1900 33.2 6131 148.7 213.7 0.0 0.0 0.0 0.0 2.9 0.0
2000 31.7 6131 138.8 202.5 0.0 0.0 0.0 0.0 2.9 0.0
2100 30.4 6131 130.4 193.1 0.0 0.0 0.0 0.0 2.9 0.0
2200 29.3 6131 122.8 184.6 0.0 0.0 0.0 0.0 2.9 0.0
2300 28.4 6131 116.7 177.6 0.0 0.0 0.0 0.0 2.9 0.0

Hourly Analysis Program v4.80 Page 77 of 142


Hourly Zone Loads for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: C1-43 Pre Function 1


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.2 51 3914.9 43104.9 44691.7 0.0 0.0 0.0
0100 27.2 23.1 51 3914.9 42733.2 44466.6 0.0 0.0 0.0
0200 26.6 23.1 52 3914.9 42395.4 44250.2 0.0 0.0 0.0
0300 26.2 23.0 52 3914.9 42108.4 44051.0 0.0 0.0 0.0
0400 25.8 23.0 52 3914.9 41866.3 43868.4 0.0 0.0 0.0
0500 25.7 22.9 52 3914.9 41693.9 43714.5 0.0 0.0 0.0
0600 25.9 22.9 52 3914.9 41659.3 43620.9 0.0 0.0 0.0
0700 26.5 22.9 52 3914.9 41885.7 43645.6 0.0 0.0 0.0
0800 27.5 23.0 52 3914.9 42472.5 43839.8 0.0 0.0 0.0
0900 29.0 23.1 51 3914.9 43368.1 44191.6 0.0 0.0 0.0
1000 30.7 23.2 50 3914.9 44441.0 44651.1 0.0 0.0 0.0
1100 32.6 23.3 49 3914.9 45611.4 45185.7 0.0 0.0 0.0
1200 34.4 23.4 49 3914.9 46729.7 45730.6 0.0 0.0 0.0
1300 35.8 23.5 48 3914.9 47526.0 46164.2 0.0 0.0 0.0
1400 36.7 23.6 48 3914.9 47983.9 46465.8 0.0 0.0 0.0
1500 37.0 23.6 48 3914.9 48236.1 46681.9 0.0 0.0 0.0
1600 36.7 23.7 48 3914.9 48257.2 46796.5 0.0 0.0 0.0
1700 35.9 23.7 48 3914.9 48038.5 46798.9 0.0 0.0 0.0
1800 34.6 23.6 48 3914.9 47461.7 46631.6 0.0 0.0 0.0
1900 33.2 23.5 49 3914.9 46517.3 46280.2 0.0 0.0 0.0
2000 31.7 23.5 49 3914.9 45562.3 45889.7 0.0 0.0 0.0
2100 30.4 23.4 50 3914.9 44764.6 45538.0 0.0 0.0 0.0
2200 29.3 23.3 50 3914.9 44092.9 45219.4 0.0 0.0 0.0
2300 28.4 23.2 51 3914.9 43546.7 44938.7 0.0 0.0 0.0

ZONE: C1-43 Pre Function 2


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.6 51 1615.6 18864.0 19221.6 0.0 0.0 0.0
0100 27.2 23.6 51 1615.6 18767.5 19167.4 0.0 0.0 0.0
0200 26.6 23.5 52 1615.6 18669.5 19110.9 0.0 0.0 0.0
0300 26.2 23.5 52 1615.6 18586.3 19058.9 0.0 0.0 0.0
0400 25.8 23.5 52 1615.6 18518.6 19012.4 0.0 0.0 0.0
0500 25.7 23.5 52 1615.6 18483.2 18978.8 0.0 0.0 0.0
0600 25.9 23.5 52 1615.6 18497.2 18966.5 0.0 0.0 0.0
0700 26.5 23.5 52 1615.6 18562.2 18977.7 0.0 0.0 0.0
0800 27.5 23.5 52 1615.6 18695.8 19021.1 0.0 0.0 0.0
0900 29.0 23.5 51 1615.6 18899.6 19099.2 0.0 0.0 0.0
1000 30.7 23.6 50 1615.6 19143.0 19200.7 0.0 0.0 0.0
1100 32.6 23.7 49 1615.6 19426.4 19326.3 0.0 0.0 0.0
1200 34.4 23.7 49 1615.6 19701.6 19456.2 0.0 0.0 0.0
1300 35.8 23.8 48 1615.6 19828.1 19530.4 0.0 0.0 0.0
1400 36.7 23.8 48 1615.6 19852.0 19562.3 0.0 0.0 0.0
1500 37.0 23.8 48 1615.6 19874.4 19591.9 0.0 0.0 0.0
1600 36.7 23.8 48 1615.6 19895.3 19620.1 0.0 0.0 0.0
1700 35.9 23.8 48 1615.6 19914.8 19647.0 0.0 0.0 0.0
1800 34.6 23.8 48 1615.6 19861.3 19642.5 0.0 0.0 0.0
1900 33.2 23.8 49 1615.6 19664.9 19574.7 0.0 0.0 0.0
2000 31.7 23.8 49 1615.6 19461.0 19495.9 0.0 0.0 0.0
2100 30.4 23.7 50 1615.6 19282.7 19421.7 0.0 0.0 0.0
2200 29.3 23.7 50 1615.6 19115.1 19347.1 0.0 0.0 0.0
2300 28.4 23.6 51 1615.6 18975.3 19279.9 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 78 of 142


Hourly Zone Loads for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: C1-50 Meeting room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 51 60.0 0.0 0.0 0.0 482.6 0.0
0100 27.2 20.1 51 60.0 0.0 0.0 0.0 482.6 0.0
0200 26.6 20.1 52 60.0 0.0 0.0 0.0 482.6 0.0
0300 26.2 20.1 52 60.0 0.0 0.0 0.0 482.6 0.0
0400 25.8 20.1 52 60.0 0.0 0.0 0.0 482.6 0.0
0500 25.7 20.1 52 60.0 0.0 0.0 0.0 482.6 0.0
0600 25.9 20.1 52 60.0 0.0 0.0 0.0 482.6 0.0
0700 26.5 20.1 52 60.0 0.0 0.0 0.0 482.6 0.0
0800 27.5 20.1 52 60.0 0.0 0.0 0.0 482.6 0.0
0900 29.0 20.1 51 60.0 0.0 0.0 0.0 482.6 0.0
1000 30.7 20.1 50 60.0 0.0 0.0 0.0 482.6 0.0
1100 32.6 20.1 49 60.0 0.0 0.0 0.0 482.6 0.0
1200 34.4 20.1 49 60.0 0.0 0.0 0.0 482.6 0.0
1300 35.8 20.1 48 60.0 0.0 0.0 0.0 482.6 0.0
1400 36.7 20.1 48 60.0 0.0 0.0 0.0 482.6 0.0
1500 37.0 20.1 48 60.0 0.0 0.0 0.0 482.6 0.0
1600 36.7 20.1 48 60.0 0.0 0.0 0.0 482.6 0.0
1700 35.9 20.1 48 60.0 0.0 0.0 0.0 482.6 0.0
1800 34.6 20.1 48 60.0 0.0 0.0 0.0 482.6 0.0
1900 33.2 20.1 49 60.0 0.0 0.0 0.0 482.6 0.0
2000 31.7 20.1 49 60.0 0.0 0.0 0.0 482.6 0.0
2100 30.4 20.1 50 60.0 0.0 0.0 0.0 482.6 0.0
2200 29.3 20.1 50 60.0 0.0 0.0 0.0 482.6 0.0
2300 28.4 20.1 51 60.0 0.0 0.0 0.0 482.6 0.0

ZONE: C1-47 Prayer/F FA


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 51 105.0 0.0 0.0 0.0 844.6 0.0
0100 27.2 20.1 51 105.0 0.0 0.0 0.0 844.6 0.0
0200 26.6 20.1 52 105.0 0.0 0.0 0.0 844.6 0.0
0300 26.2 20.1 52 105.0 0.0 0.0 0.0 844.6 0.0
0400 25.8 20.1 52 105.0 0.0 0.0 0.0 844.6 0.0
0500 25.7 20.1 52 105.0 0.0 0.0 0.0 844.6 0.0
0600 25.9 20.1 52 105.0 0.0 0.0 0.0 844.6 0.0
0700 26.5 20.1 52 105.0 0.0 0.0 0.0 844.6 0.0
0800 27.5 20.1 52 105.0 0.0 0.0 0.0 844.6 0.0
0900 29.0 20.1 51 105.0 0.0 0.0 0.0 844.6 0.0
1000 30.7 20.1 50 105.0 0.0 0.0 0.0 844.6 0.0
1100 32.6 20.1 49 105.0 0.0 0.0 0.0 844.6 0.0
1200 34.4 20.1 49 105.0 0.0 0.0 0.0 844.6 0.0
1300 35.8 20.1 48 105.0 0.0 0.0 0.0 844.6 0.0
1400 36.7 20.1 48 105.0 0.0 0.0 0.0 844.6 0.0
1500 37.0 20.1 48 105.0 0.0 0.0 0.0 844.6 0.0
1600 36.7 20.1 48 105.0 0.0 0.0 0.0 844.6 0.0
1700 35.9 20.1 48 105.0 0.0 0.0 0.0 844.6 0.0
1800 34.6 20.1 48 105.0 0.0 0.0 0.0 844.6 0.0
1900 33.2 20.1 49 105.0 0.0 0.0 0.0 844.6 0.0
2000 31.7 20.1 49 105.0 0.0 0.0 0.0 844.6 0.0
2100 30.4 20.1 50 105.0 0.0 0.0 0.0 844.6 0.0
2200 29.3 20.1 50 105.0 0.0 0.0 0.0 844.6 0.0
2300 28.4 20.1 51 105.0 0.0 0.0 0.0 844.6 0.0

Hourly Analysis Program v4.80 Page 79 of 142


Hourly Zone Loads for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: C1-39 AV Control Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 51 15.0 0.0 0.0 0.0 120.7 0.0
0100 27.2 20.1 51 15.0 0.0 0.0 0.0 120.7 0.0
0200 26.6 20.1 52 15.0 0.0 0.0 0.0 120.7 0.0
0300 26.2 20.1 52 15.0 0.0 0.0 0.0 120.7 0.0
0400 25.8 20.1 52 15.0 0.0 0.0 0.0 120.7 0.0
0500 25.7 20.1 52 15.0 0.0 0.0 0.0 120.7 0.0
0600 25.9 20.1 52 15.0 0.0 0.0 0.0 120.7 0.0
0700 26.5 20.1 52 15.0 0.0 0.0 0.0 120.7 0.0
0800 27.5 20.1 52 15.0 0.0 0.0 0.0 120.7 0.0
0900 29.0 20.1 51 15.0 0.0 0.0 0.0 120.7 0.0
1000 30.7 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
1100 32.6 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
1200 34.4 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
1300 35.8 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
1400 36.7 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
1500 37.0 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
1600 36.7 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
1700 35.9 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
1800 34.6 20.1 48 15.0 0.0 0.0 0.0 120.7 0.0
1900 33.2 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
2000 31.7 20.1 49 15.0 0.0 0.0 0.0 120.7 0.0
2100 30.4 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
2200 29.3 20.1 50 15.0 0.0 0.0 0.0 120.7 0.0
2300 28.4 20.1 51 15.0 0.0 0.0 0.0 120.7 0.0

ZONE: C1-48 Prayer Room M FA


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 51 85.0 0.0 0.0 0.0 683.7 0.0
0100 27.2 20.1 51 85.0 0.0 0.0 0.0 683.7 0.0
0200 26.6 20.1 52 85.0 0.0 0.0 0.0 683.7 0.0
0300 26.2 20.1 52 85.0 0.0 0.0 0.0 683.7 0.0
0400 25.8 20.1 52 85.0 0.0 0.0 0.0 683.7 0.0
0500 25.7 20.1 52 85.0 0.0 0.0 0.0 683.7 0.0
0600 25.9 20.1 52 85.0 0.0 0.0 0.0 683.7 0.0
0700 26.5 20.1 52 85.0 0.0 0.0 0.0 683.7 0.0
0800 27.5 20.1 52 85.0 0.0 0.0 0.0 683.7 0.0
0900 29.0 20.1 51 85.0 0.0 0.0 0.0 683.7 0.0
1000 30.7 20.1 50 85.0 0.0 0.0 0.0 683.7 0.0
1100 32.6 20.1 49 85.0 0.0 0.0 0.0 683.7 0.0
1200 34.4 20.1 49 85.0 0.0 0.0 0.0 683.7 0.0
1300 35.8 20.1 48 85.0 0.0 0.0 0.0 683.7 0.0
1400 36.7 20.1 48 85.0 0.0 0.0 0.0 683.7 0.0
1500 37.0 20.1 48 85.0 0.0 0.0 0.0 683.7 0.0
1600 36.7 20.1 48 85.0 0.0 0.0 0.0 683.7 0.0
1700 35.9 20.1 48 85.0 0.0 0.0 0.0 683.7 0.0
1800 34.6 20.1 48 85.0 0.0 0.0 0.0 683.7 0.0
1900 33.2 20.1 49 85.0 0.0 0.0 0.0 683.7 0.0
2000 31.7 20.1 49 85.0 0.0 0.0 0.0 683.7 0.0
2100 30.4 20.1 50 85.0 0.0 0.0 0.0 683.7 0.0
2200 29.3 20.1 50 85.0 0.0 0.0 0.0 683.7 0.0
2300 28.4 20.1 51 85.0 0.0 0.0 0.0 683.7 0.0

Hourly Analysis Program v4.80 Page 80 of 142


Hourly Zone Loads for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: C1-45 Meeting Room 2


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 51 50.0 0.0 0.0 0.0 402.2 0.0
0100 27.2 20.1 51 50.0 0.0 0.0 0.0 402.2 0.0
0200 26.6 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0300 26.2 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0400 25.8 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0500 25.7 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0600 25.9 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0700 26.5 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0800 27.5 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0900 29.0 20.1 51 50.0 0.0 0.0 0.0 402.2 0.0
1000 30.7 20.1 50 50.0 0.0 0.0 0.0 402.2 0.0
1100 32.6 20.1 49 50.0 0.0 0.0 0.0 402.2 0.0
1200 34.4 20.1 49 50.0 0.0 0.0 0.0 402.2 0.0
1300 35.8 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1400 36.7 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1500 37.0 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1600 36.7 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1700 35.9 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1800 34.6 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1900 33.2 20.1 49 50.0 0.0 0.0 0.0 402.2 0.0
2000 31.7 20.1 49 50.0 0.0 0.0 0.0 402.2 0.0
2100 30.4 20.1 50 50.0 0.0 0.0 0.0 402.2 0.0
2200 29.3 20.1 50 50.0 0.0 0.0 0.0 402.2 0.0
2300 28.4 20.1 51 50.0 0.0 0.0 0.0 402.2 0.0

ZONE: C1-44 Meeting Room 1


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 51 50.0 0.0 0.0 0.0 402.2 0.0
0100 27.2 20.1 51 50.0 0.0 0.0 0.0 402.2 0.0
0200 26.6 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0300 26.2 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0400 25.8 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0500 25.7 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0600 25.9 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0700 26.5 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0800 27.5 20.1 52 50.0 0.0 0.0 0.0 402.2 0.0
0900 29.0 20.1 51 50.0 0.0 0.0 0.0 402.2 0.0
1000 30.7 20.1 50 50.0 0.0 0.0 0.0 402.2 0.0
1100 32.6 20.1 49 50.0 0.0 0.0 0.0 402.2 0.0
1200 34.4 20.1 49 50.0 0.0 0.0 0.0 402.2 0.0
1300 35.8 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1400 36.7 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1500 37.0 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1600 36.7 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1700 35.9 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1800 34.6 20.1 48 50.0 0.0 0.0 0.0 402.2 0.0
1900 33.2 20.1 49 50.0 0.0 0.0 0.0 402.2 0.0
2000 31.7 20.1 49 50.0 0.0 0.0 0.0 402.2 0.0
2100 30.4 20.1 50 50.0 0.0 0.0 0.0 402.2 0.0
2200 29.3 20.1 50 50.0 0.0 0.0 0.0 402.2 0.0
2300 28.4 20.1 51 50.0 0.0 0.0 0.0 402.2 0.0

Hourly Analysis Program v4.80 Page 81 of 142


Hourly Zone Loads for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:56PM

ZONE: C1-85 Corridor


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.9 51 235.8 2168.6 2615.0 0.0 0.0 0.0
0100 27.2 22.8 51 235.8 2101.1 2595.4 0.0 0.0 0.0
0200 26.6 22.7 52 235.8 2032.5 2574.8 0.0 0.0 0.0
0300 26.2 22.6 52 235.8 1974.2 2555.5 0.0 0.0 0.0
0400 25.8 22.6 52 235.8 1926.8 2537.9 0.0 0.0 0.0
0500 25.7 22.5 52 235.8 1902.0 2524.7 0.0 0.0 0.0
0600 25.9 22.5 52 235.8 1911.8 2518.8 0.0 0.0 0.0
0700 26.5 22.5 52 235.8 1957.2 2521.2 0.0 0.0 0.0
0800 27.5 22.6 52 235.8 2050.6 2534.9 0.0 0.0 0.0
0900 29.0 22.7 51 235.8 2193.2 2560.9 0.0 0.0 0.0
1000 30.7 22.8 50 235.8 2363.5 2595.7 0.0 0.0 0.0
1100 32.6 23.0 49 235.8 2561.7 2639.3 0.0 0.0 0.0
1200 34.4 23.1 49 235.8 2754.2 2685.1 0.0 0.0 0.0
1300 35.8 23.3 48 235.8 2846.2 2712.8 0.0 0.0 0.0
1400 36.7 23.3 48 235.8 2863.0 2725.4 0.0 0.0 0.0
1500 37.0 23.3 48 235.8 2878.8 2737.2 0.0 0.0 0.0
1600 36.7 23.4 48 235.8 2893.5 2748.6 0.0 0.0 0.0
1700 35.9 23.4 48 235.8 2907.2 2759.6 0.0 0.0 0.0
1800 34.6 23.4 48 235.8 2866.3 2758.9 0.0 0.0 0.0
1900 33.2 23.3 49 235.8 2728.8 2736.8 0.0 0.0 0.0
2000 31.7 23.2 49 235.8 2586.2 2710.3 0.0 0.0 0.0
2100 30.4 23.1 50 235.8 2461.4 2685.0 0.0 0.0 0.0
2200 29.3 23.0 50 235.8 2344.0 2659.2 0.0 0.0 0.0
2300 28.4 23.0 51 235.8 2246.2 2635.6 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 82 of 142


System Psychrometrics for AHU-H-C2-02 Prefunction
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 6131 400 91356 42947
Vent - Return Mixing Outlet 37.0 0.01203 6131 400 - -
Preheat Coil Outlet 37.0 0.01203 6131 400 0 -
Central Cooling Coil Outlet 11.1 0.00789 6131 400 174658 68309
Supply Fan Outlet 12.8 0.00789 6131 400 11355 -
Cold Supply Duct Outlet 12.8 0.00789 6131 400 - -
Zone Air - 23.5 0.00943 6131 871 69011 25362
Zone Direct Exhaust Outlet 23.5 0.00943 245 871 - -
Return Plenum Outlet 23.5 0.00943 5886 871 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
C1-43 Pre Function 1 48236 Deadband 46682 23.6 3915 906 0 0
C1-43 Pre Function 2 19874 Deadband 19592 23.8 1616 945 0 0
C1-50 Meeting room 0 Heating 0 20.1 60 400 483 0
C1-47 Prayer/F FA 0 Heating 0 20.1 105 400 845 0
C1-39 AV Control Room 0 Heating 0 20.1 15 400 121 0
C1-48 Prayer Room M FA 0 Heating 0 20.1 85 400 684 0
C1-45 Meeting Room 2 0 Heating 0 20.1 50 400 402 0
C1-44 Meeting Room 1 0 Heating 0 20.1 50 400 402 0
C1-85 Corridor 2879 Deadband 2737 23.3 236 493 0 0

Hourly Analysis Program v4.80 Page 83 of 142


Air System Sizing Summary for AHU-H-C2-03 Indoor Pool
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

Air System Information


Air System Name AHU-H-C2-03 Indoor Pool Number of zones 1
Equipment Class CW AHU Floor Area 162.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 58.8 kW Load occurs at Jul 1500
Sensible coil load 47.3 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 1900 L/s Entering DB / WB 37.0 / 22.0 °C
Max block L/s at Jun 1600 1900 L/s Leaving DB / WB 14.4 / 13.1 °C
Sum of peak zone L/s 1900 L/s Coil ADP 11.9 °C
Sensible heat ratio 0.803 Bypass Factor 0.100
m²/kW 2.8 Resulting RH 56 %
W/m² 363.2 Design supply temp. 14.4 °C
Water flow @ 6.7 °K rise 2.10 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 22.6 kW Load occurs at Des Htg
Coil L/s at Des Htg 1900 L/s Ent. DB / Lvg DB -0.8 / 10.0 °C
Max coil L/s 1900 L/s
Water flow @ 11.1 °K drop 0.49 L/s

Supply Fan Sizing Data


Actual max L/s at Jun 1600 1900 L/s Fan motor BHP 0.00 BHP
Standard L/s 1732 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 11.73 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1900 L/s L/s/person 38.00 L/s/person
L/(s-m²) 11.73 L/(s-m²)

Hourly Analysis Program v4.80 Page 84 of 142


Zone Sizing Summary for AHU-H-C2-03 Indoor Pool
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

Air System Information


Air System Name AHU-H-C2-03 Indoor Pool Number of zones 1
Equipment Class CW AHU Floor Area 162.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
UL-55 Indoor Pool 26.3 1900 1900 Jun 1600 5.2 162.0 11.73

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
UL-55 Indoor Pool 29.4 0.63 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
UL-55 Indoor Pool
ULB-55 Indoor Pool 1 26.3 Jun 1600 1900 5.2 162.0 11.73

Hourly Analysis Program v4.80 Page 85 of 142


Ventilation Sizing Summary for AHU-H-C2-03 Indoor Pool
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 1900 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
UL-55 Indoor Pool
ULB-55 Indoor Pool 1 162.0 50.0 1900.1 0.00 0.00 0.0 100.0 1900.1
Totals (incl. Space Multipliers) 1900.1 1900.1

Hourly Analysis Program v4.80 Page 86 of 142


Air System Design Load Summary for AHU-H-C2-03 Indoor Pool
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 60 m² 3576 - 60 m² - -
Wall Transmission 52 m² 544 - 52 m² 505 -
Roof Transmission 162 m² 1410 - 162 m² 1009 -
Window Transmission 60 m² 952 - 60 m² 3200 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5508 W 5508 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 50 10405 15970 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2339 1597 10% 471 0
>> Total Zone Loads - 25734 17567 - 5185 0
Zone Conditioning - 25120 17567 - 4459 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1900 L/s 0 - 1900 L/s 0 -
Ventilation Load 1900 L/s 22141 -5985 1900 L/s 47569 0
Supply Fan Load 1900 L/s 0 - 1900 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 47261 11582 - 52028 0
Central Cooling Coil - 47261 11582 - 0 0
Preheat Coil - 0 - - 22585 -
Terminal Reheat Coils - 0 - - 29443 -
>> Total Conditioning - 47261 11582 - 52028 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 87 of 142


Zone Design Load Summary for AHU-H-C2-03 Indoor Pool
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

UL-55 Indoor Pool DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 26.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 60 m² 4165 - 60 m² - -
Wall Transmission 52 m² 594 - 52 m² 505 -
Roof Transmission 162 m² 1407 - 162 m² 1009 -
Window Transmission 60 m² 874 - 60 m² 3200 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5508 W 5508 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 50 10405 15970 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2395 1597 10% 471 0
>> Total Zone Loads - 26349 17567 - 5185 0

Hourly Analysis Program v4.80 Page 88 of 142


Space Design Load Summary for AHU-H-C2-03 Indoor Pool
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' ULB-55 Indoor Pool '' IN ZONE '' UL-55 Indoor Pool ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 26.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 60 m² 4165 - 60 m² - -
Wall Transmission 52 m² 594 - 52 m² 505 -
Roof Transmission 162 m² 1407 - 162 m² 1009 -
Window Transmission 60 m² 874 - 60 m² 3200 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5508 W 5508 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 50 10405 15970 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2395 1597 10% 471 0
>> Total Zone Loads - 26349 17567 - 5185 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' ULB-55 Indoor Pool '' IN ZONE '' UL-55 Indoor Pool ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 40 0.365 - 459 - 387
WINDOW 1 9 1.990 0.300 131 538 480
NW EXPOSURE
WALL 12 0.365 - 136 - 117
WINDOW 1 51 1.990 0.300 743 3627 2720
H EXPOSURE
ROOF 162 0.232 - 1407 - 1009

Hourly Analysis Program v4.80 Page 89 of 142


Hourly Air System Design Day Loads for AHU-H-C2-03 Indoor Pool
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 1900 27.9 36.4 0.0 0.0 0.0 0.0 2.3 0.0
0100 27.2 1900 26.7 35.0 0.0 0.0 0.0 0.0 2.6 0.0
0200 26.6 1900 25.5 33.6 0.0 0.0 0.0 0.0 2.9 0.0
0300 26.2 1900 24.6 32.5 0.0 0.0 0.0 0.0 3.1 0.0
0400 25.8 1900 23.9 31.7 0.0 0.0 0.0 0.0 3.3 0.0
0500 25.7 1900 23.6 31.4 0.0 0.0 0.0 0.0 3.4 0.0
0600 25.9 1900 24.1 31.9 0.0 0.0 0.0 0.0 3.4 0.0
0700 26.5 1900 25.3 33.3 0.0 0.0 0.0 0.0 3.3 0.0
0800 27.5 1900 27.4 35.8 0.0 0.0 0.0 0.0 3.0 0.0
0900 29.0 1900 30.5 39.4 0.0 0.0 0.0 0.0 2.6 0.0
1000 30.7 1900 34.0 43.5 0.0 0.0 0.0 0.0 2.2 0.0
1100 32.6 1900 38.0 48.2 0.0 0.0 0.0 0.0 1.7 0.0
1200 34.4 1900 41.8 52.5 0.0 0.0 0.0 0.0 1.2 0.0
1300 35.8 1900 44.7 55.8 0.0 0.0 0.0 0.0 0.4 0.0
1400 36.7 1900 46.6 58.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 1900 47.3 58.8 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 1900 46.6 58.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 1900 44.9 56.1 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 1900 42.3 53.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 1900 39.2 49.5 0.0 0.0 0.0 0.0 0.1 0.0
2000 31.7 1900 36.2 46.0 0.0 0.0 0.0 0.0 0.7 0.0
2100 30.4 1900 33.6 42.9 0.0 0.0 0.0 0.0 1.2 0.0
2200 29.3 1900 31.2 40.2 0.0 0.0 0.0 0.0 1.7 0.0
2300 28.4 1900 29.3 38.0 0.0 0.0 0.0 0.0 2.0 0.0

Hourly Analysis Program v4.80 Page 90 of 142


Hourly Zone Loads for AHU-H-C2-03 Indoor Pool
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

ZONE: UL-55 Indoor Pool


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 25.9 60 1900.1 21342.3 21745.2 0.0 2345.8 0.0
0100 27.2 25.9 60 1900.1 21055.4 21447.3 0.0 2624.0 0.0
0200 26.6 25.9 60 1900.1 20792.8 21173.9 0.0 2879.3 0.0
0300 26.2 25.9 61 1900.1 20559.2 20929.5 0.0 3107.5 0.0
0400 25.8 25.9 61 1900.1 20351.7 20711.3 0.0 3311.2 0.0
0500 25.7 25.9 61 1900.1 20257.0 20601.2 0.0 3414.0 0.0
0600 25.9 25.9 61 1900.1 20314.2 20636.8 0.0 3380.8 0.0
0700 26.5 25.9 60 1900.1 20476.1 20774.3 0.0 3252.3 0.0
0800 27.5 25.9 60 1900.1 20778.8 21048.0 0.0 2996.8 0.0
0900 29.0 25.9 60 1900.1 21197.0 21434.5 0.0 2636.0 0.0
1000 30.7 25.9 59 1900.1 21679.8 21885.9 0.0 2214.5 0.0
1100 32.6 25.9 59 1900.1 22222.3 22397.3 0.0 1737.0 0.0
1200 34.4 26.0 58 1900.1 22825.7 22970.0 0.0 1202.3 0.0
1300 35.8 26.0 58 1900.1 23692.6 23795.1 0.0 431.9 0.0
1400 36.7 26.2 57 1900.1 24782.0 24582.9 0.0 0.0 0.0
1500 37.0 26.4 56 1900.1 25734.1 25120.0 0.0 0.0 0.0
1600 36.7 26.6 55 1900.1 26256.6 25457.5 0.0 0.0 0.0
1700 35.9 26.5 56 1900.1 25944.9 25358.5 0.0 0.0 0.0
1800 34.6 26.1 57 1900.1 24340.4 24549.6 0.0 0.0 0.0
1900 33.2 26.0 58 1900.1 23680.5 24118.9 0.0 129.6 0.0
2000 31.7 26.0 59 1900.1 23040.7 23472.2 0.0 733.4 0.0
2100 30.4 26.0 59 1900.1 22507.4 22936.1 0.0 1234.0 0.0
2200 29.3 25.9 59 1900.1 22053.8 22476.1 0.0 1663.4 0.0
2300 28.4 25.9 60 1900.1 21669.8 22083.3 0.0 2030.2 0.0

Hourly Analysis Program v4.80 Page 91 of 142


System Psychrometrics for AHU-H-C2-03 Indoor Pool
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 1900 400 22141 -5985
Vent - Return Mixing Outlet 37.0 0.01203 1900 400 - -
Preheat Coil Outlet 37.0 0.01203 1900 400 0 -
Central Cooling Coil Outlet 14.4 0.00976 1900 400 47261 11582
Supply Fan Outlet 14.4 0.00976 1900 400 0 -
Cold Supply Duct Outlet 14.4 0.00976 1900 400 - -
Zone Air - 26.4 0.01320 1900 996 25120 17567
Return Plenum Outlet 26.4 0.01320 1900 996 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
UL-55 Indoor Pool 25734 Deadband 25120 26.4 1900 996 0 0

Hourly Analysis Program v4.80 Page 92 of 142


Air System Sizing Summary for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

Air System Information


Air System Name AHU-H-C2-04 - Laundry Number of zones 4
Equipment Class CW AHU Floor Area 254.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 53.7 kW Load occurs at Jul 1500
Sensible coil load 39.6 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 2206 L/s Entering DB / WB 30.6 / 20.6 °C
Max block L/s at Jul 1600 2439 L/s Leaving DB / WB 14.3 / 13.4 °C
Sum of peak zone L/s 2439 L/s Coil ADP 12.5 °C
Sensible heat ratio 0.738 Bypass Factor 0.100
m²/kW 4.7 Resulting RH 53 %
W/m² 211.5 Design supply temp. 16.0 °C
Water flow @ 6.7 °K rise 1.92 L/s Zone T-stat Check 4 of 4 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 0.4 kW Load occurs at Des Htg
Coil L/s at Des Htg 732 L/s Ent. DB / Lvg DB 12.4 / 12.8 °C
Max coil L/s 2439 L/s
Water flow @ 11.0 °K drop 0.01 L/s

Supply Fan Sizing Data


Actual max L/s at Jul 1600 2439 L/s Fan motor BHP 5.69 BHP
Standard L/s 2223 L/s Fan motor kW 4.52 kW
Actual max L/(s-m²) 9.60 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 900 L/s L/s/person 10.59 L/s/person
L/(s-m²) 3.54 L/(s-m²)

Hourly Analysis Program v4.80 Page 93 of 142


Zone Sizing Summary for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

Air System Information


Air System Name AHU-H-C2-04 - Laundry Number of zones 4
Equipment Class CW AHU Floor Area 254.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C1-95 Laundry Office 0.7 78 24 Jul 1600 0.1 7.0 11.20
C1-94 Laundry Area 23.5 1938 581 Jul 1600 3.8 196.0 9.89
C1-96 Uniform issuance 2.2 253 76 Jul 1600 0.6 33.0 7.67
C1-97 Clean Linen 1.5 169 51 Jul 1600 0.8 18.0 9.41

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
C1-95 Laundry Office 0.2 0.00 0.0 0.00 0
C1-94 Laundry Area 7.0 0.15 0.0 0.00 0
C1-96 Uniform issuance 1.0 0.02 0.0 0.00 0
C1-97 Clean Linen 1.0 0.02 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-95 Laundry Office
C1L-95-Laundry Office 1 0.7 Jul 1600 78 0.1 7.0 11.20
C1-94 Laundry Area
C1L-94-Laundry Area 1 23.5 Jul 1600 1938 3.8 196.0 9.89
C1-96 Uniform issuance
C1L-96 Uniform Issunace 1 2.2 Jul 1600 253 0.6 33.0 7.67
C1-97 Clean Linen
C1L-97-Clean Linen 1 1.5 Jul 1600 169 0.8 18.0 9.41

Hourly Analysis Program v4.80 Page 94 of 142


Ventilation Sizing Summary for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

1. Summary
Ventilation Sizing Method ASHRAE Std 62.1-2007
Design Condition Minimum flow (heating)
Occupant Diversity 1.000
Uncorrected Ventilation Airflow Rate 348 L/s
System Ventilation Efficiency 0.697
Design Ventilation Airflow Rate 499 L/s
Design Ventilation Airflow Rate, Corrected for Exhaust Air 900 L/s

2. Space Ventilation Analysis Table


Minimum Floor Required Time Required Air Required Uncorrected Space
Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation
Zone Name / Space Name Mult. (L/s) (m²) (L/(s-m²)) Occupancy (L/s/person) Effectiveness (L/s) (L/s) Efficiency
C1-95 Laundry Office
C1L-95-Laundry Office 1 24 7.0 0.30 2.0 2.50 0.80 9 7 1.098
C1-94 Laundry Area
C1L-94-Laundry Area 1 581 196.0 0.60 66.0 2.50 0.80 353 283 0.868
C1-96 Uniform issuance
C1L-96 Uniform Issunace 1 76 33.0 0.60 11.0 2.50 0.80 59 47 0.697
C1-97 Clean Linen
C1L-97-Clean Linen 1 51 18.0 0.60 6.0 0.00 0.80 14 11 1.210
Totals (incl. Space Multipliers) 732 348 0.697

Hourly Analysis Program v4.80 Page 95 of 142


Air System Design Load Summary for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 226 m² 2007 - 226 m² 1145 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 227 m² 529 - 227 m² 1296 -
Partitions 119 m² 1064 - 119 m² 2263 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2238 W 2238 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 605 W 605 - 0 0 -
People 85 6103 5109 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 12775 9300 - 0 0
Safety Factor 10% / 10% 2532 1441 10% 470 0
>> Total Zone Loads - 27853 15849 - 5174 0
Zone Conditioning - 27324 15849 - 4783 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1392 L/s 0 - 462 L/s 0 -
Ventilation Load 814 L/s 8185 -1761 270 L/s 6193 0
Supply Fan Load 2206 L/s 4128 - 732 L/s -1806 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 39637 14089 - 9170 0
Central Cooling Coil - 39637 14089 - 0 0
Preheat Coil - 0 - - 362 -
Terminal Reheat Coils - 0 - - 8808 -
>> Total Conditioning - 39637 14089 - 9170 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 96 of 142


Zone Design Load Summary for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

C1-95 Laundry Office DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 7 m² 66 - 7 m² 35 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 28 - 7 m² 42 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 140 W 140 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 63 12 10% 8 0
>> Total Zone Loads - 690 132 - 85 0

C1-94 Laundry Area DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 168 m² 1458 - 168 m² 851 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 196 m² 413 - 196 m² 1113 -
Partitions 77 m² 537 - 77 m² 1455 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1405 W 1405 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 66 4739 3967 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 12775 9300 - 0 0
Safety Factor 10% / 10% 2133 1327 10% 342 0
>> Total Zone Loads - 23460 14593 - 3762 0

Hourly Analysis Program v4.80 Page 97 of 142


Zone Design Load Summary for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

C1-96 Uniform issuance DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 33 m² 309 - 33 m² 167 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 6 m² 22 - 6 m² 33 -
Partitions 17 m² 216 - 17 m² 323 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 333 W 333 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 355 W 355 - 0 0 -
People 11 790 661 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 203 66 10% 52 0
>> Total Zone Loads - 2228 727 - 576 0

C1-97 Clean Linen DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 18 m² 169 - 18 m² 91 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 18 m² 72 - 18 m² 108 -
Partitions 26 m² 324 - 26 m² 485 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 360 W 360 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 136 36 10% 68 0
>> Total Zone Loads - 1492 397 - 752 0

Hourly Analysis Program v4.80 Page 98 of 142


Space Design Load Summary for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1L-95-Laundry Office '' IN ZONE '' C1-95 Laundry Office ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 7 m² 66 - 7 m² 35 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 28 - 7 m² 42 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 140 W 140 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 63 12 10% 8 0
>> Total Zone Loads - 690 132 - 85 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1L-95-Laundry Office '' IN ZONE '' C1-95 Laundry Office ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 7 0.232 - 66 - 35

Hourly Analysis Program v4.80 Page 99 of 142


Space Design Load Summary for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' C1L-94-Laundry Area '' IN ZONE '' C1-94 Laundry Area ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 168 m² 1458 - 168 m² 851 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 196 m² 413 - 196 m² 1113 -
Partitions 77 m² 537 - 77 m² 1455 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1405 W 1405 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 66 4739 3967 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 12775 9300 - 0 0
Safety Factor 10% / 10% 2133 1327 10% 342 0
>> Total Zone Loads - 23460 14593 - 3762 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' C1L-94-Laundry Area '' IN ZONE '' C1-94 Laundry Area ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 168 0.232 - 1458 - 851

Hourly Analysis Program v4.80 Page 100 of 142


Space Design Load Summary for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' C1L-96 Uniform Issunace '' IN ZONE '' C1-96 Uniform issuance ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 33 m² 309 - 33 m² 167 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 6 m² 22 - 6 m² 33 -
Partitions 17 m² 216 - 17 m² 323 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 333 W 333 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 355 W 355 - 0 0 -
People 11 790 661 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 203 66 10% 52 0
>> Total Zone Loads - 2228 727 - 576 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' C1L-96 Uniform Issunace '' IN ZONE '' C1-96 Uniform issuance ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 33 0.232 - 309 - 167

Hourly Analysis Program v4.80 Page 101 of 142


Space Design Load Summary for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' C1L-97-Clean Linen '' IN ZONE '' C1-97 Clean Linen ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 18 m² 169 - 18 m² 91 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 18 m² 72 - 18 m² 108 -
Partitions 26 m² 324 - 26 m² 485 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 360 W 360 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 136 36 10% 68 0
>> Total Zone Loads - 1492 397 - 752 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' C1L-97-Clean Linen '' IN ZONE '' C1-97 Clean Linen ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 18 0.232 - 169 - 91

Hourly Analysis Program v4.80 Page 102 of 142


Hourly Air System Design Day Loads for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 2031 28.8 42.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 2017 28.1 41.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 2003 27.4 40.6 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 1991 26.9 40.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 1981 26.5 39.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 1973 26.3 39.3 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 1971 26.4 39.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 1979 27.0 40.1 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 1999 28.1 41.3 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 2031 29.8 43.1 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 2069 31.8 45.3 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 2111 34.1 47.8 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 2152 36.4 50.2 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 2180 38.1 52.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 2196 39.2 53.2 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 2206 39.6 53.7 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 2208 39.4 53.5 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 2204 38.6 52.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 2187 37.2 51.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 2155 35.3 49.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 2122 33.5 47.1 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 2094 32.0 45.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 2069 30.6 44.1 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 2048 29.6 42.9 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 103 of 142


Hourly Zone Loads for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

ZONE: C1-95 Laundry Office


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 55 65.1 627.2 626.0 0.0 0.0 0.0
0100 27.2 24.7 55 64.7 622.9 621.8 0.0 0.0 0.0
0200 26.6 24.7 55 64.4 619.0 618.0 0.0 0.0 0.0
0300 26.2 24.7 55 64.1 615.8 614.8 0.0 0.0 0.0
0400 25.8 24.7 55 63.8 613.0 611.9 0.0 0.0 0.0
0500 25.7 24.7 56 63.6 610.9 609.7 0.0 0.0 0.0
0600 25.9 24.7 56 63.5 610.3 608.8 0.0 0.0 0.0
0700 26.5 24.7 55 63.7 612.8 610.8 0.0 0.0 0.0
0800 27.5 24.7 55 64.3 619.9 616.8 0.0 0.0 0.0
0900 29.0 24.7 55 65.1 630.7 626.1 0.0 0.0 0.0
1000 30.7 24.8 54 66.2 643.6 637.6 0.0 0.0 0.0
1100 32.6 24.8 54 67.3 657.5 650.0 0.0 0.0 0.0
1200 34.4 24.8 53 68.4 670.7 662.1 0.0 0.0 0.0
1300 35.8 24.8 53 69.2 680.4 671.1 0.0 0.0 0.0
1400 36.7 24.8 53 69.7 686.7 677.2 0.0 0.0 0.0
1500 37.0 24.8 53 70.0 690.1 680.8 0.0 0.0 0.0
1600 36.7 24.8 53 70.1 690.2 681.3 0.0 0.0 0.0
1700 35.9 24.8 53 69.9 686.8 678.9 0.0 0.0 0.0
1800 34.6 24.8 53 69.3 679.5 672.8 0.0 0.0 0.0
1900 33.2 24.8 53 68.4 668.0 662.8 0.0 0.0 0.0
2000 31.7 24.8 54 67.5 656.4 652.6 0.0 0.0 0.0
2100 30.4 24.8 54 66.7 646.8 644.0 0.0 0.0 0.0
2200 29.3 24.8 54 66.1 638.8 636.8 0.0 0.0 0.0
2300 28.4 24.7 55 65.6 632.4 630.9 0.0 0.0 0.0

ZONE: C1-94 Laundry Area


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 27.8 55 1646.3 21468.7 21325.8 0.0 0.0 0.0
0100 27.2 27.8 55 1636.3 21319.7 21182.8 0.0 0.0 0.0
0200 26.6 27.8 55 1627.0 21182.0 21049.5 0.0 0.0 0.0
0300 26.2 27.7 55 1619.0 21065.1 20934.4 0.0 0.0 0.0
0400 25.8 27.7 55 1612.1 20967.0 20836.2 0.0 0.0 0.0
0500 25.7 27.7 56 1607.2 20899.9 20765.8 0.0 0.0 0.0
0600 25.9 27.7 56 1605.9 20891.1 20747.9 0.0 0.0 0.0
0700 26.5 27.7 55 1611.0 20983.2 20821.0 0.0 0.0 0.0
0800 27.5 27.8 55 1625.0 21214.4 21020.3 0.0 0.0 0.0
0900 29.0 27.8 55 1646.7 21567.3 21331.6 0.0 0.0 0.0
1000 30.7 27.8 54 1673.0 21989.8 21709.5 0.0 0.0 0.0
1100 32.6 27.8 54 1702.1 22454.6 22129.8 0.0 0.0 0.0
1200 34.4 27.8 53 1730.2 22899.6 22537.1 0.0 0.0 0.0
1300 35.8 27.9 53 1749.3 23194.2 22814.1 0.0 0.0 0.0
1400 36.7 27.9 53 1760.3 23356.8 22974.8 0.0 0.0 0.0
1500 37.0 27.9 53 1766.9 23448.3 23071.6 0.0 0.0 0.0
1600 36.7 27.9 53 1768.6 23460.0 23096.4 0.0 0.0 0.0
1700 35.9 27.9 53 1765.1 23388.8 23045.6 0.0 0.0 0.0
1800 34.6 27.9 53 1753.4 23185.6 22874.8 0.0 0.0 0.0
1900 33.2 27.8 53 1731.3 22817.6 22553.6 0.0 0.0 0.0
2000 31.7 27.8 54 1708.5 22444.4 22222.3 0.0 0.0 0.0
2100 30.4 27.8 54 1688.9 22131.0 21939.8 0.0 0.0 0.0
2200 29.3 27.8 54 1672.0 21863.2 21695.1 0.0 0.0 0.0
2300 28.4 27.8 55 1657.9 21644.7 21492.2 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 104 of 142


Hourly Zone Loads for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

ZONE: C1-96 Uniform issuance


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 55 196.9 1881.4 1875.9 0.0 0.0 0.0
0100 27.2 24.6 55 194.7 1856.4 1852.6 0.0 0.0 0.0
0200 26.6 24.6 55 192.7 1833.7 1831.1 0.0 0.0 0.0
0300 26.2 24.6 55 191.0 1814.4 1812.3 0.0 0.0 0.0
0400 25.8 24.6 55 189.5 1798.1 1796.0 0.0 0.0 0.0
0500 25.7 24.6 56 188.3 1786.5 1783.7 0.0 0.0 0.0
0600 25.9 24.6 56 187.9 1784.2 1779.1 0.0 0.0 0.0
0700 26.5 24.6 55 188.8 1799.4 1789.4 0.0 0.0 0.0
0800 27.5 24.6 55 191.7 1838.9 1820.4 0.0 0.0 0.0
0900 29.0 24.7 55 196.3 1899.1 1869.5 0.0 0.0 0.0
1000 30.7 24.7 54 201.9 1971.3 1929.8 0.0 0.0 0.0
1100 32.6 24.7 54 208.0 2050.0 1996.6 0.0 0.0 0.0
1200 34.4 24.8 53 213.9 2125.2 2061.7 0.0 0.0 0.0
1300 35.8 24.8 53 218.2 2178.6 2109.6 0.0 0.0 0.0
1400 36.7 24.8 53 220.9 2209.5 2139.3 0.0 0.0 0.0
1500 37.0 24.8 53 222.5 2226.5 2157.4 0.0 0.0 0.0
1600 36.7 24.8 53 222.9 2227.9 2162.4 0.0 0.0 0.0
1700 35.9 24.8 53 222.1 2213.1 2153.4 0.0 0.0 0.0
1800 34.6 24.8 53 219.5 2174.5 2124.0 0.0 0.0 0.0
1900 33.2 24.8 53 214.9 2110.9 2072.9 0.0 0.0 0.0
2000 31.7 24.7 54 210.1 2046.6 2019.9 0.0 0.0 0.0
2100 30.4 24.7 54 206.0 1992.9 1974.6 0.0 0.0 0.0
2200 29.3 24.7 54 202.4 1947.8 1935.5 0.0 0.0 0.0
2300 28.4 24.7 55 199.4 1911.0 1903.0 0.0 0.0 0.0

ZONE: C1-97 Clean Linen


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 55 123.0 1180.3 1161.1 0.0 0.0 0.0
0100 27.2 24.6 55 120.8 1155.2 1138.2 0.0 0.0 0.0
0200 26.6 24.5 55 118.7 1131.2 1116.1 0.0 0.0 0.0
0300 26.2 24.5 55 116.9 1110.9 1096.9 0.0 0.0 0.0
0400 25.8 24.5 55 115.3 1094.0 1080.7 0.0 0.0 0.0
0500 25.7 24.5 56 114.3 1083.4 1069.7 0.0 0.0 0.0
0600 25.9 24.5 56 114.1 1083.8 1068.0 0.0 0.0 0.0
0700 26.5 24.5 55 115.2 1099.8 1079.5 0.0 0.0 0.0
0800 27.5 24.5 55 118.1 1137.1 1109.3 0.0 0.0 0.0
0900 29.0 24.6 55 122.5 1194.1 1156.2 0.0 0.0 0.0
1000 30.7 24.6 54 127.9 1262.3 1213.3 0.0 0.0 0.0
1100 32.6 24.7 54 133.9 1338.7 1278.3 0.0 0.0 0.0
1200 34.4 24.7 53 139.7 1412.3 1341.8 0.0 0.0 0.0
1300 35.8 24.8 53 143.3 1456.9 1381.8 0.0 0.0 0.0
1400 36.7 24.8 53 145.1 1476.6 1401.4 0.0 0.0 0.0
1500 37.0 24.8 53 146.3 1488.5 1414.2 0.0 0.0 0.0
1600 36.7 24.8 53 146.7 1491.7 1419.6 0.0 0.0 0.0
1700 35.9 24.8 53 146.5 1486.0 1417.3 0.0 0.0 0.0
1800 34.6 24.8 53 144.6 1458.1 1396.1 0.0 0.0 0.0
1900 33.2 24.7 53 140.4 1400.2 1349.2 0.0 0.0 0.0
2000 31.7 24.7 54 135.9 1341.0 1300.2 0.0 0.0 0.0
2100 30.4 24.7 54 132.0 1290.6 1257.6 0.0 0.0 0.0
2200 29.3 24.6 54 128.4 1246.1 1219.4 0.0 0.0 0.0
2300 28.4 24.6 55 125.4 1209.6 1187.4 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 105 of 142


System Psychrometrics for AHU-H-C2-04 - Laundry
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 814 400 8185 -1761
Vent - Return Mixing Outlet 30.6 0.01254 2206 790 - -
Preheat Coil Outlet 30.6 0.01254 2206 790 0 -
Central Cooling Coil Outlet 14.3 0.01016 2206 790 39637 14089
Supply Fan Outlet 16.0 0.01016 2206 790 4128 -
Cold Supply Duct Outlet 16.0 0.01016 2206 790 - -
Zone Air - 26.9 0.01284 2206 1018 27324 15849
Zone Direct Exhaust Outlet 26.9 0.01284 814 1018 - -
Return Plenum Outlet 26.9 0.01284 1392 1018 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
C1-95 Laundry Office 690 Cooling 681 24.8 70 962 0 0
C1-94 Laundry Area 23448 Cooling 23072 27.9 1767 1012 0 0
C1-96 Uniform issuance 2227 Cooling 2157 24.8 223 1080 0 0
C1-97 Clean Linen 1489 Cooling 1414 24.8 146 1032 0 0

Hourly Analysis Program v4.80 Page 106 of 142


Air System Sizing Summary for AHU-H-C2-05 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

Air System Information


Air System Name AHU-H-C2-05 Ball Room Number of zones 1
Equipment Class CW AHU Floor Area 315.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 85.8 kW Load occurs at Jul 1500
Sensible coil load 58.7 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 3593 L/s Entering DB / WB 27.6 / 19.4 °C
Max block L/s at Jul 1600 3906 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 3906 L/s Coil ADP 11.1 °C
Sensible heat ratio 0.684 Bypass Factor 0.100
m²/kW 3.7 Resulting RH 56 %
W/m² 272.3 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 3.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s at Jul 1600 3906 L/s Fan motor BHP 0.00 BHP
Standard L/s 3562 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 12.40 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 882 L/s L/s/person 2.80 L/s/person
L/(s-m²) 2.80 L/(s-m²)

Hourly Analysis Program v4.80 Page 107 of 142


Zone Sizing Summary for AHU-H-C2-05 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

Air System Information


Air System Name AHU-H-C2-05 Ball Room Number of zones 1
Equipment Class CW AHU Floor Area 315.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
GF-51 Ball Room 1 48.2 3906 882 Jul 1600 3.8 315.0 12.40

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
GF-51 Ball Room 1 11.8 0.25 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
GF-51 Ball Room 1
GFB-51 Ball Room 1 1 48.2 Jul 1600 3906 3.8 315.0 12.40

Hourly Analysis Program v4.80 Page 108 of 142


Ventilation Sizing Summary for AHU-H-C2-05 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 882 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
GF-51 Ball Room 1
GFB-51 Ball Room 1 1 315.0 315.0 3906.5 2.50 0.30 0.0 0.0 882.0
Totals (incl. Space Multipliers) 3906.5 882.0

Hourly Analysis Program v4.80 Page 109 of 142


Air System Design Load Summary for AHU-H-C2-05 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:57PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 315 m² 2961 - 315 m² 1596 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 315 m² 1258 - 315 m² 1890 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3780 W 3780 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10000 W 10000 - 0 0 -
People 315 25861 24917 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4386 2492 10% 349 0
>> Total Zone Loads - 48246 27408 - 3835 0
Zone Conditioning - 47884 27408 - 3596 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 3593 L/s 0 - 882 L/s 0 -
Ventilation Load 811 L/s 10813 -341 199 L/s 4579 0
Supply Fan Load 3593 L/s 0 - 882 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 58697 27067 - 8176 0
Central Cooling Coil - 58697 27068 - -2523 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 10699 -
>> Total Conditioning - 58697 27068 - 8176 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 110 of 142


Zone Design Load Summary for AHU-H-C2-05 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

GF-51 Ball Room 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 315 m² 2954 - 315 m² 1596 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 315 m² 1268 - 315 m² 1890 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3780 W 3780 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10000 W 10000 - 0 0 -
People 315 25861 24917 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4386 2492 10% 349 0
>> Total Zone Loads - 48249 27408 - 3835 0

Hourly Analysis Program v4.80 Page 111 of 142


Space Design Load Summary for AHU-H-C2-05 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GFB-51 Ball Room 1 '' IN ZONE '' GF-51 Ball Room 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 315 m² 2954 - 315 m² 1596 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 315 m² 1268 - 315 m² 1890 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3780 W 3780 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10000 W 10000 - 0 0 -
People 315 25861 24917 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4386 2492 10% 349 0
>> Total Zone Loads - 48249 27408 - 3835 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GFB-51 Ball Room 1 '' IN ZONE '' GF-51 Ball Room 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 315 0.232 - 2954 - 1596

Hourly Analysis Program v4.80 Page 112 of 142


Hourly Air System Design Day Loads for AHU-H-C2-05 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 3415 47.8 74.2 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 3402 47.1 73.5 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 3391 46.4 72.8 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 3380 45.9 72.3 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 3372 45.5 71.8 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 3365 45.3 71.6 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 3362 45.5 71.8 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 3369 46.0 72.4 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 3389 47.2 73.6 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 3419 48.9 75.4 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 3456 50.9 77.5 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 3496 53.2 79.9 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 3535 55.4 82.3 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 3563 57.1 84.1 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 3582 58.2 85.2 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 3593 58.7 85.8 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 3594 58.4 85.5 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 3585 57.6 84.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 3566 56.1 83.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 3533 54.3 81.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 3501 52.5 79.2 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 3473 51.0 77.6 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 3450 49.6 76.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 3431 48.6 75.1 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 113 of 142


Hourly Zone Loads for AHU-H-C2-05 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

ZONE: GF-51 Ball Room 1


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 58 3415.5 45417.6 45288.5 0.0 0.0 0.0
0100 27.2 24.8 58 3402.3 45222.1 45096.9 0.0 0.0 0.0
0200 26.6 24.8 58 3390.6 45049.2 44926.0 0.0 0.0 0.0
0300 26.2 24.8 58 3380.5 44902.3 44779.0 0.0 0.0 0.0
0400 25.8 24.8 58 3371.8 44777.3 44652.4 0.0 0.0 0.0
0500 25.7 24.8 58 3365.0 44682.4 44554.0 0.0 0.0 0.0
0600 25.9 24.8 58 3362.5 44653.8 44517.2 0.0 0.0 0.0
0700 26.5 24.8 58 3369.2 44770.2 44615.6 0.0 0.0 0.0
0800 27.5 24.8 58 3388.9 45087.8 44902.0 0.0 0.0 0.0
0900 29.0 24.8 58 3419.5 45572.5 45346.6 0.0 0.0 0.0
1000 30.7 24.8 58 3456.4 46153.5 45885.0 0.0 0.0 0.0
1100 32.6 24.9 57 3496.3 46779.0 46469.6 0.0 0.0 0.0
1200 34.4 24.9 57 3534.6 47374.6 47031.1 0.0 0.0 0.0
1300 35.8 24.9 57 3563.0 47809.6 47448.1 0.0 0.0 0.0
1400 36.7 24.9 57 3582.0 48093.6 47727.2 0.0 0.0 0.0
1500 37.0 24.9 56 3592.7 48245.7 47884.5 0.0 0.0 0.0
1600 36.7 24.9 56 3594.0 48249.2 47903.6 0.0 0.0 0.0
1700 35.9 24.9 57 3585.5 48098.6 47778.2 0.0 0.0 0.0
1800 34.6 24.9 57 3565.6 47771.5 47486.7 0.0 0.0 0.0
1900 33.2 24.9 57 3533.4 47252.2 47013.3 0.0 0.0 0.0
2000 31.7 24.9 57 3500.5 46729.6 46531.1 0.0 0.0 0.0
2100 30.4 24.8 58 3472.9 46296.8 46127.2 0.0 0.0 0.0
2200 29.3 24.8 58 3449.9 45940.3 45790.8 0.0 0.0 0.0
2300 28.4 24.8 58 3431.0 45652.1 45515.4 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 114 of 142


System Psychrometrics for AHU-H-C2-05 Ball Room
Project Name: J17006-0100D FD REV2
Prepared by: dar

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 811 400 10813 -341
Vent - Return Mixing Outlet 27.6 0.01215 3593 2453 - -
Preheat Coil Outlet 27.6 0.01215 3593 2453 0 -
Central Cooling Coil Outlet 12.8 0.00935 3593 2453 58697 27068
Supply Fan Outlet 12.8 0.00935 3593 2453 0 -
Cold Supply Duct Outlet 12.8 0.00935 3593 2453 - -
Zone Air - 24.9 0.01219 3593 3051 47884 27408
Return Plenum Outlet 24.9 0.01219 3593 3051 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
GF-51 Ball Room 1 48246 Cooling 47884 24.9 3593 3051 0 0

Hourly Analysis Program v4.80


Air System Sizing Summary for AHU-H-C2-06 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

Air System Information


Air System Name AHU-H-C2-06 Ball Room Number of zones 1
Equipment Class CW AHU Floor Area 315.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 85.7 kW Load occurs at Jul 1500
Sensible coil load 58.6 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 3588 L/s Entering DB / WB 27.6 / 19.4 °C
Max block L/s at Jul 1600 3900 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 3900 L/s Coil ADP 11.1 °C
Sensible heat ratio 0.684 Bypass Factor 0.100
m²/kW 3.7 Resulting RH 56 %
W/m² 272.0 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 3.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s at Jul 1600 3900 L/s Fan motor BHP 0.00 BHP
Standard L/s 3556 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 12.38 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 882 L/s L/s/person 2.80 L/s/person
L/(s-m²) 2.80 L/(s-m²)

Hourly Analysis Program v4.80 Page 116 of 142


Zone Sizing Summary for AHU-H-C2-06 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

Air System Information


Air System Name AHU-H-C2-06 Ball Room Number of zones 1
Equipment Class CW AHU Floor Area 315.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
GF-51 Ball Room 2 48.2 3900 882 Jul 1600 3.7 315.0 12.38

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
GF-51 Ball Room 2 11.7 0.25 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
GF-51 Ball Room 2
GFB-51 Ball Room 2 1 48.2 Jul 1600 3900 3.7 315.0 12.38

Hourly Analysis Program v4.80 Page 117 of 142


Ventilation Sizing Summary for AHU-H-C2-06 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 882 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
GF-51 Ball Room 2
GFB-51 Ball Room 2 1 315.0 315.0 3900.4 2.50 0.30 0.0 0.0 882.0
Totals (incl. Space Multipliers) 3900.4 882.0

Hourly Analysis Program v4.80 Page 118 of 142


Air System Design Load Summary for AHU-H-C2-06 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 315 m² 2961 - 315 m² 1596 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 315 m² 1191 - 315 m² 1789 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3780 W 3780 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10000 W 10000 - 0 0 -
People 315 25861 24917 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4379 2492 10% 338 0
>> Total Zone Loads - 48171 27408 - 3723 0
Zone Conditioning - 47820 27408 - 3494 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 3588 L/s 0 - 882 L/s 0 -
Ventilation Load 811 L/s 10815 -349 199 L/s 4587 0
Supply Fan Load 3588 L/s 0 - 882 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 58635 27059 - 8081 0
Central Cooling Coil - 58635 27060 - -2516 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 10597 -
>> Total Conditioning - 58635 27060 - 8081 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 119 of 142


Zone Design Load Summary for AHU-H-C2-06 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

GF-51 Ball Room 2 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 315 m² 2954 - 315 m² 1596 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 315 m² 1200 - 315 m² 1789 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3780 W 3780 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10000 W 10000 - 0 0 -
People 315 25861 24917 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4379 2492 10% 338 0
>> Total Zone Loads - 48174 27408 - 3723 0

Hourly Analysis Program v4.80 Page 120 of 142


Space Design Load Summary for AHU-H-C2-06 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GFB-51 Ball Room 2 '' IN ZONE '' GF-51 Ball Room 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 315 m² 2954 - 315 m² 1596 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 315 m² 1200 - 315 m² 1789 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3780 W 3780 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10000 W 10000 - 0 0 -
People 315 25861 24917 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4379 2492 10% 338 0
>> Total Zone Loads - 48174 27408 - 3723 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GFB-51 Ball Room 2 '' IN ZONE '' GF-51 Ball Room 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 315 0.232 - 2954 - 1596

Hourly Analysis Program v4.80 Page 121 of 142


Hourly Air System Design Day Loads for AHU-H-C2-06 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 3412 47.7 74.2 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 3400 47.0 73.5 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 3388 46.4 72.8 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 3378 45.9 72.2 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 3369 45.5 71.8 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 3363 45.3 71.6 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 3360 45.4 71.7 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 3367 46.0 72.3 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 3386 47.1 73.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 3416 48.8 75.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 3453 50.9 77.5 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 3492 53.1 79.9 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 3530 55.3 82.2 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 3558 57.0 84.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 3577 58.1 85.2 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 3588 58.6 85.7 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 3589 58.4 85.4 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 3580 57.5 84.5 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 3561 56.1 83.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 3529 54.2 81.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 3496 52.4 79.1 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 3469 50.9 77.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 3446 49.6 76.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 3428 48.5 75.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 122 of 142


Hourly Zone Loads for AHU-H-C2-06 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

ZONE: GF-51 Ball Room 2


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 58 3412.5 45373.4 45251.5 0.0 0.0 0.0
0100 27.2 24.8 58 3399.5 45180.8 45062.8 0.0 0.0 0.0
0200 26.6 24.8 58 3388.0 45010.9 44894.7 0.0 0.0 0.0
0300 26.2 24.8 58 3378.1 44866.5 44750.2 0.0 0.0 0.0
0400 25.8 24.8 58 3369.5 44743.5 44625.6 0.0 0.0 0.0
0500 25.7 24.8 58 3362.8 44649.7 44528.3 0.0 0.0 0.0
0600 25.9 24.8 58 3360.3 44620.6 44491.3 0.0 0.0 0.0
0700 26.5 24.8 58 3366.9 44735.1 44587.9 0.0 0.0 0.0
0800 27.5 24.8 58 3386.3 45048.7 44870.6 0.0 0.0 0.0
0900 29.0 24.8 58 3416.5 45527.2 45309.6 0.0 0.0 0.0
1000 30.7 24.8 58 3452.9 46100.8 45841.3 0.0 0.0 0.0
1100 32.6 24.9 57 3492.3 46717.8 46417.9 0.0 0.0 0.0
1200 34.4 24.9 57 3530.1 47305.1 46971.7 0.0 0.0 0.0
1300 35.8 24.9 57 3558.2 47736.8 47385.5 0.0 0.0 0.0
1400 36.7 24.9 57 3577.2 48020.1 47663.7 0.0 0.0 0.0
1500 37.0 24.9 56 3587.8 48171.5 47820.3 0.0 0.0 0.0
1600 36.7 24.9 56 3589.1 48174.4 47838.7 0.0 0.0 0.0
1700 35.9 24.9 57 3580.5 48023.2 47712.7 0.0 0.0 0.0
1800 34.6 24.9 57 3560.7 47697.2 47422.0 0.0 0.0 0.0
1900 33.2 24.9 57 3528.9 47183.9 46953.9 0.0 0.0 0.0
2000 31.7 24.9 57 3496.4 46667.4 46477.3 0.0 0.0 0.0
2100 30.4 24.8 58 3469.1 46239.9 46078.4 0.0 0.0 0.0
2200 29.3 24.8 58 3446.4 45888.6 45746.7 0.0 0.0 0.0
2300 28.4 24.8 58 3427.8 45604.5 45475.3 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 123 of 142


System Psychrometrics for AHU-H-C2-06 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 811 400 10815 -349
Vent - Return Mixing Outlet 27.6 0.01216 3588 2452 - -
Preheat Coil Outlet 27.6 0.01216 3588 2452 0 -
Central Cooling Coil Outlet 12.8 0.00935 3588 2452 58635 27060
Supply Fan Outlet 12.8 0.00935 3588 2452 0 -
Cold Supply Duct Outlet 12.8 0.00935 3588 2452 - -
Zone Air - 24.9 0.01219 3588 3051 47820 27408
Return Plenum Outlet 24.9 0.01219 3588 3051 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
GF-51 Ball Room 2 48171 Cooling 47820 24.9 3588 3051 0 0

Hourly Analysis Program v4.80 Page 124 of 142


Air System Sizing Summary for AHU-H-C2-07 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

Air System Information


Air System Name AHU-H-C2-07 Ball Room Number of zones 1
Equipment Class CW AHU Floor Area 315.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 87.8 kW Load occurs at Jun 1600
Sensible coil load 60.0 kW OA DB / WB 36.1 / 21.9 °C
Coil L/s at Jun 1600 3756 L/s Entering DB / WB 27.3 / 19.3 °C
Max block L/s at Jun 1700 4100 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 4100 L/s Coil ADP 11.2 °C
Sensible heat ratio 0.683 Bypass Factor 0.100
m²/kW 3.6 Resulting RH 56 %
W/m² 278.8 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 3.14 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s at Jun 1700 4100 L/s Fan motor BHP 0.00 BHP
Standard L/s 3738 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 13.02 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 882 L/s L/s/person 2.80 L/s/person
L/(s-m²) 2.80 L/(s-m²)

Hourly Analysis Program v4.80 Page 125 of 142


Zone Sizing Summary for AHU-H-C2-07 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

Air System Information


Air System Name AHU-H-C2-07 Ball Room Number of zones 1
Equipment Class CW AHU Floor Area 315.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
GF-51 Ball Room 3 50.6 4100 882 Jun 1700 5.3 315.0 13.02

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
GF-51 Ball Room 3 13.3 0.29 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
GF-51 Ball Room 3
GFB-51 Ball Room 3 1 50.6 Jun 1700 4100 5.3 315.0 13.02

Hourly Analysis Program v4.80 Page 126 of 142


Ventilation Sizing Summary for AHU-H-C2-07 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 882 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
GF-51 Ball Room 3
GFB-51 Ball Room 3 1 315.0 315.0 4100.0 2.50 0.30 0.0 0.0 882.0
Totals (incl. Space Multipliers) 4100.0 882.0

Hourly Analysis Program v4.80 Page 127 of 142


Air System Design Load Summary for AHU-H-C2-07 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 164 m² 2072 - 164 m² 1305 -
Roof Transmission 315 m² 2956 - 315 m² 1596 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 315 m² 1254 - 315 m² 1890 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3780 W 3780 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10000 W 10000 - 0 0 -
People 315 25861 24917 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4592 2492 10% 479 0
>> Total Zone Loads - 50516 27408 - 5270 0
Zone Conditioning - 50043 27408 - 4976 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 3756 L/s 0 - 882 L/s 0 -
Ventilation Load 808 L/s 9978 391 190 L/s 4362 0
Supply Fan Load 3756 L/s 0 - 882 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 60020 27799 - 9338 0
Central Cooling Coil - 60020 27800 - -2735 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 12073 -
>> Total Conditioning - 60020 27800 - 9338 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 128 of 142


Zone Design Load Summary for AHU-H-C2-07 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

GF-51 Ball Room 3 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.3 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 164 m² 2325 - 164 m² 1305 -
Roof Transmission 315 m² 2805 - 315 m² 1596 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 315 m² 1265 - 315 m² 1890 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3780 W 3780 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10000 W 10000 - 0 0 -
People 315 25861 24917 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4604 2492 10% 479 0
>> Total Zone Loads - 50639 27408 - 5270 0

Hourly Analysis Program v4.80 Page 129 of 142


Space Design Load Summary for AHU-H-C2-07 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GFB-51 Ball Room 3 '' IN ZONE '' GF-51 Ball Room 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.3 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 164 m² 2325 - 164 m² 1305 -
Roof Transmission 315 m² 2805 - 315 m² 1596 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 315 m² 1265 - 315 m² 1890 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3780 W 3780 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10000 W 10000 - 0 0 -
People 315 25861 24917 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4604 2492 10% 479 0
>> Total Zone Loads - 50639 27408 - 5270 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GFB-51 Ball Room 3 '' IN ZONE '' GF-51 Ball Room 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 164 0.365 - 2325 - 1305
H EXPOSURE
ROOF 315 0.232 - 2805 - 1596

Hourly Analysis Program v4.80 Page 130 of 142


Hourly Air System Design Day Loads for AHU-H-C2-07 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 3485 48.5 75.1 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 3465 47.8 74.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 3449 47.1 73.6 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 3434 46.5 73.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 3422 46.0 72.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 3412 45.8 72.2 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 3408 45.9 72.3 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 3417 46.5 73.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 3441 47.7 74.2 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 3478 49.4 76.1 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 3521 51.5 78.3 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 3569 53.9 80.8 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 3616 56.2 83.2 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 3654 58.0 85.1 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 3691 59.4 86.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 3726 60.3 87.6 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 3753 60.5 87.8 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 3762 59.9 87.2 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 3742 58.5 85.7 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 3682 56.2 83.3 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 3620 53.9 80.9 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 3573 52.1 79.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 3537 50.6 77.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 3508 49.4 76.1 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 131 of 142


Hourly Zone Loads for AHU-H-C2-07 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

ZONE: GF-51 Ball Room 3


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 58 3484.6 46223.0 46088.2 0.0 0.0 0.0
0100 27.2 24.8 58 3465.3 45938.6 45809.4 0.0 0.0 0.0
0200 26.6 24.8 58 3448.6 45693.5 45566.7 0.0 0.0 0.0
0300 26.2 24.8 58 3434.1 45484.7 45357.6 0.0 0.0 0.0
0400 25.8 24.8 58 3421.5 45305.5 45176.3 0.0 0.0 0.0
0500 25.7 24.8 58 3411.6 45166.4 45032.5 0.0 0.0 0.0
0600 25.9 24.8 58 3407.9 45124.8 44979.7 0.0 0.0 0.0
0700 26.5 24.8 58 3416.8 45277.1 45108.2 0.0 0.0 0.0
0800 27.5 24.8 58 3441.0 45664.7 45457.7 0.0 0.0 0.0
0900 29.0 24.8 58 3477.5 46239.8 45985.6 0.0 0.0 0.0
1000 30.7 24.8 57 3521.5 46926.4 46622.6 0.0 0.0 0.0
1100 32.6 24.8 57 3569.2 47667.5 47315.7 0.0 0.0 0.0
1200 34.4 24.8 57 3615.7 48386.7 47993.8 0.0 0.0 0.0
1300 35.8 24.9 56 3653.7 48967.9 48548.6 0.0 0.0 0.0
1400 36.7 24.9 56 3690.6 49530.0 49088.0 0.0 0.0 0.0
1500 37.0 24.9 56 3726.1 50068.5 49607.8 0.0 0.0 0.0
1600 36.7 24.9 56 3752.7 50465.8 49998.6 0.0 0.0 0.0
1700 35.9 24.9 56 3762.4 50595.2 50141.5 0.0 0.0 0.0
1800 34.6 24.9 56 3742.4 50255.6 49847.8 0.0 0.0 0.0
1900 33.2 24.9 56 3682.3 49287.6 48966.0 0.0 0.0 0.0
2000 31.7 24.8 57 3620.5 48309.0 48063.0 0.0 0.0 0.0
2100 30.4 24.8 57 3573.2 47571.1 47374.3 0.0 0.0 0.0
2200 29.3 24.8 57 3536.7 47008.1 46842.9 0.0 0.0 0.0
2300 28.4 24.8 58 3507.9 46570.9 46425.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 132 of 142


System Psychrometrics for AHU-H-C2-07 Ball Room
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 802 400 10697 -120
Vent - Return Mixing Outlet 27.5 0.01208 3726 2499 - -
Preheat Coil Outlet 27.5 0.01208 3726 2499 0 -
Central Cooling Coil Outlet 12.8 0.00935 3726 2499 60304 27290
Supply Fan Outlet 12.8 0.00935 3726 2499 0 -
Cold Supply Duct Outlet 12.8 0.00935 3726 2499 - -
Zone Air - 24.9 0.01209 3726 3074 49608 27408
Return Plenum Outlet 24.9 0.01209 3726 3074 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
GF-51 Ball Room 3 50069 Cooling 49608 24.9 3726 3074 0 0

Hourly Analysis Program v4.80 Page 133 of 142


Air System Sizing Summary for AHU-H-C2-08 GSM
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

Air System Information


Air System Name AHU-H-C2-08 GSM Number of zones 1
Equipment Class CW AHU Floor Area 9.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 33.6 kW Load occurs at Jul 1700
Sensible coil load 33.6 kW OA DB / WB 35.9 / 21.7 °C
Coil L/s at Jul 1700 2513 L/s Entering DB / WB 24.9 / 7.5 °C
Max block L/s at Jul 1700 2723 L/s Leaving DB / WB 12.8 / 1.4 °C
Sum of peak zone L/s 2723 L/s Coil ADP 11.4 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 0.3 Resulting RH 0 %
W/m² 3729.3 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 1.20 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s at Jul 1700 2723 L/s Fan motor BHP 0.00 BHP
Standard L/s 2483 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 302.57 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.80 Page 134 of 142


Zone Sizing Summary for AHU-H-C2-08 GSM
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:58PM

Air System Information


Air System Name AHU-H-C2-08 GSM Number of zones 1
Equipment Class CW AHU Floor Area 9.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C2-25 GSM Room 33.6 2723 27 Jul 1700 0.8 9.0 302.57

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C2-25 GSM Room
EL-C2-25 GSM 1 33.6 Jul 1700 2723 0.8 9.0 302.57

Hourly Analysis Program v4.80 Page 135 of 142


Ventilation Sizing Summary for AHU-H-C2-08 GSM
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
C2-25 GSM Room
EL-C2-25 GSM 1 9.0 0.0 2723.1 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 2723.1 0.0

Hourly Analysis Program v4.80 Page 136 of 142


Air System Design Load Summary for AHU-H-C2-08 GSM
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 37 - 9 m² 54 -
Partitions 37 m² 474 - 37 m² 703 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 67 W 67 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 30000 W 29999 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3058 0 10% 76 0
>> Total Zone Loads - 33633 0 - 833 0
Zone Conditioning - 33564 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2513 L/s 0 - 27 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 2513 L/s 0 - 27 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 33564 0 - 0 0
Central Cooling Coil - 33564 0 - 0 0
Preheat Coil - 0 - - 0 -
>> Total Conditioning - 33564 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 137 of 142


Zone Design Load Summary for AHU-H-C2-08 GSM
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

C2-25 GSM Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 37 - 9 m² 54 -
Partitions 37 m² 474 - 37 m² 703 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 67 W 67 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 30000 W 29999 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3058 0 10% 76 0
>> Total Zone Loads - 33633 0 - 833 0

Hourly Analysis Program v4.80 Page 138 of 142


Space Design Load Summary for AHU-H-C2-08 GSM
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' EL-C2-25 GSM '' IN ZONE '' C2-25 GSM Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 37 - 9 m² 54 -
Partitions 37 m² 474 - 37 m² 703 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 67 W 67 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 30000 W 29999 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3058 0 10% 76 0
>> Total Zone Loads - 33633 0 - 833 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' EL-C2-25 GSM '' IN ZONE '' C2-25 GSM Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 139 of 142


Hourly Air System Design Day Loads for AHU-H-C2-08 GSM
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 2496 33.3 33.3 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 2495 33.3 33.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 2493 33.3 33.3 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 2492 33.3 33.3 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 2491 33.2 33.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 2490 33.2 33.2 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 2490 33.2 33.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 2491 33.3 33.3 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 2493 33.3 33.3 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 2497 33.3 33.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 2500 33.4 33.4 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 2505 33.5 33.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 2509 33.5 33.5 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 2511 33.5 33.5 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 2512 33.5 33.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 2512 33.6 33.6 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 2512 33.6 33.6 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 2513 33.6 33.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 2512 33.5 33.5 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 2509 33.5 33.5 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 2505 33.5 33.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 2503 33.4 33.4 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 2500 33.4 33.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 2498 33.4 33.4 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 140 of 142


Hourly Zone Loads for AHU-H-C2-08 GSM
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

ZONE: C2-25 GSM Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 - 2496.1 33395.0 33326.5 0.0 0.0 0.0
0100 27.2 24.9 - 2494.6 33373.4 33304.9 0.0 0.0 0.0
0200 26.6 24.9 - 2493.1 33351.4 33283.0 0.0 0.0 0.0
0300 26.2 24.9 - 2491.8 33332.7 33264.3 0.0 0.0 0.0
0400 25.8 24.9 - 2490.7 33317.5 33249.1 0.0 0.0 0.0
0500 25.7 24.9 - 2490.2 33309.5 33241.2 0.0 0.0 0.0
0600 25.9 24.9 - 2490.4 33312.7 33244.3 0.0 0.0 0.0
0700 26.5 24.9 - 2491.4 33327.3 33258.8 0.0 0.0 0.0
0800 27.5 24.9 - 2493.5 33357.3 33288.6 0.0 0.0 0.0
0900 29.0 24.9 - 2496.6 33403.1 33334.2 0.0 0.0 0.0
1000 30.7 24.9 - 2500.4 33457.8 33388.7 0.0 0.0 0.0
1100 32.6 24.9 - 2504.8 33521.4 33452.1 0.0 0.0 0.0
1200 34.4 24.9 - 2509.1 33583.3 33513.6 0.0 0.0 0.0
1300 35.8 24.9 - 2511.1 33613.6 33543.9 0.0 0.0 0.0
1400 36.7 24.9 - 2511.5 33619.0 33549.4 0.0 0.0 0.0
1500 37.0 24.9 - 2511.9 33624.1 33554.5 0.0 0.0 0.0
1600 36.7 24.9 - 2512.2 33628.9 33559.3 0.0 0.0 0.0
1700 35.9 24.9 - 2512.5 33633.3 33563.7 0.0 0.0 0.0
1800 34.6 24.9 - 2511.6 33619.4 33549.9 0.0 0.0 0.0
1900 33.2 24.9 - 2508.5 33575.3 33506.0 0.0 0.0 0.0
2000 31.7 24.9 - 2505.4 33529.5 33460.4 0.0 0.0 0.0
2100 30.4 24.9 - 2502.6 33489.4 33420.5 0.0 0.0 0.0
2200 29.3 24.9 - 2500.0 33451.7 33383.0 0.0 0.0 0.0
2300 28.4 24.9 - 2497.8 33420.3 33351.7 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 141 of 142


System Psychrometrics for AHU-H-C2-08 GSM
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 0 400 0 0
Vent - Return Mixing Outlet 24.9 0.00000 2512 800 - -
Preheat Coil Outlet 24.9 0.00000 2512 800 0 -
Central Cooling Coil Outlet 12.8 0.00000 2512 800 33554 0
Supply Fan Outlet 12.8 0.00000 2512 800 0 -
Cold Supply Duct Outlet 12.8 0.00000 2512 800 - -
Zone Air - 24.9 0.00000 2512 800 33554 0
Return Plenum Outlet 24.9 0.00000 2512 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
C2-25 GSM Room 33624 Cooling 33554 24.9 2512 800 0 0

Hourly Analysis Program v4.80 Page 142 of 142


Air System Sizing Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

Air System Information


Air System Name AHU-H-C3-01 - Reception & Tea L Number of zones 22
Equipment Class CW AHU Floor Area 1126.2 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 148.6 kW Load occurs at Jun 1600
Sensible coil load 120.6 kW OA DB / WB 36.1 / 21.9 °C
Coil L/s at Jun 1600 6931 L/s Entering DB / WB 26.9 / 17.4 °C
Max block L/s at Jun 1600 7684 L/s Leaving DB / WB 11.1 / 10.3 °C
Sum of peak zone L/s 7848 L/s Coil ADP 9.3 °C
Sensible heat ratio 0.812 Bypass Factor 0.100
m²/kW 7.6 Resulting RH 42 %
W/m² 131.9 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 5.31 L/s Zone T-stat Check 22 of 22 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s at Jun 1600 7684 L/s Fan motor BHP 17.94 BHP
Standard L/s 7005 L/s Fan motor kW 14.23 kW
Actual max L/(s-m²) 6.82 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1439 L/s L/s/person 6.39 L/s/person
L/(s-m²) 1.28 L/(s-m²)

Hourly Analysis Program v4.80 Page 1 of 263


Zone Sizing Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

Air System Information


Air System Name AHU-H-C3-01 - Reception & Tea L Number of zones 22
Equipment Class CW AHU Floor Area 1126.2 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
GF-30 Lug 2.4 198 59 Jul 1500 1.5 26.0 7.63
GF-40 Lobby 9.7 786 236 Jul 1700 3.6 182.0 4.32
GF-34 Valet Elevator Lob 1.2 99 30 Jun 1300 0.9 6.0 16.53
GF-15 Vestibule 6.2 506 152 Sep 1500 1.6 62.0 8.16
GF-18 WC 1.6 150 150 Jul 1700 1.1 22.0 6.82
GF-16 Corridor 1.4 117 35 Sep 1600 0.6 22.0 5.30
GF-17 Pantry/WSTN 3.7 297 297 Sep 1600 1.0 34.0 8.74
GF-20 Tea Lounge/Bar 17.2 1399 630 Jun 1600 6.7 215.0 6.51
GF-21 Reception 1 8.0 653 196 Jun 1600 2.8 121.2 5.39
GF-21 Reception 2 20.2 1642 492 Jun 1600 9.5 181.0 9.07
GF-24 Guest Relation 4.2 340 102 Jun 0800 2.0 22.0 15.44
GF-25 Front Desk Manager 0.7 53 16 Jul 1700 0.1 9.0 5.93
GF-26 Guest Relation MGR 0.6 52 16 Jul 1700 0.1 8.0 6.53
GF-28 FOH Manager 0.7 53 16 Jun 1000 0.2 8.0 6.68
GF-27 Female Inspection 0.6 50 15 Jul 1700 0.0 5.0 10.06
GF-22 Viewing Room 0.7 56 17 Sep 1600 0.3 6.0 9.39
GF13/GF11 Inspect/Lobby 1.7 139 42 Sep 1600 0.5 26.0 5.34
GF-29 Vestibule 6.8 549 165 Jun 0800 3.7 49.0 11.20
GF-33 Service Lobby 2 Cr 2.6 209 63 Jul 1600 2.7 44.0 4.74
GF-39 Luggage 0.9 76 23 Jul 1700 0.5 24.0 3.17
GF-32 Lobby 2.2 174 52 Jul 1700 2.0 26.0 6.71
GF-19 WC 1.8 250 250 Jul 1700 0.7 28.0 8.93

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
GF-30 Lug 2.0 0.04 0.0 0.00 0
GF-40 Lobby 5.7 0.12 0.0 0.00 0
GF-34 Valet Elevator Lob 1.2 0.03 0.0 0.00 0
GF-15 Vestibule 3.0 0.06 0.0 0.00 0
GF-18 WC 2.5 0.05 0.0 0.00 0
GF-16 Corridor 0.9 0.02 0.0 0.00 0
GF-17 Pantry/WSTN 3.7 0.08 0.0 0.00 0
GF-20 Tea Lounge/Bar 12.4 0.27 0.0 0.00 0
GF-21 Reception 1 4.5 0.10 0.0 0.00 0
GF-21 Reception 2 14.0 0.30 0.0 0.00 0
GF-24 Guest Relation 2.9 0.06 0.0 0.00 0
GF-25 Front Desk Manager 0.2 0.00 0.0 0.00 0
GF-26 Guest Relation MGR 0.2 0.00 0.0 0.00 0
GF-28 FOH Manager 0.3 0.01 0.0 0.00 0
GF-27 Female Inspection 0.2 0.00 0.0 0.00 0

Hourly Analysis Program v4.80 Page 2 of 263


Zone Sizing Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
GF-22 Viewing Room 0.4 0.01 0.0 0.00 0
GF13/GF11 Inspect/Lobby 0.8 0.02 0.0 0.00 0
GF-29 Vestibule 5.2 0.11 0.0 0.00 0
GF-33 Service Lobby 2 Cr 3.2 0.07 0.0 0.00 0
GF-39 Luggage 0.7 0.02 0.0 0.00 0
GF-32 Lobby 2.5 0.05 0.0 0.00 0
GF-19 WC 3.0 0.06 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
GF-30 Lug
GFA-30 Lug 1 2.4 Jul 1500 198 1.5 26.0 7.63
GF-40 Lobby
GFA 40 Lobby 1 9.7 Jul 1700 786 3.6 182.0 4.32
GF-34 Valet Elevator Lob
GFA-34 Valet Elevator 1 1.2 Jun 1300 99 0.9 6.0 16.53
GF-15 Vestibule
GFA-15 Vestibule 1 6.2 Sep 1500 506 1.6 62.0 8.16
GF-18 WC
GFA-18 WC 1 1.6 Jul 1700 150 1.1 22.0 6.82
GF-16 Corridor
GFA-16 Corridor 1 1.4 Sep 1600 117 0.6 22.0 5.30
GF-17 Pantry/WSTN
GFA-17 Pantry/WSTN 1 3.7 Sep 1600 297 1.0 34.0 8.74
GF-20 Tea Lounge/Bar
GFA-20 Tea Lounge 1 17.2 Jun 1600 1399 6.7 215.0 6.51
GF-21 Reception 1
GFA-21 Reception Area 1 1 8.0 Jun 1600 653 2.8 121.2 5.39
GF-21 Reception 2
GFA-21 Reception Area 2 1 20.2 Jun 1600 1642 9.5 181.0 9.07
GF-24 Guest Relation
GFA-24 Guest Relation 1 4.2 Jun 0800 340 2.0 22.0 15.44
GF-25 Front Desk Manager
GFA-25 Front Desk M 1 0.7 Jul 1700 53 0.1 9.0 5.93
GF-26 Guest Relation MGR
GFA-26 Guest Relation M 1 0.6 Jul 1700 52 0.1 8.0 6.53
GF-28 FOH Manager
GFA-28 FOH Manager 1 0.7 Jun 1000 53 0.2 8.0 6.68
GF-27 Female Inspection
GFA-27 - Female Ins. 1 0.6 Jul 1700 50 0.0 5.0 10.06
GF-22 Viewing Room
GFA-22 Viewing Room 1 0.7 Sep 1600 56 0.3 6.0 9.39
GF13/GF11 Inspect/Lobby
GFA-13 Female inspect 1 0.6 Jul 1700 50 0.0 5.0 10.06
GFA-11 Service Lobby 1 1.1 Sep 1600 88 0.4 21.0 4.21
GF-29 Vestibule
GFA-29 Vestibule 1 6.8 Jun 0800 549 3.7 49.0 11.20
GF-33 Service Lobby 2 Cr
GFA-37 Service Lobby 2 1 2.6 Jul 1600 209 2.7 44.0 4.74
GF-39 Luggage
GFA-39 Lugg 1 0.9 Jul 1700 76 0.5 24.0 3.17
GF-32 Lobby
GFA-32 Lobby 1 2.2 Jul 1700 174 2.0 26.0 6.71

Hourly Analysis Program v4.80 Page 3 of 263


Zone Sizing Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
GF-19 WC
GFA-19 WC 1 1.8 Jul 1700 250 0.7 28.0 8.93

Hourly Analysis Program v4.80 Page 4 of 263


Ventilation Sizing Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

1. Summary
Ventilation Sizing Method ASHRAE Std 62.1-2007
Design Condition Minimum flow (heating)
Occupant Diversity 1.000
Uncorrected Ventilation Airflow Rate 916 L/s
System Ventilation Efficiency 0.636
Design Ventilation Airflow Rate 1439 L/s

2. Space Ventilation Analysis Table


Minimum Floor Required Time Required Air Required Uncorrected Space
Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation
Zone Name / Space Name Mult. (L/s) (m²) (L/(s-m²)) Occupancy (L/s/person) Effectiveness (L/s) (L/s) Efficiency
GF-30 Lug
GFA-30 Lug 1 59 26.0 0.30 1.0 2.50 0.80 13 10 1.083
GF-40 Lobby
GFA 40 Lobby 1 236 182.0 0.30 40.0 0.00 0.80 68 55 1.010
GF-34 Valet Elevator Lob
GFA-34 Valet Elevator 1 30 6.0 0.60 1.0 2.50 0.80 8 6 1.044
GF-15 Vestibule
GFA-15 Vestibule 1 152 62.0 0.30 6.0 3.80 0.80 52 41 0.959
GF-18 WC
GFA-18 WC 1 150 22.0 0.30 5.0 0.00 0.80 8 7 1.245
GF-16 Corridor
GFA-16 Corridor 1 35 22.0 0.30 3.0 0.00 0.80 8 7 1.064
GF-17 Pantry/WSTN
GFA-17 Pantry/WSTN 1 297 34.0 0.90 7.0 3.80 0.80 72 57 1.059
GF-20 Tea Lounge/Bar
GFA-20 Tea Lounge 1 630 215.0 0.30 71.0 3.80 0.80 418 334 0.636
GF-21 Reception 1
GFA-21 Reception Area 1 1 196 121.2 0.30 13.0 3.80 0.80 107 86 0.753
GF-21 Reception 2
GFA-21 Reception Area 2 1 492 181.0 0.30 38.0 3.80 0.80 248 199 0.796
GF-24 Guest Relation
GFA-24 Guest Relation 1 102 22.0 0.30 3.0 2.50 0.80 18 14 1.127
GF-25 Front Desk Manager
GFA-25 Front Desk M 1 16 9.0 0.30 2.0 2.50 0.80 10 8 0.699
GF-26 Guest Relation MGR
GFA-26 Guest Relation M 1 16 8.0 0.30 2.0 2.50 0.80 9 7 0.710
GF-28 FOH Manager
GFA-28 FOH Manager 1 16 8.0 0.30 1.0 2.50 0.80 6 5 0.918
GF-27 Female Inspection
GFA-27 - Female Ins. 1 15 5.0 0.30 2.0 2.50 0.80 8 7 0.762
GF-22 Viewing Room
GFA-22 Viewing Room 1 17 6.0 0.30 2.0 2.50 0.80 9 7 0.797
GF13/GF11 Inspect/Lobby
GFA-13 Female inspect 1 15 5.0 0.30 2.0 2.50 0.80 8 7 0.762

Hourly Analysis Program v4.80 Page 5 of 263


Ventilation Sizing Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GFA-11 Service Lobby 1 27 21.0 0.30 3.0 0.00 0.80 8 6 1.003


GF-29 Vestibule
GFA-29 Vestibule 1 165 49.0 0.30 5.0 0.00 0.80 18 15 1.188
GF-33 Service Lobby 2 Cr
GFA-37 Service Lobby 2 1 63 44.0 0.30 5.0 0.00 0.80 17 13 1.036
GF-39 Luggage
GFA-39 Lugg 1 23 24.0 0.30 1.0 2.50 0.80 12 10 0.769
GF-32 Lobby
GFA-32 Lobby 1 52 26.0 0.30 3.0 0.00 0.80 10 8 1.114
GF-19 WC
GFA-19 WC 1 250 28.0 0.30 9.0 0.00 0.80 11 8 1.258
Totals (incl. Space Multipliers) 3053 916 0.636

Hourly Analysis Program v4.80 Page 6 of 263


Air System Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 266 m² 15289 - 266 m² - -
Wall Transmission 342 m² 3581 - 342 m² 2723 -
Roof Transmission 85 m² 798 - 85 m² 431 -
Window Transmission 266 m² 5464 - 266 m² 11540 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 21 m² 84 - 21 m² 126 -
Partitions 864 m² 10864 - 864 m² 16424 -
Ceiling 1126 m² 4470 - 1126 m² 6757 -
Overhead Lighting 15018 W 15017 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11600 W 11599 - 0 0 -
People 225 17341 15325 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8451 1532 10% 3800 0
>> Total Zone Loads - 92958 16857 - 41800 0
Zone Conditioning - 89233 16857 - 39042 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 6241 L/s 0 - 2481 L/s 0 -
Ventilation Load 1298 L/s 18130 11100 572 L/s 13148 0
Supply Fan Load 6931 L/s 12975 - 3052 L/s -6522 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 120339 27957 - 45668 0
Central Cooling Coil - 120627 27967 - -17854 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - -289 - - 63522 -
>> Total Conditioning - 120339 27967 - 45668 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 7 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF-30 Lug DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 81 - 2 m² - -
Wall Transmission 23 m² 186 - 23 m² 183 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 44 - 2 m² 87 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 49 m² 617 - 49 m² 931 -
Ceiling 26 m² 103 - 26 m² 156 -
Overhead Lighting 1118 W 1118 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 222 6 10% 136 0
>> Total Zone Loads - 2444 66 - 1492 0

GF-40 Lobby DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 115 m² 1467 - 115 m² 2176 -
Ceiling 182 m² 736 - 182 m² 1092 -
Overhead Lighting 2730 W 2730 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 40 2872 2404 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 880 240 10% 327 0
>> Total Zone Loads - 9685 2644 - 3594 0

Hourly Analysis Program v4.80 Page 8 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF-34 Valet Elevator Lob DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.2 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 419 - 9 m² - -
Wall Transmission 18 m² 156 - 18 m² 139 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 167 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 160 - 13 m² 249 -
Ceiling 6 m² 23 - 6 m² 36 -
Overhead Lighting 120 W 120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 111 4 10% 81 0
>> Total Zone Loads - 1223 39 - 896 0

GF-15 Vestibule DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 21 m² 1880 - 21 m² - -
Wall Transmission 22 m² 345 - 22 m² 175 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 21 m² 412 - 21 m² 911 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 62 m² 240 - 62 m² 372 -
Overhead Lighting 1860 W 1860 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 567 36 10% 146 0
>> Total Zone Loads - 6235 397 - 1604 0

Hourly Analysis Program v4.80 Page 9 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF-18 WC DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 46 m² 589 - 46 m² 874 -
Ceiling 22 m² 89 - 22 m² 132 -
Overhead Lighting 440 W 440 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 146 18 10% 101 0
>> Total Zone Loads - 1601 194 - 1107 0

GF-16 Corridor DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 54 m² 896 - 54 m² 430 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 22 m² 86 - 22 m² 132 -
Overhead Lighting 110 W 110 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 131 18 10% 56 0
>> Total Zone Loads - 1438 198 - 618 0

Hourly Analysis Program v4.80 Page 10 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF-17 Pantry/WSTN DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 42 m² 690 - 42 m² 331 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 226 - 18 m² 346 -
Ceiling 34 m² 133 - 34 m² 204 -
Overhead Lighting 279 W 279 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 7 503 421 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 333 42 10% 88 0
>> Total Zone Loads - 3664 463 - 969 0

GF-20 Tea Lounge/Bar DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 34 m² 2418 - 34 m² - -
Wall Transmission 24 m² 303 - 24 m² 191 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 34 m² 698 - 34 m² 1475 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 165 m² 2074 - 165 m² 3135 -
Ceiling 215 m² 853 - 215 m² 1290 -
Overhead Lighting 1505 W 1505 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 71 5829 5616 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1568 562 10% 609 0
>> Total Zone Loads - 17248 6178 - 6700 0

Hourly Analysis Program v4.80 Page 11 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF-21 Reception 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 20 m² 1422 - 20 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 20 m² 411 - 20 m² 868 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 48 m² 601 - 48 m² 908 -
Ceiling 121 m² 481 - 121 m² 727 -
Overhead Lighting 1333 W 1333 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 13 1067 1028 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 732 103 10% 250 0
>> Total Zone Loads - 8047 1131 - 2753 0

GF-21 Reception 2 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 80 m² 5689 - 80 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 85 m² 798 - 85 m² 431 -
Window Transmission 80 m² 1643 - 80 m² 3471 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 194 m² 2436 - 194 m² 3682 -
Ceiling 181 m² 718 - 181 m² 1086 -
Overhead Lighting 1991 W 1991 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 38 3120 3006 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1839 301 10% 867 0
>> Total Zone Loads - 20234 3306 - 9536 0

Hourly Analysis Program v4.80 Page 12 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF-24 Guest Relation DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.0 °C / 19.3 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 36 m² 2230 - 36 m² - -
Wall Transmission 11 m² 103 - 11 m² 86 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 36 m² 254 - 36 m² 1562 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 22 m² 41 - 22 m² 132 -
Overhead Lighting 214 W 214 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 750 W 750 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 381 18 10% 178 0
>> Total Zone Loads - 4187 198 - 1958 0

GF-25 Front Desk Manager DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 9 m² 36 - 9 m² 54 -
Overhead Lighting 168 W 168 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 60 12 10% 5 0
>> Total Zone Loads - 658 132 - 59 0

Hourly Analysis Program v4.80 Page 13 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF-26 Guest Relation MGR DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 8 m² 32 - 8 m² 48 -
Overhead Lighting 160 W 160 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 59 12 10% 5 0
>> Total Zone Loads - 644 132 - 53 0

GF-28 FOH Manager DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.1 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 13 m² 135 - 13 m² 102 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 8 m² 21 - 8 m² 48 -
Overhead Lighting 121 W 121 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 60 6 10% 15 0
>> Total Zone Loads - 658 66 - 165 0

Hourly Analysis Program v4.80 Page 14 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF-27 Female Inspection DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 5 m² 20 - 5 m² 30 -
Overhead Lighting 100 W 100 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 56 12 10% 3 0
>> Total Zone Loads - 620 132 - 33 0

GF-22 Viewing Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 25 m² 332 - 25 m² 199 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 6 m² 24 - 6 m² 36 -
Overhead Lighting 132 W 132 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 63 12 10% 23 0
>> Total Zone Loads - 694 132 - 258 0

Hourly Analysis Program v4.80 Page 15 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF13/GF11 Inspect/Lobby DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 16 m² 265 - 16 m² 127 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 21 m² 83 - 21 m² 126 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 26 m² 102 - 26 m² 156 -
Overhead Lighting 415 W 415 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 5 390 358 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 155 36 10% 41 0
>> Total Zone Loads - 1710 393 - 450 0

GF-29 Vestibule DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.0 °C / 19.3 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 64 m² 3964 - 64 m² - -
Wall Transmission 33 m² 314 - 33 m² 263 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 64 m² 451 - 64 m² 2776 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 49 m² 92 - 49 m² 294 -
Overhead Lighting 490 W 490 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 615 18 10% 333 0
>> Total Zone Loads - 6763 194 - 3666 0

Hourly Analysis Program v4.80 Page 16 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF-33 Service Lobby 2 Cr DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 63 m² 511 - 63 m² 497 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 88 m² 1118 - 88 m² 1672 -
Ceiling 44 m² 177 - 44 m² 264 -
Overhead Lighting 172 W 172 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 234 30 10% 243 0
>> Total Zone Loads - 2571 331 - 2677 0

GF-39 Luggage DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 205 - 16 m² 304 -
Ceiling 24 m² 97 - 24 m² 144 -
Overhead Lighting 480 W 480 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 85 6 10% 45 0
>> Total Zone Loads - 939 66 - 493 0

Hourly Analysis Program v4.80 Page 17 of 263


Zone Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

GF-32 Lobby DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 88 m² 1127 - 88 m² 1672 -
Ceiling 26 m² 105 - 26 m² 156 -
Overhead Lighting 520 W 520 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 202 106 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 195 11 10% 183 0
>> Total Zone Loads - 2150 116 - 2011 0

GF-19 WC DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 25 m² 320 - 25 m² 475 -
Ceiling 28 m² 113 - 28 m² 168 -
Overhead Lighting 560 W 560 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 9 607 317 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 160 32 10% 64 0
>> Total Zone Loads - 1760 348 - 707 0

Hourly Analysis Program v4.80 Page 18 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GFA-30 Lug '' IN ZONE '' GF-30 Lug ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 81 - 2 m² - -
Wall Transmission 23 m² 186 - 23 m² 183 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 44 - 2 m² 87 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 49 m² 617 - 49 m² 931 -
Ceiling 26 m² 103 - 26 m² 156 -
Overhead Lighting 1118 W 1118 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 222 6 10% 136 0
>> Total Zone Loads - 2444 66 - 1492 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GFA-30 Lug '' IN ZONE '' GF-30 Lug ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 23 0.365 - 186 - 183
WINDOW 1 2 1.990 0.300 44 81 87

Hourly Analysis Program v4.80 Page 19 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' GFA 40 Lobby '' IN ZONE '' GF-40 Lobby ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 115 m² 1467 - 115 m² 2176 -
Ceiling 182 m² 736 - 182 m² 1092 -
Overhead Lighting 2730 W 2730 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 40 2872 2404 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 880 240 10% 327 0
>> Total Zone Loads - 9685 2644 - 3594 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' GFA 40 Lobby '' IN ZONE '' GF-40 Lobby ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 20 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' GFA-34 Valet Elevator '' IN ZONE '' GF-34 Valet Elevator Lob ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.2 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 419 - 9 m² - -
Wall Transmission 18 m² 156 - 18 m² 139 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 167 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 160 - 13 m² 249 -
Ceiling 6 m² 23 - 6 m² 36 -
Overhead Lighting 120 W 120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 111 4 10% 81 0
>> Total Zone Loads - 1223 39 - 896 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' GFA-34 Valet Elevator '' IN ZONE '' GF-34 Valet Elevator Lob ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 13 0.365 - 117 - 102
NE EXPOSURE
WALL 5 0.365 - 38 - 37
WINDOW 1 9 1.990 0.300 167 419 390

Hourly Analysis Program v4.80 Page 21 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' GFA-15 Vestibule '' IN ZONE '' GF-15 Vestibule ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 21 m² 1880 - 21 m² - -
Wall Transmission 22 m² 345 - 22 m² 175 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 21 m² 412 - 21 m² 911 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 62 m² 240 - 62 m² 372 -
Overhead Lighting 1860 W 1860 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 567 36 10% 146 0
>> Total Zone Loads - 6235 397 - 1604 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' GFA-15 Vestibule '' IN ZONE '' GF-15 Vestibule ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 22 0.365 - 345 - 175
WINDOW 1 21 1.990 0.300 412 1880 911

Hourly Analysis Program v4.80 Page 22 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' GFA-18 WC '' IN ZONE '' GF-18 WC ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 46 m² 589 - 46 m² 874 -
Ceiling 22 m² 89 - 22 m² 132 -
Overhead Lighting 440 W 440 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 146 18 10% 101 0
>> Total Zone Loads - 1601 194 - 1107 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' GFA-18 WC '' IN ZONE '' GF-18 WC ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 23 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' GFA-16 Corridor '' IN ZONE '' GF-16 Corridor ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 54 m² 896 - 54 m² 430 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 22 m² 86 - 22 m² 132 -
Overhead Lighting 110 W 110 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 131 18 10% 56 0
>> Total Zone Loads - 1438 198 - 618 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' GFA-16 Corridor '' IN ZONE '' GF-16 Corridor ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 54 0.365 - 896 - 430

Hourly Analysis Program v4.80 Page 24 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' GFA-17 Pantry/WSTN '' IN ZONE '' GF-17 Pantry/WSTN ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 42 m² 690 - 42 m² 331 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 226 - 18 m² 346 -
Ceiling 34 m² 133 - 34 m² 204 -
Overhead Lighting 279 W 279 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 7 503 421 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 333 42 10% 88 0
>> Total Zone Loads - 3664 463 - 969 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' GFA-17 Pantry/WSTN '' IN ZONE '' GF-17 Pantry/WSTN ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 42 0.365 - 690 - 331

Hourly Analysis Program v4.80 Page 25 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' GFA-20 Tea Lounge '' IN ZONE '' GF-20 Tea Lounge/Bar ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 34 m² 2418 - 34 m² - -
Wall Transmission 24 m² 303 - 24 m² 191 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 34 m² 698 - 34 m² 1475 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 165 m² 2074 - 165 m² 3135 -
Ceiling 215 m² 853 - 215 m² 1290 -
Overhead Lighting 1505 W 1505 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 71 5829 5616 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1568 562 10% 609 0
>> Total Zone Loads - 17248 6178 - 6700 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' GFA-20 Tea Lounge '' IN ZONE '' GF-20 Tea Lounge/Bar ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 24 0.365 - 303 - 191
WINDOW 1 34 1.990 0.300 698 2418 1475

Hourly Analysis Program v4.80 Page 26 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' GFA-21 Reception Area 1 '' IN ZONE '' GF-21 Reception 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 20 m² 1422 - 20 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 20 m² 411 - 20 m² 868 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 48 m² 601 - 48 m² 908 -
Ceiling 121 m² 481 - 121 m² 727 -
Overhead Lighting 1333 W 1333 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 13 1067 1028 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 732 103 10% 250 0
>> Total Zone Loads - 8047 1131 - 2753 0

TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' GFA-21 Reception Area 1 '' IN ZONE '' GF-21 Reception 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WINDOW 1 20 1.990 0.300 411 1422 868

Hourly Analysis Program v4.80 Page 27 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 10.1.A. COMPONENT LOADS FOR SPACE '' GFA-21 Reception Area 2 '' IN ZONE '' GF-21 Reception 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 80 m² 5689 - 80 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 85 m² 798 - 85 m² 431 -
Window Transmission 80 m² 1643 - 80 m² 3471 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 194 m² 2436 - 194 m² 3682 -
Ceiling 181 m² 718 - 181 m² 1086 -
Overhead Lighting 1991 W 1991 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 38 3120 3006 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1839 301 10% 867 0
>> Total Zone Loads - 20234 3306 - 9536 0

TABLE 10.1.B. ENVELOPE LOADS FOR SPACE '' GFA-21 Reception Area 2 '' IN ZONE '' GF-21 Reception 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WINDOW 1 80 1.990 0.300 1643 5689 3471
H EXPOSURE
ROOF 85 0.232 - 798 - 431

Hourly Analysis Program v4.80 Page 28 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 11.1.A. COMPONENT LOADS FOR SPACE '' GFA-24 Guest Relation '' IN ZONE '' GF-24 Guest Relation ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.0 °C / 19.3 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 36 m² 2230 - 36 m² - -
Wall Transmission 11 m² 103 - 11 m² 86 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 36 m² 254 - 36 m² 1562 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 22 m² 41 - 22 m² 132 -
Overhead Lighting 214 W 214 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 750 W 750 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 381 18 10% 178 0
>> Total Zone Loads - 4187 198 - 1958 0

TABLE 11.1.B. ENVELOPE LOADS FOR SPACE '' GFA-24 Guest Relation '' IN ZONE '' GF-24 Guest Relation ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 11 0.365 - 103 - 86
WINDOW 1 36 1.990 0.300 254 2230 1562

Hourly Analysis Program v4.80 Page 29 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 12.1.A. COMPONENT LOADS FOR SPACE '' GFA-25 Front Desk M '' IN ZONE '' GF-25 Front Desk Manager ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 9 m² 36 - 9 m² 54 -
Overhead Lighting 168 W 168 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 60 12 10% 5 0
>> Total Zone Loads - 658 132 - 59 0

TABLE 12.1.B. ENVELOPE LOADS FOR SPACE '' GFA-25 Front Desk M '' IN ZONE '' GF-25 Front Desk Manager ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 30 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 13.1.A. COMPONENT LOADS FOR SPACE '' GFA-26 Guest Relation M '' IN ZONE '' GF-26 Guest Relation MGR ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 8 m² 32 - 8 m² 48 -
Overhead Lighting 160 W 160 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 59 12 10% 5 0
>> Total Zone Loads - 644 132 - 53 0

TABLE 13.1.B. ENVELOPE LOADS FOR SPACE '' GFA-26 Guest Relation M '' IN ZONE '' GF-26 Guest Relation MGR ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 31 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 14.1.A. COMPONENT LOADS FOR SPACE '' GFA-28 FOH Manager '' IN ZONE '' GF-28 FOH Manager ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.1 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 13 m² 135 - 13 m² 102 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 8 m² 21 - 8 m² 48 -
Overhead Lighting 121 W 121 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 60 6 10% 15 0
>> Total Zone Loads - 658 66 - 165 0

TABLE 14.1.B. ENVELOPE LOADS FOR SPACE '' GFA-28 FOH Manager '' IN ZONE '' GF-28 FOH Manager ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 13 0.365 - 135 - 102

Hourly Analysis Program v4.80 Page 32 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 15.1.A. COMPONENT LOADS FOR SPACE '' GFA-27 - Female Ins. '' IN ZONE '' GF-27 Female Inspection ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 5 m² 20 - 5 m² 30 -
Overhead Lighting 100 W 100 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 56 12 10% 3 0
>> Total Zone Loads - 620 132 - 33 0

TABLE 15.1.B. ENVELOPE LOADS FOR SPACE '' GFA-27 - Female Ins. '' IN ZONE '' GF-27 Female Inspection ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 33 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 16.1.A. COMPONENT LOADS FOR SPACE '' GFA-22 Viewing Room '' IN ZONE '' GF-22 Viewing Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 25 m² 332 - 25 m² 199 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 6 m² 24 - 6 m² 36 -
Overhead Lighting 132 W 132 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 63 12 10% 23 0
>> Total Zone Loads - 694 132 - 258 0

TABLE 16.1.B. ENVELOPE LOADS FOR SPACE '' GFA-22 Viewing Room '' IN ZONE '' GF-22 Viewing Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 17 0.365 - 282 - 135
NE EXPOSURE
WALL 8 0.365 - 50 - 64

Hourly Analysis Program v4.80 Page 34 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 17.1.A. COMPONENT LOADS FOR SPACE '' GFA-13 Female inspect '' IN ZONE '' GF13/GF11 Inspect/Lobby ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 5 m² 20 - 5 m² 30 -
Overhead Lighting 100 W 100 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 56 12 10% 3 0
>> Total Zone Loads - 620 132 - 33 0

TABLE 17.1.B. ENVELOPE LOADS FOR SPACE '' GFA-13 Female inspect '' IN ZONE '' GF13/GF11 Inspect/Lobby ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 35 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 17.2.A. COMPONENT LOADS FOR SPACE '' GFA-11 Service Lobby '' IN ZONE '' GF13/GF11 Inspect/Lobby ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 16 m² 265 - 16 m² 127 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 21 m² 83 - 21 m² 126 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 21 m² 82 - 21 m² 126 -
Overhead Lighting 315 W 315 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 246 237 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 99 24 10% 38 0
>> Total Zone Loads - 1091 261 - 417 0

TABLE 17.2.B. ENVELOPE LOADS FOR SPACE '' GFA-11 Service Lobby '' IN ZONE '' GF13/GF11 Inspect/Lobby ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 16 0.365 - 265 - 127

Hourly Analysis Program v4.80 Page 36 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 18.1.A. COMPONENT LOADS FOR SPACE '' GFA-29 Vestibule '' IN ZONE '' GF-29 Vestibule ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.0 °C / 19.3 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 64 m² 3964 - 64 m² - -
Wall Transmission 33 m² 314 - 33 m² 263 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 64 m² 451 - 64 m² 2776 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 49 m² 92 - 49 m² 294 -
Overhead Lighting 490 W 490 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 5 337 176 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 615 18 10% 333 0
>> Total Zone Loads - 6763 194 - 3666 0

TABLE 18.1.B. ENVELOPE LOADS FOR SPACE '' GFA-29 Vestibule '' IN ZONE '' GF-29 Vestibule ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 33 0.365 - 314 - 263
WINDOW 1 64 1.990 0.300 451 3964 2776

Hourly Analysis Program v4.80 Page 37 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 19.1.A. COMPONENT LOADS FOR SPACE '' GFA-37 Service Lobby 2 '' IN ZONE '' GF-33 Service Lobby 2 Cr ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 63 m² 511 - 63 m² 497 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 88 m² 1118 - 88 m² 1672 -
Ceiling 44 m² 177 - 44 m² 264 -
Overhead Lighting 172 W 172 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 234 30 10% 243 0
>> Total Zone Loads - 2571 331 - 2677 0

TABLE 19.1.B. ENVELOPE LOADS FOR SPACE '' GFA-37 Service Lobby 2 '' IN ZONE '' GF-33 Service Lobby 2 Cr ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 48 0.365 - 385 - 382
E EXPOSURE
WALL 15 0.365 - 126 - 115

Hourly Analysis Program v4.80 Page 38 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 20.1.A. COMPONENT LOADS FOR SPACE '' GFA-39 Lugg '' IN ZONE '' GF-39 Luggage ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 205 - 16 m² 304 -
Ceiling 24 m² 97 - 24 m² 144 -
Overhead Lighting 480 W 480 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 85 6 10% 45 0
>> Total Zone Loads - 939 66 - 493 0

TABLE 20.1.B. ENVELOPE LOADS FOR SPACE '' GFA-39 Lugg '' IN ZONE '' GF-39 Luggage ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 39 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 21.1.A. COMPONENT LOADS FOR SPACE '' GFA-32 Lobby '' IN ZONE '' GF-32 Lobby ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 88 m² 1127 - 88 m² 1672 -
Ceiling 26 m² 105 - 26 m² 156 -
Overhead Lighting 520 W 520 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 202 106 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 195 11 10% 183 0
>> Total Zone Loads - 2150 116 - 2011 0

TABLE 21.1.B. ENVELOPE LOADS FOR SPACE '' GFA-32 Lobby '' IN ZONE '' GF-32 Lobby ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 40 of 263


Space Design Load Summary for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 05:59PM

TABLE 22.1.A. COMPONENT LOADS FOR SPACE '' GFA-19 WC '' IN ZONE '' GF-19 WC ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 25 m² 320 - 25 m² 475 -
Ceiling 28 m² 113 - 28 m² 168 -
Overhead Lighting 560 W 560 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 9 607 317 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 160 32 10% 64 0
>> Total Zone Loads - 1760 348 - 707 0

TABLE 22.1.B. ENVELOPE LOADS FOR SPACE '' GFA-19 WC '' IN ZONE '' GF-19 WC ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 41 of 263


Hourly Air System Design Day Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 5677 87.8 112.2 0.0 0.0 0.0 0.0 0.4 0.0
0100 27.2 5575 85.5 109.7 0.0 0.0 0.0 0.0 0.5 0.0
0200 26.6 5475 83.3 107.3 0.0 0.0 0.0 0.0 0.5 0.0
0300 26.2 5386 81.4 105.2 0.0 0.0 0.0 0.0 0.5 0.0
0400 25.8 5306 79.7 103.4 0.0 0.0 0.0 0.0 0.5 0.0
0500 25.7 5383 80.8 104.6 0.0 0.0 0.0 0.0 0.5 0.0
0600 25.9 5558 83.8 107.9 0.0 0.0 0.0 0.0 0.5 0.0
0700 26.5 5692 86.6 111.0 0.0 0.0 0.0 0.0 0.5 0.0
0800 27.5 5814 89.8 114.5 0.0 0.0 0.0 0.0 0.5 0.0
0900 29.0 5923 93.4 118.3 0.0 0.0 0.0 0.0 0.4 0.0
1000 30.7 6033 97.3 122.5 0.0 0.0 0.0 0.0 0.4 0.0
1100 32.6 6194 102.5 128.1 0.0 0.0 0.0 0.0 0.4 0.0
1200 34.4 6367 107.9 133.9 0.0 0.0 0.0 0.0 0.3 0.0
1300 35.8 6535 112.8 139.2 0.0 0.0 0.0 0.0 0.3 0.0
1400 36.7 6701 117.1 143.8 0.0 0.0 0.0 0.0 0.3 0.0
1500 37.0 6846 120.3 147.3 0.0 0.0 0.0 0.0 0.3 0.0
1600 36.7 6924 121.3 148.5 0.0 0.0 0.0 0.0 0.3 0.0
1700 35.9 6873 119.2 146.3 0.0 0.0 0.0 0.0 0.3 0.0
1800 34.6 6592 112.3 138.7 0.0 0.0 0.0 0.0 0.3 0.0
1900 33.2 6414 107.1 133.1 0.0 0.0 0.0 0.0 0.3 0.0
2000 31.7 6233 102.0 127.6 0.0 0.0 0.0 0.0 0.4 0.0
2100 30.4 6072 97.7 122.9 0.0 0.0 0.0 0.0 0.4 0.0
2200 29.3 5922 93.7 118.7 0.0 0.0 0.0 0.0 0.4 0.0
2300 28.4 5790 90.5 115.1 0.0 0.0 0.0 0.0 0.4 0.0

Hourly Analysis Program v4.80 Page 42 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF-30 Lug


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 45 146.0 1939.2 1896.1 0.0 0.0 0.0
0100 27.2 24.6 45 143.0 1893.5 1854.5 0.0 0.0 0.0
0200 26.6 24.6 45 140.1 1848.6 1813.5 0.0 0.0 0.0
0300 26.2 24.5 45 137.6 1809.9 1777.5 0.0 0.0 0.0
0400 25.8 24.5 45 135.4 1777.4 1746.7 0.0 0.0 0.0
0500 25.7 24.5 45 136.1 1794.1 1756.9 0.0 0.0 0.0
0600 25.9 24.6 45 140.7 1875.0 1821.3 0.0 0.0 0.0
0700 26.5 24.6 45 147.0 1984.1 1910.9 0.0 0.0 0.0
0800 27.5 24.7 44 153.4 2093.0 2002.0 0.0 0.0 0.0
0900 29.0 24.7 44 158.8 2183.2 2078.8 0.0 0.0 0.0
1000 30.7 24.7 44 163.0 2254.1 2140.4 0.0 0.0 0.0
1100 32.6 24.8 44 167.5 2328.1 2205.0 0.0 0.0 0.0
1200 34.4 24.8 43 171.7 2398.6 2267.3 0.0 0.0 0.0
1300 35.8 24.8 43 174.0 2433.9 2300.8 0.0 0.0 0.0
1400 36.7 24.8 43 174.6 2439.2 2309.2 0.0 0.0 0.0
1500 37.0 24.8 43 175.1 2444.1 2316.6 0.0 0.0 0.0
1600 36.7 24.8 42 175.3 2443.8 2319.4 0.0 0.0 0.0
1700 35.9 24.8 43 175.0 2435.6 2315.4 0.0 0.0 0.0
1800 34.6 24.8 43 172.7 2391.7 2281.1 0.0 0.0 0.0
1900 33.2 24.8 43 167.7 2302.4 2208.0 0.0 0.0 0.0
2000 31.7 24.7 44 162.4 2211.0 2131.7 0.0 0.0 0.0
2100 30.4 24.7 44 157.7 2130.4 2063.4 0.0 0.0 0.0
2200 29.3 24.7 44 153.2 2055.5 1998.8 0.0 0.0 0.0
2300 28.4 24.6 44 149.3 1991.6 1942.9 0.0 0.0 0.0

ZONE: GF-40 Lobby


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 45 647.8 8656.3 8507.7 0.0 0.0 0.0
0100 27.2 24.7 45 642.1 8562.6 8425.0 0.0 0.0 0.0
0200 26.6 24.7 45 636.2 8467.6 8340.5 0.0 0.0 0.0
0300 26.2 24.7 45 631.1 8386.9 8266.5 0.0 0.0 0.0
0400 25.8 24.7 45 626.8 8321.2 8203.9 0.0 0.0 0.0
0500 25.7 24.7 45 624.1 8286.7 8165.6 0.0 0.0 0.0
0600 25.9 24.7 45 624.1 8300.2 8165.3 0.0 0.0 0.0
0700 26.5 24.7 45 626.8 8363.2 8205.1 0.0 0.0 0.0
0800 27.5 24.7 44 633.4 8492.6 8299.0 0.0 0.0 0.0
0900 29.0 24.7 44 643.8 8690.2 8449.6 0.0 0.0 0.0
1000 30.7 24.7 44 656.5 8926.0 8634.4 0.0 0.0 0.0
1100 32.6 24.8 44 671.6 9200.7 8854.0 0.0 0.0 0.0
1200 34.4 24.8 43 686.5 9467.3 9072.3 0.0 0.0 0.0
1300 35.8 24.8 43 694.6 9600.2 9190.6 0.0 0.0 0.0
1400 36.7 24.8 43 696.9 9623.7 9224.1 0.0 0.0 0.0
1500 37.0 24.8 43 698.9 9645.6 9254.5 0.0 0.0 0.0
1600 36.7 24.8 42 700.9 9666.1 9282.8 0.0 0.0 0.0
1700 35.9 24.8 43 702.7 9685.3 9309.1 0.0 0.0 0.0
1800 34.6 24.8 43 700.1 9623.3 9271.5 0.0 0.0 0.0
1900 33.2 24.8 43 690.6 9432.8 9131.3 0.0 0.0 0.0
2000 31.7 24.8 44 680.3 9235.1 8980.1 0.0 0.0 0.0
2100 30.4 24.8 44 670.9 9062.1 8844.0 0.0 0.0 0.0
2200 29.3 24.8 44 661.9 8899.5 8713.0 0.0 0.0 0.0
2300 28.4 24.7 44 654.2 8763.9 8600.3 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 43 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF-34 Valet Elevator Lob


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.4 45 55.5 709.2 705.0 0.0 0.0 0.0
0100 27.2 24.3 45 52.8 670.8 668.9 0.0 0.0 0.0
0200 26.6 24.3 45 50.2 634.1 634.3 0.0 0.0 0.0
0300 26.2 24.2 45 47.9 601.5 603.4 0.0 0.0 0.0
0400 25.8 24.2 45 45.8 573.0 576.1 0.0 0.0 0.0
0500 25.7 24.3 45 54.3 702.2 689.8 0.0 0.0 0.0
0600 25.9 24.5 45 67.9 911.4 876.5 0.0 0.0 0.0
0700 26.5 24.7 45 76.3 1042.7 995.2 0.0 0.0 0.0
0800 27.5 24.7 44 81.2 1120.2 1066.3 0.0 0.0 0.0
0900 29.0 24.7 44 82.9 1144.0 1089.6 0.0 0.0 0.0
1000 30.7 24.8 44 83.0 1144.9 1092.1 0.0 0.0 0.0
1100 32.6 24.8 44 85.5 1182.9 1127.6 0.0 0.0 0.0
1200 34.4 24.8 43 87.5 1213.7 1156.9 0.0 0.0 0.0
1300 35.8 24.8 43 88.0 1220.5 1164.6 0.0 0.0 0.0
1400 36.7 24.8 43 87.6 1212.8 1159.1 0.0 0.0 0.0
1500 37.0 24.8 43 86.8 1198.4 1147.5 0.0 0.0 0.0
1600 36.7 24.8 42 85.2 1170.8 1123.7 0.0 0.0 0.0
1700 35.9 24.7 43 82.6 1127.3 1085.4 0.0 0.0 0.0
1800 34.6 24.7 43 78.4 1059.7 1025.2 0.0 0.0 0.0
1900 33.2 24.6 43 74.0 990.3 962.8 0.0 0.0 0.0
2000 31.7 24.6 44 69.6 921.2 900.3 0.0 0.0 0.0
2100 30.4 24.5 44 65.6 859.6 844.1 0.0 0.0 0.0
2200 29.3 24.4 44 61.8 802.3 791.5 0.0 0.0 0.0
2300 28.4 24.4 44 58.4 752.1 745.1 0.0 0.0 0.0

ZONE: GF-15 Vestibule


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.5 45 330.6 4238.1 4251.1 0.0 0.0 0.0
0100 27.2 24.5 45 324.6 4150.4 4167.9 0.0 0.0 0.0
0200 26.6 24.5 45 318.8 4067.1 4088.2 0.0 0.0 0.0
0300 26.2 24.4 45 313.6 3992.6 4016.1 0.0 0.0 0.0
0400 25.8 24.4 45 308.9 3926.7 3951.4 0.0 0.0 0.0
0500 25.7 24.4 45 306.8 3902.0 3922.5 0.0 0.0 0.0
0600 25.9 24.4 45 308.1 3929.7 3940.1 0.0 0.0 0.0
0700 26.5 24.4 45 310.9 3979.9 3978.6 0.0 0.0 0.0
0800 27.5 24.4 44 315.6 4058.6 4043.3 0.0 0.0 0.0
0900 29.0 24.5 44 322.0 4163.0 4132.0 0.0 0.0 0.0
1000 30.7 24.5 44 329.9 4289.2 4241.4 0.0 0.0 0.0
1100 32.6 24.5 44 341.4 4471.4 4401.5 0.0 0.0 0.0
1200 34.4 24.6 43 361.9 4797.5 4689.4 0.0 0.0 0.0
1300 35.8 24.6 43 383.8 5143.8 4999.3 0.0 0.0 0.0
1400 36.7 24.7 43 402.2 5432.6 5262.7 0.0 0.0 0.0
1500 37.0 24.7 43 414.3 5617.9 5438.0 0.0 0.0 0.0
1600 36.7 24.7 42 417.2 5648.4 5478.7 0.0 0.0 0.0
1700 35.9 24.7 43 407.4 5472.3 5337.4 0.0 0.0 0.0
1800 34.6 24.6 43 385.7 5106.7 5026.3 0.0 0.0 0.0
1900 33.2 24.6 43 374.2 4917.7 4862.8 0.0 0.0 0.0
2000 31.7 24.6 44 363.0 4737.4 4705.1 0.0 0.0 0.0
2100 30.4 24.5 44 353.4 4585.8 4570.1 0.0 0.0 0.0
2200 29.3 24.5 44 344.8 4451.8 4449.0 0.0 0.0 0.0
2300 28.4 24.5 44 337.2 4336.6 4343.1 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 44 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF-18 WC
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.1 45 150.0 1284.0 1537.3 0.0 0.0 0.0
0100 27.2 22.0 45 150.0 1255.2 1524.6 0.0 0.0 0.0
0200 26.6 22.0 45 150.0 1225.9 1511.4 0.0 0.0 0.0
0300 26.2 21.9 45 150.0 1201.0 1499.3 0.0 0.0 0.0
0400 25.8 21.8 45 150.0 1180.8 1488.5 0.0 0.0 0.0
0500 25.7 21.8 45 150.0 1170.2 1480.9 0.0 0.0 0.0
0600 25.9 21.8 45 150.0 1174.4 1478.4 0.0 0.0 0.0
0700 26.5 21.8 45 150.0 1193.7 1481.4 0.0 0.0 0.0
0800 27.5 21.8 44 150.0 1233.6 1492.1 0.0 0.0 0.0
0900 29.0 22.0 44 150.0 1294.4 1510.9 0.0 0.0 0.0
1000 30.7 22.1 44 150.0 1367.0 1535.2 0.0 0.0 0.0
1100 32.6 22.3 44 150.0 1451.6 1565.1 0.0 0.0 0.0
1200 34.4 22.5 43 150.0 1533.7 1595.9 0.0 0.0 0.0
1300 35.8 22.6 43 150.0 1574.6 1614.2 0.0 0.0 0.0
1400 36.7 22.6 43 150.0 1581.8 1621.5 0.0 0.0 0.0
1500 37.0 22.7 43 150.0 1588.6 1628.3 0.0 0.0 0.0
1600 36.7 22.7 42 150.0 1594.9 1634.7 0.0 0.0 0.0
1700 35.9 22.7 43 150.0 1600.8 1640.7 0.0 0.0 0.0
1800 34.6 22.7 43 150.0 1581.7 1638.2 0.0 0.0 0.0
1900 33.2 22.6 43 150.0 1523.0 1621.6 0.0 0.0 0.0
2000 31.7 22.5 44 150.0 1462.2 1602.6 0.0 0.0 0.0
2100 30.4 22.4 44 150.0 1408.9 1584.8 0.0 0.0 0.0
2200 29.3 22.3 44 150.0 1358.8 1567.0 0.0 0.0 0.0
2300 28.4 22.2 44 150.0 1317.1 1551.0 0.0 0.0 0.0

ZONE: GF-16 Corridor


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.2 45 56.1 679.5 706.2 0.0 0.0 0.0
0100 27.2 24.2 45 53.8 647.7 676.3 0.0 0.0 0.0
0200 26.6 24.2 45 51.9 620.6 650.3 0.0 0.0 0.0
0300 26.2 24.2 45 50.1 597.2 627.2 0.0 0.0 0.0
0400 25.8 24.2 45 48.5 576.8 606.6 0.0 0.0 0.0
0500 25.7 24.1 45 47.3 560.8 589.8 0.0 0.0 0.0
0600 25.9 24.1 45 46.7 557.0 583.0 0.0 0.0 0.0
0700 26.5 24.1 45 47.4 571.2 591.3 0.0 0.0 0.0
0800 27.5 24.2 44 48.9 599.4 611.7 0.0 0.0 0.0
0900 29.0 24.2 44 51.1 637.0 640.6 0.0 0.0 0.0
1000 30.7 24.2 44 53.8 681.5 676.0 0.0 0.0 0.0
1100 32.6 24.3 44 57.2 736.2 720.6 0.0 0.0 0.0
1200 34.4 24.3 43 62.5 822.5 792.0 0.0 0.0 0.0
1300 35.8 24.4 43 69.9 943.6 893.3 0.0 0.0 0.0
1400 36.7 24.5 43 78.0 1075.2 1005.0 0.0 0.0 0.0
1500 37.0 24.6 43 85.2 1190.7 1105.5 0.0 0.0 0.0
1600 36.7 24.7 42 90.0 1265.5 1174.1 0.0 0.0 0.0
1700 35.9 24.7 43 91.3 1278.5 1192.6 0.0 0.0 0.0
1800 34.6 24.6 43 87.7 1207.8 1141.9 0.0 0.0 0.0
1900 33.2 24.5 43 79.5 1059.2 1025.3 0.0 0.0 0.0
2000 31.7 24.4 44 71.8 926.7 918.4 0.0 0.0 0.0
2100 30.4 24.4 44 66.2 835.0 842.3 0.0 0.0 0.0
2200 29.3 24.3 44 62.0 768.9 785.9 0.0 0.0 0.0
2300 28.4 24.3 44 58.8 718.9 741.9 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 45 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF-17 Pantry/WSTN


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.5 45 297.2 2948.8 3156.8 0.0 0.0 0.0
0100 27.2 22.4 45 297.2 2911.4 3134.3 0.0 0.0 0.0
0200 26.6 22.3 45 297.2 2877.5 3112.7 0.0 0.0 0.0
0300 26.2 22.3 45 297.2 2848.4 3092.9 0.0 0.0 0.0
0400 25.8 22.2 45 297.2 2823.7 3074.7 0.0 0.0 0.0
0500 25.7 22.2 45 297.2 2806.6 3059.7 0.0 0.0 0.0
0600 25.9 22.1 45 297.2 2805.5 3051.9 0.0 0.0 0.0
0700 26.5 22.1 45 297.2 2825.1 3053.8 0.0 0.0 0.0
0800 27.5 22.2 44 297.2 2864.6 3065.5 0.0 0.0 0.0
0900 29.0 22.2 44 297.2 2920.7 3086.2 0.0 0.0 0.0
1000 30.7 22.3 44 297.2 2987.3 3113.5 0.0 0.0 0.0
1100 32.6 22.4 44 297.2 3067.1 3148.5 0.0 0.0 0.0
1200 34.4 22.6 43 297.2 3170.2 3196.1 0.0 0.0 0.0
1300 35.8 22.7 43 297.2 3281.7 3250.1 0.0 0.0 0.0
1400 36.7 22.9 43 297.2 3386.2 3303.9 0.0 0.0 0.0
1500 37.0 23.1 43 297.2 3478.2 3354.4 0.0 0.0 0.0
1600 36.7 23.2 42 297.2 3538.7 3392.8 0.0 0.0 0.0
1700 35.9 23.2 43 297.2 3551.3 3410.7 0.0 0.0 0.0
1800 34.6 23.2 43 297.2 3488.4 3394.6 0.0 0.0 0.0
1900 33.2 23.0 43 297.2 3347.7 3341.3 0.0 0.0 0.0
2000 31.7 22.9 44 297.2 3218.6 3287.9 0.0 0.0 0.0
2100 30.4 22.7 44 297.2 3124.2 3246.1 0.0 0.0 0.0
2200 29.3 22.6 44 297.2 3051.0 3211.3 0.0 0.0 0.0
2300 28.4 22.5 44 297.2 2993.9 3182.0 0.0 0.0 0.0

ZONE: GF-20 Tea Lounge/Bar


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.5 45 1057.3 13729.3 13655.2 0.0 0.0 0.0
0100 27.2 24.5 45 1042.1 13483.5 13435.2 0.0 0.0 0.0
0200 26.6 24.5 45 1026.9 13242.3 13217.5 0.0 0.0 0.0
0300 26.2 24.5 45 1013.3 13031.8 13023.0 0.0 0.0 0.0
0400 25.8 24.5 45 1001.4 12852.3 12852.9 0.0 0.0 0.0
0500 25.7 24.5 45 995.2 12775.2 12764.9 0.0 0.0 0.0
0600 25.9 24.5 45 997.0 12837.1 12790.4 0.0 0.0 0.0
0700 26.5 24.5 45 1004.2 12989.7 12893.1 0.0 0.0 0.0
0800 27.5 24.5 44 1018.6 13263.7 13098.4 0.0 0.0 0.0
0900 29.0 24.5 44 1040.1 13657.7 13406.8 0.0 0.0 0.0
1000 30.7 24.5 44 1065.6 14115.8 13774.6 0.0 0.0 0.0
1100 32.6 24.6 44 1095.2 14641.6 14204.8 0.0 0.0 0.0
1200 34.4 24.6 43 1124.5 15153.4 14632.0 0.0 0.0 0.0
1300 35.8 24.7 43 1153.7 15659.6 15061.5 0.0 0.0 0.0
1400 36.7 24.7 43 1186.1 16221.5 15541.5 0.0 0.0 0.0
1500 37.0 24.7 43 1218.6 16780.8 16026.0 0.0 0.0 0.0
1600 36.7 24.8 42 1241.7 17162.5 16373.6 0.0 0.0 0.0
1700 35.9 24.8 43 1241.7 17109.7 16373.7 0.0 0.0 0.0
1800 34.6 24.7 43 1194.7 16187.9 15669.2 0.0 0.0 0.0
1900 33.2 24.7 43 1168.3 15686.7 15277.7 0.0 0.0 0.0
2000 31.7 24.6 44 1140.9 15179.1 14873.8 0.0 0.0 0.0
2100 30.4 24.6 44 1116.7 14742.8 14518.1 0.0 0.0 0.0
2200 29.3 24.6 44 1094.0 14345.0 14187.0 0.0 0.0 0.0
2300 28.4 24.6 44 1074.2 14007.8 13899.3 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 46 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF-21 Reception 1


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 45 488.6 6394.6 6356.8 0.0 0.0 0.0
0100 27.2 24.6 45 481.6 6285.4 6257.7 0.0 0.0 0.0
0200 26.6 24.6 45 474.7 6177.9 6159.4 0.0 0.0 0.0
0300 26.2 24.6 45 468.4 6083.3 6071.0 0.0 0.0 0.0
0400 25.8 24.6 45 462.9 6001.8 5992.9 0.0 0.0 0.0
0500 25.7 24.6 45 460.2 5970.5 5955.7 0.0 0.0 0.0
0600 25.9 24.6 45 461.4 6004.0 5972.3 0.0 0.0 0.0
0700 26.5 24.6 45 464.7 6072.1 6019.1 0.0 0.0 0.0
0800 27.5 24.6 44 471.0 6188.9 6108.0 0.0 0.0 0.0
0900 29.0 24.6 44 480.3 6354.4 6239.4 0.0 0.0 0.0
1000 30.7 24.6 44 491.3 6544.9 6394.6 0.0 0.0 0.0
1100 32.6 24.7 44 504.0 6762.9 6575.7 0.0 0.0 0.0
1200 34.4 24.7 43 516.5 6974.4 6754.8 0.0 0.0 0.0
1300 35.8 24.7 43 531.0 7220.2 6964.8 0.0 0.0 0.0
1400 36.7 24.8 43 548.8 7519.9 7221.9 0.0 0.0 0.0
1500 37.0 24.8 43 566.1 7809.1 7474.5 0.0 0.0 0.0
1600 36.7 24.8 42 577.7 7993.7 7644.8 0.0 0.0 0.0
1700 35.9 24.8 43 575.7 7932.8 7615.6 0.0 0.0 0.0
1800 34.6 24.8 43 547.7 7410.0 7205.7 0.0 0.0 0.0
1900 33.2 24.7 43 536.6 7210.2 7045.5 0.0 0.0 0.0
2000 31.7 24.7 44 525.4 7009.5 6882.6 0.0 0.0 0.0
2100 30.4 24.7 44 515.0 6830.3 6733.9 0.0 0.0 0.0
2200 29.3 24.7 44 505.1 6662.2 6591.6 0.0 0.0 0.0
2300 28.4 24.6 44 496.3 6516.8 6465.5 0.0 0.0 0.0

ZONE: GF-21 Reception 2


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.5 45 1049.3 13549.2 13469.0 0.0 0.0 0.0
0100 27.2 24.4 45 1020.8 13124.9 13075.4 0.0 0.0 0.0
0200 26.6 24.4 45 992.9 12714.7 12692.5 0.0 0.0 0.0
0300 26.2 24.4 45 967.9 12353.0 12350.3 0.0 0.0 0.0
0400 25.8 24.4 45 945.9 12039.3 12049.1 0.0 0.0 0.0
0500 25.7 24.4 45 935.6 11912.5 11909.6 0.0 0.0 0.0
0600 25.9 24.4 45 941.0 12029.3 11983.3 0.0 0.0 0.0
0700 26.5 24.4 45 955.9 12289.0 12185.8 0.0 0.0 0.0
0800 27.5 24.4 44 984.0 12751.4 12569.6 0.0 0.0 0.0
0900 29.0 24.4 44 1024.5 13405.8 13127.1 0.0 0.0 0.0
1000 30.7 24.5 44 1071.7 14159.6 13779.5 0.0 0.0 0.0
1100 32.6 24.5 44 1125.0 15008.3 14522.7 0.0 0.0 0.0
1200 34.4 24.6 43 1176.8 15828.2 15250.0 0.0 0.0 0.0
1300 35.8 24.6 43 1240.3 16840.3 16150.1 0.0 0.0 0.0
1400 36.7 24.7 43 1318.7 18099.3 17272.8 0.0 0.0 0.0
1500 37.0 24.8 43 1392.4 19282.0 18340.7 0.0 0.0 0.0
1600 36.7 24.8 42 1438.9 20006.8 19020.8 0.0 0.0 0.0
1700 35.9 24.8 43 1425.1 19709.5 18817.9 0.0 0.0 0.0
1800 34.6 24.7 43 1300.4 17569.1 17009.3 0.0 0.0 0.0
1900 33.2 24.6 43 1252.0 16762.9 16317.2 0.0 0.0 0.0
2000 31.7 24.6 44 1203.0 15957.3 15620.9 0.0 0.0 0.0
2100 30.4 24.6 44 1158.7 15244.8 14996.1 0.0 0.0 0.0
2200 29.3 24.5 44 1117.3 14590.0 14414.4 0.0 0.0 0.0
2300 28.4 24.5 44 1080.7 14025.6 13905.4 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 47 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF-24 Guest Relation


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.4 45 205.4 2619.5 2625.5 0.0 0.0 0.0
0100 27.2 24.4 45 198.4 2520.1 2529.3 0.0 0.0 0.0
0200 26.6 24.4 45 191.6 2424.3 2436.4 0.0 0.0 0.0
0300 26.2 24.3 45 185.4 2338.3 2352.5 0.0 0.0 0.0
0400 25.8 24.3 45 179.8 2262.3 2277.7 0.0 0.0 0.0
0500 25.7 24.5 45 215.3 2798.7 2762.2 0.0 0.0 0.0
0600 25.9 24.7 45 266.2 3582.0 3478.2 0.0 0.0 0.0
0700 26.5 24.8 45 290.3 3956.8 3827.5 0.0 0.0 0.0
0800 27.5 24.8 44 298.3 4074.9 3943.5 0.0 0.0 0.0
0900 29.0 24.8 44 293.4 3988.4 3871.9 0.0 0.0 0.0
1000 30.7 24.8 44 284.9 3846.9 3748.0 0.0 0.0 0.0
1100 32.6 24.8 44 288.1 3894.9 3795.2 0.0 0.0 0.0
1200 34.4 24.8 43 292.6 3961.9 3860.3 0.0 0.0 0.0
1300 35.8 24.8 43 295.5 4004.5 3903.1 0.0 0.0 0.0
1400 36.7 24.8 43 296.0 4009.0 3910.9 0.0 0.0 0.0
1500 37.0 24.8 43 293.7 3967.6 3876.3 0.0 0.0 0.0
1600 36.7 24.8 42 287.6 3868.0 3787.8 0.0 0.0 0.0
1700 35.9 24.7 43 277.8 3710.6 3645.3 0.0 0.0 0.0
1800 34.6 24.7 43 264.0 3493.5 3446.8 0.0 0.0 0.0
1900 33.2 24.6 43 252.8 3321.5 3287.8 0.0 0.0 0.0
2000 31.7 24.6 44 241.7 3152.0 3130.1 0.0 0.0 0.0
2100 30.4 24.5 44 231.5 2999.0 2986.6 0.0 0.0 0.0
2200 29.3 24.5 44 221.8 2855.9 2851.5 0.0 0.0 0.0
2300 28.4 24.4 44 213.1 2729.3 2731.0 0.0 0.0 0.0

ZONE: GF-25 Front Desk Manager


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 45 48.1 641.1 637.7 0.0 0.0 0.0
0100 27.2 24.8 45 48.0 639.6 636.3 0.0 0.0 0.0
0200 26.6 24.8 45 47.9 638.0 634.8 0.0 0.0 0.0
0300 26.2 24.8 45 47.8 636.6 633.5 0.0 0.0 0.0
0400 25.8 24.8 45 47.7 635.6 632.4 0.0 0.0 0.0
0500 25.7 24.8 45 47.7 635.0 631.8 0.0 0.0 0.0
0600 25.9 24.8 45 47.7 635.2 631.8 0.0 0.0 0.0
0700 26.5 24.8 45 47.7 636.3 632.6 0.0 0.0 0.0
0800 27.5 24.8 44 47.9 638.4 634.3 0.0 0.0 0.0
0900 29.0 24.8 44 48.0 641.7 637.0 0.0 0.0 0.0
1000 30.7 24.9 44 48.3 645.6 640.3 0.0 0.0 0.0
1100 32.6 24.9 44 48.5 650.1 644.2 0.0 0.0 0.0
1200 34.4 24.9 43 48.8 654.5 648.1 0.0 0.0 0.0
1300 35.8 24.9 43 48.9 656.7 650.2 0.0 0.0 0.0
1400 36.7 24.9 43 49.0 657.1 650.7 0.0 0.0 0.0
1500 37.0 24.9 43 49.0 657.5 651.2 0.0 0.0 0.0
1600 36.7 24.9 42 49.0 657.8 651.7 0.0 0.0 0.0
1700 35.9 24.9 43 49.1 658.1 652.1 0.0 0.0 0.0
1800 34.6 24.9 43 49.0 657.1 651.4 0.0 0.0 0.0
1900 33.2 24.9 43 48.8 653.9 648.8 0.0 0.0 0.0
2000 31.7 24.9 44 48.7 650.7 646.1 0.0 0.0 0.0
2100 30.4 24.9 44 48.5 647.8 643.7 0.0 0.0 0.0
2200 29.3 24.9 44 48.3 645.1 641.3 0.0 0.0 0.0
2300 28.4 24.9 44 48.2 642.9 639.3 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 48 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF-26 Guest Relation MGR


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 45 47.2 629.0 625.9 0.0 0.0 0.0
0100 27.2 24.8 45 47.1 627.6 624.6 0.0 0.0 0.0
0200 26.6 24.8 45 47.0 626.2 623.3 0.0 0.0 0.0
0300 26.2 24.8 45 46.9 625.0 622.1 0.0 0.0 0.0
0400 25.8 24.8 45 46.9 624.0 621.2 0.0 0.0 0.0
0500 25.7 24.8 45 46.8 623.5 620.6 0.0 0.0 0.0
0600 25.9 24.8 45 46.8 623.7 620.6 0.0 0.0 0.0
0700 26.5 24.8 45 46.9 624.7 621.3 0.0 0.0 0.0
0800 27.5 24.8 44 47.0 626.6 622.9 0.0 0.0 0.0
0900 29.0 24.8 44 47.2 629.5 625.3 0.0 0.0 0.0
1000 30.7 24.9 44 47.4 632.9 628.3 0.0 0.0 0.0
1100 32.6 24.9 44 47.6 637.0 631.8 0.0 0.0 0.0
1200 34.4 24.9 43 47.8 640.9 635.3 0.0 0.0 0.0
1300 35.8 24.9 43 48.0 642.8 637.1 0.0 0.0 0.0
1400 36.7 24.9 43 48.0 643.2 637.6 0.0 0.0 0.0
1500 37.0 24.9 43 48.0 643.5 638.1 0.0 0.0 0.0
1600 36.7 24.9 42 48.0 643.8 638.5 0.0 0.0 0.0
1700 35.9 24.9 43 48.1 644.1 638.8 0.0 0.0 0.0
1800 34.6 24.9 43 48.0 643.2 638.2 0.0 0.0 0.0
1900 33.2 24.9 43 47.9 640.4 635.9 0.0 0.0 0.0
2000 31.7 24.9 44 47.7 637.5 633.4 0.0 0.0 0.0
2100 30.4 24.9 44 47.6 634.9 631.2 0.0 0.0 0.0
2200 29.3 24.9 44 47.4 632.6 629.1 0.0 0.0 0.0
2300 28.4 24.9 44 47.3 630.6 627.3 0.0 0.0 0.0

ZONE: GF-28 FOH Manager


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 45 42.9 562.8 561.8 0.0 0.0 0.0
0100 27.2 24.7 45 42.4 556.1 555.4 0.0 0.0 0.0
0200 26.6 24.7 45 42.0 550.1 549.6 0.0 0.0 0.0
0300 26.2 24.7 45 41.7 544.7 544.4 0.0 0.0 0.0
0400 25.8 24.7 45 41.3 540.0 539.7 0.0 0.0 0.0
0500 25.7 24.7 45 41.2 538.5 537.7 0.0 0.0 0.0
0600 25.9 24.7 45 42.3 557.5 553.3 0.0 0.0 0.0
0700 26.5 24.7 45 44.6 597.0 586.7 0.0 0.0 0.0
0800 27.5 24.8 44 46.7 633.0 617.8 0.0 0.0 0.0
0900 29.0 24.8 44 48.0 652.9 635.7 0.0 0.0 0.0
1000 30.7 24.9 44 48.3 656.8 640.2 0.0 0.0 0.0
1100 32.6 24.8 44 47.9 649.7 635.2 0.0 0.0 0.0
1200 34.4 24.8 43 47.5 641.5 628.8 0.0 0.0 0.0
1300 35.8 24.8 43 47.3 637.1 625.6 0.0 0.0 0.0
1400 36.7 24.8 43 47.2 635.9 625.0 0.0 0.0 0.0
1500 37.0 24.8 43 47.3 636.2 625.6 0.0 0.0 0.0
1600 36.7 24.8 42 47.3 635.6 625.4 0.0 0.0 0.0
1700 35.9 24.8 43 47.1 632.7 623.1 0.0 0.0 0.0
1800 34.6 24.8 43 46.7 625.2 617.0 0.0 0.0 0.0
1900 33.2 24.8 43 46.0 612.8 606.5 0.0 0.0 0.0
2000 31.7 24.8 44 45.2 600.4 595.7 0.0 0.0 0.0
2100 30.4 24.7 44 44.6 589.4 586.0 0.0 0.0 0.0
2200 29.3 24.7 44 43.9 579.4 577.0 0.0 0.0 0.0
2300 28.4 24.7 44 43.4 570.5 569.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 49 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF-27 Female Inspection


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 45 45.8 610.7 608.6 0.0 0.0 0.0
0100 27.2 24.9 45 45.8 609.9 607.7 0.0 0.0 0.0
0200 26.6 24.9 45 45.7 609.0 606.9 0.0 0.0 0.0
0300 26.2 24.9 45 45.7 608.3 606.2 0.0 0.0 0.0
0400 25.8 24.9 45 45.6 607.7 605.6 0.0 0.0 0.0
0500 25.7 24.9 45 45.6 607.3 605.2 0.0 0.0 0.0
0600 25.9 24.9 45 45.6 607.5 605.3 0.0 0.0 0.0
0700 26.5 24.9 45 45.6 608.0 605.8 0.0 0.0 0.0
0800 27.5 24.9 44 45.7 609.2 606.8 0.0 0.0 0.0
0900 29.0 24.9 44 45.8 611.0 608.4 0.0 0.0 0.0
1000 30.7 24.9 44 46.0 613.2 610.4 0.0 0.0 0.0
1100 32.6 24.9 44 46.1 615.7 612.7 0.0 0.0 0.0
1200 34.4 24.9 43 46.3 618.2 614.9 0.0 0.0 0.0
1300 35.8 24.9 43 46.3 619.4 616.1 0.0 0.0 0.0
1400 36.7 24.9 43 46.4 619.6 616.4 0.0 0.0 0.0
1500 37.0 24.9 43 46.4 619.8 616.7 0.0 0.0 0.0
1600 36.7 24.9 42 46.4 620.0 616.9 0.0 0.0 0.0
1700 35.9 24.9 43 46.4 620.2 617.1 0.0 0.0 0.0
1800 34.6 24.9 43 46.4 619.6 616.6 0.0 0.0 0.0
1900 33.2 24.9 43 46.3 617.9 615.1 0.0 0.0 0.0
2000 31.7 24.9 44 46.2 616.1 613.5 0.0 0.0 0.0
2100 30.4 24.9 44 46.1 614.5 612.0 0.0 0.0 0.0
2200 29.3 24.9 44 46.0 613.0 610.7 0.0 0.0 0.0
2300 28.4 24.9 44 45.9 611.7 609.5 0.0 0.0 0.0

ZONE: GF-22 Viewing Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.4 45 34.4 436.4 439.8 0.0 0.0 0.0
0100 27.2 24.4 45 33.5 423.2 427.1 0.0 0.0 0.0
0200 26.6 24.4 45 32.7 412.0 416.1 0.0 0.0 0.0
0300 26.2 24.4 45 31.9 402.1 406.4 0.0 0.0 0.0
0400 25.8 24.3 45 31.3 393.5 397.7 0.0 0.0 0.0
0500 25.7 24.3 45 30.9 387.9 391.8 0.0 0.0 0.0
0600 25.9 24.4 45 31.5 398.4 400.1 0.0 0.0 0.0
0700 26.5 24.4 45 33.3 426.9 424.5 0.0 0.0 0.0
0800 27.5 24.4 44 35.2 456.8 450.7 0.0 0.0 0.0
0900 29.0 24.5 44 36.6 479.0 470.3 0.0 0.0 0.0
1000 30.7 24.5 44 37.5 492.9 482.9 0.0 0.0 0.0
1100 32.6 24.5 44 38.2 502.7 492.0 0.0 0.0 0.0
1200 34.4 24.5 43 39.4 521.8 509.3 0.0 0.0 0.0
1300 35.8 24.6 43 41.6 555.8 540.0 0.0 0.0 0.0
1400 36.7 24.7 43 44.1 596.2 576.6 0.0 0.0 0.0
1500 37.0 24.7 43 46.4 632.5 610.0 0.0 0.0 0.0
1600 36.7 24.8 42 47.9 655.4 631.8 0.0 0.0 0.0
1700 35.9 24.8 43 48.2 657.4 635.3 0.0 0.0 0.0
1800 34.6 24.7 43 46.7 631.2 613.6 0.0 0.0 0.0
1900 33.2 24.7 43 43.5 578.8 568.3 0.0 0.0 0.0
2000 31.7 24.6 44 40.6 531.4 526.6 0.0 0.0 0.0
2100 30.4 24.5 44 38.5 497.5 496.3 0.0 0.0 0.0
2200 29.3 24.5 44 36.8 472.3 473.3 0.0 0.0 0.0
2300 28.4 24.5 44 35.5 452.5 455.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 50 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF13/GF11 Inspect/Lobby


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 45 107.8 1415.5 1406.9 0.0 0.0 0.0
0100 27.2 24.7 45 106.8 1399.0 1392.6 0.0 0.0 0.0
0200 26.6 24.6 45 105.8 1383.9 1379.3 0.0 0.0 0.0
0300 26.2 24.6 45 105.0 1371.0 1367.6 0.0 0.0 0.0
0400 25.8 24.6 45 104.3 1360.1 1357.6 0.0 0.0 0.0
0500 25.7 24.6 45 103.8 1352.8 1350.5 0.0 0.0 0.0
0600 25.9 24.6 45 103.7 1352.6 1349.2 0.0 0.0 0.0
0700 26.5 24.6 45 104.2 1361.6 1355.5 0.0 0.0 0.0
0800 27.5 24.6 44 105.1 1379.6 1369.3 0.0 0.0 0.0
0900 29.0 24.6 44 106.6 1405.4 1389.9 0.0 0.0 0.0
1000 30.7 24.7 44 108.3 1436.2 1414.8 0.0 0.0 0.0
1100 32.6 24.7 44 110.4 1472.9 1444.8 0.0 0.0 0.0
1200 34.4 24.7 43 113.0 1518.4 1482.4 0.0 0.0 0.0
1300 35.8 24.7 43 115.6 1563.1 1519.8 0.0 0.0 0.0
1400 36.7 24.8 43 118.0 1603.8 1554.3 0.0 0.0 0.0
1500 37.0 24.8 43 120.1 1639.6 1585.1 0.0 0.0 0.0
1600 36.7 24.8 42 121.5 1663.3 1606.2 0.0 0.0 0.0
1700 35.9 24.8 43 121.9 1668.5 1612.4 0.0 0.0 0.0
1800 34.6 24.8 43 120.7 1644.0 1594.1 0.0 0.0 0.0
1900 33.2 24.8 43 117.5 1585.8 1547.8 0.0 0.0 0.0
2000 31.7 24.7 44 114.5 1531.8 1504.1 0.0 0.0 0.0
2100 30.4 24.7 44 112.2 1491.7 1471.2 0.0 0.0 0.0
2200 29.3 24.7 44 110.4 1460.1 1444.9 0.0 0.0 0.0
2300 28.4 24.7 44 109.0 1435.1 1423.9 0.0 0.0 0.0

ZONE: GF-29 Vestibule


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.4 45 309.8 3895.2 3941.2 0.0 0.0 0.0
0100 27.2 24.3 45 296.8 3711.0 3764.6 0.0 0.0 0.0
0200 26.6 24.3 45 284.1 3533.9 3594.2 0.0 0.0 0.0
0300 26.2 24.3 45 272.6 3375.2 3439.9 0.0 0.0 0.0
0400 25.8 24.2 45 262.3 3234.8 3302.0 0.0 0.0 0.0
0500 25.7 24.4 45 324.0 4186.8 4134.6 0.0 0.0 0.0
0600 25.9 24.6 45 414.1 5599.8 5390.9 0.0 0.0 0.0
0700 26.5 24.8 45 459.0 6308.8 6037.0 0.0 0.0 0.0
0800 27.5 24.8 44 475.5 6557.9 6277.4 0.0 0.0 0.0
0900 29.0 24.8 44 468.7 6426.0 6178.1 0.0 0.0 0.0
1000 30.7 24.7 44 454.5 6179.3 5972.0 0.0 0.0 0.0
1100 32.6 24.8 44 459.9 6257.5 6050.3 0.0 0.0 0.0
1200 34.4 24.8 43 467.3 6368.4 6158.3 0.0 0.0 0.0
1300 35.8 24.8 43 472.3 6439.7 6231.2 0.0 0.0 0.0
1400 36.7 24.8 43 473.3 6446.5 6246.2 0.0 0.0 0.0
1500 37.0 24.8 43 469.4 6373.3 6189.0 0.0 0.0 0.0
1600 36.7 24.8 42 459.0 6195.6 6037.1 0.0 0.0 0.0
1700 35.9 24.7 43 441.8 5912.6 5788.9 0.0 0.0 0.0
1800 34.6 24.6 43 417.4 5518.5 5438.5 0.0 0.0 0.0
1900 33.2 24.6 43 397.1 5199.0 5150.2 0.0 0.0 0.0
2000 31.7 24.5 44 376.7 4883.8 4863.4 0.0 0.0 0.0
2100 30.4 24.5 44 357.9 4599.4 4601.8 0.0 0.0 0.0
2200 29.3 24.4 44 340.1 4333.9 4355.3 0.0 0.0 0.0
2300 28.4 24.4 44 324.0 4099.0 4134.9 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 51 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF-33 Service Lobby 2 Cr


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.4 45 130.0 1683.2 1665.3 0.0 0.0 0.0
0100 27.2 24.4 45 124.9 1601.4 1595.6 0.0 0.0 0.0
0200 26.6 24.4 45 119.9 1522.1 1527.5 0.0 0.0 0.0
0300 26.2 24.3 45 115.5 1453.7 1467.1 0.0 0.0 0.0
0400 25.8 24.3 45 111.6 1396.2 1414.9 0.0 0.0 0.0
0500 25.7 24.3 45 109.6 1371.1 1387.0 0.0 0.0 0.0
0600 25.9 24.3 45 114.6 1472.4 1455.0 0.0 0.0 0.0
0700 26.5 24.4 45 127.1 1705.2 1625.2 0.0 0.0 0.0
0800 27.5 24.5 44 140.9 1960.5 1817.4 0.0 0.0 0.0
0900 29.0 24.6 44 152.7 2173.4 1982.0 0.0 0.0 0.0
1000 30.7 24.7 44 161.2 2325.3 2103.6 0.0 0.0 0.0
1100 32.6 24.7 44 167.7 2437.2 2196.4 0.0 0.0 0.0
1200 34.4 24.7 43 173.0 2526.7 2273.2 0.0 0.0 0.0
1300 35.8 24.8 43 175.5 2561.9 2309.3 0.0 0.0 0.0
1400 36.7 24.8 43 175.9 2558.9 2316.0 0.0 0.0 0.0
1500 37.0 24.8 43 176.8 2566.1 2329.1 0.0 0.0 0.0
1600 36.7 24.8 42 177.5 2570.7 2339.6 0.0 0.0 0.0
1700 35.9 24.8 43 177.6 2564.2 2341.0 0.0 0.0 0.0
1800 34.6 24.8 43 174.4 2494.5 2294.0 0.0 0.0 0.0
1900 33.2 24.7 43 166.3 2333.9 2176.6 0.0 0.0 0.0
2000 31.7 24.6 44 157.6 2169.5 2052.8 0.0 0.0 0.0
2100 30.4 24.6 44 149.8 2025.1 1941.3 0.0 0.0 0.0
2200 29.3 24.5 44 142.3 1891.3 1835.8 0.0 0.0 0.0
2300 28.4 24.5 44 135.6 1777.1 1743.5 0.0 0.0 0.0

ZONE: GF-39 Luggage


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 45 59.9 798.1 783.3 0.0 0.0 0.0
0100 27.2 24.7 45 59.2 785.3 772.6 0.0 0.0 0.0
0200 26.6 24.6 45 58.4 772.3 761.5 0.0 0.0 0.0
0300 26.2 24.6 45 57.7 761.2 751.7 0.0 0.0 0.0
0400 25.8 24.6 45 57.1 752.2 743.4 0.0 0.0 0.0
0500 25.7 24.6 45 56.8 747.5 738.1 0.0 0.0 0.0
0600 25.9 24.6 45 56.7 749.3 737.7 0.0 0.0 0.0
0700 26.5 24.6 45 57.1 757.9 742.4 0.0 0.0 0.0
0800 27.5 24.6 44 57.9 775.7 754.0 0.0 0.0 0.0
0900 29.0 24.7 44 59.2 802.8 773.0 0.0 0.0 0.0
1000 30.7 24.7 44 60.8 835.1 796.4 0.0 0.0 0.0
1100 32.6 24.7 44 62.8 872.8 824.4 0.0 0.0 0.0
1200 34.4 24.8 43 64.7 909.3 852.4 0.0 0.0 0.0
1300 35.8 24.8 43 65.8 927.5 867.8 0.0 0.0 0.0
1400 36.7 24.8 43 66.1 930.8 872.6 0.0 0.0 0.0
1500 37.0 24.8 43 66.4 933.8 876.9 0.0 0.0 0.0
1600 36.7 24.8 42 66.7 936.6 880.9 0.0 0.0 0.0
1700 35.9 24.8 43 66.9 939.2 884.6 0.0 0.0 0.0
1800 34.6 24.8 43 66.6 930.7 880.3 0.0 0.0 0.0
1900 33.2 24.8 43 65.4 904.6 862.8 0.0 0.0 0.0
2000 31.7 24.8 44 64.1 877.5 843.8 0.0 0.0 0.0
2100 30.4 24.7 44 62.9 853.8 826.5 0.0 0.0 0.0
2200 29.3 24.7 44 61.8 831.5 809.8 0.0 0.0 0.0
2300 28.4 24.7 44 60.8 812.9 795.4 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 52 of 263


Hourly Zone Loads for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

ZONE: GF-32 Lobby


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.5 45 117.5 1574.5 1514.4 0.0 0.0 0.0
0100 27.2 24.5 45 114.2 1522.1 1469.3 0.0 0.0 0.0
0200 26.6 24.5 45 110.9 1468.9 1423.3 0.0 0.0 0.0
0300 26.2 24.4 45 108.0 1423.8 1383.4 0.0 0.0 0.0
0400 25.8 24.4 45 105.6 1387.0 1350.1 0.0 0.0 0.0
0500 25.7 24.4 45 104.2 1367.7 1330.7 0.0 0.0 0.0
0600 25.9 24.4 45 104.3 1375.3 1332.8 0.0 0.0 0.0
0700 26.5 24.4 45 106.1 1410.5 1357.4 0.0 0.0 0.0
0800 27.5 24.5 44 110.1 1482.9 1412.3 0.0 0.0 0.0
0900 29.0 24.5 44 116.4 1593.4 1498.7 0.0 0.0 0.0
1000 30.7 24.6 44 123.9 1725.4 1603.8 0.0 0.0 0.0
1100 32.6 24.6 44 132.6 1879.0 1727.7 0.0 0.0 0.0
1200 34.4 24.7 43 141.1 2028.2 1849.9 0.0 0.0 0.0
1300 35.8 24.7 43 145.6 2102.5 1914.3 0.0 0.0 0.0
1400 36.7 24.8 43 146.7 2115.7 1930.3 0.0 0.0 0.0
1500 37.0 24.8 43 147.7 2127.9 1944.9 0.0 0.0 0.0
1600 36.7 24.8 42 148.6 2139.4 1958.5 0.0 0.0 0.0
1700 35.9 24.8 43 149.5 2150.1 1971.1 0.0 0.0 0.0
1800 34.6 24.8 43 147.9 2115.5 1947.5 0.0 0.0 0.0
1900 33.2 24.7 43 142.2 2008.9 1865.9 0.0 0.0 0.0
2000 31.7 24.7 44 136.2 1898.3 1779.2 0.0 0.0 0.0
2100 30.4 24.6 44 130.8 1801.5 1701.9 0.0 0.0 0.0
2200 29.3 24.6 44 125.6 1710.5 1628.1 0.0 0.0 0.0
2300 28.4 24.5 44 121.1 1634.7 1565.4 0.0 0.0 0.0

ZONE: GF-19 WC
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.8 45 250.0 1557.6 1767.8 0.0 446.9 0.0
0100 27.2 20.8 45 250.0 1539.2 1750.2 0.0 463.0 0.0
0200 26.6 20.8 45 250.0 1520.5 1732.4 0.0 479.3 0.0
0300 26.2 20.8 45 250.0 1504.6 1717.0 0.0 493.4 0.0
0400 25.8 20.8 45 250.0 1491.7 1704.2 0.0 505.1 0.0
0500 25.7 20.8 45 250.0 1484.9 1697.0 0.0 511.7 0.0
0600 25.9 20.8 45 250.0 1487.5 1698.5 0.0 510.4 0.0
0700 26.5 20.8 45 250.0 1499.9 1708.8 0.0 500.9 0.0
0800 27.5 20.8 44 250.0 1525.4 1731.2 0.0 480.4 0.0
0900 29.0 20.8 44 250.0 1564.3 1766.1 0.0 448.5 0.0
1000 30.7 20.9 44 250.0 1610.7 1808.2 0.0 410.0 0.0
1100 32.6 20.9 44 250.0 1664.7 1857.6 0.0 364.8 0.0
1200 34.4 20.9 43 250.0 1717.2 1906.0 0.0 320.4 0.0
1300 35.8 20.9 43 250.0 1743.4 1931.1 0.0 297.5 0.0
1400 36.7 20.9 43 250.0 1748.0 1936.7 0.0 292.4 0.0
1500 37.0 20.9 43 250.0 1752.3 1941.8 0.0 287.7 0.0
1600 36.7 20.9 42 250.0 1756.3 1946.6 0.0 283.3 0.0
1700 35.9 20.9 43 250.0 1760.1 1951.1 0.0 279.2 0.0
1800 34.6 20.9 43 250.0 1747.9 1941.0 0.0 288.4 0.0
1900 33.2 20.9 43 250.0 1710.4 1907.9 0.0 318.7 0.0
2000 31.7 20.9 44 250.0 1671.5 1872.9 0.0 350.7 0.0
2100 30.4 20.9 44 250.0 1637.5 1842.0 0.0 379.0 0.0
2200 29.3 20.9 44 250.0 1605.5 1812.6 0.0 405.9 0.0
2300 28.4 20.9 44 250.0 1578.8 1787.8 0.0 428.6 0.0

Hourly Analysis Program v4.80 Page 53 of 263


System Psychrometrics for AHU-H-C3-01 - Reception & Tea L
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 1282 400 19212 10180
Vent - Return Mixing Outlet 27.1 0.00963 6846 1248 - -
Preheat Coil Outlet 27.1 0.00963 6846 1248 0 -
Central Cooling Coil Outlet 11.1 0.00816 6846 1248 120290 27040
Supply Fan Outlet 12.8 0.00816 6846 1248 12820 -
Cold Supply Duct Outlet 12.8 0.00816 6846 1248 - -
Zone Air - 24.8 0.00908 6846 1444 87970 16857
Zone Direct Exhaust Outlet 24.8 0.00908 690 1444 - -
Return Plenum Outlet 24.8 0.00908 6156 1444 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
GF-30 Lug 2444 Cooling 2317 24.8 175 1271 0 0
GF-40 Lobby 9646 Cooling 9254 24.8 699 1563 0 0
GF-34 Valet Elevator Lob 1198 Cooling 1147 24.8 87 1290 0 0
GF-15 Vestibule 5618 Cooling 5438 24.7 414 1321 0 0
GF-18 WC 1589 Deadband 1628 22.7 150 1386 0 0
GF-16 Corridor 1191 Cooling 1106 24.6 85 1439 0 0
GF-17 Pantry/WSTN 3478 Deadband 3354 23.1 297 1372 0 0
GF-20 Tea Lounge/Bar 16781 Cooling 16026 24.7 1219 1642 0 0
GF-21 Reception 1 7809 Cooling 7474 24.8 566 1398 0 0
GF-21 Reception 2 19282 Cooling 18341 24.8 1392 1428 0 0
GF-24 Guest Relation 3968 Cooling 3876 24.8 294 1297 0 0
GF-25 Front Desk Manager 657 Cooling 651 24.9 49 1470 0 0
GF-26 Guest Relation MGR 644 Cooling 638 24.9 48 1475 0 0
GF-28 FOH Manager 636 Cooling 626 24.8 47 1359 0 0
GF-27 Female Inspection 620 Cooling 617 24.9 46 1483 0 0
GF-22 Viewing Room 632 Cooling 610 24.7 46 1483 0 0
GF13/GF11 Inspect/Lobby 1640 Cooling 1585 24.8 120 1506 0 0
GF-29 Vestibule 6373 Cooling 6189 24.8 469 1286 0 0
GF-33 Service Lobby 2 Cr 2566 Cooling 2329 24.8 177 1399 0 0
GF-39 Luggage 934 Cooling 877 24.8 66 1324 0 0
GF-32 Lobby 2128 Cooling 1945 24.8 148 1329 0 0
GF-19 WC 1752 Heating 1942 20.9 250 1398 288 0

Hourly Analysis Program v4.80 Page 54 of 263


Air System Sizing Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

Air System Information


Air System Name AHU-H-C3-02 - C1 Areas Number of zones 24
Equipment Class CW AHU Floor Area 792.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 90.4 kW Load occurs at Jul 1500
Sensible coil load 71.0 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 3440 L/s Entering DB / WB 29.9 / 18.7 °C
Max block L/s at Jul 1600 3874 L/s Leaving DB / WB 11.1 / 10.1 °C
Sum of peak zone L/s 3877 L/s Coil ADP 9.0 °C
Sensible heat ratio 0.785 Bypass Factor 0.100
m²/kW 8.8 Resulting RH 41 %
W/m² 114.2 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 3.23 L/s Zone T-stat Check 24 of 24 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 2.5 kW Load occurs at Des Htg
Coil L/s at Des Htg 1610 L/s Ent. DB / Lvg DB 11.4 / 12.8 °C
Max coil L/s 3874 L/s
Water flow @ 11.0 °K drop 0.05 L/s

Supply Fan Sizing Data


Actual max L/s at Jul 1600 3874 L/s Fan motor BHP 9.04 BHP
Standard L/s 3532 L/s Fan motor kW 7.17 kW
Actual max L/(s-m²) 4.89 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1610 L/s L/s/person 11.50 L/s/person
L/(s-m²) 2.03 L/(s-m²)

Hourly Analysis Program v4.80 Page 55 of 263


Zone Sizing Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

Air System Information


Air System Name AHU-H-C3-02 - C1 Areas Number of zones 24
Equipment Class CW AHU Floor Area 792.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C1-06 Purch & Receive ST 1.9 153 46 Jul 1700 1.0 10.0 15.30
C1-07 Purchasing Manager 0.8 68 20 Jul 1700 0.6 5.0 13.58
C1-09 Monitoring Station 1.7 140 42 Jul 1700 1.1 19.0 7.35
C1-10 SecuritySupervisor 0.8 69 21 Jul 1700 0.3 9.0 7.63
C1-20 Linen Collection 0.5 45 45 Jul 1700 0.5 14.0 3.21
C1-52 Closing Room 2.1 171 51 Jul 1600 1.1 30.0 5.71
C1-90 Lobby 1.7 138 41 Jul 1700 1.6 25.0 5.52
C1-93 Bridal Suite 3.0 242 73 Jul 1700 1.6 32.0 7.57
C1-101 Assistance HK 1.0 82 25 Jul 1600 0.4 12.0 6.87
C1-100 HK Manager 0.9 76 23 Jul 1600 0.3 12.0 6.36
C1-102 Houskeepking 2.6 213 64 Jul 1600 1.0 41.0 5.19
C1-109 Nurse 1.2 93 28 Jul 1600 0.5 17.0 5.50
C1-112 HR Reception 1.7 140 42 Jul 1600 0.6 27.0 5.18
C1-113 HR Clerk 0.8 61 18 Jun 1500 0.1 10.0 6.10
C1-114 DR of HR 1.0 82 25 Jul 1600 0.4 10.0 8.18
C1-116 DR of Training 0.8 62 19 Jun 1500 0.1 10.0 6.23
C1-115 Training Room 3.8 306 220 Jun 1500 0.3 35.0 8.74
C1-117 ENG. Reception 2.4 199 60 Jul 1600 0.4 27.0 7.36
C1-119 DIR of Engineerin 0.8 67 20 Jul 1600 0.3 9.0 7.46
C1-122 M+E Workshop 1.3 110 110 Jun 1500 0.2 23.0 4.78
C1-121 Carpenter Shop 1.4 110 110 Jul 1600 0.5 18.0 6.12
C1-125 Electric Repair 1.0 80 80 Jul 1600 0.3 6.0 13.33
C1-124 Paint Shop 1.4 110 110 Jul 1600 0.8 10.0 11.03
C1-25 Corridor 1 13.1 1059 318 Jul 1600 11.3 381.0 2.78

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
C1-06 Purch & Receive ST 1.5 0.03 0.0 0.00 0
C1-07 Purchasing Manager 0.8 0.02 0.0 0.00 0
C1-09 Monitoring Station 1.5 0.03 0.0 0.00 0
C1-10 SecuritySupervisor 0.5 0.01 0.0 0.00 0
C1-20 Linen Collection 0.9 0.02 0.0 0.00 0
C1-52 Closing Room 1.6 0.03 0.0 0.00 0
C1-90 Lobby 2.0 0.04 0.0 0.00 0
C1-93 Bridal Suite 2.3 0.05 0.0 0.00 0
C1-101 Assistance HK 0.6 0.01 0.0 0.00 0
C1-100 HK Manager 0.5 0.01 0.0 0.00 0
C1-102 Houskeepking 1.6 0.03 0.0 0.00 0
C1-109 Nurse 0.8 0.02 0.0 0.00 0
C1-112 HR Reception 1.0 0.02 0.0 0.00 0
C1-113 HR Clerk 0.2 0.00 0.0 0.00 0

Hourly Analysis Program v4.80 Page 56 of 263


Zone Sizing Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
C1-114 DR of HR 0.6 0.01 0.0 0.00 0
C1-116 DR of Training 0.2 0.00 0.0 0.00 0
C1-115 Training Room 2.3 0.05 0.0 0.00 0
C1-117 ENG. Reception 1.0 0.02 0.0 0.00 0
C1-119 DIR of Engineerin 0.5 0.01 0.0 0.00 0
C1-122 M+E Workshop 1.2 0.03 0.0 0.00 0
C1-121 Carpenter Shop 1.5 0.03 0.0 0.00 0
C1-125 Electric Repair 1.0 0.02 0.0 0.00 0
C1-124 Paint Shop 1.8 0.04 0.0 0.00 0
C1-25 Corridor 1 14.2 0.31 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-06 Purch & Receive ST
C1A-06 Purch & Rec St 1 1.9 Jul 1700 153 1.0 10.0 15.30
C1-07 Purchasing Manager
C1A-07 Purch. Manager 1 0.8 Jul 1700 68 0.6 5.0 13.58
C1-09 Monitoring Station
C1A-09 Monitoring Statio 1 1.7 Jul 1700 140 1.1 19.0 7.35
C1-10 SecuritySupervisor
C1A-10 Security Supervis 1 0.8 Jul 1700 69 0.3 9.0 7.63
C1-20 Linen Collection
C1A-20 Linen Collection 1 0.5 Jul 1700 45 0.5 14.0 3.21
C1-52 Closing Room
C1A-52 Closing Room 1 2.1 Jul 1600 171 1.1 30.0 5.71
C1-90 Lobby
C1A-90-Lobby 1 1.7 Jul 1700 138 1.6 25.0 5.52
C1-93 Bridal Suite
C1A-93 Bridal Suite 1 3.0 Jul 1700 242 1.6 32.0 7.57
C1-101 Assistance HK
C1A-101 Assistance HK 1 1.0 Jul 1600 82 0.4 12.0 6.87
C1-100 HK Manager
C1A-100 HK Manager 1 0.9 Jul 1600 76 0.3 12.0 6.36
C1-102 Houskeepking
C1A-102 Housekeeping 1 2.6 Jul 1600 213 1.0 41.0 5.19
C1-109 Nurse
C1A-109 Nurse 1 1.2 Jul 1600 93 0.5 17.0 5.50
C1-112 HR Reception
C1A-112 HR Reception 1 1.7 Jul 1600 140 0.6 27.0 5.18
C1-113 HR Clerk
C1A-113 HR Clerk 1 0.8 Jun 1500 61 0.1 10.0 6.10
C1-114 DR of HR
C1A-114 DR of HR 1 1.0 Jul 1600 82 0.4 10.0 8.18
C1-116 DR of Training
C1A-116 Dr. of Training 1 0.8 Jun 1500 62 0.1 10.0 6.23
C1-115 Training Room
C1A-115 Training Rm 1 3.8 Jun 1500 306 0.3 35.0 8.74
C1-117 ENG. Reception
C1A-117 ENG Reception 1 2.4 Jul 1600 199 0.4 27.0 7.36
C1-119 DIR of Engineerin
C1A-119 Dirc of Eng 1 0.8 Jul 1600 67 0.3 9.0 7.46
C1-122 M+E Workshop
C1A-122 M+E Workshop 1 1.3 Jun 1500 110 0.2 23.0 4.78

Hourly Analysis Program v4.80 Page 57 of 263


Zone Sizing Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-121 Carpenter Shop
C1A-121 Carpenter Shop 1 1.4 Jul 1600 110 0.5 18.0 6.12
C1-125 Electric Repair
C1A-125 Electric Rep. 1 1.0 Jul 1600 80 0.3 6.0 13.33
C1-124 Paint Shop
C1A-124 Paint Shop 1 1.4 Jul 1600 110 0.8 10.0 11.03
C1-25 Corridor 1
C1A-25 Corridor 1 1 13.1 Jul 1600 1059 11.3 381.0 2.78

Hourly Analysis Program v4.80 Page 58 of 263


Ventilation Sizing Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

1. Summary
Ventilation Sizing Method ASHRAE Std 62.1-2007
Design Condition Minimum flow (heating)
Occupant Diversity 1.000
Uncorrected Ventilation Airflow Rate 627 L/s
System Ventilation Efficiency 0.390
Design Ventilation Airflow Rate 1610 L/s

2. Space Ventilation Analysis Table


Minimum Floor Required Time Required Air Required Uncorrected Space
Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation
Zone Name / Space Name Mult. (L/s) (m²) (L/(s-m²)) Occupancy (L/s/person) Effectiveness (L/s) (L/s) Efficiency
C1-06 Purch & Receive ST
C1A-06 Purch & Rec St 1 46 10.0 0.30 3.0 2.50 0.80 13 11 1.104
C1-07 Purchasing Manager
C1A-07 Purch. Manager 1 20 5.0 0.30 1.0 2.50 0.80 5 4 1.144
C1-09 Monitoring Station
C1A-09 Monitoring Statio 1 42 19.0 0.30 2.0 2.50 0.80 13 11 1.070
C1-10 SecuritySupervisor
C1A-10 Security Supervis 1 21 9.0 0.30 3.0 2.50 0.80 13 10 0.771
C1-20 Linen Collection
C1A-20 Linen Collection 1 45 14.0 0.60 0.0 0.00 0.80 11 8 1.156
C1-52 Closing Room
C1A-52 Closing Room 1 51 30.0 0.30 7.0 3.80 0.80 45 36 0.524
C1-90 Lobby
C1A-90-Lobby 1 41 25.0 0.30 3.0 0.00 0.80 9 8 1.163
C1-93 Bridal Suite
C1A-93 Bridal Suite 1 73 32.0 0.30 7.0 2.50 0.80 34 27 0.923
C1-101 Assistance HK
C1A-101 Assistance HK 1 25 12.0 0.30 2.0 2.50 0.80 11 9 0.955
C1-100 HK Manager
C1A-100 HK Manager 1 23 12.0 0.30 3.0 2.50 0.80 14 11 0.784
C1-102 Houskeepking
C1A-102 Housekeeping 1 64 41.0 0.30 5.0 2.50 0.80 31 25 0.903
C1-109 Nurse
C1A-109 Nurse 1 28 17.0 0.30 3.0 2.50 0.80 16 13 0.828
C1-112 HR Reception
C1A-112 HR Reception 1 42 27.0 0.30 5.0 2.50 0.80 26 21 0.776
C1-113 HR Clerk
C1A-113 HR Clerk 1 18 10.0 0.30 3.0 2.50 0.80 13 11 0.672
C1-114 DR of HR
C1A-114 DR of HR 1 25 10.0 0.30 3.0 2.50 0.80 13 11 0.855
C1-116 DR of Training
C1A-116 Dr. of Training 1 19 10.0 0.30 3.0 2.50 0.80 13 11 0.687
C1-115 Training Room
C1A-115 Training Rm 1 220 35.0 0.60 31.0 5.00 0.80 220 176 0.390

Hourly Analysis Program v4.80 Page 59 of 263


Ventilation Sizing Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:00PM

C1-117 ENG. Reception


C1A-117 ENG Reception 1 60 27.0 0.30 8.0 2.50 0.80 35 28 0.800
C1-119 DIR of Engineerin
C1A-119 Dirc of Eng 1 20 9.0 0.30 2.0 2.50 0.80 10 8 0.911
C1-122 M+E Workshop
C1A-122 M+E Workshop 1 110 23.0 0.90 3.0 5.00 0.80 45 36 0.984
C1-121 Carpenter Shop
C1A-121 Carpenter Shop 1 110 18.0 0.90 2.0 5.00 0.80 33 26 1.092
C1-125 Electric Repair
C1A-125 Electric Rep. 1 80 6.0 0.90 1.0 5.00 0.80 13 10 1.227
C1-124 Paint Shop
C1A-124 Paint Shop 1 110 10.0 0.30 1.0 2.50 0.80 7 6 1.327
C1-25 Corridor 1
C1A-25 Corridor 1 1 318 381.0 0.30 39.0 0.00 0.80 143 114 0.940
Totals (incl. Space Multipliers) 1610 627 0.390

Hourly Analysis Program v4.80 Page 60 of 263


Air System Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 488 m² 4588 - 488 m² 2473 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 605 m² 2408 - 605 m² 3606 -
Partitions 885 m² 11156 - 885 m² 16819 -
Ceiling 24 m² 96 - 24 m² 144 -
Overhead Lighting 6919 W 6919 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6850 W 6850 - 0 0 -
People 140 9715 6466 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 10% / 10% 4323 647 10% 2304 0
>> Total Zone Loads - 47553 7112 - 25346 0
Zone Conditioning - 44705 7112 - 23363 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2661 L/s 0 - 978 L/s 0 -
Ventilation Load 1430 L/s 19890 12294 669 L/s 15388 0
Supply Fan Load 3440 L/s 6442 - 1610 L/s -3390 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 71037 19406 - 35362 0
Central Cooling Coil - 71037 19406 - -3390 0
Preheat Coil - 0 - - 2465 -
Terminal Reheat Coils - 0 - - 36286 -
>> Total Conditioning - 71037 19406 - 35362 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-06 Purch & Receive ST DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 10 m² 41 - 10 m² 60 -
Partitions 47 m² 601 - 47 m² 891 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 108 W 108 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 750 W 750 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 171 18 10% 95 0
>> Total Zone Loads - 1886 198 - 1046 0

C1-07 Purchasing Manager DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 5 m² 21 - 5 m² 20 -
Partitions 29 m² 375 - 29 m² 557 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 43 W 43 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 76 6 10% 58 0
>> Total Zone Loads - 837 66 - 634 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-09 Monitoring Station DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 77 - 19 m² 105 -
Partitions 48 m² 608 - 48 m² 903 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 235 W 235 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 156 12 10% 101 0
>> Total Zone Loads - 1721 132 - 1108 0

C1-10 SecuritySupervisor DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 37 - 9 m² 50 -
Partitions 12 m² 151 - 12 m² 224 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 116 W 116 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 77 18 10% 27 0
>> Total Zone Loads - 846 198 - 301 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-20 Linen Collection DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 14 m² 57 - 14 m² 84 -
Partitions 15 m² 197 - 15 m² 293 -
Ceiling 14 m² 57 - 14 m² 84 -
Overhead Lighting 161 W 161 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 47 0 10% 46 0
>> Total Zone Loads - 519 0 - 507 0

C1-52 Closing Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 30 m² 281 - 30 m² 152 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 121 - 30 m² 180 -
Partitions 35 m² 446 - 35 m² 667 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 600 W 600 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 7 472 246 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 192 25 10% 100 0
>> Total Zone Loads - 2112 271 - 1099 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-90 Lobby DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 97 - 24 m² 144 -
Partitions 68 m² 871 - 68 m² 1292 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 375 W 375 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 202 106 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 155 11 10% 144 0
>> Total Zone Loads - 1700 116 - 1580 0

C1-93 Bridal Suite DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 32 m² 130 - 32 m² 192 -
Partitions 68 m² 871 - 68 m² 1292 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 992 W 992 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 7 472 246 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 271 25 10% 148 0
>> Total Zone Loads - 2986 271 - 1632 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-101 Assistance HK DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 12 m² 113 - 12 m² 61 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 12 m² 48 - 12 m² 72 -
Partitions 12 m² 149 - 12 m² 222 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 221 W 221 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 92 12 10% 36 0
>> Total Zone Loads - 1017 132 - 391 0

C1-100 HK Manager DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 12 m² 113 - 12 m² 61 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 12 m² 48 - 12 m² 72 -
Partitions 5 m² 65 - 5 m² 97 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 165 W 165 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 86 18 10% 23 0
>> Total Zone Loads - 941 198 - 253 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-102 Houskeepking DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 41 m² 384 - 41 m² 208 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 41 m² 165 - 41 m² 246 -
Partitions 23 m² 297 - 23 m² 445 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 677 W 676 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 238 30 10% 90 0
>> Total Zone Loads - 2621 331 - 988 0

C1-109 Nurse DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 17 m² 159 - 17 m² 86 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 16 m² 64 - 16 m² 96 -
Partitions 16 m² 208 - 16 m² 312 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 163 W 163 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 202 106 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 105 11 10% 49 0
>> Total Zone Loads - 1152 116 - 543 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-112 HR Reception DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 27 m² 253 - 27 m² 137 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 23 m² 297 - 23 m² 445 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 157 W 157 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 157 30 10% 58 0
>> Total Zone Loads - 1724 331 - 640 0

C1-113 HR Clerk DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 94 - 10 m² 51 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 124 W 124 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 68 18 10% 5 0
>> Total Zone Loads - 752 198 - 56 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-114 DR of HR DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 94 - 10 m² 51 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 159 - 13 m² 238 -
Ceiling 10 m² 40 - 10 m² 60 -
Overhead Lighting 159 W 159 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 92 18 10% 35 0
>> Total Zone Loads - 1009 198 - 383 0

C1-116 DR of Training DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 94 - 10 m² 51 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 139 W 138 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 70 18 10% 5 0
>> Total Zone Loads - 768 198 - 56 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-115 Training Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 35 m² 330 - 35 m² 177 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 5 m² 65 - 5 m² 99 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 344 W 344 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 31 2089 1091 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 343 109 10% 28 0
>> Total Zone Loads - 3771 1200 - 304 0

C1-117 ENG. Reception DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 27 m² 253 - 27 m² 137 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 164 - 13 m² 245 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 235 W 235 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 8 574 481 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 223 48 10% 38 0
>> Total Zone Loads - 2449 529 - 420 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-119 DIR of Engineerin DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 9 m² 84 - 9 m² 46 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 160 - 13 m² 239 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 114 W 114 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 75 12 10% 29 0
>> Total Zone Loads - 827 132 - 314 0

C1-122 M+E Workshop DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 23 m² 217 - 23 m² 117 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 4 m² 50 - 4 m² 76 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 500 0 - 0 0
Safety Factor 10% / 10% 123 40 10% 19 0
>> Total Zone Loads - 1349 440 - 212 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-121 Carpenter Shop DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 18 m² 169 - 18 m² 91 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 233 - 18 m² 348 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 189 W 189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 500 0 - 0 0
Safety Factor 10% / 10% 123 12 10% 44 0
>> Total Zone Loads - 1358 132 - 483 0

C1-125 Electric Repair DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 6 m² 56 - 6 m² 30 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 12 m² 149 - 12 m² 222 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 74 W 74 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 86 133 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 87 13 10% 25 0
>> Total Zone Loads - 952 147 - 278 0

Hourly Analysis Program v4.80


Zone Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2
Prepared by: dar

C1-124 Paint Shop DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 94 - 10 m² 51 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 37 m² 472 - 37 m² 703 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 98 W 98 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 500 0 - 0 0
Safety Factor 10% / 10% 124 6 10% 75 0
>> Total Zone Loads - 1359 66 - 829 0

C1-25 Corridor 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 191 m² 1791 - 191 m² 968 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 381 m² 1526 - 381 m² 2286 -
Partitions 369 m² 4690 - 369 m² 7011 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1231 W 1231 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 39 2629 1373 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1187 137 10% 1026 0
>> Total Zone Loads - 13052 1510 - 11291 0

Hourly Analysis Program v4.80


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1A-06 Purch & Rec St '' IN ZONE '' C1-06 Purch & Receive ST ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 10 m² 41 - 10 m² 60 -
Partitions 47 m² 601 - 47 m² 891 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 108 W 108 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 750 W 750 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 171 18 10% 95 0
>> Total Zone Loads - 1886 198 - 1046 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1A-06 Purch & Rec St '' IN ZONE '' C1-06 Purch & Receive ST ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 74 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' C1A-07 Purch. Manager '' IN ZONE '' C1-07 Purchasing Manager ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 5 m² 21 - 5 m² 20 -
Partitions 29 m² 375 - 29 m² 557 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 43 W 43 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 76 6 10% 58 0
>> Total Zone Loads - 837 66 - 634 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' C1A-07 Purch. Manager '' IN ZONE '' C1-07 Purchasing Manager ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 75 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' C1A-09 Monitoring Statio '' IN ZONE '' C1-09 Monitoring Station ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 77 - 19 m² 105 -
Partitions 48 m² 608 - 48 m² 903 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 235 W 235 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 156 12 10% 101 0
>> Total Zone Loads - 1721 132 - 1108 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' C1A-09 Monitoring Statio '' IN ZONE '' C1-09 Monitoring Station ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 76 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' C1A-10 Security Supervis '' IN ZONE '' C1-10 SecuritySupervisor ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 37 - 9 m² 50 -
Partitions 12 m² 151 - 12 m² 224 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 116 W 116 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 77 18 10% 27 0
>> Total Zone Loads - 846 198 - 301 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' C1A-10 Security Supervis '' IN ZONE '' C1-10 SecuritySupervisor ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 77 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' C1A-20 Linen Collection '' IN ZONE '' C1-20 Linen Collection ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 14 m² 57 - 14 m² 84 -
Partitions 15 m² 197 - 15 m² 293 -
Ceiling 14 m² 57 - 14 m² 84 -
Overhead Lighting 161 W 161 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 47 0 10% 46 0
>> Total Zone Loads - 519 0 - 507 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' C1A-20 Linen Collection '' IN ZONE '' C1-20 Linen Collection ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 78 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' C1A-52 Closing Room '' IN ZONE '' C1-52 Closing Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 30 m² 281 - 30 m² 152 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 121 - 30 m² 180 -
Partitions 35 m² 446 - 35 m² 667 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 600 W 600 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 7 472 246 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 192 25 10% 100 0
>> Total Zone Loads - 2112 271 - 1099 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' C1A-52 Closing Room '' IN ZONE '' C1-52 Closing Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 30 0.232 - 281 - 152

Hourly Analysis Program v4.80 Page 79 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' C1A-90-Lobby '' IN ZONE '' C1-90 Lobby ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 97 - 24 m² 144 -
Partitions 68 m² 871 - 68 m² 1292 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 375 W 375 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 202 106 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 155 11 10% 144 0
>> Total Zone Loads - 1700 116 - 1580 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' C1A-90-Lobby '' IN ZONE '' C1-90 Lobby ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 80 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' C1A-93 Bridal Suite '' IN ZONE '' C1-93 Bridal Suite ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 32 m² 130 - 32 m² 192 -
Partitions 68 m² 871 - 68 m² 1292 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 992 W 992 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 7 472 246 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 271 25 10% 148 0
>> Total Zone Loads - 2986 271 - 1632 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' C1A-93 Bridal Suite '' IN ZONE '' C1-93 Bridal Suite ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 81 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' C1A-101 Assistance HK '' IN ZONE '' C1-101 Assistance HK ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 12 m² 113 - 12 m² 61 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 12 m² 48 - 12 m² 72 -
Partitions 12 m² 149 - 12 m² 222 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 221 W 221 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 92 12 10% 36 0
>> Total Zone Loads - 1017 132 - 391 0

TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' C1A-101 Assistance HK '' IN ZONE '' C1-101 Assistance HK ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 12 0.232 - 113 - 61

Hourly Analysis Program v4.80 Page 82 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 10.1.A. COMPONENT LOADS FOR SPACE '' C1A-100 HK Manager '' IN ZONE '' C1-100 HK Manager ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 12 m² 113 - 12 m² 61 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 12 m² 48 - 12 m² 72 -
Partitions 5 m² 65 - 5 m² 97 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 165 W 165 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 86 18 10% 23 0
>> Total Zone Loads - 941 198 - 253 0

TABLE 10.1.B. ENVELOPE LOADS FOR SPACE '' C1A-100 HK Manager '' IN ZONE '' C1-100 HK Manager ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 12 0.232 - 113 - 61

Hourly Analysis Program v4.80 Page 83 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 11.1.A. COMPONENT LOADS FOR SPACE '' C1A-102 Housekeeping '' IN ZONE '' C1-102 Houskeepking ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 41 m² 384 - 41 m² 208 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 41 m² 165 - 41 m² 246 -
Partitions 23 m² 297 - 23 m² 445 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 677 W 676 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 238 30 10% 90 0
>> Total Zone Loads - 2621 331 - 988 0

TABLE 11.1.B. ENVELOPE LOADS FOR SPACE '' C1A-102 Housekeeping '' IN ZONE '' C1-102 Houskeepking ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 41 0.232 - 384 - 208

Hourly Analysis Program v4.80 Page 84 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 12.1.A. COMPONENT LOADS FOR SPACE '' C1A-109 Nurse '' IN ZONE '' C1-109 Nurse ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 17 m² 159 - 17 m² 86 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 16 m² 64 - 16 m² 96 -
Partitions 16 m² 208 - 16 m² 312 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 163 W 163 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 202 106 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 105 11 10% 49 0
>> Total Zone Loads - 1152 116 - 543 0

TABLE 12.1.B. ENVELOPE LOADS FOR SPACE '' C1A-109 Nurse '' IN ZONE '' C1-109 Nurse ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 17 0.232 - 159 - 86

Hourly Analysis Program v4.80 Page 85 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 13.1.A. COMPONENT LOADS FOR SPACE '' C1A-112 HR Reception '' IN ZONE '' C1-112 HR Reception ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 27 m² 253 - 27 m² 137 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 23 m² 297 - 23 m² 445 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 157 W 157 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 157 30 10% 58 0
>> Total Zone Loads - 1724 331 - 640 0

TABLE 13.1.B. ENVELOPE LOADS FOR SPACE '' C1A-112 HR Reception '' IN ZONE '' C1-112 HR Reception ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 27 0.232 - 253 - 137

Hourly Analysis Program v4.80 Page 86 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 14.1.A. COMPONENT LOADS FOR SPACE '' C1A-113 HR Clerk '' IN ZONE '' C1-113 HR Clerk ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 94 - 10 m² 51 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 124 W 124 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 68 18 10% 5 0
>> Total Zone Loads - 752 198 - 56 0

TABLE 14.1.B. ENVELOPE LOADS FOR SPACE '' C1A-113 HR Clerk '' IN ZONE '' C1-113 HR Clerk ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.232 - 94 - 51

Hourly Analysis Program v4.80 Page 87 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 15.1.A. COMPONENT LOADS FOR SPACE '' C1A-114 DR of HR '' IN ZONE '' C1-114 DR of HR ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 94 - 10 m² 51 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 159 - 13 m² 238 -
Ceiling 10 m² 40 - 10 m² 60 -
Overhead Lighting 159 W 159 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 92 18 10% 35 0
>> Total Zone Loads - 1009 198 - 383 0

TABLE 15.1.B. ENVELOPE LOADS FOR SPACE '' C1A-114 DR of HR '' IN ZONE '' C1-114 DR of HR ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.232 - 94 - 51

Hourly Analysis Program v4.80 Page 88 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 16.1.A. COMPONENT LOADS FOR SPACE '' C1A-116 Dr. of Training '' IN ZONE '' C1-116 DR of Training ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 94 - 10 m² 51 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 139 W 138 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 70 18 10% 5 0
>> Total Zone Loads - 768 198 - 56 0

TABLE 16.1.B. ENVELOPE LOADS FOR SPACE '' C1A-116 Dr. of Training '' IN ZONE '' C1-116 DR of Training ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.232 - 94 - 51

Hourly Analysis Program v4.80 Page 89 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 17.1.A. COMPONENT LOADS FOR SPACE '' C1A-115 Training Rm '' IN ZONE '' C1-115 Training Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 35 m² 330 - 35 m² 177 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 5 m² 65 - 5 m² 99 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 344 W 344 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 600 - 0 0 -
People 31 2089 1091 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 343 109 10% 28 0
>> Total Zone Loads - 3771 1200 - 304 0

TABLE 17.1.B. ENVELOPE LOADS FOR SPACE '' C1A-115 Training Rm '' IN ZONE '' C1-115 Training Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 35 0.232 - 330 - 177

Hourly Analysis Program v4.80 Page 90 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 18.1.A. COMPONENT LOADS FOR SPACE '' C1A-117 ENG Reception '' IN ZONE '' C1-117 ENG. Reception ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 27 m² 253 - 27 m² 137 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 164 - 13 m² 245 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 235 W 235 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 8 574 481 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 223 48 10% 38 0
>> Total Zone Loads - 2449 529 - 420 0

TABLE 18.1.B. ENVELOPE LOADS FOR SPACE '' C1A-117 ENG Reception '' IN ZONE '' C1-117 ENG. Reception ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 27 0.232 - 253 - 137

Hourly Analysis Program v4.80 Page 91 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 19.1.A. COMPONENT LOADS FOR SPACE '' C1A-119 Dirc of Eng '' IN ZONE '' C1-119 DIR of Engineerin ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 9 m² 84 - 9 m² 46 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 160 - 13 m² 239 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 114 W 114 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 75 12 10% 29 0
>> Total Zone Loads - 827 132 - 314 0

TABLE 19.1.B. ENVELOPE LOADS FOR SPACE '' C1A-119 Dirc of Eng '' IN ZONE '' C1-119 DIR of Engineerin ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 9 0.232 - 84 - 46

Hourly Analysis Program v4.80 Page 92 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 20.1.A. COMPONENT LOADS FOR SPACE '' C1A-122 M+E Workshop '' IN ZONE '' C1-122 M+E Workshop ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 23 m² 217 - 23 m² 117 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 4 m² 50 - 4 m² 76 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 500 0 - 0 0
Safety Factor 10% / 10% 123 40 10% 19 0
>> Total Zone Loads - 1349 440 - 212 0

TABLE 20.1.B. ENVELOPE LOADS FOR SPACE '' C1A-122 M+E Workshop '' IN ZONE '' C1-122 M+E Workshop ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 23 0.232 - 217 - 117

Hourly Analysis Program v4.80 Page 93 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 21.1.A. COMPONENT LOADS FOR SPACE '' C1A-121 Carpenter Shop '' IN ZONE '' C1-121 Carpenter Shop ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 18 m² 169 - 18 m² 91 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 233 - 18 m² 348 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 189 W 189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 500 0 - 0 0
Safety Factor 10% / 10% 123 12 10% 44 0
>> Total Zone Loads - 1358 132 - 483 0

TABLE 21.1.B. ENVELOPE LOADS FOR SPACE '' C1A-121 Carpenter Shop '' IN ZONE '' C1-121 Carpenter Shop ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 18 0.232 - 169 - 91

Hourly Analysis Program v4.80 Page 94 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 22.1.A. COMPONENT LOADS FOR SPACE '' C1A-125 Electric Rep. '' IN ZONE '' C1-125 Electric Repair ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 6 m² 56 - 6 m² 30 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 12 m² 149 - 12 m² 222 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 74 W 74 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 1 86 133 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 87 13 10% 25 0
>> Total Zone Loads - 952 147 - 278 0

TABLE 22.1.B. ENVELOPE LOADS FOR SPACE '' C1A-125 Electric Rep. '' IN ZONE '' C1-125 Electric Repair ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 6 0.232 - 56 - 30

Hourly Analysis Program v4.80 Page 95 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 23.1.A. COMPONENT LOADS FOR SPACE '' C1A-124 Paint Shop '' IN ZONE '' C1-124 Paint Shop ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 94 - 10 m² 51 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 37 m² 472 - 37 m² 703 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 98 W 98 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 500 0 - 0 0
Safety Factor 10% / 10% 124 6 10% 75 0
>> Total Zone Loads - 1359 66 - 829 0

TABLE 23.1.B. ENVELOPE LOADS FOR SPACE '' C1A-124 Paint Shop '' IN ZONE '' C1-124 Paint Shop ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.232 - 94 - 51

Hourly Analysis Program v4.80 Page 96 of 263


Space Design Load Summary for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:01PM

TABLE 24.1.A. COMPONENT LOADS FOR SPACE '' C1A-25 Corridor 1 '' IN ZONE '' C1-25 Corridor 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 191 m² 1791 - 191 m² 968 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 381 m² 1526 - 381 m² 2286 -
Partitions 369 m² 4690 - 369 m² 7011 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1231 W 1231 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 39 2629 1373 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1187 137 10% 1026 0
>> Total Zone Loads - 13052 1510 - 11291 0

TABLE 24.1.B. ENVELOPE LOADS FOR SPACE '' C1A-25 Corridor 1 '' IN ZONE '' C1-25 Corridor 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 191 0.232 - 1791 - 968

Hourly Analysis Program v4.80 Page 97 of 263


Hourly Air System Design Day Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 2992 48.8 65.4 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 2947 47.2 63.7 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 2903 45.8 61.9 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 2864 44.5 60.5 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 2830 43.6 59.4 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 2808 43.1 58.8 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 2803 43.3 59.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 2823 44.3 60.2 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 2878 46.5 62.7 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 2964 50.0 66.6 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 3070 54.2 71.4 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 3191 59.2 77.1 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 3309 64.3 82.9 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 3381 67.8 86.9 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 3416 70.0 89.3 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 3440 71.0 90.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 3453 70.8 90.2 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 3454 69.6 88.9 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 3421 66.9 86.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 3339 63.0 81.6 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 3252 59.1 77.2 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 3175 55.8 73.4 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 3103 52.9 70.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 3042 50.6 67.5 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 98 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-06 Purch & Receive ST


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 43 117.6 1587.1 1533.8 0.0 0.0 0.0
0100 27.2 24.6 44 115.8 1559.8 1508.7 0.0 0.0 0.0
0200 26.6 24.6 44 114.0 1532.1 1483.1 0.0 0.0 0.0
0300 26.2 24.6 44 112.5 1508.6 1461.2 0.0 0.0 0.0
0400 25.8 24.6 44 111.2 1489.5 1443.1 0.0 0.0 0.0
0500 25.7 24.6 44 110.5 1479.4 1433.1 0.0 0.0 0.0
0600 25.9 24.6 44 110.7 1483.4 1435.5 0.0 0.0 0.0
0700 26.5 24.6 44 111.8 1501.7 1450.8 0.0 0.0 0.0
0800 27.5 24.6 44 114.1 1539.4 1483.5 0.0 0.0 0.0
0900 29.0 24.7 43 117.6 1596.9 1534.0 0.0 0.0 0.0
1000 30.7 24.7 43 121.9 1665.6 1594.9 0.0 0.0 0.0
1100 32.6 24.7 42 126.8 1745.6 1666.2 0.0 0.0 0.0
1200 34.4 24.8 42 131.6 1823.2 1736.0 0.0 0.0 0.0
1300 35.8 24.8 42 134.0 1861.4 1771.3 0.0 0.0 0.0
1400 36.7 24.8 41 134.5 1868.2 1778.9 0.0 0.0 0.0
1500 37.0 24.8 41 135.0 1874.6 1785.9 0.0 0.0 0.0
1600 36.7 24.8 41 135.4 1880.5 1792.4 0.0 0.0 0.0
1700 35.9 24.8 41 135.9 1886.1 1798.5 0.0 0.0 0.0
1800 34.6 24.8 42 134.9 1868.6 1784.0 0.0 0.0 0.0
1900 33.2 24.8 42 131.6 1813.1 1735.8 0.0 0.0 0.0
2000 31.7 24.8 42 128.1 1755.5 1685.2 0.0 0.0 0.0
2100 30.4 24.7 43 125.0 1705.2 1640.4 0.0 0.0 0.0
2200 29.3 24.7 43 122.1 1657.8 1598.1 0.0 0.0 0.0
2300 28.4 24.7 43 119.6 1618.3 1562.4 0.0 0.0 0.0

ZONE: C1-07 Purchasing Manager


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 43 48.4 653.9 626.3 0.0 0.0 0.0
0100 27.2 24.5 44 47.3 637.2 611.3 0.0 0.0 0.0
0200 26.6 24.5 44 46.2 620.3 596.1 0.0 0.0 0.0
0300 26.2 24.5 44 45.3 605.9 583.0 0.0 0.0 0.0
0400 25.8 24.5 44 44.5 594.2 572.2 0.0 0.0 0.0
0500 25.7 24.5 44 44.1 588.1 566.2 0.0 0.0 0.0
0600 25.9 24.5 44 44.2 590.5 567.6 0.0 0.0 0.0
0700 26.5 24.5 44 44.8 601.7 576.6 0.0 0.0 0.0
0800 27.5 24.5 44 46.2 624.7 595.9 0.0 0.0 0.0
0900 29.0 24.6 43 48.3 659.9 625.9 0.0 0.0 0.0
1000 30.7 24.6 43 50.9 701.9 662.1 0.0 0.0 0.0
1100 32.6 24.7 42 53.9 750.8 704.5 0.0 0.0 0.0
1200 34.4 24.7 42 56.7 798.3 746.0 0.0 0.0 0.0
1300 35.8 24.8 42 58.2 821.7 767.1 0.0 0.0 0.0
1400 36.7 24.8 41 58.5 825.9 771.8 0.0 0.0 0.0
1500 37.0 24.8 41 58.8 829.8 776.0 0.0 0.0 0.0
1600 36.7 24.8 41 59.1 833.5 779.9 0.0 0.0 0.0
1700 35.9 24.8 41 59.3 836.9 783.6 0.0 0.0 0.0
1800 34.6 24.8 42 58.7 826.0 775.0 0.0 0.0 0.0
1900 33.2 24.7 42 56.8 792.1 746.4 0.0 0.0 0.0
2000 31.7 24.7 42 54.7 756.9 716.3 0.0 0.0 0.0
2100 30.4 24.7 43 52.8 726.1 689.8 0.0 0.0 0.0
2200 29.3 24.6 43 51.1 697.2 664.6 0.0 0.0 0.0
2300 28.4 24.6 43 49.6 673.0 643.3 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 99 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-09 Monitoring Station


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 43 104.4 1403.1 1357.7 0.0 0.0 0.0
0100 27.2 24.6 44 102.6 1374.1 1331.9 0.0 0.0 0.0
0200 26.6 24.6 44 100.7 1344.6 1305.5 0.0 0.0 0.0
0300 26.2 24.6 44 99.1 1319.6 1282.7 0.0 0.0 0.0
0400 25.8 24.6 44 97.7 1299.2 1263.7 0.0 0.0 0.0
0500 25.7 24.5 44 96.9 1288.5 1252.7 0.0 0.0 0.0
0600 25.9 24.5 44 97.0 1292.7 1254.0 0.0 0.0 0.0
0700 26.5 24.6 44 98.0 1312.2 1268.3 0.0 0.0 0.0
0800 27.5 24.6 44 100.3 1352.4 1299.9 0.0 0.0 0.0
0900 29.0 24.6 43 103.8 1413.6 1349.7 0.0 0.0 0.0
1000 30.7 24.7 43 108.0 1486.7 1410.1 0.0 0.0 0.0
1100 32.6 24.7 42 113.0 1571.8 1481.3 0.0 0.0 0.0
1200 34.4 24.8 42 117.8 1654.5 1551.5 0.0 0.0 0.0
1300 35.8 24.8 42 120.3 1694.7 1587.6 0.0 0.0 0.0
1400 36.7 24.8 41 120.9 1701.9 1596.6 0.0 0.0 0.0
1500 37.0 24.8 41 121.5 1708.7 1604.8 0.0 0.0 0.0
1600 36.7 24.8 41 122.0 1715.0 1612.4 0.0 0.0 0.0
1700 35.9 24.8 41 122.5 1721.0 1619.5 0.0 0.0 0.0
1800 34.6 24.8 42 121.6 1702.7 1606.6 0.0 0.0 0.0
1900 33.2 24.8 42 118.4 1643.7 1559.6 0.0 0.0 0.0
2000 31.7 24.7 42 115.0 1582.4 1509.7 0.0 0.0 0.0
2100 30.4 24.7 43 111.9 1528.8 1465.3 0.0 0.0 0.0
2200 29.3 24.7 43 108.9 1478.4 1422.9 0.0 0.0 0.0
2300 28.4 24.6 43 106.4 1436.4 1386.9 0.0 0.0 0.0

ZONE: C1-10 SecuritySupervisor


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 43 56.7 759.8 744.1 0.0 0.0 0.0
0100 27.2 24.7 44 56.2 751.9 736.9 0.0 0.0 0.0
0200 26.6 24.7 44 55.6 743.8 729.4 0.0 0.0 0.0
0300 26.2 24.7 44 55.2 737.0 723.0 0.0 0.0 0.0
0400 25.8 24.7 44 54.8 731.4 717.7 0.0 0.0 0.0
0500 25.7 24.7 44 54.6 728.5 714.6 0.0 0.0 0.0
0600 25.9 24.7 44 54.6 729.7 714.9 0.0 0.0 0.0
0700 26.5 24.7 44 54.9 735.0 719.0 0.0 0.0 0.0
0800 27.5 24.7 44 55.5 745.9 727.9 0.0 0.0 0.0
0900 29.0 24.7 43 56.5 762.7 741.9 0.0 0.0 0.0
1000 30.7 24.8 43 57.7 782.6 758.9 0.0 0.0 0.0
1100 32.6 24.8 42 59.1 805.8 779.0 0.0 0.0 0.0
1200 34.4 24.8 42 60.4 828.4 798.8 0.0 0.0 0.0
1300 35.8 24.8 42 61.1 839.2 808.8 0.0 0.0 0.0
1400 36.7 24.8 41 61.3 841.2 811.3 0.0 0.0 0.0
1500 37.0 24.8 41 61.4 843.0 813.6 0.0 0.0 0.0
1600 36.7 24.8 41 61.6 844.7 815.8 0.0 0.0 0.0
1700 35.9 24.8 41 61.7 846.3 817.8 0.0 0.0 0.0
1800 34.6 24.8 42 61.5 841.5 814.3 0.0 0.0 0.0
1900 33.2 24.8 42 60.6 825.4 801.0 0.0 0.0 0.0
2000 31.7 24.8 42 59.6 808.7 787.0 0.0 0.0 0.0
2100 30.4 24.8 43 58.7 794.1 774.4 0.0 0.0 0.0
2200 29.3 24.8 43 57.9 780.3 762.5 0.0 0.0 0.0
2300 28.4 24.7 43 57.2 768.9 752.4 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 100 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-20 Linen Collection


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.5 43 45.0 374.6 479.9 0.0 0.0 0.0
0100 27.2 22.4 44 45.0 361.4 476.1 0.0 0.0 0.0
0200 26.6 22.3 44 45.0 348.0 472.1 0.0 0.0 0.0
0300 26.2 22.3 44 45.0 336.6 468.4 0.0 0.0 0.0
0400 25.8 22.2 44 45.0 327.3 465.0 0.0 0.0 0.0
0500 25.7 22.1 44 45.0 322.5 462.4 0.0 0.0 0.0
0600 25.9 22.1 44 45.0 324.4 461.3 0.0 0.0 0.0
0700 26.5 22.1 44 45.0 333.3 461.8 0.0 0.0 0.0
0800 27.5 22.2 44 45.0 351.5 464.4 0.0 0.0 0.0
0900 29.0 22.3 43 45.0 379.4 469.5 0.0 0.0 0.0
1000 30.7 22.4 43 45.0 412.7 476.2 0.0 0.0 0.0
1100 32.6 22.6 42 45.0 451.4 484.7 0.0 0.0 0.0
1200 34.4 22.8 42 45.0 489.1 493.5 0.0 0.0 0.0
1300 35.8 22.9 42 45.0 507.1 498.9 0.0 0.0 0.0
1400 36.7 22.9 41 45.0 510.4 501.3 0.0 0.0 0.0
1500 37.0 23.0 41 45.0 513.5 503.6 0.0 0.0 0.0
1600 36.7 23.0 41 45.0 516.4 505.8 0.0 0.0 0.0
1700 35.9 23.1 41 45.0 519.0 507.9 0.0 0.0 0.0
1800 34.6 23.1 42 45.0 511.0 507.8 0.0 0.0 0.0
1900 33.2 23.0 42 45.0 484.1 503.5 0.0 0.0 0.0
2000 31.7 22.9 42 45.0 456.2 498.4 0.0 0.0 0.0
2100 30.4 22.8 43 45.0 431.8 493.5 0.0 0.0 0.0
2200 29.3 22.7 43 45.0 408.9 488.5 0.0 0.0 0.0
2300 28.4 22.6 43 45.0 389.8 483.9 0.0 0.0 0.0

ZONE: C1-52 Closing Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 43 124.4 1636.3 1614.2 0.0 0.0 0.0
0100 27.2 24.6 44 122.0 1598.5 1580.2 0.0 0.0 0.0
0200 26.6 24.5 44 119.7 1562.7 1547.5 0.0 0.0 0.0
0300 26.2 24.5 44 117.7 1532.2 1519.0 0.0 0.0 0.0
0400 25.8 24.5 44 115.9 1506.9 1494.7 0.0 0.0 0.0
0500 25.7 24.5 44 114.7 1490.8 1477.9 0.0 0.0 0.0
0600 25.9 24.5 44 114.4 1490.8 1474.3 0.0 0.0 0.0
0700 26.5 24.5 44 115.6 1514.8 1490.5 0.0 0.0 0.0
0800 27.5 24.5 44 118.7 1571.4 1533.9 0.0 0.0 0.0
0900 29.0 24.6 43 123.6 1657.9 1602.6 0.0 0.0 0.0
1000 30.7 24.6 43 129.5 1761.4 1686.7 0.0 0.0 0.0
1100 32.6 24.7 42 136.2 1877.0 1782.3 0.0 0.0 0.0
1200 34.4 24.7 42 142.7 1988.1 1875.9 0.0 0.0 0.0
1300 35.8 24.8 42 146.8 2056.7 1936.4 0.0 0.0 0.0
1400 36.7 24.8 41 149.0 2088.5 1967.5 0.0 0.0 0.0
1500 37.0 24.8 41 150.4 2107.5 1988.0 0.0 0.0 0.0
1600 36.7 24.8 41 150.9 2112.0 1996.5 0.0 0.0 0.0
1700 35.9 24.8 41 150.7 2101.5 1992.4 0.0 0.0 0.0
1800 34.6 24.8 42 148.5 2057.7 1960.7 0.0 0.0 0.0
1900 33.2 24.8 42 143.8 1969.4 1891.7 0.0 0.0 0.0
2000 31.7 24.7 42 138.8 1879.3 1819.5 0.0 0.0 0.0
2100 30.4 24.7 43 134.4 1802.7 1756.7 0.0 0.0 0.0
2200 29.3 24.6 43 130.5 1735.6 1700.5 0.0 0.0 0.0
2300 28.4 24.6 43 127.2 1680.5 1653.2 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 101 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-90 Lobby


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.5 43 93.5 1249.1 1205.8 0.0 0.0 0.0
0100 27.2 24.5 44 91.0 1207.9 1170.7 0.0 0.0 0.0
0200 26.6 24.5 44 88.4 1166.1 1134.9 0.0 0.0 0.0
0300 26.2 24.4 44 86.1 1130.6 1103.8 0.0 0.0 0.0
0400 25.8 24.4 44 84.2 1101.7 1077.7 0.0 0.0 0.0
0500 25.7 24.4 44 83.1 1086.6 1062.2 0.0 0.0 0.0
0600 25.9 24.4 44 83.2 1092.6 1063.2 0.0 0.0 0.0
0700 26.5 24.4 44 84.5 1120.2 1081.5 0.0 0.0 0.0
0800 27.5 24.5 44 87.5 1177.1 1123.2 0.0 0.0 0.0
0900 29.0 24.5 43 92.3 1264.0 1189.2 0.0 0.0 0.0
1000 30.7 24.6 43 98.1 1367.7 1269.7 0.0 0.0 0.0
1100 32.6 24.6 42 104.8 1488.5 1364.9 0.0 0.0 0.0
1200 34.4 24.7 42 111.3 1605.8 1459.1 0.0 0.0 0.0
1300 35.8 24.7 42 114.7 1662.9 1508.3 0.0 0.0 0.0
1400 36.7 24.8 41 115.6 1673.2 1521.3 0.0 0.0 0.0
1500 37.0 24.8 41 116.5 1682.9 1533.2 0.0 0.0 0.0
1600 36.7 24.8 41 117.2 1691.8 1544.2 0.0 0.0 0.0
1700 35.9 24.8 41 117.9 1700.2 1554.4 0.0 0.0 0.0
1800 34.6 24.8 42 116.8 1674.2 1537.9 0.0 0.0 0.0
1900 33.2 24.7 42 112.5 1590.4 1475.9 0.0 0.0 0.0
2000 31.7 24.7 42 107.9 1503.5 1409.7 0.0 0.0 0.0
2100 30.4 24.6 43 103.8 1427.5 1350.4 0.0 0.0 0.0
2200 29.3 24.6 43 99.7 1356.0 1293.7 0.0 0.0 0.0
2300 28.4 24.5 43 96.3 1296.4 1245.2 0.0 0.0 0.0

ZONE: C1-93 Bridal Suite


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 43 187.6 2520.2 2447.9 0.0 0.0 0.0
0100 27.2 24.6 44 184.9 2477.7 2409.5 0.0 0.0 0.0
0200 26.6 24.6 44 182.1 2434.5 2370.5 0.0 0.0 0.0
0300 26.2 24.6 44 179.8 2397.8 2336.6 0.0 0.0 0.0
0400 25.8 24.6 44 177.8 2367.9 2308.4 0.0 0.0 0.0
0500 25.7 24.6 44 176.6 2352.3 2292.1 0.0 0.0 0.0
0600 25.9 24.6 44 176.8 2358.4 2294.1 0.0 0.0 0.0
0700 26.5 24.6 44 178.3 2387.0 2315.4 0.0 0.0 0.0
0800 27.5 24.6 44 181.6 2445.9 2362.5 0.0 0.0 0.0
0900 29.0 24.7 43 186.8 2535.7 2436.4 0.0 0.0 0.0
1000 30.7 24.7 43 193.0 2642.9 2526.2 0.0 0.0 0.0
1100 32.6 24.7 42 200.3 2767.7 2632.0 0.0 0.0 0.0
1200 34.4 24.8 42 207.5 2888.9 2736.2 0.0 0.0 0.0
1300 35.8 24.8 42 211.2 2947.6 2789.5 0.0 0.0 0.0
1400 36.7 24.8 41 212.1 2958.3 2802.9 0.0 0.0 0.0
1500 37.0 24.8 41 212.9 2968.2 2815.0 0.0 0.0 0.0
1600 36.7 24.8 41 213.7 2977.5 2826.3 0.0 0.0 0.0
1700 35.9 24.8 41 214.4 2986.2 2836.8 0.0 0.0 0.0
1800 34.6 24.8 42 213.1 2959.6 2817.7 0.0 0.0 0.0
1900 33.2 24.8 42 208.3 2873.0 2747.9 0.0 0.0 0.0
2000 31.7 24.8 42 203.2 2783.2 2673.7 0.0 0.0 0.0
2100 30.4 24.7 43 198.7 2704.6 2607.7 0.0 0.0 0.0
2200 29.3 24.7 43 194.3 2630.7 2544.7 0.0 0.0 0.0
2300 28.4 24.7 43 190.6 2569.1 2491.2 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 102 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-101 Assistance HK


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 43 63.6 840.0 829.2 0.0 0.0 0.0
0100 27.2 24.6 44 62.7 826.2 816.4 0.0 0.0 0.0
0200 26.6 24.6 44 61.8 813.2 804.2 0.0 0.0 0.0
0300 26.2 24.6 44 61.1 802.1 793.7 0.0 0.0 0.0
0400 25.8 24.6 44 60.4 792.8 784.6 0.0 0.0 0.0
0500 25.7 24.6 44 60.0 786.9 778.4 0.0 0.0 0.0
0600 25.9 24.6 44 59.9 786.7 777.1 0.0 0.0 0.0
0700 26.5 24.6 44 60.3 795.4 783.3 0.0 0.0 0.0
0800 27.5 24.6 44 61.5 816.3 800.1 0.0 0.0 0.0
0900 29.0 24.7 43 63.4 848.2 826.5 0.0 0.0 0.0
1000 30.7 24.7 43 65.6 886.4 858.7 0.0 0.0 0.0
1100 32.6 24.7 42 68.1 928.9 895.1 0.0 0.0 0.0
1200 34.4 24.8 42 70.6 969.7 930.6 0.0 0.0 0.0
1300 35.8 24.8 42 72.2 995.4 953.8 0.0 0.0 0.0
1400 36.7 24.8 41 73.0 1007.8 966.0 0.0 0.0 0.0
1500 37.0 24.8 41 73.5 1015.1 973.8 0.0 0.0 0.0
1600 36.7 24.8 41 73.7 1016.6 976.7 0.0 0.0 0.0
1700 35.9 24.8 41 73.6 1012.1 974.4 0.0 0.0 0.0
1800 34.6 24.8 42 72.7 995.5 961.6 0.0 0.0 0.0
1900 33.2 24.8 42 70.9 962.7 934.9 0.0 0.0 0.0
2000 31.7 24.8 42 69.0 929.4 907.1 0.0 0.0 0.0
2100 30.4 24.7 43 67.3 901.1 883.1 0.0 0.0 0.0
2200 29.3 24.7 43 65.8 876.5 861.7 0.0 0.0 0.0
2300 28.4 24.7 43 64.6 856.3 843.9 0.0 0.0 0.0

ZONE: C1-100 HK Manager


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 43 61.0 803.5 798.2 0.0 0.0 0.0
0100 27.2 24.7 44 60.3 793.2 788.7 0.0 0.0 0.0
0200 26.6 24.7 44 59.7 783.8 779.8 0.0 0.0 0.0
0300 26.2 24.7 44 59.1 775.8 772.0 0.0 0.0 0.0
0400 25.8 24.7 44 58.7 769.1 765.3 0.0 0.0 0.0
0500 25.7 24.6 44 58.3 764.5 760.4 0.0 0.0 0.0
0600 25.9 24.6 44 58.2 763.8 758.9 0.0 0.0 0.0
0700 26.5 24.6 44 58.5 770.1 763.3 0.0 0.0 0.0
0800 27.5 24.7 44 59.4 786.0 776.0 0.0 0.0 0.0
0900 29.0 24.7 43 60.8 810.4 796.2 0.0 0.0 0.0
1000 30.7 24.7 43 62.5 839.5 820.8 0.0 0.0 0.0
1100 32.6 24.8 42 64.4 871.4 848.2 0.0 0.0 0.0
1200 34.4 24.8 42 66.3 902.0 875.0 0.0 0.0 0.0
1300 35.8 24.8 42 67.5 922.6 893.6 0.0 0.0 0.0
1400 36.7 24.8 41 68.3 934.1 904.7 0.0 0.0 0.0
1500 37.0 24.8 41 68.8 940.5 911.6 0.0 0.0 0.0
1600 36.7 24.8 41 68.9 941.3 913.6 0.0 0.0 0.0
1700 35.9 24.8 41 68.7 936.1 910.5 0.0 0.0 0.0
1800 34.6 24.8 42 67.9 921.8 899.4 0.0 0.0 0.0
1900 33.2 24.8 42 66.5 896.4 878.7 0.0 0.0 0.0
2000 31.7 24.8 42 65.0 870.6 857.2 0.0 0.0 0.0
2100 30.4 24.7 43 63.8 849.0 838.7 0.0 0.0 0.0
2200 29.3 24.7 43 62.7 830.6 822.7 0.0 0.0 0.0
2300 28.4 24.7 43 61.7 815.6 809.3 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 103 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-102 Houskeepking


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 43 161.3 2114.8 2101.4 0.0 0.0 0.0
0100 27.2 24.6 44 158.9 2076.6 2066.5 0.0 0.0 0.0
0200 26.6 24.6 44 156.6 2041.1 2033.7 0.0 0.0 0.0
0300 26.2 24.6 44 154.5 2011.0 2005.0 0.0 0.0 0.0
0400 25.8 24.6 44 152.8 1985.8 1980.3 0.0 0.0 0.0
0500 25.7 24.6 44 151.5 1968.8 1962.2 0.0 0.0 0.0
0600 25.9 24.6 44 151.1 1966.9 1956.6 0.0 0.0 0.0
0700 26.5 24.6 44 152.2 1990.6 1972.0 0.0 0.0 0.0
0800 27.5 24.6 44 155.4 2049.5 2016.9 0.0 0.0 0.0
0900 29.0 24.6 43 160.4 2139.5 2088.1 0.0 0.0 0.0
1000 30.7 24.7 43 166.5 2247.2 2175.6 0.0 0.0 0.0
1100 32.6 24.7 42 173.3 2366.0 2273.9 0.0 0.0 0.0
1200 34.4 24.8 42 180.0 2479.8 2370.0 0.0 0.0 0.0
1300 35.8 24.8 42 184.5 2554.5 2436.0 0.0 0.0 0.0
1400 36.7 24.8 41 187.1 2594.6 2474.7 0.0 0.0 0.0
1500 37.0 24.8 41 188.8 2617.4 2499.1 0.0 0.0 0.0
1600 36.7 24.8 41 189.4 2620.6 2507.5 0.0 0.0 0.0
1700 35.9 24.8 41 188.8 2603.6 2498.9 0.0 0.0 0.0
1800 34.6 24.8 42 186.2 2552.6 2461.9 0.0 0.0 0.0
1900 33.2 24.8 42 181.3 2459.1 2389.1 0.0 0.0 0.0
2000 31.7 24.7 42 176.0 2364.2 2313.1 0.0 0.0 0.0
2100 30.4 24.7 43 171.5 2284.3 2247.5 0.0 0.0 0.0
2200 29.3 24.7 43 167.5 2215.8 2189.9 0.0 0.0 0.0
2300 28.4 24.7 43 164.1 2159.8 2141.5 0.0 0.0 0.0

ZONE: C1-109 Nurse


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 43 68.9 905.0 895.1 0.0 0.0 0.0
0100 27.2 24.6 44 67.7 885.7 877.6 0.0 0.0 0.0
0200 26.6 24.6 44 66.5 867.4 860.9 0.0 0.0 0.0
0300 26.2 24.6 44 65.4 852.0 846.3 0.0 0.0 0.0
0400 25.8 24.5 44 64.6 839.1 833.9 0.0 0.0 0.0
0500 25.7 24.5 44 63.9 830.7 825.1 0.0 0.0 0.0
0600 25.9 24.5 44 63.8 830.4 822.9 0.0 0.0 0.0
0700 26.5 24.5 44 64.4 842.6 831.0 0.0 0.0 0.0
0800 27.5 24.6 44 65.9 871.8 853.4 0.0 0.0 0.0
0900 29.0 24.6 43 68.5 916.5 888.8 0.0 0.0 0.0
1000 30.7 24.6 43 71.5 969.9 932.2 0.0 0.0 0.0
1100 32.6 24.7 42 74.9 1029.3 981.3 0.0 0.0 0.0
1200 34.4 24.8 42 78.3 1086.4 1029.3 0.0 0.0 0.0
1300 35.8 24.8 42 80.4 1122.3 1061.1 0.0 0.0 0.0
1400 36.7 24.8 41 81.6 1139.9 1078.2 0.0 0.0 0.0
1500 37.0 24.8 41 82.4 1150.1 1089.2 0.0 0.0 0.0
1600 36.7 24.8 41 82.6 1152.2 1093.6 0.0 0.0 0.0
1700 35.9 24.8 41 82.5 1145.9 1090.8 0.0 0.0 0.0
1800 34.6 24.8 42 81.3 1122.4 1073.8 0.0 0.0 0.0
1900 33.2 24.8 42 78.9 1076.6 1038.1 0.0 0.0 0.0
2000 31.7 24.7 42 76.3 1029.9 1000.7 0.0 0.0 0.0
2100 30.4 24.7 43 74.0 990.3 968.2 0.0 0.0 0.0
2200 29.3 24.7 43 72.0 955.9 939.4 0.0 0.0 0.0
2300 28.4 24.6 43 70.3 927.6 915.1 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 104 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-112 HR Reception


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 43 106.2 1392.6 1384.2 0.0 0.0 0.0
0100 27.2 24.6 44 104.6 1367.7 1361.4 0.0 0.0 0.0
0200 26.6 24.6 44 103.1 1344.7 1340.1 0.0 0.0 0.0
0300 26.2 24.6 44 101.8 1325.1 1321.4 0.0 0.0 0.0
0400 25.8 24.6 44 100.7 1308.7 1305.3 0.0 0.0 0.0
0500 25.7 24.6 44 99.9 1297.6 1293.5 0.0 0.0 0.0
0600 25.9 24.6 44 99.6 1296.3 1289.8 0.0 0.0 0.0
0700 26.5 24.6 44 100.3 1311.7 1299.8 0.0 0.0 0.0
0800 27.5 24.6 44 102.4 1350.1 1329.0 0.0 0.0 0.0
0900 29.0 24.6 43 105.6 1408.6 1375.4 0.0 0.0 0.0
1000 30.7 24.7 43 109.6 1478.8 1432.4 0.0 0.0 0.0
1100 32.6 24.7 42 114.1 1556.0 1496.3 0.0 0.0 0.0
1200 34.4 24.8 42 118.4 1630.1 1558.9 0.0 0.0 0.0
1300 35.8 24.8 42 121.4 1680.2 1603.1 0.0 0.0 0.0
1400 36.7 24.8 41 123.1 1706.6 1628.5 0.0 0.0 0.0
1500 37.0 24.8 41 124.2 1721.6 1644.6 0.0 0.0 0.0
1600 36.7 24.8 41 124.6 1723.7 1650.1 0.0 0.0 0.0
1700 35.9 24.8 41 124.2 1712.4 1644.3 0.0 0.0 0.0
1800 34.6 24.8 42 122.5 1677.7 1619.0 0.0 0.0 0.0
1900 33.2 24.8 42 119.2 1616.7 1571.6 0.0 0.0 0.0
2000 31.7 24.7 42 115.8 1554.9 1522.0 0.0 0.0 0.0
2100 30.4 24.7 43 112.9 1502.9 1479.3 0.0 0.0 0.0
2200 29.3 24.7 43 110.3 1458.3 1441.7 0.0 0.0 0.0
2300 28.4 24.7 43 108.1 1421.9 1410.3 0.0 0.0 0.0

ZONE: C1-113 HR Clerk


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 43 51.8 679.6 682.2 0.0 0.0 0.0
0100 27.2 24.8 44 51.5 675.1 677.9 0.0 0.0 0.0
0200 26.6 24.8 44 51.2 671.4 674.2 0.0 0.0 0.0
0300 26.2 24.8 44 51.0 668.2 670.9 0.0 0.0 0.0
0400 25.8 24.7 44 50.8 665.5 668.1 0.0 0.0 0.0
0500 25.7 24.7 44 50.6 663.1 665.6 0.0 0.0 0.0
0600 25.9 24.7 44 50.5 661.9 664.1 0.0 0.0 0.0
0700 26.5 24.7 44 50.7 664.4 665.8 0.0 0.0 0.0
0800 27.5 24.8 44 51.1 672.1 672.0 0.0 0.0 0.0
0900 29.0 24.8 43 51.8 683.9 681.8 0.0 0.0 0.0
1000 30.7 24.8 43 52.6 698.0 693.9 0.0 0.0 0.0
1100 32.6 24.8 42 53.5 712.7 706.8 0.0 0.0 0.0
1200 34.4 24.8 42 54.3 726.7 719.2 0.0 0.0 0.0
1300 35.8 24.8 42 55.0 738.6 730.0 0.0 0.0 0.0
1400 36.7 24.9 41 55.6 747.2 738.1 0.0 0.0 0.0
1500 37.0 24.9 41 55.9 751.6 742.7 0.0 0.0 0.0
1600 36.7 24.9 41 55.9 751.4 743.3 0.0 0.0 0.0
1700 35.9 24.9 41 55.7 746.2 739.6 0.0 0.0 0.0
1800 34.6 24.9 42 55.2 736.5 731.8 0.0 0.0 0.0
1900 33.2 24.8 42 54.4 723.5 721.0 0.0 0.0 0.0
2000 31.7 24.8 42 53.7 710.6 710.0 0.0 0.0 0.0
2100 30.4 24.8 43 53.1 700.0 700.8 0.0 0.0 0.0
2200 29.3 24.8 43 52.6 691.7 693.4 0.0 0.0 0.0
2300 28.4 24.8 43 52.1 685.1 687.3 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 105 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-114 DR of HR
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 43 63.7 845.2 832.0 0.0 0.0 0.0
0100 27.2 24.6 44 62.9 832.2 819.9 0.0 0.0 0.0
0200 26.6 24.6 44 62.1 819.8 808.3 0.0 0.0 0.0
0300 26.2 24.6 44 61.3 809.3 798.2 0.0 0.0 0.0
0400 25.8 24.6 44 60.7 800.5 789.7 0.0 0.0 0.0
0500 25.7 24.6 44 60.3 795.0 784.0 0.0 0.0 0.0
0600 25.9 24.6 44 60.3 795.1 783.1 0.0 0.0 0.0
0700 26.5 24.6 44 60.7 803.3 789.3 0.0 0.0 0.0
0800 27.5 24.6 44 61.9 822.8 805.4 0.0 0.0 0.0
0900 29.0 24.7 43 63.6 852.5 830.6 0.0 0.0 0.0
1000 30.7 24.7 43 65.7 888.1 861.2 0.0 0.0 0.0
1100 32.6 24.7 42 68.1 927.9 895.8 0.0 0.0 0.0
1200 34.4 24.8 42 70.5 966.1 929.6 0.0 0.0 0.0
1300 35.8 24.8 42 72.0 990.1 951.5 0.0 0.0 0.0
1400 36.7 24.8 41 72.7 1000.8 962.2 0.0 0.0 0.0
1500 37.0 24.8 41 73.2 1007.3 969.1 0.0 0.0 0.0
1600 36.7 24.8 41 73.3 1008.9 971.8 0.0 0.0 0.0
1700 35.9 24.8 41 73.2 1005.5 970.0 0.0 0.0 0.0
1800 34.6 24.8 42 72.4 990.1 957.8 0.0 0.0 0.0
1900 33.2 24.8 42 70.7 959.8 932.5 0.0 0.0 0.0
2000 31.7 24.8 42 68.8 928.8 906.1 0.0 0.0 0.0
2100 30.4 24.7 43 67.3 902.5 883.3 0.0 0.0 0.0
2200 29.3 24.7 43 65.9 879.4 863.0 0.0 0.0 0.0
2300 28.4 24.7 43 64.7 860.4 845.9 0.0 0.0 0.0

ZONE: C1-116 DR of Training


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 43 53.0 695.7 698.2 0.0 0.0 0.0
0100 27.2 24.8 44 52.7 691.2 693.8 0.0 0.0 0.0
0200 26.6 24.8 44 52.4 687.4 690.1 0.0 0.0 0.0
0300 26.2 24.8 44 52.2 684.3 686.9 0.0 0.0 0.0
0400 25.8 24.7 44 52.0 681.5 684.1 0.0 0.0 0.0
0500 25.7 24.7 44 51.8 679.1 681.5 0.0 0.0 0.0
0600 25.9 24.7 44 51.7 678.0 680.1 0.0 0.0 0.0
0700 26.5 24.7 44 51.9 680.5 681.8 0.0 0.0 0.0
0800 27.5 24.8 44 52.3 688.2 688.0 0.0 0.0 0.0
0900 29.0 24.8 43 53.0 699.9 697.9 0.0 0.0 0.0
1000 30.7 24.8 43 53.8 714.0 710.0 0.0 0.0 0.0
1100 32.6 24.8 42 54.7 728.8 722.9 0.0 0.0 0.0
1200 34.4 24.8 42 55.5 742.8 735.3 0.0 0.0 0.0
1300 35.8 24.9 42 56.3 754.6 746.1 0.0 0.0 0.0
1400 36.7 24.9 41 56.8 763.2 754.3 0.0 0.0 0.0
1500 37.0 24.9 41 57.1 767.7 758.9 0.0 0.0 0.0
1600 36.7 24.9 41 57.2 767.4 759.4 0.0 0.0 0.0
1700 35.9 24.9 41 56.9 762.3 755.7 0.0 0.0 0.0
1800 34.6 24.9 42 56.4 752.6 747.9 0.0 0.0 0.0
1900 33.2 24.8 42 55.6 739.6 737.1 0.0 0.0 0.0
2000 31.7 24.8 42 54.9 726.6 726.1 0.0 0.0 0.0
2100 30.4 24.8 43 54.3 716.1 716.8 0.0 0.0 0.0
2200 29.3 24.8 43 53.8 707.8 709.4 0.0 0.0 0.0
2300 28.4 24.8 43 53.3 701.1 703.3 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 106 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-115 Training Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 43 270.5 3489.1 3502.9 0.0 0.0 0.0
0100 27.2 24.6 44 269.4 3470.6 3485.7 0.0 0.0 0.0
0200 26.6 24.5 44 268.5 3454.7 3470.5 0.0 0.0 0.0
0300 26.2 24.5 44 267.7 3441.1 3457.0 0.0 0.0 0.0
0400 25.8 24.5 44 267.0 3429.5 3445.1 0.0 0.0 0.0
0500 25.7 24.5 44 266.4 3420.1 3435.1 0.0 0.0 0.0
0600 25.9 24.5 44 266.0 3416.4 3429.6 0.0 0.0 0.0
0700 26.5 24.5 44 266.4 3427.2 3435.8 0.0 0.0 0.0
0800 27.5 24.5 44 267.8 3458.0 3458.2 0.0 0.0 0.0
0900 29.0 24.6 43 270.0 3505.1 3494.5 0.0 0.0 0.0
1000 30.7 24.6 43 272.7 3561.5 3539.3 0.0 0.0 0.0
1100 32.6 24.6 42 275.6 3621.6 3588.1 0.0 0.0 0.0
1200 34.4 24.7 42 278.5 3678.6 3635.7 0.0 0.0 0.0
1300 35.8 24.7 42 280.8 3724.1 3675.1 0.0 0.0 0.0
1400 36.7 24.7 41 282.5 3754.9 3703.5 0.0 0.0 0.0
1500 37.0 24.7 41 283.5 3771.1 3720.4 0.0 0.0 0.0
1600 36.7 24.7 41 283.8 3770.8 3724.2 0.0 0.0 0.0
1700 35.9 24.7 41 283.2 3753.5 3714.0 0.0 0.0 0.0
1800 34.6 24.7 42 281.6 3717.5 3688.3 0.0 0.0 0.0
1900 33.2 24.7 42 279.3 3666.3 3649.5 0.0 0.0 0.0
2000 31.7 24.6 42 276.9 3615.0 3609.3 0.0 0.0 0.0
2100 30.4 24.6 43 274.9 3572.9 3575.1 0.0 0.0 0.0
2200 29.3 24.6 43 273.1 3538.9 3546.7 0.0 0.0 0.0
2300 28.4 24.6 43 271.7 3511.5 3523.0 0.0 0.0 0.0

ZONE: C1-117 ENG. Reception


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 43 165.2 2179.2 2170.8 0.0 0.0 0.0
0100 27.2 24.7 44 163.9 2160.1 2152.6 0.0 0.0 0.0
0200 26.6 24.7 44 162.7 2142.9 2135.9 0.0 0.0 0.0
0300 26.2 24.7 44 161.7 2128.3 2121.5 0.0 0.0 0.0
0400 25.8 24.7 44 160.9 2115.9 2109.0 0.0 0.0 0.0
0500 25.7 24.7 44 160.2 2106.9 2099.5 0.0 0.0 0.0
0600 25.9 24.7 44 160.0 2104.7 2096.0 0.0 0.0 0.0
0700 26.5 24.7 44 160.6 2116.3 2104.5 0.0 0.0 0.0
0800 27.5 24.7 44 162.3 2146.8 2129.7 0.0 0.0 0.0
0900 29.0 24.7 43 165.1 2193.3 2169.4 0.0 0.0 0.0
1000 30.7 24.8 43 168.4 2249.0 2217.8 0.0 0.0 0.0
1100 32.6 24.8 42 172.0 2309.5 2271.1 0.0 0.0 0.0
1200 34.4 24.8 42 175.6 2367.3 2322.7 0.0 0.0 0.0
1300 35.8 24.8 42 178.2 2409.3 2361.4 0.0 0.0 0.0
1400 36.7 24.9 41 179.8 2434.3 2385.6 0.0 0.0 0.0
1500 37.0 24.9 41 180.8 2447.9 2400.0 0.0 0.0 0.0
1600 36.7 24.9 41 181.0 2448.7 2403.2 0.0 0.0 0.0
1700 35.9 24.9 41 180.4 2436.3 2394.6 0.0 0.0 0.0
1800 34.6 24.8 42 178.7 2405.4 2369.6 0.0 0.0 0.0
1900 33.2 24.8 42 175.9 2356.0 2328.0 0.0 0.0 0.0
2000 31.7 24.8 42 173.0 2306.3 2285.2 0.0 0.0 0.0
2100 30.4 24.8 43 170.5 2264.8 2248.8 0.0 0.0 0.0
2200 29.3 24.8 43 168.4 2230.1 2217.8 0.0 0.0 0.0
2300 28.4 24.8 43 166.6 2202.0 2192.1 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 107 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-119 DIR of Engineerin


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 43 52.0 688.6 678.9 0.0 0.0 0.0
0100 27.2 24.6 44 51.3 677.7 668.8 0.0 0.0 0.0
0200 26.6 24.6 44 50.6 667.4 659.1 0.0 0.0 0.0
0300 26.2 24.6 44 50.0 658.6 650.8 0.0 0.0 0.0
0400 25.8 24.6 44 49.5 651.3 643.6 0.0 0.0 0.0
0500 25.7 24.6 44 49.2 646.6 638.8 0.0 0.0 0.0
0600 25.9 24.6 44 49.1 646.6 637.8 0.0 0.0 0.0
0700 26.5 24.6 44 49.5 653.5 642.9 0.0 0.0 0.0
0800 27.5 24.6 44 50.4 669.9 656.2 0.0 0.0 0.0
0900 29.0 24.7 43 51.9 694.9 677.2 0.0 0.0 0.0
1000 30.7 24.7 43 53.7 724.9 702.7 0.0 0.0 0.0
1100 32.6 24.7 42 55.7 758.3 731.6 0.0 0.0 0.0
1200 34.4 24.8 42 57.6 790.4 759.8 0.0 0.0 0.0
1300 35.8 24.8 42 58.9 810.8 778.3 0.0 0.0 0.0
1400 36.7 24.8 41 59.5 820.3 787.7 0.0 0.0 0.0
1500 37.0 24.8 41 59.9 825.9 793.7 0.0 0.0 0.0
1600 36.7 24.8 41 60.1 827.2 795.9 0.0 0.0 0.0
1700 35.9 24.8 41 60.0 824.0 794.3 0.0 0.0 0.0
1800 34.6 24.8 42 59.3 810.6 783.9 0.0 0.0 0.0
1900 33.2 24.8 42 57.8 785.0 762.7 0.0 0.0 0.0
2000 31.7 24.8 42 56.3 758.9 740.7 0.0 0.0 0.0
2100 30.4 24.7 43 55.0 736.7 721.6 0.0 0.0 0.0
2200 29.3 24.7 43 53.8 717.3 704.7 0.0 0.0 0.0
2300 28.4 24.7 43 52.8 701.4 690.5 0.0 0.0 0.0

ZONE: C1-122 M+E Workshop


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.9 43 110.0 1160.0 1220.0 0.0 0.0 0.0
0100 27.2 22.8 44 110.0 1147.5 1213.8 0.0 0.0 0.0
0200 26.6 22.8 44 110.0 1136.7 1207.9 0.0 0.0 0.0
0300 26.2 22.7 44 110.0 1127.5 1202.4 0.0 0.0 0.0
0400 25.8 22.7 44 110.0 1119.6 1197.2 0.0 0.0 0.0
0500 25.7 22.6 44 110.0 1113.3 1192.4 0.0 0.0 0.0
0600 25.9 22.6 44 110.0 1111.0 1188.9 0.0 0.0 0.0
0700 26.5 22.6 44 110.0 1118.3 1188.6 0.0 0.0 0.0
0800 27.5 22.7 44 110.0 1138.9 1193.1 0.0 0.0 0.0
0900 29.0 22.7 43 110.0 1170.5 1202.0 0.0 0.0 0.0
1000 30.7 22.8 43 110.0 1208.4 1214.0 0.0 0.0 0.0
1100 32.6 22.9 42 110.0 1248.8 1228.0 0.0 0.0 0.0
1200 34.4 23.1 42 110.0 1287.2 1242.4 0.0 0.0 0.0
1300 35.8 23.2 42 110.0 1317.6 1255.1 0.0 0.0 0.0
1400 36.7 23.3 41 110.0 1337.9 1265.2 0.0 0.0 0.0
1500 37.0 23.3 41 110.0 1348.6 1272.5 0.0 0.0 0.0
1600 36.7 23.3 41 110.0 1348.5 1276.3 0.0 0.0 0.0
1700 35.9 23.3 41 110.0 1337.1 1276.1 0.0 0.0 0.0
1800 34.6 23.3 42 110.0 1313.3 1271.3 0.0 0.0 0.0
1900 33.2 23.2 42 110.0 1279.0 1262.1 0.0 0.0 0.0
2000 31.7 23.1 42 110.0 1244.6 1251.8 0.0 0.0 0.0
2100 30.4 23.1 43 110.0 1216.3 1242.4 0.0 0.0 0.0
2200 29.3 23.0 43 110.0 1193.4 1234.0 0.0 0.0 0.0
2300 28.4 22.9 43 110.0 1175.0 1226.6 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 108 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-121 Carpenter Shop


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.8 43 110.1 1121.2 1217.7 0.0 0.0 0.0
0100 27.2 22.8 44 110.1 1103.1 1208.8 0.0 0.0 0.0
0200 26.6 22.7 44 110.1 1086.3 1200.0 0.0 0.0 0.0
0300 26.2 22.6 44 110.1 1072.0 1191.9 0.0 0.0 0.0
0400 25.8 22.6 44 110.1 1060.0 1184.5 0.0 0.0 0.0
0500 25.7 22.5 44 110.1 1052.1 1178.4 0.0 0.0 0.0
0600 25.9 22.5 44 110.1 1051.4 1174.9 0.0 0.0 0.0
0700 26.5 22.5 44 110.1 1062.7 1175.8 0.0 0.0 0.0
0800 27.5 22.6 44 110.1 1090.3 1183.0 0.0 0.0 0.0
0900 29.0 22.7 43 110.1 1132.4 1196.3 0.0 0.0 0.0
1000 30.7 22.8 43 110.1 1182.9 1213.8 0.0 0.0 0.0
1100 32.6 23.0 42 110.1 1238.7 1234.5 0.0 0.0 0.0
1200 34.4 23.2 42 110.1 1292.2 1255.8 0.0 0.0 0.0
1300 35.8 23.3 42 110.1 1327.7 1271.9 0.0 0.0 0.0
1400 36.7 23.4 41 110.1 1345.7 1282.4 0.0 0.0 0.0
1500 37.0 23.4 41 110.1 1356.0 1290.3 0.0 0.0 0.0
1600 36.7 23.5 41 110.1 1357.8 1295.1 0.0 0.0 0.0
1700 35.9 23.5 41 110.1 1350.6 1296.5 0.0 0.0 0.0
1800 34.6 23.5 42 110.1 1326.4 1291.4 0.0 0.0 0.0
1900 33.2 23.3 42 110.1 1282.8 1278.5 0.0 0.0 0.0
2000 31.7 23.2 42 110.1 1238.5 1264.0 0.0 0.0 0.0
2100 30.4 23.1 43 110.1 1201.1 1250.7 0.0 0.0 0.0
2200 29.3 23.0 43 110.1 1168.8 1238.4 0.0 0.0 0.0
2300 28.4 22.9 43 110.1 1142.4 1227.4 0.0 0.0 0.0

ZONE: C1-125 Electric Repair


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.9 43 80.0 840.5 885.0 0.0 0.0 0.0
0100 27.2 22.8 44 80.0 831.4 879.1 0.0 0.0 0.0
0200 26.6 22.7 44 80.0 822.7 873.4 0.0 0.0 0.0
0300 26.2 22.7 44 80.0 815.3 868.2 0.0 0.0 0.0
0400 25.8 22.6 44 80.0 809.2 863.6 0.0 0.0 0.0
0500 25.7 22.6 44 80.0 805.4 860.2 0.0 0.0 0.0
0600 25.9 22.6 44 80.0 805.6 858.8 0.0 0.0 0.0
0700 26.5 22.6 44 80.0 811.4 860.5 0.0 0.0 0.0
0800 27.5 22.6 44 80.0 824.8 866.3 0.0 0.0 0.0
0900 29.0 22.8 43 80.0 845.3 876.2 0.0 0.0 0.0
1000 30.7 22.9 43 80.0 869.8 888.7 0.0 0.0 0.0
1100 32.6 23.1 42 80.0 897.4 903.4 0.0 0.0 0.0
1200 34.4 23.2 42 80.0 923.9 918.2 0.0 0.0 0.0
1300 35.8 23.3 42 80.0 940.1 928.2 0.0 0.0 0.0
1400 36.7 23.4 41 80.0 946.8 933.6 0.0 0.0 0.0
1500 37.0 23.4 41 80.0 951.0 937.6 0.0 0.0 0.0
1600 36.7 23.5 41 80.0 952.2 940.0 0.0 0.0 0.0
1700 35.9 23.5 41 80.0 950.4 940.8 0.0 0.0 0.0
1800 34.6 23.4 42 80.0 940.4 937.1 0.0 0.0 0.0
1900 33.2 23.3 42 80.0 919.6 927.6 0.0 0.0 0.0
2000 31.7 23.2 42 80.0 898.4 917.2 0.0 0.0 0.0
2100 30.4 23.1 43 80.0 880.3 907.8 0.0 0.0 0.0
2200 29.3 23.0 43 80.0 864.3 899.1 0.0 0.0 0.0
2300 28.4 22.9 43 80.0 851.1 891.5 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 109 of 263


Hourly Zone Loads for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:02PM

ZONE: C1-124 Paint Shop


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.8 43 110.3 1074.9 1209.0 0.0 0.0 0.0
0100 27.2 22.7 44 110.3 1050.2 1196.4 0.0 0.0 0.0
0200 26.6 22.6 44 110.3 1026.0 1183.7 0.0 0.0 0.0
0300 26.2 22.5 44 110.3 1005.4 1172.2 0.0 0.0 0.0
0400 25.8 22.4 44 110.3 988.4 1162.2 0.0 0.0 0.0
0500 25.7 22.3 44 110.3 978.6 1155.1 0.0 0.0 0.0
0600 25.9 22.3 44 110.3 980.4 1152.8 0.0 0.0 0.0
0700 26.5 22.3 44 110.3 996.6 1156.8 0.0 0.0 0.0
0800 27.5 22.4 44 110.3 1032.3 1169.4 0.0 0.0 0.0
0900 29.0 22.6 43 110.3 1086.8 1190.6 0.0 0.0 0.0
1000 30.7 22.8 43 110.3 1151.9 1217.4 0.0 0.0 0.0
1100 32.6 23.1 42 110.3 1226.2 1249.2 0.0 0.0 0.0
1200 34.4 23.4 42 110.3 1297.9 1281.3 0.0 0.0 0.0
1300 35.8 23.5 42 110.3 1332.5 1299.2 0.0 0.0 0.0
1400 36.7 23.6 41 110.3 1346.0 1308.7 0.0 0.0 0.0
1500 37.0 23.6 41 110.3 1355.0 1316.1 0.0 0.0 0.0
1600 36.7 23.7 41 110.3 1359.0 1321.3 0.0 0.0 0.0
1700 35.9 23.7 41 110.3 1357.9 1324.1 0.0 0.0 0.0
1800 34.6 23.7 42 110.3 1340.7 1320.0 0.0 0.0 0.0
1900 33.2 23.5 42 110.3 1286.5 1300.2 0.0 0.0 0.0
2000 31.7 23.3 42 110.3 1230.9 1278.3 0.0 0.0 0.0
2100 30.4 23.2 43 110.3 1183.0 1258.4 0.0 0.0 0.0
2200 29.3 23.0 43 110.3 1139.5 1239.5 0.0 0.0 0.0
2300 28.4 22.9 43 110.3 1103.6 1223.0 0.0 0.0 0.0

ZONE: C1-25 Corridor 1


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.5 43 686.6 8792.8 8823.8 0.0 0.0 0.0
0100 27.2 24.4 44 665.8 8437.4 8535.5 0.0 0.0 0.0
0200 26.6 24.4 44 645.1 8092.0 8250.8 0.0 0.0 0.0
0300 26.2 24.4 44 626.7 7798.8 7998.6 0.0 0.0 0.0
0400 25.8 24.4 44 610.7 7556.8 7780.0 0.0 0.0 0.0
0500 25.7 24.4 44 599.5 7412.1 7627.5 0.0 0.0 0.0
0600 25.9 24.4 44 596.5 7428.9 7587.3 0.0 0.0 0.0
0700 26.5 24.4 44 604.7 7658.8 7698.1 0.0 0.0 0.0
0800 27.5 24.4 44 628.1 8178.6 8016.9 0.0 0.0 0.0
0900 29.0 24.4 43 666.0 8972.3 8538.8 0.0 0.0 0.0
1000 30.7 24.5 43 712.8 9921.1 9187.8 0.0 0.0 0.0
1100 32.6 24.6 42 766.7 10995.1 9944.2 0.0 0.0 0.0
1200 34.4 24.7 42 819.7 12030.8 10697.5 0.0 0.0 0.0
1300 35.8 24.7 42 852.3 12619.9 11166.6 0.0 0.0 0.0
1400 36.7 24.7 41 868.3 12851.2 11396.4 0.0 0.0 0.0
1500 37.0 24.7 41 879.9 12998.6 11564.9 0.0 0.0 0.0
1600 36.7 24.8 41 886.8 13052.3 11665.9 0.0 0.0 0.0
1700 35.9 24.8 41 888.9 13009.1 11695.4 0.0 0.0 0.0
1800 34.6 24.7 42 876.3 12664.5 11513.0 0.0 0.0 0.0
1900 33.2 24.7 42 841.4 11867.9 11008.9 0.0 0.0 0.0
2000 31.7 24.6 42 803.4 11051.0 10465.8 0.0 0.0 0.0
2100 30.4 24.6 43 769.3 10351.0 9981.9 0.0 0.0 0.0
2200 29.3 24.5 43 737.5 9723.7 9533.0 0.0 0.0 0.0
2300 28.4 24.5 43 709.9 9206.0 9146.8 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 110 of 263


System Psychrometrics for AHU-H-C3-02 - C1 Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:04PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 1430 400 19890 12294
Vent - Return Mixing Outlet 29.9 0.01016 3440 698 - -
Preheat Coil Outlet 29.9 0.01016 3440 698 0 -
Central Cooling Coil Outlet 11.1 0.00806 3440 698 71037 19406
Supply Fan Outlet 12.8 0.00806 3440 698 6442 -
Cold Supply Duct Outlet 12.8 0.00806 3440 698 - -
Zone Air - 24.8 0.00883 3440 909 44705 7112
Zone Direct Exhaust Outlet 24.8 0.00883 779 909 - -
Return Plenum Outlet 24.8 0.00883 2661 909 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
C1-06 Purch & Receive ST 1875 Cooling 1786 24.8 135 833 0 0
C1-07 Purchasing Manager 830 Cooling 776 24.8 59 803 0 0
C1-09 Monitoring Station 1709 Cooling 1605 24.8 121 800 0 0
C1-10 SecuritySupervisor 843 Cooling 814 24.8 61 984 0 0
C1-20 Linen Collection 513 Deadband 504 23.0 45 707 0 0
C1-52 Closing Room 2107 Cooling 1988 24.8 150 912 0 0
C1-90 Lobby 1683 Cooling 1533 24.8 116 821 0 0
C1-93 Bridal Suite 2968 Cooling 2815 24.8 213 852 0 0
C1-101 Assistance HK 1015 Cooling 974 24.8 74 861 0 0
C1-100 HK Manager 941 Cooling 912 24.8 69 954 0 0
C1-102 Houskeepking 2617 Cooling 2499 24.8 189 857 0 0
C1-109 Nurse 1150 Cooling 1089 24.8 82 868 0 0
C1-112 HR Reception 1722 Cooling 1645 24.8 124 935 0 0
C1-113 HR Clerk 752 Cooling 743 24.9 56 1011 0 0
C1-114 DR of HR 1007 Cooling 969 24.8 73 939 0 0
C1-116 DR of Training 768 Cooling 759 24.9 57 1005 0 0
C1-115 Training Room 3771 Cooling 3720 24.7 284 1189 0 0
C1-117 ENG. Reception 2448 Cooling 2400 24.9 181 958 0 0
C1-119 DIR of Engineerin 826 Cooling 794 24.8 60 896 0 0
C1-122 M+E Workshop 1349 Deadband 1273 23.3 110 964 0 0
C1-121 Carpenter Shop 1356 Deadband 1290 23.4 110 810 0 0
C1-125 Electric Repair 951 Deadband 938 23.4 80 825 0 0
C1-124 Paint Shop 1355 Deadband 1316 23.6 110 758 0 0
C1-25 Corridor 1 12999 Cooling 11565 24.7 880 902 0 0

Hourly Analysis Program v4.80 Page 111 of 263


Air System Sizing Summary for AHU-H-C3-03 Employee Cafeteria
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:04PM

Air System Information


Air System Name AHU-H-C3-03 Employee Cafeteria Number of zones 2
Equipment Class CW AHU Floor Area 170.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 26.3 kW Load occurs at Jul 1500
Sensible coil load 20.7 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 1046 L/s Entering DB / WB 29.1 / 18.4 °C
Max block L/s at Jul 1700 1153 L/s Leaving DB / WB 11.1 / 10.2 °C
Sum of peak zone L/s 1153 L/s Coil ADP 9.1 °C
Sensible heat ratio 0.785 Bypass Factor 0.100
m²/kW 6.5 Resulting RH 43 %
W/m² 155.0 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 0.94 L/s Zone T-stat Check 2 of 2 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s at Jul 1700 1153 L/s Fan motor BHP 2.69 BHP
Standard L/s 1051 L/s Fan motor kW 2.14 kW
Actual max L/(s-m²) 6.78 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 403 L/s L/s/person 5.59 L/s/person
L/(s-m²) 2.37 L/(s-m²)

Hourly Analysis Program v4.80 Page 112 of 263


Zone Sizing Summary for AHU-H-C3-03 Employee Cafeteria
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:04PM

Air System Information


Air System Name AHU-H-C3-03 Employee Cafeteria Number of zones 2
Equipment Class CW AHU Floor Area 170.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C1-71 Employee Cafeteria 12.5 1011 506 Jul 1700 2.3 152.0 6.65
C1-70 Pantry 1.7 142 43 Jul 1700 1.3 18.0 7.88

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
C1-71 Employee Cafeteria 6.9 0.15 0.0 0.00 0
C1-70 Pantry 1.7 0.04 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-71 Employee Cafeteria
C1E-71 Employee Cafe 1 12.5 Jul 1700 1011 2.3 152.0 6.65
C1-70 Pantry
C1E-70 Pantry 1 1.7 Jul 1700 142 1.3 18.0 7.88

Hourly Analysis Program v4.80 Page 113 of 263


Ventilation Sizing Summary for AHU-H-C3-03 Employee Cafeteria
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:04PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 403 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
C1-71 Employee Cafeteria
C1E-71 Employee Cafe 1 152.0 70.0 1011.5 3.80 0.90 0.0 0.0 402.8
C1-70 Pantry
C1E-70 Pantry 1 18.0 2.0 141.8 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 1153.3 402.8

Hourly Analysis Program v4.80 Page 114 of 263


Air System Design Load Summary for AHU-H-C3-03 Employee Cafeteria
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:04PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 170 m² 679 - 170 m² 1020 -
Partitions 114 m² 1430 - 114 m² 2157 -
Ceiling 18 m² 72 - 18 m² 108 -
Overhead Lighting 1400 W 1400 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 72 4853 2534 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4455 0 - 0 0
Safety Factor 10% / 10% 1289 253 10% 328 0
>> Total Zone Loads - 14177 2788 - 3613 0
Zone Conditioning - 13820 2788 - 3316 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 996 L/s 0 - 506 L/s 0 -
Ventilation Load 365 L/s 4900 2882 191 L/s 4404 0
Supply Fan Load 1046 L/s 1956 - 548 L/s -1111 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 20676 5670 - 6609 0
Central Cooling Coil - 20676 5672 - -1112 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 7721 -
>> Total Conditioning - 20676 5672 - 6609 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 115 of 263


Zone Design Load Summary for AHU-H-C3-03 Employee Cafeteria
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:04PM

C1-71 Employee Cafeteria DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 152 m² 617 - 152 m² 912 -
Partitions 62 m² 794 - 62 m² 1178 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1131 W 1131 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 70 4718 2464 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4075 0 - 0 0
Safety Factor 10% / 10% 1133 246 10% 209 0
>> Total Zone Loads - 12468 2710 - 2299 0

C1-70 Pantry DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 18 m² 73 - 18 m² 108 -
Partitions 52 m² 660 - 52 m² 979 -
Ceiling 18 m² 73 - 18 m² 108 -
Overhead Lighting 269 W 269 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 380 0 - 0 0
Safety Factor 10% / 10% 159 7 10% 119 0
>> Total Zone Loads - 1748 77 - 1314 0

Hourly Analysis Program v4.80 Page 116 of 263


Space Design Load Summary for AHU-H-C3-03 Employee Cafeteria
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:04PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1E-71 Employee Cafe '' IN ZONE '' C1-71 Employee Cafeteria ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 152 m² 617 - 152 m² 912 -
Partitions 62 m² 794 - 62 m² 1178 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1131 W 1131 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 70 4718 2464 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4075 0 - 0 0
Safety Factor 10% / 10% 1133 246 10% 209 0
>> Total Zone Loads - 12468 2710 - 2299 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1E-71 Employee Cafe '' IN ZONE '' C1-71 Employee Cafeteria ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 117 of 263


Space Design Load Summary for AHU-H-C3-03 Employee Cafeteria
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:04PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' C1E-70 Pantry '' IN ZONE '' C1-70 Pantry ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 18 m² 73 - 18 m² 108 -
Partitions 52 m² 660 - 52 m² 979 -
Ceiling 18 m² 73 - 18 m² 108 -
Overhead Lighting 269 W 269 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 380 0 - 0 0
Safety Factor 10% / 10% 159 7 10% 119 0
>> Total Zone Loads - 1748 77 - 1314 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' C1E-70 Pantry '' IN ZONE '' C1-70 Pantry ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 118 of 263


Hourly Air System Design Day Loads for AHU-H-C3-03 Employee Cafeteria
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:05PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 993 16.0 21.3 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 987 15.7 21.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 981 15.4 20.7 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 976 15.2 20.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 972 15.0 20.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 969 14.9 20.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 970 15.0 20.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 973 15.2 20.4 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 979 15.7 21.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 990 16.5 21.8 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 1003 17.4 22.7 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 1019 18.4 23.9 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 1034 19.4 25.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 1042 20.1 25.7 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 1044 20.5 26.2 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 1046 20.7 26.3 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 1047 20.6 26.2 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 1049 20.3 26.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 1047 19.7 25.4 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 1037 19.0 24.5 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 1026 18.2 23.7 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 1016 17.5 22.9 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 1007 16.9 22.3 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 999 16.4 21.8 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 119 of 263


Hourly Zone Loads for AHU-H-C3-03 Employee Cafeteria
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:05PM

ZONE: C1-71 Employee Cafeteria


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 44 890.9 11816.6 11713.1 0.0 0.0 0.0
0100 27.2 24.7 44 887.3 11756.6 11658.8 0.0 0.0 0.0
0200 26.6 24.7 44 883.7 11695.7 11603.4 0.0 0.0 0.0
0300 26.2 24.7 44 880.5 11644.0 11555.0 0.0 0.0 0.0
0400 25.8 24.7 44 877.8 11601.9 11514.2 0.0 0.0 0.0
0500 25.7 24.7 44 876.1 11579.8 11489.5 0.0 0.0 0.0
0600 25.9 24.7 44 876.2 11588.6 11490.2 0.0 0.0 0.0
0700 26.5 24.7 44 878.0 11629.0 11517.4 0.0 0.0 0.0
0800 27.5 24.7 44 882.2 11712.0 11580.4 0.0 0.0 0.0
0900 29.0 24.7 44 888.8 11838.7 11680.9 0.0 0.0 0.0
1000 30.7 24.8 43 896.9 11990.0 11803.8 0.0 0.0 0.0
1100 32.6 24.8 43 906.5 12166.1 11949.6 0.0 0.0 0.0
1200 34.4 24.8 43 915.9 12337.1 12094.1 0.0 0.0 0.0
1300 35.8 24.8 43 920.6 12414.5 12165.6 0.0 0.0 0.0
1400 36.7 24.8 43 921.9 12429.3 12186.5 0.0 0.0 0.0
1500 37.0 24.8 43 923.2 12443.2 12205.5 0.0 0.0 0.0
1600 36.7 24.8 43 924.3 12456.2 12223.2 0.0 0.0 0.0
1700 35.9 24.8 43 925.4 12468.3 12239.7 0.0 0.0 0.0
1800 34.6 24.8 43 924.1 12436.2 12220.0 0.0 0.0 0.0
1900 33.2 24.8 43 918.0 12314.2 12126.3 0.0 0.0 0.0
2000 31.7 24.8 43 911.4 12187.5 12025.6 0.0 0.0 0.0
2100 30.4 24.8 43 905.5 12076.6 11935.3 0.0 0.0 0.0
2200 29.3 24.8 44 899.8 11972.4 11848.5 0.0 0.0 0.0
2300 28.4 24.8 44 894.9 11885.6 11774.1 0.0 0.0 0.0

ZONE: C1-70 Pantry


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 44 102.1 1372.9 1323.1 0.0 0.0 0.0
0100 27.2 24.6 44 99.9 1338.6 1292.8 0.0 0.0 0.0
0200 26.6 24.5 44 97.7 1303.9 1262.0 0.0 0.0 0.0
0300 26.2 24.5 44 95.8 1274.3 1235.3 0.0 0.0 0.0
0400 25.8 24.5 44 94.2 1250.3 1213.1 0.0 0.0 0.0
0500 25.7 24.5 44 93.3 1237.7 1200.3 0.0 0.0 0.0
0600 25.9 24.5 44 93.4 1242.7 1202.0 0.0 0.0 0.0
0700 26.5 24.5 44 94.6 1265.7 1219.0 0.0 0.0 0.0
0800 27.5 24.5 44 97.3 1313.0 1256.4 0.0 0.0 0.0
0900 29.0 24.6 44 101.5 1385.3 1315.1 0.0 0.0 0.0
1000 30.7 24.6 43 106.5 1471.5 1386.2 0.0 0.0 0.0
1100 32.6 24.7 43 112.4 1572.0 1470.0 0.0 0.0 0.0
1200 34.4 24.7 43 118.1 1669.5 1552.5 0.0 0.0 0.0
1300 35.8 24.8 43 121.0 1717.2 1594.9 0.0 0.0 0.0
1400 36.7 24.8 43 121.7 1725.8 1605.3 0.0 0.0 0.0
1500 37.0 24.8 43 122.4 1733.8 1614.8 0.0 0.0 0.0
1600 36.7 24.8 43 123.0 1741.2 1623.5 0.0 0.0 0.0
1700 35.9 24.8 43 123.5 1748.2 1631.7 0.0 0.0 0.0
1800 34.6 24.8 43 122.5 1726.5 1616.1 0.0 0.0 0.0
1900 33.2 24.8 43 118.7 1656.8 1560.7 0.0 0.0 0.0
2000 31.7 24.7 43 114.6 1584.5 1501.8 0.0 0.0 0.0
2100 30.4 24.7 43 111.0 1521.2 1449.5 0.0 0.0 0.0
2200 29.3 24.6 44 107.5 1461.8 1399.7 0.0 0.0 0.0
2300 28.4 24.6 44 104.5 1412.2 1357.3 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 120 of 263


System Psychrometrics for AHU-H-C3-03 Employee Cafeteria
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:05PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 365 400 4900 2882
Vent - Return Mixing Outlet 29.1 0.01012 1046 953 - -
Preheat Coil Outlet 29.1 0.01012 1046 953 0 -
Central Cooling Coil Outlet 11.1 0.00810 1046 953 20676 5672
Supply Fan Outlet 12.8 0.00810 1046 953 1956 -
Cold Supply Duct Outlet 12.8 0.00810 1046 953 - -
Zone Air - 24.8 0.00909 1046 1249 13820 2788
Zone Direct Exhaust Outlet 24.8 0.00909 50 1249 - -
Return Plenum Outlet 24.8 0.00909 996 1249 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
C1-71 Employee Cafeteria 12443 Cooling 12206 24.8 923 1280 0 0
C1-70 Pantry 1734 Cooling 1615 24.8 122 1018 0 0

Hourly Analysis Program v4.80 Page 121 of 263


Air System Sizing Summary for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:05PM

Air System Information


Air System Name AHU-H-C3-04 GF Restaurant Number of zones 4
Equipment Class CW AHU Floor Area 349.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 88.1 kW Load occurs at Jul 1500
Sensible coil load 66.9 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 2829 L/s Entering DB / WB 32.6 / 19.9 °C
Max block L/s at Jul 1300 3093 L/s Leaving DB / WB 11.1 / 10.1 °C
Sum of peak zone L/s 3104 L/s Coil ADP 8.7 °C
Sensible heat ratio 0.760 Bypass Factor 0.100
m²/kW 4.0 Resulting RH 40 %
W/m² 252.4 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 3.15 L/s Zone T-stat Check 4 of 4 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 13.8 kW Load occurs at Des Htg
Coil L/s at Des Htg 2003 L/s Ent. DB / Lvg DB 6.6 / 12.8 °C
Max coil L/s 3093 L/s
Water flow @ 11.0 °K drop 0.30 L/s

Supply Fan Sizing Data


Actual max L/s at Jul 1300 3093 L/s Fan motor BHP 7.22 BHP
Standard L/s 2820 L/s Fan motor kW 5.73 kW
Actual max L/(s-m²) 8.86 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 2003 L/s L/s/person 22.50 L/s/person
L/(s-m²) 5.74 L/(s-m²)

Hourly Analysis Program v4.80 Page 122 of 263


Zone Sizing Summary for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:05PM

Air System Information


Air System Name AHU-H-C3-04 GF Restaurant Number of zones 4
Equipment Class CW AHU Floor Area 349.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
GF-14 Restaurant Area 1 25.0 2026 1170 Aug 1300 8.0 225.0 9.00
GF-14 Restaurant Area 2 3.6 292 270 Jun 1300 1.2 43.0 6.80
GF-14 Restaurant Area 3 7.5 612 473 Jun 0800 2.4 75.0 8.15
GF-14 Humidor 1.6 174 90 Jul 1700 0.0 6.0 29.06

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
GF-14 Restaurant Area 1 18.6 0.40 0.0 0.00 0
GF-14 Restaurant Area 2 3.7 0.08 0.0 0.00 0
GF-14 Restaurant Area 3 6.7 0.15 0.0 0.00 0
GF-14 Humidor 0.8 0.02 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
GF-14 Restaurant Area 1
GFR-14 RestA 1 25.0 Aug 1300 2026 8.0 225.0 9.00
GF-14 Restaurant Area 2
GFR-14 RestB 1 3.6 Jun 1300 292 1.2 43.0 6.80
GF-14 Restaurant Area 3
GFR-14 RestC 1 7.5 Jun 0800 612 2.4 75.0 8.15
GF-14 Humidor
GFR-14 Humidor 1 1.6 Jul 1700 174 0.0 6.0 29.06

Hourly Analysis Program v4.80 Page 123 of 263


Ventilation Sizing Summary for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:05PM

1. Summary
Ventilation Sizing Method ASHRAE Std 62.1-2007
Design Condition Minimum flow (heating)
Occupant Diversity 1.000
Uncorrected Ventilation Airflow Rate 1602 L/s
System Ventilation Efficiency 0.800
Design Ventilation Airflow Rate 2003 L/s

2. Space Ventilation Analysis Table


Minimum Floor Required Time Required Air Required Uncorrected Space
Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation
Zone Name / Space Name Mult. (L/s) (m²) (L/(s-m²)) Occupancy (L/s/person) Effectiveness (L/s) (L/s) Efficiency
GF-14 Restaurant Area 1
GFR-14 RestA 1 1170 225.0 0.00 52.0 18.00 0.80 1170 936 0.800
GF-14 Restaurant Area 2
GFR-14 RestB 1 270 43.0 0.00 12.0 18.00 0.80 270 216 0.800
GF-14 Restaurant Area 3
GFR-14 RestC 1 473 75.0 0.00 21.0 18.00 0.80 473 378 0.800
GF-14 Humidor
GFR-14 Humidor 1 90 6.0 0.00 4.0 18.00 0.80 90 72 0.800
Totals (incl. Space Multipliers) 2003 1602 0.800

Hourly Analysis Program v4.80 Page 124 of 263


Air System Design Load Summary for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:05PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 139 m² 5795 - 139 m² - -
Wall Transmission 138 m² 1141 - 138 m² 1100 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 139 m² 3036 - 139 m² 6030 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 95 m² 379 - 95 m² 570 -
Partitions 45 m² 567 - 45 m² 855 -
Ceiling 352 m² 1413 - 352 m² 2108 -
Overhead Lighting 6980 W 6980 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 89 5999 3133 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 8667 0 - 0 0
Safety Factor 10% / 10% 3398 313 10% 1066 0
>> Total Zone Loads - 37374 3446 - 11729 0
Zone Conditioning - 36442 3446 - 11108 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2829 L/s 0 - 2003 L/s 0 -
Ventilation Load 1831 L/s 25186 17714 1296 L/s 29740 0
Supply Fan Load 2829 L/s 5288 - 2003 L/s -3793 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 66916 21160 - 37054 0
Central Cooling Coil - 66916 21160 - -3793 0
Preheat Coil - 0 - - 13774 -
Terminal Reheat Coils - 0 - - 27073 -
>> Total Conditioning - 66916 21160 - 37054 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 125 of 263


Zone Design Load Summary for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:05PM

GF-14 Restaurant Area 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 85 m² 3918 - 85 m² - -
Wall Transmission 104 m² 893 - 104 m² 824 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 85 m² 1670 - 85 m² 3687 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 95 m² 372 - 95 m² 570 -
Partitions 45 m² 556 - 45 m² 855 -
Ceiling 227 m² 886 - 227 m² 1362 -
Overhead Lighting 4500 W 4500 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 52 3505 1830 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 6402 0 - 0 0
Safety Factor 10% / 10% 2270 183 10% 730 0
>> Total Zone Loads - 24972 2013 - 8028 0

GF-14 Restaurant Area 2 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.2 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 18 m² 837 - 18 m² - -
Wall Transmission 8 m² 70 - 8 m² 68 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 18 m² 334 - 18 m² 781 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 43 m² 165 - 43 m² 258 -
Overhead Lighting 860 W 860 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 200 0 - 0 0
Safety Factor 10% / 10% 327 42 10% 111 0
>> Total Zone Loads - 3602 465 - 1217 0

Hourly Analysis Program v4.80 Page 126 of 263


Zone Design Load Summary for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:05PM

GF-14 Restaurant Area 3 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.0 °C / 19.3 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 36 m² 2230 - 36 m² - -
Wall Transmission 26 m² 250 - 26 m² 208 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 36 m² 254 - 36 m² 1562 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 75 m² 140 - 75 m² 450 -
Overhead Lighting 1500 W 1500 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 21 1415 739 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1065 0 - 0 0
Safety Factor 10% / 10% 685 74 10% 222 0
>> Total Zone Loads - 7539 813 - 2442 0

GF-14 Humidor DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 7 m² 41 - 7 m² 38 -
Overhead Lighting 120 W 120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 0 - 0 0
Safety Factor 10% / 10% 143 14 10% 4 0
>> Total Zone Loads - 1574 155 - 42 0

Hourly Analysis Program v4.80 Page 127 of 263


Space Design Load Summary for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:06PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GFR-14 RestA '' IN ZONE '' GF-14 Restaurant Area 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 85 m² 3918 - 85 m² - -
Wall Transmission 104 m² 893 - 104 m² 824 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 85 m² 1670 - 85 m² 3687 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 95 m² 372 - 95 m² 570 -
Partitions 45 m² 556 - 45 m² 855 -
Ceiling 227 m² 886 - 227 m² 1362 -
Overhead Lighting 4500 W 4500 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 52 3505 1830 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 6402 0 - 0 0
Safety Factor 10% / 10% 2270 183 10% 730 0
>> Total Zone Loads - 24972 2013 - 8028 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GFR-14 RestA '' IN ZONE '' GF-14 Restaurant Area 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 68 0.365 - 495 - 541
WINDOW 1 35 1.990 0.300 687 1251 1518
SE EXPOSURE
WALL 36 0.365 - 398 - 282
WINDOW 1 50 1.990 0.300 982 2667 2169

Hourly Analysis Program v4.80 Page 128 of 263


Space Design Load Summary for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:06PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' GFR-14 RestB '' IN ZONE '' GF-14 Restaurant Area 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.2 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 18 m² 837 - 18 m² - -
Wall Transmission 8 m² 70 - 8 m² 68 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 18 m² 334 - 18 m² 781 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 43 m² 165 - 43 m² 258 -
Overhead Lighting 860 W 860 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 200 0 - 0 0
Safety Factor 10% / 10% 327 42 10% 111 0
>> Total Zone Loads - 3602 465 - 1217 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' GFR-14 RestB '' IN ZONE '' GF-14 Restaurant Area 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 8 0.365 - 70 - 68
WINDOW 1 18 1.990 0.300 334 837 781

Hourly Analysis Program v4.80 Page 129 of 263


Space Design Load Summary for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:06PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' GFR-14 RestC '' IN ZONE '' GF-14 Restaurant Area 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.0 °C / 19.3 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 36 m² 2230 - 36 m² - -
Wall Transmission 26 m² 250 - 26 m² 208 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 36 m² 254 - 36 m² 1562 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 75 m² 140 - 75 m² 450 -
Overhead Lighting 1500 W 1500 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 21 1415 739 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1065 0 - 0 0
Safety Factor 10% / 10% 685 74 10% 222 0
>> Total Zone Loads - 7539 813 - 2442 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' GFR-14 RestC '' IN ZONE '' GF-14 Restaurant Area 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 26 0.365 - 250 - 208
WINDOW 1 36 1.990 0.300 254 2230 1562

Hourly Analysis Program v4.80 Page 130 of 263


Space Design Load Summary for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:06PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' GFR-14 Humidor '' IN ZONE '' GF-14 Humidor ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 7 m² 41 - 7 m² 38 -
Overhead Lighting 120 W 120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 0 - 0 0
Safety Factor 10% / 10% 143 14 10% 4 0
>> Total Zone Loads - 1574 155 - 42 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' GFR-14 Humidor '' IN ZONE '' GF-14 Humidor ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 131 of 263


Hourly Air System Design Day Loads for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:06PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 2515 42.5 60.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 2487 41.0 58.2 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 2459 39.5 56.4 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 2437 38.3 55.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 2420 37.4 54.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 2476 38.2 55.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 2602 40.8 58.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 2693 43.4 61.8 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 2755 46.5 65.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 2785 49.9 69.4 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 2793 53.4 73.2 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 2804 57.5 77.7 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 2819 61.4 82.1 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 2831 64.5 85.4 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 2834 66.3 87.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 2829 66.9 88.1 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 2813 65.9 86.8 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 2786 63.6 84.3 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 2744 60.2 80.3 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 2701 56.4 76.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 2658 52.6 71.7 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 2618 49.4 68.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 2580 46.6 64.8 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 2545 44.3 62.1 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 132 of 263


Hourly Zone Loads for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:06PM

ZONE: GF-14 Restaurant Area 1


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.5 43 1598.8 20448.9 20551.7 0.0 0.0 0.0
0100 27.2 24.5 43 1577.3 20105.3 20231.7 0.0 0.0 0.0
0200 26.6 24.4 44 1556.3 19773.7 19920.5 0.0 0.0 0.0
0300 26.2 24.4 44 1537.2 19479.5 19639.2 0.0 0.0 0.0
0400 25.8 24.4 44 1520.2 19222.9 19388.6 0.0 0.0 0.0
0500 25.7 24.4 44 1561.7 20017.7 20001.2 0.0 0.0 0.0
0600 25.9 24.5 43 1651.9 21679.7 21347.9 0.0 0.0 0.0
0700 26.5 24.6 42 1723.5 22983.8 22433.9 0.0 0.0 0.0
0800 27.5 24.7 42 1776.5 23935.6 23248.0 0.0 0.0 0.0
0900 29.0 24.7 42 1807.0 24459.9 23721.1 0.0 0.0 0.0
1000 30.7 24.7 41 1818.4 24621.5 23897.8 0.0 0.0 0.0
1100 32.6 24.8 41 1826.2 24721.7 24020.0 0.0 0.0 0.0
1200 34.4 24.8 41 1834.9 24842.4 24155.8 0.0 0.0 0.0
1300 35.8 24.8 40 1843.0 24955.0 24282.8 0.0 0.0 0.0
1400 36.7 24.8 40 1843.9 24932.3 24296.7 0.0 0.0 0.0
1500 37.0 24.8 40 1840.0 24824.8 24236.4 0.0 0.0 0.0
1600 36.7 24.8 40 1828.7 24581.1 24059.0 0.0 0.0 0.0
1700 35.9 24.7 41 1809.1 24190.0 23753.7 0.0 0.0 0.0
1800 34.6 24.7 41 1777.5 23584.2 23263.4 0.0 0.0 0.0
1900 33.2 24.7 41 1744.2 22965.7 22751.2 0.0 0.0 0.0
2000 31.7 24.6 42 1710.2 22349.0 22231.0 0.0 0.0 0.0
2100 30.4 24.6 42 1678.9 21797.3 21755.9 0.0 0.0 0.0
2200 29.3 24.5 43 1649.1 21283.0 21305.6 0.0 0.0 0.0
2300 28.4 24.5 43 1622.3 20833.2 20903.3 0.0 0.0 0.0

ZONE: GF-14 Restaurant Area 2


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.2 43 270.0 2812.0 3085.6 0.0 0.0 0.0
0100 27.2 23.1 43 270.0 2755.5 3053.3 0.0 0.0 0.0
0200 26.6 23.0 44 270.0 2700.9 3020.9 0.0 0.0 0.0
0300 26.2 22.9 44 270.0 2652.2 2989.9 0.0 0.0 0.0
0400 25.8 22.8 44 270.0 2609.4 2960.7 0.0 0.0 0.0
0500 25.7 23.0 44 270.0 2875.4 3045.2 0.0 0.0 0.0
0600 25.9 23.5 43 270.0 3272.4 3188.9 0.0 0.0 0.0
0700 26.5 23.8 42 270.0 3472.8 3271.9 0.0 0.0 0.0
0800 27.5 23.9 42 270.0 3547.7 3311.9 0.0 0.0 0.0
0900 29.0 24.0 42 270.0 3520.2 3314.2 0.0 0.0 0.0
1000 30.7 23.9 41 270.0 3463.4 3303.3 0.0 0.0 0.0
1100 32.6 24.0 41 270.0 3500.9 3324.8 0.0 0.0 0.0
1200 34.4 24.1 41 271.3 3547.1 3361.4 0.0 0.0 0.0
1300 35.8 24.1 40 272.5 3574.7 3389.8 0.0 0.0 0.0
1400 36.7 24.1 40 273.1 3577.9 3404.6 0.0 0.0 0.0
1500 37.0 24.1 40 273.1 3558.5 3406.0 0.0 0.0 0.0
1600 36.7 24.1 40 272.5 3509.7 3389.7 0.0 0.0 0.0
1700 35.9 24.0 41 271.1 3431.3 3355.1 0.0 0.0 0.0
1800 34.6 23.9 41 270.0 3317.6 3307.6 0.0 0.0 0.0
1900 33.2 23.8 41 270.0 3218.1 3270.7 0.0 0.0 0.0
2000 31.7 23.7 42 270.0 3119.4 3231.4 0.0 0.0 0.0
2100 30.4 23.5 42 270.0 3030.7 3193.3 0.0 0.0 0.0
2200 29.3 23.4 43 270.0 2947.7 3155.3 0.0 0.0 0.0
2300 28.4 23.3 43 270.0 2874.8 3119.2 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 133 of 263


Hourly Zone Loads for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:06PM

ZONE: GF-14 Restaurant Area 3


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.1 43 488.4 5902.5 6076.9 0.0 0.0 0.0
0100 27.2 24.1 43 482.0 5787.6 5974.5 0.0 0.0 0.0
0200 26.6 24.0 44 475.7 5677.0 5874.6 0.0 0.0 0.0
0300 26.2 24.0 44 472.5 5578.2 5803.4 0.0 0.0 0.0
0400 25.8 23.9 44 472.5 5491.3 5760.2 0.0 0.0 0.0
0500 25.7 24.1 44 487.2 6023.2 6058.0 0.0 0.0 0.0
0600 25.9 24.3 43 523.1 6830.4 6645.8 0.0 0.0 0.0
0700 26.5 24.5 42 542.6 7257.7 6975.8 0.0 0.0 0.0
0800 27.5 24.5 42 551.2 7429.4 7125.0 0.0 0.0 0.0
0900 29.0 24.5 42 550.6 7382.6 7114.7 0.0 0.0 0.0
1000 30.7 24.5 41 546.7 7264.6 7047.8 0.0 0.0 0.0
1100 32.6 24.5 41 550.1 7325.9 7106.0 0.0 0.0 0.0
1200 34.4 24.6 41 554.3 7404.3 7177.9 0.0 0.0 0.0
1300 35.8 24.6 40 557.1 7452.2 7228.2 0.0 0.0 0.0
1400 36.7 24.6 40 558.2 7457.1 7246.4 0.0 0.0 0.0
1500 37.0 24.6 40 557.3 7417.8 7230.9 0.0 0.0 0.0
1600 36.7 24.6 40 553.8 7319.2 7169.6 0.0 0.0 0.0
1700 35.9 24.5 41 547.5 7159.7 7060.5 0.0 0.0 0.0
1800 34.6 24.4 41 537.8 6928.8 6894.7 0.0 0.0 0.0
1900 33.2 24.4 41 528.9 6726.7 6743.9 0.0 0.0 0.0
2000 31.7 24.3 42 519.8 6526.5 6590.6 0.0 0.0 0.0
2100 30.4 24.3 42 511.2 6346.4 6448.2 0.0 0.0 0.0
2200 29.3 24.2 43 502.9 6178.3 6311.8 0.0 0.0 0.0
2300 28.4 24.2 43 495.3 6030.3 6187.8 0.0 0.0 0.0

ZONE: GF-14 Humidor


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 21.8 43 157.6 1560.3 1557.4 0.0 0.0 0.0
0100 27.2 21.8 43 157.5 1559.1 1556.2 0.0 0.0 0.0
0200 26.6 21.8 44 157.4 1557.9 1555.0 0.0 0.0 0.0
0300 26.2 21.8 44 157.3 1556.9 1554.0 0.0 0.0 0.0
0400 25.8 21.8 44 157.2 1556.0 1553.2 0.0 0.0 0.0
0500 25.7 21.8 44 157.2 1555.6 1552.7 0.0 0.0 0.0
0600 25.9 21.8 43 157.2 1555.8 1552.8 0.0 0.0 0.0
0700 26.5 21.8 42 157.2 1556.6 1553.5 0.0 0.0 0.0
0800 27.5 21.8 42 157.4 1558.2 1555.1 0.0 0.0 0.0
0900 29.0 21.8 42 157.6 1560.8 1557.4 0.0 0.0 0.0
1000 30.7 21.8 41 157.8 1563.8 1560.3 0.0 0.0 0.0
1100 32.6 21.8 41 158.1 1567.3 1563.6 0.0 0.0 0.0
1200 34.4 21.8 41 158.3 1570.8 1566.9 0.0 0.0 0.0
1300 35.8 21.8 40 158.5 1572.5 1568.6 0.0 0.0 0.0
1400 36.7 21.8 40 158.5 1572.8 1568.9 0.0 0.0 0.0
1500 37.0 21.8 40 158.5 1573.0 1569.2 0.0 0.0 0.0
1600 36.7 21.8 40 158.6 1573.3 1569.5 0.0 0.0 0.0
1700 35.9 21.8 41 158.6 1573.6 1569.8 0.0 0.0 0.0
1800 34.6 21.8 41 158.5 1572.8 1569.1 0.0 0.0 0.0
1900 33.2 21.8 41 158.3 1570.3 1566.9 0.0 0.0 0.0
2000 31.7 21.8 42 158.1 1567.8 1564.5 0.0 0.0 0.0
2100 30.4 21.8 42 158.0 1565.5 1562.4 0.0 0.0 0.0
2200 29.3 21.8 43 157.8 1563.5 1560.4 0.0 0.0 0.0
2300 28.4 21.8 43 157.7 1561.7 1558.8 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 134 of 263


System Psychrometrics for AHU-H-C3-04 GF Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 1831 400 25186 17714
Vent - Return Mixing Outlet 32.6 0.01076 2829 481 - -
Preheat Coil Outlet 32.6 0.01076 2829 481 0 -
Central Cooling Coil Outlet 11.1 0.00798 2829 481 66916 21160
Supply Fan Outlet 12.8 0.00798 2829 481 5288 -
Cold Supply Duct Outlet 12.8 0.00798 2829 481 - -
Zone Air - 24.5 0.00843 2829 628 36442 3446
Return Plenum Outlet 24.5 0.00843 2829 628 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
GF-14 Restaurant Area 1 24825 Cooling 24236 24.8 1840 614 0 0
GF-14 Restaurant Area 2 3559 Cooling 3406 24.1 273 683 0 0
GF-14 Restaurant Area 3 7418 Cooling 7231 24.6 557 656 0 0
GF-14 Humidor 1573 Cooling 1569 21.8 159 601 0 0

Hourly Analysis Program v4.80 Page 135 of 263


Air System Sizing Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM

Air System Information


Air System Name AHU-H-C3-05 GF Kitchen Number of zones 8
Equipment Class CW AHU Floor Area 106.4 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 81.2 kW Load occurs at Jul 1500
Sensible coil load 58.4 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 2050 L/s Entering DB / WB 37.0 / 22.0 °C
Max block L/s at Aug 1600 2050 L/s Leaving DB / WB 11.1 / 10.0 °C
Sum of peak zone L/s 2050 L/s Coil ADP 8.2 °C
Sensible heat ratio 0.719 Bypass Factor 0.100
m²/kW 1.3 Resulting RH 42 %
W/m² 763.5 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 2.90 L/s Zone T-stat Check 8 of 8 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 30.7 kW Load occurs at Des Htg
Coil L/s at Des Htg 2050 L/s Ent. DB / Lvg DB -0.8 / 12.8 °C
Max coil L/s 2050 L/s
Water flow @ 11.0 °K drop 0.67 L/s

Supply Fan Sizing Data


Actual max L/s at Aug 1600 2050 L/s Fan motor BHP 4.79 BHP
Standard L/s 1869 L/s Fan motor kW 3.80 kW
Actual max L/(s-m²) 19.27 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 2050 L/s L/s/person 102.51 L/s/person
L/(s-m²) 19.27 L/(s-m²)

Hourly Analysis Program v4.80 Page 136 of 263


Zone Sizing Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM

Air System Information


Air System Name AHU-H-C3-05 GF Kitchen Number of zones 8
Equipment Class CW AHU Floor Area 106.4 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
GF-03 Dishwash 2.8 230 230 Jul 1700 0.5 16.0 14.37
GF-04 Corridor 3.6 289 289 Aug 1700 1.1 25.0 11.55
GF-05 Room Service 6.3 513 513 Jul 1700 0.3 21.0 24.43
GF-06 Order Taker 0.5 39 39 Jul 1700 0.5 4.0 9.75
GF-07 Dry Storage 0.4 35 35 Jul 1700 0.4 5.4 6.55
GF-02 Cold Kitchen 2.6 210 210 Sep 1500 0.4 10.0 20.98
GF-08 Hot Kitchen 7.5 609 609 Jul 1700 0.3 24.0 25.38
GF-01 Refrigration Room 0.0 125 125 Des Htg 0.0 1.0 125.00

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
GF-03 Dishwash 2.6 0.06 0.0 0.00 0
GF-04 Corridor 3.7 0.08 0.0 0.00 0
GF-05 Room Service 4.9 0.11 0.0 0.00 0
GF-06 Order Taker 0.9 0.02 0.0 0.00 0
GF-07 Dry Storage 0.8 0.02 0.0 0.00 0
GF-02 Cold Kitchen 2.3 0.05 0.0 0.00 0
GF-08 Hot Kitchen 5.8 0.13 0.0 0.00 0
GF-01 Refrigration Room 1.1 0.02 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
GF-03 Dishwash
GFK-03 Dishwash 1 2.8 Jul 1700 230 0.5 16.0 14.37
GF-04 Corridor
GFK-04 Corridor 1 3.6 Aug 1700 289 1.1 25.0 11.55
GF-05 Room Service
GFK-05 Room Service 1 6.3 Jul 1700 513 0.3 21.0 24.43
GF-06 Order Taker
GFK-06 Order Taker 1 0.5 Jul 1700 39 0.5 4.0 9.75
GF-07 Dry Storage
GFK-07 Dry Storage 1 0.4 Jul 1700 35 0.4 5.4 6.55
GF-02 Cold Kitchen
GFK-02 Cold Kitchen 1 2.6 Sep 1500 210 0.4 10.0 20.98
GF-08 Hot Kitchen
GFK-08 Hot Kitchen 1 7.5 Jul 1700 609 0.3 24.0 25.38
GF-01 Refrigration Room
GFK-01 - Refrigration Rm 1 0.0 Jan 0000 125 0.0 1.0 125.00

Hourly Analysis Program v4.80 Page 137 of 263


Zone Sizing Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM

Hourly Analysis Program v4.80 Page 138 of 263


Ventilation Sizing Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM Air System Design Load
Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 2050 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
GF-03 Dishwash
GFK-03 Dishwash 1 16.0 4.0 229.9 0.00 0.00 0.0 100.0 229.9
GF-04 Corridor
GFK-04 Corridor 1 25.0 2.0 288.9 0.00 0.00 0.0 100.0 288.9
GF-05 Room Service
GFK-05 Room Service 1 21.0 5.0 513.0 0.00 0.00 0.0 100.0 513.0
GF-06 Order Taker
GFK-06 Order Taker 1 4.0 1.0 39.0 0.00 0.00 0.0 100.0 39.0
GF-07 Dry Storage
GFK-07 Dry Storage 1 5.4 1.0 35.4 0.00 0.00 0.0 100.0 35.4
GF-02 Cold Kitchen
GFK-02 Cold Kitchen 1 10.0 2.0 209.8 0.00 0.00 0.0 100.0 209.8
GF-08 Hot Kitchen
GFK-08 Hot Kitchen 1 24.0 5.0 609.2 0.00 0.00 0.0 100.0 609.2
GF-01 Refrigration Room
GFK-01 - Refrigration Rm 1 1.0 0.0 125.0 0.00 0.00 125.0 100.0 250.0
Totals (incl. Space Multipliers) 2050.1 2050.1

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m² 255 - 4 m² - -
Wall Transmission 16 m² 168 - 16 m² 123 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 4 m² 87 - 4 m² 174 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 104 m² 415 - 104 m² 620 -
Partitions 91 m² 1142 - 91 m² 1721 -
Ceiling 105 m² 418 - 105 m² 630 -
Overhead Lighting 1000 W 1000 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -

Hourly Analysis Program v4.80 Page 139 of 263 Hourly Analysis Program v4.80 Page 139 of 263
Ventilation Sizing Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM Air System Design Load
Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM
People 20 1701 2520 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 16237 0 - 0 0
Safety Factor 10% / 10% 2142 252 10% 327 0
>> Total Zone Loads - 23565 2772 - 3595 0
Zone Conditioning - 23405 2772 - 3224 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2050 L/s 0 - 2050 L/s 0 -
Ventilation Load 2050 L/s 30193 20069 2050 L/s 47176 0
Supply Fan Load 2050 L/s 3797 - 2050 L/s -3797 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 57394 22840 - 46603 0
Central Cooling Coil - 58400 22840 - -3797 0
Preheat Coil - 0 - - 30686 -
Terminal Reheat Coils - -1005 - - 19714 -
>> Total Conditioning - 57394 22840 - 46603 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 140 of 263 Hourly Analysis Program v4.80 Page 140 of 263
Ventilation Sizing Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM Air System Design Load
Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM

Hourly Analysis Program v4.80 Page 141 of 263 Hourly Analysis Program v4.80 Page 141 of 263
Zone Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM

GF-03 Dishwash DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 16 m² 65 - 16 m² 96 -
Partitions 15 m² 196 - 15 m² 291 -
Ceiling 16 m² 65 - 16 m² 96 -
Overhead Lighting 151 W 151 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1754 0 - 0 0
Safety Factor 10% / 10% 258 53 10% 48 0
>> Total Zone Loads - 2834 587 - 531 0

GF-04 Corridor DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 7 m² 53 - 7 m² 52 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 25 m² 101 - 25 m² 150 -
Partitions 34 m² 436 - 34 m² 646 -
Ceiling 25 m² 101 - 25 m² 150 -
Overhead Lighting 236 W 235 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2137 0 - 0 0
Safety Factor 10% / 10% 324 27 10% 100 0
>> Total Zone Loads - 3561 293 - 1097 0

Hourly Analysis Program v4.80 Page 142 of 263


Zone Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM

GF-05 Room Service DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 21 m² 85 - 21 m² 126 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 21 m² 85 - 21 m² 126 -
Overhead Lighting 198 W 198 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4948 0 - 0 0
Safety Factor 10% / 10% 575 67 10% 25 0
>> Total Zone Loads - 6323 733 - 277 0

GF-06 Order Taker DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 4 m² 16 - 4 m² 22 -
Partitions 23 m² 292 - 23 m² 433 -
Ceiling 4 m² 16 - 4 m² 24 -
Overhead Lighting 41 W 41 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 44 6 10% 48 0
>> Total Zone Loads - 481 66 - 527 0

Hourly Analysis Program v4.80 Page 143 of 263


Zone Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM

GF-07 Dry Storage DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 4 m² 16 - 4 m² 22 -
Partitions 19 m² 237 - 19 m² 352 -
Ceiling 4 m² 16 - 4 m² 24 -
Overhead Lighting 55 W 55 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 40 6 10% 40 0
>> Total Zone Loads - 436 66 - 437 0

GF-02 Cold Kitchen DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m² 358 - 4 m² - -
Wall Transmission 9 m² 141 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 4 m² 79 - 4 m² 174 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 10 m² 39 - 10 m² 60 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 10 m² 39 - 10 m² 60 -
Overhead Lighting 94 W 94 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1428 0 - 0 0
Safety Factor 10% / 10% 235 27 10% 37 0
>> Total Zone Loads - 2586 293 - 402 0

Hourly Analysis Program v4.80 Page 144 of 263


Zone Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:07PM

GF-08 Hot Kitchen DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 97 - 24 m² 144 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 25 m² 101 - 25 m² 150 -
Overhead Lighting 226 W 226 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 5970 0 - 0 0
Safety Factor 10% / 10% 683 67 10% 29 0
>> Total Zone Loads - 7510 733 - 323 0

GF-01 Refrigration Room DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

Hourly Analysis Program v4.80 Page 145 of 263


Space Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:08PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GFK-03 Dishwash '' IN ZONE '' GF-03 Dishwash ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 16 m² 65 - 16 m² 96 -
Partitions 15 m² 196 - 15 m² 291 -
Ceiling 16 m² 65 - 16 m² 96 -
Overhead Lighting 151 W 151 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1754 0 - 0 0
Safety Factor 10% / 10% 258 53 10% 48 0
>> Total Zone Loads - 2834 587 - 531 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GFK-03 Dishwash '' IN ZONE '' GF-03 Dishwash ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 146 of 263


Space Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:08PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' GFK-04 Corridor '' IN ZONE '' GF-04 Corridor ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 7 m² 53 - 7 m² 52 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 25 m² 101 - 25 m² 150 -
Partitions 34 m² 436 - 34 m² 646 -
Ceiling 25 m² 101 - 25 m² 150 -
Overhead Lighting 236 W 235 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2137 0 - 0 0
Safety Factor 10% / 10% 324 27 10% 100 0
>> Total Zone Loads - 3561 293 - 1097 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' GFK-04 Corridor '' IN ZONE '' GF-04 Corridor ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 7 0.365 - 53 - 52

Hourly Analysis Program v4.80 Page 147 of 263


Space Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:08PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' GFK-05 Room Service '' IN ZONE '' GF-05 Room Service ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 21 m² 85 - 21 m² 126 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 21 m² 85 - 21 m² 126 -
Overhead Lighting 198 W 198 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4948 0 - 0 0
Safety Factor 10% / 10% 575 67 10% 25 0
>> Total Zone Loads - 6323 733 - 277 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' GFK-05 Room Service '' IN ZONE '' GF-05 Room Service ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 148 of 263


Space Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:08PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' GFK-06 Order Taker '' IN ZONE '' GF-06 Order Taker ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 4 m² 16 - 4 m² 22 -
Partitions 23 m² 292 - 23 m² 433 -
Ceiling 4 m² 16 - 4 m² 24 -
Overhead Lighting 41 W 41 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 44 6 10% 48 0
>> Total Zone Loads - 481 66 - 527 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' GFK-06 Order Taker '' IN ZONE '' GF-06 Order Taker ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 149 of 263


Space Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:08PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' GFK-07 Dry Storage '' IN ZONE '' GF-07 Dry Storage ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 4 m² 16 - 4 m² 22 -
Partitions 19 m² 237 - 19 m² 352 -
Ceiling 4 m² 16 - 4 m² 24 -
Overhead Lighting 55 W 55 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 40 6 10% 40 0
>> Total Zone Loads - 436 66 - 437 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' GFK-07 Dry Storage '' IN ZONE '' GF-07 Dry Storage ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 150 of 263


Space Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:08PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' GFK-02 Cold Kitchen '' IN ZONE '' GF-02 Cold Kitchen ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m² 358 - 4 m² - -
Wall Transmission 9 m² 141 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 4 m² 79 - 4 m² 174 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 10 m² 39 - 10 m² 60 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 10 m² 39 - 10 m² 60 -
Overhead Lighting 94 W 94 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1428 0 - 0 0
Safety Factor 10% / 10% 235 27 10% 37 0
>> Total Zone Loads - 2586 293 - 402 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' GFK-02 Cold Kitchen '' IN ZONE '' GF-02 Cold Kitchen ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 9 0.365 - 141 - 72
WINDOW 1 4 1.990 0.300 79 358 174

Hourly Analysis Program v4.80 Page 151 of 263


Space Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:08PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' GFK-08 Hot Kitchen '' IN ZONE '' GF-08 Hot Kitchen ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 97 - 24 m² 144 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 25 m² 101 - 25 m² 150 -
Overhead Lighting 226 W 226 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 5970 0 - 0 0
Safety Factor 10% / 10% 683 67 10% 29 0
>> Total Zone Loads - 7510 733 - 323 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' GFK-08 Hot Kitchen '' IN ZONE '' GF-08 Hot Kitchen ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 152 of 263


Space Design Load Summary for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:08PM

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' GFK-01 - Refrigration Rm '' IN ZONE '' GF-01 Refrigration Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' GFK-01 - Refrigration Rm '' IN ZONE '' GF-01 Refrigration Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 153 of 263


Hourly Air System Design Day Loads for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:09PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 2050 37.5 57.7 0.0 0.0 0.0 0.0 1.0 0.0
0100 27.2 2050 36.2 56.2 0.0 0.0 0.0 0.0 1.0 0.0
0200 26.6 2050 34.9 54.8 0.0 0.0 0.0 0.0 1.0 0.0
0300 26.2 2050 33.9 53.6 0.0 0.0 0.0 0.0 1.0 0.0
0400 25.8 2050 33.2 52.7 0.0 0.0 0.0 0.0 1.0 0.0
0500 25.7 2050 32.9 52.4 0.0 0.0 0.0 0.0 1.0 0.0
0600 25.9 2050 33.4 53.0 0.0 0.0 0.0 0.0 1.0 0.0
0700 26.5 2050 34.7 54.5 0.0 0.0 0.0 0.0 1.0 0.0
0800 27.5 2050 37.0 57.1 0.0 0.0 0.0 0.0 1.0 0.0
0900 29.0 2050 40.3 60.8 0.0 0.0 0.0 0.0 1.0 0.0
1000 30.7 2050 44.1 65.1 0.0 0.0 0.0 0.0 1.0 0.0
1100 32.6 2050 48.5 70.0 0.0 0.0 0.0 0.0 1.0 0.0
1200 34.4 2050 52.5 74.6 0.0 0.0 0.0 0.0 1.0 0.0
1300 35.8 2050 55.6 78.1 0.0 0.0 0.0 0.0 1.0 0.0
1400 36.7 2050 57.6 80.4 0.0 0.0 0.0 0.0 1.0 0.0
1500 37.0 2050 58.4 81.2 0.0 0.0 0.0 0.0 1.0 0.0
1600 36.7 2050 57.6 80.4 0.0 0.0 0.0 0.0 1.0 0.0
1700 35.9 2050 55.9 78.4 0.0 0.0 0.0 0.0 1.0 0.0
1800 34.6 2050 53.0 75.2 0.0 0.0 0.0 0.0 1.0 0.0
1900 33.2 2050 49.7 71.5 0.0 0.0 0.0 0.0 1.0 0.0
2000 31.7 2050 46.4 67.7 0.0 0.0 0.0 0.0 1.0 0.0
2100 30.4 2050 43.6 64.6 0.0 0.0 0.0 0.0 1.0 0.0
2200 29.3 2050 41.1 61.7 0.0 0.0 0.0 0.0 1.0 0.0
2300 28.4 2050 39.0 59.4 0.0 0.0 0.0 0.0 1.0 0.0

Hourly Analysis Program v4.80 Page 154 of 263


Hourly Zone Loads for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:09PM

ZONE: GF-03 Dishwash


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.6 45 229.9 2682.7 2727.1 0.0 0.0 0.0
0100 27.2 23.5 46 229.9 2668.8 2717.8 0.0 0.0 0.0
0200 26.6 23.5 46 229.9 2654.8 2708.1 0.0 0.0 0.0
0300 26.2 23.5 46 229.9 2642.8 2699.4 0.0 0.0 0.0
0400 25.8 23.4 46 229.9 2633.1 2691.8 0.0 0.0 0.0
0500 25.7 23.4 46 229.9 2628.0 2686.7 0.0 0.0 0.0
0600 25.9 23.4 46 229.9 2630.0 2685.5 0.0 0.0 0.0
0700 26.5 23.4 46 229.9 2639.4 2688.7 0.0 0.0 0.0
0800 27.5 23.5 46 229.9 2658.5 2697.6 0.0 0.0 0.0
0900 29.0 23.5 45 229.9 2687.7 2712.7 0.0 0.0 0.0
1000 30.7 23.6 44 229.9 2722.6 2731.7 0.0 0.0 0.0
1100 32.6 23.7 44 229.9 2763.2 2754.8 0.0 0.0 0.0
1200 34.4 23.8 43 229.9 2802.7 2778.3 0.0 0.0 0.0
1300 35.8 23.8 43 229.9 2821.5 2791.3 0.0 0.0 0.0
1400 36.7 23.9 42 229.9 2824.9 2796.1 0.0 0.0 0.0
1500 37.0 23.9 42 229.9 2828.2 2800.5 0.0 0.0 0.0
1600 36.7 23.9 42 229.9 2831.2 2804.6 0.0 0.0 0.0
1700 35.9 23.9 42 229.9 2834.0 2808.5 0.0 0.0 0.0
1800 34.6 23.9 43 229.9 2825.6 2806.1 0.0 0.0 0.0
1900 33.2 23.8 43 229.9 2797.5 2792.6 0.0 0.0 0.0
2000 31.7 23.8 44 229.9 2768.2 2777.4 0.0 0.0 0.0
2100 30.4 23.7 44 229.9 2742.7 2763.4 0.0 0.0 0.0
2200 29.3 23.7 45 229.9 2718.6 2749.6 0.0 0.0 0.0
2300 28.4 23.6 45 229.9 2698.6 2737.4 0.0 0.0 0.0

ZONE: GF-04 Corridor


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.4 45 288.9 3233.8 3372.1 0.0 0.0 0.0
0100 27.2 23.4 46 288.9 3203.9 3355.4 0.0 0.0 0.0
0200 26.6 23.3 46 288.9 3174.0 3338.3 0.0 0.0 0.0
0300 26.2 23.3 46 288.9 3148.4 3322.9 0.0 0.0 0.0
0400 25.8 23.2 46 288.9 3127.4 3309.3 0.0 0.0 0.0
0500 25.7 23.2 46 288.9 3116.4 3300.1 0.0 0.0 0.0
0600 25.9 23.2 46 288.9 3125.1 3299.9 0.0 0.0 0.0
0700 26.5 23.2 46 288.9 3156.9 3310.6 0.0 0.0 0.0
0800 27.5 23.3 46 288.9 3211.0 3332.3 0.0 0.0 0.0
0900 29.0 23.4 45 288.9 3282.3 3363.1 0.0 0.0 0.0
1000 30.7 23.5 44 288.9 3359.7 3398.4 0.0 0.0 0.0
1100 32.6 23.6 44 288.9 3442.6 3437.7 0.0 0.0 0.0
1200 34.4 23.7 43 288.9 3517.6 3475.1 0.0 0.0 0.0
1300 35.8 23.8 43 288.9 3548.2 3493.9 0.0 0.0 0.0
1400 36.7 23.8 42 288.9 3549.6 3499.7 0.0 0.0 0.0
1500 37.0 23.8 42 288.9 3553.0 3505.8 0.0 0.0 0.0
1600 36.7 23.8 42 288.9 3556.8 3511.7 0.0 0.0 0.0
1700 35.9 23.9 42 288.9 3559.8 3517.0 0.0 0.0 0.0
1800 34.6 23.8 43 288.9 3539.2 3511.5 0.0 0.0 0.0
1900 33.2 23.8 43 288.9 3478.9 3487.4 0.0 0.0 0.0
2000 31.7 23.7 44 288.9 3416.5 3460.7 0.0 0.0 0.0
2100 30.4 23.6 44 288.9 3362.0 3436.1 0.0 0.0 0.0
2200 29.3 23.5 45 288.9 3310.9 3411.9 0.0 0.0 0.0
2300 28.4 23.5 45 288.9 3268.1 3390.4 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 155 of 263


Hourly Zone Loads for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:09PM

ZONE: GF-05 Room Service


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.9 45 513.0 6244.9 6261.0 0.0 0.0 0.0
0100 27.2 23.9 46 513.0 6237.6 6255.3 0.0 0.0 0.0
0200 26.6 23.9 46 513.0 6230.3 6249.4 0.0 0.0 0.0
0300 26.2 23.9 46 513.0 6224.0 6244.2 0.0 0.0 0.0
0400 25.8 23.9 46 513.0 6219.0 6239.7 0.0 0.0 0.0
0500 25.7 23.8 46 513.0 6216.3 6236.9 0.0 0.0 0.0
0600 25.9 23.8 46 513.0 6217.4 6236.6 0.0 0.0 0.0
0700 26.5 23.9 46 513.0 6222.2 6239.0 0.0 0.0 0.0
0800 27.5 23.9 46 513.0 6232.2 6245.1 0.0 0.0 0.0
0900 29.0 23.9 45 513.0 6247.5 6255.0 0.0 0.0 0.0
1000 30.7 23.9 44 513.0 6265.8 6267.4 0.0 0.0 0.0
1100 32.6 23.9 44 513.0 6287.0 6282.1 0.0 0.0 0.0
1200 34.4 24.0 43 513.0 6307.6 6297.0 0.0 0.0 0.0
1300 35.8 24.0 43 513.0 6316.8 6304.5 0.0 0.0 0.0
1400 36.7 24.0 42 513.0 6318.6 6307.0 0.0 0.0 0.0
1500 37.0 24.0 42 513.0 6320.3 6309.3 0.0 0.0 0.0
1600 36.7 24.0 42 513.0 6321.9 6311.5 0.0 0.0 0.0
1700 35.9 24.0 42 513.0 6323.3 6313.5 0.0 0.0 0.0
1800 34.6 24.0 43 513.0 6319.6 6312.0 0.0 0.0 0.0
1900 33.2 24.0 43 513.0 6304.9 6302.9 0.0 0.0 0.0
2000 31.7 23.9 44 513.0 6289.6 6292.9 0.0 0.0 0.0
2100 30.4 23.9 44 513.0 6276.2 6283.8 0.0 0.0 0.0
2200 29.3 23.9 45 513.0 6263.7 6275.0 0.0 0.0 0.0
2300 28.4 23.9 45 513.0 6253.2 6267.4 0.0 0.0 0.0

ZONE: GF-06 Order Taker


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.7 45 39.0 329.7 423.5 0.0 0.0 0.0
0100 27.2 22.5 46 39.0 315.9 418.4 0.0 0.0 0.0
0200 26.6 22.4 46 39.0 301.9 413.1 0.0 0.0 0.0
0300 26.2 22.3 46 39.0 290.1 408.4 0.0 0.0 0.0
0400 25.8 22.2 46 39.0 280.4 404.3 0.0 0.0 0.0
0500 25.7 22.2 46 39.0 275.3 401.7 0.0 0.0 0.0
0600 25.9 22.1 46 39.0 277.3 401.2 0.0 0.0 0.0
0700 26.5 22.2 46 39.0 286.6 403.2 0.0 0.0 0.0
0800 27.5 22.3 46 39.0 305.6 408.4 0.0 0.0 0.0
0900 29.0 22.5 45 39.0 334.7 417.1 0.0 0.0 0.0
1000 30.7 22.8 44 39.0 369.3 427.8 0.0 0.0 0.0
1100 32.6 23.1 44 39.0 409.7 440.8 0.0 0.0 0.0
1200 34.4 23.4 43 39.0 448.9 453.9 0.0 0.0 0.0
1300 35.8 23.5 43 39.0 468.2 461.2 0.0 0.0 0.0
1400 36.7 23.6 42 39.0 471.7 463.7 0.0 0.0 0.0
1500 37.0 23.7 42 39.0 474.9 465.9 0.0 0.0 0.0
1600 36.7 23.7 42 39.0 477.9 468.0 0.0 0.0 0.0
1700 35.9 23.7 42 39.0 480.7 469.9 0.0 0.0 0.0
1800 34.6 23.7 43 39.0 471.8 468.2 0.0 0.0 0.0
1900 33.2 23.5 43 39.0 443.8 460.3 0.0 0.0 0.0
2000 31.7 23.3 44 39.0 414.7 451.6 0.0 0.0 0.0
2100 30.4 23.1 44 39.0 389.3 443.7 0.0 0.0 0.0
2200 29.3 23.0 45 39.0 365.4 435.9 0.0 0.0 0.0
2300 28.4 22.8 45 39.0 345.5 429.2 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 156 of 263


Hourly Zone Loads for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:09PM

ZONE: GF-07 Dry Storage


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.7 45 35.4 310.5 385.3 0.0 0.0 0.0
0100 27.2 22.6 46 35.4 299.0 381.0 0.0 0.0 0.0
0200 26.6 22.5 46 35.4 287.4 376.6 0.0 0.0 0.0
0300 26.2 22.4 46 35.4 277.6 372.6 0.0 0.0 0.0
0400 25.8 22.3 46 35.4 269.6 369.1 0.0 0.0 0.0
0500 25.7 22.2 46 35.4 265.4 366.6 0.0 0.0 0.0
0600 25.9 22.2 46 35.4 267.0 365.9 0.0 0.0 0.0
0700 26.5 22.2 46 35.4 274.7 367.1 0.0 0.0 0.0
0800 27.5 22.3 46 35.4 290.5 370.9 0.0 0.0 0.0
0900 29.0 22.5 45 35.4 314.6 377.4 0.0 0.0 0.0
1000 30.7 22.7 44 35.4 343.4 385.8 0.0 0.0 0.0
1100 32.6 23.0 44 35.4 376.9 396.0 0.0 0.0 0.0
1200 34.4 23.2 43 35.4 409.4 406.4 0.0 0.0 0.0
1300 35.8 23.4 43 35.4 425.4 412.5 0.0 0.0 0.0
1400 36.7 23.5 42 35.4 428.3 414.8 0.0 0.0 0.0
1500 37.0 23.5 42 35.4 431.0 416.9 0.0 0.0 0.0
1600 36.7 23.6 42 35.4 433.5 419.0 0.0 0.0 0.0
1700 35.9 23.6 42 35.4 435.8 420.9 0.0 0.0 0.0
1800 34.6 23.6 43 35.4 428.4 419.9 0.0 0.0 0.0
1900 33.2 23.4 43 35.4 405.2 414.1 0.0 0.0 0.0
2000 31.7 23.3 44 35.4 381.1 407.5 0.0 0.0 0.0
2100 30.4 23.1 44 35.4 360.0 401.4 0.0 0.0 0.0
2200 29.3 23.0 45 35.4 340.1 395.3 0.0 0.0 0.0
2300 28.4 22.8 45 35.4 323.6 389.9 0.0 0.0 0.0

ZONE: GF-02 Cold Kitchen


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.4 45 209.8 2132.4 2227.1 0.0 0.0 0.0
0100 27.2 22.4 46 209.8 2111.8 2211.7 0.0 0.0 0.0
0200 26.6 22.3 46 209.8 2092.4 2196.8 0.0 0.0 0.0
0300 26.2 22.3 46 209.8 2075.2 2183.1 0.0 0.0 0.0
0400 25.8 22.2 46 209.8 2060.1 2170.7 0.0 0.0 0.0
0500 25.7 22.2 46 209.8 2053.6 2163.5 0.0 0.0 0.0
0600 25.9 22.2 46 209.8 2058.7 2163.7 0.0 0.0 0.0
0700 26.5 22.2 46 209.8 2070.2 2168.4 0.0 0.0 0.0
0800 27.5 22.2 46 209.8 2089.2 2178.2 0.0 0.0 0.0
0900 29.0 22.3 45 209.8 2114.7 2192.6 0.0 0.0 0.0
1000 30.7 22.4 44 209.8 2145.5 2211.1 0.0 0.0 0.0
1100 32.6 22.5 44 209.8 2188.2 2237.7 0.0 0.0 0.0
1200 34.4 22.7 43 209.8 2261.1 2283.9 0.0 0.0 0.0
1300 35.8 22.9 43 209.8 2338.9 2334.9 0.0 0.0 0.0
1400 36.7 23.1 42 209.8 2405.8 2380.7 0.0 0.0 0.0
1500 37.0 23.3 42 209.8 2451.7 2414.4 0.0 0.0 0.0
1600 36.7 23.3 42 209.8 2464.4 2428.1 0.0 0.0 0.0
1700 35.9 23.3 42 209.8 2432.2 2413.5 0.0 0.0 0.0
1800 34.6 23.1 43 209.8 2356.1 2370.3 0.0 0.0 0.0
1900 33.2 22.9 43 209.8 2304.6 2340.0 0.0 0.0 0.0
2000 31.7 22.8 44 209.8 2256.2 2310.4 0.0 0.0 0.0
2100 30.4 22.7 44 209.8 2217.2 2285.5 0.0 0.0 0.0
2200 29.3 22.6 45 209.8 2183.9 2263.4 0.0 0.0 0.0
2300 28.4 22.5 45 209.8 2155.9 2244.1 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 157 of 263


Hourly Zone Loads for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:09PM

ZONE: GF-08 Hot Kitchen


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.9 45 609.2 7418.2 7432.6 0.0 0.0 0.0
0100 27.2 23.9 46 609.2 7409.8 7425.6 0.0 0.0 0.0
0200 26.6 23.9 46 609.2 7401.2 7418.3 0.0 0.0 0.0
0300 26.2 23.9 46 609.2 7393.9 7411.9 0.0 0.0 0.0
0400 25.8 23.8 46 609.2 7388.0 7406.3 0.0 0.0 0.0
0500 25.7 23.8 46 609.2 7384.9 7402.8 0.0 0.0 0.0
0600 25.9 23.8 46 609.2 7386.2 7402.4 0.0 0.0 0.0
0700 26.5 23.8 46 609.2 7391.8 7405.4 0.0 0.0 0.0
0800 27.5 23.9 46 609.2 7403.5 7412.9 0.0 0.0 0.0
0900 29.0 23.9 45 609.2 7421.4 7425.1 0.0 0.0 0.0
1000 30.7 23.9 44 609.2 7442.6 7440.3 0.0 0.0 0.0
1100 32.6 23.9 44 609.2 7467.4 7458.5 0.0 0.0 0.0
1200 34.4 24.0 43 609.2 7491.5 7476.8 0.0 0.0 0.0
1300 35.8 24.0 43 609.2 7502.2 7486.1 0.0 0.0 0.0
1400 36.7 24.0 42 609.2 7504.3 7489.3 0.0 0.0 0.0
1500 37.0 24.0 42 609.2 7506.3 7492.2 0.0 0.0 0.0
1600 36.7 24.0 42 609.2 7508.1 7494.9 0.0 0.0 0.0
1700 35.9 24.0 42 609.2 7509.8 7497.4 0.0 0.0 0.0
1800 34.6 24.0 43 609.2 7505.4 7495.5 0.0 0.0 0.0
1900 33.2 24.0 43 609.2 7488.2 7484.3 0.0 0.0 0.0
2000 31.7 23.9 44 609.2 7470.4 7472.0 0.0 0.0 0.0
2100 30.4 23.9 44 609.2 7454.8 7460.8 0.0 0.0 0.0
2200 29.3 23.9 45 609.2 7440.2 7450.0 0.0 0.0 0.0
2300 28.4 23.9 45 609.2 7427.9 7440.5 0.0 0.0 0.0

ZONE: GF-01 Refrigration Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.1 45 125.0 0.0 0.0 0.0 1005.5 0.0
0100 27.2 20.1 46 125.0 0.0 0.0 0.0 1005.5 0.0
0200 26.6 20.1 46 125.0 0.0 0.0 0.0 1005.5 0.0
0300 26.2 20.1 46 125.0 0.0 0.0 0.0 1005.5 0.0
0400 25.8 20.1 46 125.0 0.0 0.0 0.0 1005.5 0.0
0500 25.7 20.1 46 125.0 0.0 0.0 0.0 1005.5 0.0
0600 25.9 20.1 46 125.0 0.0 0.0 0.0 1005.5 0.0
0700 26.5 20.1 46 125.0 0.0 0.0 0.0 1005.5 0.0
0800 27.5 20.1 46 125.0 0.0 0.0 0.0 1005.5 0.0
0900 29.0 20.1 45 125.0 0.0 0.0 0.0 1005.5 0.0
1000 30.7 20.1 44 125.0 0.0 0.0 0.0 1005.5 0.0
1100 32.6 20.1 44 125.0 0.0 0.0 0.0 1005.5 0.0
1200 34.4 20.1 43 125.0 0.0 0.0 0.0 1005.5 0.0
1300 35.8 20.1 43 125.0 0.0 0.0 0.0 1005.5 0.0
1400 36.7 20.1 42 125.0 0.0 0.0 0.0 1005.5 0.0
1500 37.0 20.1 42 125.0 0.0 0.0 0.0 1005.5 0.0
1600 36.7 20.1 42 125.0 0.0 0.0 0.0 1005.5 0.0
1700 35.9 20.1 42 125.0 0.0 0.0 0.0 1005.5 0.0
1800 34.6 20.1 43 125.0 0.0 0.0 0.0 1005.5 0.0
1900 33.2 20.1 43 125.0 0.0 0.0 0.0 1005.5 0.0
2000 31.7 20.1 44 125.0 0.0 0.0 0.0 1005.5 0.0
2100 30.4 20.1 44 125.0 0.0 0.0 0.0 1005.5 0.0
2200 29.3 20.1 45 125.0 0.0 0.0 0.0 1005.5 0.0
2300 28.4 20.1 45 125.0 0.0 0.0 0.0 1005.5 0.0

Hourly Analysis Program v4.80 Page 158 of 263


System Psychrometrics for AHU-H-C3-05 GF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:10PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 2050 400 30193 20069
Vent - Return Mixing Outlet 37.0 0.01203 2050 400 - -
Preheat Coil Outlet 37.0 0.01203 2050 400 0 -
Central Cooling Coil Outlet 11.1 0.00789 2050 400 58400 22840
Supply Fan Outlet 12.8 0.00789 2050 400 3797 -
Cold Supply Duct Outlet 12.8 0.00789 2050 400 - -
Zone Air - 23.6 0.00839 2050 488 23405 2772
Return Plenum Outlet 23.6 0.00839 2050 488 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
GF-03 Dishwash 2828 Deadband 2801 23.9 230 564 0 0
GF-04 Corridor 3553 Deadband 3506 23.8 289 465 0 0
GF-05 Room Service 6320 Deadband 6309 24.0 513 492 0 0
GF-06 Order Taker 475 Deadband 466 23.7 39 545 0 0
GF-07 Dry Storage 431 Deadband 417 23.5 35 560 0 0
GF-02 Cold Kitchen 2452 Deadband 2414 23.3 210 490 0 0
GF-08 Hot Kitchen 7506 Deadband 7492 24.0 609 477 0 0
GF-01 Refrigration Room 0 Heating 0 20.1 125 400 1005 0

Hourly Analysis Program v4.80 Page 159 of 263


Air System Sizing Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:10PM

Air System Information


Air System Name AHU-H-C3-06 C1 Kitchen Number of zones 16
Equipment Class CW AHU Floor Area 291.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 132.4 kW Load occurs at Jul 1500
Sensible coil load 95.1 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 3340 L/s Entering DB / WB 37.0 / 22.0 °C
Max block L/s at Jul 1600 3340 L/s Leaving DB / WB 11.1 / 10.0 °C
Sum of peak zone L/s 3401 L/s Coil ADP 8.2 °C
Sensible heat ratio 0.719 Bypass Factor 0.100
m²/kW 2.2 Resulting RH 60 %
W/m² 454.8 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 4.73 L/s Zone T-stat Check 16 of 16 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 50.0 kW Load occurs at Des Htg
Coil L/s at Des Htg 3340 L/s Ent. DB / Lvg DB -0.8 / 12.8 °C
Max coil L/s 3340 L/s
Water flow @ 11.0 °K drop 1.09 L/s

Supply Fan Sizing Data


Actual max L/s at Jul 1600 3340 L/s Fan motor BHP 7.80 BHP
Standard L/s 3045 L/s Fan motor kW 6.19 kW
Actual max L/(s-m²) 11.48 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 3340 L/s L/s/person 58.60 L/s/person
L/(s-m²) 11.48 L/(s-m²)

Hourly Analysis Program v4.80 Page 160 of 263


Zone Sizing Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:10PM

Air System Information


Air System Name AHU-H-C3-06 C1 Kitchen Number of zones 16
Equipment Class CW AHU Floor Area 291.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C1-02 Waste Handling 3.1 530 530 Jul 1600 0.5 31.0 17.10
C1-05 Flower Room 1.6 133 133 Jul 1700 0.8 22.0 6.04
C1-13 F&V Sanitization 0.6 45 45 Jul 1700 0.0 7.0 6.46
C1-14 - Cold Kitchen 2.1 172 172 Jul 1700 0.2 28.0 6.13
C1-15 Sea Food Prep 0.4 33 33 Jul 1700 0.1 7.0 4.77
C1-16 Meat Prep 1.2 95 95 Jul 1700 0.1 11.0 8.66
C1-26 Chocolate Room 1.4 111 111 Jul 1600 0.3 8.0 13.84
C1-17 Pork Prep 0.6 80 80 Jul 1700 0.0 7.0 11.43
C1-22 Dry Storage 0.5 40 40 Jul 1700 0.2 15.0 2.67
C1-23 Mini Bar Storage 0.3 22 22 Jul 1700 0.0 5.0 4.50
C1-24 Beverage Storage 1.4 151 151 Jul 1700 0.3 27.0 5.58
C1-26 Bakery 6.7 544 544 Jul 1600 1.5 63.0 8.63
C1-18 Kitchen Corridor 0.9 73 22 Jul 1700 0.3 39.0 1.87
Refrigration Comp 1 0.0 694 694 Des Htg 0.0 1.0 694.00
Refrigeration RM 2 0.0 630 630 Des Htg 0.0 1.0 630.00
C1-04 Waste Chiller 0.6 48 48 Jul 1600 0.4 19.0 2.54

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
C1-02 Waste Handling 5.3 0.11 0.0 0.00 0
C1-05 Flower Room 2.0 0.04 0.0 0.00 0
C1-13 F&V Sanitization 0.4 0.01 0.0 0.00 0
C1-14 - Cold Kitchen 1.7 0.04 0.0 0.00 0
C1-15 Sea Food Prep 0.4 0.01 0.0 0.00 0
C1-16 Meat Prep 0.9 0.02 0.0 0.00 0
C1-26 Chocolate Room 1.3 0.03 0.0 0.00 0
C1-17 Pork Prep 0.8 0.02 0.0 0.00 0
C1-22 Dry Storage 0.6 0.01 0.0 0.00 0
C1-23 Mini Bar Storage 0.2 0.01 0.0 0.00 0
C1-24 Beverage Storage 1.2 0.03 0.0 0.00 0
C1-26 Bakery 6.4 0.14 0.0 0.00 0
C1-18 Kitchen Corridor 0.5 0.01 0.0 0.00 0
Refrigration Comp 1 0.0 0.00 0.0 0.00 0
Refrigeration RM 2 0.0 0.00 0.0 0.00 0
C1-04 Waste Chiller 0.8 0.02 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)

Hourly Analysis Program v4.80 Page 161 of 263


Zone Sizing Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:10PM

C1-02 Waste Handling


C1K2-02 Waste Handling 1 3.1 Jul 1600 530 0.5 31.0 17.10
C1-05 Flower Room
C1K2-05 Flower Room 1 1.6 Jul 1700 133 0.8 22.0 6.04
C1-13 F&V Sanitization
C1K2-13 F&V Sanitation 1 0.6 Jul 1700 45 0.0 7.0 6.46
C1-14 - Cold Kitchen
C1K2-14 Cold Kitchen 1 2.1 Jul 1700 172 0.2 28.0 6.13
C1-15 Sea Food Prep
C1K2-15 Sea Food Prep 1 0.4 Jul 1700 33 0.1 7.0 4.77
C1-16 Meat Prep
C1K2-16 Meat Prep 1 1.2 Jul 1700 95 0.1 11.0 8.66
C1-26 Chocolate Room
C1K2-26 Chocolate Room 1 1.4 Jul 1600 111 0.3 8.0 13.84
C1-17 Pork Prep
C1K2-17 Pork Prep 1 0.6 Jul 1700 80 0.0 7.0 11.43
C1-22 Dry Storage
C1K2-22 Dry Storage 1 0.5 Jul 1700 40 0.2 15.0 2.67
C1-23 Mini Bar Storage
C1K2-23 Mini Bar Stor 1 0.3 Jul 1700 22 0.0 5.0 4.50
C1-24 Beverage Storage
C1K2-24 Beverage Storage 1 1.4 Jul 1700 151 0.3 27.0 5.58
C1-26 Bakery
C1K2-26 Bakery 1 6.7 Jul 1600 544 1.5 63.0 8.63
C1-18 Kitchen Corridor
C1K2-25 Kitchen Corridor 1 0.9 Jul 1700 73 0.3 39.0 1.87
Refrigration Comp 1
C1K2 - Refrigration RM 1 1 0.0 Jan 0000 694 0.0 1.0 694.00
Refrigeration RM 2
C1K2 - Refrigration RM 2 1 0.0 Jan 0000 630 0.0 1.0 630.00
C1-04 Waste Chiller
C1K2-04 Waste Chiller 1 0.6 Jul 1600 48 0.4 19.0 2.54

Hourly Analysis Program v4.80 Page 162 of 263


Ventilation Sizing Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:10PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 3340 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
C1-02 Waste Handling
C1K2-02 Waste Handling 1 31.0 7.0 530.0 0.00 0.00 0.0 100.0 530.0
C1-05 Flower Room
C1K2-05 Flower Room 1 22.0 5.0 132.8 0.00 0.00 0.0 100.0 132.8
C1-13 F&V Sanitization
C1K2-13 F&V Sanitation 1 7.0 2.0 45.2 0.00 0.00 0.0 100.0 45.2
C1-14 - Cold Kitchen
C1K2-14 Cold Kitchen 1 28.0 6.0 171.6 0.00 0.00 0.0 100.0 171.6
C1-15 Sea Food Prep
C1K2-15 Sea Food Prep 1 7.0 2.0 33.4 0.00 0.00 0.0 100.0 33.4
C1-16 Meat Prep
C1K2-16 Meat Prep 1 11.0 3.0 95.2 0.00 0.00 0.0 100.0 95.2
C1-26 Chocolate Room
C1K2-26 Chocolate Room 1 8.0 2.0 110.7 0.00 0.00 0.0 100.0 110.7
C1-17 Pork Prep
C1K2-17 Pork Prep 1 7.0 2.0 80.0 0.00 0.00 0.0 100.0 80.0
C1-22 Dry Storage
C1K2-22 Dry Storage 1 15.0 3.0 40.1 0.00 0.00 0.0 100.0 40.1
C1-23 Mini Bar Storage
C1K2-23 Mini Bar Stor 1 5.0 1.0 22.5 0.00 0.00 0.0 100.0 22.5
C1-24 Beverage Storage
C1K2-24 Beverage Storage 1 27.0 6.0 150.7 0.00 0.00 0.0 100.0 150.7
C1-26 Bakery
C1K2-26 Bakery 1 63.0 13.0 543.8 0.00 0.00 0.0 100.0 543.8
C1-18 Kitchen Corridor
C1K2-25 Kitchen Corridor 1 39.0 4.0 73.0 0.00 0.30 0.0 0.0 11.7
Refrigration Comp 1
C1K2 - Refrigration RM 1 1 1.0 0.0 694.0 0.00 0.00 694.0 100.0 1388.0
Refrigeration RM 2
C1K2 - Refrigration RM 2 1 1.0 0.0 630.0 0.00 0.00 630.0 100.0 1260.0
C1-04 Waste Chiller
C1K2-04 Waste Chiller 1 19.0 1.0 48.3 0.00 0.00 0.0 100.0 48.3
Totals (incl. Space Multipliers) 3401.2 3340.0

Hourly Analysis Program v4.80 Page 163 of 263


Air System Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:11PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 92 m² 865 - 92 m² 466 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 235 m² 954 - 235 m² 1708 -
Partitions 102 m² 1037 - 102 m² 1940 -
Ceiling 22 m² 88 - 22 m² 132 -
Overhead Lighting 3519 W 3518 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 57 4707 6474 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 8109 0 - 0 0
Safety Factor 10% / 10% 1928 647 10% 425 0
>> Total Zone Loads - 21205 7121 - 4671 0
Zone Conditioning - 20893 7121 - 4338 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2740 L/s 0 - 2732 L/s 0 -
Ventilation Load 3340 L/s 66852 30089 3340 L/s 65736 0
Supply Fan Load 3340 L/s 6185 - 3340 L/s -6185 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 93930 37210 - 63889 0
Central Cooling Coil - 95143 37210 - -6185 0
Preheat Coil - 0 - - 49993 -
Terminal Reheat Coils - -1565 - - 20130 -
>> Total Conditioning - 93577 37210 - 63937 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 164 of 263


Zone Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:11PM

C1-02 Waste Handling DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 31 m² 291 - 31 m² 157 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 188 - 15 m² 281 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 255 W 255 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 7 605 933 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1452 0 - 0 0
Safety Factor 10% / 10% 279 93 10% 44 0
>> Total Zone Loads - 3071 1026 - 482 0

C1-05 Flower Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 30 m² 384 - 30 m² 570 -
Ceiling 22 m² 89 - 22 m² 132 -
Overhead Lighting 79 W 79 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 504 0 - 0 0
Safety Factor 10% / 10% 149 67 10% 70 0
>> Total Zone Loads - 1637 733 - 772 0

Hourly Analysis Program v4.80 Page 165 of 263


Zone Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:11PM

C1-13 F&V Sanitization DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 6 m² 24 - 6 m² 36 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 85 W 85 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 224 0 - 0 0
Safety Factor 10% / 10% 51 27 10% 4 0
>> Total Zone Loads - 557 293 - 40 0

C1-14 - Cold Kitchen DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 114 - 28 m² 168 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 342 W 342 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 6 519 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 948 0 - 0 0
Safety Factor 10% / 10% 192 80 10% 17 0
>> Total Zone Loads - 2115 880 - 185 0

Hourly Analysis Program v4.80 Page 166 of 263


Zone Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:11PM

C1-15 Sea Food Prep DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 24 - 7 m² 92 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 154 W 154 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 23 0 - 0 0
Safety Factor 10% / 10% 37 27 10% 9 0
>> Total Zone Loads - 412 293 - 101 0

C1-16 Meat Prep DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 11 m² 45 - 11 m² 66 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 242 W 242 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 521 0 - 0 0
Safety Factor 10% / 10% 107 40 10% 7 0
>> Total Zone Loads - 1174 440 - 73 0

Hourly Analysis Program v4.80 Page 167 of 263


Zone Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:11PM

C1-26 Chocolate Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 8 m² 75 - 8 m² 41 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 8 m² 32 - 8 m² 48 -
Partitions 8 m² -8 - 8 m² 148 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 98 W 98 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 870 0 - 0 0
Safety Factor 10% / 10% 124 27 10% 24 0
>> Total Zone Loads - 1364 293 - 260 0

C1-17 Pork Prep DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 28 - 7 m² 42 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 154 W 154 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 170 0 - 0 0
Safety Factor 10% / 10% 53 27 10% 4 0
>> Total Zone Loads - 578 293 - 46 0

Hourly Analysis Program v4.80 Page 168 of 263


Zone Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:11PM

C1-22 Dry Storage DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 15 m² 52 - 15 m² 196 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 182 W 182 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 45 18 10% 20 0
>> Total Zone Loads - 494 198 - 216 0

C1-23 Mini Bar Storage DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 5 m² 20 - 5 m² 30 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 160 W 160 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 25 6 10% 3 0
>> Total Zone Loads - 277 66 - 33 0

Hourly Analysis Program v4.80 Page 169 of 263


Zone Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:11PM

C1-24 Beverage Storage DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 142 - 27 m² 305 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 328 W 328 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 336 0 - 0 0
Safety Factor 10% / 10% 124 36 10% 30 0
>> Total Zone Loads - 1360 397 - 335 0

C1-26 Bakery DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 42 m² 394 - 42 m² 213 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 63 m² 254 - 63 m² 378 -
Partitions 39 m² 496 - 39 m² 741 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 765 W 765 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 13 1124 1733 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3061 0 - 0 0
Safety Factor 10% / 10% 609 173 10% 133 0
>> Total Zone Loads - 6703 1906 - 1465 0

Hourly Analysis Program v4.80 Page 170 of 263


Zone Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:11PM

C1-18 Kitchen Corridor DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 39 m² 158 - 39 m² 234 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 390 W 390 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 82 14 10% 23 0
>> Total Zone Loads - 900 155 - 257 0

Refrigration Comp 1 DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

Hourly Analysis Program v4.80 Page 171 of 263


Zone Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:11PM

Refrigeration RM 2 DESIGN COOLING DESIGN HEATING


NO COOLING DATA HEATING DATA AT DES HTG
NO COOLING OA DB / WB HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² - - 0 m² - -
Wall Transmission 0 m² - - 0 m² 0 -
Roof Transmission 0 m² - - 0 m² 0 -
Window Transmission 0 m² - - 0 m² 0 -
Skylight Transmission 0 m² - - 0 m² 0 -
Door Loads 0 m² - - 0 m² 0 -
Floor Transmission 0 m² - - 0 m² 0 -
Partitions 0 m² - - 0 m² 0 -
Ceiling 0 m² - - 0 m² 0 -
Overhead Lighting - - - 0 0 -
Task Lighting - - - 0 0 -
Electric Equipment - - - 0 0 -
People - - - 0 0 0
Infiltration - - - - 0 0
Miscellaneous - - - - 0 0
Safety Factor 10% / 10% - - 10% 0 0
>> Total Zone Loads - - - - 0 0

C1-04 Waste Chiller DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 11 m² 103 - 11 m² 56 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 77 - 19 m² 114 -
Partitions 11 m² -10 - 11 m² 200 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 285 W 285 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 86 133 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 54 13 10% 37 0
>> Total Zone Loads - 595 147 - 406 0

Hourly Analysis Program v4.80 Page 172 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1K2-02 Waste Handling '' IN ZONE '' C1-02 Waste Handling ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 31 m² 291 - 31 m² 157 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 188 - 15 m² 281 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 255 W 255 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 7 605 933 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1452 0 - 0 0
Safety Factor 10% / 10% 279 93 10% 44 0
>> Total Zone Loads - 3071 1026 - 482 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-02 Waste Handling '' IN ZONE '' C1-02 Waste Handling ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 31 0.232 - 291 - 157

Hourly Analysis Program v4.80 Page 173 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' C1K2-05 Flower Room '' IN ZONE '' C1-05 Flower Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 30 m² 384 - 30 m² 570 -
Ceiling 22 m² 89 - 22 m² 132 -
Overhead Lighting 79 W 79 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 504 0 - 0 0
Safety Factor 10% / 10% 149 67 10% 70 0
>> Total Zone Loads - 1637 733 - 772 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-05 Flower Room '' IN ZONE '' C1-05 Flower Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 174 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' C1K2-13 F&V Sanitation '' IN ZONE '' C1-13 F&V Sanitization ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 6 m² 24 - 6 m² 36 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 85 W 85 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 224 0 - 0 0
Safety Factor 10% / 10% 51 27 10% 4 0
>> Total Zone Loads - 557 293 - 40 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-13 F&V Sanitation '' IN ZONE '' C1-13 F&V Sanitization ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 175 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' C1K2-14 Cold Kitchen '' IN ZONE '' C1-14 - Cold Kitchen ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 114 - 28 m² 168 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 342 W 342 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 6 519 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 948 0 - 0 0
Safety Factor 10% / 10% 192 80 10% 17 0
>> Total Zone Loads - 2115 880 - 185 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-14 Cold Kitchen '' IN ZONE '' C1-14 - Cold Kitchen ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 176 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' C1K2-15 Sea Food Prep '' IN ZONE '' C1-15 Sea Food Prep ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 24 - 7 m² 92 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 154 W 154 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 23 0 - 0 0
Safety Factor 10% / 10% 37 27 10% 9 0
>> Total Zone Loads - 412 293 - 101 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-15 Sea Food Prep '' IN ZONE '' C1-15 Sea Food Prep ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 177 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' C1K2-16 Meat Prep '' IN ZONE '' C1-16 Meat Prep ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 11 m² 45 - 11 m² 66 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 242 W 242 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 521 0 - 0 0
Safety Factor 10% / 10% 107 40 10% 7 0
>> Total Zone Loads - 1174 440 - 73 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-16 Meat Prep '' IN ZONE '' C1-16 Meat Prep ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 178 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' C1K2-26 Chocolate Room '' IN ZONE '' C1-26 Chocolate Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 8 m² 75 - 8 m² 41 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 8 m² 32 - 8 m² 48 -
Partitions 8 m² -8 - 8 m² 148 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 98 W 98 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 870 0 - 0 0
Safety Factor 10% / 10% 124 27 10% 24 0
>> Total Zone Loads - 1364 293 - 260 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-26 Chocolate Room '' IN ZONE '' C1-26 Chocolate Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 8 0.232 - 75 - 41

Hourly Analysis Program v4.80 Page 179 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' C1K2-17 Pork Prep '' IN ZONE '' C1-17 Pork Prep ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 28 - 7 m² 42 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 154 W 154 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 170 0 - 0 0
Safety Factor 10% / 10% 53 27 10% 4 0
>> Total Zone Loads - 578 293 - 46 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-17 Pork Prep '' IN ZONE '' C1-17 Pork Prep ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 180 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' C1K2-22 Dry Storage '' IN ZONE '' C1-22 Dry Storage ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 15 m² 52 - 15 m² 196 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 182 W 182 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 45 18 10% 20 0
>> Total Zone Loads - 494 198 - 216 0

TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-22 Dry Storage '' IN ZONE '' C1-22 Dry Storage ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 181 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 10.1.A. COMPONENT LOADS FOR SPACE '' C1K2-23 Mini Bar Stor '' IN ZONE '' C1-23 Mini Bar Storage ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 5 m² 20 - 5 m² 30 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 160 W 160 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 25 6 10% 3 0
>> Total Zone Loads - 277 66 - 33 0

TABLE 10.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-23 Mini Bar Stor '' IN ZONE '' C1-23 Mini Bar Storage ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 182 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 11.1.A. COMPONENT LOADS FOR SPACE '' C1K2-24 Beverage Storage '' IN ZONE '' C1-24 Beverage Storage ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 142 - 27 m² 305 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 328 W 328 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 336 0 - 0 0
Safety Factor 10% / 10% 124 36 10% 30 0
>> Total Zone Loads - 1360 397 - 335 0

TABLE 11.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-24 Beverage Storage '' IN ZONE '' C1-24 Beverage Storage ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 183 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 12.1.A. COMPONENT LOADS FOR SPACE '' C1K2-26 Bakery '' IN ZONE '' C1-26 Bakery ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 42 m² 394 - 42 m² 213 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 63 m² 254 - 63 m² 378 -
Partitions 39 m² 496 - 39 m² 741 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 765 W 765 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 13 1124 1733 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3061 0 - 0 0
Safety Factor 10% / 10% 609 173 10% 133 0
>> Total Zone Loads - 6703 1906 - 1465 0

TABLE 12.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-26 Bakery '' IN ZONE '' C1-26 Bakery ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 42 0.232 - 394 - 213

Hourly Analysis Program v4.80 Page 184 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 13.1.A. COMPONENT LOADS FOR SPACE '' C1K2-25 Kitchen Corridor '' IN ZONE '' C1-18 Kitchen Corridor ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 39 m² 158 - 39 m² 234 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 390 W 390 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 82 14 10% 23 0
>> Total Zone Loads - 900 155 - 257 0

TABLE 13.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-25 Kitchen Corridor '' IN ZONE '' C1-18 Kitchen Corridor ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 185 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 14.1.A. COMPONENT LOADS FOR SPACE '' C1K2 - Refrigration RM 1 '' IN ZONE '' Refrigration Comp 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 14.1.B. ENVELOPE LOADS FOR SPACE '' C1K2 - Refrigration RM 1 '' IN ZONE '' Refrigration Comp 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 186 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 15.1.A. COMPONENT LOADS FOR SPACE '' C1K2 - Refrigration RM 2 '' IN ZONE '' Refrigeration RM 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 16.4 °C / 11.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 0 0 10% 0 0
>> Total Zone Loads - 0 0 - 0 0

TABLE 15.1.B. ENVELOPE LOADS FOR SPACE '' C1K2 - Refrigration RM 2 '' IN ZONE '' Refrigeration RM 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 187 of 263


Space Design Load Summary for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:12PM

TABLE 16.1.A. COMPONENT LOADS FOR SPACE '' C1K2-04 Waste Chiller '' IN ZONE '' C1-04 Waste Chiller ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 11 m² 103 - 11 m² 56 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 77 - 19 m² 114 -
Partitions 11 m² -10 - 11 m² 200 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 285 W 285 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 86 133 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 54 13 10% 37 0
>> Total Zone Loads - 595 147 - 406 0

TABLE 16.1.B. ENVELOPE LOADS FOR SPACE '' C1K2-04 Waste Chiller '' IN ZONE '' C1-04 Waste Chiller ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 11 0.232 - 103 - 56

Hourly Analysis Program v4.80 Page 188 of 263


Hourly Air System Design Day Loads for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:14PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 3340 61.1 93.9 0.0 0.0 0.0 0.0 1.8 0.0
0100 27.2 3340 59.0 91.6 0.0 0.0 0.0 0.0 1.9 0.0
0200 26.6 3340 56.9 89.2 0.0 0.0 0.0 0.0 1.9 0.0
0300 26.2 3340 55.3 87.3 0.0 0.0 0.0 0.0 1.9 0.0
0400 25.8 3340 54.0 85.9 0.0 0.0 0.0 0.0 1.9 0.0
0500 25.7 3340 53.6 85.4 0.0 0.0 0.0 0.0 1.9 0.0
0600 25.9 3340 54.4 86.4 0.0 0.0 0.0 0.0 1.9 0.0
0700 26.5 3340 56.5 88.7 0.0 0.0 0.0 0.0 1.9 0.0
0800 27.5 3340 60.3 93.0 0.0 0.0 0.0 0.0 1.9 0.0
0900 29.0 3340 65.7 99.1 0.0 0.0 0.0 0.0 1.8 0.0
1000 30.7 3340 71.9 106.1 0.0 0.0 0.0 0.0 1.8 0.0
1100 32.6 3340 78.9 114.1 0.0 0.0 0.0 0.0 1.7 0.0
1200 34.4 3340 85.6 121.6 0.0 0.0 0.0 0.0 1.6 0.0
1300 35.8 3340 90.6 127.2 0.0 0.0 0.0 0.0 1.6 0.0
1400 36.7 3340 93.9 130.9 0.0 0.0 0.0 0.0 1.6 0.0
1500 37.0 3340 95.1 132.4 0.0 0.0 0.0 0.0 1.6 0.0
1600 36.7 3340 93.9 130.9 0.0 0.0 0.0 0.0 1.6 0.0
1700 35.9 3340 91.0 127.7 0.0 0.0 0.0 0.0 1.6 0.0
1800 34.6 3340 86.4 122.5 0.0 0.0 0.0 0.0 1.6 0.0
1900 33.2 3340 81.0 116.4 0.0 0.0 0.0 0.0 1.7 0.0
2000 31.7 3340 75.6 110.3 0.0 0.0 0.0 0.0 1.7 0.0
2100 30.4 3340 71.1 105.2 0.0 0.0 0.0 0.0 1.7 0.0
2200 29.3 3340 66.9 100.5 0.0 0.0 0.0 0.0 1.8 0.0
2300 28.4 3340 63.6 96.8 0.0 0.0 0.0 0.0 1.8 0.0

Hourly Analysis Program v4.80 Page 189 of 263


Hourly Zone Loads for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:14PM

ZONE: C1-02 Waste Handling


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.7 64 522.1 2761.6 2885.9 0.0 1708.0 0.0
0100 27.2 20.7 64 522.1 2739.6 2864.3 0.0 1727.5 0.0
0200 26.6 20.7 65 522.2 2719.9 2844.7 0.0 1745.1 0.0
0300 26.2 20.7 65 522.3 2703.1 2828.0 0.0 1760.2 0.0
0400 25.8 20.7 65 522.3 2688.8 2813.7 0.0 1773.1 0.0
0500 25.7 20.7 65 522.3 2678.5 2803.0 0.0 1782.6 0.0
0600 25.9 20.7 65 522.3 2676.1 2799.9 0.0 1785.5 0.0
0700 26.5 20.7 65 522.3 2689.3 2811.7 0.0 1774.9 0.0
0800 27.5 20.7 65 522.3 2724.3 2844.1 0.0 1745.6 0.0
0900 29.0 20.7 64 522.2 2777.7 2894.3 0.0 1700.5 0.0
1000 30.7 20.7 63 522.1 2841.6 2954.8 0.0 1646.0 0.0
1100 32.6 20.7 62 521.9 2911.1 3020.9 0.0 1586.5 0.0
1200 34.4 20.7 61 521.8 2977.4 3084.4 0.0 1529.3 0.0
1300 35.8 20.7 61 521.7 3025.6 3131.1 0.0 1487.2 0.0
1400 36.7 20.7 60 521.7 3054.3 3159.6 0.0 1461.7 0.0
1500 37.0 20.7 60 521.7 3069.9 3175.7 0.0 1447.2 0.0
1600 36.7 20.7 60 521.6 3070.9 3177.8 0.0 1445.2 0.0
1700 35.9 20.7 60 521.6 3056.7 3165.5 0.0 1456.3 0.0
1800 34.6 20.7 61 521.6 3021.1 3132.8 0.0 1485.8 0.0
1900 33.2 20.7 62 521.7 2964.5 3079.9 0.0 1533.4 0.0
2000 31.7 20.7 62 521.8 2907.4 3026.0 0.0 1581.9 0.0
2100 30.4 20.7 63 521.9 2859.8 2980.7 0.0 1622.7 0.0
2200 29.3 20.7 63 522.0 2820.0 2942.6 0.0 1657.0 0.0
2300 28.4 20.7 64 522.0 2787.7 2911.4 0.0 1685.1 0.0

ZONE: C1-05 Flower Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.2 64 130.8 1416.1 1520.4 0.0 0.0 0.0
0100 27.2 23.1 64 130.8 1396.0 1511.5 0.0 0.0 0.0
0200 26.6 23.1 65 130.9 1375.6 1502.2 0.0 0.0 0.0
0300 26.2 23.0 65 130.9 1358.2 1493.6 0.0 0.0 0.0
0400 25.8 23.0 65 130.9 1344.1 1485.9 0.0 0.0 0.0
0500 25.7 22.9 65 130.9 1336.7 1480.3 0.0 0.0 0.0
0600 25.9 22.9 65 130.9 1339.6 1478.2 0.0 0.0 0.0
0700 26.5 22.9 65 130.9 1353.1 1479.9 0.0 0.0 0.0
0800 27.5 23.0 65 130.9 1380.9 1486.9 0.0 0.0 0.0
0900 29.0 23.1 64 130.9 1423.4 1499.7 0.0 0.0 0.0
1000 30.7 23.2 63 130.8 1474.1 1516.3 0.0 0.0 0.0
1100 32.6 23.3 62 130.8 1533.1 1536.8 0.0 0.0 0.0
1200 34.4 23.5 61 130.8 1590.4 1558.1 0.0 0.0 0.0
1300 35.8 23.5 61 130.7 1618.9 1571.0 0.0 0.0 0.0
1400 36.7 23.6 60 130.7 1623.9 1576.4 0.0 0.0 0.0
1500 37.0 23.6 60 130.7 1628.7 1581.4 0.0 0.0 0.0
1600 36.7 23.7 60 130.7 1633.1 1586.1 0.0 0.0 0.0
1700 35.9 23.7 60 130.7 1637.2 1590.7 0.0 0.0 0.0
1800 34.6 23.7 61 130.7 1623.9 1589.3 0.0 0.0 0.0
1900 33.2 23.6 62 130.7 1582.9 1578.2 0.0 0.0 0.0
2000 31.7 23.5 62 130.8 1540.5 1565.4 0.0 0.0 0.0
2100 30.4 23.4 63 130.8 1503.3 1553.2 0.0 0.0 0.0
2200 29.3 23.3 63 130.8 1468.4 1541.0 0.0 0.0 0.0
2300 28.4 23.3 64 130.8 1439.2 1530.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 190 of 263


Hourly Zone Loads for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:14PM

ZONE: C1-13 F&V Sanitization


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.8 64 44.6 546.4 549.7 0.0 0.0 0.0
0100 27.2 23.8 64 44.6 545.4 549.1 0.0 0.0 0.0
0200 26.6 23.8 65 44.6 544.3 548.5 0.0 0.0 0.0
0300 26.2 23.8 65 44.6 543.4 547.9 0.0 0.0 0.0
0400 25.8 23.8 65 44.6 542.7 547.4 0.0 0.0 0.0
0500 25.7 23.8 65 44.6 542.3 547.1 0.0 0.0 0.0
0600 25.9 23.8 65 44.6 542.5 546.9 0.0 0.0 0.0
0700 26.5 23.8 65 44.6 543.2 547.0 0.0 0.0 0.0
0800 27.5 23.8 65 44.6 544.6 547.4 0.0 0.0 0.0
0900 29.0 23.8 64 44.6 546.8 548.2 0.0 0.0 0.0
1000 30.7 23.8 63 44.5 549.4 549.2 0.0 0.0 0.0
1100 32.6 23.9 62 44.5 552.5 550.5 0.0 0.0 0.0
1200 34.4 23.9 61 44.5 555.4 551.8 0.0 0.0 0.0
1300 35.8 23.9 61 44.5 556.6 552.5 0.0 0.0 0.0
1400 36.7 23.9 60 44.5 556.8 552.9 0.0 0.0 0.0
1500 37.0 23.9 60 44.5 557.1 553.2 0.0 0.0 0.0
1600 36.7 23.9 60 44.5 557.3 553.5 0.0 0.0 0.0
1700 35.9 23.9 60 44.5 557.5 553.8 0.0 0.0 0.0
1800 34.6 23.9 61 44.5 557.1 553.9 0.0 0.0 0.0
1900 33.2 23.9 62 44.5 555.0 553.2 0.0 0.0 0.0
2000 31.7 23.9 62 44.5 552.8 552.4 0.0 0.0 0.0
2100 30.4 23.9 63 44.5 550.9 551.7 0.0 0.0 0.0
2200 29.3 23.9 63 44.5 549.1 550.9 0.0 0.0 0.0
2300 28.4 23.9 64 44.5 547.6 550.3 0.0 0.0 0.0

ZONE: C1-14 - Cold Kitchen


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.8 64 169.0 2063.0 2078.8 0.0 0.0 0.0
0100 27.2 23.8 64 169.0 2058.2 2076.3 0.0 0.0 0.0
0200 26.6 23.8 65 169.0 2053.3 2073.6 0.0 0.0 0.0
0300 26.2 23.8 65 169.1 2049.1 2071.1 0.0 0.0 0.0
0400 25.8 23.8 65 169.1 2045.7 2068.9 0.0 0.0 0.0
0500 25.7 23.7 65 169.1 2043.9 2067.2 0.0 0.0 0.0
0600 25.9 23.7 65 169.1 2044.6 2066.5 0.0 0.0 0.0
0700 26.5 23.7 65 169.1 2047.9 2066.8 0.0 0.0 0.0
0800 27.5 23.8 65 169.1 2054.6 2068.7 0.0 0.0 0.0
0900 29.0 23.8 64 169.0 2064.8 2072.1 0.0 0.0 0.0
1000 30.7 23.8 63 169.0 2077.0 2076.7 0.0 0.0 0.0
1100 32.6 23.8 62 168.9 2091.2 2082.5 0.0 0.0 0.0
1200 34.4 23.9 61 168.9 2105.0 2088.5 0.0 0.0 0.0
1300 35.8 23.9 61 168.9 2110.5 2091.6 0.0 0.0 0.0
1400 36.7 23.9 60 168.9 2111.6 2093.2 0.0 0.0 0.0
1500 37.0 23.9 60 168.9 2112.7 2094.7 0.0 0.0 0.0
1600 36.7 23.9 60 168.9 2113.8 2096.1 0.0 0.0 0.0
1700 35.9 23.9 60 168.8 2114.7 2097.5 0.0 0.0 0.0
1800 34.6 23.9 61 168.8 2112.9 2097.7 0.0 0.0 0.0
1900 33.2 23.9 62 168.9 2103.1 2094.8 0.0 0.0 0.0
2000 31.7 23.9 62 168.9 2092.9 2091.3 0.0 0.0 0.0
2100 30.4 23.9 63 168.9 2084.0 2088.0 0.0 0.0 0.0
2200 29.3 23.8 63 169.0 2075.6 2084.6 0.0 0.0 0.0
2300 28.4 23.8 64 169.0 2068.6 2081.5 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 191 of 263


Hourly Zone Loads for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:14PM

ZONE: C1-15 Sea Food Prep


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.5 64 32.9 381.3 391.5 0.0 0.0 0.0
0100 27.2 23.4 64 32.9 378.4 390.2 0.0 0.0 0.0
0200 26.6 23.4 65 32.9 375.5 388.8 0.0 0.0 0.0
0300 26.2 23.3 65 32.9 373.1 387.5 0.0 0.0 0.0
0400 25.8 23.3 65 32.9 371.1 386.3 0.0 0.0 0.0
0500 25.7 23.3 65 32.9 370.1 385.5 0.0 0.0 0.0
0600 25.9 23.3 65 32.9 370.5 385.0 0.0 0.0 0.0
0700 26.5 23.3 65 32.9 372.4 385.2 0.0 0.0 0.0
0800 27.5 23.3 65 32.9 376.3 386.0 0.0 0.0 0.0
0900 29.0 23.3 64 32.9 382.3 387.7 0.0 0.0 0.0
1000 30.7 23.4 63 32.9 389.5 390.0 0.0 0.0 0.0
1100 32.6 23.5 62 32.9 397.8 392.9 0.0 0.0 0.0
1200 34.4 23.6 61 32.9 405.9 395.9 0.0 0.0 0.0
1300 35.8 23.6 61 32.9 409.1 397.5 0.0 0.0 0.0
1400 36.7 23.6 60 32.9 409.8 398.3 0.0 0.0 0.0
1500 37.0 23.7 60 32.9 410.5 399.1 0.0 0.0 0.0
1600 36.7 23.7 60 32.9 411.1 399.9 0.0 0.0 0.0
1700 35.9 23.7 60 32.9 411.6 400.6 0.0 0.0 0.0
1800 34.6 23.7 61 32.9 410.6 400.8 0.0 0.0 0.0
1900 33.2 23.7 62 32.9 404.8 399.4 0.0 0.0 0.0
2000 31.7 23.6 62 32.9 398.8 397.7 0.0 0.0 0.0
2100 30.4 23.6 63 32.9 393.6 396.1 0.0 0.0 0.0
2200 29.3 23.5 63 32.9 388.6 394.4 0.0 0.0 0.0
2300 28.4 23.5 64 32.9 384.5 392.8 0.0 0.0 0.0

ZONE: C1-16 Meat Prep


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.9 64 93.8 1153.5 1158.9 0.0 0.0 0.0
0100 27.2 23.8 64 93.8 1151.6 1157.7 0.0 0.0 0.0
0200 26.6 23.8 65 93.8 1149.7 1156.5 0.0 0.0 0.0
0300 26.2 23.8 65 93.8 1148.0 1155.3 0.0 0.0 0.0
0400 25.8 23.8 65 93.8 1146.7 1154.3 0.0 0.0 0.0
0500 25.7 23.8 65 93.9 1146.0 1153.6 0.0 0.0 0.0
0600 25.9 23.8 65 93.9 1146.3 1153.3 0.0 0.0 0.0
0700 26.5 23.8 65 93.8 1147.6 1153.6 0.0 0.0 0.0
0800 27.5 23.8 65 93.8 1150.2 1154.5 0.0 0.0 0.0
0900 29.0 23.8 64 93.8 1154.2 1156.2 0.0 0.0 0.0
1000 30.7 23.9 63 93.8 1159.0 1158.4 0.0 0.0 0.0
1100 32.6 23.9 62 93.8 1164.6 1161.2 0.0 0.0 0.0
1200 34.4 23.9 61 93.8 1170.0 1164.0 0.0 0.0 0.0
1300 35.8 23.9 61 93.7 1172.2 1165.5 0.0 0.0 0.0
1400 36.7 23.9 60 93.7 1172.6 1166.2 0.0 0.0 0.0
1500 37.0 23.9 60 93.7 1173.1 1166.8 0.0 0.0 0.0
1600 36.7 23.9 60 93.7 1173.5 1167.4 0.0 0.0 0.0
1700 35.9 23.9 60 93.7 1173.8 1168.0 0.0 0.0 0.0
1800 34.6 23.9 61 93.7 1173.1 1168.1 0.0 0.0 0.0
1900 33.2 23.9 62 93.7 1169.3 1166.6 0.0 0.0 0.0
2000 31.7 23.9 62 93.8 1165.3 1164.9 0.0 0.0 0.0
2100 30.4 23.9 63 93.8 1161.7 1163.3 0.0 0.0 0.0
2200 29.3 23.9 63 93.8 1158.5 1161.6 0.0 0.0 0.0
2300 28.4 23.9 64 93.8 1155.7 1160.2 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 192 of 263


Hourly Zone Loads for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:14PM

ZONE: C1-26 Chocolate Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.4 64 109.0 1263.4 1291.9 0.0 0.0 0.0
0100 27.2 23.4 64 109.0 1255.7 1286.6 0.0 0.0 0.0
0200 26.6 23.3 65 109.1 1248.6 1281.4 0.0 0.0 0.0
0300 26.2 23.3 65 109.1 1242.5 1276.8 0.0 0.0 0.0
0400 25.8 23.2 65 109.1 1237.5 1272.7 0.0 0.0 0.0
0500 25.7 23.2 65 109.1 1234.1 1269.4 0.0 0.0 0.0
0600 25.9 23.2 65 109.1 1233.7 1267.9 0.0 0.0 0.0
0700 26.5 23.2 65 109.1 1238.5 1269.2 0.0 0.0 0.0
0800 27.5 23.3 65 109.1 1250.3 1274.6 0.0 0.0 0.0
0900 29.0 23.3 64 109.0 1268.3 1283.8 0.0 0.0 0.0
1000 30.7 23.4 63 109.0 1289.8 1295.5 0.0 0.0 0.0
1100 32.6 23.5 62 109.0 1313.6 1309.0 0.0 0.0 0.0
1200 34.4 23.7 61 109.0 1336.4 1322.5 0.0 0.0 0.0
1300 35.8 23.7 61 109.0 1351.3 1332.3 0.0 0.0 0.0
1400 36.7 23.8 60 108.9 1359.1 1338.4 0.0 0.0 0.0
1500 37.0 23.8 60 108.9 1363.6 1342.7 0.0 0.0 0.0
1600 36.7 23.8 60 108.9 1364.3 1344.9 0.0 0.0 0.0
1700 35.9 23.8 60 108.9 1361.0 1344.8 0.0 0.0 0.0
1800 34.6 23.8 61 108.9 1351.0 1340.7 0.0 0.0 0.0
1900 33.2 23.7 62 108.9 1332.3 1331.6 0.0 0.0 0.0
2000 31.7 23.6 62 109.0 1313.3 1321.6 0.0 0.0 0.0
2100 30.4 23.6 63 109.0 1297.4 1312.8 0.0 0.0 0.0
2200 29.3 23.5 63 109.0 1283.6 1304.8 0.0 0.0 0.0
2300 28.4 23.5 64 109.0 1272.4 1297.8 0.0 0.0 0.0

ZONE: C1-17 Pork Prep


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.8 64 78.8 565.0 578.8 0.0 128.5 0.0
0100 27.2 20.8 64 78.8 563.8 577.6 0.0 129.5 0.0
0200 26.6 20.8 65 78.8 562.6 576.4 0.0 130.6 0.0
0300 26.2 20.8 65 78.8 561.5 575.4 0.0 131.5 0.0
0400 25.8 20.8 65 78.8 560.7 574.5 0.0 132.3 0.0
0500 25.7 20.8 65 78.8 560.2 574.1 0.0 132.7 0.0
0600 25.9 20.8 65 78.8 560.4 574.2 0.0 132.6 0.0
0700 26.5 20.8 65 78.8 561.2 574.9 0.0 132.0 0.0
0800 27.5 20.8 65 78.8 562.9 576.4 0.0 130.6 0.0
0900 29.0 20.8 64 78.8 565.5 578.7 0.0 128.5 0.0
1000 30.7 20.8 63 78.8 568.5 581.5 0.0 126.0 0.0
1100 32.6 20.8 62 78.8 572.1 584.8 0.0 123.1 0.0
1200 34.4 20.8 61 78.8 575.5 588.1 0.0 120.1 0.0
1300 35.8 20.8 61 78.8 576.9 589.4 0.0 118.9 0.0
1400 36.7 20.8 60 78.7 577.2 589.8 0.0 118.6 0.0
1500 37.0 20.8 60 78.7 577.4 590.1 0.0 118.3 0.0
1600 36.7 20.8 60 78.7 577.7 590.4 0.0 118.0 0.0
1700 35.9 20.8 60 78.7 577.9 590.7 0.0 117.8 0.0
1800 34.6 20.8 61 78.7 577.5 590.3 0.0 118.1 0.0
1900 33.2 20.8 62 78.7 575.0 588.1 0.0 120.1 0.0
2000 31.7 20.8 62 78.8 572.5 585.8 0.0 122.2 0.0
2100 30.4 20.8 63 78.8 570.2 583.7 0.0 124.0 0.0
2200 29.3 20.8 63 78.8 568.1 581.8 0.0 125.8 0.0
2300 28.4 20.8 64 78.8 566.4 580.1 0.0 127.3 0.0

Hourly Analysis Program v4.80 Page 193 of 263


Hourly Zone Loads for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:14PM

ZONE: C1-22 Dry Storage


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.1 64 39.5 429.2 456.0 0.0 0.0 0.0
0100 27.2 23.1 64 39.5 423.2 454.1 0.0 0.0 0.0
0200 26.6 23.0 65 39.5 417.0 452.1 0.0 0.0 0.0
0300 26.2 23.0 65 39.5 411.7 450.2 0.0 0.0 0.0
0400 25.8 23.0 65 39.5 407.5 448.4 0.0 0.0 0.0
0500 25.7 22.9 65 39.5 405.2 447.0 0.0 0.0 0.0
0600 25.9 22.9 65 39.5 406.1 446.3 0.0 0.0 0.0
0700 26.5 22.9 65 39.5 410.2 446.3 0.0 0.0 0.0
0800 27.5 22.9 65 39.5 418.7 447.4 0.0 0.0 0.0
0900 29.0 23.0 64 39.5 431.5 449.6 0.0 0.0 0.0
1000 30.7 23.1 63 39.5 446.9 452.7 0.0 0.0 0.0
1100 32.6 23.1 62 39.5 464.8 456.7 0.0 0.0 0.0
1200 34.4 23.2 61 39.5 482.1 460.9 0.0 0.0 0.0
1300 35.8 23.3 61 39.5 489.0 463.3 0.0 0.0 0.0
1400 36.7 23.3 60 39.5 490.5 464.6 0.0 0.0 0.0
1500 37.0 23.4 60 39.5 491.8 465.8 0.0 0.0 0.0
1600 36.7 23.4 60 39.5 493.1 467.0 0.0 0.0 0.0
1700 35.9 23.4 60 39.5 494.3 468.2 0.0 0.0 0.0
1800 34.6 23.4 61 39.5 492.1 468.6 0.0 0.0 0.0
1900 33.2 23.4 62 39.5 479.7 466.8 0.0 0.0 0.0
2000 31.7 23.3 62 39.5 466.9 464.5 0.0 0.0 0.0
2100 30.4 23.3 63 39.5 455.6 462.3 0.0 0.0 0.0
2200 29.3 23.2 63 39.5 445.0 459.9 0.0 0.0 0.0
2300 28.4 23.2 64 39.5 436.2 457.8 0.0 0.0 0.0

ZONE: C1-23 Mini Bar Storage


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.8 64 22.2 268.0 271.2 0.0 0.0 0.0
0100 27.2 23.7 64 22.2 267.2 270.8 0.0 0.0 0.0
0200 26.6 23.7 65 22.2 266.3 270.4 0.0 0.0 0.0
0300 26.2 23.7 65 22.2 265.6 270.1 0.0 0.0 0.0
0400 25.8 23.7 65 22.2 265.0 269.7 0.0 0.0 0.0
0500 25.7 23.7 65 22.2 264.6 269.5 0.0 0.0 0.0
0600 25.9 23.7 65 22.2 264.8 269.3 0.0 0.0 0.0
0700 26.5 23.7 65 22.2 265.4 269.4 0.0 0.0 0.0
0800 27.5 23.7 65 22.2 266.6 269.6 0.0 0.0 0.0
0900 29.0 23.7 64 22.2 268.4 270.1 0.0 0.0 0.0
1000 30.7 23.7 63 22.2 270.6 270.8 0.0 0.0 0.0
1100 32.6 23.8 62 22.2 273.1 271.6 0.0 0.0 0.0
1200 34.4 23.8 61 22.1 275.6 272.5 0.0 0.0 0.0
1300 35.8 23.8 61 22.1 276.5 273.0 0.0 0.0 0.0
1400 36.7 23.8 60 22.1 276.7 273.2 0.0 0.0 0.0
1500 37.0 23.8 60 22.1 276.9 273.4 0.0 0.0 0.0
1600 36.7 23.9 60 22.1 277.1 273.7 0.0 0.0 0.0
1700 35.9 23.9 60 22.1 277.3 273.9 0.0 0.0 0.0
1800 34.6 23.9 61 22.1 277.0 273.9 0.0 0.0 0.0
1900 33.2 23.8 62 22.1 275.2 273.5 0.0 0.0 0.0
2000 31.7 23.8 62 22.1 273.4 273.0 0.0 0.0 0.0
2100 30.4 23.8 63 22.2 271.8 272.6 0.0 0.0 0.0
2200 29.3 23.8 63 22.2 270.3 272.1 0.0 0.0 0.0
2300 28.4 23.8 64 22.2 269.0 271.6 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 194 of 263


Hourly Zone Loads for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:14PM

ZONE: C1-24 Beverage Storage


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.5 64 148.5 1243.1 1280.3 0.0 0.0 0.0
0100 27.2 20.5 64 148.5 1232.1 1274.8 0.0 0.0 0.0
0200 26.6 20.5 65 148.5 1221.0 1269.0 0.0 0.0 0.0
0300 26.2 20.4 65 148.5 1211.6 1263.6 0.0 0.0 0.0
0400 25.8 20.4 65 148.5 1203.9 1258.7 0.0 0.0 0.0
0500 25.7 20.4 65 148.5 1199.9 1255.0 0.0 0.0 0.0
0600 25.9 20.4 65 148.5 1201.5 1253.4 0.0 0.0 0.0
0700 26.5 20.4 65 148.5 1208.9 1254.1 0.0 0.0 0.0
0800 27.5 20.4 65 148.5 1224.0 1257.9 0.0 0.0 0.0
0900 29.0 20.4 64 148.5 1247.2 1265.3 0.0 0.0 0.0
1000 30.7 20.5 63 148.5 1274.9 1275.1 0.0 0.0 0.0
1100 32.6 20.6 62 148.4 1307.1 1287.3 0.0 0.0 0.0
1200 34.4 20.6 61 148.4 1338.3 1300.2 0.0 0.0 0.0
1300 35.8 20.7 61 148.4 1350.6 1307.0 0.0 0.0 0.0
1400 36.7 20.7 60 148.4 1353.3 1310.5 0.0 0.0 0.0
1500 37.0 20.7 60 148.4 1355.8 1313.7 0.0 0.0 0.0
1600 36.7 20.7 60 148.3 1358.1 1316.8 0.0 0.0 0.0
1700 35.9 20.8 60 148.3 1360.3 1319.8 0.0 0.0 0.0
1800 34.6 20.8 61 148.3 1356.2 1320.5 0.0 0.0 0.0
1900 33.2 20.7 62 148.4 1333.9 1314.3 0.0 0.0 0.0
2000 31.7 20.7 62 148.4 1310.8 1307.0 0.0 0.0 0.0
2100 30.4 20.6 63 148.4 1290.5 1299.9 0.0 0.0 0.0
2200 29.3 20.6 63 148.4 1271.5 1292.7 0.0 0.0 0.0
2300 28.4 20.6 64 148.5 1255.7 1286.1 0.0 0.0 0.0

ZONE: C1-26 Bakery


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.3 64 535.7 6058.3 6273.8 0.0 0.0 0.0
0100 27.2 23.2 64 535.7 6007.4 6243.5 0.0 0.0 0.0
0200 26.6 23.2 65 535.8 5959.1 6213.6 0.0 0.0 0.0
0300 26.2 23.1 65 535.8 5918.0 6186.2 0.0 0.0 0.0
0400 25.8 23.1 65 535.9 5883.9 6161.4 0.0 0.0 0.0
0500 25.7 23.1 65 535.9 5862.1 6141.8 0.0 0.0 0.0
0600 25.9 23.0 65 535.9 5861.9 6131.9 0.0 0.0 0.0
0700 26.5 23.1 65 535.9 5894.1 6137.0 0.0 0.0 0.0
0800 27.5 23.1 65 535.8 5970.8 6163.4 0.0 0.0 0.0
0900 29.0 23.2 64 535.7 6087.9 6210.5 0.0 0.0 0.0
1000 30.7 23.3 63 535.6 6228.0 6271.5 0.0 0.0 0.0
1100 32.6 23.4 62 535.5 6384.4 6343.7 0.0 0.0 0.0
1200 34.4 23.5 61 535.3 6534.6 6417.4 0.0 0.0 0.0
1300 35.8 23.6 61 535.3 6626.8 6469.3 0.0 0.0 0.0
1400 36.7 23.7 60 535.2 6670.9 6501.3 0.0 0.0 0.0
1500 37.0 23.7 60 535.2 6696.9 6525.4 0.0 0.0 0.0
1600 36.7 23.7 60 535.2 6702.8 6540.3 0.0 0.0 0.0
1700 35.9 23.7 60 535.2 6687.8 6545.1 0.0 0.0 0.0
1800 34.6 23.7 61 535.2 6628.8 6529.3 0.0 0.0 0.0
1900 33.2 23.6 62 535.3 6509.0 6484.2 0.0 0.0 0.0
2000 31.7 23.6 62 535.4 6386.8 6433.8 0.0 0.0 0.0
2100 30.4 23.5 63 535.4 6283.1 6387.8 0.0 0.0 0.0
2200 29.3 23.4 63 535.5 6192.4 6344.8 0.0 0.0 0.0
2300 28.4 23.3 64 535.6 6118.0 6306.8 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 195 of 263


Hourly Zone Loads for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:14PM

ZONE: C1-18 Kitchen Corridor


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 64 61.4 827.6 821.0 0.0 0.0 0.0
0100 27.2 24.8 64 61.0 820.9 815.8 0.0 0.0 0.0
0200 26.6 24.8 65 60.7 814.0 810.4 0.0 0.0 0.0
0300 26.2 24.8 65 60.3 808.2 805.5 0.0 0.0 0.0
0400 25.8 24.7 65 60.0 803.5 801.3 0.0 0.0 0.0
0500 25.7 24.7 65 59.9 801.0 798.4 0.0 0.0 0.0
0600 25.9 24.7 65 59.8 802.0 797.8 0.0 0.0 0.0
0700 26.5 24.7 65 59.9 806.6 799.5 0.0 0.0 0.0
0800 27.5 24.8 65 60.3 815.9 804.6 0.0 0.0 0.0
0900 29.0 24.8 64 60.8 830.1 813.0 0.0 0.0 0.0
1000 30.7 24.8 63 61.5 847.1 823.7 0.0 0.0 0.0
1100 32.6 24.8 62 62.4 866.9 836.7 0.0 0.0 0.0
1200 34.4 24.8 61 63.3 886.1 849.9 0.0 0.0 0.0
1300 35.8 24.8 61 63.7 893.7 856.2 0.0 0.0 0.0
1400 36.7 24.8 60 63.9 895.3 858.8 0.0 0.0 0.0
1500 37.0 24.8 60 64.0 896.9 861.2 0.0 0.0 0.0
1600 36.7 24.8 60 64.2 898.3 863.4 0.0 0.0 0.0
1700 35.9 24.8 60 64.3 899.6 865.6 0.0 0.0 0.0
1800 34.6 24.8 61 64.3 897.1 865.2 0.0 0.0 0.0
1900 33.2 24.8 62 63.8 883.4 857.6 0.0 0.0 0.0
2000 31.7 24.8 62 63.2 869.2 849.1 0.0 0.0 0.0
2100 30.4 24.8 63 62.7 856.8 841.3 0.0 0.0 0.0
2200 29.3 24.8 63 62.2 845.1 833.6 0.0 0.0 0.0
2300 28.4 24.8 64 61.7 835.3 826.8 0.0 0.0 0.0

ZONE: Refrigration Comp 1


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 12.8 64 683.6 0.0 0.0 0.0 0.0 0.0
0100 27.2 12.8 64 683.7 0.0 0.0 0.0 0.0 0.0
0200 26.6 12.8 65 683.8 0.0 0.0 0.0 0.0 0.0
0300 26.2 12.8 65 683.9 0.0 0.0 0.0 0.0 0.0
0400 25.8 12.8 65 683.9 0.0 0.0 0.0 0.0 0.0
0500 25.7 12.8 65 684.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 12.8 65 684.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 12.8 65 683.9 0.0 0.0 0.0 0.0 0.0
0800 27.5 12.8 65 683.9 0.0 0.0 0.0 0.0 0.0
0900 29.0 12.8 64 683.8 0.0 0.0 0.0 0.0 0.0
1000 30.7 12.8 63 683.6 0.0 0.0 0.0 0.0 0.0
1100 32.6 12.8 62 683.4 0.0 0.0 0.0 0.0 0.0
1200 34.4 12.8 61 683.2 0.0 0.0 0.0 0.0 0.0
1300 35.8 12.8 61 683.2 0.0 0.0 0.0 0.0 0.0
1400 36.7 12.8 60 683.1 0.0 0.0 0.0 0.0 0.0
1500 37.0 12.8 60 683.1 0.0 0.0 0.0 0.0 0.0
1600 36.7 12.8 60 683.1 0.0 0.0 0.0 0.0 0.0
1700 35.9 12.8 60 683.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 12.8 61 683.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 12.8 62 683.1 0.0 0.0 0.0 0.0 0.0
2000 31.7 12.8 62 683.3 0.0 0.0 0.0 0.0 0.0
2100 30.4 12.8 63 683.4 0.0 0.0 0.0 0.0 0.0
2200 29.3 12.8 63 683.5 0.0 0.0 0.0 0.0 0.0
2300 28.4 12.8 64 683.6 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 196 of 263


Hourly Zone Loads for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:14PM

ZONE: Refrigeration RM 2
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 12.8 64 620.6 0.0 0.0 0.0 0.0 0.0
0100 27.2 12.8 64 620.7 0.0 0.0 0.0 0.0 0.0
0200 26.6 12.8 65 620.7 0.0 0.0 0.0 0.0 0.0
0300 26.2 12.8 65 620.8 0.0 0.0 0.0 0.0 0.0
0400 25.8 12.8 65 620.8 0.0 0.0 0.0 0.0 0.0
0500 25.7 12.8 65 620.9 0.0 0.0 0.0 0.0 0.0
0600 25.9 12.8 65 620.9 0.0 0.0 0.0 0.0 0.0
0700 26.5 12.8 65 620.9 0.0 0.0 0.0 0.0 0.0
0800 27.5 12.8 65 620.8 0.0 0.0 0.0 0.0 0.0
0900 29.0 12.8 64 620.7 0.0 0.0 0.0 0.0 0.0
1000 30.7 12.8 63 620.6 0.0 0.0 0.0 0.0 0.0
1100 32.6 12.8 62 620.4 0.0 0.0 0.0 0.0 0.0
1200 34.4 12.8 61 620.2 0.0 0.0 0.0 0.0 0.0
1300 35.8 12.8 61 620.2 0.0 0.0 0.0 0.0 0.0
1400 36.7 12.8 60 620.1 0.0 0.0 0.0 0.0 0.0
1500 37.0 12.8 60 620.1 0.0 0.0 0.0 0.0 0.0
1600 36.7 12.8 60 620.1 0.0 0.0 0.0 0.0 0.0
1700 35.9 12.8 60 620.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 12.8 61 620.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 12.8 62 620.1 0.0 0.0 0.0 0.0 0.0
2000 31.7 12.8 62 620.2 0.0 0.0 0.0 0.0 0.0
2100 30.4 12.8 63 620.3 0.0 0.0 0.0 0.0 0.0
2200 29.3 12.8 63 620.4 0.0 0.0 0.0 0.0 0.0
2300 28.4 12.8 64 620.5 0.0 0.0 0.0 0.0 0.0

ZONE: C1-04 Waste Chiller


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.7 64 47.5 442.5 526.7 0.0 0.0 0.0
0100 27.2 22.7 64 47.6 430.7 523.4 0.0 0.0 0.0
0200 26.6 22.6 65 47.6 419.6 520.0 0.0 0.0 0.0
0300 26.2 22.5 65 47.6 410.1 516.9 0.0 0.0 0.0
0400 25.8 22.5 65 47.6 402.2 513.9 0.0 0.0 0.0
0500 25.7 22.4 65 47.6 397.1 511.4 0.0 0.0 0.0
0600 25.9 22.4 65 47.6 396.8 509.7 0.0 0.0 0.0
0700 26.5 22.4 65 47.6 404.2 509.7 0.0 0.0 0.0
0800 27.5 22.4 65 47.6 422.3 511.8 0.0 0.0 0.0
0900 29.0 22.5 64 47.6 449.7 516.1 0.0 0.0 0.0
1000 30.7 22.6 63 47.5 482.7 522.1 0.0 0.0 0.0
1100 32.6 22.8 62 47.5 519.2 529.3 0.0 0.0 0.0
1200 34.4 22.9 61 47.5 554.3 536.9 0.0 0.0 0.0
1300 35.8 23.0 61 47.5 576.1 542.6 0.0 0.0 0.0
1400 36.7 23.1 60 47.5 587.3 546.5 0.0 0.0 0.0
1500 37.0 23.1 60 47.5 593.8 549.6 0.0 0.0 0.0
1600 36.7 23.2 60 47.5 595.0 551.7 0.0 0.0 0.0
1700 35.9 23.2 60 47.5 590.7 552.7 0.0 0.0 0.0
1800 34.6 23.2 61 47.5 576.4 551.6 0.0 0.0 0.0
1900 33.2 23.1 62 47.5 548.1 547.5 0.0 0.0 0.0
2000 31.7 23.0 62 47.5 519.3 542.7 0.0 0.0 0.0
2100 30.4 22.9 63 47.5 494.9 538.3 0.0 0.0 0.0
2200 29.3 22.9 63 47.5 473.7 534.0 0.0 0.0 0.0
2300 28.4 22.8 64 47.5 456.4 530.1 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 197 of 263


System Psychrometrics for AHU-H-C3-06 C1 Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:17PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 3340 400 66852 30089
Vent - Return Mixing Outlet 37.0 0.01203 3340 400 - -
Preheat Coil Outlet 37.0 0.01203 3340 400 0 -
Central Cooling Coil Outlet 11.1 0.00789 3340 400 95143 37210
Supply Fan Outlet 12.8 0.00789 3340 400 6185 -
Cold Supply Duct Outlet 12.8 0.00789 3340 400 - -
Zone Air - 18.4 0.00868 3340 544 20893 7121
Zone Direct Exhaust Outlet 18.4 0.00868 600 544 - -
Return Plenum Outlet 18.4 0.00868 2740 544 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
C1-02 Waste Handling 3070 Heating 3176 20.7 522 527 1447 0
C1-05 Flower Room 1629 Deadband 1581 23.6 131 761 0 0
C1-13 F&V Sanitization 557 Deadband 553 23.9 45 824 0 0
C1-14 - Cold Kitchen 2113 Deadband 2095 23.9 169 735 0 0
C1-15 Sea Food Prep 410 Deadband 399 23.7 33 974 0 0
C1-16 Meat Prep 1173 Deadband 1167 23.9 94 702 0 0
C1-26 Chocolate Room 1364 Deadband 1343 23.8 109 573 0 0
C1-17 Pork Prep 577 Heating 590 20.8 79 640 118 0
C1-22 Dry Storage 492 Deadband 466 23.4 39 830 0 0
C1-23 Mini Bar Storage 277 Deadband 273 23.8 22 656 0 0
C1-24 Beverage Storage 1356 Deadband 1314 20.7 148 629 0 0
C1-26 Bakery 6697 Deadband 6525 23.7 535 629 0 0
C1-18 Kitchen Corridor 897 Cooling 861 24.8 64 675 0 0
Refrigration Comp 1 0 Deadband 0 12.8 683 400 0 0
Refrigeration RM 2 0 Deadband 0 12.8 620 400 0 0
C1-04 Waste Chiller 594 Deadband 550 23.1 48 599 0 0

Hourly Analysis Program v4.80 Page 198 of 263


Air System Sizing Summary for AHU-H-C3-07 EL Substation
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:18PM

Air System Information


Air System Name AHU-H-C3-07 EL Substation Number of zones 1
Equipment Class CW AHU Floor Area 135.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 51.5 kW Load occurs at Jul 1700
Sensible coil load 51.5 kW OA DB / WB 35.9 / 21.7 °C
Coil L/s at Jul 1700 2730 L/s Entering DB / WB 29.9 / 9.7 °C
Max block L/s at Jul 1700 2910 L/s Leaving DB / WB 12.8 / 1.4 °C
Sum of peak zone L/s 2910 L/s Coil ADP 10.9 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 2.6 Resulting RH 0 %
W/m² 381.8 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 1.84 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s at Jul 1700 2910 L/s Fan motor BHP 0.00 BHP
Standard L/s 2653 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 21.56 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.80 Page 199 of 263


Zone Sizing Summary for AHU-H-C3-07 EL Substation
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:18PM

Air System Information


Air System Name AHU-H-C3-07 EL Substation Number of zones 1
Equipment Class CW AHU Floor Area 135.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C3-31 EL Substation 52.0 2910 29 Jul 1700 4.6 135.0 21.56

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C3-31 EL Substation
EL-C2-31 Substation 1 52.0 Jul 1700 2910 4.6 135.0 21.56

Hourly Analysis Program v4.80 Page 200 of 263


Ventilation Sizing Summary for AHU-H-C3-07 EL Substation
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:18PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
C3-31 EL Substation
EL-C2-31 Substation 1 135.0 0.0 2910.0 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 2910.0 0.0

Hourly Analysis Program v4.80 Page 201 of 263


Air System Design Load Summary for AHU-H-C3-07 EL Substation
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:18PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 135 m² 143 - 135 m² 810 -
Partitions 158 m² 524 - 158 m² 3006 -
Ceiling 66 m² 69 - 66 m² 396 -
Overhead Lighting 999 W 999 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 45500 W 45498 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4723 0 10% 421 0
>> Total Zone Loads - 51956 0 - 4633 0
Zone Conditioning - 51547 0 - 1 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2730 L/s 0 - 29 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 2730 L/s 0 - 29 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 51547 0 - 1 0
Central Cooling Coil - 51547 0 - 0 0
Preheat Coil - 0 - - 0 -
>> Total Conditioning - 51547 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 202 of 263


Zone Design Load Summary for AHU-H-C3-07 EL Substation
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:18PM

C3-31 EL Substation DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 29.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 135 m² 143 - 135 m² 810 -
Partitions 158 m² 524 - 158 m² 3006 -
Ceiling 66 m² 69 - 66 m² 396 -
Overhead Lighting 999 W 999 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 45500 W 45498 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4723 0 10% 421 0
>> Total Zone Loads - 51956 0 - 4633 0

Hourly Analysis Program v4.80 Page 203 of 263


Space Design Load Summary for AHU-H-C3-07 EL Substation
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:18PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' EL-C2-31 Substation '' IN ZONE '' C3-31 EL Substation ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 29.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 135 m² 143 - 135 m² 810 -
Partitions 158 m² 524 - 158 m² 3006 -
Ceiling 66 m² 69 - 66 m² 396 -
Overhead Lighting 999 W 999 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 45500 W 45498 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4723 0 10% 421 0
>> Total Zone Loads - 51956 0 - 4633 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' EL-C2-31 Substation '' IN ZONE '' C3-31 EL Substation ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 204 of 263


Hourly Air System Design Day Loads for AHU-H-C3-07 EL Substation
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:18PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 2666 50.3 50.3 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 2660 50.1 50.1 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 2654 50.0 50.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 2649 49.9 49.9 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 2644 49.8 49.8 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 2642 49.8 49.8 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 2643 49.8 49.8 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 2647 49.9 49.9 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 2655 50.0 50.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 2667 50.3 50.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 2682 50.6 50.6 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 2699 50.9 50.9 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 2716 51.3 51.3 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 2724 51.4 51.4 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 2726 51.5 51.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 2727 51.5 51.5 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 2729 51.5 51.5 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 2730 51.5 51.5 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 2727 51.5 51.5 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 2715 51.2 51.2 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 2702 51.0 51.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 2691 50.8 50.8 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 2681 50.6 50.6 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 2673 50.4 50.4 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 205 of 263


Hourly Zone Loads for AHU-H-C3-07 EL Substation
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:18PM

ZONE: C3-31 EL Substation


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 29.9 - 2665.8 50634.9 50266.8 0.0 0.0 0.0
0100 27.2 29.9 - 2659.9 50514.1 50147.8 0.0 0.0 0.0
0200 26.6 29.9 - 2653.8 50391.5 50026.9 0.0 0.0 0.0
0300 26.2 29.9 - 2648.6 50287.4 49923.9 0.0 0.0 0.0
0400 25.8 29.9 - 2644.4 50202.7 49839.6 0.0 0.0 0.0
0500 25.7 29.9 - 2642.1 50158.3 49794.4 0.0 0.0 0.0
0600 25.9 29.9 - 2642.9 50175.8 49809.3 0.0 0.0 0.0
0700 26.5 29.9 - 2646.7 50257.0 49886.2 0.0 0.0 0.0
0800 27.5 29.9 - 2654.8 50424.1 50046.8 0.0 0.0 0.0
0900 29.0 29.9 - 2667.2 50679.0 50293.2 0.0 0.0 0.0
1000 30.7 29.9 - 2682.0 50983.4 50588.3 0.0 0.0 0.0
1100 32.6 29.9 - 2699.2 51337.9 50932.9 0.0 0.0 0.0
1200 34.4 29.9 - 2716.0 51682.0 51268.5 0.0 0.0 0.0
1300 35.8 29.9 - 2724.2 51846.5 51430.9 0.0 0.0 0.0
1400 36.7 29.9 - 2725.8 51876.6 51463.1 0.0 0.0 0.0
1500 37.0 29.9 - 2727.3 51904.8 51493.0 0.0 0.0 0.0
1600 36.7 29.9 - 2728.7 51931.1 51520.9 0.0 0.0 0.0
1700 35.9 29.9 - 2730.0 51955.7 51546.8 0.0 0.0 0.0
1800 34.6 29.9 - 2726.5 51882.5 51478.0 0.0 0.0 0.0
1900 33.2 29.9 - 2714.7 51636.8 51241.6 0.0 0.0 0.0
2000 31.7 29.9 - 2702.3 51381.7 50994.9 0.0 0.0 0.0
2100 30.4 29.9 - 2691.5 51158.6 50778.4 0.0 0.0 0.0
2200 29.3 29.9 - 2681.2 50948.8 50574.2 0.0 0.0 0.0
2300 28.4 29.9 - 2672.7 50773.9 50403.3 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 206 of 263


System Psychrometrics for AHU-H-C3-07 EL Substation
Project Name: J17006-0100D FD REV2
Prepared by: dar

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 0 400 0 0
Vent - Return Mixing Outlet 29.9 0.00000 2727 800 - -
Preheat Coil Outlet 29.9 0.00000 2727 800 0 -
Central Cooling Coil Outlet 12.8 0.00000 2727 800 51493 0
Supply Fan Outlet 12.8 0.00000 2727 800 0 -
Cold Supply Duct Outlet 12.8 0.00000 2727 800 - -
Zone Air - 29.9 0.00000 2727 800 51493 0
Return Plenum Outlet 29.9 0.00000 2727 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
C3-31 EL Substation 51905 Cooling 51493 29.9 2727 800 0 0

Hourly Analysis Program v4.80


Air System Sizing Summary for AHU-H-C3-08 MDB
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:19PM

Air System Information


Air System Name AHU-H-C3-08 MDB Number of zones 1
Equipment Class CW AHU Floor Area 151.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 34.7 kW Load occurs at Jul 1700
Sensible coil load 34.7 kW OA DB / WB 35.9 / 21.7 °C
Coil L/s at Jul 1700 1952 L/s Entering DB / WB 28.9 / 9.3 °C
Max block L/s at Jul 1700 2098 L/s Leaving DB / WB 12.8 / 1.4 °C
Sum of peak zone L/s 2098 L/s Coil ADP 11.0 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 4.4 Resulting RH 0 %
W/m² 229.8 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 1.24 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max L/s at Jul 1700 2098 L/s Fan motor BHP 0.00 BHP
Standard L/s 1912 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 13.89 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.80 Page 208 of 263


Zone Sizing Summary for AHU-H-C3-08 MDB
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:19PM

Air System Information


Air System Name AHU-H-C3-08 MDB Number of zones 1
Equipment Class CW AHU Floor Area 151.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C2-32 MDB Room 35.1 2098 21 Jul 1700 4.9 151.0 13.89

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C2-32 MDB Room
EL-C2-32 MDB Room 1 35.1 Jul 1700 2098 4.9 151.0 13.89

Hourly Analysis Program v4.80 Page 209 of 263


Ventilation Sizing Summary for AHU-H-C3-08 MDB
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:19PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
C2-32 MDB Room
EL-C2-32 MDB Room 1 151.0 0.0 2097.5 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 2097.5 0.0

Hourly Analysis Program v4.80 Page 210 of 263


Air System Design Load Summary for AHU-H-C3-08 MDB
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:19PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 151 m² 250 - 151 m² 906 -
Partitions 183 m² 952 - 183 m² 3471 -
Ceiling 17 m² 28 - 17 m² 102 -
Overhead Lighting 1117 W 1117 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 29600 W 29599 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3195 0 10% 448 0
>> Total Zone Loads - 35141 0 - 4927 0
Zone Conditioning - 34699 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1952 L/s 0 - 21 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1952 L/s 0 - 21 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 34699 0 - 0 0
Central Cooling Coil - 34699 0 - 0 0
Preheat Coil - 0 - - 0 -
>> Total Conditioning - 34699 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 211 of 263


Zone Design Load Summary for AHU-H-C3-08 MDB
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:19PM

C2-32 MDB Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 28.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 151 m² 250 - 151 m² 906 -
Partitions 183 m² 952 - 183 m² 3471 -
Ceiling 17 m² 28 - 17 m² 102 -
Overhead Lighting 1117 W 1117 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 29600 W 29599 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3195 0 10% 448 0
>> Total Zone Loads - 35141 0 - 4927 0

Hourly Analysis Program v4.80 Page 212 of 263


Space Design Load Summary for AHU-H-C3-08 MDB
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:19PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' EL-C2-32 MDB Room '' IN ZONE '' C2-32 MDB Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 28.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 151 m² 250 - 151 m² 906 -
Partitions 183 m² 952 - 183 m² 3471 -
Ceiling 17 m² 28 - 17 m² 102 -
Overhead Lighting 1117 W 1117 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 29600 W 29599 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3195 0 10% 448 0
>> Total Zone Loads - 35141 0 - 4927 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' EL-C2-32 MDB Room '' IN ZONE '' C2-32 MDB Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 213 of 263


Hourly Air System Design Day Loads for AHU-H-C3-08 MDB
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:19PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 1882 33.4 33.4 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 1875 33.2 33.2 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 1868 33.1 33.1 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 1862 33.0 33.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 1857 32.9 32.9 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 1855 32.9 32.9 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 1856 32.9 32.9 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 1860 33.0 33.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 1869 33.1 33.1 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 1882 33.4 33.4 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 1899 33.7 33.7 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 1918 34.0 34.0 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 1937 34.4 34.4 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 1946 34.6 34.6 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 1948 34.6 34.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 1949 34.6 34.6 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 1951 34.7 34.7 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 1952 34.7 34.7 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 1949 34.6 34.6 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 1936 34.4 34.4 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 1922 34.1 34.1 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 1910 33.9 33.9 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 1899 33.7 33.7 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 1889 33.5 33.5 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 214 of 263


Hourly Zone Loads for AHU-H-C3-08 MDB
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:20PM

ZONE: C2-32 MDB Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 28.9 - 1881.5 33736.7 33364.5 0.0 0.0 0.0
0100 27.2 28.9 - 1874.8 33608.3 33239.1 0.0 0.0 0.0
0200 26.6 28.9 - 1868.0 33477.8 33111.6 0.0 0.0 0.0
0300 26.2 28.9 - 1862.2 33367.1 33002.8 0.0 0.0 0.0
0400 25.8 28.9 - 1857.5 33277.0 32913.4 0.0 0.0 0.0
0500 25.7 28.9 - 1854.9 33229.7 32864.7 0.0 0.0 0.0
0600 25.9 28.9 - 1855.6 33248.4 32878.9 0.0 0.0 0.0
0700 26.5 28.9 - 1859.9 33334.8 32958.1 0.0 0.0 0.0
0800 27.5 28.9 - 1868.7 33512.4 33124.6 0.0 0.0 0.0
0900 29.0 28.9 - 1882.4 33783.6 33381.3 0.0 0.0 0.0
1000 30.7 28.9 - 1898.8 34107.3 33689.3 0.0 0.0 0.0
1100 32.6 28.9 - 1917.9 34484.3 34049.4 0.0 0.0 0.0
1200 34.4 28.9 - 1936.6 34850.3 34400.8 0.0 0.0 0.0
1300 35.8 28.9 - 1945.7 35024.9 34571.8 0.0 0.0 0.0
1400 36.7 28.9 - 1947.6 35056.9 34607.4 0.0 0.0 0.0
1500 37.0 28.9 - 1949.3 35086.8 34640.3 0.0 0.0 0.0
1600 36.7 28.9 - 1950.9 35114.8 34670.9 0.0 0.0 0.0
1700 35.9 28.9 - 1952.4 35140.9 34699.4 0.0 0.0 0.0
1800 34.6 28.9 - 1948.7 35063.5 34629.3 0.0 0.0 0.0
1900 33.2 28.9 - 1935.7 34802.1 34383.7 0.0 0.0 0.0
2000 31.7 28.9 - 1922.1 34530.8 34126.8 0.0 0.0 0.0
2100 30.4 28.9 - 1910.0 34293.5 33900.7 0.0 0.0 0.0
2200 29.3 28.9 - 1898.7 34070.4 33687.1 0.0 0.0 0.0
2300 28.4 28.9 - 1889.1 33884.4 33507.8 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 215 of 263


System Psychrometrics for AHU-H-C3-08 MDB
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:20PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 0 400 0 0
Vent - Return Mixing Outlet 28.9 0.00000 1949 800 - -
Preheat Coil Outlet 28.9 0.00000 1949 800 0 -
Central Cooling Coil Outlet 12.8 0.00000 1949 800 34640 0
Supply Fan Outlet 12.8 0.00000 1949 800 0 -
Cold Supply Duct Outlet 12.8 0.00000 1949 800 - -
Zone Air - 28.9 0.00000 1949 800 34640 0
Return Plenum Outlet 28.9 0.00000 1949 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
C2-32 MDB Room 35087 Cooling 34640 28.9 1949 800 0 0

Hourly Analysis Program v4.80 Page 216 of 263


Air System Sizing Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:20PM

Air System Information


Air System Name AHU-H-C3-09 C1 Fresh AHU Number of zones 7
Equipment Class CW AHU Floor Area 349.5 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 64.7 kW Load occurs at Jul 1500
Sensible coil load 46.5 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 1633 L/s Entering DB / WB 37.0 / 22.0 °C
Max block L/s at Jan 0000 1633 L/s Leaving DB / WB 11.1 / 10.0 °C
Sum of peak zone L/s 1633 L/s Coil ADP 8.2 °C
Sensible heat ratio 0.719 Bypass Factor 0.100
m²/kW 5.4 Resulting RH 44 %
W/m² 185.2 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 2.31 L/s Zone T-stat Check 7 of 7 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 24.4 kW Load occurs at Des Htg
Coil L/s at Des Htg 1633 L/s Ent. DB / Lvg DB -0.8 / 12.8 °C
Max coil L/s 1633 L/s
Water flow @ 11.0 °K drop 0.53 L/s

Supply Fan Sizing Data


Actual max L/s at Jan 0000 1633 L/s Fan motor BHP 3.81 BHP
Standard L/s 1489 L/s Fan motor kW 3.02 kW
Actual max L/(s-m²) 4.67 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1633 L/s L/s/person 22.07 L/s/person
L/(s-m²) 4.67 L/(s-m²)

Hourly Analysis Program v4.80 Page 217 of 263


Zone Sizing Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:20PM

Air System Information


Air System Name AHU-H-C3-09 C1 Fresh AHU Number of zones 7
Equipment Class CW AHU Floor Area 349.5 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C1-25 Corridor 4.3 345 345 Jul 1600 2.1 88.0 3.92
C1-81 M Locker room 5.8 575 575 Jul 1600 3.9 130.0 4.42
C1-75 F WC 0.5 41 41 Jul 1600 0.1 9.0 4.52
C1-87 WC 3.0 243 243 Jul 1700 1.4 39.0 6.22
C1-83 WC 2.9 235 235 Jul 1700 1.9 37.5 6.28
C1-74 Prayer Room 1.3 107 107 Jul 1700 0.4 20.0 5.37
C1-77 F Locker 1.1 88 88 Jul 1700 0.5 26.0 3.37

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
C1-25 Corridor 5.2 0.11 0.0 0.00 0
C1-81 M Locker room 9.1 0.20 0.0 0.00 0
C1-75 F WC 0.5 0.01 0.0 0.00 0
C1-87 WC 3.6 0.08 0.0 0.00 0
C1-83 WC 4.0 0.09 0.0 0.00 0
C1-74 Prayer Room 1.4 0.03 0.0 0.00 0
C1-77 F Locker 1.3 0.03 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-25 Corridor
C1G-25 Corridor 4 1 4.3 Jul 1600 345 2.1 88.0 3.92
C1-81 M Locker room
C1G-81 M Locker Room 1 5.8 Jul 1600 575 3.9 130.0 4.42
C1-75 F WC
C1G-75 F WC 1 0.5 Jul 1600 41 0.1 9.0 4.52
C1-87 WC
C1G-87 WC 1 3.0 Jul 1700 243 1.4 39.0 6.22
C1-83 WC
C1G-83 WC 1 2.9 Jul 1700 235 1.9 37.5 6.28
C1-74 Prayer Room
C1G-74 Prayer Room 1 1.3 Jul 1700 107 0.4 20.0 5.37
C1-77 F Locker
C1G-77 F Locker 1 1.1 Jul 1700 88 0.5 26.0 3.37

Hourly Analysis Program v4.80 Page 218 of 263


Ventilation Sizing Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:20PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 1633 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
C1-25 Corridor
C1G-25 Corridor 4 1 88.0 9.0 344.8 0.00 0.00 0.0 100.0 344.8
C1-81 M Locker room
C1G-81 M Locker Room 1 130.0 19.0 575.0 0.00 0.00 0.0 100.0 575.0
C1-75 F WC
C1G-75 F WC 1 9.0 4.0 40.7 0.00 0.00 0.0 100.0 40.7
C1-87 WC
C1G-87 WC 1 39.0 15.0 242.6 0.00 0.00 0.0 100.0 242.6
C1-83 WC
C1G-83 WC 1 37.5 10.0 235.4 0.00 0.00 0.0 100.0 235.4
C1-74 Prayer Room
C1G-74 Prayer Room 1 20.0 10.0 107.3 0.00 0.00 0.0 100.0 107.3
C1-77 F Locker
C1G-77 F Locker 1 26.0 7.0 87.6 0.00 0.00 0.0 100.0 87.6
Totals (incl. Space Multipliers) 1633.4 1633.4

Hourly Analysis Program v4.80 Page 219 of 263


Air System Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:21PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 227 m² 2134 - 227 m² 1150 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 350 m² 1393 - 350 m² 2097 -
Partitions 308 m² 3885 - 308 m² 5858 -
Ceiling 46 m² 183 - 46 m² 276 -
Overhead Lighting 3182 W 3182 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 74 5115 3327 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1160 0 - 0 0
Safety Factor 10% / 10% 1705 333 10% 938 0
>> Total Zone Loads - 18757 3660 - 10319 0
Zone Conditioning - 18135 3660 - 9527 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1058 L/s 0 - 1058 L/s 0 -
Ventilation Load 1633 L/s 25369 14538 1633 L/s 37565 0
Supply Fan Load 1633 L/s 3025 - 1633 L/s -3025 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 46529 18197 - 44068 0
Central Cooling Coil - 46529 18197 - -3025 0
Preheat Coil - 0 - - 24449 -
Terminal Reheat Coils - 0 - - 22644 -
>> Total Conditioning - 46529 18197 - 44068 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 220 of 263


Zone Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:21PM

C1-25 Corridor DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 88 m² 825 - 88 m² 446 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 88 m² 352 - 88 m² 528 -
Partitions 50 m² 635 - 50 m² 950 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 284 W 284 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 9 607 317 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1160 0 - 0 0
Safety Factor 10% / 10% 386 32 10% 192 0
>> Total Zone Loads - 4250 348 - 2116 0

C1-81 M Locker room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 130 m² 1219 - 130 m² 659 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 130 m² 523 - 130 m² 780 -
Partitions 110 m² 1398 - 110 m² 2090 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 749 W 749 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 19 1364 1142 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 525 114 10% 353 0
>> Total Zone Loads - 5779 1256 - 3882 0

Hourly Analysis Program v4.80 Page 221 of 263


Zone Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:21PM

C1-75 F WC DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 9 m² 84 - 9 m² 46 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 36 - 9 m² 54 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 66 W 66 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 46 14 10% 10 0
>> Total Zone Loads - 501 155 - 110 0

C1-87 WC DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 39 m² 157 - 39 m² 234 -
Partitions 54 m² 692 - 54 m² 1026 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 858 W 858 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 15 1011 528 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 272 53 10% 126 0
>> Total Zone Loads - 2990 581 - 1386 0

Hourly Analysis Program v4.80 Page 222 of 263


Zone Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:21PM

C1-83 WC DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 38 m² 152 - 38 m² 225 -
Partitions 77 m² 986 - 77 m² 1463 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 825 W 825 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 264 35 10% 169 0
>> Total Zone Loads - 2901 387 - 1857 0

C1-74 Prayer Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 20 m² 81 - 20 m² 120 -
Partitions 9 m² 111 - 9 m² 165 -
Ceiling 20 m² 81 - 20 m² 120 -
Overhead Lighting 211 W 211 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 120 60 10% 41 0
>> Total Zone Loads - 1323 661 - 446 0

Hourly Analysis Program v4.80 Page 223 of 263


Zone Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:21PM

C1-77 F Locker DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 106 - 26 m² 156 -
Partitions 9 m² 110 - 9 m² 163 -
Ceiling 26 m² 105 - 26 m² 156 -
Overhead Lighting 190 W 190 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 7 472 246 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 98 25 10% 48 0
>> Total Zone Loads - 1080 271 - 523 0

Hourly Analysis Program v4.80 Page 224 of 263


Space Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:22PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1G-25 Corridor 4 '' IN ZONE '' C1-25 Corridor ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 88 m² 825 - 88 m² 446 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 88 m² 352 - 88 m² 528 -
Partitions 50 m² 635 - 50 m² 950 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 284 W 284 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 9 607 317 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1160 0 - 0 0
Safety Factor 10% / 10% 386 32 10% 192 0
>> Total Zone Loads - 4250 348 - 2116 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1G-25 Corridor 4 '' IN ZONE '' C1-25 Corridor ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 88 0.232 - 825 - 446

Hourly Analysis Program v4.80 Page 225 of 263


Space Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:22PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' C1G-81 M Locker Room '' IN ZONE '' C1-81 M Locker room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 130 m² 1219 - 130 m² 659 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 130 m² 523 - 130 m² 780 -
Partitions 110 m² 1398 - 110 m² 2090 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 749 W 749 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 19 1364 1142 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 525 114 10% 353 0
>> Total Zone Loads - 5779 1256 - 3882 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' C1G-81 M Locker Room '' IN ZONE '' C1-81 M Locker room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 130 0.232 - 1219 - 659

Hourly Analysis Program v4.80 Page 226 of 263


Space Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:22PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' C1G-75 F WC '' IN ZONE '' C1-75 F WC ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 9 m² 84 - 9 m² 46 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 9 m² 36 - 9 m² 54 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 66 W 66 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 46 14 10% 10 0
>> Total Zone Loads - 501 155 - 110 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' C1G-75 F WC '' IN ZONE '' C1-75 F WC ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 9 0.232 - 84 - 46

Hourly Analysis Program v4.80 Page 227 of 263


Space Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:22PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' C1G-87 WC '' IN ZONE '' C1-87 WC ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 39 m² 157 - 39 m² 234 -
Partitions 54 m² 692 - 54 m² 1026 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 858 W 858 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 15 1011 528 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 272 53 10% 126 0
>> Total Zone Loads - 2990 581 - 1386 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' C1G-87 WC '' IN ZONE '' C1-87 WC ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 228 of 263


Space Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:22PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' C1G-83 WC '' IN ZONE '' C1-83 WC ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 38 m² 152 - 38 m² 225 -
Partitions 77 m² 986 - 77 m² 1463 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 825 W 825 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 264 35 10% 169 0
>> Total Zone Loads - 2901 387 - 1857 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' C1G-83 WC '' IN ZONE '' C1-83 WC ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 229 of 263


Space Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:22PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' C1G-74 Prayer Room '' IN ZONE '' C1-74 Prayer Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 20 m² 81 - 20 m² 120 -
Partitions 9 m² 111 - 9 m² 165 -
Ceiling 20 m² 81 - 20 m² 120 -
Overhead Lighting 211 W 211 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 120 60 10% 41 0
>> Total Zone Loads - 1323 661 - 446 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' C1G-74 Prayer Room '' IN ZONE '' C1-74 Prayer Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 230 of 263


Space Design Load Summary for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:22PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' C1G-77 F Locker '' IN ZONE '' C1-77 F Locker ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 106 - 26 m² 156 -
Partitions 9 m² 110 - 9 m² 163 -
Ceiling 26 m² 105 - 26 m² 156 -
Overhead Lighting 190 W 190 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 7 472 246 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 98 25 10% 48 0
>> Total Zone Loads - 1080 271 - 523 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' C1G-77 F Locker '' IN ZONE '' C1-77 F Locker ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 231 of 263


Hourly Air System Design Day Loads for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:23PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 1633 29.9 45.9 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 1633 28.9 44.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 1633 27.8 43.6 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 1633 27.0 42.7 0.0 0.0 0.0 0.0 0.1 0.0
0400 25.8 1633 26.4 42.0 0.0 0.0 0.0 0.0 0.3 0.0
0500 25.7 1633 26.2 41.8 0.0 0.0 0.0 0.0 0.4 0.0
0600 25.9 1633 26.6 42.2 0.0 0.0 0.0 0.0 0.4 0.0
0700 26.5 1633 27.6 43.4 0.0 0.0 0.0 0.0 0.4 0.0
0800 27.5 1633 29.5 45.5 0.0 0.0 0.0 0.0 0.2 0.0
0900 29.0 1633 32.1 48.5 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 1633 35.2 51.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 1633 38.6 55.8 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 1633 41.9 59.5 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 1633 44.3 62.2 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 1633 45.9 64.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 1633 46.5 64.7 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 1633 45.9 64.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 1633 44.5 62.4 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 1633 42.3 59.9 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 1633 39.6 56.9 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 1633 37.0 54.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 1633 34.7 51.4 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 1633 32.7 49.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 1633 31.1 47.3 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 232 of 263


Hourly Zone Loads for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:23PM

ZONE: C1-25 Corridor


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.5 48 344.8 3158.5 3678.9 0.0 0.0 0.0
0100 27.2 22.4 49 344.8 3075.9 3647.3 0.0 0.0 0.0
0200 26.6 22.3 49 344.8 2999.2 3616.0 0.0 0.0 0.0
0300 26.2 22.3 49 344.8 2934.1 3586.8 0.0 0.0 0.0
0400 25.8 22.2 49 344.8 2879.5 3559.5 0.0 0.0 0.0
0500 25.7 22.1 50 344.8 2842.7 3536.5 0.0 0.0 0.0
0600 25.9 22.1 50 344.8 2838.7 3522.0 0.0 0.0 0.0
0700 26.5 22.1 49 344.8 2890.0 3522.7 0.0 0.0 0.0
0800 27.5 22.1 49 344.8 3017.4 3545.5 0.0 0.0 0.0
0900 29.0 22.3 48 344.8 3211.7 3589.6 0.0 0.0 0.0
1000 30.7 22.4 47 344.8 3444.3 3648.7 0.0 0.0 0.0
1100 32.6 22.6 47 344.8 3701.0 3719.5 0.0 0.0 0.0
1200 34.4 22.8 46 344.8 3947.0 3793.1 0.0 0.0 0.0
1300 35.8 22.9 45 344.8 4107.9 3849.3 0.0 0.0 0.0
1400 36.7 23.0 45 344.8 4194.2 3888.2 0.0 0.0 0.0
1500 37.0 23.1 44 344.8 4243.2 3918.0 0.0 0.0 0.0
1600 36.7 23.2 44 344.8 4250.3 3936.7 0.0 0.0 0.0
1700 35.9 23.2 44 344.8 4213.9 3943.1 0.0 0.0 0.0
1800 34.6 23.2 45 344.8 4104.3 3928.4 0.0 0.0 0.0
1900 33.2 23.0 45 344.8 3902.4 3886.1 0.0 0.0 0.0
2000 31.7 22.9 46 344.8 3697.4 3837.4 0.0 0.0 0.0
2100 30.4 22.8 47 344.8 3524.8 3792.4 0.0 0.0 0.0
2200 29.3 22.7 47 344.8 3376.7 3750.3 0.0 0.0 0.0
2300 28.4 22.6 48 344.8 3255.8 3712.3 0.0 0.0 0.0

ZONE: C1-81 M Locker room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 21.2 48 575.0 3964.8 5309.5 0.0 0.0 0.0
0100 27.2 21.1 49 575.0 3824.2 5252.7 0.0 0.0 0.0
0200 26.6 21.0 49 575.0 3692.0 5196.3 0.0 0.0 0.0
0300 26.2 21.0 49 575.0 3579.7 5048.7 0.0 131.4 0.0
0400 25.8 21.0 49 575.0 3486.0 4910.5 0.0 260.6 0.0
0500 25.7 21.0 50 575.0 3424.8 4805.9 0.0 358.3 0.0
0600 25.9 21.0 50 575.0 3421.6 4756.3 0.0 404.7 0.0
0700 26.5 21.0 49 575.0 3509.9 4790.6 0.0 372.7 0.0
0800 27.5 21.0 49 575.0 3723.7 4938.3 0.0 234.6 0.0
0900 29.0 21.0 48 575.0 4050.1 5189.4 0.0 0.0 0.0
1000 30.7 21.2 47 575.0 4440.7 5291.2 0.0 0.0 0.0
1100 32.6 21.4 47 575.0 4874.5 5415.7 0.0 0.0 0.0
1200 34.4 21.6 46 575.0 5290.9 5544.9 0.0 0.0 0.0
1300 35.8 21.7 45 575.0 5555.3 5640.1 0.0 0.0 0.0
1400 36.7 21.8 45 575.0 5687.5 5702.2 0.0 0.0 0.0
1500 37.0 21.9 44 575.0 5764.3 5749.5 0.0 0.0 0.0
1600 36.7 21.9 44 575.0 5778.9 5779.5 0.0 0.0 0.0
1700 35.9 21.9 44 575.0 5728.9 5790.0 0.0 0.0 0.0
1800 34.6 21.9 45 575.0 5554.3 5763.1 0.0 0.0 0.0
1900 33.2 21.8 45 575.0 5218.2 5685.8 0.0 0.0 0.0
2000 31.7 21.6 46 575.0 4876.0 5597.5 0.0 0.0 0.0
2100 30.4 21.5 47 575.0 4586.7 5516.1 0.0 0.0 0.0
2200 29.3 21.4 47 575.0 4335.6 5439.4 0.0 0.0 0.0
2300 28.4 21.3 48 575.0 4129.9 5370.4 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 233 of 263


Hourly Zone Loads for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:23PM

ZONE: C1-75 F WC
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 22.8 48 40.7 420.5 449.1 0.0 0.0 0.0
0100 27.2 22.8 49 40.7 415.0 446.5 0.0 0.0 0.0
0200 26.6 22.7 49 40.7 410.0 444.0 0.0 0.0 0.0
0300 26.2 22.7 49 40.7 405.8 441.6 0.0 0.0 0.0
0400 25.8 22.6 49 40.7 402.2 439.4 0.0 0.0 0.0
0500 25.7 22.6 50 40.7 399.5 437.4 0.0 0.0 0.0
0600 25.9 22.5 50 40.7 398.7 436.0 0.0 0.0 0.0
0700 26.5 22.5 49 40.7 402.0 436.0 0.0 0.0 0.0
0800 27.5 22.6 49 40.7 411.1 437.8 0.0 0.0 0.0
0900 29.0 22.7 48 40.7 425.0 441.5 0.0 0.0 0.0
1000 30.7 22.8 47 40.7 441.6 446.5 0.0 0.0 0.0
1100 32.6 22.9 47 40.7 459.4 452.3 0.0 0.0 0.0
1200 34.4 23.0 46 40.7 476.4 458.4 0.0 0.0 0.0
1300 35.8 23.2 45 40.7 488.9 463.4 0.0 0.0 0.0
1400 36.7 23.2 45 40.7 497.0 467.3 0.0 0.0 0.0
1500 37.0 23.3 44 40.7 501.3 470.2 0.0 0.0 0.0
1600 36.7 23.3 44 40.7 501.4 471.8 0.0 0.0 0.0
1700 35.9 23.3 44 40.7 497.1 471.9 0.0 0.0 0.0
1800 34.6 23.3 45 40.7 487.8 470.2 0.0 0.0 0.0
1900 33.2 23.2 45 40.7 472.9 466.5 0.0 0.0 0.0
2000 31.7 23.1 46 40.7 458.0 462.3 0.0 0.0 0.0
2100 30.4 23.0 47 40.7 445.6 458.4 0.0 0.0 0.0
2200 29.3 23.0 47 40.7 435.5 454.9 0.0 0.0 0.0
2300 28.4 22.9 48 40.7 427.2 451.8 0.0 0.0 0.0

ZONE: C1-87 WC
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.2 48 242.6 2591.5 2777.9 0.0 0.0 0.0
0100 27.2 23.1 49 242.6 2555.0 2761.5 0.0 0.0 0.0
0200 26.6 23.1 49 242.6 2518.0 2744.3 0.0 0.0 0.0
0300 26.2 23.0 49 242.6 2486.6 2728.6 0.0 0.0 0.0
0400 25.8 23.0 49 242.6 2461.0 2714.4 0.0 0.0 0.0
0500 25.7 22.9 50 242.6 2447.6 2704.2 0.0 0.0 0.0
0600 25.9 22.9 50 242.6 2452.9 2700.4 0.0 0.0 0.0
0700 26.5 22.9 49 242.6 2477.4 2703.7 0.0 0.0 0.0
0800 27.5 23.0 49 242.6 2527.8 2716.8 0.0 0.0 0.0
0900 29.0 23.1 48 242.6 2604.8 2740.3 0.0 0.0 0.0
1000 30.7 23.2 47 242.6 2696.6 2771.0 0.0 0.0 0.0
1100 32.6 23.3 47 242.6 2803.6 2808.9 0.0 0.0 0.0
1200 34.4 23.5 46 242.6 2907.4 2848.2 0.0 0.0 0.0
1300 35.8 23.6 45 242.6 2957.0 2871.2 0.0 0.0 0.0
1400 36.7 23.6 45 242.6 2966.1 2881.0 0.0 0.0 0.0
1500 37.0 23.6 44 242.6 2974.6 2890.1 0.0 0.0 0.0
1600 36.7 23.7 44 242.6 2982.6 2898.7 0.0 0.0 0.0
1700 35.9 23.7 44 242.6 2990.0 2906.9 0.0 0.0 0.0
1800 34.6 23.7 45 242.6 2967.9 2905.0 0.0 0.0 0.0
1900 33.2 23.6 45 242.6 2893.7 2884.5 0.0 0.0 0.0
2000 31.7 23.5 46 242.6 2816.8 2860.8 0.0 0.0 0.0
2100 30.4 23.4 47 242.6 2749.4 2838.3 0.0 0.0 0.0
2200 29.3 23.3 47 242.6 2686.1 2815.8 0.0 0.0 0.0
2300 28.4 23.3 48 242.6 2633.4 2795.5 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 234 of 263


Hourly Zone Loads for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:23PM

ZONE: C1-83 WC
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.0 48 235.4 2371.3 2646.3 0.0 0.0 0.0
0100 27.2 22.9 49 235.4 2322.9 2626.0 0.0 0.0 0.0
0200 26.6 22.9 49 235.4 2273.8 2604.7 0.0 0.0 0.0
0300 26.2 22.8 49 235.4 2232.1 2585.3 0.0 0.0 0.0
0400 25.8 22.7 49 235.4 2198.1 2568.0 0.0 0.0 0.0
0500 25.7 22.7 50 235.4 2180.3 2555.6 0.0 0.0 0.0
0600 25.9 22.6 50 235.4 2187.3 2551.4 0.0 0.0 0.0
0700 26.5 22.7 49 235.4 2219.8 2556.0 0.0 0.0 0.0
0800 27.5 22.7 49 235.4 2286.8 2572.8 0.0 0.0 0.0
0900 29.0 22.8 48 235.4 2388.9 2602.7 0.0 0.0 0.0
1000 30.7 23.0 47 235.4 2510.8 2641.4 0.0 0.0 0.0
1100 32.6 23.2 47 235.4 2652.8 2689.1 0.0 0.0 0.0
1200 34.4 23.4 46 235.4 2790.7 2738.2 0.0 0.0 0.0
1300 35.8 23.5 45 235.4 2857.5 2767.1 0.0 0.0 0.0
1400 36.7 23.5 45 235.4 2869.6 2778.9 0.0 0.0 0.0
1500 37.0 23.6 44 235.4 2880.9 2789.8 0.0 0.0 0.0
1600 36.7 23.6 44 235.4 2891.4 2800.1 0.0 0.0 0.0
1700 35.9 23.6 44 235.4 2901.3 2810.0 0.0 0.0 0.0
1800 34.6 23.6 45 235.4 2871.1 2806.9 0.0 0.0 0.0
1900 33.2 23.5 45 235.4 2772.7 2780.6 0.0 0.0 0.0
2000 31.7 23.4 46 235.4 2670.5 2750.5 0.0 0.0 0.0
2100 30.4 23.3 47 235.4 2581.0 2722.1 0.0 0.0 0.0
2200 29.3 23.2 47 235.4 2497.0 2693.7 0.0 0.0 0.0
2300 28.4 23.1 48 235.4 2426.9 2668.3 0.0 0.0 0.0

ZONE: C1-74 Prayer Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.4 48 107.3 1196.2 1250.9 0.0 0.0 0.0
0100 27.2 23.3 49 107.3 1184.6 1245.7 0.0 0.0 0.0
0200 26.6 23.3 49 107.3 1172.7 1240.3 0.0 0.0 0.0
0300 26.2 23.3 49 107.3 1162.7 1235.3 0.0 0.0 0.0
0400 25.8 23.2 49 107.3 1154.6 1230.7 0.0 0.0 0.0
0500 25.7 23.2 50 107.3 1150.3 1227.3 0.0 0.0 0.0
0600 25.9 23.2 50 107.3 1152.0 1225.9 0.0 0.0 0.0
0700 26.5 23.2 49 107.3 1159.8 1226.7 0.0 0.0 0.0
0800 27.5 23.2 49 107.3 1175.9 1230.5 0.0 0.0 0.0
0900 29.0 23.3 48 107.3 1200.4 1237.6 0.0 0.0 0.0
1000 30.7 23.4 47 107.3 1229.7 1247.0 0.0 0.0 0.0
1100 32.6 23.5 47 107.3 1263.9 1258.6 0.0 0.0 0.0
1200 34.4 23.6 46 107.3 1297.0 1270.8 0.0 0.0 0.0
1300 35.8 23.6 45 107.3 1312.5 1278.0 0.0 0.0 0.0
1400 36.7 23.6 45 107.3 1315.4 1281.2 0.0 0.0 0.0
1500 37.0 23.7 44 107.3 1318.1 1284.2 0.0 0.0 0.0
1600 36.7 23.7 44 107.3 1320.6 1287.1 0.0 0.0 0.0
1700 35.9 23.7 44 107.3 1323.0 1289.9 0.0 0.0 0.0
1800 34.6 23.7 45 107.3 1316.3 1289.7 0.0 0.0 0.0
1900 33.2 23.7 45 107.3 1292.6 1283.6 0.0 0.0 0.0
2000 31.7 23.6 46 107.3 1268.1 1276.4 0.0 0.0 0.0
2100 30.4 23.5 47 107.3 1246.6 1269.6 0.0 0.0 0.0
2200 29.3 23.5 47 107.3 1226.4 1262.7 0.0 0.0 0.0
2300 28.4 23.4 48 107.3 1209.5 1256.4 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 235 of 263


Hourly Zone Loads for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:23PM

ZONE: C1-77 F Locker


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.2 48 87.6 931.8 1006.9 0.0 0.0 0.0
0100 27.2 23.2 49 87.6 918.2 1002.4 0.0 0.0 0.0
0200 26.6 23.1 49 87.6 904.3 997.6 0.0 0.0 0.0
0300 26.2 23.1 49 87.6 892.6 993.1 0.0 0.0 0.0
0400 25.8 23.1 49 87.6 883.0 989.0 0.0 0.0 0.0
0500 25.7 23.0 50 87.6 878.0 985.9 0.0 0.0 0.0
0600 25.9 23.0 50 87.6 879.9 984.4 0.0 0.0 0.0
0700 26.5 23.0 49 87.6 889.1 984.7 0.0 0.0 0.0
0800 27.5 23.0 49 87.6 908.0 987.7 0.0 0.0 0.0
0900 29.0 23.1 48 87.6 936.8 993.5 0.0 0.0 0.0
1000 30.7 23.2 47 87.6 971.2 1001.3 0.0 0.0 0.0
1100 32.6 23.3 47 87.6 1011.2 1011.2 0.0 0.0 0.0
1200 34.4 23.4 46 87.6 1050.1 1021.6 0.0 0.0 0.0
1300 35.8 23.5 45 87.6 1068.1 1027.9 0.0 0.0 0.0
1400 36.7 23.5 45 87.6 1071.5 1030.9 0.0 0.0 0.0
1500 37.0 23.5 44 87.6 1074.7 1033.7 0.0 0.0 0.0
1600 36.7 23.5 44 87.6 1077.6 1036.4 0.0 0.0 0.0
1700 35.9 23.6 44 87.6 1080.4 1039.1 0.0 0.0 0.0
1800 34.6 23.6 45 87.6 1072.7 1039.2 0.0 0.0 0.0
1900 33.2 23.5 45 87.6 1044.9 1034.4 0.0 0.0 0.0
2000 31.7 23.5 46 87.6 1016.1 1028.5 0.0 0.0 0.0
2100 30.4 23.4 47 87.6 990.9 1022.8 0.0 0.0 0.0
2200 29.3 23.3 47 87.6 967.2 1017.0 0.0 0.0 0.0
2300 28.4 23.3 48 87.6 947.5 1011.6 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 236 of 263


System Psychrometrics for AHU-H-C3-09 C1 Fresh AHU
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:24PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 1633 400 25369 14538
Vent - Return Mixing Outlet 37.0 0.01203 1633 400 - -
Preheat Coil Outlet 37.0 0.01203 1633 400 0 -
Central Cooling Coil Outlet 11.1 0.00789 1633 400 46529 18197
Supply Fan Outlet 12.8 0.00789 1633 400 3025 -
Cold Supply Duct Outlet 12.8 0.00789 1633 400 - -
Zone Air - 23.4 0.00872 1633 622 18135 3660
Zone Direct Exhaust Outlet 23.4 0.00872 575 622 - -
Return Plenum Outlet 23.4 0.00872 1058 622 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
C1-25 Corridor 4243 Deadband 3918 23.1 345 515 0 0
C1-81 M Locker room 5764 Deadband 5750 21.9 575 587 0 0
C1-75 F WC 501 Deadband 470 23.3 41 833 0 0
C1-87 WC 2975 Deadband 2890 23.6 243 672 0 0
C1-83 WC 2881 Deadband 2790 23.6 235 587 0 0
C1-74 Prayer Room 1318 Deadband 1284 23.7 107 928 0 0
C1-77 F Locker 1075 Deadband 1034 23.5 88 752 0 0

Hourly Analysis Program v4.80 Page 237 of 263


Air System Sizing Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:25PM

Air System Information


Air System Name AHU-H-RF-01 RF Kitchen Number of zones 5
Equipment Class CW AHU Floor Area 122.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 133.8 kW Load occurs at Jul 1500
Sensible coil load 99.4 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 3658 L/s Entering DB / WB 37.0 / 22.0 °C
Max block L/s at Jul 1500 3658 L/s Leaving DB / WB 12.3 / 11.1 °C
Sum of peak zone L/s 3658 L/s Coil ADP 9.6 °C
Sensible heat ratio 0.742 Bypass Factor 0.100
m²/kW 0.9 Resulting RH 46 %
W/m² 1097.1 Design supply temp. 14.0 °C
Water flow @ 6.7 °K rise 4.78 L/s Zone T-stat Check 5 of 5 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 54.7 kW Load occurs at Des Htg
Coil L/s at Des Htg 3658 L/s Ent. DB / Lvg DB -0.8 / 12.8 °C
Max coil L/s 3658 L/s
Water flow @ 11.0 °K drop 1.19 L/s

Supply Fan Sizing Data


Actual max L/s at Jul 1500 3658 L/s Fan motor BHP 8.54 BHP
Standard L/s 3335 L/s Fan motor kW 6.77 kW
Actual max L/(s-m²) 29.98 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 3658 L/s L/s/person 152.41 L/s/person
L/(s-m²) 29.98 L/(s-m²)

Hourly Analysis Program v4.80 Page 238 of 263


Zone Sizing Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:25PM

Air System Information


Air System Name AHU-H-RF-01 RF Kitchen Number of zones 5
Equipment Class CW AHU Floor Area 122.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
F18-07 Dishwash & Pot. 3.8 344 344 Sep 1000 1.2 22.0 15.63
F18-09 Hot and Dessert 14.5 1400 1400 Jul 1500 0.4 39.0 35.90
Prep Station 1.3 114 114 Jul 1500 0.2 14.0 8.13
F18-11 Sushi and robata 4.3 1600 1600 Jul 1500 0.4 38.0 42.11
F18-08 Chiller 0.2 200 200 Jun 1500 0.1 9.0 22.22

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
F18-07 Dishwash & Pot. 3.8 0.08 0.0 0.00 0
F18-09 Hot and Dessert 11.2 0.24 0.0 0.00 0
Prep Station 1.0 0.02 0.0 0.00 0
F18-11 Sushi and robata 12.8 0.28 0.0 0.00 0
F18-08 Chiller 1.6 0.03 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
F18-07 Dishwash & Pot.
F18K-07 Dishwash 1 3.8 Sep 1000 344 1.2 22.0 15.63
F18-09 Hot and Dessert
F18K-09 Hot and Dessert 1 14.5 Jul 1500 1400 0.4 39.0 35.90
Prep Station
F18K-170 Prep Station 1 1.3 Jul 1500 114 0.2 14.0 8.13
F18-11 Sushi and robata
F18K-11 Sushi + Robata 1 4.3 Jul 1500 1600 0.4 38.0 42.11
F18-08 Chiller
F18K-08 Chiller 1 0.2 Jun 1500 200 0.1 9.0 22.22

Hourly Analysis Program v4.80 Page 239 of 263


Ventilation Sizing Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:25PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 3658 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
F18-07 Dishwash & Pot.
F18K-07 Dishwash 1 22.0 5.0 343.9 0.00 0.00 0.0 100.0 343.9
F18-09 Hot and Dessert
F18K-09 Hot and Dessert 1 39.0 8.0 1400.0 0.00 0.00 0.0 100.0 1400.0
Prep Station
F18K-170 Prep Station 1 14.0 3.0 113.9 0.00 0.00 0.0 100.0 113.9
F18-11 Sushi and robata
F18K-11 Sushi + Robata 1 38.0 8.0 1600.0 0.00 0.00 0.0 100.0 1600.0
F18-08 Chiller
F18K-08 Chiller 1 9.0 0.0 200.0 0.00 0.00 0.0 100.0 200.0
Totals (incl. Space Multipliers) 3657.8 3657.8

Hourly Analysis Program v4.80 Page 240 of 263


Air System Design Load Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:25PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 17 m² 737 - 17 m² - -
Wall Transmission 87 m² 709 - 87 m² 690 -
Roof Transmission 123 m² 1145 - 123 m² 621 -
Window Transmission 17 m² 371 - 17 m² 737 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1241 W 1241 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 24 2076 3199 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 15224 0 - 0 0
Safety Factor 10% / 10% 2150 320 10% 205 0
>> Total Zone Loads - 23654 3519 - 2253 0
Zone Conditioning - 23871 3519 - 2011 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 458 L/s 0 - 458 L/s 0 -
Ventilation Load 3658 L/s 60683 30956 3658 L/s 84235 0
Supply Fan Load 3658 L/s 6774 - 3658 L/s -6774 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 91328 34475 - 79472 0
Central Cooling Coil - 99366 34475 - -1943 0
Preheat Coil - 0 - - 54750 -
Terminal Reheat Coils - -8037 - - 26665 -
>> Total Conditioning - 91328 34475 - 79472 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 241 of 263


Zone Design Load Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:25PM

F18-07 Dishwash & Pot. DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.6 °C / 19.6 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 17 m² 1399 - 17 m² - -
Wall Transmission 26 m² 240 - 26 m² 210 -
Roof Transmission 22 m² 74 - 22 m² 111 -
Window Transmission 17 m² 172 - 17 m² 737 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 224 W 224 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 900 0 - 0 0
Safety Factor 10% / 10% 344 67 10% 106 0
>> Total Zone Loads - 3785 733 - 1165 0

F18-09 Hot and Dessert DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 25 m² 205 - 25 m² 201 -
Roof Transmission 39 m² 367 - 39 m² 198 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 397 W 397 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 8 692 1066 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 11549 0 - 0 0
Safety Factor 10% / 10% 1321 107 10% 40 0
>> Total Zone Loads - 14530 1173 - 439 0

Hourly Analysis Program v4.80 Page 242 of 263


Zone Design Load Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:25PM

Prep Station DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 10 m² 81 - 10 m² 80 -
Roof Transmission 14 m² 132 - 14 m² 71 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 142 W 142 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 525 0 - 0 0
Safety Factor 10% / 10% 114 40 10% 15 0
>> Total Zone Loads - 1253 440 - 166 0

F18-11 Sushi and robata DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 25 m² 202 - 25 m² 199 -
Roof Transmission 38 m² 357 - 38 m² 193 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 386 W 386 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 8 692 1066 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2250 0 - 0 0
Safety Factor 10% / 10% 389 107 10% 39 0
>> Total Zone Loads - 4277 1173 - 431 0

Hourly Analysis Program v4.80 Page 243 of 263


Zone Design Load Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:25PM

F18-08 Chiller DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 83 - 10 m² 48 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 92 W 92 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 17 0 10% 5 0
>> Total Zone Loads - 192 0 - 53 0

Hourly Analysis Program v4.80 Page 244 of 263


Space Design Load Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:26PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' F18K-07 Dishwash '' IN ZONE '' F18-07 Dishwash & Pot. ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.6 °C / 19.6 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 17 m² 1399 - 17 m² - -
Wall Transmission 26 m² 240 - 26 m² 210 -
Roof Transmission 22 m² 74 - 22 m² 111 -
Window Transmission 17 m² 172 - 17 m² 737 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 224 W 224 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 432 667 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 900 0 - 0 0
Safety Factor 10% / 10% 344 67 10% 106 0
>> Total Zone Loads - 3785 733 - 1165 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' F18K-07 Dishwash '' IN ZONE '' F18-07 Dishwash & Pot. ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 14 0.365 - 84 - 115
SE EXPOSURE
WALL 12 0.365 - 156 - 95
WINDOW 1 17 1.990 0.300 172 1399 737
H EXPOSURE
ROOF 22 0.232 - 74 - 111

Hourly Analysis Program v4.80 Page 245 of 263


Space Design Load Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:26PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' F18K-09 Hot and Dessert '' IN ZONE '' F18-09 Hot and Dessert ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 25 m² 205 - 25 m² 201 -
Roof Transmission 39 m² 367 - 39 m² 198 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 397 W 397 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 8 692 1066 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 11549 0 - 0 0
Safety Factor 10% / 10% 1321 107 10% 40 0
>> Total Zone Loads - 14530 1173 - 439 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' F18K-09 Hot and Dessert '' IN ZONE '' F18-09 Hot and Dessert ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 25 0.365 - 205 - 201
H EXPOSURE
ROOF 39 0.232 - 367 - 198

Hourly Analysis Program v4.80 Page 246 of 263


Space Design Load Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:26PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' F18K-170 Prep Station '' IN ZONE '' Prep Station ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 10 m² 81 - 10 m² 80 -
Roof Transmission 14 m² 132 - 14 m² 71 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 142 W 142 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 525 0 - 0 0
Safety Factor 10% / 10% 114 40 10% 15 0
>> Total Zone Loads - 1253 440 - 166 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' F18K-170 Prep Station '' IN ZONE '' Prep Station ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 10 0.365 - 81 - 80
H EXPOSURE
ROOF 14 0.232 - 132 - 71

Hourly Analysis Program v4.80 Page 247 of 263


Space Design Load Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:26PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' F18K-11 Sushi + Robata '' IN ZONE '' F18-11 Sushi and robata ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 25 m² 202 - 25 m² 199 -
Roof Transmission 38 m² 357 - 38 m² 193 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 386 W 386 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 8 692 1066 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2250 0 - 0 0
Safety Factor 10% / 10% 389 107 10% 39 0
>> Total Zone Loads - 4277 1173 - 431 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' F18K-11 Sushi + Robata '' IN ZONE '' F18-11 Sushi and robata ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 25 0.365 - 202 - 199
H EXPOSURE
ROOF 38 0.232 - 357 - 193

Hourly Analysis Program v4.80 Page 248 of 263


Space Design Load Summary for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:26PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' F18K-08 Chiller '' IN ZONE '' F18-08 Chiller ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 27.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 10 m² 83 - 10 m² 48 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 92 W 92 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 17 0 10% 5 0
>> Total Zone Loads - 192 0 - 53 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' F18K-08 Chiller '' IN ZONE '' F18-08 Chiller ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 10 0.232 - 83 - 48

Hourly Analysis Program v4.80 Page 249 of 263


Hourly Air System Design Day Loads for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:27PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 3658 62.1 91.4 0.0 0.0 0.0 0.0 8.4 0.0
0100 27.2 3658 59.8 88.7 0.0 0.0 0.0 0.0 8.5 0.0
0200 26.6 3658 57.5 86.1 0.0 0.0 0.0 0.0 8.5 0.0
0300 26.2 3658 55.7 84.0 0.0 0.0 0.0 0.0 8.5 0.0
0400 25.8 3658 54.3 82.5 0.0 0.0 0.0 0.0 8.5 0.0
0500 25.7 3658 53.9 81.9 0.0 0.0 0.0 0.0 8.5 0.0
0600 25.9 3658 54.8 83.0 0.0 0.0 0.0 0.0 8.5 0.0
0700 26.5 3658 57.1 85.6 0.0 0.0 0.0 0.0 8.4 0.0
0800 27.5 3658 61.2 90.3 0.0 0.0 0.0 0.0 8.3 0.0
0900 29.0 3658 67.1 97.1 0.0 0.0 0.0 0.0 8.3 0.0
1000 30.7 3658 73.9 104.8 0.0 0.0 0.0 0.0 8.2 0.0
1100 32.6 3658 81.6 113.6 0.0 0.0 0.0 0.0 8.2 0.0
1200 34.4 3658 88.9 121.9 0.0 0.0 0.0 0.0 8.1 0.0
1300 35.8 3658 94.4 128.1 0.0 0.0 0.0 0.0 8.1 0.0
1400 36.7 3658 98.0 132.3 0.0 0.0 0.0 0.0 8.1 0.0
1500 37.0 3658 99.4 133.8 0.0 0.0 0.0 0.0 8.0 0.0
1600 36.7 3658 98.0 132.3 0.0 0.0 0.0 0.0 8.0 0.0
1700 35.9 3658 94.8 128.7 0.0 0.0 0.0 0.0 8.1 0.0
1800 34.6 3658 89.8 123.0 0.0 0.0 0.0 0.0 8.1 0.0
1900 33.2 3658 83.9 116.2 0.0 0.0 0.0 0.0 8.2 0.0
2000 31.7 3658 78.0 109.5 0.0 0.0 0.0 0.0 8.3 0.0
2100 30.4 3658 73.0 103.8 0.0 0.0 0.0 0.0 8.3 0.0
2200 29.3 3658 68.4 98.7 0.0 0.0 0.0 0.0 8.4 0.0
2300 28.4 3658 64.8 94.5 0.0 0.0 0.0 0.0 8.4 0.0

Hourly Analysis Program v4.80 Page 250 of 263


Hourly Zone Loads for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:27PM

ZONE: F18-07 Dishwash & Pot.


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 21.7 52 343.9 2498.4 2899.1 0.0 0.0 0.0
0100 27.2 21.5 52 343.9 2432.7 2853.2 0.0 0.0 0.0
0200 26.6 21.4 53 343.9 2371.6 2809.4 0.0 0.0 0.0
0300 26.2 21.3 53 343.9 2317.0 2768.8 0.0 0.0 0.0
0400 25.8 21.2 54 343.9 2268.6 2731.2 0.0 0.0 0.0
0500 25.7 21.3 54 343.9 2366.2 2771.3 0.0 0.0 0.0
0600 25.9 21.7 53 343.9 2658.4 2919.1 0.0 0.0 0.0
0700 26.5 22.1 51 343.9 2950.4 3075.4 0.0 0.0 0.0
0800 27.5 22.5 50 343.9 3202.1 3216.6 0.0 0.0 0.0
0900 29.0 22.8 49 343.9 3373.1 3319.6 0.0 0.0 0.0
1000 30.7 22.9 48 343.9 3440.2 3369.6 0.0 0.0 0.0
1100 32.6 22.9 47 343.9 3419.3 3372.2 0.0 0.0 0.0
1200 34.4 22.9 47 343.9 3400.0 3373.4 0.0 0.0 0.0
1300 35.8 23.0 46 343.9 3417.7 3392.8 0.0 0.0 0.0
1400 36.7 23.0 46 343.9 3421.7 3404.6 0.0 0.0 0.0
1500 37.0 23.0 46 343.9 3402.6 3403.2 0.0 0.0 0.0
1600 36.7 22.9 46 343.9 3346.8 3381.1 0.0 0.0 0.0
1700 35.9 22.8 47 343.9 3250.6 3335.2 0.0 0.0 0.0
1800 34.6 22.6 47 343.9 3113.2 3264.6 0.0 0.0 0.0
1900 33.2 22.4 48 343.9 2987.9 3196.8 0.0 0.0 0.0
2000 31.7 22.3 49 343.9 2864.4 3127.4 0.0 0.0 0.0
2100 30.4 22.1 50 343.9 2755.5 3063.3 0.0 0.0 0.0
2200 29.3 21.9 51 343.9 2657.8 3003.4 0.0 0.0 0.0
2300 28.4 21.8 51 343.9 2572.4 2948.7 0.0 0.0 0.0

ZONE: F18-09 Hot and Dessert


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.2 52 1400.0 14132.6 14223.9 0.0 0.0 0.0
0100 27.2 23.2 52 1400.0 14104.6 14198.5 0.0 0.0 0.0
0200 26.6 23.2 53 1400.0 14080.9 14176.3 0.0 0.0 0.0
0300 26.2 23.2 53 1400.0 14060.2 14156.5 0.0 0.0 0.0
0400 25.8 23.2 54 1400.0 14042.1 14138.5 0.0 0.0 0.0
0500 25.7 23.2 54 1400.0 14030.9 14126.0 0.0 0.0 0.0
0600 25.9 23.2 53 1400.0 14063.5 14147.2 0.0 0.0 0.0
0700 26.5 23.2 51 1400.0 14149.6 14210.8 0.0 0.0 0.0
0800 27.5 23.3 50 1400.0 14247.0 14285.3 0.0 0.0 0.0
0900 29.0 23.3 49 1400.0 14326.3 14348.0 0.0 0.0 0.0
1000 30.7 23.3 48 1400.0 14382.2 14394.0 0.0 0.0 0.0
1100 32.6 23.4 47 1400.0 14417.8 14425.2 0.0 0.0 0.0
1200 34.4 23.4 47 1400.0 14448.3 14452.5 0.0 0.0 0.0
1300 35.8 23.4 46 1400.0 14482.2 14482.6 0.0 0.0 0.0
1400 36.7 23.4 46 1400.0 14512.6 14510.4 0.0 0.0 0.0
1500 37.0 23.4 46 1400.0 14529.8 14528.2 0.0 0.0 0.0
1600 36.7 23.4 46 1400.0 14527.1 14530.4 0.0 0.0 0.0
1700 35.9 23.4 47 1400.0 14500.7 14513.9 0.0 0.0 0.0
1800 34.6 23.4 47 1400.0 14449.8 14477.6 0.0 0.0 0.0
1900 33.2 23.4 48 1400.0 14380.2 14425.5 0.0 0.0 0.0
2000 31.7 23.3 49 1400.0 14310.9 14371.9 0.0 0.0 0.0
2100 30.4 23.3 50 1400.0 14252.9 14325.7 0.0 0.0 0.0
2200 29.3 23.3 51 1400.0 14205.5 14286.7 0.0 0.0 0.0
2300 28.4 23.3 51 1400.0 14166.0 14253.1 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 251 of 263


Hourly Zone Loads for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:27PM

ZONE: Prep Station


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 23.2 52 113.9 1106.5 1159.0 0.0 0.0 0.0
0100 27.2 23.2 52 113.9 1096.1 1152.6 0.0 0.0 0.0
0200 26.6 23.1 53 113.9 1087.2 1146.7 0.0 0.0 0.0
0300 26.2 23.1 53 113.9 1079.5 1141.2 0.0 0.0 0.0
0400 25.8 23.1 54 113.9 1072.7 1136.1 0.0 0.0 0.0
0500 25.7 23.0 54 113.9 1068.6 1132.1 0.0 0.0 0.0
0600 25.9 23.1 53 113.9 1081.7 1135.4 0.0 0.0 0.0
0700 26.5 23.2 51 113.9 1115.4 1148.1 0.0 0.0 0.0
0800 27.5 23.3 50 113.9 1152.8 1163.7 0.0 0.0 0.0
0900 29.0 23.4 49 113.9 1182.5 1177.1 0.0 0.0 0.0
1000 30.7 23.5 48 113.9 1202.6 1187.0 0.0 0.0 0.0
1100 32.6 23.5 47 113.9 1214.6 1194.0 0.0 0.0 0.0
1200 34.4 23.6 47 113.9 1224.6 1200.2 0.0 0.0 0.0
1300 35.8 23.6 46 113.9 1236.3 1207.3 0.0 0.0 0.0
1400 36.7 23.7 46 113.9 1247.2 1214.1 0.0 0.0 0.0
1500 37.0 23.7 46 113.9 1253.3 1219.2 0.0 0.0 0.0
1600 36.7 23.7 46 113.9 1252.3 1221.1 0.0 0.0 0.0
1700 35.9 23.7 47 113.9 1242.6 1219.1 0.0 0.0 0.0
1800 34.6 23.7 47 113.9 1223.8 1212.8 0.0 0.0 0.0
1900 33.2 23.6 48 113.9 1198.2 1202.8 0.0 0.0 0.0
2000 31.7 23.5 49 113.9 1172.6 1192.1 0.0 0.0 0.0
2100 30.4 23.4 50 113.9 1151.2 1182.4 0.0 0.0 0.0
2200 29.3 23.4 51 113.9 1133.6 1173.8 0.0 0.0 0.0
2300 28.4 23.3 51 113.9 1118.9 1166.0 0.0 0.0 0.0

ZONE: F18-11 Sushi and robata


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.4 52 1600.0 3888.1 4139.0 0.0 7194.5 0.0
0100 27.2 20.4 52 1600.0 3860.7 4111.7 0.0 7218.4 0.0
0200 26.6 20.4 53 1600.0 3837.4 4088.6 0.0 7238.8 0.0
0300 26.2 20.4 53 1600.0 3817.2 4068.3 0.0 7256.6 0.0
0400 25.8 20.4 54 1600.0 3799.4 4050.5 0.0 7272.3 0.0
0500 25.7 20.4 54 1600.0 3788.5 4039.3 0.0 7282.1 0.0
0600 25.9 20.4 53 1600.0 3820.7 4070.1 0.0 7255.1 0.0
0700 26.5 20.4 51 1600.0 3905.7 4152.1 0.0 7183.0 0.0
0800 27.5 20.4 50 1600.0 4001.5 4245.0 0.0 7101.3 0.0
0900 29.0 20.4 49 1600.0 4079.3 4320.8 0.0 7034.8 0.0
1000 30.7 20.5 48 1600.0 4133.7 4374.1 0.0 6987.9 0.0
1100 32.6 20.5 47 1600.0 4168.1 4408.1 0.0 6958.0 0.0
1200 34.4 20.5 47 1600.0 4197.5 4437.2 0.0 6932.4 0.0
1300 35.8 20.5 46 1600.0 4230.3 4469.7 0.0 6903.9 0.0
1400 36.7 20.5 46 1600.0 4260.0 4499.2 0.0 6878.0 0.0
1500 37.0 20.5 46 1600.0 4276.7 4516.1 0.0 6863.1 0.0
1600 36.7 20.5 46 1600.0 4274.0 4514.1 0.0 6864.8 0.0
1700 35.9 20.5 47 1600.0 4248.2 4489.6 0.0 6886.4 0.0
1800 34.6 20.5 47 1600.0 4198.5 4441.8 0.0 6928.4 0.0
1900 33.2 20.5 48 1600.0 4130.4 4375.9 0.0 6986.3 0.0
2000 31.7 20.4 49 1600.0 4062.6 4310.0 0.0 7044.2 0.0
2100 30.4 20.4 50 1600.0 4005.9 4254.8 0.0 7092.8 0.0
2200 29.3 20.4 51 1600.0 3959.4 4209.3 0.0 7132.7 0.0
2300 28.4 20.4 51 1600.0 3920.8 4171.2 0.0 7166.2 0.0

Hourly Analysis Program v4.80 Page 252 of 263


Hourly Zone Loads for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:27PM

ZONE: F18-08 Chiller


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 20.2 52 200.0 123.2 139.6 0.0 1231.2 0.0
0100 27.2 20.2 52 200.0 119.0 135.3 0.0 1234.9 0.0
0200 26.6 20.2 53 200.0 115.4 131.8 0.0 1238.1 0.0
0300 26.2 20.2 53 200.0 112.4 128.7 0.0 1240.7 0.0
0400 25.8 20.2 54 200.0 109.8 126.1 0.0 1243.1 0.0
0500 25.7 20.2 54 200.0 107.5 123.7 0.0 1245.1 0.0
0600 25.9 20.2 53 200.0 106.4 122.5 0.0 1246.2 0.0
0700 26.5 20.2 51 200.0 108.8 124.7 0.0 1244.3 0.0
0800 27.5 20.2 50 200.0 116.1 131.5 0.0 1238.3 0.0
0900 29.0 20.2 49 200.0 127.3 142.1 0.0 1229.0 0.0
1000 30.7 20.2 48 200.0 140.6 154.8 0.0 1217.8 0.0
1100 32.6 20.2 47 200.0 154.7 168.3 0.0 1206.0 0.0
1200 34.4 20.3 47 200.0 168.0 181.1 0.0 1194.7 0.0
1300 35.8 20.3 46 200.0 179.3 192.1 0.0 1185.1 0.0
1400 36.7 20.3 46 200.0 187.4 200.1 0.0 1178.0 0.0
1500 37.0 20.3 46 200.0 191.6 204.4 0.0 1174.2 0.0
1600 36.7 20.3 46 200.0 191.4 204.4 0.0 1174.2 0.0
1700 35.9 20.3 47 200.0 186.5 200.0 0.0 1178.1 0.0
1800 34.6 20.3 47 200.0 177.3 191.4 0.0 1185.7 0.0
1900 33.2 20.2 48 200.0 164.9 179.8 0.0 1195.9 0.0
2000 31.7 20.2 49 200.0 152.6 168.1 0.0 1206.2 0.0
2100 30.4 20.2 50 200.0 142.6 158.4 0.0 1214.6 0.0
2200 29.3 20.2 51 200.0 134.7 150.8 0.0 1221.3 0.0
2300 28.4 20.2 51 200.0 128.4 144.6 0.0 1226.8 0.0

Hourly Analysis Program v4.80 Page 253 of 263


System Psychrometrics for AHU-H-RF-01 RF Kitchen
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:28PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 3658 400 60683 30956
Vent - Return Mixing Outlet 37.0 0.01203 3658 400 - -
Preheat Coil Outlet 37.0 0.01203 3658 400 0 -
Central Cooling Coil Outlet 12.3 0.00852 3658 400 99366 34475
Supply Fan Outlet 14.0 0.00852 3658 400 6774 -
Cold Supply Duct Outlet 14.0 0.00852 3658 400 - -
Zone Air - 23.2 0.00888 3658 462 23871 3519
Zone Direct Exhaust Outlet 23.2 0.00888 3200 462 - -
Return Plenum Outlet 23.2 0.00888 458 462 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
F18-07 Dishwash & Pot. 3403 Deadband 3403 23.0 344 537 0 0
F18-09 Hot and Dessert 14530 Deadband 14528 23.4 1400 454 0 0
Prep Station 1253 Deadband 1219 23.7 114 649 0 0
F18-11 Sushi and robata 4277 Heating 4516 20.5 1600 447 6863 0
F18-08 Chiller 192 Heating 204 20.3 200 400 1174 0

Hourly Analysis Program v4.80 Page 254 of 263


Air System Sizing Summary for AHU-H-RF-02 F18 Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:29PM

Air System Information


Air System Name AHU-H-RF-02 F18 Restaurant Number of zones 1
Equipment Class CW AHU Floor Area 417.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 109.4 kW Load occurs at Aug 1500
Sensible coil load 84.3 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Aug 1500 3684 L/s Entering DB / WB 31.9 / 19.5 °C
Max block L/s at Sep 1500 4109 L/s Leaving DB / WB 11.1 / 10.1 °C
Sum of peak zone L/s 4109 L/s Coil ADP 8.8 °C
Sensible heat ratio 0.771 Bypass Factor 0.100
m²/kW 3.8 Resulting RH 39 %
W/m² 262.4 Design supply temp. 12.8 °C
Water flow @ 6.7 °K rise 3.91 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Preheat Coil Sizing Data


Max coil load 12.8 kW Load occurs at Des Htg
Coil L/s at Des Htg 2363 L/s Ent. DB / Lvg DB 7.9 / 12.8 °C
Max coil L/s 4109 L/s
Water flow @ 11.0 °K drop 0.28 L/s

Supply Fan Sizing Data


Actual max L/s at Sep 1500 4109 L/s Fan motor BHP 9.59 BHP
Standard L/s 3746 L/s Fan motor kW 7.61 kW
Actual max L/(s-m²) 9.85 L/(s-m²) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 2400 L/s L/s/person 22.86 L/s/person
L/(s-m²) 5.76 L/(s-m²)

Hourly Analysis Program v4.80 Page 255 of 263


Zone Sizing Summary for AHU-H-RF-02 F18 Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:29PM

Air System Information


Air System Name AHU-H-RF-02 F18 Restaurant Number of zones 1
Equipment Class CW AHU Floor Area 417.0 m²
Air System Type VAV Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
F18-12 Speciality Rest. 50.6 4109 2363 Sep 1500 12.2 417.0 9.85

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.0 °K (kW) @ 11.0 °K (L/s)
F18-12 Speciality Rest. 33.6 0.73 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
F18-12 Speciality Rest.
F18R-12 Spec Restaurant 1 50.6 Sep 1500 4109 12.2 417.0 9.85

Hourly Analysis Program v4.80 Page 256 of 263


Ventilation Sizing Summary for AHU-H-RF-02 F18 Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:29PM

1. Summary
Ventilation Sizing Method ASHRAE Std 62.1-2007
Design Condition Minimum flow (heating)
Occupant Diversity 1.000
Uncorrected Ventilation Airflow Rate 1890 L/s
System Ventilation Efficiency 1.000
Design Ventilation Airflow Rate 2363 L/s
Design Ventilation Airflow Rate, Corrected for Exhaust Air 2400 L/s

2. Space Ventilation Analysis Table


Minimum Floor Required Time Required Air Required Uncorrected Space
Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Ventilation
Zone Name / Space Name Mult. (L/s) (m²) (L/(s-m²)) Occupancy (L/s/person) Effectiveness (L/s) (L/s) Efficiency
F18-12 Speciality Rest.
F18R-12 Spec Restaurant 1 2363 417.0 0.00 105.0 18.00 0.80 2363 1890 1.000
Totals (incl. Space Multipliers) 2363 1890 1.000

Hourly Analysis Program v4.80 Page 257 of 263


Air System Design Load Summary for AHU-H-RF-02 F18 Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:29PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 134 m² 9249 - 134 m² - -
Wall Transmission 97 m² 956 - 97 m² 770 -
Roof Transmission 437 m² 3928 - 437 m² 2214 -
Window Transmission 134 m² 2927 - 134 m² 5813 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 123 m² 1550 - 123 m² 2337 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 12510 W 12509 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 105 7077 3696 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 7700 0 - 0 0
Safety Factor 10% / 10% 4590 370 10% 1113 0
>> Total Zone Loads - 50485 4066 - 12247 0
Zone Conditioning - 48409 4066 - 11137 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1532 L/s 0 - 982 L/s 0 -
Ventilation Load 2152 L/s 29033 20996 1380 L/s 31748 0
Supply Fan Load 3684 L/s 6898 - 2363 L/s -4508 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 84340 25062 - 38377 0
Central Cooling Coil - 84340 25062 - -4508 0
Preheat Coil - 0 - - 12760 -
Terminal Reheat Coils - 0 - - 30125 -
>> Total Conditioning - 84340 25062 - 38377 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 258 of 263


Zone Design Load Summary for AHU-H-RF-02 F18 Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:29PM

F18-12 Speciality Rest. DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 134 m² 10259 - 134 m² - -
Wall Transmission 97 m² 910 - 97 m² 770 -
Roof Transmission 437 m² 3444 - 437 m² 2214 -
Window Transmission 134 m² 2630 - 134 m² 5813 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 123 m² 1511 - 123 m² 2337 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 12510 W 12509 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 105 7077 3696 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 7700 0 - 0 0
Safety Factor 10% / 10% 4604 370 10% 1113 0
>> Total Zone Loads - 50645 4066 - 12247 0

Hourly Analysis Program v4.80 Page 259 of 263


Space Design Load Summary for AHU-H-RF-02 F18 Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:29PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' F18R-12 Spec Restaurant '' IN ZONE '' F18-12 Speciality Rest. ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 134 m² 10259 - 134 m² - -
Wall Transmission 97 m² 910 - 97 m² 770 -
Roof Transmission 437 m² 3444 - 437 m² 2214 -
Window Transmission 134 m² 2630 - 134 m² 5813 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 123 m² 1511 - 123 m² 2337 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 12510 W 12509 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 105 7077 3696 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 7700 0 - 0 0
Safety Factor 10% / 10% 4604 370 10% 1113 0
>> Total Zone Loads - 50645 4066 - 12247 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' F18R-12 Spec Restaurant '' IN ZONE '' F18-12 Speciality Rest. ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 30 0.365 - 473 - 240
WINDOW 1 101 1.990 0.300 1983 9042 4382
NW EXPOSURE
WALL 22 0.365 - 157 - 171
WINDOW 1 33 1.990 0.300 648 1217 1432
NE EXPOSURE
WALL 45 0.365 - 280 - 358
H EXPOSURE
ROOF 437 0.232 - 3444 - 2214

Hourly Analysis Program v4.80 Page 260 of 263


Hourly Air System Design Day Loads for AHU-H-RF-02 F18 Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:30PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 3039 51.0 70.5 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.2 2994 49.1 68.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.6 2951 47.3 66.2 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.2 2912 45.9 64.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 2877 44.7 62.9 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 2858 44.1 62.3 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.9 2865 44.7 62.9 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.5 2893 46.2 64.7 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.5 2943 48.9 67.9 0.0 0.0 0.0 0.0 0.0 0.0
0900 29.0 3010 52.9 72.5 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.7 3086 57.7 77.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 32.6 3178 63.4 84.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.4 3304 69.8 92.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.8 3437 75.7 99.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.7 3557 80.5 104.7 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.0 3641 83.3 108.1 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.7 3669 83.2 108.1 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.9 3614 80.0 104.4 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.6 3461 73.7 97.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.2 3376 68.7 91.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 31.7 3290 63.8 85.4 0.0 0.0 0.0 0.0 0.0 0.0
2100 30.4 3215 59.7 80.7 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.3 3148 56.1 76.6 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.4 3090 53.3 73.2 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 261 of 263


Hourly Zone Loads for AHU-H-RF-02 F18 Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:30PM

ZONE: F18-12 Speciality Rest.


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.4 42 3039.2 38581.4 38692.6 0.0 0.0 0.0
0100 27.2 24.3 42 2993.6 37853.8 38027.1 0.0 0.0 0.0
0200 26.6 24.3 43 2950.7 37181.6 37404.6 0.0 0.0 0.0
0300 26.2 24.3 43 2911.9 36587.0 36844.2 0.0 0.0 0.0
0400 25.8 24.3 43 2877.0 36063.0 36341.6 0.0 0.0 0.0
0500 25.7 24.3 43 2858.4 35822.2 36073.3 0.0 0.0 0.0
0600 25.9 24.3 43 2865.4 36021.6 36173.8 0.0 0.0 0.0
0700 26.5 24.3 43 2893.1 36568.6 36573.5 0.0 0.0 0.0
0800 27.5 24.3 42 2943.2 37487.4 37295.6 0.0 0.0 0.0
0900 29.0 24.4 42 3009.5 38675.3 38259.0 0.0 0.0 0.0
1000 30.7 24.4 42 3085.9 40023.5 39375.2 0.0 0.0 0.0
1100 32.6 24.4 41 3178.0 41639.7 40732.7 0.0 0.0 0.0
1200 34.4 24.5 41 3304.1 43860.3 42611.2 0.0 0.0 0.0
1300 35.8 24.6 40 3437.0 46197.5 44616.1 0.0 0.0 0.0
1400 36.7 24.7 40 3556.6 48289.2 46444.7 0.0 0.0 0.0
1500 37.0 24.7 40 3641.3 49727.0 47751.5 0.0 0.0 0.0
1600 36.7 24.7 40 3669.1 50098.8 48183.1 0.0 0.0 0.0
1700 35.9 24.7 40 3613.7 48922.9 47323.9 0.0 0.0 0.0
1800 34.6 24.6 40 3460.6 45987.9 44976.1 0.0 0.0 0.0
1900 33.2 24.6 41 3375.8 44412.4 43689.9 0.0 0.0 0.0
2000 31.7 24.5 41 3290.2 42859.3 42404.0 0.0 0.0 0.0
2100 30.4 24.5 41 3215.3 41536.0 41285.7 0.0 0.0 0.0
2200 29.3 24.4 42 3148.4 40387.3 40296.1 0.0 0.0 0.0
2300 28.4 24.4 42 3090.1 39410.8 39437.4 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 262 of 263


System Psychrometrics for AHU-H-RF-02 F18 Restaurant
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:30PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 2127 400 28758 20724
Vent - Return Mixing Outlet 31.9 0.01052 3641 494 - -
Preheat Coil Outlet 31.9 0.01052 3641 494 0 -
Central Cooling Coil Outlet 11.1 0.00799 3641 494 83329 24790
Supply Fan Outlet 12.8 0.00799 3641 494 6819 -
Cold Supply Duct Outlet 12.8 0.00799 3641 494 - -
Zone Air - 24.7 0.00841 3641 627 47752 4066
Zone Direct Exhaust Outlet 24.7 0.00841 2127 627 - -
Return Plenum Outlet 24.7 0.00841 1514 627 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
F18-12 Speciality Rest. 49727 Cooling 47752 24.7 3641 627 0 0

Hourly Analysis Program v4.80 Page 263 of 263


Air System Sizing Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Air System Information


Air System Name FCU - C1 Number of zones 9
Equipment Class TERM Floor Area 286.0 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Cooling Coil Sizing Data


Total coil load 1.3 kW Load occurs at Jul 1500
Sensible coil load 1.0 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 37 L/s Entering DB / WB 37.0 / 22.0 °C
Max coil L/s 37 L/s Leaving DB / WB 12.8 / 11.6 °C
Sensible heat ratio 0.754 Bypass Factor 0.100
Water flow @ 6.7 °K rise 0.05 L/s

Ventilation Fan Sizing Data


Actual max L/s 37 L/s Fan motor BHP 0.00 BHP
Standard L/s 33 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 0.13 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 37 L/s L/s/person 0.31 L/s/person
L/(s-m²) 0.13 L/(s-m²)

Hourly Analysis Program v4.80 Page 1 of 773


Zone Sizing Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Air System Information


Air System Name FCU - C1 Number of zones 9
Equipment Class TERM Floor Area 286.0 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C1-44 Meeting Room 3 4.6 373 373 Jul 1600 0.6 50.0 7.45
C1-45 Meeting Room 2 4.6 373 373 Jul 1600 0.6 50.0 7.45
C1-47 Prayer Room F 5.6 456 456 Jul 1600 1.7 39.0 11.68
C1-48 Prayer Room M 4.9 401 401 Jul 1600 2.0 28.0 14.34
C1-50 Meeting Room 6.2 499 499 Jul 1600 2.6 80.0 6.24
C1-53 Executive Chef Off 1.3 103 103 Jul 1600 0.7 11.0 9.37
C1-54 Executive Chef Off 1.3 109 109 Jul 1600 0.6 9.0 12.07
C1-34 Chef Office 0.5 40 40 Jul 1600 0.1 5.0 8.05
C1-37 Banquet Services 1.5 125 125 Jul 1600 1.0 14.0 8.90

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 6.7 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
C1-44 Meeting Room 3 6.0 4.7 25.0 / 18.0 13.6 / 13.0 0.22 Jun 1600
C1-45 Meeting Room 2 6.0 4.7 25.0 / 18.0 13.6 / 13.0 0.22 Jun 1600
C1-47 Prayer Room F 6.6 5.6 24.9 / 17.7 13.8 / 13.2 0.24 Jun 1300
C1-48 Prayer Room M 5.7 4.9 24.9 / 17.6 13.8 / 13.1 0.20 Aug 1500
C1-50 Meeting Room 8.2 6.1 25.0 / 18.4 13.9 / 13.3 0.29 Jul 1500
C1-53 Executive Chef Off 1.3 1.1 23.7 / 17.5 14.0 / 13.5 0.05 Jul 1500
C1-54 Executive Chef Off 1.4 1.2 24.1 / 17.5 14.0 / 13.4 0.05 Aug 1700
C1-34 Chef Office 0.6 0.5 23.8 / 17.4 13.7 / 13.1 0.02 Jul 1600
C1-37 Banquet Services 1.6 1.3 23.6 / 17.5 14.0 / 13.5 0.06 Jul 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.0 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
C1-44 Meeting Room 3 0.5 21.0 / 22.3 0.01 373 0.094 0.075 0
C1-45 Meeting Room 2 0.5 21.0 / 22.3 0.01 373 0.094 0.075 0
C1-47 Prayer Room F 1.6 21.0 / 24.1 0.03 456 0.115 0.091 0
C1-48 Prayer Room M 1.9 20.8 / 25.0 0.04 401 0.101 0.080 0
C1-50 Meeting Room 2.5 20.9 / 25.5 0.05 499 0.126 0.100 0
C1-53 Executive Chef Off 0.9 18.5 / 26.6 0.02 103 0.026 0.021 11
C1-54 Executive Chef Off 0.8 19.3 / 25.8 0.02 109 0.027 0.022 8
C1-34 Chef Office 0.1 18.9 / 22.3 0.00 40 0.010 0.008 4
C1-37 Banquet Services 1.3 18.3 / 27.6 0.03 125 0.031 0.025 14

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-44 Meeting Room 3
C1F-44 Meeting Room 3 1 4.6 Jul 1600 373 0.6 50.0 7.45

Hourly Analysis Program v4.80 Page 2 of 773


Zone Sizing Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-45 Meeting Room 2
C1F-45 Meeting Room 2 1 4.6 Jul 1600 373 0.6 50.0 7.45
C1-47 Prayer Room F
C1F-47 Prayer Rm F 1 5.6 Jul 1600 456 1.7 39.0 11.68
C1-48 Prayer Room M
C1F-48 Prayer Rm M 1 4.9 Jul 1600 401 2.0 28.0 14.34
C1-50 Meeting Room
C1F-50 Meeting Room 1 6.2 Jul 1600 499 2.6 80.0 6.24
C1-53 Executive Chef Off
C1F-53 Executive Chef Of 1 1.3 Jul 1600 103 0.7 11.0 9.37
C1-54 Executive Chef Off
C1F-54 Executive Chef Of 1 1.3 Jul 1600 109 0.6 9.0 12.07
C1-34 Chef Office
C1F-34 Chef Office 1 0.5 Jul 1600 40 0.1 5.0 8.05
C1-37 Banquet Services
C1F-37 Banquet Services 1 1.5 Jul 1600 125 1.0 14.0 8.90

Hourly Analysis Program v4.80 Page 3 of 773


Ventilation Sizing Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 37 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
C1-44 Meeting Room 3
C1F-44 Meeting Room 3 1 50.0 14.0 372.6 0.00 0.00 0.0 0.0 0.0
C1-45 Meeting Room 2
C1F-45 Meeting Room 2 1 50.0 14.0 372.6 0.00 0.00 0.0 0.0 0.0
C1-47 Prayer Room F
C1F-47 Prayer Rm F 1 39.0 35.0 455.6 0.00 0.00 0.0 0.0 0.0
C1-48 Prayer Room M
C1F-48 Prayer Rm M 1 28.0 30.0 401.4 0.00 0.00 0.0 0.0 0.0
C1-50 Meeting Room
C1F-50 Meeting Room 1 80.0 14.0 499.2 0.00 0.00 0.0 0.0 0.0
C1-53 Executive Chef Off
C1F-53 Executive Chef Of 1 11.0 3.0 103.0 2.50 0.30 0.0 0.0 10.8
C1-54 Executive Chef Off
C1F-54 Executive Chef Of 1 9.0 2.0 108.6 2.50 0.30 0.0 0.0 7.7
C1-34 Chef Office
C1F-34 Chef Office 1 5.0 1.0 40.3 2.50 0.30 0.0 0.0 4.0
C1-37 Banquet Services
C1F-37 Banquet Services 1 14.0 4.0 124.5 2.50 0.30 0.0 0.0 14.2
Totals (incl. Space Multipliers) 2477.8 36.7

Hourly Analysis Program v4.80 Page 4 of 773


Air System Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 290 m² 2722 - 290 m² 1469 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 277 m² 1103 - 277 m² 1662 -
Partitions 309 m² 3886 - 309 m² 5875 -
Ceiling 9 m² 36 - 9 m² 54 -
Overhead Lighting 5816 W 5815 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5750 W 5750 - 0 0 -
People 117 8400 7032 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2771 703 10% 906 0
>> Total Zone Loads - 30483 7735 - 9966 0
Zone Conditioning - 29689 7735 - 9685 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 37 L/s 0 - 37 L/s 0 -
Ventilation Load 37 L/s 452 67 37 L/s 865 0
Ventilation Fan Load 37 L/s 0 - 37 L/s 0 -
Space Fan Coil Fans - 496 - - -496 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 30637 7802 - 10054 0
Cooling Coil - 941 334 - 0 0
Terminal Unit Cooling - 29695 7477 - 0 0
Terminal Unit Heating - 0 - - 10054 -
>> Total Conditioning - 30637 7812 - 10054 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 5 of 773


Zone Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

C1-44 Meeting Room 3 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 50 m² 469 - 50 m² 253 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 50 m² 201 - 50 m² 300 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1000 W 1000 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 14 1005 841 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 418 84 10% 55 0
>> Total Zone Loads - 4593 926 - 609 0

C1-45 Meeting Room 2 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 50 m² 469 - 50 m² 253 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 50 m² 201 - 50 m² 300 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1000 W 1000 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 14 1005 841 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 418 84 10% 55 0
>> Total Zone Loads - 4593 926 - 609 0

Hourly Analysis Program v4.80 Page 6 of 773


Zone Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

C1-47 Prayer Room F DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 39 m² 366 - 39 m² 198 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 39 m² 157 - 39 m² 234 -
Partitions 59 m² 743 - 59 m² 1112 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1326 W 1326 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 35 2513 2104 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 511 210 10% 154 0
>> Total Zone Loads - 5616 2314 - 1697 0

C1-48 Prayer Room M DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 28 m² 263 - 28 m² 142 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 113 - 28 m² 168 -
Partitions 80 m² 1017 - 80 m² 1520 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 952 W 952 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 30 2154 1803 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 450 180 10% 183 0
>> Total Zone Loads - 4948 1983 - 2013 0

Hourly Analysis Program v4.80 Page 7 of 773


Zone Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

C1-50 Meeting Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 80 m² 750 - 80 m² 405 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 80 m² 322 - 80 m² 480 -
Partitions 80 m² 1017 - 80 m² 1520 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1000 W 1000 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 14 1005 841 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 559 84 10% 241 0
>> Total Zone Loads - 6154 926 - 2646 0

C1-53 Executive Chef Off DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 15 m² 141 - 15 m² 76 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 11 m² 44 - 11 m² 66 -
Partitions 27 m² 339 - 27 m² 507 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 165 W 165 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 115 18 10% 65 0
>> Total Zone Loads - 1270 198 - 714 0

Hourly Analysis Program v4.80 Page 8 of 773


Zone Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

C1-54 Executive Chef Off DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 9 m² 84 - 9 m² 46 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 25 m² 318 - 25 m² 475 -
Ceiling 9 m² 36 - 9 m² 54 -
Overhead Lighting 135 W 135 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 122 12 10% 57 0
>> Total Zone Loads - 1338 132 - 632 0

C1-34 Chef Office DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 5 m² 47 - 5 m² 25 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 5 m² 20 - 5 m² 30 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 63 W 62 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 45 6 10% 6 0
>> Total Zone Loads - 496 66 - 61 0

Hourly Analysis Program v4.80 Page 9 of 773


Zone Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

C1-37 Banquet Services DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 14 m² 131 - 14 m² 71 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 14 m² 56 - 14 m² 84 -
Partitions 39 m² 496 - 39 m² 741 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 175 W 175 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 140 24 10% 90 0
>> Total Zone Loads - 1535 264 - 986 0

Hourly Analysis Program v4.80 Page 10 of 773


Space Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' C1F-44 Meeting Room 3 '' IN ZONE '' C1-44 Meeting Room 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 50 m² 469 - 50 m² 253 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 50 m² 201 - 50 m² 300 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1000 W 1000 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 14 1005 841 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 418 84 10% 55 0
>> Total Zone Loads - 4593 926 - 609 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' C1F-44 Meeting Room 3 '' IN ZONE '' C1-44 Meeting Room 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 50 0.232 - 469 - 253

Hourly Analysis Program v4.80 Page 11 of 773


Space Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' C1F-45 Meeting Room 2 '' IN ZONE '' C1-45 Meeting Room 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 50 m² 469 - 50 m² 253 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 50 m² 201 - 50 m² 300 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1000 W 1000 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 14 1005 841 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 418 84 10% 55 0
>> Total Zone Loads - 4593 926 - 609 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' C1F-45 Meeting Room 2 '' IN ZONE '' C1-45 Meeting Room 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 50 0.232 - 469 - 253

Hourly Analysis Program v4.80 Page 12 of 773


Space Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' C1F-47 Prayer Rm F '' IN ZONE '' C1-47 Prayer Room F ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 39 m² 366 - 39 m² 198 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 39 m² 157 - 39 m² 234 -
Partitions 59 m² 743 - 59 m² 1112 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1326 W 1326 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 35 2513 2104 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 511 210 10% 154 0
>> Total Zone Loads - 5616 2314 - 1697 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' C1F-47 Prayer Rm F '' IN ZONE '' C1-47 Prayer Room F ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 39 0.232 - 366 - 198

Hourly Analysis Program v4.80 Page 13 of 773


Space Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' C1F-48 Prayer Rm M '' IN ZONE '' C1-48 Prayer Room M ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 28 m² 263 - 28 m² 142 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 113 - 28 m² 168 -
Partitions 80 m² 1017 - 80 m² 1520 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 952 W 952 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 30 2154 1803 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 450 180 10% 183 0
>> Total Zone Loads - 4948 1983 - 2013 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' C1F-48 Prayer Rm M '' IN ZONE '' C1-48 Prayer Room M ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 28 0.232 - 263 - 142

Hourly Analysis Program v4.80 Page 14 of 773


Space Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' C1F-50 Meeting Room '' IN ZONE '' C1-50 Meeting Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 80 m² 750 - 80 m² 405 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 80 m² 322 - 80 m² 480 -
Partitions 80 m² 1017 - 80 m² 1520 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1000 W 1000 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 14 1005 841 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 559 84 10% 241 0
>> Total Zone Loads - 6154 926 - 2646 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' C1F-50 Meeting Room '' IN ZONE '' C1-50 Meeting Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 80 0.232 - 750 - 405

Hourly Analysis Program v4.80 Page 15 of 773


Space Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' C1F-53 Executive Chef Of '' IN ZONE '' C1-53 Executive Chef Off ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 15 m² 141 - 15 m² 76 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 11 m² 44 - 11 m² 66 -
Partitions 27 m² 339 - 27 m² 507 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 165 W 165 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 115 18 10% 65 0
>> Total Zone Loads - 1270 198 - 714 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' C1F-53 Executive Chef Of '' IN ZONE '' C1-53 Executive Chef Off ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 15 0.232 - 141 - 76

Hourly Analysis Program v4.80 Page 16 of 773


Space Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' C1F-54 Executive Chef Of '' IN ZONE '' C1-54 Executive Chef Off ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 9 m² 84 - 9 m² 46 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 25 m² 318 - 25 m² 475 -
Ceiling 9 m² 36 - 9 m² 54 -
Overhead Lighting 135 W 135 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 500 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 122 12 10% 57 0
>> Total Zone Loads - 1338 132 - 632 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' C1F-54 Executive Chef Of '' IN ZONE '' C1-54 Executive Chef Off ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 9 0.232 - 84 - 46

Hourly Analysis Program v4.80 Page 17 of 773


Space Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' C1F-34 Chef Office '' IN ZONE '' C1-34 Chef Office ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 5 m² 47 - 5 m² 25 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 5 m² 20 - 5 m² 30 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 63 W 62 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 45 6 10% 6 0
>> Total Zone Loads - 496 66 - 61 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' C1F-34 Chef Office '' IN ZONE '' C1-34 Chef Office ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 5 0.232 - 47 - 25

Hourly Analysis Program v4.80 Page 18 of 773


Space Design Load Summary for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' C1F-37 Banquet Services '' IN ZONE '' C1-37 Banquet Services ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 14 m² 131 - 14 m² 71 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 14 m² 56 - 14 m² 84 -
Partitions 39 m² 496 - 39 m² 741 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 175 W 175 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 140 24 10% 90 0
>> Total Zone Loads - 1535 264 - 986 0

TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' C1F-37 Banquet Services '' IN ZONE '' C1-37 Banquet Services ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 14 0.232 - 131 - 71

Hourly Analysis Program v4.80 Page 19 of 773


Hourly Air System Design Day Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

DESIGN MONTH: JULY


COMMON CENTRAL CENTRAL CENTRAL VENT VENT ZONE
OA VENT COOLING COOLING HEATING COOLING HEATING TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 37 0.0 0.0 0.0 0.9 0.0 32.9 0.0 0.0
0100 27.2 37 0.0 0.0 0.0 0.8 0.0 32.8 0.0 0.0
0200 26.6 37 0.0 0.0 0.0 0.8 0.0 32.2 0.0 0.0
0300 26.2 37 0.0 0.0 0.0 0.8 0.0 32.2 0.0 0.0
0400 25.8 37 0.0 0.0 0.0 0.8 0.0 31.9 0.0 0.0
0500 25.7 37 0.0 0.0 0.0 0.8 0.0 31.7 0.0 0.0
0600 25.9 37 0.0 0.0 0.0 0.8 0.0 31.8 0.0 0.0
0700 26.5 37 0.0 0.0 0.0 0.8 0.0 32.1 0.0 0.0
0800 27.5 37 0.0 0.0 0.0 0.9 0.0 32.4 0.0 0.0
0900 29.0 37 0.0 0.0 0.0 0.9 0.0 33.1 0.0 0.0
1000 30.7 37 0.0 0.0 0.0 1.0 0.0 34.2 0.0 0.0
1100 32.6 37 0.0 0.0 0.0 1.1 0.0 34.8 0.0 0.0
1200 34.4 37 0.0 0.0 0.0 1.2 0.0 35.7 0.0 0.0
1300 35.8 37 0.0 0.0 0.0 1.2 0.0 36.6 0.0 0.0
1400 36.7 37 0.0 0.0 0.0 1.3 0.0 36.6 0.0 0.0
1500 37.0 37 0.0 0.0 0.0 1.3 0.0 37.1 0.0 0.0
1600 36.7 37 0.0 0.0 0.0 1.3 0.0 36.8 0.0 0.0
1700 35.9 37 0.0 0.0 0.0 1.2 0.0 37.0 0.0 0.0
1800 34.6 37 0.0 0.0 0.0 1.2 0.0 36.5 0.0 0.0
1900 33.2 37 0.0 0.0 0.0 1.1 0.0 35.8 0.0 0.0
2000 31.7 37 0.0 0.0 0.0 1.1 0.0 35.4 0.0 0.0
2100 30.4 37 0.0 0.0 0.0 1.0 0.0 34.7 0.0 0.0
2200 29.3 37 0.0 0.0 0.0 0.9 0.0 34.0 0.0 0.0
2300 28.4 37 0.0 0.0 0.0 0.9 0.0 33.5 0.0 0.0

Hourly Analysis Program v4.80 Page 20 of 773


Hourly Zone Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: C1-44 Meeting Room 3


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 57 372.6 4143.4 4122.0 5555.2 0.0 0.0
0100 27.2 24.8 57 372.6 4112.4 4079.9 5514.8 0.0 0.0
0200 26.6 24.9 57 372.6 4084.9 4041.2 5476.4 0.0 0.0
0300 26.2 24.8 57 372.6 4061.6 4075.2 5512.1 0.0 0.0
0400 25.8 24.9 58 372.6 4041.8 3969.0 5404.3 0.0 0.0
0500 25.7 24.8 58 372.6 4026.7 3992.8 5430.0 0.0 0.0
0600 25.9 24.8 57 372.6 4022.1 4032.2 5468.9 0.0 0.0
0700 26.5 24.9 58 372.6 4040.6 3969.1 5404.2 0.0 0.0
0800 27.5 24.8 57 372.6 4091.0 4052.9 5487.5 0.0 0.0
0900 29.0 25.0 57 372.6 4168.0 4065.4 5498.0 0.0 0.0
1000 30.7 24.9 56 372.6 4260.2 4206.7 5638.1 0.0 0.0
1100 32.6 24.9 55 372.6 4359.5 4292.1 5721.3 0.0 0.0
1200 34.4 24.9 54 372.6 4454.0 4371.7 5808.4 0.0 0.0
1300 35.8 24.8 53 372.6 4523.0 4516.3 5945.5 0.0 0.0
1400 36.7 25.0 54 372.6 4568.1 4461.8 5877.2 0.0 0.0
1500 37.0 24.9 53 372.6 4592.3 4526.9 5946.4 0.0 0.0
1600 36.7 25.0 53 372.6 4592.8 4511.0 5943.1 0.0 0.0
1700 35.9 24.8 53 372.6 4568.9 4580.9 6008.8 0.0 0.0
1800 34.6 25.0 54 372.6 4517.0 4410.2 5835.6 0.0 0.0
1900 33.2 24.9 54 372.6 4434.6 4388.1 5816.1 0.0 0.0
2000 31.7 24.8 54 372.6 4351.6 4381.5 5812.9 0.0 0.0
2100 30.4 24.8 55 372.6 4282.9 4303.9 5736.8 0.0 0.0
2200 29.3 24.9 56 372.6 4226.3 4198.2 5630.2 0.0 0.0
2300 28.4 24.9 56 372.6 4180.6 4137.5 5569.9 0.0 0.0

ZONE: C1-45 Meeting Room 2


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 57 372.6 4143.4 4122.0 5555.2 0.0 0.0
0100 27.2 24.8 57 372.6 4112.4 4079.9 5514.8 0.0 0.0
0200 26.6 24.9 57 372.6 4084.9 4041.2 5476.4 0.0 0.0
0300 26.2 24.8 57 372.6 4061.6 4075.2 5512.1 0.0 0.0
0400 25.8 24.9 58 372.6 4041.8 3969.0 5404.3 0.0 0.0
0500 25.7 24.8 58 372.6 4026.7 3992.8 5430.0 0.0 0.0
0600 25.9 24.8 57 372.6 4022.1 4032.2 5468.9 0.0 0.0
0700 26.5 24.9 58 372.6 4040.6 3969.1 5404.2 0.0 0.0
0800 27.5 24.8 57 372.6 4091.0 4052.9 5487.5 0.0 0.0
0900 29.0 25.0 57 372.6 4168.0 4065.4 5498.0 0.0 0.0
1000 30.7 24.9 56 372.6 4260.2 4206.7 5638.1 0.0 0.0
1100 32.6 24.9 55 372.6 4359.5 4292.1 5721.3 0.0 0.0
1200 34.4 24.9 54 372.6 4454.0 4371.7 5808.4 0.0 0.0
1300 35.8 24.8 53 372.6 4523.0 4516.3 5945.5 0.0 0.0
1400 36.7 25.0 54 372.6 4568.1 4461.8 5877.2 0.0 0.0
1500 37.0 24.9 53 372.6 4592.3 4526.9 5946.4 0.0 0.0
1600 36.7 25.0 53 372.6 4592.8 4511.0 5943.1 0.0 0.0
1700 35.9 24.8 53 372.6 4568.9 4580.9 6008.8 0.0 0.0
1800 34.6 25.0 54 372.6 4517.0 4410.2 5835.6 0.0 0.0
1900 33.2 24.9 54 372.6 4434.6 4388.1 5816.1 0.0 0.0
2000 31.7 24.8 54 372.6 4351.6 4381.5 5812.9 0.0 0.0
2100 30.4 24.8 55 372.6 4282.9 4303.9 5736.8 0.0 0.0
2200 29.3 24.9 56 372.6 4226.3 4198.2 5630.2 0.0 0.0
2300 28.4 24.9 56 372.6 4180.6 4137.5 5569.9 0.0 0.0

Hourly Analysis Program v4.80 Page 21 of 773


Hourly Zone Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: C1-47 Prayer Room F


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 56 455.6 4921.6 4788.6 5943.0 0.0 0.0
0100 27.2 24.8 56 455.6 4865.6 4808.0 5967.0 0.0 0.0
0200 26.6 25.0 57 455.6 4811.8 4652.8 5809.0 0.0 0.0
0300 26.2 24.9 57 455.6 4766.2 4621.0 5777.3 0.0 0.0
0400 25.8 24.8 57 455.6 4728.3 4673.8 5833.8 0.0 0.0
0500 25.7 24.9 58 455.6 4704.9 4568.6 5727.0 0.0 0.0
0600 25.9 24.7 57 455.6 4705.9 4656.4 5815.6 0.0 0.0
0700 26.5 24.6 56 455.6 4741.7 4765.8 5913.4 0.0 0.0
0800 27.5 24.8 57 455.6 4825.1 4693.9 5850.6 0.0 0.0
0900 29.0 24.7 55 455.6 4952.3 4890.3 6049.7 0.0 0.0
1000 30.7 24.7 54 455.6 5104.4 5040.7 6197.8 0.0 0.0
1100 32.6 24.9 54 455.6 5275.3 5106.2 6258.7 0.0 0.0
1200 34.4 24.8 52 455.6 5439.8 5323.8 6477.4 0.0 0.0
1300 35.8 25.0 52 455.6 5538.8 5350.4 6501.4 0.0 0.0
1400 36.7 25.0 52 455.6 5582.0 5401.0 6550.8 0.0 0.0
1500 37.0 25.0 51 455.6 5608.3 5431.5 6580.7 0.0 0.0
1600 36.7 25.0 51 455.6 5615.7 5442.6 6594.0 0.0 0.0
1700 35.9 25.0 51 455.6 5603.5 5433.5 6582.9 0.0 0.0
1800 34.6 25.0 52 455.6 5542.0 5374.2 6524.3 0.0 0.0
1900 33.2 25.0 53 455.6 5412.9 5246.5 6397.5 0.0 0.0
2000 31.7 25.0 54 455.6 5280.9 5115.2 6267.1 0.0 0.0
2100 30.4 24.8 54 455.6 5168.5 5087.8 6243.8 0.0 0.0
2200 29.3 25.0 55 455.6 5069.0 4908.7 6062.3 0.0 0.0
2300 28.4 24.8 55 455.6 4987.2 4936.6 6094.1 0.0 0.0

ZONE: C1-48 Prayer Room M


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 56 401.4 4226.4 4068.8 4913.2 0.0 0.0
0100 27.2 24.9 57 401.4 4165.4 4000.6 4846.4 0.0 0.0
0200 26.6 24.7 57 401.4 4105.8 4007.1 4855.3 0.0 0.0
0300 26.2 24.8 58 401.4 4055.2 3909.3 4755.4 0.0 0.0
0400 25.8 24.8 58 401.4 4013.5 3860.9 4707.2 0.0 0.0
0500 25.7 24.7 58 401.4 3989.1 3891.8 4740.9 0.0 0.0
0600 25.9 24.9 59 401.4 3992.8 3788.5 4632.1 0.0 0.0
0700 26.5 24.6 57 401.4 4032.4 3982.7 4832.8 0.0 0.0
0800 27.5 24.6 56 401.4 4120.9 4074.9 4924.4 0.0 0.0
0900 29.0 24.7 56 401.4 4255.9 4146.5 4994.9 0.0 0.0
1000 30.7 24.7 54 401.4 4417.2 4335.6 5183.4 0.0 0.0
1100 32.6 25.0 54 401.4 4600.6 4367.9 5210.3 0.0 0.0
1200 34.4 25.0 52 401.4 4777.6 4548.3 5390.9 0.0 0.0
1300 35.8 25.0 52 401.4 4878.0 4647.4 5489.7 0.0 0.0
1400 36.7 25.0 51 401.4 4914.2 4686.2 5527.3 0.0 0.0
1500 37.0 25.0 51 401.4 4937.9 4716.8 5557.4 0.0 0.0
1600 36.7 25.0 51 401.4 4947.8 4732.4 5575.1 0.0 0.0
1700 35.9 25.0 51 401.4 4943.3 4732.7 5573.9 0.0 0.0
1800 34.6 25.0 51 401.4 4885.4 4678.3 5520.0 0.0 0.0
1900 33.2 24.9 52 401.4 4750.6 4618.4 5462.8 0.0 0.0
2000 31.7 24.8 53 401.4 4612.2 4506.5 5352.3 0.0 0.0
2100 30.4 24.7 53 401.4 4493.2 4449.8 5298.6 0.0 0.0
2200 29.3 24.8 55 401.4 4385.9 4245.3 5090.9 0.0 0.0
2300 28.4 24.8 56 401.4 4297.2 4153.5 4999.0 0.0 0.0

Hourly Analysis Program v4.80 Page 22 of 773


Hourly Zone Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: C1-50 Meeting Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 63 499.2 4964.9 4792.4 7047.9 0.0 0.0
0100 27.2 24.6 62 499.2 4871.7 4879.1 7129.7 0.0 0.0
0200 26.6 24.8 64 499.2 4783.5 4590.9 6847.6 0.0 0.0
0300 26.2 24.7 64 499.2 4708.6 4645.4 6904.7 0.0 0.0
0400 25.8 24.6 64 499.2 4646.3 4683.1 6938.5 0.0 0.0
0500 25.7 24.7 65 499.2 4606.2 4501.3 6760.9 0.0 0.0
0600 25.9 24.7 65 499.2 4605.2 4511.5 6769.2 0.0 0.0
0700 26.5 24.6 64 499.2 4664.0 4640.8 6902.2 0.0 0.0
0800 27.5 24.7 64 499.2 4804.9 4638.8 6895.9 0.0 0.0
0900 29.0 24.6 62 499.2 5019.8 4925.4 7186.6 0.0 0.0
1000 30.7 24.7 60 499.2 5277.1 5155.6 7415.3 0.0 0.0
1100 32.6 24.8 59 499.2 5563.7 5299.1 7555.4 0.0 0.0
1200 34.4 24.9 58 499.2 5839.0 5456.0 7710.5 0.0 0.0
1300 35.8 24.8 56 499.2 6011.3 5824.9 8084.8 0.0 0.0
1400 36.7 25.0 57 499.2 6094.3 5698.6 7952.6 0.0 0.0
1500 37.0 24.8 55 499.2 6143.1 5982.2 8241.2 0.0 0.0
1600 36.7 25.0 57 499.2 6153.6 5744.0 7999.4 0.0 0.0
1700 35.9 25.0 56 499.2 6124.2 5785.5 8040.0 0.0 0.0
1800 34.6 24.8 56 499.2 6012.3 5811.7 8069.4 0.0 0.0
1900 33.2 24.9 58 499.2 5791.8 5539.1 7795.2 0.0 0.0
2000 31.7 24.7 58 499.2 5567.1 5521.7 7782.6 0.0 0.0
2100 30.4 24.8 60 499.2 5376.7 5219.6 7478.2 0.0 0.0
2200 29.3 24.7 60 499.2 5210.5 5194.7 7456.0 0.0 0.0
2300 28.4 24.7 62 499.2 5074.2 4964.5 7223.1 0.0 0.0

ZONE: C1-53 Executive Chef Off


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 61 103.0 985.8 967.4 1035.1 0.0 0.0
0100 27.2 24.8 63 103.0 962.7 913.8 967.4 0.0 0.0
0200 26.6 24.7 63 103.0 940.4 909.7 967.1 0.0 0.0
0300 26.2 24.7 64 103.0 921.4 886.9 939.2 0.0 0.0
0400 25.8 24.6 64 103.0 905.7 888.8 943.7 0.0 0.0
0500 25.7 24.7 65 103.0 896.1 853.5 897.9 0.0 0.0
0600 25.9 24.6 65 103.0 896.8 867.1 916.7 0.0 0.0
0700 26.5 24.6 64 103.0 911.6 877.6 928.3 0.0 0.0
0800 27.5 24.5 62 103.0 945.9 938.0 1007.2 0.0 0.0
0900 29.0 24.7 62 103.0 998.2 949.6 1010.4 0.0 0.0
1000 30.7 24.7 60 103.0 1060.7 1016.1 1086.3 0.0 0.0
1100 32.6 24.8 58 103.0 1131.1 1069.9 1147.5 0.0 0.0
1200 34.4 24.8 55 103.0 1198.9 1142.7 1233.5 0.0 0.0
1300 35.8 24.8 54 103.0 1239.4 1181.9 1279.1 0.0 0.0
1400 36.7 24.8 54 103.0 1256.4 1195.8 1291.3 0.0 0.0
1500 37.0 24.8 53 103.0 1266.9 1216.6 1318.4 0.0 0.0
1600 36.7 25.0 54 103.0 1270.1 1184.0 1270.0 0.0 0.0
1700 35.9 24.9 54 103.0 1265.8 1200.9 1294.9 0.0 0.0
1800 34.6 24.9 54 103.0 1240.9 1174.7 1264.5 0.0 0.0
1900 33.2 24.7 55 103.0 1188.0 1152.5 1250.6 0.0 0.0
2000 31.7 24.9 58 103.0 1133.8 1061.1 1133.6 0.0 0.0
2100 30.4 24.8 59 103.0 1087.6 1047.5 1125.9 0.0 0.0
2200 29.3 24.8 60 103.0 1046.6 1002.2 1071.6 0.0 0.0
2300 28.4 24.6 60 103.0 1012.8 995.2 1069.3 0.0 0.0

Hourly Analysis Program v4.80 Page 23 of 773


Hourly Zone Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: C1-54 Executive Chef Off


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 59 108.6 1110.5 1059.0 1153.8 0.0 0.0
0100 27.2 24.8 59 108.6 1091.3 1048.0 1143.6 0.0 0.0
0200 26.6 24.8 59 108.6 1072.5 1033.9 1129.1 0.0 0.0
0300 26.2 24.8 60 108.6 1056.6 1021.1 1115.5 0.0 0.0
0400 25.8 24.6 60 108.6 1043.4 1025.1 1124.0 0.0 0.0
0500 25.7 24.8 61 108.6 1035.7 994.6 1085.3 0.0 0.0
0600 25.9 24.7 61 108.6 1036.9 1000.1 1091.8 0.0 0.0
0700 26.5 24.6 60 108.6 1049.3 1025.4 1123.0 0.0 0.0
0800 27.5 24.8 60 108.6 1077.2 1024.9 1115.8 0.0 0.0
0900 29.0 24.8 58 108.6 1119.8 1073.6 1171.1 0.0 0.0
1000 30.7 24.8 57 108.6 1170.6 1119.5 1220.4 0.0 0.0
1100 32.6 24.9 55 108.6 1228.4 1173.3 1278.5 0.0 0.0
1200 34.4 24.9 53 108.6 1284.1 1226.0 1335.7 0.0 0.0
1300 35.8 24.9 53 108.6 1316.3 1253.7 1364.5 0.0 0.0
1400 36.7 24.8 52 108.6 1327.9 1285.7 1402.7 0.0 0.0
1500 37.0 25.0 52 108.6 1335.4 1262.4 1371.3 0.0 0.0
1600 36.7 25.0 52 108.6 1338.5 1276.0 1388.1 0.0 0.0
1700 35.9 24.9 52 108.6 1337.0 1279.6 1393.4 0.0 0.0
1800 34.6 24.8 52 108.6 1318.2 1281.1 1400.2 0.0 0.0
1900 33.2 24.9 54 108.6 1275.7 1214.8 1322.9 0.0 0.0
2000 31.7 24.9 55 108.6 1232.0 1179.9 1286.2 0.0 0.0
2100 30.4 24.9 56 108.6 1194.5 1148.2 1252.8 0.0 0.0
2200 29.3 24.8 57 108.6 1160.7 1118.9 1221.5 0.0 0.0
2300 28.4 24.8 58 108.6 1132.7 1094.3 1195.2 0.0 0.0

ZONE: C1-34 Chef Office


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 56 40.3 451.5 448.2 509.0 0.0 0.0
0100 27.2 24.8 56 40.3 448.4 450.6 513.8 0.0 0.0
0200 26.6 25.0 57 40.3 445.7 434.8 492.3 0.0 0.0
0300 26.2 24.7 56 40.3 443.3 447.7 511.4 0.0 0.0
0400 25.8 24.7 56 40.3 441.3 444.9 508.6 0.0 0.0
0500 25.7 24.7 57 40.3 439.8 443.3 506.9 0.0 0.0
0600 25.9 24.7 57 40.3 439.4 440.4 502.8 0.0 0.0
0700 26.5 24.8 57 40.3 441.2 436.8 497.1 0.0 0.0
0800 27.5 24.9 57 40.3 446.3 436.6 494.7 0.0 0.0
0900 29.0 24.9 56 40.3 454.0 447.5 507.2 0.0 0.0
1000 30.7 24.8 55 40.3 463.2 462.2 524.6 0.0 0.0
1100 32.6 24.8 54 40.3 473.1 470.0 532.1 0.0 0.0
1200 34.4 24.9 54 40.3 482.6 473.2 533.2 0.0 0.0
1300 35.8 24.8 53 40.3 489.5 486.7 549.6 0.0 0.0
1400 36.7 25.0 54 40.3 494.0 481.0 539.1 0.0 0.0
1500 37.0 25.0 53 40.3 496.4 487.9 548.1 0.0 0.0
1600 36.7 24.8 53 40.3 496.4 495.2 559.0 0.0 0.0
1700 35.9 25.0 53 40.3 494.0 482.3 541.9 0.0 0.0
1800 34.6 25.0 54 40.3 488.9 481.9 543.1 0.0 0.0
1900 33.2 24.9 54 40.3 480.6 475.6 536.9 0.0 0.0
2000 31.7 24.8 54 40.3 472.3 474.6 538.6 0.0 0.0
2100 30.4 24.8 55 40.3 465.4 467.9 531.8 0.0 0.0
2200 29.3 24.8 55 40.3 459.8 461.4 524.8 0.0 0.0
2300 28.4 24.7 55 40.3 455.2 459.2 523.6 0.0 0.0

Hourly Analysis Program v4.80 Page 24 of 773


Hourly Zone Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: C1-37 Banquet Services


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 62 124.5 1180.3 1147.6 1218.4 0.0 0.0
0100 27.2 24.6 63 124.5 1150.3 1115.2 1177.7 0.0 0.0
0200 26.6 24.6 64 124.5 1121.1 1084.5 1140.8 0.0 0.0
0300 26.2 24.6 65 124.5 1096.2 1070.1 1126.4 0.0 0.0
0400 25.8 24.7 66 124.5 1075.8 1016.7 1053.6 0.0 0.0
0500 25.7 24.6 66 124.5 1063.7 1026.6 1071.3 0.0 0.0
0600 25.9 24.5 65 124.5 1065.5 1060.8 1121.0 0.0 0.0
0700 26.5 24.6 65 124.5 1085.0 1039.1 1084.7 0.0 0.0
0800 27.5 24.6 64 124.5 1128.4 1084.7 1139.9 0.0 0.0
0900 29.0 24.7 63 124.5 1194.8 1129.0 1187.6 0.0 0.0
1000 30.7 24.7 60 124.5 1274.1 1211.4 1286.3 0.0 0.0
1100 32.6 24.7 58 124.5 1364.2 1302.4 1391.1 0.0 0.0
1200 34.4 24.8 57 124.5 1451.1 1351.6 1443.0 0.0 0.0
1300 35.8 24.9 56 124.5 1500.6 1384.1 1475.5 0.0 0.0
1400 36.7 24.8 54 124.5 1518.5 1429.6 1533.3 0.0 0.0
1500 37.0 24.7 54 124.5 1530.2 1465.1 1579.1 0.0 0.0
1600 36.7 24.9 55 124.5 1535.0 1426.5 1525.8 0.0 0.0
1700 35.9 24.8 54 124.5 1532.7 1468.5 1586.1 0.0 0.0
1800 34.6 24.8 55 124.5 1504.1 1421.3 1528.0 0.0 0.0
1900 33.2 24.8 56 124.5 1437.8 1355.7 1450.9 0.0 0.0
2000 31.7 24.7 57 124.5 1369.8 1324.9 1423.0 0.0 0.0
2100 30.4 24.8 60 124.5 1311.3 1228.7 1301.0 0.0 0.0
2200 29.3 24.7 60 124.5 1258.6 1208.4 1284.7 0.0 0.0
2300 28.4 24.8 62 124.5 1215.0 1149.0 1209.9 0.0 0.0

Hourly Analysis Program v4.80 Page 25 of 773


System Psychrometrics for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 37 400 492 59
Vent - Return Mixing Outlet 37.0 0.01203 37 0 - -
Vent. Cooling Coil Outlet 12.8 0.00880 37 400 977 319
Ventilation Fan Outlet 12.8 0.00880 37 400 0 -
Cold Supply Duct Outlet 12.8 0.00880 37 400 0 -
Zone Air - 24.8 0.01143 37 1943 29616 7735
Return Plenum Outlet 24.8 0.01143 37 1943 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

Hourly Analysis Program v4.80 Page 26 of 773


System Psychrometrics for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
C1-44 Meeting Room 3 (
Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 25.1 0.01150 373 0 - -
Cooling Coil Outlet - 13.9 0.01016 373 0 4601 1345
Heating Coil Inlet - 13.9 0.01016 373 0 - -
Heating Coil Outlet - 13.9 0.01016 373 0 0 -
Zone Air - 24.9 0.01151 373 0 4527 -
C1-45 Meeting Room 2 (
Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 25.1 0.01150 373 0 - -
Cooling Coil Outlet - 13.9 0.01016 373 0 4601 1345
Heating Coil Inlet - 13.9 0.01016 373 0 - -
Heating Coil Outlet - 13.9 0.01016 373 0 0 -
Zone Air - 24.9 0.01151 373 0 4527 -
C1-47 Prayer Room F (
Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 25.1 0.01114 456 0 - -
Cooling Coil Outlet - 14.1 0.01028 456 0 5523 1058
Heating Coil Inlet - 14.1 0.01028 456 0 - -
Heating Coil Outlet - 14.1 0.01028 456 0 0 -
Zone Air - 25.0 0.01114 456 0 5432 -
C1-48 Prayer Room M (
Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 25.2 0.01112 401 0 - -
Cooling Coil Outlet - 14.3 0.01042 401 0 4797 760
Heating Coil Inlet - 14.3 0.01042 401 0 - -
Heating Coil Outlet - 14.3 0.01042 401 0 0 -
Zone Air - 25.0 0.01112 401 0 4717 -
C1-50 Meeting Room ( Cooling
)
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 25.0 0.01180 499 0 - -
Cooling Coil Outlet - 13.9 0.01019 499 0 6082 2159
Heating Coil Inlet - 13.9 0.01019 499 0 - -
Heating Coil Outlet - 13.9 0.01019 499 0 0 -
Zone Air - 24.8 0.01180 499 0 5982 -
C1-53 Executive Chef Off (
Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 23.7 0.01112 103 0 - -
Cooling Coil Outlet - 14.0 0.01031 103 0 1095 223
Heating Coil Inlet - 14.0 0.01031 103 0 - -
Heating Coil Outlet - 14.0 0.01031 103 0 0 -
Zone Air - 24.8 0.01138 103 1973 1217 -
C1-54 Executive Chef Off (
Cooling )
Ventilation Air - - - 8 - - -
Cooling Coil Inlet - 24.3 0.01121 109 0 - -
Cooling Coil Outlet - 14.4 0.01056 109 0 1181 191
Heating Coil Inlet - 14.4 0.01056 109 0 - -
Heating Coil Outlet - 14.4 0.01056 109 0 0 -
Zone Air - 25.0 0.01139 109 1871 1262 -
C1-34 Chef Office ( Cooling )
Ventilation Air - - - 4 - - -
Cooling Coil Inlet - 23.9 0.01123 40 0 - -
Cooling Coil Outlet - 14.0 0.01025 40 0 442 106
Heating Coil Inlet - 14.0 0.01025 40 0 - -
Heating Coil Outlet - 14.0 0.01025 40 0 0 -
Zone Air - 25.0 0.01150 40 1816 488 -

Hourly Analysis Program v4.80 Page 27 of 773


System Psychrometrics for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
C1-37 Banquet Services (
Cooling )
Ventilation Air - - - 14 - - -
Cooling Coil Inlet - 23.6 0.01116 125 0 - -
Cooling Coil Outlet - 14.1 0.01034 125 0 1303 276
Heating Coil Inlet - 14.1 0.01034 125 0 - -
Heating Coil Outlet - 14.1 0.01034 125 0 0 -
Zone Air - 24.7 0.01147 125 1995 1465 -

Hourly Analysis Program v4.80 Page 28 of 773


Hourly Air System Design Day Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Data for July

Total Cooling Total Heating

35

30

25
Load ( kW )

20

15

10

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 29 of 773


Hourly Zone Design Day Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Zone: C1-44 Meeting Room 3


Data for July

Zone Sensible Zone Conditioning


4500

4000

3500

3000

2500
W

2000

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: C1-45 Meeting Room 2


Data for July

Zone Sensible Zone Conditioning


4500

4000

3500

3000

2500
W

2000

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 30 of 773


Hourly Zone Design Day Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Zone: C1-47 Prayer Room F


Data for July

Zone Sensible Zone Conditioning


5500
5000
4500
4000
3500
3000
W

2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: C1-48 Prayer Room M


Data for July

Zone Sensible Zone Conditioning


5000

4500

4000

3500

3000
W

2500

2000

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 31 of 773


Hourly Zone Design Day Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Zone: C1-50 Meeting Room


Data for July

Zone Sensible Zone Conditioning


6000
5500
5000
4500
4000
3500
W

3000
2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: C1-53 Executive Chef Off


Data for July

Zone Sensible Zone Conditioning


1300
1200
1100
1000
900
800
700
W

600
500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 32 of 773


Hourly Zone Design Day Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Zone: C1-54 Executive Chef Off


Data for July

Zone Sensible Zone Conditioning


1300
1200
1100
1000
900
800
700
W

600
500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: C1-34 Chef Office


Data for July

Zone Sensible Zone Conditioning


500

450

400

350

300
W

250

200

150

100

50

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 33 of 773


Hourly Zone Design Day Loads for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Zone: C1-37 Banquet Services


Data for July

Zone Sensible Zone Conditioning

1400

1200

1000

800
W

600

400

200

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 34 of 773


Psychrometric Analysis for FCU - C1
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program v4.80 Page 35 of 773


Air System Sizing Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Air System Information


Air System Name FCU - Club Lounge Number of zones 12
Equipment Class TERM Floor Area 535.0 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Cooling Coil Sizing Data


Total coil load 12.1 kW Load occurs at Jul 1500
Sensible coil load 12.1 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 645 L/s Entering DB / WB 37.0 / 22.0 °C
Max coil L/s 645 L/s Leaving DB / WB 20.0 / 17.0 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
Water flow @ 5.5 °K rise 0.53 L/s

Ventilation Fan Sizing Data


Actual max L/s 645 L/s Fan motor BHP 0.00 BHP
Standard L/s 588 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 1.21 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 645 L/s L/s/person 4.42 L/s/person
L/(s-m²) 1.21 L/(s-m²)

Hourly Analysis Program v4.80 Page 36 of 773


Zone Sizing Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Air System Information


Air System Name FCU - Club Lounge Number of zones 12
Equipment Class TERM Floor Area 535.0 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
F1-39 Club Lounge 1 1.0 80 80 Jul 1700 0.4 24.0 3.35
F1-38 Business Center 2.5 203 203 Sep 1500 1.0 26.0 7.82
F1-39 Club Lounge 3 4.9 398 398 Aug 1600 1.5 55.0 7.24
F1-39 Club Lounge 4 3.8 307 307 Jun 1600 1.1 60.0 5.12
F1-39 Club Lounge 5 3.4 277 277 Jun 1600 1.0 43.0 6.45
F1-39 Club Lounge 6 7.2 585 585 Jun 1600 1.5 56.0 10.44
F1-39 Club Lounge 7 3.3 270 270 Sep 1500 1.1 40.0 6.74
Boardroom Bot 5.0 402 402 Jun 1400 1.7 54.0 7.45
Boardroom Top 1 5.2 418 418 Sep 1500 1.7 54.0 7.74
Boardroom Top 2 5.5 444 444 Sep 1500 1.7 54.0 8.22
Boardroom Top 3 5.2 418 418 Sep 1500 1.7 54.0 7.74
Pantry 2.8 226 226 Jul 1700 0.5 15.0 15.06

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.5 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
F1-39 Club Lounge 1 1.2 0.8 23.7 / 18.1 14.1 / 13.6 0.05 Jun 1500
F1-38 Business Center 2.6 2.2 24.2 / 17.7 14.2 / 13.6 0.12 Sep 1500
F1-39 Club Lounge 3 5.3 4.3 23.9 / 17.7 14.1 / 13.6 0.23 Jun 1600
F1-39 Club Lounge 4 4.3 3.3 23.6 / 17.8 14.0 / 13.4 0.19 Jun 1700
F1-39 Club Lounge 5 3.9 3.0 23.6 / 17.6 13.8 / 13.2 0.17 Jun 1700
F1-39 Club Lounge 6 8.0 7.0 24.5 / 17.3 13.6 / 12.9 0.35 Jul 1700
F1-39 Club Lounge 7 3.6 3.0 24.2 / 17.7 14.1 / 13.5 0.16 Sep 1500
Boardroom Bot 5.6 4.6 24.3 / 17.6 13.9 / 13.2 0.24 Jun 1300
Boardroom Top 1 5.7 4.9 24.4 / 17.5 13.8 / 13.2 0.25 Sep 1500
Boardroom Top 2 6.0 5.1 24.3 / 17.4 13.8 / 13.2 0.26 Sep 1400
Boardroom Top 3 5.7 4.9 24.4 / 17.5 13.8 / 13.2 0.25 Sep 1500
Pantry 3.0 2.6 24.7 / 17.5 14.1 / 13.4 0.13 Jun 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.0 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
F1-39 Club Lounge 1 0.9 14.9 / 25.5 0.02 80 0.020 0.016 22
F1-38 Business Center 1.7 17.3 / 25.1 0.04 203 0.051 0.041 34
F1-39 Club Lounge 3 3.6 15.9 / 24.1 0.08 398 0.100 0.080 93
F1-39 Club Lounge 4 3.1 14.9 / 24.1 0.07 307 0.077 0.061 86
F1-39 Club Lounge 5 2.9 14.7 / 24.1 0.06 277 0.070 0.055 81
F1-39 Club Lounge 6 2.9 19.2 / 23.6 0.06 585 0.147 0.117 55
F1-39 Club Lounge 7 2.1 17.2 / 24.3 0.05 270 0.068 0.054 46
Boardroom Bot 3.0 18.0 / 24.7 0.06 402 0.101 0.080 56
Boardroom Top 1 2.7 18.6 / 24.6 0.06 418 0.105 0.084 46
Boardroom Top 2 3.0 18.3 / 24.4 0.07 444 0.112 0.089 56
Boardroom Top 3 2.7 18.6 / 24.6 0.06 418 0.105 0.084 46

Hourly Analysis Program v4.80 Page 37 of 773


Zone Sizing Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.0 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Pantry 1.0 19.0 / 23.0 0.02 226 0.057 0.045 23

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
F1-39 Club Lounge 1
F1-39 Club Lounge 1 1 1.0 Jul 1700 80 0.4 24.0 3.35
F1-38 Business Center
F1-38 Business Centre 1 2.5 Sep 1500 203 1.0 26.0 7.82
F1-39 Club Lounge 3
F1-39 Club Lounge 3 1 4.9 Aug 1600 398 1.5 55.0 7.24
F1-39 Club Lounge 4
F1-39 Club Lounge 4 1 3.8 Jun 1600 307 1.1 60.0 5.12
F1-39 Club Lounge 5
F1-39 Club Lounge 5 1 3.4 Jun 1600 277 1.0 43.0 6.45
F1-39 Club Lounge 6
F1-39 Club Lounge 2 1 7.2 Jun 1600 585 1.5 56.0 10.44
F1-39 Club Lounge 7
F1-35 Prefunction 1 3.3 Sep 1500 270 1.1 40.0 6.74
Boardroom Bot
F1-47 Boardroom 1 5.0 Jun 1400 402 1.7 54.0 7.45
Boardroom Top 1
F1-36 Boardroom 1 5.2 Sep 1500 418 1.7 54.0 7.74
Boardroom Top 2
F1-37 Boardroom 1 5.5 Sep 1500 444 1.7 54.0 8.22
Boardroom Top 3
F1-36 Boardroom 1 5.2 Sep 1500 418 1.7 54.0 7.74
Pantry
F1-39 Pantry 1 2.8 Jul 1700 226 0.5 15.0 15.06

Hourly Analysis Program v4.80 Page 38 of 773


Ventilation Sizing Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 645 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
F1-39 Club Lounge 1
F1-39 Club Lounge 1 1 24.0 4.0 80.3 3.80 0.30 0.0 0.0 22.4
F1-38 Business Center
F1-38 Business Centre 1 26.0 7.0 203.2 3.80 0.30 0.0 0.0 34.4
F1-39 Club Lounge 3
F1-39 Club Lounge 3 1 55.0 20.0 397.9 3.80 0.30 0.0 0.0 92.5
F1-39 Club Lounge 4
F1-39 Club Lounge 4 1 60.0 18.0 306.9 3.80 0.30 0.0 0.0 86.4
F1-39 Club Lounge 5
F1-39 Club Lounge 5 1 43.0 18.0 277.4 3.80 0.30 0.0 0.0 81.3
F1-39 Club Lounge 6
F1-39 Club Lounge 2 1 56.0 10.0 584.8 3.80 0.30 0.0 0.0 54.8
F1-39 Club Lounge 7
F1-35 Prefunction 1 40.0 9.0 269.7 3.80 0.30 0.0 0.0 46.2
Boardroom Bot
F1-47 Boardroom 1 54.0 16.0 402.2 2.50 0.30 0.0 0.0 56.2
Boardroom Top 1
F1-36 Boardroom 1 54.0 12.0 418.0 2.50 0.30 0.0 0.0 46.2
Boardroom Top 2
F1-37 Boardroom 1 54.0 16.0 443.6 2.50 0.30 0.0 0.0 56.2
Boardroom Top 3
F1-36 Boardroom 1 54.0 12.0 418.0 2.50 0.30 0.0 0.0 46.2
Pantry
F1-39 Pantry 1 15.0 4.0 226.0 0.00 1.50 0.0 0.0 22.5
Totals (incl. Space Multipliers) 4028.0 645.3

Hourly Analysis Program v4.80 Page 39 of 773


Air System Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2
Prepared by: dar

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.3 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 99 m² 5699 - 99 m² - -
Wall Transmission 147 m² 1723 - 147 m² 1170 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 99 m² 1951 - 99 m² 4295 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 263 m² 3338 - 263 m² 5003 -
Ceiling 535 m² 2142 - 535 m² 3210 -
Overhead Lighting 6889 W 6888 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 9684 W 9684 - 0 0 -
People 146 10087 6534 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1735 0 - 0 0
Safety Factor 10% / 10% 4325 653 10% 1368 0
>> Total Zone Loads - 47571 7187 - 15045 0
Zone Conditioning - 46428 7187 - 15086 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 645 L/s 0 - 645 L/s 0 -
Ventilation Load 645 L/s 7449 1786 645 L/s 15345 0
Ventilation Fan Load 645 L/s 0 - 645 L/s 0 -
Space Fan Coil Fans - 806 - - -806 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 54683 8973 - 29625 0
Cooling Coil - 10876 0 - 0 0
Terminal Unit Cooling - 43807 8960 - 0 0
Terminal Unit Heating - 0 - - 29642 -
>> Total Conditioning - 54683 8960 - 29642 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80


Zone Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2
Prepared by: dar

F1-39 Club Lounge 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 161 - 13 m² 239 -
Ceiling 24 m² 97 - 24 m² 144 -
Overhead Lighting 372 W 372 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 90 14 10% 38 0
>> Total Zone Loads - 990 155 - 422 0

F1-38 Business Center DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 806 - 9 m² - -
Wall Transmission 9 m² 141 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 177 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 178 - 15 m² 276 -
Ceiling 26 m² 101 - 26 m² 156 -
Overhead Lighting 403 W 403 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 7 472 246 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 228 25 10% 89 0
>> Total Zone Loads - 2505 271 - 983 0

Hourly Analysis Program v4.80


Zone Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2
Prepared by: dar

F1-39 Club Lounge 3 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 18 m² 1174 - 18 m² - -
Wall Transmission 34 m² 474 - 34 m² 267 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 18 m² 390 - 18 m² 781 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 55 m² 221 - 55 m² 330 -
Overhead Lighting 853 W 852 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 20 1348 704 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 446 70 10% 138 0
>> Total Zone Loads - 4905 774 - 1515 0

F1-39 Club Lounge 4 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 640 - 9 m² - -
Wall Transmission 8 m² 101 - 8 m² 64 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 185 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 132 - 11 m² 200 -
Ceiling 60 m² 238 - 60 m² 360 -
Overhead Lighting 930 W 930 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 18 1213 634 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 344 63 10% 101 0
>> Total Zone Loads - 3783 697 - 1115 0

Hourly Analysis Program v4.80


Zone Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2
Prepared by: dar

F1-39 Club Lounge 5 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 640 - 9 m² - -
Wall Transmission 8 m² 101 - 8 m² 64 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 185 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 132 - 11 m² 200 -
Ceiling 43 m² 171 - 43 m² 258 -
Overhead Lighting 667 W 666 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 18 1213 634 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 311 63 10% 91 0
>> Total Zone Loads - 3419 697 - 1003 0

F1-39 Club Lounge 6 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 640 - 9 m² - -
Wall Transmission 43 m² 374 - 43 m² 339 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 185 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 206 - 16 m² 312 -
Ceiling 56 m² 222 - 56 m² 336 -
Overhead Lighting 868 W 868 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3384 W 3384 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 655 35 10% 138 0
>> Total Zone Loads - 7209 387 - 1515 0

Hourly Analysis Program v4.80


Zone Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2
Prepared by: dar

F1-39 Club Lounge 7 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 806 - 9 m² - -
Wall Transmission 10 m² 155 - 10 m² 79 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 177 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 203 - 17 m² 314 -
Ceiling 40 m² 155 - 40 m² 240 -
Overhead Lighting 620 W 620 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 9 607 317 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 302 32 10% 102 0
>> Total Zone Loads - 3324 348 - 1125 0

Boardroom Bot DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 405 - 9 m² - -
Wall Transmission 9 m² 72 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 180 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 41 m² 505 - 41 m² 779 -
Ceiling 54 m² 210 - 54 m² 324 -
Overhead Lighting 486 W 486 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 16 1149 962 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 451 96 10% 157 0
>> Total Zone Loads - 4958 1058 - 1722 0

Hourly Analysis Program v4.80


Zone Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2
Prepared by: dar

Boardroom Top 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 806 - 9 m² - -
Wall Transmission 9 m² 141 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 177 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 41 m² 504 - 41 m² 779 -
Ceiling 54 m² 209 - 54 m² 324 -
Overhead Lighting 486 W 486 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 468 72 10% 157 0
>> Total Zone Loads - 5152 793 - 1722 0

Boardroom Top 2 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 806 - 9 m² - -
Wall Transmission 9 m² 141 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 177 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 41 m² 504 - 41 m² 779 -
Ceiling 54 m² 209 - 54 m² 324 -
Overhead Lighting 486 W 486 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 16 1149 962 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 497 96 10% 157 0
>> Total Zone Loads - 5468 1058 - 1722 0

Hourly Analysis Program v4.80


Zone Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2
Prepared by: dar

Boardroom Top 3 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 806 - 9 m² - -
Wall Transmission 9 m² 141 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 177 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 41 m² 504 - 41 m² 779 -
Ceiling 54 m² 209 - 54 m² 324 -
Overhead Lighting 486 W 486 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 468 72 10% 157 0
>> Total Zone Loads - 5152 793 - 1722 0

Pantry DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 234 - 18 m² 348 -
Ceiling 15 m² 61 - 15 m² 90 -
Overhead Lighting 233 W 232 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1735 0 - 0 0
Safety Factor 10% / 10% 253 14 10% 44 0
>> Total Zone Loads - 2785 155 - 481 0

Hourly Analysis Program v4.80


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' F1-39 Club Lounge 1 '' IN ZONE '' F1-39 Club Lounge 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 161 - 13 m² 239 -
Ceiling 24 m² 97 - 24 m² 144 -
Overhead Lighting 372 W 372 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 90 14 10% 38 0
>> Total Zone Loads - 990 155 - 422 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' F1-39 Club Lounge 1 '' IN ZONE '' F1-39 Club Lounge 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 47 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' F1-38 Business Centre '' IN ZONE '' F1-38 Business Center ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 806 - 9 m² - -
Wall Transmission 9 m² 141 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 177 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 178 - 15 m² 276 -
Ceiling 26 m² 101 - 26 m² 156 -
Overhead Lighting 403 W 403 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 7 472 246 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 228 25 10% 89 0
>> Total Zone Loads - 2505 271 - 983 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' F1-38 Business Centre '' IN ZONE '' F1-38 Business Center ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 9 0.365 - 141 - 72
WINDOW 1 9 1.990 0.300 177 806 390

Hourly Analysis Program v4.80 Page 48 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' F1-39 Club Lounge 3 '' IN ZONE '' F1-39 Club Lounge 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 18 m² 1174 - 18 m² - -
Wall Transmission 34 m² 474 - 34 m² 267 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 18 m² 390 - 18 m² 781 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 55 m² 221 - 55 m² 330 -
Overhead Lighting 853 W 852 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 20 1348 704 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 446 70 10% 138 0
>> Total Zone Loads - 4905 774 - 1515 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' F1-39 Club Lounge 3 '' IN ZONE '' F1-39 Club Lounge 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 25 0.365 - 379 - 199
WINDOW 1 9 1.990 0.300 195 665 390
NW EXPOSURE
WALL 9 0.365 - 95 - 68
WINDOW 1 9 1.990 0.300 195 510 390

Hourly Analysis Program v4.80 Page 49 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' F1-39 Club Lounge 4 '' IN ZONE '' F1-39 Club Lounge 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 640 - 9 m² - -
Wall Transmission 8 m² 101 - 8 m² 64 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 185 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 132 - 11 m² 200 -
Ceiling 60 m² 238 - 60 m² 360 -
Overhead Lighting 930 W 930 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 18 1213 634 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 344 63 10% 101 0
>> Total Zone Loads - 3783 697 - 1115 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' F1-39 Club Lounge 4 '' IN ZONE '' F1-39 Club Lounge 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 8 0.365 - 101 - 64
WINDOW 1 9 1.990 0.300 185 640 390

Hourly Analysis Program v4.80 Page 50 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' F1-39 Club Lounge 5 '' IN ZONE '' F1-39 Club Lounge 5 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 640 - 9 m² - -
Wall Transmission 8 m² 101 - 8 m² 64 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 185 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 132 - 11 m² 200 -
Ceiling 43 m² 171 - 43 m² 258 -
Overhead Lighting 667 W 666 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 18 1213 634 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 311 63 10% 91 0
>> Total Zone Loads - 3419 697 - 1003 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' F1-39 Club Lounge 5 '' IN ZONE '' F1-39 Club Lounge 5 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 8 0.365 - 101 - 64
WINDOW 1 9 1.990 0.300 185 640 390

Hourly Analysis Program v4.80 Page 51 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' F1-39 Club Lounge 2 '' IN ZONE '' F1-39 Club Lounge 6 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 640 - 9 m² - -
Wall Transmission 43 m² 374 - 43 m² 339 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 185 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 206 - 16 m² 312 -
Ceiling 56 m² 222 - 56 m² 336 -
Overhead Lighting 868 W 868 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3384 W 3384 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 655 35 10% 138 0
>> Total Zone Loads - 7209 387 - 1515 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' F1-39 Club Lounge 2 '' IN ZONE '' F1-39 Club Lounge 6 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 35 0.365 - 273 - 275
NW EXPOSURE
WALL 8 0.365 - 101 - 64
WINDOW 1 9 1.990 0.300 185 640 390

Hourly Analysis Program v4.80 Page 52 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' F1-35 Prefunction '' IN ZONE '' F1-39 Club Lounge 7 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 806 - 9 m² - -
Wall Transmission 10 m² 155 - 10 m² 79 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 177 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 17 m² 203 - 17 m² 314 -
Ceiling 40 m² 155 - 40 m² 240 -
Overhead Lighting 620 W 620 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 9 607 317 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 302 32 10% 102 0
>> Total Zone Loads - 3324 348 - 1125 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' F1-35 Prefunction '' IN ZONE '' F1-39 Club Lounge 7 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 10 0.365 - 155 - 79
WINDOW 1 9 1.990 0.300 177 806 390

Hourly Analysis Program v4.80 Page 53 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' F1-47 Boardroom '' IN ZONE '' Boardroom Bot ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 405 - 9 m² - -
Wall Transmission 9 m² 72 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 180 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 41 m² 505 - 41 m² 779 -
Ceiling 54 m² 210 - 54 m² 324 -
Overhead Lighting 486 W 486 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 16 1149 962 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 451 96 10% 157 0
>> Total Zone Loads - 4958 1058 - 1722 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' F1-47 Boardroom '' IN ZONE '' Boardroom Bot ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 9 0.365 - 72 - 72
WINDOW 1 9 1.990 0.300 180 405 390

Hourly Analysis Program v4.80 Page 54 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' F1-36 Boardroom '' IN ZONE '' Boardroom Top 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 806 - 9 m² - -
Wall Transmission 9 m² 141 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 177 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 41 m² 504 - 41 m² 779 -
Ceiling 54 m² 209 - 54 m² 324 -
Overhead Lighting 486 W 486 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 468 72 10% 157 0
>> Total Zone Loads - 5152 793 - 1722 0

TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' F1-36 Boardroom '' IN ZONE '' Boardroom Top 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 9 0.365 - 141 - 72
WINDOW 1 9 1.990 0.300 177 806 390

Hourly Analysis Program v4.80 Page 55 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 10.1.A. COMPONENT LOADS FOR SPACE '' F1-37 Boardroom '' IN ZONE '' Boardroom Top 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 806 - 9 m² - -
Wall Transmission 9 m² 141 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 177 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 41 m² 504 - 41 m² 779 -
Ceiling 54 m² 209 - 54 m² 324 -
Overhead Lighting 486 W 486 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 16 1149 962 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 497 96 10% 157 0
>> Total Zone Loads - 5468 1058 - 1722 0

TABLE 10.1.B. ENVELOPE LOADS FOR SPACE '' F1-37 Boardroom '' IN ZONE '' Boardroom Top 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 9 0.365 - 141 - 72
WINDOW 1 9 1.990 0.300 177 806 390

Hourly Analysis Program v4.80 Page 56 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 11.1.A. COMPONENT LOADS FOR SPACE '' F1-36 Boardroom '' IN ZONE '' Boardroom Top 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 806 - 9 m² - -
Wall Transmission 9 m² 141 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 177 - 9 m² 390 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 41 m² 504 - 41 m² 779 -
Ceiling 54 m² 209 - 54 m² 324 -
Overhead Lighting 486 W 486 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 468 72 10% 157 0
>> Total Zone Loads - 5152 793 - 1722 0

TABLE 11.1.B. ENVELOPE LOADS FOR SPACE '' F1-36 Boardroom '' IN ZONE '' Boardroom Top 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 9 0.365 - 141 - 72
WINDOW 1 9 1.990 0.300 177 806 390

Hourly Analysis Program v4.80 Page 57 of 773


Space Design Load Summary for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

TABLE 12.1.A. COMPONENT LOADS FOR SPACE '' F1-39 Pantry '' IN ZONE '' Pantry ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 234 - 18 m² 348 -
Ceiling 15 m² 61 - 15 m² 90 -
Overhead Lighting 233 W 232 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1735 0 - 0 0
Safety Factor 10% / 10% 253 14 10% 44 0
>> Total Zone Loads - 2785 155 - 481 0

TABLE 12.1.B. ENVELOPE LOADS FOR SPACE '' F1-39 Pantry '' IN ZONE '' Pantry ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 58 of 773


Hourly Air System Design Day Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

DESIGN MONTH: JULY


COMMON CENTRAL CENTRAL CENTRAL VENT VENT ZONE
OA VENT COOLING COOLING HEATING COOLING HEATING TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 645 0.0 0.0 0.0 5.5 0.0 42.5 0.0 0.0
0100 27.2 645 0.0 0.0 0.0 5.1 0.0 41.9 0.0 0.0
0200 26.6 645 0.0 0.0 0.0 4.7 0.0 41.2 0.0 0.0
0300 26.2 645 0.0 0.0 0.0 4.4 0.0 40.5 0.0 0.0
0400 25.8 645 0.0 0.0 0.0 4.1 0.0 39.8 0.0 0.0
0500 25.7 645 0.0 0.0 0.0 4.0 0.0 39.8 0.0 0.0
0600 25.9 645 0.0 0.0 0.0 4.2 0.0 40.3 0.0 0.0
0700 26.5 645 0.0 0.0 0.0 4.6 0.0 40.9 0.0 0.0
0800 27.5 645 0.0 0.0 0.0 5.3 0.0 42.1 0.0 0.0
0900 29.0 645 0.0 0.0 0.0 6.4 0.0 43.4 0.0 0.0
1000 30.7 645 0.0 0.0 0.0 7.6 0.0 43.5 0.0 0.0
1100 32.6 645 0.0 0.0 0.0 8.9 0.0 45.4 0.0 0.0
1200 34.4 645 0.0 0.0 0.0 10.2 0.0 47.2 0.0 0.0
1300 35.8 645 0.0 0.0 0.0 11.2 0.0 49.3 0.0 0.0
1400 36.7 645 0.0 0.0 0.0 11.8 0.0 50.3 0.0 0.0
1500 37.0 645 0.0 0.0 0.0 12.1 0.0 52.5 0.0 0.0
1600 36.7 645 0.0 0.0 0.0 11.8 0.0 52.6 0.0 0.0
1700 35.9 645 0.0 0.0 0.0 11.3 0.0 52.6 0.0 0.0
1800 34.6 645 0.0 0.0 0.0 10.4 0.0 50.0 0.0 0.0
1900 33.2 645 0.0 0.0 0.0 9.3 0.0 49.0 0.0 0.0
2000 31.7 645 0.0 0.0 0.0 8.3 0.0 47.0 0.0 0.0
2100 30.4 645 0.0 0.0 0.0 7.4 0.0 45.9 0.0 0.0
2200 29.3 645 0.0 0.0 0.0 6.6 0.0 44.0 0.0 0.0
2300 28.4 645 0.0 0.0 0.0 6.0 0.0 43.5 0.0 0.0

Hourly Analysis Program v4.80 Page 59 of 773


Hourly Zone Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: F1-39 Club Lounge 1


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 60 80.3 869.3 841.0 1010.9 0.0 0.0
0100 27.2 24.8 60 80.3 858.4 843.6 1016.7 0.0 0.0
0200 26.6 24.8 60 80.3 847.2 830.9 998.2 0.0 0.0
0300 26.2 24.7 60 80.3 837.7 825.8 994.2 0.0 0.0
0400 25.8 24.7 60 80.3 830.0 829.8 1003.1 0.0 0.0
0500 25.7 24.8 61 80.3 826.0 803.6 955.9 0.0 0.0
0600 25.9 24.8 62 80.3 827.6 786.2 925.1 0.0 0.0
0700 26.5 24.7 61 80.3 834.9 820.2 984.0 0.0 0.0
0800 27.5 24.7 60 80.3 850.1 841.2 1018.4 0.0 0.0
0900 29.0 24.8 60 80.3 873.3 837.0 1006.4 0.0 0.0
1000 30.7 24.8 59 80.3 901.0 860.9 1040.3 0.0 0.0
1100 32.6 24.8 57 80.3 933.2 912.8 1125.9 0.0 0.0
1200 34.4 24.8 57 80.3 964.5 916.5 1124.7 0.0 0.0
1300 35.8 24.8 56 80.3 980.1 941.9 1164.6 0.0 0.0
1400 36.7 24.9 56 80.3 982.9 929.1 1141.3 0.0 0.0
1500 37.0 24.9 56 80.3 985.4 941.6 1161.5 0.0 0.0
1600 36.7 24.8 55 80.3 987.8 951.9 1178.6 0.0 0.0
1700 35.9 24.9 56 80.3 990.1 938.6 1154.9 0.0 0.0
1800 34.6 24.9 56 80.3 982.8 929.7 1140.4 0.0 0.0
1900 33.2 24.8 56 80.3 960.5 925.4 1137.7 0.0 0.0
2000 31.7 24.9 58 80.3 937.3 890.0 1081.1 0.0 0.0
2100 30.4 24.8 58 80.3 917.0 893.7 1092.1 0.0 0.0
2200 29.3 24.8 58 80.3 897.9 873.8 1061.4 0.0 0.0
2300 28.4 24.9 60 80.3 882.0 840.0 1006.2 0.0 0.0

ZONE: F1-38 Business Center


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 65 203.2 1577.0 1563.9 1610.5 0.0 0.0
0100 27.2 24.5 66 203.2 1531.8 1522.3 1554.2 0.0 0.0
0200 26.6 24.5 67 203.2 1488.4 1477.2 1489.5 0.0 0.0
0300 26.2 24.6 68 203.2 1449.9 1415.0 1395.7 0.0 0.0
0400 25.8 24.5 68 203.2 1416.4 1404.9 1390.5 0.0 0.0
0500 25.7 24.7 70 203.2 1403.0 1346.4 1289.4 0.0 0.0
0600 25.9 24.5 68 203.2 1416.0 1421.8 1417.1 0.0 0.0
0700 26.5 24.6 68 203.2 1442.7 1404.1 1380.4 0.0 0.0
0800 27.5 24.5 67 203.2 1487.0 1490.6 1518.5 0.0 0.0
0900 29.0 24.5 66 203.2 1548.0 1520.5 1549.4 0.0 0.0
1000 30.7 24.6 65 203.2 1621.4 1563.9 1601.5 0.0 0.0
1100 32.6 24.6 63 203.2 1722.0 1663.4 1737.9 0.0 0.0
1200 34.4 24.6 60 203.2 1883.4 1832.2 1970.5 0.0 0.0
1300 35.8 24.7 58 203.2 2041.9 1967.6 2144.2 0.0 0.0
1400 36.7 24.9 57 203.2 2166.6 2046.5 2233.9 0.0 0.0
1500 37.0 24.7 54 203.2 2246.9 2188.6 2440.4 0.0 0.0
1600 36.7 24.7 54 203.2 2261.2 2196.7 2449.3 0.0 0.0
1700 35.9 24.9 56 203.2 2187.2 2079.5 2276.9 0.0 0.0
1800 34.6 24.7 58 203.2 2025.9 1964.5 2133.6 0.0 0.0
1900 33.2 24.6 59 203.2 1930.1 1910.1 2072.9 0.0 0.0
2000 31.7 24.7 61 203.2 1837.4 1781.0 1890.4 0.0 0.0
2100 30.4 24.6 62 203.2 1758.7 1727.8 1825.3 0.0 0.0
2200 29.3 24.6 63 203.2 1688.2 1683.9 1776.1 0.0 0.0
2300 28.4 24.5 64 203.2 1627.9 1625.2 1696.0 0.0 0.0

Hourly Analysis Program v4.80 Page 60 of 773


Hourly Zone Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: F1-39 Club Lounge 3


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 61 397.9 3497.6 3547.8 3674.4 0.0 0.0
0100 27.2 24.6 62 397.9 3414.4 3404.4 3434.8 0.0 0.0
0200 26.6 24.6 63 397.9 3336.3 3324.9 3315.8 0.0 0.0
0300 26.2 24.7 64 397.9 3266.7 3206.7 3120.8 0.0 0.0
0400 25.8 24.6 64 397.9 3205.3 3194.6 3125.2 0.0 0.0
0500 25.7 24.6 65 397.9 3180.0 3153.4 3057.9 0.0 0.0
0600 25.9 24.6 65 397.9 3202.7 3159.2 3060.0 0.0 0.0
0700 26.5 24.5 64 397.9 3249.2 3273.8 3265.1 0.0 0.0
0800 27.5 24.6 63 397.9 3323.4 3297.1 3284.0 0.0 0.0
0900 29.0 24.6 62 397.9 3421.6 3406.9 3448.5 0.0 0.0
1000 30.7 24.7 62 397.9 3536.2 3413.8 3416.3 0.0 0.0
1100 32.6 24.6 60 397.9 3683.4 3676.0 3855.0 0.0 0.0
1200 34.4 24.7 59 397.9 3900.4 3808.5 4016.3 0.0 0.0
1300 35.8 24.9 57 397.9 4177.4 3993.4 4243.2 0.0 0.0
1400 36.7 24.8 54 397.9 4484.0 4382.6 4842.6 0.0 0.0
1500 37.0 24.9 53 397.9 4742.9 4555.5 5043.9 0.0 0.0
1600 36.7 25.0 52 397.9 4877.2 4660.8 5181.9 0.0 0.0
1700 35.9 24.9 52 397.9 4789.1 4644.1 5180.6 0.0 0.0
1800 34.6 24.8 55 397.9 4387.5 4294.1 4686.1 0.0 0.0
1900 33.2 24.7 56 397.9 4185.7 4166.2 4539.3 0.0 0.0
2000 31.7 24.7 57 397.9 3992.8 3980.4 4275.0 0.0 0.0
2100 30.4 24.7 59 397.9 3836.8 3831.1 4061.1 0.0 0.0
2200 29.3 24.6 60 397.9 3704.1 3702.8 3879.2 0.0 0.0
2300 28.4 24.6 61 397.9 3592.2 3594.0 3720.8 0.0 0.0

ZONE: F1-39 Club Lounge 4


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 60 306.9 3020.8 2985.5 3228.6 0.0 0.0
0100 27.2 24.8 61 306.9 2972.4 2890.2 3059.9 0.0 0.0
0200 26.6 24.6 60 306.9 2925.6 2960.4 3218.4 0.0 0.0
0300 26.2 24.8 62 306.9 2884.4 2765.9 2851.5 0.0 0.0
0400 25.8 24.7 61 306.9 2848.7 2851.7 3028.6 0.0 0.0
0500 25.7 24.6 61 306.9 2834.3 2905.9 3157.4 0.0 0.0
0600 25.9 24.6 61 306.9 2848.0 2862.1 3067.4 0.0 0.0
0700 26.5 24.7 62 306.9 2877.0 2794.5 2921.8 0.0 0.0
0800 27.5 24.6 60 306.9 2926.0 2956.0 3218.7 0.0 0.0
0900 29.0 24.6 60 306.9 2994.2 2981.0 3248.4 0.0 0.0
1000 30.7 24.7 60 306.9 3072.3 2995.2 3245.0 0.0 0.0
1100 32.6 24.7 59 306.9 3161.3 3083.3 3380.1 0.0 0.0
1200 34.4 24.8 58 306.9 3248.0 3100.1 3377.2 0.0 0.0
1300 35.8 24.7 56 306.9 3358.6 3330.6 3775.3 0.0 0.0
1400 36.7 24.8 56 306.9 3505.8 3367.0 3791.9 0.0 0.0
1500 37.0 24.8 53 306.9 3653.6 3581.6 4138.2 0.0 0.0
1600 36.7 24.9 53 306.9 3754.7 3613.1 4154.2 0.0 0.0
1700 35.9 24.8 53 306.9 3740.0 3655.1 4238.1 0.0 0.0
1800 34.6 24.9 56 306.9 3507.5 3351.6 3750.8 0.0 0.0
1900 33.2 24.7 55 306.9 3405.9 3378.2 3830.1 0.0 0.0
2000 31.7 24.9 58 306.9 3304.1 3153.0 3442.9 0.0 0.0
2100 30.4 24.8 58 306.9 3217.9 3181.1 3519.6 0.0 0.0
2200 29.3 24.7 58 306.9 3141.0 3110.7 3422.4 0.0 0.0
2300 28.4 24.7 59 306.9 3075.6 3039.7 3305.7 0.0 0.0

Hourly Analysis Program v4.80 Page 61 of 773


Hourly Zone Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: F1-39 Club Lounge 5


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 59 277.4 2687.5 2676.8 2762.5 0.0 0.0
0100 27.2 24.7 60 277.4 2642.0 2620.3 2667.5 0.0 0.0
0200 26.6 24.8 61 277.4 2598.2 2525.2 2493.3 0.0 0.0
0300 26.2 24.7 60 277.4 2559.5 2557.8 2582.7 0.0 0.0
0400 25.8 24.7 61 277.4 2525.8 2509.3 2496.0 0.0 0.0
0500 25.7 24.8 62 277.4 2512.5 2450.1 2380.9 0.0 0.0
0600 25.9 24.7 61 277.4 2525.7 2519.2 2521.9 0.0 0.0
0700 26.5 24.6 60 277.4 2552.8 2581.6 2649.2 0.0 0.0
0800 27.5 24.7 60 277.4 2597.7 2559.5 2578.5 0.0 0.0
0900 29.0 24.5 59 277.4 2659.8 2702.2 2851.4 0.0 0.0
1000 30.7 24.6 58 277.4 2730.6 2720.9 2860.7 0.0 0.0
1100 32.6 24.6 58 277.4 2810.9 2787.3 2955.2 0.0 0.0
1200 34.4 24.7 57 277.4 2889.4 2846.0 3035.9 0.0 0.0
1300 35.8 24.7 56 277.4 2995.8 2932.9 3165.5 0.0 0.0
1400 36.7 24.9 55 277.4 3142.2 2980.3 3189.4 0.0 0.0
1500 37.0 24.8 53 277.4 3289.4 3217.8 3592.4 0.0 0.0
1600 36.7 25.0 53 277.4 3389.9 3197.2 3503.5 0.0 0.0
1700 35.9 24.9 52 277.4 3374.5 3273.9 3656.8 0.0 0.0
1800 34.6 24.8 54 277.4 3143.9 3097.7 3410.8 0.0 0.0
1900 33.2 24.8 55 277.4 3048.3 3004.5 3264.5 0.0 0.0
2000 31.7 24.7 56 277.4 2952.6 2911.0 3120.6 0.0 0.0
2100 30.4 24.7 57 277.4 2871.9 2860.9 3061.2 0.0 0.0
2200 29.3 24.8 59 277.4 2800.0 2713.9 2788.7 0.0 0.0
2300 28.4 24.7 59 277.4 2738.9 2712.3 2816.8 0.0 0.0

ZONE: F1-39 Club Lounge 6


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 54 584.8 6268.1 6153.3 6781.3 0.0 0.0
0100 27.2 24.8 54 584.8 6202.8 6173.4 6827.4 0.0 0.0
0200 26.6 24.8 55 584.8 6140.9 6075.9 6705.8 0.0 0.0
0300 26.2 24.8 55 584.8 6086.2 6013.0 6629.7 0.0 0.0
0400 25.8 24.9 55 584.8 6038.6 5955.6 6558.3 0.0 0.0
0500 25.7 24.9 56 584.8 6020.6 5927.3 6522.2 0.0 0.0
0600 25.9 24.9 55 584.8 6085.5 5982.2 6585.4 0.0 0.0
0700 26.5 24.9 54 584.8 6220.5 6108.1 6732.7 0.0 0.0
0800 27.5 24.9 54 584.8 6365.1 6244.7 6891.1 0.0 0.0
0900 29.0 24.9 53 584.8 6484.6 6356.7 7020.4 0.0 0.0
1000 30.7 25.0 53 584.8 6570.3 6435.0 7109.9 0.0 0.0
1100 32.6 25.0 52 584.8 6636.6 6493.3 7172.8 0.0 0.0
1200 34.4 24.9 51 584.8 6697.6 6645.2 7372.9 0.0 0.0
1300 35.8 24.9 51 584.8 6794.8 6724.9 7461.8 0.0 0.0
1400 36.7 24.9 50 584.8 6938.5 6850.5 7605.4 0.0 0.0
1500 37.0 24.9 49 584.8 7086.7 7013.0 7797.4 0.0 0.0
1600 36.7 24.9 49 584.8 7186.0 7101.5 7899.9 0.0 0.0
1700 35.9 24.7 49 584.8 7163.0 7176.3 8011.6 0.0 0.0
1800 34.6 24.9 50 584.8 6911.2 6831.9 7589.6 0.0 0.0
1900 33.2 25.0 52 584.8 6778.6 6626.0 7327.2 0.0 0.0
2000 31.7 24.8 52 584.8 6645.6 6585.7 7303.3 0.0 0.0
2100 30.4 24.9 53 584.8 6531.8 6430.4 7110.7 0.0 0.0
2200 29.3 24.9 53 584.8 6429.9 6321.8 6982.8 0.0 0.0
2300 28.4 24.9 54 584.8 6342.4 6224.4 6863.2 0.0 0.0

Hourly Analysis Program v4.80 Page 62 of 773


Hourly Zone Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: F1-39 Club Lounge 7


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 63 269.7 2350.4 2263.7 2417.7 0.0 0.0
0100 27.2 24.6 63 269.7 2301.3 2298.4 2487.5 0.0 0.0
0200 26.6 24.6 63 269.7 2253.9 2247.8 2420.5 0.0 0.0
0300 26.2 24.6 64 269.7 2212.1 2206.5 2365.0 0.0 0.0
0400 25.8 24.6 65 269.7 2175.8 2164.9 2310.1 0.0 0.0
0500 25.7 24.6 65 269.7 2160.9 2156.9 2296.8 0.0 0.0
0600 25.9 24.6 65 269.7 2174.4 2167.9 2315.4 0.0 0.0
0700 26.5 24.6 64 269.7 2203.6 2197.2 2358.8 0.0 0.0
0800 27.5 24.7 64 269.7 2253.1 2176.4 2310.8 0.0 0.0
0900 29.0 24.5 62 269.7 2321.9 2324.6 2537.7 0.0 0.0
1000 30.7 24.8 63 269.7 2404.8 2285.5 2449.0 0.0 0.0
1100 32.6 24.7 61 269.7 2516.3 2458.7 2700.1 0.0 0.0
1200 34.4 24.8 59 269.7 2688.9 2571.3 2835.2 0.0 0.0
1300 35.8 24.8 57 269.7 2854.4 2741.9 3064.6 0.0 0.0
1400 36.7 24.9 56 269.7 2982.1 2831.1 3171.1 0.0 0.0
1500 37.0 24.7 53 269.7 3065.2 3016.8 3444.8 0.0 0.0
1600 36.7 24.8 54 269.7 3081.4 2966.5 3359.7 0.0 0.0
1700 35.9 24.8 55 269.7 3008.3 2897.8 3266.2 0.0 0.0
1800 34.6 24.8 56 269.7 2843.6 2780.4 3122.0 0.0 0.0
1900 33.2 24.8 58 269.7 2738.4 2671.3 2973.8 0.0 0.0
2000 31.7 24.6 58 269.7 2636.2 2630.9 2938.4 0.0 0.0
2100 30.4 24.8 60 269.7 2549.6 2475.3 2707.5 0.0 0.0
2200 29.3 24.7 61 269.7 2472.0 2450.4 2690.9 0.0 0.0
2300 28.4 24.7 62 269.7 2405.9 2349.2 2539.2 0.0 0.0

ZONE: Boardroom Bot


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 56 402.2 4262.4 4136.5 4635.6 0.0 0.0
0100 27.2 24.8 56 402.2 4204.3 4149.6 4670.0 0.0 0.0
0200 26.6 24.9 57 402.2 4146.9 4014.7 4478.8 0.0 0.0
0300 26.2 24.8 57 402.2 4097.0 4050.3 4546.8 0.0 0.0
0400 25.8 24.8 58 402.2 4054.6 3934.4 4379.8 0.0 0.0
0500 25.7 24.8 56 402.2 4177.0 4116.8 4631.1 0.0 0.0
0600 25.9 24.8 54 402.2 4386.5 4329.5 4907.2 0.0 0.0
0700 26.5 24.8 54 402.2 4519.7 4402.2 4985.8 0.0 0.0
0800 27.5 24.8 53 402.2 4608.4 4491.5 5098.0 0.0 0.0
0900 29.0 24.7 52 402.2 4659.9 4617.3 5275.6 0.0 0.0
1000 30.7 25.0 53 402.2 4702.0 4476.9 5052.5 0.0 0.0
1100 32.6 24.9 52 402.2 4798.4 4667.3 5311.8 0.0 0.0
1200 34.4 24.8 51 402.2 4896.5 4811.7 5504.7 0.0 0.0
1300 35.8 25.0 51 402.2 4947.6 4735.3 5376.1 0.0 0.0
1400 36.7 24.9 51 402.2 4955.6 4816.8 5492.8 0.0 0.0
1500 37.0 25.0 51 402.2 4952.4 4756.1 5399.7 0.0 0.0
1600 36.7 24.9 51 402.2 4933.8 4807.5 5479.3 0.0 0.0
1700 35.9 25.0 51 402.2 4899.1 4727.0 5374.8 0.0 0.0
1800 34.6 24.9 51 402.2 4821.4 4713.7 5365.7 0.0 0.0
1900 33.2 24.9 52 402.2 4711.3 4592.4 5210.2 0.0 0.0
2000 31.7 24.8 53 402.2 4599.4 4569.5 5205.1 0.0 0.0
2100 30.4 24.8 54 402.2 4500.4 4425.6 5014.5 0.0 0.0
2200 29.3 24.9 55 402.2 4407.6 4259.9 4787.5 0.0 0.0
2300 28.4 24.8 55 402.2 4328.2 4264.8 4813.8 0.0 0.0

Hourly Analysis Program v4.80 Page 63 of 773


Hourly Zone Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: Boardroom Top 1


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 59 418.0 4033.6 3885.0 4358.0 0.0 0.0
0100 27.2 24.7 59 418.0 3969.1 3896.4 4384.8 0.0 0.0
0200 26.6 24.7 60 418.0 3906.2 3816.3 4285.2 0.0 0.0
0300 26.2 24.6 60 418.0 3851.1 3847.1 4344.8 0.0 0.0
0400 25.8 24.8 61 418.0 3804.0 3681.6 4102.7 0.0 0.0
0500 25.7 24.7 61 418.0 3783.6 3722.6 4182.7 0.0 0.0
0600 25.9 24.8 61 418.0 3799.4 3681.8 4111.4 0.0 0.0
0700 26.5 24.7 60 418.0 3839.0 3772.1 4244.6 0.0 0.0
0800 27.5 24.7 60 418.0 3909.9 3838.5 4317.2 0.0 0.0
0900 29.0 24.6 58 418.0 4011.5 4012.5 4552.2 0.0 0.0
1000 30.7 24.8 58 418.0 4133.4 3994.8 4503.1 0.0 0.0
1100 32.6 24.9 58 418.0 4290.4 4085.4 4595.0 0.0 0.0
1200 34.4 24.8 55 418.0 4506.6 4369.7 4956.3 0.0 0.0
1300 35.8 24.7 53 418.0 4692.4 4641.0 5304.2 0.0 0.0
1400 36.7 25.0 54 418.0 4822.0 4566.6 5167.9 0.0 0.0
1500 37.0 24.9 52 418.0 4906.8 4740.8 5392.6 0.0 0.0
1600 36.7 24.9 53 418.0 4925.2 4710.7 5337.9 0.0 0.0
1700 35.9 24.9 53 418.0 4855.2 4712.3 5355.3 0.0 0.0
1800 34.6 24.8 53 418.0 4681.2 4607.1 5249.7 0.0 0.0
1900 33.2 24.7 54 418.0 4546.3 4482.7 5107.5 0.0 0.0
2000 31.7 24.8 56 418.0 4412.9 4284.4 4845.1 0.0 0.0
2100 30.4 24.7 56 418.0 4298.6 4288.2 4877.1 0.0 0.0
2200 29.3 24.9 58 418.0 4194.7 4001.9 4489.0 0.0 0.0
2300 28.4 24.8 58 418.0 4106.6 4002.1 4502.5 0.0 0.0

ZONE: Boardroom Top 2


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 57 443.6 4349.5 4377.7 4900.9 0.0 0.0
0100 27.2 24.7 58 443.6 4285.1 4216.3 4687.3 0.0 0.0
0200 26.6 24.6 58 443.6 4222.1 4245.5 4738.8 0.0 0.0
0300 26.2 24.6 59 443.6 4167.0 4110.5 4550.4 0.0 0.0
0400 25.8 24.6 59 443.6 4119.9 4080.9 4517.5 0.0 0.0
0500 25.7 24.7 60 443.6 4099.5 3968.0 4355.1 0.0 0.0
0600 25.9 24.6 59 443.6 4115.3 4103.2 4553.6 0.0 0.0
0700 26.5 24.8 60 443.6 4154.9 3976.7 4346.7 0.0 0.0
0800 27.5 24.5 58 443.6 4225.8 4241.0 4733.9 0.0 0.0
0900 29.0 24.8 59 443.6 4327.4 4158.8 4573.1 0.0 0.0
1000 30.7 24.6 57 443.6 4449.3 4394.7 4909.5 0.0 0.0
1100 32.6 24.6 56 443.6 4606.3 4558.0 5117.4 0.0 0.0
1200 34.4 24.8 55 443.6 4822.5 4621.5 5167.1 0.0 0.0
1300 35.8 24.9 54 443.6 5008.4 4807.3 5393.5 0.0 0.0
1400 36.7 24.9 53 443.6 5137.9 4929.6 5532.9 0.0 0.0
1500 37.0 24.8 52 443.6 5222.7 5097.7 5758.2 0.0 0.0
1600 36.7 24.8 52 443.6 5241.1 5126.8 5797.0 0.0 0.0
1700 35.9 24.8 52 443.6 5171.1 5067.9 5734.9 0.0 0.0
1800 34.6 24.9 54 443.6 4997.1 4787.0 5344.5 0.0 0.0
1900 33.2 24.6 54 443.6 4862.2 4855.1 5483.7 0.0 0.0
2000 31.7 24.8 55 443.6 4728.8 4620.4 5169.4 0.0 0.0
2100 30.4 24.9 57 443.6 4614.5 4402.3 4865.8 0.0 0.0
2200 29.3 24.9 57 443.6 4510.6 4341.2 4801.1 0.0 0.0
2300 28.4 24.7 57 443.6 4422.5 4415.7 4934.8 0.0 0.0

Hourly Analysis Program v4.80 Page 64 of 773


Hourly Zone Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:48PM

ZONE: Boardroom Top 3


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 59 418.0 4033.6 3885.0 4358.0 0.0 0.0
0100 27.2 24.7 59 418.0 3969.1 3896.4 4384.8 0.0 0.0
0200 26.6 24.7 60 418.0 3906.2 3816.3 4285.2 0.0 0.0
0300 26.2 24.6 60 418.0 3851.1 3847.1 4344.8 0.0 0.0
0400 25.8 24.8 61 418.0 3804.0 3681.6 4102.7 0.0 0.0
0500 25.7 24.7 61 418.0 3783.6 3722.6 4182.7 0.0 0.0
0600 25.9 24.8 61 418.0 3799.4 3681.8 4111.4 0.0 0.0
0700 26.5 24.7 60 418.0 3839.0 3772.1 4244.6 0.0 0.0
0800 27.5 24.7 60 418.0 3909.9 3838.5 4317.2 0.0 0.0
0900 29.0 24.6 58 418.0 4011.5 4012.5 4552.2 0.0 0.0
1000 30.7 24.8 58 418.0 4133.4 3994.8 4503.1 0.0 0.0
1100 32.6 24.9 58 418.0 4290.4 4085.4 4595.0 0.0 0.0
1200 34.4 24.8 55 418.0 4506.6 4369.7 4956.3 0.0 0.0
1300 35.8 24.7 53 418.0 4692.4 4641.0 5304.2 0.0 0.0
1400 36.7 25.0 54 418.0 4822.0 4566.6 5167.9 0.0 0.0
1500 37.0 24.9 52 418.0 4906.8 4740.8 5392.6 0.0 0.0
1600 36.7 24.9 53 418.0 4925.2 4710.7 5337.9 0.0 0.0
1700 35.9 24.9 53 418.0 4855.2 4712.3 5355.3 0.0 0.0
1800 34.6 24.8 53 418.0 4681.2 4607.1 5249.7 0.0 0.0
1900 33.2 24.7 54 418.0 4546.3 4482.7 5107.5 0.0 0.0
2000 31.7 24.8 56 418.0 4412.9 4284.4 4845.1 0.0 0.0
2100 30.4 24.7 56 418.0 4298.6 4288.2 4877.1 0.0 0.0
2200 29.3 24.9 58 418.0 4194.7 4001.9 4489.0 0.0 0.0
2300 28.4 24.8 58 418.0 4106.6 4002.1 4502.5 0.0 0.0

ZONE: Pantry
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 25.1 50 226.0 2647.6 2597.8 2783.7 0.0 0.0
0100 27.2 25.1 51 226.0 2635.0 2585.2 2768.5 0.0 0.0
0200 26.6 25.1 51 226.0 2622.3 2572.4 2753.2 0.0 0.0
0300 26.2 24.9 50 226.0 2611.5 2588.7 2781.6 0.0 0.0
0400 25.8 25.0 51 226.0 2602.7 2566.9 2752.4 0.0 0.0
0500 25.7 24.9 51 226.0 2598.1 2574.7 2766.2 0.0 0.0
0600 25.9 25.0 51 226.0 2599.9 2565.9 2753.0 0.0 0.0
0700 26.5 25.0 51 226.0 2608.3 2561.3 2743.4 0.0 0.0
0800 27.5 24.9 50 226.0 2625.6 2598.1 2793.5 0.0 0.0
0900 29.0 25.1 50 226.0 2652.1 2587.9 2775.3 0.0 0.0
1000 30.7 25.1 50 226.0 2683.7 2630.2 2822.3 0.0 0.0
1100 32.6 25.1 49 226.0 2720.5 2668.9 2868.5 0.0 0.0
1200 34.4 25.1 49 226.0 2756.2 2706.5 2918.4 0.0 0.0
1300 35.8 25.1 49 226.0 2774.0 2725.3 2940.0 0.0 0.0
1400 36.7 25.1 49 226.0 2777.2 2728.9 2943.9 0.0 0.0
1500 37.0 25.1 48 226.0 2780.1 2732.3 2946.5 0.0 0.0
1600 36.7 25.0 48 226.0 2782.8 2735.4 2950.2 0.0 0.0
1700 35.9 25.0 48 226.0 2785.4 2738.2 2953.6 0.0 0.0
1800 34.6 25.1 49 226.0 2777.1 2729.8 2944.9 0.0 0.0
1900 33.2 25.1 49 226.0 2751.6 2703.6 2913.7 0.0 0.0
2000 31.7 25.1 49 226.0 2725.1 2676.5 2882.1 0.0 0.0
2100 30.4 25.1 50 226.0 2701.9 2652.8 2854.2 0.0 0.0
2200 29.3 25.1 50 226.0 2680.2 2630.7 2823.3 0.0 0.0
2300 28.4 25.1 50 226.0 2662.0 2612.3 2801.1 0.0 0.0

Hourly Analysis Program v4.80 Page 65 of 773


System Psychrometrics for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 645 400 8642 1368
Vent - Return Mixing Outlet 37.0 0.01203 645 0 - -
Vent. Cooling Coil Outlet 20.0 0.01203 645 400 12074 0
Ventilation Fan Outlet 20.0 0.01203 645 400 0 -
Cold Supply Duct Outlet 20.0 0.01203 645 400 0 -
Zone Air - 24.8 0.01124 645 1506 46583 7187
Return Plenum Outlet 24.8 0.01124 645 1506 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

Hourly Analysis Program v4.80 Page 66 of 773


System Psychrometrics for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
F1-39 Club Lounge 1 ( Cooling
)
Ventilation Air - - - 22 - - -
Cooling Coil Inlet - 23.7 0.01201 80 0 - -
Cooling Coil Outlet - 14.2 0.01052 80 0 838 323
Heating Coil Inlet - 14.2 0.01052 80 0 - -
Heating Coil Outlet - 14.2 0.01052 80 0 0 -
Zone Air - 24.9 0.01200 80 1187 942 -
F1-38 Business Center (
Cooling )
Ventilation Air - - - 34 - - -
Cooling Coil Inlet - 24.1 0.01166 203 0 - -
Cooling Coil Outlet - 14.9 0.01095 203 0 2051 389
Heating Coil Inlet - 14.9 0.01095 203 0 - -
Heating Coil Outlet - 14.9 0.01095 203 0 0 -
Zone Air - 24.7 0.01159 203 1296 2189 -
F1-39 Club Lounge 3 ( Cooling
)
Ventilation Air - - - 93 - - -
Cooling Coil Inlet - 23.9 0.01149 398 0 - -
Cooling Coil Outlet - 14.5 0.01065 398 0 4137 907
Heating Coil Inlet - 14.5 0.01065 398 0 - -
Heating Coil Outlet - 14.5 0.01065 398 0 0 -
Zone Air - 24.9 0.01133 398 1352 4555 -
F1-39 Club Lounge 4 ( Cooling
)
Ventilation Air - - - 86 - - -
Cooling Coil Inlet - 23.6 0.01159 307 0 - -
Cooling Coil Outlet - 14.2 0.01045 307 0 3191 948
Heating Coil Inlet - 14.2 0.01045 307 0 - -
Heating Coil Outlet - 14.2 0.01045 307 0 0 -
Zone Air - 24.8 0.01142 307 1318 3582 -
F1-39 Club Lounge 5 ( Cooling
)
Ventilation Air - - - 81 - - -
Cooling Coil Inlet - 23.6 0.01149 277 0 - -
Cooling Coil Outlet - 14.2 0.01049 277 0 2847 746
Heating Coil Inlet - 14.2 0.01049 277 0 - -
Heating Coil Outlet - 14.2 0.01049 277 0 0 -
Zone Air - 24.8 0.01126 277 1375 3218 -
F1-39 Club Lounge 6 ( Cooling
)
Ventilation Air - - - 55 - - -
Cooling Coil Inlet - 24.6 0.01079 585 0 - -
Cooling Coil Outlet - 14.0 0.01018 585 0 6836 961
Heating Coil Inlet - 14.0 0.01018 585 0 - -
Heating Coil Outlet - 14.0 0.01018 585 0 0 -
Zone Air - 24.9 0.01065 585 1204 7013 -
F1-39 Club Lounge 7 ( Cooling
)
Ventilation Air - - - 46 - - -
Cooling Coil Inlet - 24.1 0.01152 270 0 - -
Cooling Coil Outlet - 14.5 0.01068 270 0 2831 613
Heating Coil Inlet - 14.5 0.01068 270 0 - -
Heating Coil Outlet - 14.5 0.01068 270 0 0 -
Zone Air - 24.7 0.01141 270 1258 3017 -
Boardroom Bot ( Cooling )
Ventilation Air - - - 56 - - -
Cooling Coil Inlet - 24.5 0.01121 402 0 - -
Cooling Coil Outlet - 14.2 0.01041 402 0 4528 871
Heating Coil Inlet - 14.2 0.01041 402 0 - -
Heating Coil Outlet - 14.2 0.01041 402 0 0 -
Zone Air - 25.0 0.01107 402 2012 4756 -

Hourly Analysis Program v4.80 Page 67 of 773


System Psychrometrics for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Boardroom Top 1 ( Cooling )
Ventilation Air - - - 46 - - -
Cooling Coil Inlet - 24.5 0.01136 418 0 - -
Cooling Coil Outlet - 14.6 0.01064 418 0 4577 815
Heating Coil Inlet - 14.6 0.01064 418 0 - -
Heating Coil Outlet - 14.6 0.01064 418 0 0 -
Zone Air - 24.9 0.01128 418 1871 4741 -
Boardroom Top 2 ( Cooling )
Ventilation Air - - - 56 - - -
Cooling Coil Inlet - 24.4 0.01122 444 0 - -
Cooling Coil Outlet - 14.3 0.01049 444 0 4890 868
Heating Coil Inlet - 14.3 0.01049 444 0 - -
Heating Coil Outlet - 14.3 0.01049 444 0 0 -
Zone Air - 24.8 0.01110 444 2012 5098 -
Boardroom Top 3 ( Cooling )
Ventilation Air - - - 46 - - -
Cooling Coil Inlet - 24.5 0.01136 418 0 - -
Cooling Coil Outlet - 14.6 0.01064 418 0 4577 815
Heating Coil Inlet - 14.6 0.01064 418 0 - -
Heating Coil Outlet - 14.6 0.01064 418 0 0 -
Zone Air - 24.9 0.01128 418 1871 4741 -
Pantry ( Cooling )
Ventilation Air - - - 23 - - -
Cooling Coil Inlet - 24.7 0.01070 226 0 - -
Cooling Coil Outlet - 14.1 0.01022 226 0 2652 294
Heating Coil Inlet - 14.1 0.01022 226 0 - -
Heating Coil Outlet - 14.1 0.01022 226 0 0 -
Zone Air - 25.1 0.01055 226 1183 2732 -

Hourly Analysis Program v4.80 Page 68 of 773


Hourly Air System Design Day Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Data for July

Total Cooling Total Heating


65
60
55
50
45
Load ( kW )

40
35
30
25
20
15
10
5
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 69 of 773


Hourly Zone Design Day Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Zone: F1-39 Club Lounge 1


Data for July

Zone Sensible Zone Conditioning


1000

900

800

700

600
W

500

400

300

200

100

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-38 Business Center


Data for July

Zone Sensible Zone Conditioning


2200
2000
1800
1600
1400
1200
W

1000
800
600
400
200
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 70 of 773


Hourly Zone Design Day Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Zone: F1-39 Club Lounge 3


Data for July

Zone Sensible Zone Conditioning


5000

4500

4000

3500

3000
W

2500

2000

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-39 Club Lounge 4


Data for July

Zone Sensible Zone Conditioning

3500

3000

2500

2000
W

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 71 of 773


Hourly Zone Design Day Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Zone: F1-39 Club Lounge 5


Data for July

Zone Sensible Zone Conditioning

3000

2500

2000
W

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-39 Club Lounge 6


Data for July

Zone Sensible Zone Conditioning


7000

6000

5000

4000
W

3000

2000

1000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 72 of 773


Hourly Zone Design Day Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Zone: F1-39 Club Lounge 7


Data for July

Zone Sensible Zone Conditioning


3000

2500

2000
W

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: Boardroom Bot


Data for July

Zone Sensible Zone Conditioning


5000

4500

4000

3500

3000
W

2500

2000

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 73 of 773


Hourly Zone Design Day Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Zone: Boardroom Top 1


Data for July

Zone Sensible Zone Conditioning


5000

4500

4000

3500

3000
W

2500

2000

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: Boardroom Top 2


Data for July

Zone Sensible Zone Conditioning

5000
4500
4000
3500
3000
W

2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 74 of 773


Hourly Zone Design Day Loads for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Zone: Boardroom Top 3


Data for July

Zone Sensible Zone Conditioning


5000

4500

4000

3500

3000
W

2500

2000

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: Pantry
Data for July

Zone Sensible Zone Conditioning

2500

2000

1500
W

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 75 of 773


Psychrometric Analysis for FCU - Club Lounge
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program v4.80 Page 76 of 773


Air System Sizing Summary for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Air System Information


Air System Name FCU - Executive (25) Number of zones 2
Equipment Class TERM Floor Area 82.5 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Cooling Coil Sizing Data


Total coil load 1.0 kW Load occurs at Jul 1500
Sensible coil load 1.0 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 55 L/s Entering DB / WB 37.0 / 22.0 °C
Max coil L/s 55 L/s Leaving DB / WB 20.0 / 17.0 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
Water flow @ 5.5 °K rise 0.04 L/s

Ventilation Fan Sizing Data


Actual max L/s 55 L/s Fan motor BHP 0.00 BHP
Standard L/s 50 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 0.66 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 55 L/s L/s/person 4.56 L/s/person
L/(s-m²) 0.66 L/(s-m²)

Hourly Analysis Program v4.80 Page 77 of 773


Zone Sizing Summary for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Air System Information


Air System Name FCU - Executive (25) Number of zones 2
Equipment Class TERM Floor Area 82.5 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Executive 2.6 210 210 Jun 1600 1.8 38.0 5.54
Living Room + Office 3.2 261 261 Jun 1600 1.7 44.5 5.87

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.5 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Executive 2.7 2.4 24.6 / 17.6 14.3 / 13.6 0.12 Jun 1700
Living Room + Office 3.4 3.0 24.2 / 17.4 13.9 / 13.3 0.15 Jun 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.0 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Executive 2.1 19.0 / 28.2 0.05 210 0.053 0.042 16
Living Room + Office 2.5 17.6 / 26.1 0.05 261 0.066 0.052 38

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Executive
TYP.25 - Executive - BD 1 2.6 Jun 1600 210 1.8 38.0 5.54
Living Room + Office
TYP.25 Executive - LR 1 2.9 Jun 1600 235 1.4 41.0 5.74
TYP.25 Executive - OFF 1 0.3 Jul 1700 26 0.3 3.5 7.44

Hourly Analysis Program v4.80 Page 78 of 773


Ventilation Sizing Summary for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 55 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Executive
TYP.25 - Executive - BD 1 38.0 2.0 210.4 2.50 0.30 0.0 0.0 16.4
Living Room + Office
TYP.25 Executive - LR 1 41.0 9.0 235.2 2.50 0.30 0.0 0.0 34.8
TYP.25 Executive - OFF 1 3.5 1.0 26.1 2.50 0.30 0.0 0.0 3.6
Totals (incl. Space Multipliers) 471.7 54.8

Hourly Analysis Program v4.80 Page 79 of 773


Air System Design Load Summary for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 996 - 14 m² - -
Wall Transmission 14 m² 181 - 14 m² 114 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 288 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 106 m² 1327 - 106 m² 2006 -
Ceiling 83 m² 327 - 83 m² 495 -
Overhead Lighting 1155 W 1155 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 528 42 10% 322 0
>> Total Zone Loads - 5810 465 - 3545 0
Zone Conditioning - 5515 465 - 3385 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 55 L/s 0 - 55 L/s 0 -
Ventilation Load 55 L/s 684 240 55 L/s 1285 0
Ventilation Fan Load 55 L/s 0 - 55 L/s 0 -
Space Fan Coil Fans - 94 - - -94 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6293 705 - 4576 0
Cooling Coil - 970 0 - 0 0
Terminal Unit Cooling - 5322 709 - 0 0
Terminal Unit Heating - 0 - - 4575 -
>> Total Conditioning - 6293 709 - 4575 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 80 of 773


Zone Design Load Summary for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Executive DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 498 - 7 m² - -
Wall Transmission 7 m² 82 - 7 m² 52 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 144 - 7 m² 304 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 57 m² 716 - 57 m² 1083 -
Ceiling 38 m² 151 - 38 m² 228 -
Overhead Lighting 532 W 532 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 236 7 10% 167 0
>> Total Zone Loads - 2593 77 - 1833 0

Living Room + Office DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 498 - 7 m² - -
Wall Transmission 8 m² 99 - 8 m² 62 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 144 - 7 m² 304 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 49 m² 611 - 49 m² 923 -
Ceiling 45 m² 177 - 45 m² 267 -
Overhead Lighting 623 W 623 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 292 35 10% 156 0
>> Total Zone Loads - 3217 387 - 1712 0

Hourly Analysis Program v4.80 Page 81 of 773


Space Design Load Summary for FCU - Executive (25)
Project Name: J17006-0100D FD REV2
Prepared by: dar

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' TYP.25 - Executive - BD '' IN ZONE '' Executive ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 498 - 7 m² - -
Wall Transmission 7 m² 82 - 7 m² 52 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 144 - 7 m² 304 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 57 m² 716 - 57 m² 1083 -
Ceiling 38 m² 151 - 38 m² 228 -
Overhead Lighting 532 W 532 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 236 7 10% 167 0
>> Total Zone Loads - 2593 77 - 1833 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' TYP.25 - Executive - BD '' IN ZONE '' Executive ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 0.365 - 82 - 52
WINDOW 1 7 1.990 0.300 144 498 304

Hourly Analysis Program v4.80


Space Design Load Summary for FCU - Executive (25)
Project Name: J17006-0100D FD REV2
Prepared by: dar

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' TYP.25 Executive - LR '' IN ZONE '' Living Room + Office ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 498 - 7 m² - -
Wall Transmission 8 m² 99 - 8 m² 62 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 144 - 7 m² 304 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 452 - 36 m² 684 -
Ceiling 41 m² 163 - 41 m² 246 -
Overhead Lighting 574 W 574 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 9 607 317 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 264 32 10% 130 0
>> Total Zone Loads - 2899 348 - 1425 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' TYP.25 Executive - LR '' IN ZONE '' Living Room + Office ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 8 0.365 - 99 - 62
WINDOW 1 7 1.990 0.300 144 498 304

Hourly Analysis Program v4.80


Space Design Load Summary for FCU - Executive (25)
Project Name: J17006-0100D FD REV2
Prepared by: dar

TABLE 2.2.A. COMPONENT LOADS FOR SPACE '' TYP.25 Executive - OFF '' IN ZONE '' Living Room + Office ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 161 - 13 m² 239 -
Ceiling 4 m² 14 - 4 m² 21 -
Overhead Lighting 49 W 49 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 29 4 10% 26 0
>> Total Zone Loads - 321 39 - 286 0

TABLE 2.2.B. ENVELOPE LOADS FOR SPACE '' TYP.25 Executive - OFF '' IN ZONE '' Living Room + Office ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80


Hourly Air System Design Day Loads for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

DESIGN MONTH: JULY


COMMON CENTRAL CENTRAL CENTRAL VENT VENT ZONE
OA VENT COOLING COOLING HEATING COOLING HEATING TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 55 0.0 0.0 0.0 0.5 0.0 4.2 0.0 0.0
0100 27.2 55 0.0 0.0 0.0 0.4 0.0 4.0 0.0 0.0
0200 26.6 55 0.0 0.0 0.0 0.4 0.0 3.9 0.0 0.0
0300 26.2 55 0.0 0.0 0.0 0.4 0.0 3.7 0.0 0.0
0400 25.8 55 0.0 0.0 0.0 0.4 0.0 3.8 0.0 0.0
0500 25.7 55 0.0 0.0 0.0 0.3 0.0 3.5 0.0 0.0
0600 25.9 55 0.0 0.0 0.0 0.4 0.0 3.7 0.0 0.0
0700 26.5 55 0.0 0.0 0.0 0.4 0.0 3.6 0.0 0.0
0800 27.5 55 0.0 0.0 0.0 0.5 0.0 4.0 0.0 0.0
0900 29.0 55 0.0 0.0 0.0 0.5 0.0 4.0 0.0 0.0
1000 30.7 55 0.0 0.0 0.0 0.6 0.0 4.3 0.0 0.0
1100 32.6 55 0.0 0.0 0.0 0.8 0.0 4.7 0.0 0.0
1200 34.4 55 0.0 0.0 0.0 0.9 0.0 5.0 0.0 0.0
1300 35.8 55 0.0 0.0 0.0 0.9 0.0 5.2 0.0 0.0
1400 36.7 55 0.0 0.0 0.0 1.0 0.0 5.5 0.0 0.0
1500 37.0 55 0.0 0.0 0.0 1.0 0.0 5.6 0.0 0.0
1600 36.7 55 0.0 0.0 0.0 1.0 0.0 5.9 0.0 0.0
1700 35.9 55 0.0 0.0 0.0 1.0 0.0 6.0 0.0 0.0
1800 34.6 55 0.0 0.0 0.0 0.9 0.0 5.5 0.0 0.0
1900 33.2 55 0.0 0.0 0.0 0.8 0.0 5.1 0.0 0.0
2000 31.7 55 0.0 0.0 0.0 0.7 0.0 5.0 0.0 0.0
2100 30.4 55 0.0 0.0 0.0 0.6 0.0 4.6 0.0 0.0
2200 29.3 55 0.0 0.0 0.0 0.6 0.0 4.6 0.0 0.0
2300 28.4 55 0.0 0.0 0.0 0.5 0.0 4.2 0.0 0.0

Hourly Analysis Program v4.80 Page 85 of 773


Hourly Zone Loads for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

ZONE: Executive
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 63 210.4 1734.6 1680.1 1793.9 0.0 0.0
0100 27.2 24.6 64 210.4 1671.7 1623.8 1728.5 0.0 0.0
0200 26.6 24.6 65 210.4 1609.7 1567.5 1662.9 0.0 0.0
0300 26.2 24.5 66 210.4 1555.9 1517.9 1600.3 0.0 0.0
0400 25.8 24.5 67 210.4 1510.3 1475.3 1555.1 0.0 0.0
0500 25.7 24.6 68 210.4 1489.8 1424.3 1493.0 0.0 0.0
0600 25.9 24.5 67 210.4 1504.1 1458.0 1531.2 0.0 0.0
0700 26.5 24.6 67 210.4 1543.6 1450.2 1521.6 0.0 0.0
0800 27.5 24.5 64 210.4 1616.5 1595.5 1700.6 0.0 0.0
0900 29.0 24.7 65 210.4 1722.7 1586.6 1679.8 0.0 0.0
1000 30.7 24.6 61 210.4 1846.8 1787.1 1922.3 0.0 0.0
1100 32.6 24.6 59 210.4 1989.8 1877.3 2019.5 0.0 0.0
1200 34.4 24.7 57 210.4 2129.0 1998.1 2160.6 0.0 0.0
1300 35.8 24.7 55 210.4 2250.9 2103.7 2281.7 0.0 0.0
1400 36.7 24.8 54 210.4 2372.1 2210.4 2402.7 0.0 0.0
1500 37.0 24.8 52 210.4 2493.6 2316.4 2528.6 0.0 0.0
1600 36.7 24.8 51 210.4 2578.4 2394.3 2611.3 0.0 0.0
1700 35.9 24.8 50 210.4 2572.6 2418.9 2641.4 0.0 0.0
1800 34.6 24.8 53 210.4 2375.1 2232.6 2427.8 0.0 0.0
1900 33.2 24.8 55 210.4 2244.3 2115.5 2291.5 0.0 0.0
2000 31.7 24.7 57 210.4 2111.3 2002.0 2162.8 0.0 0.0
2100 30.4 24.7 59 210.4 1997.4 1905.8 2047.9 0.0 0.0
2200 29.3 24.7 60 210.4 1893.6 1817.4 1952.3 0.0 0.0
2300 28.4 24.6 62 210.4 1806.1 1742.0 1865.4 0.0 0.0

ZONE: Living Room + Office


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 59 261.3 2382.7 2334.1 2381.6 0.0 0.0
0100 27.2 24.6 60 261.3 2322.5 2277.7 2309.6 0.0 0.0
0200 26.6 24.6 61 261.3 2263.5 2219.3 2233.3 0.0 0.0
0300 26.2 24.7 62 261.3 2212.2 2105.5 2069.5 0.0 0.0
0400 25.8 24.5 61 261.3 2168.6 2186.4 2203.2 0.0 0.0
0500 25.7 24.7 63 261.3 2149.0 2075.1 2038.2 0.0 0.0
0600 25.9 24.5 61 261.3 2162.7 2186.0 2205.8 0.0 0.0
0700 26.5 24.7 62 261.3 2200.1 2107.6 2079.3 0.0 0.0
0800 27.5 24.5 60 261.3 2268.8 2263.1 2302.3 0.0 0.0
0900 29.0 24.6 60 261.3 2368.4 2290.7 2326.1 0.0 0.0
1000 30.7 24.8 59 261.3 2484.7 2343.0 2382.2 0.0 0.0
1100 32.6 24.6 56 261.3 2618.5 2553.4 2669.2 0.0 0.0
1200 34.4 24.7 55 261.3 2748.8 2665.4 2811.2 0.0 0.0
1300 35.8 24.7 54 261.3 2866.9 2742.4 2906.7 0.0 0.0
1400 36.7 24.7 52 261.3 2989.5 2893.6 3106.7 0.0 0.0
1500 37.0 24.9 52 261.3 3113.3 2860.3 3025.6 0.0 0.0
1600 36.7 24.8 50 261.3 3200.5 3051.5 3291.6 0.0 0.0
1700 35.9 24.7 50 261.3 3196.1 3088.5 3346.6 0.0 0.0
1800 34.6 24.7 52 261.3 3000.8 2883.8 3085.9 0.0 0.0
1900 33.2 24.9 54 261.3 2873.5 2687.9 2817.3 0.0 0.0
2000 31.7 24.7 55 261.3 2744.2 2678.0 2825.9 0.0 0.0
2100 30.4 24.8 57 261.3 2634.2 2471.5 2542.0 0.0 0.0
2200 29.3 24.6 57 261.3 2534.8 2506.7 2612.6 0.0 0.0
2300 28.4 24.8 60 261.3 2451.2 2293.6 2311.2 0.0 0.0

Hourly Analysis Program v4.80 Page 86 of 773


System Psychrometrics for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 55 400 729 112
Vent - Return Mixing Outlet 37.0 0.01203 55 0 - -
Vent. Cooling Coil Outlet 20.0 0.01203 55 400 1024 0
Ventilation Fan Outlet 20.0 0.01203 55 400 0 -
Cold Supply Duct Outlet 20.0 0.01203 55 400 0 -
Zone Air - 24.9 0.01127 55 1365 5177 465
Return Plenum Outlet 24.9 0.01127 55 1365 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Executive ( Cooling )
Ventilation Air - - - 16 - - -
Cooling Coil Inlet - 24.6 0.01124 210 0 - -
Cooling Coil Outlet - 14.8 0.01079 210 0 2272 257
Heating Coil Inlet - 14.8 0.01079 210 0 - -
Heating Coil Outlet - 14.8 0.01079 210 0 0 -
Zone Air - 24.8 0.01117 210 937 2316 -
Living Room + Office ( Cooling
)
Ventilation Air - - - 38 - - -
Cooling Coil Inlet - 24.4 0.01142 261 0 - -
Cooling Coil Outlet - 15.0 0.01097 261 0 2704 322
Heating Coil Inlet - 15.0 0.01097 261 0 - -
Heating Coil Outlet - 15.0 0.01097 261 0 0 -
Zone Air - 24.9 0.01132 261 1549 2860 -

Hourly Analysis Program v4.80 Page 87 of 773


Hourly Air System Design Day Loads for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Data for July

Total Cooling Total Heating


7

5
Load ( kW )

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 88 of 773


Hourly Zone Design Day Loads for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Zone: Executive
Data for July

Zone Sensible Zone Conditioning


2500

2000

1500
W

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: Living Room + Office


Data for July

Zone Sensible Zone Conditioning

3000

2500

2000
W

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 89 of 773


Psychrometric Analysis for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM Air System Sizing Summary for FCU -
Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM
The psychrometric graph cannot be generated for this type of system.
Air System Information
Air System Name FCU - Executive (26) Number of zones 2
Equipment Class TERM Floor Area 82.5 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Cooling Coil Sizing Data


Total coil load 1.0 kW Load occurs at Jul 1500
Sensible coil load 1.0 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 55 L/s Entering DB / WB 37.0 / 22.0 °C
Max coil L/s 55 L/s Leaving DB / WB 20.0 / 17.0 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
Water flow @ 5.5 °K rise 0.04 L/s

Ventilation Fan Sizing Data


Actual max L/s 55 L/s Fan motor BHP 0.00 BHP
Standard L/s 50 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 0.66 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 55 L/s L/s/person 4.56 L/s/person
L/(s-m²) 0.66 L/(s-m²)

Hourly Analysis Program v4.80 Page 90 of 773 Hourly Analysis Program v4.80 Page 90 of 773
Psychrometric Analysis for FCU - Executive (25)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM Air System Sizing Summary for FCU -
Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Hourly Analysis Program v4.80 Page 91 of 773 Hourly Analysis Program v4.80 Page 91 of 773
Zone Sizing Summary for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Air System Information


Air System Name FCU - Executive (26) Number of zones 2
Equipment Class TERM Floor Area 82.5 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Bedroom 3.2 260 260 Jun 1600 2.3 38.0 6.83
Living Room + Office 4.3 351 351 Aug 1600 2.3 44.5 7.89

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.5 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Bedroom 3.3 3.0 24.6 / 17.4 14.2 / 13.5 0.14 Jul 1700
Living Room + Office 4.4 4.0 24.5 / 17.5 14.2 / 13.6 0.19 Aug 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.0 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Bedroom 2.6 19.3 / 28.3 0.06 260 0.065 0.052 16
Living Room + Office 3.1 18.5 / 26.5 0.07 351 0.089 0.070 38

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Bedroom
TYP.26 Executive - BD 1 3.2 Jun 1600 260 2.3 38.0 6.83
Living Room + Office
TYP.26 Executive - LR 1 3.9 Aug 1600 315 1.9 41.0 7.69
TYP.26 Executive - OF 1 0.4 Sep 1600 36 0.3 3.5 10.26

Hourly Analysis Program v4.80 Page 92 of 773


Ventilation Sizing Summary for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 55 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Bedroom
TYP.26 Executive - BD 1 38.0 2.0 259.5 2.50 0.30 0.0 0.0 16.4
Living Room + Office
TYP.26 Executive - LR 1 41.0 9.0 315.2 2.50 0.30 0.0 0.0 34.8
TYP.26 Executive - OF 1 3.5 1.0 35.9 2.50 0.30 0.0 0.0 3.6
Totals (incl. Space Multipliers) 610.6 54.8

Hourly Analysis Program v4.80 Page 93 of 773


Air System Design Load Summary for FCU - Executive (26)
Project Name: J17006-0100D FD REV2
Prepared by: dar

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 28 m² 1549 - 28 m² - -
Wall Transmission 58 m² 713 - 58 m² 464 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 28 m² 583 - 28 m² 1215 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 106 m² 1353 - 106 m² 2006 -
Ceiling 83 m² 334 - 83 m² 495 -
Overhead Lighting 1155 W 1155 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 670 42 10% 418 0
>> Total Zone Loads - 7365 465 - 4598 0
Zone Conditioning - 7073 465 - 4479 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 55 L/s 0 - 55 L/s 0 -
Ventilation Load 55 L/s 669 204 55 L/s 1293 0
Ventilation Fan Load 55 L/s 0 - 55 L/s 0 -
Space Fan Coil Fans - 122 - - -122 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 7864 668 - 5650 0
Cooling Coil - 956 0 - 0 0
Terminal Unit Cooling - 6908 669 - 0 0
Terminal Unit Heating - 0 - - 5649 -
>> Total Conditioning - 7864 669 - 5649 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80


Zone Design Load Summary for FCU - Executive (26)
Project Name: J17006-0100D FD REV2
Prepared by: dar

Bedroom DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 782 - 14 m² - -
Wall Transmission 22 m² 205 - 22 m² 175 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 288 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 57 m² 716 - 57 m² 1083 -
Ceiling 38 m² 151 - 38 m² 228 -
Overhead Lighting 532 W 532 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 291 7 10% 209 0
>> Total Zone Loads - 3199 77 - 2303 0

Living Room + Office DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 913 - 14 m² - -
Wall Transmission 36 m² 519 - 36 m² 289 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 303 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 49 m² 618 - 49 m² 923 -
Ceiling 45 m² 179 - 45 m² 267 -
Overhead Lighting 623 W 623 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 393 35 10% 209 0
>> Total Zone Loads - 4322 387 - 2295 0

Hourly Analysis Program v4.80


Space Design Load Summary for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' TYP.26 Executive - BD '' IN ZONE '' Bedroom ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 782 - 14 m² - -
Wall Transmission 22 m² 205 - 22 m² 175 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 288 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 57 m² 716 - 57 m² 1083 -
Ceiling 38 m² 151 - 38 m² 228 -
Overhead Lighting 532 W 532 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 291 7 10% 209 0
>> Total Zone Loads - 3199 77 - 2303 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' TYP.26 Executive - BD '' IN ZONE '' Bedroom ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 16 0.365 - 122 - 123
WINDOW 1 7 1.990 0.300 144 284 304
NW EXPOSURE
WALL 7 0.365 - 82 - 52
WINDOW 1 7 1.990 0.300 144 498 304

Hourly Analysis Program v4.80 Page 96 of 773


Space Design Load Summary for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' TYP.26 Executive - LR '' IN ZONE '' Living Room + Office ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 913 - 14 m² - -
Wall Transmission 29 m² 413 - 29 m² 233 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 303 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 458 - 36 m² 684 -
Ceiling 41 m² 165 - 41 m² 246 -
Overhead Lighting 574 W 574 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 9 607 317 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 353 32 10% 177 0
>> Total Zone Loads - 3886 348 - 1948 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' TYP.26 Executive - LR '' IN ZONE '' Living Room + Office ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 22 0.365 - 326 - 171
WINDOW 1 7 1.990 0.300 152 517 304
NW EXPOSURE
WALL 8 0.365 - 87 - 62
WINDOW 1 7 1.990 0.300 152 397 304

Hourly Analysis Program v4.80 Page 97 of 773


Space Design Load Summary for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

TABLE 2.2.A. COMPONENT LOADS FOR SPACE '' TYP.26 Executive - OF '' IN ZONE '' Living Room + Office ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 7 m² 116 - 7 m² 56 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 156 - 13 m² 239 -
Ceiling 4 m² 14 - 4 m² 21 -
Overhead Lighting 49 W 49 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 40 4 10% 32 0
>> Total Zone Loads - 443 39 - 348 0

TABLE 2.2.B. ENVELOPE LOADS FOR SPACE '' TYP.26 Executive - OF '' IN ZONE '' Living Room + Office ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 0.365 - 116 - 56

Hourly Analysis Program v4.80 Page 98 of 773


Hourly Air System Design Day Loads for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

DESIGN MONTH: JULY


COMMON CENTRAL CENTRAL CENTRAL VENT VENT ZONE
OA VENT COOLING COOLING HEATING COOLING HEATING TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 55 0.0 0.0 0.0 0.5 0.0 4.9 0.0 0.0
0100 27.2 55 0.0 0.0 0.0 0.4 0.0 4.7 0.0 0.0
0200 26.6 55 0.0 0.0 0.0 0.4 0.0 4.4 0.0 0.0
0300 26.2 55 0.0 0.0 0.0 0.4 0.0 4.3 0.0 0.0
0400 25.8 55 0.0 0.0 0.0 0.4 0.0 4.0 0.0 0.0
0500 25.7 55 0.0 0.0 0.0 0.3 0.0 4.1 0.0 0.0
0600 25.9 55 0.0 0.0 0.0 0.4 0.0 4.4 0.0 0.0
0700 26.5 55 0.0 0.0 0.0 0.4 0.0 4.6 0.0 0.0
0800 27.5 55 0.0 0.0 0.0 0.5 0.0 4.8 0.0 0.0
0900 29.0 55 0.0 0.0 0.0 0.5 0.0 5.1 0.0 0.0
1000 30.7 55 0.0 0.0 0.0 0.6 0.0 5.3 0.0 0.0
1100 32.6 55 0.0 0.0 0.0 0.8 0.0 5.7 0.0 0.0
1200 34.4 55 0.0 0.0 0.0 0.9 0.0 6.3 0.0 0.0
1300 35.8 55 0.0 0.0 0.0 0.9 0.0 6.6 0.0 0.0
1400 36.7 55 0.0 0.0 0.0 1.0 0.0 6.7 0.0 0.0
1500 37.0 55 0.0 0.0 0.0 1.0 0.0 7.4 0.0 0.0
1600 36.7 55 0.0 0.0 0.0 1.0 0.0 7.5 0.0 0.0
1700 35.9 55 0.0 0.0 0.0 1.0 0.0 7.6 0.0 0.0
1800 34.6 55 0.0 0.0 0.0 0.9 0.0 6.9 0.0 0.0
1900 33.2 55 0.0 0.0 0.0 0.8 0.0 6.4 0.0 0.0
2000 31.7 55 0.0 0.0 0.0 0.7 0.0 6.0 0.0 0.0
2100 30.4 55 0.0 0.0 0.0 0.6 0.0 5.8 0.0 0.0
2200 29.3 55 0.0 0.0 0.0 0.6 0.0 5.2 0.0 0.0
2300 28.4 55 0.0 0.0 0.0 0.5 0.0 5.1 0.0 0.0

Hourly Analysis Program v4.80 Page 99 of 773


Hourly Zone Loads for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

ZONE: Bedroom
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.5 63 259.5 2038.4 2055.1 2194.8 0.0 0.0
0100 27.2 24.6 66 259.5 1951.3 1859.9 1951.4 0.0 0.0
0200 26.6 24.5 66 259.5 1866.6 1843.8 1941.7 0.0 0.0
0300 26.2 24.5 67 259.5 1792.3 1773.0 1861.2 0.0 0.0
0400 25.8 24.5 68 259.5 1728.6 1696.6 1771.2 0.0 0.0
0500 25.7 24.4 67 259.5 1811.7 1804.1 1903.6 0.0 0.0
0600 25.9 24.6 65 259.5 1997.8 1908.9 2021.8 0.0 0.0
0700 26.5 24.6 63 259.5 2150.0 2059.7 2190.7 0.0 0.0
0800 27.5 24.8 62 259.5 2280.6 2086.1 2216.3 0.0 0.0
0900 29.0 24.6 59 259.5 2386.2 2273.2 2431.2 0.0 0.0
1000 30.7 24.8 59 259.5 2481.5 2282.4 2431.2 0.0 0.0
1100 32.6 24.6 56 259.5 2620.0 2518.9 2710.4 0.0 0.0
1200 34.4 24.6 54 259.5 2757.3 2644.6 2849.3 0.0 0.0
1300 35.8 24.8 54 259.5 2879.9 2706.5 2918.9 0.0 0.0
1400 36.7 24.9 53 259.5 3000.1 2728.3 2927.3 0.0 0.0
1500 37.0 24.8 51 259.5 3113.4 2929.5 3157.8 0.0 0.0
1600 36.7 24.9 51 259.5 3177.8 2926.4 3147.6 0.0 0.0
1700 35.9 24.7 50 259.5 3137.7 3016.4 3261.5 0.0 0.0
1800 34.6 24.9 54 259.5 2891.7 2670.6 2860.3 0.0 0.0
1900 33.2 24.8 56 259.5 2718.9 2550.1 2729.8 0.0 0.0
2000 31.7 24.8 58 259.5 2544.5 2411.2 2572.5 0.0 0.0
2100 30.4 24.6 59 259.5 2393.3 2333.3 2488.5 0.0 0.0
2200 29.3 24.7 61 259.5 2255.0 2140.7 2267.7 0.0 0.0
2300 28.4 24.6 62 259.5 2136.9 2106.4 2238.0 0.0 0.0

ZONE: Living Room + Office


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 63 351.1 2823.3 2753.2 2737.3 0.0 0.0
0100 27.2 24.5 63 351.1 2726.4 2734.8 2735.4 0.0 0.0
0200 26.6 24.6 65 351.1 2634.1 2545.4 2479.5 0.0 0.0
0300 26.2 24.5 65 351.1 2553.1 2531.5 2481.2 0.0 0.0
0400 25.8 24.7 67 351.1 2483.1 2353.6 2225.8 0.0 0.0
0500 25.7 24.6 67 351.1 2450.9 2353.3 2227.3 0.0 0.0
0600 25.9 24.5 66 351.1 2471.5 2474.7 2405.7 0.0 0.0
0700 26.5 24.6 66 351.1 2527.9 2455.8 2363.4 0.0 0.0
0800 27.5 24.5 64 351.1 2626.9 2622.4 2590.4 0.0 0.0
0900 29.0 24.6 63 351.1 2765.4 2695.4 2667.2 0.0 0.0
1000 30.7 24.6 62 351.1 2928.6 2865.1 2880.3 0.0 0.0
1100 32.6 24.7 61 351.1 3129.7 2952.1 2963.0 0.0 0.0
1200 34.4 24.6 57 351.1 3388.2 3305.3 3424.1 0.0 0.0
1300 35.8 24.7 55 351.1 3662.1 3531.9 3690.1 0.0 0.0
1400 36.7 24.9 54 351.1 3931.2 3657.4 3814.5 0.0 0.0
1500 37.0 24.7 50 351.1 4160.9 4015.6 4277.1 0.0 0.0
1600 36.7 24.8 50 351.1 4286.5 4069.0 4331.3 0.0 0.0
1700 35.9 24.8 50 351.1 4227.5 4056.5 4315.6 0.0 0.0
1800 34.6 24.7 52 351.1 3885.9 3790.8 4010.9 0.0 0.0
1900 33.2 24.7 55 351.1 3647.6 3511.3 3668.3 0.0 0.0
2000 31.7 24.7 57 351.1 3416.9 3278.5 3379.3 0.0 0.0
2100 30.4 24.6 58 351.1 3229.7 3193.7 3296.3 0.0 0.0
2200 29.3 24.7 61 351.1 3068.5 2926.7 2946.0 0.0 0.0
2300 28.4 24.6 61 351.1 2934.2 2875.1 2896.6 0.0 0.0

Hourly Analysis Program v4.80 Page 100 of 773


System Psychrometrics for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 55 400 738 186
Vent - Return Mixing Outlet 37.0 0.01203 55 0 - -
Vent. Cooling Coil Outlet 20.0 0.01203 55 400 1024 0
Ventilation Fan Outlet 20.0 0.01203 55 400 0 -
Cold Supply Duct Outlet 20.0 0.01203 55 400 0 -
Zone Air - 24.8 0.01076 55 1365 6945 465
Return Plenum Outlet 24.8 0.01076 55 1365 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Bedroom ( Cooling )
Ventilation Air - - - 16 - - -
Cooling Coil Inlet - 24.7 0.01097 260 0 - -
Cooling Coil Outlet - 14.6 0.01059 260 0 2894 263
Heating Coil Inlet - 14.6 0.01059 260 0 - -
Heating Coil Outlet - 14.6 0.01059 260 0 0 -
Zone Air - 24.8 0.01090 260 937 2929 -
Living Room + Office ( Cooling
)
Ventilation Air - - - 38 - - -
Cooling Coil Inlet - 24.4 0.01086 351 0 - -
Cooling Coil Outlet - 14.3 0.01045 351 0 3886 391
Heating Coil Inlet - 14.3 0.01045 351 0 - -
Heating Coil Outlet - 14.3 0.01045 351 0 0 -
Zone Air - 24.7 0.01071 351 1549 4016 -

Hourly Analysis Program v4.80 Page 101 of 773


Hourly Air System Design Day Loads for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Data for July

Total Cooling Total Heating

6
Load ( kW )

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 102 of 773


Hourly Zone Design Day Loads for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Zone: Bedroom
Data for July

Zone Sensible Zone Conditioning

3000

2500

2000
W

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: Living Room + Office


Data for July

Zone Sensible Zone Conditioning

4000

3500

3000

2500
W

2000

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 103 of 773


Psychrometric Analysis for FCU - Executive (26)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program v4.80 Page 104 of 773


Air System Sizing Summary for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Air System Information


Air System Name FCU - Executive (31) Number of zones 2
Equipment Class TERM Floor Area 82.5 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Cooling Coil Sizing Data


Total coil load 1.0 kW Load occurs at Jul 1500
Sensible coil load 1.0 kW OA DB / WB 37.0 / 22.0 °C
Coil L/s at Jul 1500 55 L/s Entering DB / WB 37.0 / 22.0 °C
Max coil L/s 55 L/s Leaving DB / WB 20.0 / 17.0 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
Water flow @ 5.5 °K rise 0.04 L/s

Ventilation Fan Sizing Data


Actual max L/s 55 L/s Fan motor BHP 0.00 BHP
Standard L/s 50 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 0.66 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 55 L/s L/s/person 4.56 L/s/person
L/(s-m²) 0.66 L/(s-m²)

Hourly Analysis Program v4.80 Page 105 of 773


Zone Sizing Summary for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

Air System Information


Air System Name FCU - Executive (31) Number of zones 2
Equipment Class TERM Floor Area 82.5 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Bedroom 3.5 286 286 Sep 1500 2.3 38.0 7.52
Living Room + Office 3.7 303 303 Jul 1300 2.3 44.5 6.81

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.5 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Bedroom 3.5 3.3 24.6 / 17.4 14.2 / 13.5 0.15 Sep 1600
Living Room + Office 3.9 3.5 24.3 / 17.3 14.0 / 13.3 0.17 Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.0 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Bedroom 2.6 19.5 / 27.7 0.06 286 0.072 0.057 16
Living Room + Office 3.0 18.0 / 27.1 0.07 303 0.076 0.061 38

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Bedroom
TYP.31 Executive - BD 1 3.5 Sep 1500 286 2.3 38.0 7.52
Living Room + Office
TYP.31 Executive - LR 1 3.4 Jul 1300 272 1.9 41.0 6.64
TYP.31 Executive - OFF 1 0.4 Jul 1600 31 0.3 3.5 8.84

Hourly Analysis Program v4.80 Page 106 of 773


Ventilation Sizing Summary for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:49PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 55 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Bedroom
TYP.31 Executive - BD 1 38.0 2.0 285.7 2.50 0.30 0.0 0.0 16.4
Living Room + Office
TYP.31 Executive - LR 1 41.0 9.0 272.2 2.50 0.30 0.0 0.0 34.8
TYP.31 Executive - OFF 1 3.5 1.0 30.9 2.50 0.30 0.0 0.0 3.6
Totals (incl. Space Multipliers) 588.8 54.8

Hourly Analysis Program v4.80 Page 107 of 773


Air System Design Load Summary for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 28 m² 1368 - 28 m² - -
Wall Transmission 58 m² 574 - 58 m² 464 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 28 m² 606 - 28 m² 1215 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 106 m² 1342 - 106 m² 2006 -
Ceiling 83 m² 331 - 83 m² 495 -
Overhead Lighting 1155 W 1155 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 638 42 10% 418 0
>> Total Zone Loads - 7023 465 - 4598 0
Zone Conditioning - 6742 465 - 4449 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 55 L/s 0 - 55 L/s 0 -
Ventilation Load 55 L/s 718 202 55 L/s 1287 0
Ventilation Fan Load 55 L/s 0 - 55 L/s 0 -
Space Fan Coil Fans - 118 - - -118 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 7577 667 - 5618 0
Cooling Coil - 1004 0 - 0 0
Terminal Unit Cooling - 6573 665 - 0 0
Terminal Unit Heating - 0 - - 5617 -
>> Total Conditioning - 7577 665 - 5617 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 108 of 773


Zone Design Load Summary for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

Bedroom DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1009 - 14 m² - -
Wall Transmission 22 m² 304 - 22 m² 175 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 275 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 57 m² 700 - 57 m² 1083 -
Ceiling 38 m² 147 - 38 m² 228 -
Overhead Lighting 532 W 532 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 320 7 10% 209 0
>> Total Zone Loads - 3522 77 - 2303 0

Living Room + Office DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 636 - 14 m² - -
Wall Transmission 36 m² 311 - 36 m² 289 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 275 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 49 m² 601 - 49 m² 923 -
Ceiling 45 m² 174 - 45 m² 267 -
Overhead Lighting 623 W 623 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 339 35 10% 209 0
>> Total Zone Loads - 3733 387 - 2295 0

Hourly Analysis Program v4.80 Page 109 of 773


Space Design Load Summary for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' TYP.31 Executive - BD '' IN ZONE '' Bedroom ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1009 - 14 m² - -
Wall Transmission 22 m² 304 - 22 m² 175 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 275 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 57 m² 700 - 57 m² 1083 -
Ceiling 38 m² 147 - 38 m² 228 -
Overhead Lighting 532 W 532 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 320 7 10% 209 0
>> Total Zone Loads - 3522 77 - 2303 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' TYP.31 Executive - BD '' IN ZONE '' Bedroom ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 16 0.365 - 243 - 123
WINDOW 1 7 1.990 0.300 137 627 304
SE EXPOSURE
WALL 7 0.365 - 61 - 52
WINDOW 1 7 1.990 0.300 137 382 304

Hourly Analysis Program v4.80 Page 110 of 773


Space Design Load Summary for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' TYP.31 Executive - LR '' IN ZONE '' Living Room + Office ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.8 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 636 - 14 m² - -
Wall Transmission 29 m² 254 - 29 m² 233 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 275 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 445 - 36 m² 684 -
Ceiling 41 m² 160 - 41 m² 246 -
Overhead Lighting 574 W 574 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 9 607 317 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 305 32 10% 177 0
>> Total Zone Loads - 3355 348 - 1948 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' TYP.31 Executive - LR '' IN ZONE '' Living Room + Office ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 22 0.365 - 176 - 171
WINDOW 1 7 1.990 0.300 137 307 304
SE EXPOSURE
WALL 8 0.365 - 77 - 62
WINDOW 1 7 1.990 0.300 137 329 304

Hourly Analysis Program v4.80 Page 111 of 773


Space Design Load Summary for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

TABLE 2.2.A. COMPONENT LOADS FOR SPACE '' TYP.31 Executive - OFF '' IN ZONE '' Living Room + Office ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 7 m² 56 - 7 m² 56 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 160 - 13 m² 239 -
Ceiling 4 m² 14 - 4 m² 21 -
Overhead Lighting 49 W 49 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 67 35 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 35 4 10% 32 0
>> Total Zone Loads - 381 39 - 348 0

TABLE 2.2.B. ENVELOPE LOADS FOR SPACE '' TYP.31 Executive - OFF '' IN ZONE '' Living Room + Office ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 7 0.365 - 56 - 56

Hourly Analysis Program v4.80 Page 112 of 773


Hourly Air System Design Day Loads for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

DESIGN MONTH: JULY


COMMON CENTRAL CENTRAL CENTRAL VENT VENT ZONE
OA VENT COOLING COOLING HEATING COOLING HEATING TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 55 0.0 0.0 0.0 0.5 0.0 4.7 0.0 0.0
0100 27.2 55 0.0 0.0 0.0 0.4 0.0 4.6 0.0 0.0
0200 26.6 55 0.0 0.0 0.0 0.4 0.0 4.5 0.0 0.0
0300 26.2 55 0.0 0.0 0.0 0.4 0.0 4.3 0.0 0.0
0400 25.8 55 0.0 0.0 0.0 0.4 0.0 4.0 0.0 0.0
0500 25.7 55 0.0 0.0 0.0 0.3 0.0 4.4 0.0 0.0
0600 25.9 55 0.0 0.0 0.0 0.4 0.0 4.7 0.0 0.0
0700 26.5 55 0.0 0.0 0.0 0.4 0.0 5.1 0.0 0.0
0800 27.5 55 0.0 0.0 0.0 0.5 0.0 5.8 0.0 0.0
0900 29.0 55 0.0 0.0 0.0 0.5 0.0 6.1 0.0 0.0
1000 30.7 55 0.0 0.0 0.0 0.6 0.0 6.2 0.0 0.0
1100 32.6 55 0.0 0.0 0.0 0.8 0.0 6.4 0.0 0.0
1200 34.4 55 0.0 0.0 0.0 0.9 0.0 6.6 0.0 0.0
1300 35.8 55 0.0 0.0 0.0 0.9 0.0 6.9 0.0 0.0
1400 36.7 55 0.0 0.0 0.0 1.0 0.0 7.0 0.0 0.0
1500 37.0 55 0.0 0.0 0.0 1.0 0.0 6.9 0.0 0.0
1600 36.7 55 0.0 0.0 0.0 1.0 0.0 7.1 0.0 0.0
1700 35.9 55 0.0 0.0 0.0 1.0 0.0 7.0 0.0 0.0
1800 34.6 55 0.0 0.0 0.0 0.9 0.0 6.6 0.0 0.0
1900 33.2 55 0.0 0.0 0.0 0.8 0.0 6.3 0.0 0.0
2000 31.7 55 0.0 0.0 0.0 0.7 0.0 5.7 0.0 0.0
2100 30.4 55 0.0 0.0 0.0 0.6 0.0 5.6 0.0 0.0
2200 29.3 55 0.0 0.0 0.0 0.6 0.0 5.1 0.0 0.0
2300 28.4 55 0.0 0.0 0.0 0.5 0.0 5.0 0.0 0.0

Hourly Analysis Program v4.80 Page 113 of 773


Hourly Zone Loads for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

ZONE: Bedroom
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 67 285.7 2056.4 1954.7 2040.6 0.0 0.0
0100 27.2 24.5 67 285.7 1967.7 1956.8 2044.9 0.0 0.0
0200 26.6 24.5 68 285.7 1881.7 1858.0 1935.5 0.0 0.0
0300 26.2 24.5 69 285.7 1806.3 1774.7 1843.3 0.0 0.0
0400 25.8 24.5 71 285.7 1741.6 1702.5 1761.3 0.0 0.0
0500 25.7 24.5 70 285.7 1761.1 1715.6 1769.7 0.0 0.0
0600 25.9 24.6 70 285.7 1888.5 1754.9 1814.3 0.0 0.0
0700 26.5 24.6 67 285.7 2033.2 1912.6 1990.1 0.0 0.0
0800 27.5 24.4 64 285.7 2194.7 2180.7 2310.2 0.0 0.0
0900 29.0 24.5 62 285.7 2361.0 2324.3 2468.8 0.0 0.0
1000 30.7 24.6 61 285.7 2510.9 2394.8 2541.4 0.0 0.0
1100 32.6 24.7 60 285.7 2662.0 2464.6 2611.3 0.0 0.0
1200 34.4 24.6 56 285.7 2863.5 2738.7 2924.9 0.0 0.0
1300 35.8 24.6 54 285.7 3042.5 2913.2 3121.2 0.0 0.0
1400 36.7 24.9 54 285.7 3160.3 2896.7 3090.9 0.0 0.0
1500 37.0 24.9 53 285.7 3234.9 2995.9 3199.1 0.0 0.0
1600 36.7 24.8 52 285.7 3240.8 3072.5 3291.6 0.0 0.0
1700 35.9 24.8 53 285.7 3156.9 2989.2 3199.6 0.0 0.0
1800 34.6 24.7 55 285.7 2956.5 2860.7 3058.4 0.0 0.0
1900 33.2 24.7 57 285.7 2766.4 2667.3 2842.8 0.0 0.0
2000 31.7 24.7 60 285.7 2579.7 2439.9 2587.0 0.0 0.0
2100 30.4 24.7 62 285.7 2421.1 2291.4 2414.7 0.0 0.0
2200 29.3 24.7 64 285.7 2278.2 2157.2 2269.3 0.0 0.0
2300 28.4 24.5 64 285.7 2157.0 2134.4 2253.2 0.0 0.0

ZONE: Living Room + Office


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 60 303.2 2686.9 2604.1 2627.8 0.0 0.0
0100 27.2 24.7 61 303.2 2601.4 2532.2 2538.7 0.0 0.0
0200 26.6 24.6 61 303.2 2518.6 2517.6 2535.0 0.0 0.0
0300 26.2 24.6 62 303.2 2446.0 2432.6 2425.5 0.0 0.0
0400 25.8 24.7 64 303.2 2383.4 2311.9 2258.9 0.0 0.0
0500 25.7 24.5 61 303.2 2515.8 2547.4 2583.7 0.0 0.0
0600 25.9 24.6 58 303.2 2826.5 2797.3 2892.5 0.0 0.0
0700 26.5 24.8 56 303.2 3107.4 2962.2 3078.4 0.0 0.0
0800 27.5 24.7 53 303.2 3335.0 3251.5 3450.6 0.0 0.0
0900 29.0 24.7 51 303.2 3481.7 3378.8 3605.9 0.0 0.0
1000 30.7 24.7 51 303.2 3557.9 3436.2 3672.8 0.0 0.0
1100 32.6 24.8 50 303.2 3626.8 3496.5 3745.6 0.0 0.0
1200 34.4 25.0 51 303.2 3693.7 3433.2 3642.0 0.0 0.0
1300 35.8 24.9 50 303.2 3733.0 3557.2 3808.1 0.0 0.0
1400 36.7 24.8 49 303.2 3731.2 3607.6 3880.2 0.0 0.0
1500 37.0 25.0 50 303.2 3717.8 3469.5 3686.7 0.0 0.0
1600 36.7 24.8 50 303.2 3680.6 3520.7 3763.7 0.0 0.0
1700 35.9 24.8 50 303.2 3615.6 3503.3 3751.4 0.0 0.0
1800 34.6 24.8 52 303.2 3491.4 3346.5 3551.8 0.0 0.0
1900 33.2 24.7 53 303.2 3332.6 3256.5 3452.9 0.0 0.0
2000 31.7 24.8 55 303.2 3172.5 3025.6 3151.9 0.0 0.0
2100 30.4 24.6 55 303.2 3030.3 3010.4 3157.2 0.0 0.0
2200 29.3 24.8 58 303.2 2897.9 2757.0 2816.3 0.0 0.0
2300 28.4 24.8 59 303.2 2783.3 2667.3 2705.3 0.0 0.0

Hourly Analysis Program v4.80 Page 114 of 773


System Psychrometrics for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 55 400 727 139
Vent - Return Mixing Outlet 37.0 0.01203 55 0 - -
Vent. Cooling Coil Outlet 20.0 0.01203 55 400 1024 0
Ventilation Fan Outlet 20.0 0.01203 55 400 0 -
Cold Supply Duct Outlet 20.0 0.01203 55 400 0 -
Zone Air - 24.9 0.01109 55 1365 6465 465
Return Plenum Outlet 24.9 0.01109 55 1365 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Bedroom ( Cooling )
Ventilation Air - - - 16 - - -
Cooling Coil Inlet - 24.8 0.01151 286 0 - -
Cooling Coil Outlet - 15.4 0.01121 286 0 2965 234
Heating Coil Inlet - 15.4 0.01121 286 0 - -
Heating Coil Outlet - 15.4 0.01121 286 0 0 -
Zone Air - 24.9 0.01148 286 937 2996 -
Living Room + Office ( Cooling
)
Ventilation Air - - - 38 - - -
Cooling Coil Inlet - 24.5 0.01106 303 0 - -
Cooling Coil Outlet - 14.6 0.01062 303 0 3321 366
Heating Coil Inlet - 14.6 0.01062 303 0 - -
Heating Coil Outlet - 14.6 0.01062 303 0 0 -
Zone Air - 25.0 0.01092 303 1549 3469 -

Hourly Analysis Program v4.80 Page 115 of 773


Hourly Air System Design Day Loads for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

Data for July

Total Cooling Total Heating


8

6
Load ( kW )

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 116 of 773


Hourly Zone Design Day Loads for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

Zone: Bedroom
Data for July

Zone Sensible Zone Conditioning

3000

2500

2000
W

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: Living Room + Office


Data for July

Zone Sensible Zone Conditioning

3500

3000

2500

2000
W

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 117 of 773


Psychrometric Analysis for FCU - Executive (31)
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program v4.80 Page 118 of 773


Air System Sizing Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

Air System Information


Air System Name FCU - F2 - Administrative Areas Number of zones 20
Equipment Class TERM Floor Area 392.0 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Heating Coil Sizing Data


Max coil load 11.9 kW Load occurs at Des Htg
Coil L/s at Des Htg 302 L/s Ent. DB / Lvg DB -0.8 / 35.0 °C
Max coil L/s 302 L/s
Water flow @ 11.0 °K drop 0.26 L/s

Ventilation Fan Sizing Data


Actual max L/s 302 L/s Fan motor BHP 0.00 BHP
Standard L/s 275 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 0.77 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 302 L/s L/s/person 3.36 L/s/person
L/(s-m²) 0.77 L/(s-m²)

Hourly Analysis Program v4.80 Page 119 of 773


Zone Sizing Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

Air System Information


Air System Name FCU - F2 - Administrative Areas Number of zones 20
Equipment Class TERM Floor Area 392.0 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
F1-11 Admin Support 7.9 643 643 Jul 1700 1.4 129.0 4.99
F1-09 EAM Room 1.1 88 88 Jul 1600 0.4 12.0 7.34
F1-51 Director of F&B 1.2 96 96 Jun 1400 0.5 10.0 9.59
F1-06 DIR of Revenue 1.3 105 105 Sep 1100 0.5 11.0 9.50
F1-05 DIR of Public Rel 1.3 105 105 Sep 1100 0.5 11.0 9.50
F1-04 DIR Cater & Confe 1.2 100 100 Sep 1100 0.5 9.0 11.10
F1-14 Chief Accountant 1.0 80 80 Jul 1700 0.3 11.0 7.26
F1-12 Director of M&S 1.2 97 97 Jun 1400 0.5 10.0 9.68
F1-20 Cashier 0.8 64 64 Jul 1700 0.4 7.0 9.19
F18- DIR of Finance 1.3 102 102 Jun 1400 0.6 9.0 11.36
F1-15 Assitant Control 1.0 82 82 Jul 1700 0.4 11.0 7.48
F1-13 Reception Area 1.5 122 122 Jul 1700 0.3 22.0 5.56
F1-08 General Manager 2.2 179 179 Sep 1100 0.8 20.0 8.97
F1-10 Quality Manager 1.1 88 88 Jul 1600 0.4 12.0 7.31
F1-03 Call Center 2.0 164 164 Sep 1600 0.3 10.0 16.37
F1-01 Reservation Mngr 1.3 104 104 Sep 1500 0.5 7.0 14.86
F1-02 Reservation 0.8 64 64 Sep 1600 0.3 9.0 7.13
F1-21 Counting Room 0.4 31 31 Jul 1700 0.3 4.0 7.63
F1-16 Chief Accountant 5.9 481 481 Jun 1400 1.3 52.0 9.26
F1-07 Meeting Room 3.5 282 282 Sep 1100 0.8 26.0 10.85

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 6.7 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
F1-11 Admin Support 11.1 8.9 26.1 / 18.2 13.6 / 12.8 0.40 Jun 1600
F1-09 EAM Room 1.4 1.2 26.2 / 18.1 13.7 / 13.0 0.05 Aug 1600
F1-51 Director of F&B 1.5 1.3 26.1 / 18.0 13.9 / 13.1 0.05 Jun 1400
F1-06 DIR of Revenue 1.6 1.4 25.8 / 17.8 13.7 / 13.0 0.06 Sep 1400
F1-05 DIR of Public Rel 1.6 1.4 26.0 / 18.0 14.1 / 13.3 0.06 Aug 1400
F1-04 DIR Cater & Confe 1.5 1.3 25.8 / 17.7 13.7 / 12.9 0.05 Sep 1200
F1-14 Chief Accountant 1.3 1.1 26.2 / 18.0 13.6 / 12.9 0.05 Jul 1700
F1-12 Director of M&S 1.5 1.3 25.8 / 17.8 13.6 / 12.9 0.05 Jun 1300
F1-20 Cashier 0.9 0.8 25.7 / 18.0 14.2 / 13.5 0.03 Aug 1600
F18- DIR of Finance 1.5 1.4 26.0 / 17.9 14.0 / 13.2 0.05 Jul 1500
F1-15 Assitant Control 1.3 1.1 26.2 / 18.1 13.8 / 13.1 0.05 Jun 1700
F1-13 Reception Area 2.2 1.8 27.0 / 18.5 13.6 / 12.9 0.08 Jun 1600
F1-08 General Manager 2.9 2.5 26.3 / 18.1 13.9 / 13.1 0.10 Aug 1500
F1-10 Quality Manager 1.4 1.2 26.2 / 18.1 13.8 / 13.0 0.05 Jun 1400
F1-03 Call Center 2.3 2.1 26.1 / 17.9 14.3 / 13.5 0.08 Aug 1600
F1-01 Reservation Mngr 1.5 1.4 25.9 / 17.8 14.0 / 13.2 0.05 Sep 1500
F1-02 Reservation 1.0 0.9 26.5 / 18.2 13.9 / 13.1 0.04 Sep 1600
F1-21 Counting Room 0.5 0.4 26.2 / 18.3 14.3 / 13.5 0.02 Jul 1600
F1-16 Chief Accountant 6.7 5.9 24.8 / 17.4 13.7 / 13.0 0.24 Jul 1500
F1-07 Meeting Room 4.3 3.7 26.3 / 18.1 14.2 / 13.5 0.15 Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Hourly Analysis Program v4.80 Page 120 of 773


Zone Sizing Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.0 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
F1-11 Admin Support 0.2 22.6 / 22.9 0.00 643 0.000 0.000 74
F1-09 EAM Room 0.3 22.7 / 25.3 0.01 88 0.000 0.000 11
F1-51 Director of F&B 0.3 22.4 / 25.4 0.01 96 0.000 0.000 11
F1-06 DIR of Revenue 0.3 22.3 / 25.3 0.01 105 0.000 0.000 11
F1-05 DIR of Public Rel 0.4 22.4 / 25.6 0.01 105 0.000 0.000 11
F1-04 DIR Cater & Confe 0.3 22.2 / 25.0 0.01 100 0.000 0.000 10
F1-14 Chief Accountant 0.2 22.8 / 24.7 0.00 80 0.000 0.000 11
F1-12 Director of M&S 0.3 22.4 / 25.4 0.01 97 0.000 0.000 11
F1-20 Cashier 0.3 21.7 / 26.5 0.01 64 0.000 0.000 5
F18- DIR of Finance 0.5 22.2 / 26.4 0.01 102 0.000 0.000 10
F1-15 Assitant Control 0.2 22.7 / 25.1 0.00 82 0.000 0.000 11
F1-13 Reception Area 0.0 -17.8 / -17.8 0.00 122 0.000 0.000 24
F1-08 General Manager 0.5 22.8 / 25.2 0.01 179 0.000 0.000 24
F1-10 Quality Manager 0.2 22.7 / 25.2 0.01 88 0.000 0.000 11
F1-03 Call Center 0.1 22.1 / 22.9 0.00 164 0.000 0.000 13
F1-01 Reservation Mngr 0.4 22.3 / 25.6 0.01 104 0.000 0.000 10
F1-02 Reservation 0.2 23.1 / 25.5 0.00 64 0.000 0.000 10
F1-21 Counting Room 0.2 22.2 / 29.3 0.01 31 0.000 0.000 4
F1-16 Chief Accountant 1.3 21.0 / 23.4 0.03 481 0.000 0.000 0
F1-07 Meeting Room 0.3 22.6 / 23.5 0.01 282 0.000 0.000 33

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
F1-11 Admin Support
F1-11 Admin Support 1 7.9 Jul 1700 643 1.4 129.0 4.99
F1-09 EAM Room
F1-09 EAM Room 1 1.1 Jul 1600 88 0.4 12.0 7.34
F1-51 Director of F&B
F1-51 Drc of FB 1 1.2 Jun 1400 96 0.5 10.0 9.59
F1-06 DIR of Revenue
F1-06 Drc of Revenue 1 1.3 Sep 1100 105 0.5 11.0 9.50
F1-05 DIR of Public Rel
F1-05 Drc of Public Rel 1 1.3 Sep 1100 105 0.5 11.0 9.50
F1-04 DIR Cater & Confe
F1-04 Drc of Catr/Conf 1 1.2 Sep 1100 100 0.5 9.0 11.10
F1-14 Chief Accountant
F1-14 Chief Account 1 1.0 Jul 1700 80 0.3 11.0 7.26
F1-12 Director of M&S
F1-12 Drc of M&S 1 1.2 Jun 1400 97 0.5 10.0 9.68
F1-20 Cashier
F1-20 Cashier 1 0.8 Jul 1700 64 0.4 7.0 9.19
F18- DIR of Finance
F1-18 Director of Fin 1 1.3 Jun 1400 102 0.6 9.0 11.36
F1-15 Assitant Control
F1-15 Assistance Cn 1 1.0 Jul 1700 82 0.4 11.0 7.48
F1-13 Reception Area
F1-13 Reception Area 1 1.5 Jul 1700 122 0.3 22.0 5.56
F1-08 General Manager
F1-08 General Manager 1 2.2 Sep 1100 179 0.8 20.0 8.97
F1-10 Quality Manager
F1-10 Quality Manager 1 1.1 Jul 1600 88 0.4 12.0 7.31
F1-03 Call Center
F1-03 Call Center 1 2.0 Sep 1600 164 0.3 10.0 16.37
F1-01 Reservation Mngr
F1-01 Reserv Manager 1 1.3 Sep 1500 104 0.5 7.0 14.86
F1-02 Reservation
F1-02 Reservation 1 0.8 Sep 1600 64 0.3 9.0 7.13

Hourly Analysis Program v4.80 Page 121 of 773


Zone Sizing Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
F1-21 Counting Room
F1-21 Counting Room 1 0.4 Jul 1700 31 0.3 4.0 7.63
F1-16 Chief Accountant
F1-16 Accountant Support 1 5.9 Jun 1400 481 1.3 52.0 9.26
F1-07 Meeting Room
F1-07 Meeting Room 1 3.5 Sep 1100 282 0.8 26.0 10.85

Hourly Analysis Program v4.80 Page 122 of 773


Ventilation Sizing Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 302 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
F1-11 Admin Support
F1-11 Admin Support 1 129.0 14.0 643.4 2.50 0.30 0.0 0.0 73.7
F1-09 EAM Room
F1-09 EAM Room 1 12.0 3.0 88.1 2.50 0.30 0.0 0.0 11.1
F1-51 Director of F&B
F1-51 Drc of FB 1 10.0 3.0 95.9 2.50 0.30 0.0 0.0 10.5
F1-06 DIR of Revenue
F1-06 Drc of Revenue 1 11.0 3.0 104.5 2.50 0.30 0.0 0.0 10.8
F1-05 DIR of Public Rel
F1-05 Drc of Public Rel 1 11.0 3.0 104.5 2.50 0.30 0.0 0.0 10.8
F1-04 DIR Cater & Confe
F1-04 Drc of Catr/Conf 1 9.0 3.0 99.9 2.50 0.30 0.0 0.0 10.2
F1-14 Chief Accountant
F1-14 Chief Account 1 11.0 3.0 79.9 2.50 0.30 0.0 0.0 10.8
F1-12 Director of M&S
F1-12 Drc of M&S 1 10.0 3.0 96.8 2.50 0.30 0.0 0.0 10.5
F1-20 Cashier
F1-20 Cashier 1 7.0 1.0 64.3 2.50 0.30 0.0 0.0 4.6
F18- DIR of Finance
F1-18 Director of Fin 1 9.0 3.0 102.2 2.50 0.30 0.0 0.0 10.2
F1-15 Assitant Control
F1-15 Assistance Cn 1 11.0 3.0 82.3 2.50 0.30 0.0 0.0 10.8
F1-13 Reception Area
F1-13 Reception Area 1 22.0 7.0 122.4 2.50 0.30 0.0 0.0 24.1
F1-08 General Manager
F1-08 General Manager 1 20.0 7.0 179.5 2.50 0.30 0.0 0.0 23.5
F1-10 Quality Manager
F1-10 Quality Manager 1 12.0 3.0 87.7 2.50 0.30 0.0 0.0 11.1
F1-03 Call Center
F1-03 Call Center 1 10.0 4.0 163.7 2.50 0.30 0.0 0.0 13.0
F1-01 Reservation Mngr
F1-01 Reserv Manager 1 7.0 3.0 104.0 2.50 0.30 0.0 0.0 9.6
F1-02 Reservation
F1-02 Reservation 1 9.0 3.0 64.2 2.50 0.30 0.0 0.0 10.2
F1-21 Counting Room

Hourly Analysis Program v4.80 Page 123 of 773


Ventilation Sizing Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-21 Counting Room 1 4.0 1.0 30.5 2.50 0.30 0.0 0.0 3.7
F1-16 Chief Accountant
F1-16 Accountant Support 1 52.0 10.0 481.4 0.00 0.00 0.0 0.0 0.0
F1-07 Meeting Room
F1-07 Meeting Room 1 26.0 10.0 282.1 2.50 0.30 0.0 0.0 32.8
Totals (incl. Space Multipliers) 3077.2 302.0

Hourly Analysis Program v4.80 Page 124 of 773


Air System Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.0 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 42 m² 1759 - 42 m² - -
Wall Transmission 145 m² 1381 - 145 m² 1159 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 42 m² 917 - 42 m² 1830 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 255 m² 3211 - 255 m² 4890 -
Ceiling 388 m² 1544 - 388 m² 2351 -
Overhead Lighting 7840 W 7840 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10800 W 10800 - 0 0 -
People 90 6462 5409 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3391 541 10% 1023 0
>> Total Zone Loads - 37303 5950 - 11254 0
Zone Conditioning - 36434 5950 - 11166 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 302 L/s 0 - 302 L/s 0 -
Ventilation Load 302 L/s 4030 887 302 L/s 7221 0
Ventilation Fan Load 302 L/s 0 - 302 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 40464 6837 - 18388 0
Heating Coil - 0 - - 11899 -
Terminal Unit Cooling - 40464 6839 - -70 0
Terminal Unit Heating - 0 - - 6564 -
>> Total Conditioning - 40464 6839 - 18393 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 125 of 773


Zone Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-11 Admin Support DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 25 m² 315 - 25 m² 472 -
Ceiling 126 m² 510 - 126 m² 764 -
Overhead Lighting 2580 W 2580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2800 W 2800 - 0 0 -
People 14 1005 841 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 721 84 10% 124 0
>> Total Zone Loads - 7931 926 - 1359 0

F1-09 EAM Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 9 m² 72 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 161 - 13 m² 244 -
Ceiling 12 m² 48 - 12 m² 73 -
Overhead Lighting 240 W 240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 99 18 10% 39 0
>> Total Zone Loads - 1086 198 - 427 0

Hourly Analysis Program v4.80 Page 126 of 773


Zone Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-51 Director of F&B DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 135 - 3 m² - -
Wall Transmission 5 m² 40 - 5 m² 40 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 60 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 136 - 11 m² 211 -
Ceiling 10 m² 39 - 10 m² 61 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 107 18 10% 44 0
>> Total Zone Loads - 1182 198 - 487 0

F1-06 DIR of Revenue DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.5 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 232 - 3 m² - -
Wall Transmission 5 m² 72 - 5 m² 42 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 38 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 12 m² 112 - 12 m² 236 -
Ceiling 11 m² 32 - 11 m² 67 -
Overhead Lighting 220 W 220 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 117 18 10% 48 0
>> Total Zone Loads - 1288 198 - 523 0

Hourly Analysis Program v4.80 Page 127 of 773


Zone Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-05 DIR of Public Rel DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.5 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 232 - 3 m² - -
Wall Transmission 5 m² 69 - 5 m² 40 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 38 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 114 - 13 m² 242 -
Ceiling 11 m² 32 - 11 m² 67 -
Overhead Lighting 220 W 220 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 117 18 10% 48 0
>> Total Zone Loads - 1288 198 - 527 0

F1-04 DIR Cater & Confe DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.5 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 232 - 3 m² - -
Wall Transmission 6 m² 80 - 6 m² 46 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 38 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 97 - 11 m² 205 -
Ceiling 9 m² 26 - 9 m² 55 -
Overhead Lighting 180 W 180 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 112 18 10% 44 0
>> Total Zone Loads - 1231 198 - 481 0

Hourly Analysis Program v4.80 Page 128 of 773


Zone Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-14 Chief Accountant DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 165 - 13 m² 248 -
Ceiling 11 m² 44 - 11 m² 67 -
Overhead Lighting 220 W 220 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 90 18 10% 31 0
>> Total Zone Loads - 985 198 - 346 0

F1-12 Director of M&S DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 135 - 3 m² - -
Wall Transmission 6 m² 48 - 6 m² 48 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 60 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 137 - 11 m² 213 -
Ceiling 10 m² 39 - 10 m² 61 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 108 18 10% 45 0
>> Total Zone Loads - 1193 198 - 498 0

Hourly Analysis Program v4.80 Page 129 of 773


Zone Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-20 Cashier DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 231 - 18 m² 345 -
Ceiling 7 m² 28 - 7 m² 42 -
Overhead Lighting 140 W 140 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 72 6 10% 39 0
>> Total Zone Loads - 793 66 - 427 0

F18- DIR of Finance DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 135 - 3 m² - -
Wall Transmission 6 m² 48 - 6 m² 48 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 60 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 222 - 18 m² 345 -
Ceiling 9 m² 35 - 9 m² 55 -
Overhead Lighting 180 W 180 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 115 18 10% 58 0
>> Total Zone Loads - 1260 198 - 637 0

Hourly Analysis Program v4.80 Page 130 of 773


Zone Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-15 Assitant Control DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 192 - 15 m² 288 -
Ceiling 11 m² 44 - 11 m² 67 -
Overhead Lighting 220 W 220 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 92 18 10% 35 0
>> Total Zone Loads - 1014 198 - 390 0

F1-13 Reception Area DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 7 m² 90 - 7 m² 134 -
Ceiling 22 m² 89 - 22 m² 133 -
Overhead Lighting 440 W 440 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 7 503 421 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 137 42 10% 27 0
>> Total Zone Loads - 1508 463 - 294 0

Hourly Analysis Program v4.80 Page 131 of 773


Zone Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-08 General Manager DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.5 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 465 - 6 m² - -
Wall Transmission 21 m² 159 - 21 m² 169 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 6 m² 77 - 6 m² 261 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 100 - 11 m² 211 -
Ceiling 20 m² 57 - 20 m² 121 -
Overhead Lighting 400 W 400 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 7 503 421 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 201 42 10% 76 0
>> Total Zone Loads - 2212 463 - 839 0

F1-10 Quality Manager DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 9 m² 72 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 161 - 13 m² 244 -
Ceiling 11 m² 44 - 11 m² 67 -
Overhead Lighting 240 W 240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 98 18 10% 38 0
>> Total Zone Loads - 1081 198 - 421 0

Hourly Analysis Program v4.80 Page 132 of 773


Zone Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-03 Call Center DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 13 m² 212 - 13 m² 102 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 96 - 8 m² 148 -
Ceiling 10 m² 39 - 10 m² 61 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 183 24 10% 31 0
>> Total Zone Loads - 2018 264 - 342 0

F1-01 Reservation Mngr DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 164 - 3 m² - -
Wall Transmission 14 m² 193 - 14 m² 114 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 59 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 118 - 10 m² 184 -
Ceiling 7 m² 27 - 7 m² 42 -
Overhead Lighting 140 W 140 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 117 18 10% 47 0
>> Total Zone Loads - 1282 198 - 518 0

Hourly Analysis Program v4.80 Page 133 of 773


Zone Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-02 Reservation DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 12 m² 194 - 12 m² 94 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 94 - 8 m² 146 -
Ceiling 9 m² 35 - 9 m² 55 -
Overhead Lighting 180 W 180 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 72 18 10% 29 0
>> Total Zone Loads - 791 198 - 323 0

F1-21 Counting Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 14 m² 174 - 14 m² 261 -
Ceiling 4 m² 16 - 4 m² 24 -
Overhead Lighting 80 W 80 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 34 6 10% 29 0
>> Total Zone Loads - 376 66 - 314 0

Hourly Analysis Program v4.80 Page 134 of 773


Zone Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:50PM

F1-16 Chief Accountant DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 405 - 9 m² - -
Wall Transmission 19 m² 152 - 19 m² 152 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 180 - 9 m² 392 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 197 - 16 m² 307 -
Ceiling 52 m² 202 - 52 m² 315 -
Overhead Lighting 1040 W 1040 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2500 W 2500 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 539 60 10% 117 0
>> Total Zone Loads - 5934 661 - 1283 0

F1-07 Meeting Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.5 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 465 - 6 m² - -
Wall Transmission 15 m² 210 - 15 m² 122 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 6 m² 77 - 6 m² 261 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 97 - 11 m² 205 -
Ceiling 26 m² 75 - 26 m² 158 -
Overhead Lighting 520 W 520 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 316 60 10% 75 0
>> Total Zone Loads - 3477 661 - 820 0

Hourly Analysis Program v4.80 Page 135 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' F1-11 Admin Support '' IN ZONE '' F1-11 Admin Support ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 25 m² 315 - 25 m² 472 -
Ceiling 126 m² 510 - 126 m² 764 -
Overhead Lighting 2580 W 2580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2800 W 2800 - 0 0 -
People 14 1005 841 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 721 84 10% 124 0
>> Total Zone Loads - 7931 926 - 1359 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' F1-11 Admin Support '' IN ZONE '' F1-11 Admin Support ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 136 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' F1-09 EAM Room '' IN ZONE '' F1-09 EAM Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 9 m² 72 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 161 - 13 m² 244 -
Ceiling 12 m² 48 - 12 m² 73 -
Overhead Lighting 240 W 240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 99 18 10% 39 0
>> Total Zone Loads - 1086 198 - 427 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' F1-09 EAM Room '' IN ZONE '' F1-09 EAM Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 9 0.365 - 72 - 72

Hourly Analysis Program v4.80 Page 137 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' F1-51 Drc of FB '' IN ZONE '' F1-51 Director of F&B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 135 - 3 m² - -
Wall Transmission 5 m² 40 - 5 m² 40 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 60 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 136 - 11 m² 211 -
Ceiling 10 m² 39 - 10 m² 61 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 107 18 10% 44 0
>> Total Zone Loads - 1182 198 - 487 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' F1-51 Drc of FB '' IN ZONE '' F1-51 Director of F&B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 5 0.365 - 40 - 40
WINDOW 1 3 1.990 0.300 60 135 131

Hourly Analysis Program v4.80 Page 138 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' F1-06 Drc of Revenue '' IN ZONE '' F1-06 DIR of Revenue ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.5 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 232 - 3 m² - -
Wall Transmission 5 m² 72 - 5 m² 42 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 38 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 12 m² 112 - 12 m² 236 -
Ceiling 11 m² 32 - 11 m² 67 -
Overhead Lighting 220 W 220 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 117 18 10% 48 0
>> Total Zone Loads - 1288 198 - 523 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' F1-06 Drc of Revenue '' IN ZONE '' F1-06 DIR of Revenue ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 5 0.365 - 72 - 42
WINDOW 1 3 1.990 0.300 38 232 131

Hourly Analysis Program v4.80 Page 139 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' F1-05 Drc of Public Rel '' IN ZONE '' F1-05 DIR of Public Rel ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.5 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 232 - 3 m² - -
Wall Transmission 5 m² 69 - 5 m² 40 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 38 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 114 - 13 m² 242 -
Ceiling 11 m² 32 - 11 m² 67 -
Overhead Lighting 220 W 220 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 117 18 10% 48 0
>> Total Zone Loads - 1288 198 - 527 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' F1-05 Drc of Public Rel '' IN ZONE '' F1-05 DIR of Public Rel ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 5 0.365 - 69 - 40
WINDOW 1 3 1.990 0.300 38 232 131

Hourly Analysis Program v4.80 Page 140 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' F1-04 Drc of Catr/Conf '' IN ZONE '' F1-04 DIR Cater & Confe ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.5 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 232 - 3 m² - -
Wall Transmission 6 m² 80 - 6 m² 46 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 38 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 97 - 11 m² 205 -
Ceiling 9 m² 26 - 9 m² 55 -
Overhead Lighting 180 W 180 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 112 18 10% 44 0
>> Total Zone Loads - 1231 198 - 481 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' F1-04 Drc of Catr/Conf '' IN ZONE '' F1-04 DIR Cater & Confe ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 0.365 - 80 - 46
WINDOW 1 3 1.990 0.300 38 232 131

Hourly Analysis Program v4.80 Page 141 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' F1-14 Chief Account '' IN ZONE '' F1-14 Chief Accountant ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 165 - 13 m² 248 -
Ceiling 11 m² 44 - 11 m² 67 -
Overhead Lighting 220 W 220 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 90 18 10% 31 0
>> Total Zone Loads - 985 198 - 346 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' F1-14 Chief Account '' IN ZONE '' F1-14 Chief Accountant ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 142 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' F1-12 Drc of M&S '' IN ZONE '' F1-12 Director of M&S ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 135 - 3 m² - -
Wall Transmission 6 m² 48 - 6 m² 48 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 60 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 137 - 11 m² 213 -
Ceiling 10 m² 39 - 10 m² 61 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 108 18 10% 45 0
>> Total Zone Loads - 1193 198 - 498 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' F1-12 Drc of M&S '' IN ZONE '' F1-12 Director of M&S ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 6 0.365 - 48 - 48
WINDOW 1 3 1.990 0.300 60 135 131

Hourly Analysis Program v4.80 Page 143 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' F1-20 Cashier '' IN ZONE '' F1-20 Cashier ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 231 - 18 m² 345 -
Ceiling 7 m² 28 - 7 m² 42 -
Overhead Lighting 140 W 140 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 72 6 10% 39 0
>> Total Zone Loads - 793 66 - 427 0

TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' F1-20 Cashier '' IN ZONE '' F1-20 Cashier ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 144 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 10.1.A. COMPONENT LOADS FOR SPACE '' F1-18 Director of Fin '' IN ZONE '' F18- DIR of Finance ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 135 - 3 m² - -
Wall Transmission 6 m² 48 - 6 m² 48 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 60 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 18 m² 222 - 18 m² 345 -
Ceiling 9 m² 35 - 9 m² 55 -
Overhead Lighting 180 W 180 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 115 18 10% 58 0
>> Total Zone Loads - 1260 198 - 637 0

TABLE 10.1.B. ENVELOPE LOADS FOR SPACE '' F1-18 Director of Fin '' IN ZONE '' F18- DIR of Finance ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 6 0.365 - 48 - 48
WINDOW 1 3 1.990 0.300 60 135 131

Hourly Analysis Program v4.80 Page 145 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 11.1.A. COMPONENT LOADS FOR SPACE '' F1-15 Assistance Cn '' IN ZONE '' F1-15 Assitant Control ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 192 - 15 m² 288 -
Ceiling 11 m² 44 - 11 m² 67 -
Overhead Lighting 220 W 220 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 92 18 10% 35 0
>> Total Zone Loads - 1014 198 - 390 0

TABLE 11.1.B. ENVELOPE LOADS FOR SPACE '' F1-15 Assistance Cn '' IN ZONE '' F1-15 Assitant Control ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 146 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 12.1.A. COMPONENT LOADS FOR SPACE '' F1-13 Reception Area '' IN ZONE '' F1-13 Reception Area ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 7 m² 90 - 7 m² 134 -
Ceiling 22 m² 89 - 22 m² 133 -
Overhead Lighting 440 W 440 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 7 503 421 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 137 42 10% 27 0
>> Total Zone Loads - 1508 463 - 294 0

TABLE 12.1.B. ENVELOPE LOADS FOR SPACE '' F1-13 Reception Area '' IN ZONE '' F1-13 Reception Area ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 147 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 13.1.A. COMPONENT LOADS FOR SPACE '' F1-08 General Manager '' IN ZONE '' F1-08 General Manager ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.5 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 465 - 6 m² - -
Wall Transmission 21 m² 159 - 21 m² 169 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 6 m² 77 - 6 m² 261 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 100 - 11 m² 211 -
Ceiling 20 m² 57 - 20 m² 121 -
Overhead Lighting 400 W 400 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 7 503 421 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 201 42 10% 76 0
>> Total Zone Loads - 2212 463 - 839 0

TABLE 13.1.B. ENVELOPE LOADS FOR SPACE '' F1-08 General Manager '' IN ZONE '' F1-08 General Manager ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 16 0.365 - 86 - 126
SE EXPOSURE
WALL 5 0.365 - 73 - 42
WINDOW 1 6 1.990 0.300 77 465 261

Hourly Analysis Program v4.80 Page 148 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 14.1.A. COMPONENT LOADS FOR SPACE '' F1-10 Quality Manager '' IN ZONE '' F1-10 Quality Manager ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 9 m² 72 - 9 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 13 m² 161 - 13 m² 244 -
Ceiling 11 m² 44 - 11 m² 67 -
Overhead Lighting 240 W 240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 98 18 10% 38 0
>> Total Zone Loads - 1081 198 - 421 0

TABLE 14.1.B. ENVELOPE LOADS FOR SPACE '' F1-10 Quality Manager '' IN ZONE '' F1-10 Quality Manager ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 9 0.365 - 72 - 72

Hourly Analysis Program v4.80 Page 149 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 15.1.A. COMPONENT LOADS FOR SPACE '' F1-03 Call Center '' IN ZONE '' F1-03 Call Center ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 13 m² 212 - 13 m² 102 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 96 - 8 m² 148 -
Ceiling 10 m² 39 - 10 m² 61 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 4 287 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 183 24 10% 31 0
>> Total Zone Loads - 2018 264 - 342 0

TABLE 15.1.B. ENVELOPE LOADS FOR SPACE '' F1-03 Call Center '' IN ZONE '' F1-03 Call Center ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 13 0.365 - 212 - 102

Hourly Analysis Program v4.80 Page 150 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 16.1.A. COMPONENT LOADS FOR SPACE '' F1-01 Reserv Manager '' IN ZONE '' F1-01 Reservation Mngr ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 164 - 3 m² - -
Wall Transmission 14 m² 193 - 14 m² 114 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 59 - 3 m² 131 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 10 m² 118 - 10 m² 184 -
Ceiling 7 m² 27 - 7 m² 42 -
Overhead Lighting 140 W 140 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 117 18 10% 47 0
>> Total Zone Loads - 1282 198 - 518 0

TABLE 16.1.B. ENVELOPE LOADS FOR SPACE '' F1-01 Reserv Manager '' IN ZONE '' F1-01 Reservation Mngr ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 5 0.365 - 44 - 38
WINDOW 1 3 1.990 0.300 59 164 131
SW EXPOSURE
WALL 10 0.365 - 149 - 76

Hourly Analysis Program v4.80 Page 151 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 17.1.A. COMPONENT LOADS FOR SPACE '' F1-02 Reservation '' IN ZONE '' F1-02 Reservation ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.5 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 12 m² 194 - 12 m² 94 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 94 - 8 m² 146 -
Ceiling 9 m² 35 - 9 m² 55 -
Overhead Lighting 180 W 180 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 72 18 10% 29 0
>> Total Zone Loads - 791 198 - 323 0

TABLE 17.1.B. ENVELOPE LOADS FOR SPACE '' F1-02 Reservation '' IN ZONE '' F1-02 Reservation ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 12 0.365 - 194 - 94

Hourly Analysis Program v4.80 Page 152 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 18.1.A. COMPONENT LOADS FOR SPACE '' F1-21 Counting Room '' IN ZONE '' F1-21 Counting Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 14 m² 174 - 14 m² 261 -
Ceiling 4 m² 16 - 4 m² 24 -
Overhead Lighting 80 W 80 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 34 6 10% 29 0
>> Total Zone Loads - 376 66 - 314 0

TABLE 18.1.B. ENVELOPE LOADS FOR SPACE '' F1-21 Counting Room '' IN ZONE '' F1-21 Counting Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 153 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 19.1.A. COMPONENT LOADS FOR SPACE '' F1-16 Accountant Support '' IN ZONE '' F1-16 Chief Accountant ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 405 - 9 m² - -
Wall Transmission 19 m² 152 - 19 m² 152 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 180 - 9 m² 392 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 16 m² 197 - 16 m² 307 -
Ceiling 52 m² 202 - 52 m² 315 -
Overhead Lighting 1040 W 1040 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2500 W 2500 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 539 60 10% 117 0
>> Total Zone Loads - 5934 661 - 1283 0

TABLE 19.1.B. ENVELOPE LOADS FOR SPACE '' F1-16 Accountant Support '' IN ZONE '' F1-16 Chief Accountant ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 19 0.365 - 152 - 152
WINDOW 1 9 1.990 0.300 180 405 392

Hourly Analysis Program v4.80 Page 154 of 773


Space Design Load Summary for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:51PM

TABLE 20.1.A. COMPONENT LOADS FOR SPACE '' F1-07 Meeting Room '' IN ZONE '' F1-07 Meeting Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1100 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.5 °C / 20.2 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 465 - 6 m² - -
Wall Transmission 15 m² 210 - 15 m² 122 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 6 m² 77 - 6 m² 261 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 11 m² 97 - 11 m² 205 -
Ceiling 26 m² 75 - 26 m² 158 -
Overhead Lighting 520 W 520 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 316 60 10% 75 0
>> Total Zone Loads - 3477 661 - 820 0

TABLE 20.1.B. ENVELOPE LOADS FOR SPACE '' F1-07 Meeting Room '' IN ZONE '' F1-07 Meeting Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 15 0.365 - 210 - 122
WINDOW 1 6 1.990 0.300 77 465 261

Hourly Analysis Program v4.80 Page 155 of 773


Hourly Air System Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:52PM

DESIGN MONTH: JULY


COMMON CENTRAL CENTRAL CENTRAL VENT VENT ZONE
OA VENT COOLING COOLING HEATING COOLING HEATING TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 302 0.0 0.0 0.0 0.0 2.4 41.9 0.0 0.0
0100 27.2 302 0.0 0.0 0.0 0.0 2.6 41.2 0.0 0.0
0200 26.6 302 0.0 0.0 0.0 0.0 2.8 41.1 0.0 0.0
0300 26.2 302 0.0 0.0 0.0 0.0 2.9 40.6 0.0 0.0
0400 25.8 302 0.0 0.0 0.0 0.0 3.1 40.3 0.0 0.0
0500 25.7 302 0.0 0.0 0.0 0.0 3.1 40.6 0.0 0.0
0600 25.9 302 0.0 0.0 0.0 0.0 3.0 41.7 0.0 0.0
0700 26.5 302 0.0 0.0 0.0 0.0 2.8 42.6 0.0 0.0
0800 27.5 302 0.0 0.0 0.0 0.0 2.5 43.1 0.0 0.0
0900 29.0 302 0.0 0.0 0.0 0.0 2.0 44.3 0.0 0.0
1000 30.7 302 0.0 0.0 0.0 0.0 1.4 44.6 0.0 0.0
1100 32.6 302 0.0 0.0 0.0 0.0 0.8 45.5 0.0 0.0
1200 34.4 302 0.0 0.0 0.0 0.0 0.2 45.9 0.0 0.0
1300 35.8 302 0.0 0.0 0.0 0.0 0.0 46.6 0.0 0.0
1400 36.7 302 0.0 0.0 0.0 0.0 0.0 46.7 0.0 0.0
1500 37.0 302 0.0 0.0 0.0 0.0 0.0 47.3 0.0 0.0
1600 36.7 302 0.0 0.0 0.0 0.0 0.0 46.8 0.0 0.0
1700 35.9 302 0.0 0.0 0.0 0.0 0.0 46.8 0.0 0.0
1800 34.6 302 0.0 0.0 0.0 0.0 0.1 45.9 0.0 0.0
1900 33.2 302 0.0 0.0 0.0 0.0 0.6 44.9 0.0 0.0
2000 31.7 302 0.0 0.0 0.0 0.0 1.1 44.3 0.0 0.0
2100 30.4 302 0.0 0.0 0.0 0.0 1.5 43.3 0.0 0.0
2200 29.3 302 0.0 0.0 0.0 0.0 1.9 42.9 0.0 0.0
2300 28.4 302 0.0 0.0 0.0 0.0 2.2 41.9 0.0 0.0

Hourly Analysis Program v4.80 Page 156 of 773


Hourly Zone Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:53PM

ZONE: F1-11 Admin Support


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 53 643.4 7545.4 7580.8 10508.1 0.0 0.0
0100 27.2 24.8 54 643.4 7510.3 7454.8 10346.7 0.0 0.0
0200 26.6 24.8 54 643.4 7474.7 7402.3 10280.4 0.0 0.0
0300 26.2 24.8 54 643.4 7444.5 7437.8 10335.5 0.0 0.0
0400 25.8 24.9 54 643.4 7419.9 7297.7 10149.0 0.0 0.0
0500 25.7 24.9 55 643.4 7407.0 7209.3 10027.7 0.0 0.0
0600 25.9 24.8 54 643.4 7412.1 7412.1 10302.0 0.0 0.0
0700 26.5 24.8 54 643.4 7435.7 7441.8 10340.2 0.0 0.0
0800 27.5 24.9 55 643.4 7484.1 7247.1 10055.3 0.0 0.0
0900 29.0 24.8 53 643.4 7558.1 7529.4 10440.7 0.0 0.0
1000 30.7 24.9 54 643.4 7646.4 7423.8 10279.4 0.0 0.0
1100 32.6 24.8 52 643.4 7749.3 7765.5 10734.5 0.0 0.0
1200 34.4 24.9 52 643.4 7849.1 7676.6 10582.8 0.0 0.0
1300 35.8 24.9 52 643.4 7898.9 7712.1 10694.8 0.0 0.0
1400 36.7 25.0 53 643.4 7907.7 7653.1 10685.6 0.0 0.0
1500 37.0 24.8 52 643.4 7915.9 7855.9 10973.9 0.0 0.0
1600 36.7 25.0 52 643.4 7923.6 7690.2 10732.3 0.0 0.0
1700 35.9 24.8 51 643.4 7930.7 7976.9 11059.3 0.0 0.0
1800 34.6 24.8 51 643.4 7907.5 7912.5 10912.3 0.0 0.0
1900 33.2 24.9 52 643.4 7836.2 7704.6 10638.0 0.0 0.0
2000 31.7 24.7 52 643.4 7762.2 7818.8 10800.0 0.0 0.0
2100 30.4 24.9 53 643.4 7697.4 7549.8 10448.4 0.0 0.0
2200 29.3 24.9 53 643.4 7636.6 7517.4 10413.7 0.0 0.0
2300 28.4 24.9 54 643.4 7585.8 7442.7 10320.5 0.0 0.0

ZONE: F1-09 EAM Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 55 88.1 948.3 942.0 1264.4 0.0 0.0
0100 27.2 24.9 56 88.1 935.6 892.3 1192.3 0.0 0.0
0200 26.6 24.8 56 88.1 923.2 898.9 1204.9 0.0 0.0
0300 26.2 24.7 56 88.1 912.5 889.9 1196.4 0.0 0.0
0400 25.8 24.6 56 88.1 903.6 895.3 1205.9 0.0 0.0
0500 25.7 24.6 56 88.1 899.6 890.5 1200.2 0.0 0.0
0600 25.9 24.6 56 88.1 914.1 900.9 1213.2 0.0 0.0
0700 26.5 24.7 55 88.1 947.3 919.5 1230.8 0.0 0.0
0800 27.5 24.8 54 88.1 983.7 947.1 1265.7 0.0 0.0
0900 29.0 24.8 53 88.1 1014.5 981.0 1308.4 0.0 0.0
1000 30.7 24.9 53 88.1 1037.5 994.0 1321.8 0.0 0.0
1100 32.6 24.9 52 88.1 1056.0 1011.5 1343.9 0.0 0.0
1200 34.4 24.9 51 88.1 1073.0 1032.5 1368.5 0.0 0.0
1300 35.8 24.8 50 88.1 1081.3 1059.1 1414.1 0.0 0.0
1400 36.7 24.9 51 88.1 1082.5 1038.2 1396.7 0.0 0.0
1500 37.0 24.9 51 88.1 1084.6 1046.3 1411.2 0.0 0.0
1600 36.7 24.9 51 88.1 1085.9 1049.7 1410.4 0.0 0.0
1700 35.9 24.8 51 88.1 1085.5 1051.5 1404.6 0.0 0.0
1800 34.6 24.8 51 88.1 1074.9 1043.0 1382.0 0.0 0.0
1900 33.2 24.8 52 88.1 1049.9 1019.4 1353.3 0.0 0.0
2000 31.7 24.7 52 88.1 1024.3 1013.7 1350.6 0.0 0.0
2100 30.4 24.8 54 88.1 1001.7 967.9 1290.8 0.0 0.0
2200 29.3 24.8 54 88.1 980.8 946.6 1262.3 0.0 0.0
2300 28.4 24.7 54 88.1 962.9 951.1 1273.3 0.0 0.0

Hourly Analysis Program v4.80 Page 157 of 773


Hourly Zone Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:53PM

ZONE: F1-51 Director of F&B


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 56 95.9 969.8 963.1 1236.1 0.0 0.0
0100 27.2 24.8 57 95.9 952.5 927.5 1190.2 0.0 0.0
0200 26.6 24.8 58 95.9 935.5 916.1 1177.3 0.0 0.0
0300 26.2 24.6 58 95.9 920.6 915.3 1178.4 0.0 0.0
0400 25.8 24.8 59 95.9 907.9 883.6 1137.0 0.0 0.0
0500 25.7 24.7 57 95.9 949.6 937.3 1207.5 0.0 0.0
0600 25.9 24.7 54 95.9 1021.9 1010.7 1297.0 0.0 0.0
0700 26.5 24.9 54 95.9 1070.5 1030.1 1313.7 0.0 0.0
0800 27.5 24.9 53 95.9 1101.4 1058.9 1347.8 0.0 0.0
0900 29.0 24.8 52 95.9 1115.3 1089.5 1388.2 0.0 0.0
1000 30.7 24.8 51 95.9 1122.3 1098.1 1398.9 0.0 0.0
1100 32.6 24.9 51 95.9 1144.4 1100.6 1397.2 0.0 0.0
1200 34.4 24.9 51 95.9 1167.1 1121.4 1421.5 0.0 0.0
1300 35.8 24.8 50 95.9 1179.2 1149.5 1467.5 0.0 0.0
1400 36.7 25.0 50 95.9 1180.9 1131.8 1452.4 0.0 0.0
1500 37.0 24.9 50 95.9 1179.2 1138.3 1465.4 0.0 0.0
1600 36.7 24.8 50 95.9 1172.2 1145.7 1473.5 0.0 0.0
1700 35.9 24.9 50 95.9 1159.5 1124.1 1438.2 0.0 0.0
1800 34.6 24.9 51 95.9 1134.5 1094.5 1388.2 0.0 0.0
1900 33.2 24.9 52 95.9 1102.0 1069.8 1361.7 0.0 0.0
2000 31.7 24.8 53 95.9 1069.2 1041.8 1327.0 0.0 0.0
2100 30.4 24.7 54 95.9 1040.1 1029.2 1316.7 0.0 0.0
2200 29.3 24.8 55 95.9 1012.9 983.5 1257.2 0.0 0.0
2300 28.4 24.8 56 95.9 989.5 966.6 1236.9 0.0 0.0

ZONE: F1-06 DIR of Revenue


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 58 104.5 1011.1 977.5 1248.7 0.0 0.0
0100 27.2 24.7 59 104.5 992.4 969.2 1241.9 0.0 0.0
0200 26.6 24.6 58 104.5 974.1 972.7 1251.5 0.0 0.0
0300 26.2 24.7 59 104.5 958.1 944.1 1214.4 0.0 0.0
0400 25.8 24.7 60 104.5 944.4 926.6 1192.0 0.0 0.0
0500 25.7 24.8 60 104.5 959.1 920.3 1180.7 0.0 0.0
0600 25.9 24.8 58 104.5 1010.9 982.2 1257.6 0.0 0.0
0700 26.5 24.9 57 104.5 1066.0 1020.5 1300.2 0.0 0.0
0800 27.5 24.8 55 104.5 1120.4 1084.1 1378.1 0.0 0.0
0900 29.0 24.9 54 104.5 1167.4 1119.2 1418.9 0.0 0.0
1000 30.7 24.9 52 104.5 1199.6 1159.3 1469.9 0.0 0.0
1100 32.6 24.9 52 104.5 1219.2 1176.1 1487.9 0.0 0.0
1200 34.4 24.9 52 104.5 1236.1 1188.6 1502.7 0.0 0.0
1300 35.8 24.8 51 104.5 1244.9 1221.1 1554.1 0.0 0.0
1400 36.7 24.8 51 104.5 1242.2 1207.5 1546.7 0.0 0.0
1500 37.0 24.7 50 104.5 1237.8 1221.7 1571.6 0.0 0.0
1600 36.7 25.0 52 104.5 1229.1 1175.0 1503.5 0.0 0.0
1700 35.9 24.9 52 104.5 1215.3 1174.2 1495.0 0.0 0.0
1800 34.6 24.9 53 104.5 1188.6 1154.0 1461.5 0.0 0.0
1900 33.2 24.7 53 104.5 1153.5 1138.4 1447.0 0.0 0.0
2000 31.7 24.9 55 104.5 1118.1 1082.4 1375.4 0.0 0.0
2100 30.4 24.8 56 104.5 1086.7 1059.5 1349.7 0.0 0.0
2200 29.3 24.7 56 104.5 1057.4 1051.2 1345.0 0.0 0.0
2300 28.4 24.8 58 104.5 1032.2 998.4 1275.1 0.0 0.0

Hourly Analysis Program v4.80 Page 158 of 773


Hourly Zone Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:53PM

ZONE: F1-05 DIR of Public Rel


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 58 104.5 1012.6 986.4 1262.0 0.0 0.0
0100 27.2 24.7 58 104.5 993.8 972.7 1246.9 0.0 0.0
0200 26.6 24.6 59 104.5 975.5 968.8 1245.9 0.0 0.0
0300 26.2 24.7 60 104.5 959.4 933.8 1198.6 0.0 0.0
0400 25.8 24.7 60 104.5 945.7 926.0 1190.3 0.0 0.0
0500 25.7 24.7 60 104.5 960.3 935.3 1201.4 0.0 0.0
0600 25.9 24.7 58 104.5 1012.0 983.5 1259.5 0.0 0.0
0700 26.5 24.7 56 104.5 1066.8 1041.8 1331.2 0.0 0.0
0800 27.5 24.9 55 104.5 1120.9 1074.1 1365.7 0.0 0.0
0900 29.0 24.7 53 104.5 1167.8 1143.2 1455.9 0.0 0.0
1000 30.7 24.8 52 104.5 1200.2 1164.9 1477.3 0.0 0.0
1100 32.6 25.0 53 104.5 1220.1 1155.4 1458.7 0.0 0.0
1200 34.4 24.8 51 104.5 1237.6 1208.1 1529.1 0.0 0.0
1300 35.8 24.8 51 104.5 1246.8 1214.6 1545.5 0.0 0.0
1400 36.7 24.7 50 104.5 1244.3 1221.8 1567.2 0.0 0.0
1500 37.0 25.0 52 104.5 1240.0 1176.6 1508.1 0.0 0.0
1600 36.7 24.8 51 104.5 1231.4 1205.2 1548.0 0.0 0.0
1700 35.9 24.8 52 104.5 1217.7 1181.5 1503.1 0.0 0.0
1800 34.6 24.9 53 104.5 1191.1 1152.1 1458.9 0.0 0.0
1900 33.2 24.7 53 104.5 1155.8 1140.2 1449.9 0.0 0.0
2000 31.7 24.9 55 104.5 1120.2 1078.7 1370.2 0.0 0.0
2100 30.4 24.8 56 104.5 1088.6 1058.4 1348.1 0.0 0.0
2200 29.3 24.8 56 104.5 1059.2 1034.4 1320.6 0.0 0.0
2300 28.4 24.7 57 104.5 1033.8 1025.5 1314.0 0.0 0.0

ZONE: F1-04 DIR Cater & Confe


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 57 99.9 951.6 945.4 1191.9 0.0 0.0
0100 27.2 24.7 59 99.9 933.9 914.8 1152.1 0.0 0.0
0200 26.6 24.6 59 99.9 916.6 912.1 1152.8 0.0 0.0
0300 26.2 24.7 60 99.9 901.5 880.3 1110.8 0.0 0.0
0400 25.8 24.7 60 99.9 888.5 868.5 1096.7 0.0 0.0
0500 25.7 24.6 59 99.9 903.5 896.5 1133.9 0.0 0.0
0600 25.9 24.9 59 99.9 955.5 910.3 1141.7 0.0 0.0
0700 26.5 24.7 56 99.9 1011.1 998.5 1254.1 0.0 0.0
0800 27.5 24.7 54 99.9 1065.3 1044.7 1310.9 0.0 0.0
0900 29.0 24.7 53 99.9 1111.1 1084.7 1357.4 0.0 0.0
1000 30.7 24.7 52 99.9 1141.1 1116.8 1396.2 0.0 0.0
1100 32.6 24.8 52 99.9 1157.4 1118.6 1396.3 0.0 0.0
1200 34.4 24.8 51 99.9 1170.6 1134.7 1414.1 0.0 0.0
1300 35.8 24.7 50 99.9 1177.1 1156.8 1452.8 0.0 0.0
1400 36.7 25.0 52 99.9 1173.6 1117.7 1405.2 0.0 0.0
1500 37.0 25.0 52 99.9 1168.6 1120.5 1415.5 0.0 0.0
1600 36.7 24.9 52 99.9 1159.5 1115.4 1406.2 0.0 0.0
1700 35.9 24.9 52 99.9 1145.2 1104.7 1384.6 0.0 0.0
1800 34.6 24.9 53 99.9 1119.0 1081.7 1347.5 0.0 0.0
1900 33.2 24.9 54 99.9 1085.8 1051.5 1311.9 0.0 0.0
2000 31.7 24.9 55 99.9 1052.5 1020.9 1275.5 0.0 0.0
2100 30.4 24.7 55 99.9 1023.0 1010.3 1267.9 0.0 0.0
2200 29.3 24.7 56 99.9 995.4 980.9 1232.6 0.0 0.0
2300 28.4 24.9 58 99.9 971.6 937.3 1174.4 0.0 0.0

Hourly Analysis Program v4.80 Page 159 of 773


Hourly Zone Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:53PM

ZONE: F1-14 Chief Accountant


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 55 79.9 886.7 854.3 1150.1 0.0 0.0
0100 27.2 24.8 54 79.9 877.8 859.2 1158.8 0.0 0.0
0200 26.6 24.8 55 79.9 868.7 850.9 1148.6 0.0 0.0
0300 26.2 24.8 55 79.9 861.0 839.2 1133.3 0.0 0.0
0400 25.8 24.8 55 79.9 854.8 831.6 1123.4 0.0 0.0
0500 25.7 24.8 56 79.9 851.5 826.6 1116.6 0.0 0.0
0600 25.9 24.7 55 79.9 852.8 842.8 1140.4 0.0 0.0
0700 26.5 24.9 56 79.9 858.8 820.6 1105.7 0.0 0.0
0800 27.5 24.8 55 79.9 871.1 851.3 1148.4 0.0 0.0
0900 29.0 24.8 54 79.9 889.9 869.9 1170.8 0.0 0.0
1000 30.7 25.0 54 79.9 912.3 863.1 1156.7 0.0 0.0
1100 32.6 24.8 52 79.9 938.5 912.4 1221.9 0.0 0.0
1200 34.4 24.8 51 79.9 963.9 938.5 1256.5 0.0 0.0
1300 35.8 24.8 50 79.9 976.5 961.9 1297.3 0.0 0.0
1400 36.7 24.9 51 79.9 978.8 942.8 1281.3 0.0 0.0
1500 37.0 25.0 52 79.9 980.9 924.2 1255.7 0.0 0.0
1600 36.7 24.9 51 79.9 982.8 954.3 1294.7 0.0 0.0
1700 35.9 24.7 50 79.9 984.6 977.4 1318.7 0.0 0.0
1800 34.6 24.8 50 79.9 978.7 964.6 1291.5 0.0 0.0
1900 33.2 24.9 52 79.9 960.6 918.1 1228.1 0.0 0.0
2000 31.7 24.8 52 79.9 941.8 916.2 1228.2 0.0 0.0
2100 30.4 25.0 53 79.9 925.3 881.2 1180.5 0.0 0.0
2200 29.3 24.8 53 79.9 909.8 890.2 1197.0 0.0 0.0
2300 28.4 24.8 54 79.9 896.9 877.0 1180.7 0.0 0.0

ZONE: F1-12 Director of M&S


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 56 96.8 974.9 968.4 1240.8 0.0 0.0
0100 27.2 24.8 57 96.8 957.1 931.9 1194.0 0.0 0.0
0200 26.6 24.8 58 96.8 939.7 920.0 1180.6 0.0 0.0
0300 26.2 24.6 58 96.8 924.5 919.5 1181.6 0.0 0.0
0400 25.8 24.8 59 96.8 911.4 886.8 1139.3 0.0 0.0
0500 25.7 24.7 57 96.8 953.0 941.2 1210.4 0.0 0.0
0600 25.9 24.7 54 96.8 1026.8 1014.7 1300.0 0.0 0.0
0700 26.5 24.9 54 96.8 1078.4 1036.8 1320.0 0.0 0.0
0800 27.5 24.9 53 96.8 1112.1 1067.7 1356.3 0.0 0.0
0900 29.0 24.8 51 96.8 1127.4 1102.5 1402.5 0.0 0.0
1000 30.7 24.8 51 96.8 1134.6 1104.9 1404.2 0.0 0.0
1100 32.6 24.8 51 96.8 1156.0 1126.3 1429.7 0.0 0.0
1200 34.4 24.9 50 96.8 1177.9 1137.0 1440.0 0.0 0.0
1300 35.8 24.9 50 96.8 1189.5 1148.1 1461.8 0.0 0.0
1400 36.7 25.0 50 96.8 1191.2 1138.7 1458.1 0.0 0.0
1500 37.0 24.9 50 96.8 1189.4 1146.6 1473.1 0.0 0.0
1600 36.7 24.8 50 96.8 1182.4 1157.7 1486.5 0.0 0.0
1700 35.9 24.9 51 96.8 1169.5 1126.3 1435.9 0.0 0.0
1800 34.6 24.9 51 96.8 1143.9 1108.3 1405.5 0.0 0.0
1900 33.2 24.8 52 96.8 1110.6 1095.6 1394.3 0.0 0.0
2000 31.7 24.8 53 96.8 1077.0 1054.5 1343.7 0.0 0.0
2100 30.4 24.8 54 96.8 1047.1 1025.3 1309.0 0.0 0.0
2200 29.3 24.9 55 96.8 1019.2 981.9 1251.8 0.0 0.0
2300 28.4 24.8 56 96.8 995.1 968.5 1235.5 0.0 0.0

Hourly Analysis Program v4.80 Page 160 of 773


Hourly Zone Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:53PM

ZONE: F1-20 Cashier


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 56 64.3 671.8 647.0 805.2 0.0 0.0
0100 27.2 24.9 57 64.3 660.8 623.9 777.1 0.0 0.0
0200 26.6 24.7 57 64.3 649.7 627.2 782.9 0.0 0.0
0300 26.2 24.8 58 64.3 640.2 605.7 756.4 0.0 0.0
0400 25.8 24.7 58 64.3 632.4 611.6 765.1 0.0 0.0
0500 25.7 24.8 59 64.3 628.4 599.4 750.0 0.0 0.0
0600 25.9 24.6 58 64.3 630.0 620.0 776.3 0.0 0.0
0700 26.5 24.6 57 64.3 637.4 628.8 786.7 0.0 0.0
0800 27.5 24.9 58 64.3 652.6 608.2 758.9 0.0 0.0
0900 29.0 24.8 56 64.3 675.8 647.5 805.3 0.0 0.0
1000 30.7 24.7 55 64.3 703.5 676.0 838.3 0.0 0.0
1100 32.6 24.8 53 64.3 735.8 698.7 862.9 0.0 0.0
1200 34.4 24.7 51 64.3 767.1 742.1 914.2 0.0 0.0
1300 35.8 24.8 51 64.3 782.8 744.5 919.1 0.0 0.0
1400 36.7 24.8 51 64.3 785.5 749.6 929.8 0.0 0.0
1500 37.0 25.0 51 64.3 788.1 736.9 914.8 0.0 0.0
1600 36.7 24.9 51 64.3 790.5 752.4 932.2 0.0 0.0
1700 35.9 24.9 51 64.3 792.8 755.5 933.1 0.0 0.0
1800 34.6 24.9 51 64.3 785.5 750.2 921.5 0.0 0.0
1900 33.2 24.9 52 64.3 763.1 719.8 886.4 0.0 0.0
2000 31.7 24.8 53 64.3 739.8 709.4 876.0 0.0 0.0
2100 30.4 24.8 54 64.3 719.5 687.2 851.0 0.0 0.0
2200 29.3 24.7 54 64.3 700.4 683.6 849.8 0.0 0.0
2300 28.4 24.8 56 64.3 684.5 650.0 807.4 0.0 0.0

ZONE: F18- DIR of Finance


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 57 102.2 1006.3 975.5 1220.0 0.0 0.0
0100 27.2 24.7 58 102.2 984.9 956.9 1198.6 0.0 0.0
0200 26.6 24.6 58 102.2 963.9 952.8 1197.8 0.0 0.0
0300 26.2 24.7 59 102.2 945.5 913.4 1144.8 0.0 0.0
0400 25.8 24.7 60 102.2 930.0 902.4 1131.8 0.0 0.0
0500 25.7 24.7 58 102.2 970.2 936.8 1174.0 0.0 0.0
0600 25.9 24.8 56 102.2 1044.6 998.1 1245.3 0.0 0.0
0700 26.5 24.7 54 102.2 1098.6 1074.1 1341.9 0.0 0.0
0800 27.5 24.8 53 102.2 1137.3 1102.1 1373.7 0.0 0.0
0900 29.0 24.8 52 102.2 1160.1 1118.7 1391.8 0.0 0.0
1000 30.7 24.8 52 102.2 1176.3 1140.5 1418.7 0.0 0.0
1100 32.6 24.8 51 102.2 1208.2 1166.0 1447.7 0.0 0.0
1200 34.4 24.9 50 102.2 1240.4 1183.0 1464.4 0.0 0.0
1300 35.8 24.8 49 102.2 1257.1 1215.1 1514.2 0.0 0.0
1400 36.7 24.9 50 102.2 1259.6 1202.2 1505.8 0.0 0.0
1500 37.0 24.8 49 102.2 1258.7 1220.6 1535.2 0.0 0.0
1600 36.7 25.0 50 102.2 1252.5 1192.8 1493.6 0.0 0.0
1700 35.9 24.9 50 102.2 1240.3 1188.1 1480.0 0.0 0.0
1800 34.6 24.9 51 102.2 1212.3 1165.1 1445.4 0.0 0.0
1900 33.2 24.9 52 102.2 1171.7 1128.8 1403.0 0.0 0.0
2000 31.7 24.8 53 102.2 1130.5 1091.6 1356.1 0.0 0.0
2100 30.4 24.8 54 102.2 1094.0 1058.5 1317.6 0.0 0.0
2200 29.3 24.7 55 102.2 1059.9 1044.0 1306.5 0.0 0.0
2300 28.4 24.8 57 102.2 1030.6 991.0 1237.4 0.0 0.0

Hourly Analysis Program v4.80 Page 161 of 773


Hourly Zone Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:53PM

ZONE: F1-15 Assitant Control


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 54 82.3 903.7 882.5 1182.0 0.0 0.0
0100 27.2 24.8 55 82.3 893.6 872.2 1169.5 0.0 0.0
0200 26.6 24.8 55 82.3 883.4 862.7 1157.9 0.0 0.0
0300 26.2 24.8 56 82.3 874.8 852.5 1144.9 0.0 0.0
0400 25.8 24.8 56 82.3 867.7 836.1 1123.0 0.0 0.0
0500 25.7 24.7 55 82.3 864.0 859.0 1157.1 0.0 0.0
0600 25.9 24.7 55 82.3 865.4 857.7 1155.2 0.0 0.0
0700 26.5 24.7 55 82.3 872.2 858.3 1153.9 0.0 0.0
0800 27.5 24.7 55 82.3 886.1 870.6 1170.5 0.0 0.0
0900 29.0 24.7 54 82.3 907.3 882.8 1183.7 0.0 0.0
1000 30.7 24.7 53 82.3 932.7 916.6 1229.0 0.0 0.0
1100 32.6 25.0 53 82.3 962.2 904.0 1202.5 0.0 0.0
1200 34.4 24.9 52 82.3 990.8 952.7 1268.6 0.0 0.0
1300 35.8 24.7 50 82.3 1005.1 983.6 1318.3 0.0 0.0
1400 36.7 24.9 51 82.3 1007.6 965.2 1303.1 0.0 0.0
1500 37.0 24.9 51 82.3 1010.0 971.0 1314.2 0.0 0.0
1600 36.7 24.8 50 82.3 1012.2 983.0 1326.4 0.0 0.0
1700 35.9 25.0 51 82.3 1014.2 959.7 1280.2 0.0 0.0
1800 34.6 24.9 51 82.3 1007.6 972.6 1291.3 0.0 0.0
1900 33.2 25.0 53 82.3 987.1 928.3 1229.2 0.0 0.0
2000 31.7 24.8 52 82.3 965.9 939.7 1251.6 0.0 0.0
2100 30.4 24.9 53 82.3 947.3 905.1 1205.9 0.0 0.0
2200 29.3 24.8 53 82.3 929.8 907.8 1213.1 0.0 0.0
2300 28.4 24.9 54 82.3 915.3 879.3 1176.4 0.0 0.0

ZONE: F1-13 Reception Area


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 52 122.4 1424.9 1426.2 2083.4 0.0 0.0
0100 27.2 24.8 53 122.4 1417.3 1406.4 2054.0 0.0 0.0
0200 26.6 25.0 54 122.4 1409.6 1360.5 1980.4 0.0 0.0
0300 26.2 24.9 54 122.4 1403.0 1365.5 1989.4 0.0 0.0
0400 25.8 24.7 53 122.4 1397.7 1412.5 2068.3 0.0 0.0
0500 25.7 24.7 53 122.4 1394.9 1399.6 2049.7 0.0 0.0
0600 25.9 24.8 54 122.4 1396.0 1378.0 2014.2 0.0 0.0
0700 26.5 24.7 53 122.4 1401.1 1403.5 2054.5 0.0 0.0
0800 27.5 24.9 54 122.4 1411.6 1381.2 2018.6 0.0 0.0
0900 29.0 24.9 54 122.4 1427.6 1380.8 2009.8 0.0 0.0
1000 30.7 24.8 52 122.4 1446.8 1441.8 2103.2 0.0 0.0
1100 32.6 25.0 53 122.4 1469.0 1414.4 2052.7 0.0 0.0
1200 34.4 24.8 51 122.4 1490.7 1483.8 2158.8 0.0 0.0
1300 35.8 25.0 52 122.4 1501.4 1446.4 2113.9 0.0 0.0
1400 36.7 24.8 51 122.4 1503.4 1497.3 2222.1 0.0 0.0
1500 37.0 24.9 51 122.4 1505.1 1476.1 2196.9 0.0 0.0
1600 36.7 24.9 51 122.4 1506.8 1478.6 2192.3 0.0 0.0
1700 35.9 24.8 51 122.4 1508.4 1503.0 2208.6 0.0 0.0
1800 34.6 24.9 51 122.4 1503.3 1470.8 2135.1 0.0 0.0
1900 33.2 24.9 52 122.4 1487.9 1458.3 2118.2 0.0 0.0
2000 31.7 25.0 53 122.4 1471.8 1423.4 2066.5 0.0 0.0
2100 30.4 24.8 52 122.4 1457.8 1463.8 2134.8 0.0 0.0
2200 29.3 25.0 53 122.4 1444.6 1395.2 2030.4 0.0 0.0
2300 28.4 24.8 53 122.4 1433.6 1419.2 2069.3 0.0 0.0

Hourly Analysis Program v4.80 Page 162 of 773


Hourly Zone Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:53PM

ZONE: F1-08 General Manager


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 58 179.5 1712.2 1671.4 2204.2 0.0 0.0
0100 27.2 24.7 59 179.5 1678.1 1649.9 2180.8 0.0 0.0
0200 26.6 24.6 59 179.5 1645.6 1646.9 2186.3 0.0 0.0
0300 26.2 24.7 60 179.5 1616.9 1579.7 2091.8 0.0 0.0
0400 25.8 24.7 61 179.5 1591.8 1566.6 2078.3 0.0 0.0
0500 25.7 24.7 60 179.5 1623.7 1587.8 2099.8 0.0 0.0
0600 25.9 24.9 58 179.5 1745.6 1675.1 2202.6 0.0 0.0
0700 26.5 24.8 55 179.5 1887.6 1834.4 2409.5 0.0 0.0
0800 27.5 24.8 53 179.5 2014.7 1958.4 2565.2 0.0 0.0
0900 29.0 24.8 51 179.5 2102.4 2054.5 2687.1 0.0 0.0
1000 30.7 24.9 51 179.5 2140.7 2063.9 2690.1 0.0 0.0
1100 32.6 24.8 51 179.5 2140.8 2099.4 2742.4 0.0 0.0
1200 34.4 24.8 51 179.5 2139.4 2092.2 2732.1 0.0 0.0
1300 35.8 24.9 51 179.5 2143.4 2079.5 2731.3 0.0 0.0
1400 36.7 24.9 51 179.5 2138.4 2071.2 2745.3 0.0 0.0
1500 37.0 24.8 51 179.5 2129.9 2091.9 2788.6 0.0 0.0
1600 36.7 24.9 51 179.5 2111.4 2057.2 2729.3 0.0 0.0
1700 35.9 24.9 52 179.5 2080.2 2022.1 2662.0 0.0 0.0
1800 34.6 24.7 52 179.5 2026.9 2005.5 2626.0 0.0 0.0
1900 33.2 24.9 54 179.5 1964.7 1900.8 2485.9 0.0 0.0
2000 31.7 24.8 55 179.5 1902.4 1858.4 2437.1 0.0 0.0
2100 30.4 24.8 56 179.5 1847.0 1813.0 2383.2 0.0 0.0
2200 29.3 24.7 56 179.5 1795.5 1794.1 2369.7 0.0 0.0
2300 28.4 24.8 58 179.5 1750.6 1710.8 2254.1 0.0 0.0

ZONE: F1-10 Quality Manager


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 55 87.7 945.7 929.6 1245.3 0.0 0.0
0100 27.2 24.9 56 87.7 933.2 901.6 1205.9 0.0 0.0
0200 26.6 24.8 56 87.7 921.0 906.7 1217.9 0.0 0.0
0300 26.2 24.7 56 87.7 910.5 897.0 1207.3 0.0 0.0
0400 25.8 24.6 56 87.7 901.6 906.4 1221.5 0.0 0.0
0500 25.7 24.7 56 87.7 897.7 889.1 1199.8 0.0 0.0
0600 25.9 24.7 56 87.7 912.2 891.9 1197.0 0.0 0.0
0700 26.5 24.7 55 87.7 945.3 926.7 1242.2 0.0 0.0
0800 27.5 24.6 53 87.7 981.4 976.2 1307.7 0.0 0.0
0900 29.0 24.7 52 87.7 1011.9 996.9 1331.6 0.0 0.0
1000 30.7 24.8 53 87.7 1034.4 992.7 1321.5 0.0 0.0
1100 32.6 24.8 51 87.7 1052.4 1022.6 1359.4 0.0 0.0
1200 34.4 24.9 51 87.7 1068.9 1024.5 1360.7 0.0 0.0
1300 35.8 24.9 51 87.7 1077.0 1037.9 1385.3 0.0 0.0
1400 36.7 24.8 50 87.7 1078.2 1056.1 1422.3 0.0 0.0
1500 37.0 24.9 51 87.7 1080.2 1038.5 1401.3 0.0 0.0
1600 36.7 24.9 51 87.7 1081.5 1039.4 1398.6 0.0 0.0
1700 35.9 25.0 51 87.7 1081.0 1028.8 1370.0 0.0 0.0
1800 34.6 24.9 51 87.7 1070.6 1036.7 1375.7 0.0 0.0
1900 33.2 25.0 52 87.7 1045.9 999.9 1325.6 0.0 0.0
2000 31.7 24.8 52 87.7 1020.6 994.7 1325.0 0.0 0.0
2100 30.4 24.9 54 87.7 998.4 961.2 1280.0 0.0 0.0
2200 29.3 24.8 54 87.7 977.8 957.0 1279.8 0.0 0.0
2300 28.4 25.0 55 87.7 960.2 914.2 1217.3 0.0 0.0

Hourly Analysis Program v4.80 Page 163 of 773


Hourly Zone Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:53PM

ZONE: F1-03 Call Center


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 52 163.7 1786.8 1762.7 2084.9 0.0 0.0
0100 27.2 24.9 52 163.7 1774.2 1758.3 2083.2 0.0 0.0
0200 26.6 25.0 53 163.7 1762.7 1732.1 2048.1 0.0 0.0
0300 26.2 24.9 53 163.7 1752.8 1730.5 2048.8 0.0 0.0
0400 25.8 24.9 53 163.7 1744.5 1730.1 2051.2 0.0 0.0
0500 25.7 25.0 53 163.7 1738.8 1710.3 2023.7 0.0 0.0
0600 25.9 24.8 53 163.7 1738.6 1730.4 2052.9 0.0 0.0
0700 26.5 24.9 53 163.7 1745.4 1723.5 2040.5 0.0 0.0
0800 27.5 25.0 53 163.7 1759.0 1718.8 2032.1 0.0 0.0
0900 29.0 24.9 52 163.7 1778.5 1758.1 2083.5 0.0 0.0
1000 30.7 25.0 52 163.7 1801.7 1763.4 2079.6 0.0 0.0
1100 32.6 24.7 51 163.7 1829.4 1836.8 2179.1 0.0 0.0
1200 34.4 25.0 51 163.7 1864.1 1828.1 2156.7 0.0 0.0
1300 35.8 24.9 50 163.7 1899.9 1874.2 2223.4 0.0 0.0
1400 36.7 25.0 50 163.7 1932.4 1893.7 2254.9 0.0 0.0
1500 37.0 25.2 49 163.7 1960.9 1908.8 2272.1 0.0 0.0
1600 36.7 25.2 49 163.7 1979.7 1932.9 2295.9 0.0 0.0
1700 35.9 25.1 49 163.7 1983.9 1939.7 2292.3 0.0 0.0
1800 34.6 25.2 49 163.7 1963.8 1920.2 2256.9 0.0 0.0
1900 33.2 25.0 50 163.7 1918.3 1896.4 2236.2 0.0 0.0
2000 31.7 24.9 50 163.7 1876.4 1867.1 2206.8 0.0 0.0
2100 30.4 25.0 51 163.7 1845.3 1823.1 2153.0 0.0 0.0
2200 29.3 24.8 51 163.7 1821.0 1819.7 2156.1 0.0 0.0
2300 28.4 24.8 52 163.7 1801.9 1796.4 2129.3 0.0 0.0

ZONE: F1-01 Reservation Mngr


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 59 104.0 935.4 929.1 1132.9 0.0 0.0
0100 27.2 24.7 60 104.0 914.1 898.0 1093.4 0.0 0.0
0200 26.6 24.6 60 104.0 894.2 886.1 1081.1 0.0 0.0
0300 26.2 24.5 61 104.0 876.6 874.9 1070.8 0.0 0.0
0400 25.8 24.6 62 104.0 861.5 847.9 1035.5 0.0 0.0
0500 25.7 24.5 61 104.0 874.5 871.1 1066.5 0.0 0.0
0600 25.9 24.6 59 104.0 924.8 911.7 1113.1 0.0 0.0
0700 26.5 24.7 58 104.0 979.5 954.1 1160.4 0.0 0.0
0800 27.5 24.7 56 104.0 1033.7 1002.7 1216.3 0.0 0.0
0900 29.0 24.6 54 104.0 1080.3 1065.7 1295.2 0.0 0.0
1000 30.7 24.9 54 104.0 1112.5 1066.5 1287.8 0.0 0.0
1100 32.6 24.9 54 104.0 1133.1 1083.5 1305.9 0.0 0.0
1200 34.4 24.7 52 104.0 1157.4 1138.7 1379.8 0.0 0.0
1300 35.8 24.9 52 104.0 1184.0 1141.1 1383.2 0.0 0.0
1400 36.7 24.9 51 104.0 1204.2 1159.6 1415.1 0.0 0.0
1500 37.0 25.0 51 104.0 1219.6 1171.2 1429.5 0.0 0.0
1600 36.7 24.9 50 104.0 1223.6 1186.1 1446.9 0.0 0.0
1700 35.9 24.9 51 104.0 1211.7 1170.8 1416.4 0.0 0.0
1800 34.6 24.9 52 104.0 1174.8 1143.0 1378.3 0.0 0.0
1900 33.2 24.9 54 104.0 1119.7 1082.4 1305.6 0.0 0.0
2000 31.7 24.7 55 104.0 1067.3 1051.1 1274.2 0.0 0.0
2100 30.4 24.9 57 104.0 1025.3 993.0 1201.3 0.0 0.0
2200 29.3 24.8 57 104.0 989.6 967.6 1173.8 0.0 0.0
2300 28.4 24.8 59 104.0 959.9 930.3 1126.9 0.0 0.0

Hourly Analysis Program v4.80 Page 164 of 773


Hourly Zone Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:53PM

ZONE: F1-02 Reservation


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 61 64.2 577.1 568.1 795.0 0.0 0.0
0100 27.2 24.7 62 64.2 565.3 544.8 760.8 0.0 0.0
0200 26.6 24.6 62 64.2 554.5 547.8 768.5 0.0 0.0
0300 26.2 24.6 63 64.2 545.2 538.3 756.2 0.0 0.0
0400 25.8 24.6 63 64.2 537.4 529.3 744.0 0.0 0.0
0500 25.7 24.7 64 64.2 532.1 510.0 712.4 0.0 0.0
0600 25.9 24.6 63 64.2 532.0 526.0 739.8 0.0 0.0
0700 26.5 24.5 62 64.2 538.4 541.0 763.0 0.0 0.0
0800 27.5 24.8 64 64.2 551.2 520.5 726.7 0.0 0.0
0900 29.0 24.6 61 64.2 569.6 558.1 781.9 0.0 0.0
1000 30.7 24.6 60 64.2 591.5 580.0 811.4 0.0 0.0
1100 32.6 24.8 60 64.2 617.6 586.0 813.7 0.0 0.0
1200 34.4 24.6 57 64.2 650.2 639.4 889.3 0.0 0.0
1300 35.8 24.7 56 64.2 683.3 661.4 924.3 0.0 0.0
1400 36.7 24.8 55 64.2 713.1 682.0 959.2 0.0 0.0
1500 37.0 24.7 53 64.2 739.2 720.7 1016.5 0.0 0.0
1600 36.7 25.0 53 64.2 756.5 709.0 989.6 0.0 0.0
1700 35.9 24.8 52 64.2 760.3 731.4 1013.6 0.0 0.0
1800 34.6 25.0 54 64.2 741.8 696.9 954.0 0.0 0.0
1900 33.2 24.9 56 64.2 699.7 665.7 915.2 0.0 0.0
2000 31.7 24.7 56 64.2 660.7 648.8 898.6 0.0 0.0
2100 30.4 24.8 59 64.2 631.8 607.0 840.8 0.0 0.0
2200 29.3 24.7 59 64.2 609.1 602.6 839.4 0.0 0.0
2300 28.4 24.8 61 64.2 591.2 566.3 786.7 0.0 0.0

ZONE: F1-21 Counting Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 61 30.5 287.5 264.7 355.3 0.0 0.0
0100 27.2 24.6 61 30.5 279.4 271.7 366.5 0.0 0.0
0200 26.6 24.7 63 30.5 271.2 252.9 341.3 0.0 0.0
0300 26.2 24.6 63 30.5 264.2 255.1 345.8 0.0 0.0
0400 25.8 24.7 65 30.5 258.5 238.6 323.2 0.0 0.0
0500 25.7 24.5 63 30.5 255.5 248.6 338.1 0.0 0.0
0600 25.9 24.7 65 30.5 256.7 238.4 323.4 0.0 0.0
0700 26.5 24.5 62 30.5 262.2 255.7 347.3 0.0 0.0
0800 27.5 24.5 62 30.5 273.3 263.9 357.3 0.0 0.0
0900 29.0 24.6 61 30.5 290.4 271.3 365.0 0.0 0.0
1000 30.7 24.8 60 30.5 310.8 279.3 372.9 0.0 0.0
1100 32.6 24.7 56 30.5 334.5 313.5 417.1 0.0 0.0
1200 34.4 24.9 55 30.5 357.6 322.1 425.3 0.0 0.0
1300 35.8 24.8 52 30.5 369.1 344.6 457.3 0.0 0.0
1400 36.7 24.7 52 30.5 371.1 348.6 466.8 0.0 0.0
1500 37.0 24.8 52 30.5 373.0 344.1 461.6 0.0 0.0
1600 36.7 24.8 52 30.5 374.8 352.2 471.5 0.0 0.0
1700 35.9 24.8 52 30.5 376.4 348.0 461.7 0.0 0.0
1800 34.6 24.8 52 30.5 371.1 344.9 454.5 0.0 0.0
1900 33.2 24.9 55 30.5 354.6 324.1 428.1 0.0 0.0
2000 31.7 24.7 55 30.5 337.5 322.5 428.6 0.0 0.0
2100 30.4 24.9 58 30.5 322.6 293.3 389.5 0.0 0.0
2200 29.3 24.7 58 30.5 308.5 292.3 390.8 0.0 0.0
2300 28.4 24.8 61 30.5 296.8 271.0 362.7 0.0 0.0

Hourly Analysis Program v4.80 Page 165 of 773


Hourly Zone Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:53PM

ZONE: F1-16 Chief Accountant


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 53 481.4 5333.0 5295.5 6089.3 0.0 0.0
0100 27.2 24.9 54 481.4 5284.7 5222.7 6017.3 0.0 0.0
0200 26.6 24.7 53 481.4 5237.9 5258.4 6054.7 0.0 0.0
0300 26.2 24.8 54 481.4 5196.7 5167.6 5963.2 0.0 0.0
0400 25.8 24.8 54 481.4 5161.2 5119.3 5914.3 0.0 0.0
0500 25.7 24.7 53 481.4 5287.9 5326.0 6125.7 0.0 0.0
0600 25.9 24.7 52 481.4 5510.1 5495.0 6294.4 0.0 0.0
0700 26.5 25.0 52 481.4 5664.1 5479.8 6274.3 0.0 0.0
0800 27.5 25.0 51 481.4 5760.1 5610.0 6406.6 0.0 0.0
0900 29.0 25.0 51 481.4 5795.4 5664.5 6459.2 0.0 0.0
1000 30.7 24.9 51 481.4 5802.7 5686.4 6480.9 0.0 0.0
1100 32.6 24.8 50 481.4 5849.5 5802.4 6597.7 0.0 0.0
1200 34.4 25.0 50 481.4 5898.4 5736.9 6529.8 0.0 0.0
1300 35.8 25.0 50 481.4 5924.7 5795.6 6588.5 0.0 0.0
1400 36.7 25.0 50 481.4 5928.1 5813.5 6606.5 0.0 0.0
1500 37.0 24.8 49 481.4 5921.6 5892.7 6686.8 0.0 0.0
1600 36.7 25.0 50 481.4 5899.2 5737.9 6528.7 0.0 0.0
1700 35.9 25.0 50 481.4 5859.2 5745.0 6547.8 0.0 0.0
1800 34.6 25.0 51 481.4 5785.5 5685.6 6476.7 0.0 0.0
1900 33.2 24.9 51 481.4 5696.3 5609.0 6401.5 0.0 0.0
2000 31.7 24.9 52 481.4 5606.5 5529.8 6321.9 0.0 0.0
2100 30.4 24.9 52 481.4 5526.6 5458.7 6252.3 0.0 0.0
2200 29.3 24.9 53 481.4 5452.1 5391.4 6184.8 0.0 0.0
2300 28.4 24.9 53 481.4 5387.5 5332.7 6127.6 0.0 0.0

ZONE: F1-07 Meeting Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 55 282.1 2894.7 2852.3 3617.0 0.0 0.0
0100 27.2 24.9 56 282.1 2862.1 2811.1 3567.0 0.0 0.0
0200 26.6 24.7 55 282.1 2830.8 2855.6 3648.7 0.0 0.0
0300 26.2 24.9 57 282.1 2803.1 2745.8 3485.1 0.0 0.0
0400 25.8 24.6 56 282.1 2779.2 2807.5 3592.9 0.0 0.0
0500 25.7 24.6 55 282.1 2810.2 2840.8 3638.8 0.0 0.0
0600 25.9 24.7 55 282.1 2916.3 2901.2 3700.5 0.0 0.0
0700 26.5 24.7 53 282.1 3032.0 3020.0 3848.0 0.0 0.0
0800 27.5 24.9 53 282.1 3143.5 3077.2 3902.3 0.0 0.0
0900 29.0 25.0 52 282.1 3233.3 3119.2 3941.6 0.0 0.0
1000 30.7 24.9 51 282.1 3287.2 3230.4 4087.3 0.0 0.0
1100 32.6 25.0 51 282.1 3308.6 3219.6 4063.5 0.0 0.0
1200 34.4 25.0 51 282.1 3321.2 3231.1 4075.3 0.0 0.0
1300 35.8 24.9 50 282.1 3324.1 3275.0 4167.9 0.0 0.0
1400 36.7 25.0 51 282.1 3313.1 3209.5 4102.6 0.0 0.0
1500 37.0 24.9 50 282.1 3300.4 3259.3 4199.7 0.0 0.0
1600 36.7 24.9 51 282.1 3280.0 3221.4 4133.6 0.0 0.0
1700 35.9 24.9 51 282.1 3249.1 3187.3 4052.6 0.0 0.0
1800 34.6 25.0 52 282.1 3197.4 3130.5 3954.3 0.0 0.0
1900 33.2 24.8 52 282.1 3137.4 3111.9 3949.4 0.0 0.0
2000 31.7 24.9 53 282.1 3077.4 3025.7 3826.8 0.0 0.0
2100 30.4 24.9 54 282.1 3024.0 2966.0 3754.2 0.0 0.0
2200 29.3 24.8 54 282.1 2974.5 2966.8 3780.6 0.0 0.0
2300 28.4 24.9 55 282.1 2931.3 2867.8 3634.5 0.0 0.0

Hourly Analysis Program v4.80 Page 166 of 773


System Psychrometrics for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 302 400 4027 849
Vent - Return Mixing Outlet 37.0 0.01203 302 0 - -
Vent. Heating Coil Outlet 37.0 0.01203 302 400 0 -
Ventilation Fan Outlet 37.0 0.01203 302 400 0 -
Cold Supply Duct Outlet 37.0 0.01203 302 400 0 -
Zone Air - 24.9 0.01099 302 1900 36462 5950
Return Plenum Outlet 24.9 0.01099 302 1900 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

Hourly Analysis Program v4.80 Page 167 of 773


System Psychrometrics for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
F1-11 Admin Support (
Cooling )
Ventilation Air - - - 74 - - -
Cooling Coil Inlet - 26.2 0.01119 643 0 - -
Cooling Coil Outlet - 13.8 0.00996 643 0 8842 2132
Heating Coil Inlet - 13.8 0.00996 643 0 - -
Heating Coil Outlet - 13.8 0.00996 643 0 0 -
Zone Air - 24.8 0.01109 643 1476 7856 -
F1-09 EAM Room ( Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 26.4 0.01106 88 0 - -
Cooling Coil Outlet - 14.1 0.01015 88 0 1195 217
Heating Coil Inlet - 14.1 0.01015 88 0 - -
Heating Coil Outlet - 14.1 0.01015 88 0 0 -
Zone Air - 24.9 0.01092 88 1931 1046 -
F1-51 Director of F&B (
Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 26.2 0.01092 96 0 - -
Cooling Coil Outlet - 14.1 0.01019 96 0 1278 188
Heating Coil Inlet - 14.1 0.01019 96 0 - -
Heating Coil Outlet - 14.1 0.01019 96 0 0 -
Zone Air - 24.9 0.01078 96 2018 1138 -
F1-06 DIR of Revenue (
Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 26.0 0.01091 105 0 - -
Cooling Coil Outlet - 14.1 0.01018 105 0 1368 204
Heating Coil Inlet - 14.1 0.01018 105 0 - -
Heating Coil Outlet - 14.1 0.01018 105 0 0 -
Zone Air - 24.7 0.01077 105 1973 1222 -
F1-05 DIR of Public Rel (
Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 26.2 0.01134 105 0 - -
Cooling Coil Outlet - 14.8 0.01067 105 0 1319 189
Heating Coil Inlet - 14.8 0.01067 105 0 - -
Heating Coil Outlet - 14.8 0.01067 105 0 0 -
Zone Air - 25.0 0.01126 105 1973 1177 -
F1-04 DIR Cater & Confe (
Cooling )
Ventilation Air - - - 10 - - -
Cooling Coil Inlet - 26.2 0.01126 100 0 - -
Cooling Coil Outlet - 14.8 0.01066 100 0 1256 160
Heating Coil Inlet - 14.8 0.01066 100 0 - -
Heating Coil Outlet - 14.8 0.01066 100 0 0 -
Zone Air - 25.0 0.01117 100 2066 1120 -
F1-14 Chief Accountant (
Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 26.7 0.01136 80 0 - -
Cooling Coil Outlet - 14.5 0.01047 80 0 1066 189
Heating Coil Inlet - 14.5 0.01047 80 0 - -
Heating Coil Outlet - 14.5 0.01047 80 0 0 -
Zone Air - 25.0 0.01125 80 1973 924 -
F1-12 Director of M&S (
Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 26.2 0.01093 97 0 - -
Cooling Coil Outlet - 14.2 0.01021 97 0 1286 187
Heating Coil Inlet - 14.2 0.01021 97 0 - -
Heating Coil Outlet - 14.2 0.01021 97 0 0 -
Zone Air - 24.9 0.01079 97 2018 1147 -

Hourly Analysis Program v4.80 Page 168 of 773


System Psychrometrics for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
F1-20 Cashier ( Cooling )
Ventilation Air - - - 5 - - -
Cooling Coil Inlet - 25.8 0.01121 64 0 - -
Cooling Coil Outlet - 14.6 0.01054 64 0 798 117
Heating Coil Inlet - 14.6 0.01054 64 0 - -
Heating Coil Outlet - 14.6 0.01054 64 0 0 -
Zone Air - 25.0 0.01115 64 1631 737 -
F18- DIR of Finance ( Cooling )
Ventilation Air - - - 10 - - -
Cooling Coil Inlet - 26.0 0.01071 102 0 - -
Cooling Coil Outlet - 14.0 0.01006 102 0 1357 178
Heating Coil Inlet - 14.0 0.01006 102 0 - -
Heating Coil Outlet - 14.0 0.01006 102 0 0 -
Zone Air - 24.8 0.01056 102 2066 1221 -
F1-15 Assitant Control (
Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 26.5 0.01110 82 0 - -
Cooling Coil Outlet - 14.1 0.01020 82 0 1115 199
Heating Coil Inlet - 14.1 0.01020 82 0 - -
Heating Coil Outlet - 14.1 0.01020 82 0 0 -
Zone Air - 24.9 0.01095 82 1973 971 -
F1-13 Reception Area (
Cooling )
Ventilation Air - - - 24 - - -
Cooling Coil Inlet - 27.3 0.01122 122 0 - -
Cooling Coil Outlet - 13.9 0.01000 122 0 1798 399
Heating Coil Inlet - 13.9 0.01000 122 0 - -
Heating Coil Outlet - 13.9 0.01000 122 0 0 -
Zone Air - 24.9 0.01101 122 2045 1476 -
F1-08 General Manager (
Cooling )
Ventilation Air - - - 24 - - -
Cooling Coil Inlet - 26.4 0.01103 179 0 - -
Cooling Coil Outlet - 14.2 0.01024 179 0 2407 381
Heating Coil Inlet - 14.2 0.01024 179 0 - -
Heating Coil Outlet - 14.2 0.01024 179 0 0 -
Zone Air - 24.8 0.01087 179 2087 2092 -
F1-10 Quality Manager (
Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 26.4 0.01110 88 0 - -
Cooling Coil Outlet - 14.1 0.01019 88 0 1187 215
Heating Coil Inlet - 14.1 0.01019 88 0 - -
Heating Coil Outlet - 14.1 0.01019 88 0 0 -
Zone Air - 24.9 0.01096 88 1931 1039 -
F1-03 Call Center ( Cooling )
Ventilation Air - - - 13 - - -
Cooling Coil Inlet - 26.1 0.01094 164 0 - -
Cooling Coil Outlet - 14.6 0.01049 164 0 2078 194
Heating Coil Inlet - 14.6 0.01049 164 0 - -
Heating Coil Outlet - 14.6 0.01049 164 0 0 -
Zone Air - 25.2 0.01084 164 2142 1909 -
F1-01 Reservation Mngr (
Cooling )
Ventilation Air - - - 10 - - -
Cooling Coil Inlet - 26.1 0.01112 104 0 - -
Cooling Coil Outlet - 14.8 0.01065 104 0 1298 131
Heating Coil Inlet - 14.8 0.01065 104 0 - -
Heating Coil Outlet - 14.8 0.01065 104 0 0 -
Zone Air - 25.0 0.01102 104 2170 1171 -
F1-02 Reservation ( Cooling )
Ventilation Air - - - 10 - - -
Cooling Coil Inlet - 26.7 0.01137 64 0 - -

Hourly Analysis Program v4.80 Page 169 of 773


System Psychrometrics for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Cooling Coil Outlet - 14.5 0.01046 64 0 859 158
Heating Coil Inlet - 14.5 0.01046 64 0 - -
Heating Coil Outlet - 14.5 0.01046 64 0 0 -
Zone Air - 24.7 0.01125 64 2066 721 -
F1-21 Counting Room (
Cooling )
Ventilation Air - - - 4 - - -
Cooling Coil Inlet - 26.3 0.01137 31 0 - -
Cooling Coil Outlet - 14.6 0.01055 31 0 394 68
Heating Coil Inlet - 14.6 0.01055 31 0 - -
Heating Coil Outlet - 14.6 0.01055 31 0 0 -
Zone Air - 24.8 0.01128 31 1931 344 -
F1-16 Chief Accountant (
Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24.8 0.01058 481 0 - -
Cooling Coil Outlet - 13.7 0.00996 481 0 5893 794
Heating Coil Inlet - 13.7 0.00996 481 0 - -
Heating Coil Outlet - 13.7 0.00996 481 0 0 -
Zone Air - 24.8 0.01057 481 0 5893 -
F1-07 Meeting Room ( Cooling
)
Ventilation Air - - - 33 - - -
Cooling Coil Inlet - 26.3 0.01102 282 0 - -
Cooling Coil Outlet - 14.4 0.01036 282 0 3697 503
Heating Coil Inlet - 14.4 0.01036 282 0 - -
Heating Coil Outlet - 14.4 0.01036 282 0 0 -
Zone Air - 24.9 0.01088 282 2126 3259 -

Hourly Analysis Program v4.80 Page 170 of 773


Hourly Air System Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Data for July

Total Cooling Total Heating

45

40

35

30
Load ( kW )

25

20

15

10

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 171 of 773


Hourly Zone Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Zone: F1-11 Admin Support


Data for July

Zone Sensible Zone Conditioning


8000

7000

6000

5000
W

4000

3000

2000

1000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-09 EAM Room


Data for July

Zone Sensible Zone Conditioning


1100
1000
900
800
700
600
W

500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 172 of 773


Hourly Zone Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Zone: F1-51 Director of F&B


Data for July

Zone Sensible Zone Conditioning


1200
1100
1000
900
800
700
W

600
500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-06 DIR of Revenue


Data for July

Zone Sensible Zone Conditioning

1200
1100
1000
900
800
700
W

600
500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 173 of 773


Hourly Zone Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Zone: F1-05 DIR of Public Rel


Data for July

Zone Sensible Zone Conditioning

1200
1100
1000
900
800
700
W

600
500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-04 DIR Cater & Confe


Data for July

Zone Sensible Zone Conditioning


1200
1100
1000
900
800
700
W

600
500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 174 of 773


Hourly Zone Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Zone: F1-14 Chief Accountant


Data for July

Zone Sensible Zone Conditioning


1000

900

800

700

600
W

500

400

300

200

100

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-12 Director of M&S


Data for July

Zone Sensible Zone Conditioning


1200
1100
1000
900
800
700
W

600
500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 175 of 773


Hourly Zone Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Zone: F1-20 Cashier


Data for July

Zone Sensible Zone Conditioning


800

700

600

500
W

400

300

200

100

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F18- DIR of Finance


Data for July

Zone Sensible Zone Conditioning

1200
1100
1000
900
800
700
W

600
500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 176 of 773


Hourly Zone Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Zone: F1-15 Assitant Control


Data for July

Zone Sensible Zone Conditioning


1000

900

800

700

600
W

500

400

300

200

100

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-13 Reception Area


Data for July

Zone Sensible Zone Conditioning

1400

1200

1000

800
W

600

400

200

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 177 of 773


Hourly Zone Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Zone: F1-08 General Manager


Data for July

Zone Sensible Zone Conditioning


2200
2000
1800
1600
1400
1200
W

1000
800
600
400
200
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-10 Quality Manager


Data for July

Zone Sensible Zone Conditioning


1100
1000
900
800
700
600
W

500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 178 of 773


Hourly Zone Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Zone: F1-03 Call Center


Data for July

Zone Sensible Zone Conditioning


2000

1800

1600

1400

1200
W

1000

800

600

400

200

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-01 Reservation Mngr


Data for July

Zone Sensible Zone Conditioning


1200
1100
1000
900
800
700
W

600
500
400
300
200
100
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 179 of 773


Hourly Zone Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Zone: F1-02 Reservation


Data for July

Zone Sensible Zone Conditioning

700

600

500

400
W

300

200

100

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-21 Counting Room


Data for July

Zone Sensible Zone Conditioning

350

300

250

200
W

150

100

50

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 180 of 773


Hourly Zone Design Day Loads for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Zone: F1-16 Chief Accountant


Data for July

Zone Sensible Zone Conditioning


6000
5500
5000
4500
4000
3500
W

3000
2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Zone: F1-07 Meeting Room


Data for July

Zone Sensible Zone Conditioning

3000

2500

2000
W

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 181 of 773


Psychrometric Analysis for FCU - F2 - Administrative Areas
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program v4.80 Page 182 of 773


Air System Sizing Summary for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Air System Information


Air System Name FCU - Junior Suit B Number of zones 1
Equipment Class TERM Floor Area 56.0 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max L/s 0 L/s Fan motor BHP 0.00 BHP
Standard L/s 0 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 0.00 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.80 Page 183 of 773


Zone Sizing Summary for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

Air System Information


Air System Name FCU - Junior Suit B Number of zones 1
Equipment Class TERM Floor Area 56.0 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Junior Suit 2.8 224 224 Jun 1400 2.4 56.0 3.99

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 6.7 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Junior Suit 2.6 2.6 25.0 / 12.6 14.3 / 8.2 0.09 Jun 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.0 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Junior Suit 2.2 20.5 / 29.6 0.05 224 0.056 0.045 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Junior Suit
NTYP. Junior Suit B 1 2.8 Jun 1400 224 2.4 56.0 3.99

Hourly Analysis Program v4.80 Page 184 of 773


Ventilation Sizing Summary for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Junior Suit
NTYP. Junior Suit B 1 56.0 2.0 223.6 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 223.6 0.0

Hourly Analysis Program v4.80 Page 185 of 773


Air System Design Load Summary for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:55PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 22.0 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 602 - 14 m² - -
Wall Transmission 13 m² 104 - 13 m² 103 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 290 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 61 m² 373 - 61 m² 1159 -
Ceiling 56 m² 108 - 56 m² 336 -
Overhead Lighting 784 W 784 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 250 7 10% 221 0
>> Total Zone Loads - 2745 77 - 2426 0
Zone Conditioning - 2581 77 - 2278 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 45 - - -45 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2626 77 - 2233 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 2626 0 - 0 0
Terminal Unit Heating - 0 - - 2233 -
>> Total Conditioning - 2626 0 - 2233 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 186 of 773


Zone Design Load Summary for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

Junior Suit DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 630 - 14 m² - -
Wall Transmission 13 m² 104 - 13 m² 103 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 280 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 61 m² 366 - 61 m² 1159 -
Ceiling 56 m² 106 - 56 m² 336 -
Overhead Lighting 784 W 784 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 251 7 10% 221 0
>> Total Zone Loads - 2756 77 - 2426 0

Hourly Analysis Program v4.80 Page 187 of 773


Space Design Load Summary for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' NTYP. Junior Suit B '' IN ZONE '' Junior Suit ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.1 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 630 - 14 m² - -
Wall Transmission 13 m² 104 - 13 m² 103 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 280 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 61 m² 366 - 61 m² 1159 -
Ceiling 56 m² 106 - 56 m² 336 -
Overhead Lighting 784 W 784 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 251 7 10% 221 0
>> Total Zone Loads - 2756 77 - 2426 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' NTYP. Junior Suit B '' IN ZONE '' Junior Suit ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 13 0.365 - 104 - 103
WINDOW 1 14 1.990 0.300 280 630 607

Hourly Analysis Program v4.80 Page 188 of 773


Hourly Air System Design Day Loads for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

DESIGN MONTH: JULY


COMMON CENTRAL CENTRAL CENTRAL VENT VENT ZONE
OA VENT COOLING COOLING HEATING COOLING HEATING TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 0 0.0 0.0 0.0 0.0 0.0 1.8 0.0 0.0
0100 27.2 0 0.0 0.0 0.0 0.0 0.0 1.7 0.0 0.0
0200 26.6 0 0.0 0.0 0.0 0.0 0.0 1.7 0.0 0.0
0300 26.2 0 0.0 0.0 0.0 0.0 0.0 1.6 0.0 0.0
0400 25.8 0 0.0 0.0 0.0 0.0 0.0 1.6 0.0 0.0
0500 25.7 0 0.0 0.0 0.0 0.0 0.0 1.7 0.0 0.0
0600 25.9 0 0.0 0.0 0.0 0.0 0.0 2.0 0.0 0.0
0700 26.5 0 0.0 0.0 0.0 0.0 0.0 2.1 0.0 0.0
0800 27.5 0 0.0 0.0 0.0 0.0 0.0 2.3 0.0 0.0
0900 29.0 0 0.0 0.0 0.0 0.0 0.0 2.3 0.0 0.0
1000 30.7 0 0.0 0.0 0.0 0.0 0.0 2.3 0.0 0.0
1100 32.6 0 0.0 0.0 0.0 0.0 0.0 2.4 0.0 0.0
1200 34.4 0 0.0 0.0 0.0 0.0 0.0 2.5 0.0 0.0
1300 35.8 0 0.0 0.0 0.0 0.0 0.0 2.6 0.0 0.0
1400 36.7 0 0.0 0.0 0.0 0.0 0.0 2.6 0.0 0.0
1500 37.0 0 0.0 0.0 0.0 0.0 0.0 2.6 0.0 0.0
1600 36.7 0 0.0 0.0 0.0 0.0 0.0 2.6 0.0 0.0
1700 35.9 0 0.0 0.0 0.0 0.0 0.0 2.5 0.0 0.0
1800 34.6 0 0.0 0.0 0.0 0.0 0.0 2.4 0.0 0.0
1900 33.2 0 0.0 0.0 0.0 0.0 0.0 2.3 0.0 0.0
2000 31.7 0 0.0 0.0 0.0 0.0 0.0 2.2 0.0 0.0
2100 30.4 0 0.0 0.0 0.0 0.0 0.0 2.1 0.0 0.0
2200 29.3 0 0.0 0.0 0.0 0.0 0.0 2.0 0.0 0.0
2300 28.4 0 0.0 0.0 0.0 0.0 0.0 1.9 0.0 0.0

Hourly Analysis Program v4.80 Page 189 of 773


Hourly Zone Loads for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

ZONE: Junior Suit


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 24 223.6 1814.9 1791.2 1835.9 0.0 0.0
0100 27.2 24.6 24 223.6 1738.5 1655.4 1700.1 0.0 0.0
0200 26.6 24.5 24 223.6 1663.5 1658.7 1703.4 0.0 0.0
0300 26.2 24.5 24 223.6 1597.9 1593.8 1638.6 0.0 0.0
0400 25.8 24.5 24 223.6 1541.8 1534.7 1579.4 0.0 0.0
0500 25.7 24.6 24 223.6 1737.2 1667.5 1712.2 0.0 0.0
0600 25.9 24.7 24 223.6 2059.7 1920.6 1965.3 0.0 0.0
0700 26.5 24.7 24 223.6 2254.8 2084.8 2129.5 0.0 0.0
0800 27.5 24.7 24 223.6 2371.3 2235.1 2279.9 0.0 0.0
0900 29.0 24.8 24 223.6 2421.2 2219.1 2263.8 0.0 0.0
1000 30.7 24.7 24 223.6 2452.2 2266.6 2311.3 0.0 0.0
1100 32.6 24.8 24 223.6 2563.1 2351.0 2395.7 0.0 0.0
1200 34.4 24.8 24 223.6 2677.8 2451.8 2496.5 0.0 0.0
1300 35.8 24.8 24 223.6 2738.4 2538.2 2582.9 0.0 0.0
1400 36.7 24.8 24 223.6 2747.6 2519.7 2564.5 0.0 0.0
1500 37.0 24.8 24 223.6 2739.5 2539.4 2584.1 0.0 0.0
1600 36.7 24.8 24 223.6 2707.6 2561.2 2605.9 0.0 0.0
1700 35.9 24.8 24 223.6 2651.1 2452.9 2497.6 0.0 0.0
1800 34.6 24.8 24 223.6 2539.6 2382.8 2427.5 0.0 0.0
1900 33.2 24.7 24 223.6 2396.9 2268.5 2313.2 0.0 0.0
2000 31.7 24.7 24 223.6 2252.5 2151.9 2196.6 0.0 0.0
2100 30.4 24.7 24 223.6 2124.2 2045.2 2089.9 0.0 0.0
2200 29.3 24.6 24 223.6 2004.2 1944.0 1988.7 0.0 0.0
2300 28.4 24.7 24 223.6 1900.9 1806.4 1851.1 0.0 0.0

Hourly Analysis Program v4.80 Page 190 of 773


System Psychrometrics for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 0 400 0 0
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Vent. Cooling Coil Outlet -17.8 0.00000 0 0 0 0
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - -17.8 0.00000 0 0 2539 77
Return Plenum Outlet -1.1 0.00000 0 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Junior Suit ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 25.0 0.00490 224 0 - -
Cooling Coil Outlet - 14.5 0.00490 224 0 2584 0
Heating Coil Inlet - 14.5 0.00490 224 0 - -
Heating Coil Outlet - 14.5 0.00490 224 0 0 -
Zone Air - 24.8 0.00503 224 0 2539 -

Hourly Analysis Program v4.80 Page 191 of 773


Hourly Air System Design Day Loads for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

Data for July

Total Cooling Total Heating

2.5

2.0
Load ( kW )

1.5

1.0

0.5

0.0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.80 Page 192 of 773


Hourly Zone Design Day Loads for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

Zone: Junior Suit


Data for July

Zone Sensible Zone Conditioning

2500

2000

1500
W

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 193 of 773


Psychrometric Analysis for FCU - Junior Suit B
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program v4.80 Page 194 of 773


Air System Sizing Summary for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

Air System Information


Air System Name FCU - Junior Suit T Number of zones 1
Equipment Class TERM Floor Area 56.0 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Cooling Coil Sizing Data


No cooling coil loads occurred during this calculation.

Ventilation Fan Sizing Data


Actual max L/s 0 L/s Fan motor BHP 0.00 BHP
Standard L/s 0 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 0.00 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.80 Page 195 of 773


Air System Sizing Summary for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

Air System Information


Air System Name FCU - Junior Suit T Number of zones 1
Equipment Class TERM Floor Area 56.0 m²
Air System Type 4P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Junior Suit 3.5 287 287 Sep 1500 2.4 56.0 5.13

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 6.7 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Junior Suit 3.3 3.3 25.0 / 11.6 14.5 / 7.1 0.12 Sep 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.0 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Junior Suit 2.2 20.6 / 27.7 0.05 287 0.072 0.057 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Junior Suit
NTYP. Junior Suit T 1 3.5 Sep 1500 287 2.4 56.0 5.13

Hourly Analysis Program v4.80 Page 196 of 773


Ventilation Sizing Summary for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Junior Suit
NTYP. Junior Suit T 1 56.0 2.0 287.4 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 287.4 0.0

Hourly Analysis Program v4.80 Page 197 of 773


Air System Design Load Summary for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:56PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1253 - 14 m² - -
Wall Transmission 13 m² 204 - 13 m² 103 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 275 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 61 m² 364 - 61 m² 1159 -
Ceiling 56 m² 106 - 56 m² 336 -
Overhead Lighting 784 W 784 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 322 7 10% 221 0
>> Total Zone Loads - 3542 77 - 2426 0
Zone Conditioning - 3261 77 - 2288 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 57 - - -57 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3318 77 - 2231 0
Cooling Coil - 0 0 - 0 0
Terminal Unit Cooling - 3318 0 - 0 0
Terminal Unit Heating - 0 - - 2231 -
>> Total Conditioning - 3318 0 - 2231 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 198 of 773


Zone Design Load Summary for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

Junior Suit DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1253 - 14 m² - -
Wall Transmission 13 m² 204 - 13 m² 103 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 275 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 61 m² 364 - 61 m² 1159 -
Ceiling 56 m² 106 - 56 m² 336 -
Overhead Lighting 784 W 784 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 322 7 10% 221 0
>> Total Zone Loads - 3542 77 - 2426 0

Hourly Analysis Program v4.80 Page 199 of 773


Space Design Load Summary for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' NTYP. Junior Suit T '' IN ZONE '' Junior Suit ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.4 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1253 - 14 m² - -
Wall Transmission 13 m² 204 - 13 m² 103 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 275 - 14 m² 607 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 61 m² 364 - 61 m² 1159 -
Ceiling 56 m² 106 - 56 m² 336 -
Overhead Lighting 784 W 784 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100 W 100 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 322 7 10% 221 0
>> Total Zone Loads - 3542 77 - 2426 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' NTYP. Junior Suit T '' IN ZONE '' Junior Suit ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 13 0.365 - 204 - 103
WINDOW 1 14 1.990 0.300 275 1253 607

Hourly Analysis Program v4.80 Page 200 of 773


Hourly Air System Design Day Loads for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

DESIGN MONTH: JULY


COMMON CENTRAL CENTRAL CENTRAL VENT VENT ZONE
OA VENT COOLING COOLING HEATING COOLING HEATING TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 0 0.0 0.0 0.0 0.0 0.0 2.0 0.0 0.0
0100 27.2 0 0.0 0.0 0.0 0.0 0.0 1.9 0.0 0.0
0200 26.6 0 0.0 0.0 0.0 0.0 0.0 1.8 0.0 0.0
0300 26.2 0 0.0 0.0 0.0 0.0 0.0 1.7 0.0 0.0
0400 25.8 0 0.0 0.0 0.0 0.0 0.0 1.6 0.0 0.0
0500 25.7 0 0.0 0.0 0.0 0.0 0.0 1.7 0.0 0.0
0600 25.9 0 0.0 0.0 0.0 0.0 0.0 1.7 0.0 0.0
0700 26.5 0 0.0 0.0 0.0 0.0 0.0 1.7 0.0 0.0
0800 27.5 0 0.0 0.0 0.0 0.0 0.0 1.8 0.0 0.0
0900 29.0 0 0.0 0.0 0.0 0.0 0.0 1.9 0.0 0.0
1000 30.7 0 0.0 0.0 0.0 0.0 0.0 2.0 0.0 0.0
1100 32.6 0 0.0 0.0 0.0 0.0 0.0 2.2 0.0 0.0
1200 34.4 0 0.0 0.0 0.0 0.0 0.0 2.4 0.0 0.0
1300 35.8 0 0.0 0.0 0.0 0.0 0.0 2.7 0.0 0.0
1400 36.7 0 0.0 0.0 0.0 0.0 0.0 2.9 0.0 0.0
1500 37.0 0 0.0 0.0 0.0 0.0 0.0 3.0 0.0 0.0
1600 36.7 0 0.0 0.0 0.0 0.0 0.0 3.1 0.0 0.0
1700 35.9 0 0.0 0.0 0.0 0.0 0.0 2.9 0.0 0.0
1800 34.6 0 0.0 0.0 0.0 0.0 0.0 2.7 0.0 0.0
1900 33.2 0 0.0 0.0 0.0 0.0 0.0 2.5 0.0 0.0
2000 31.7 0 0.0 0.0 0.0 0.0 0.0 2.4 0.0 0.0
2100 30.4 0 0.0 0.0 0.0 0.0 0.0 2.3 0.0 0.0
2200 29.3 0 0.0 0.0 0.0 0.0 0.0 2.2 0.0 0.0
2300 28.4 0 0.0 0.0 0.0 0.0 0.0 2.1 0.0 0.0

Hourly Analysis Program v4.80 Page 201 of 773


Hourly Zone Loads for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

ZONE: Junior Suit


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.5 19 287.4 1949.7 1912.1 1969.6 0.0 0.0
0100 27.2 24.5 19 287.4 1863.6 1834.4 1891.9 0.0 0.0
0200 26.6 24.5 19 287.4 1779.9 1757.8 1815.3 0.0 0.0
0300 26.2 24.4 19 287.4 1706.4 1689.6 1747.1 0.0 0.0
0400 25.8 24.5 19 287.4 1643.1 1571.7 1629.2 0.0 0.0
0500 25.7 24.3 10 287.4 1616.6 1664.9 1722.3 0.0 0.0
0600 25.9 24.4 19 287.4 1639.3 1627.7 1685.2 0.0 0.0
0700 26.5 24.4 19 287.4 1691.5 1657.5 1715.0 0.0 0.0
0800 27.5 24.4 19 287.4 1782.5 1729.0 1786.5 0.0 0.0
0900 29.0 24.5 19 287.4 1911.1 1835.5 1893.0 0.0 0.0
1000 30.7 24.5 19 287.4 2065.8 1965.8 2023.3 0.0 0.0
1100 32.6 24.5 19 287.4 2269.3 2140.0 2197.5 0.0 0.0
1200 34.4 24.7 19 287.4 2565.3 2333.1 2390.6 0.0 0.0
1300 35.8 24.7 19 287.4 2832.9 2625.2 2682.7 0.0 0.0
1400 36.7 24.7 19 287.4 3028.5 2802.2 2859.7 0.0 0.0
1500 37.0 24.7 19 287.4 3155.2 2917.9 2975.3 0.0 0.0
1600 36.7 24.7 19 287.4 3179.5 2996.3 3053.7 0.0 0.0
1700 35.9 24.7 19 287.4 3067.5 2862.5 2920.0 0.0 0.0
1800 34.6 24.7 19 287.4 2807.1 2636.5 2694.0 0.0 0.0
1900 33.2 24.7 19 287.4 2627.6 2489.5 2547.0 0.0 0.0
2000 31.7 24.6 19 287.4 2451.2 2342.9 2400.4 0.0 0.0
2100 30.4 24.6 19 287.4 2300.2 2216.2 2273.7 0.0 0.0
2200 29.3 24.6 19 287.4 2163.4 2099.3 2156.8 0.0 0.0
2300 28.4 24.5 19 287.4 2046.8 1998.1 2055.6 0.0 0.0

Hourly Analysis Program v4.80 Page 202 of 773


System Psychrometrics for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 0 400 0 0
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Vent. Cooling Coil Outlet -17.8 0.00000 0 0 0 0
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - -17.8 0.00000 0 0 2918 77
Return Plenum Outlet -1.1 0.00000 0 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Junior Suit ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24.9 0.00381 287 0 - -
Cooling Coil Outlet - 15.5 0.00381 287 0 2975 0
Heating Coil Inlet - 15.5 0.00381 287 0 - -
Heating Coil Outlet - 15.5 0.00381 287 0 0 -
Zone Air - 24.7 0.00391 287 0 2918 -

Hourly Analysis Program v4.80 Page 203 of 773


Hourly Air System Design Day Loads for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

Data for July

Total Cooling Total Heating


3.0

2.5

2.0
Load ( kW )

1.5

1.0

0.5

0.0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.80 Page 204 of 773


Hourly Zone Design Day Loads for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

Zone: Junior Suit


Data for July

Zone Sensible Zone Conditioning

3000

2500

2000
W

1500

1000

500

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.80 Page 205 of 773


Psychrometric Analysis for FCU - Junior Suit T
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program v4.80 Page 206 of 773


Air System Sizing Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

Air System Information


Air System Name FCU - Mechanical Rooms Number of zones 31
Equipment Class TERM Floor Area 1788.9 m²
Air System Type 2P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Hourly Analysis Program v4.80 Page 207 of 773


Zone Sizing Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

Air System Information


Air System Name FCU - Mechanical Rooms Number of zones 31
Equipment Class TERM Floor Area 1788.9 m²
Air System Type 2P-FC Location Amman, Jordan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
C1-132 Mech Room 3.9 314 314 Jul 1600 3.7 102.0 3.08
C2-34 Ventilation Room 4.0 321 321 Jul 1700 2.7 60.0 5.35
C2-01 Mech Room 4.7 380 380 Jul 1700 2.9 71.0 5.35
C2-42 AHU Room 7.2 582 582 Jul 1700 5.2 186.0 3.13
C2-04 AHU Room 2.1 173 173 Jul 1700 2.3 69.0 2.51
C2-07 Ventilation Room 4.1 336 336 Jul 1700 1.3 27.0 12.45
C2-08 Indoor Swimming 4.7 381 381 Jul 1700 2.3 52.0 7.32
C2-20 Mech Room 1.5 121 121 Jul 1700 1.4 71.4 1.70
C2-15 Pump Room 6.5 530 530 Jul 1700 2.2 77.0 6.88
C2-28 Mech Room 1.3 106 106 Jul 1700 1.5 39.0 2.71
C2-19 Water Feature Pump 3.2 259 259 Jul 1700 1.0 35.0 7.39
C3-28 Ventilation Room 3.9 317 317 Jul 1700 2.3 69.0 4.59
C3-01 Ventilation Room 4.2 339 339 Jul 1700 1.6 42.0 8.07
C3-04 Outdoor Pool 5.1 413 413 Jul 1700 2.2 39.0 10.60
C3-05 Ventilation Room 4.1 336 336 Jul 1700 1.6 39.0 8.61
C3-09 Ventilation Room 3.8 309 309 Jul 1700 1.3 26.0 11.87
C3-15 Pump Room 7.0 566 566 Jul 1700 2.2 78.0 7.26
C3-18 AHU Room 4.5 364 364 Jul 1700 4.8 151.0 2.41
C3-26 Mech Room 2.3 188 188 Jul 1700 2.8 50.0 3.75
C3-31 AHU Room 2.3 183 183 Jul 1700 2.6 60.0 3.04
C3-29 Mech Room 2.6 213 213 Jul 1700 3.0 73.0 2.92
C3-25 AHURoom 1.6 129 129 Jul 1700 1.9 38.0 3.40
C3-12 Mech Room 1.6 131 131 Jul 1700 2.0 35.0 3.74
C4-26 Ventilation Room 3.9 317 317 Jul 1700 2.2 77.0 4.11
C4-06 Ventilation Room 3.9 316 316 Jul 1700 1.5 36.0 8.78
C4-10 Irrigation Pump 2.6 211 211 Jul 1700 1.1 26.0 8.11
C4-12 Ventilation Room 3.9 314 314 Jul 1700 1.3 25.0 12.56
GF-48 Mech Room 2.8 230 230 Aug 1700 3.3 38.0 6.06
C4-01 Ventilation Room 3.8 305 305 Jul 1700 1.3 34.5 8.84
C2-05 Water Feature BP 3.7 298 298 Jul 1700 1.7 37.0 8.06
C1-134 - Water Feature 3.4 279 279 Jul 1600 1.3 26.0 10.74

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 6.7 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
C1-132 Mech Room 3.5 3.5 24.8 / 7.4 14.8 / 2.5 0.12 Jul 1700
C2-34 Ventilation Room 3.8 3.8 24.7 / 7.4 14.0 / 2.1 0.14 Jul 1600
C2-01 Mech Room 4.5 4.5 24.8 / 7.4 14.0 / 2.0 0.16 Jul 1700
C2-42 AHU Room 6.7 6.7 24.8 / 7.4 14.3 / 2.2 0.24 Jul 1700
C2-04 AHU Room 1.9 1.9 24.8 / 7.4 14.7 / 2.4 0.07 Jun 1700
C2-07 Ventilation Room 4.4 4.4 25.0 / 7.6 13.2 / 1.6 0.16 Jan 0800
C2-08 Indoor Swimming 4.5 4.5 24.8 / 7.4 14.0 / 2.0 0.16 Jun 1600
C2-20 Mech Room 1.3 1.3 24.7 / 7.4 14.8 / 2.5 0.05 Jul 1300
C2-15 Pump Room 7.1 7.1 25.0 / 7.5 12.8 / 1.4 0.25 Jan 0800
C2-28 Mech Room 1.2 1.2 24.7 / 7.4 14.7 / 2.4 0.04 Jul 1800
C2-19 Water Feature Pump 3.5 3.5 25.1 / 7.6 12.8 / 1.4 0.13 Jan 0800
C3-28 Ventilation Room 3.7 3.7 24.8 / 7.4 14.1 / 2.1 0.13 Jul 1600

Hourly Analysis Program v4.80 Page 208 of 773


Zone Sizing Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 6.7 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
C3-01 Ventilation Room 4.1 4.1 24.7 / 7.4 13.8 / 2.0 0.15 Jul 1400
C3-04 Outdoor Pool 4.9 4.9 24.8 / 7.4 13.9 / 2.0 0.18 Jun 1700
C3-05 Ventilation Room 4.1 4.1 24.7 / 7.4 13.7 / 1.9 0.15 Jul 1600
C3-09 Ventilation Room 3.8 3.8 25.0 / 7.5 13.7 / 1.9 0.14 Jan 0800
C3-15 Pump Room 7.7 7.7 25.2 / 7.6 12.8 / 1.4 0.28 Jan 0800
C3-18 AHU Room 4.0 4.0 24.8 / 7.4 14.8 / 2.5 0.14 Jul 1600
C3-26 Mech Room 2.1 2.1 24.7 / 7.4 14.8 / 2.5 0.07 Jun 1700
C3-31 AHU Room 2.0 2.0 24.7 / 7.4 14.7 / 2.4 0.07 Jul 1600
C3-29 Mech Room 2.3 2.3 24.8 / 7.4 14.8 / 2.5 0.08 Jul 1700
C3-25 AHURoom 1.4 1.4 24.7 / 7.4 14.6 / 2.4 0.05 Jul 1700
C3-12 Mech Room 1.4 1.4 24.8 / 7.4 14.7 / 2.5 0.05 Jul 1700
C4-26 Ventilation Room 3.7 3.7 24.9 / 7.5 14.4 / 2.3 0.13 Jul 1600
C4-06 Ventilation Room 3.8 3.8 24.8 / 7.4 13.8 / 1.9 0.14 Jan 0800
C4-10 Irrigation Pump 2.5 2.5 24.8 / 7.4 13.9 / 2.0 0.09 Jul 1400
C4-12 Ventilation Room 3.9 3.9 25.0 / 7.5 13.7 / 1.9 0.14 Jan 0800
GF-48 Mech Room 2.6 2.6 24.8 / 7.4 14.7 / 2.4 0.09 Aug 1600
C4-01 Ventilation Room 3.9 3.9 24.9 / 7.5 13.2 / 1.6 0.14 Jan 0800
C2-05 Water Feature BP 3.5 3.5 24.8 / 7.4 14.0 / 2.1 0.13 Jul 1800
C1-134 - Water Feature 3.4 3.4 24.8 / 7.5 13.9 / 2.0 0.12 Jul 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.0 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
C1-132 Mech Room 3.6 20.4 / 30.9 0.08 314 0.000 0.000 0
C2-34 Ventilation Room 2.5 20.5 / 27.7 0.06 321 0.000 0.000 0
C2-01 Mech Room 2.8 20.6 / 27.2 0.06 380 0.000 0.000 0
C2-42 AHU Room 4.9 20.5 / 28.2 0.11 582 0.000 0.000 0
C2-04 AHU Room 2.2 20.3 / 31.8 0.05 173 0.000 0.000 0
C2-07 Ventilation Room 1.3 21.0 / 24.5 0.03 336 0.000 0.000 0
C2-08 Indoor Swimming 2.2 20.7 / 26.0 0.05 381 0.000 0.000 0
C2-20 Mech Room 1.2 20.3 / 29.6 0.03 121 0.000 0.000 0
C2-15 Pump Room 2.2 20.8 / 24.6 0.05 530 0.000 0.000 0
C2-28 Mech Room 1.3 20.2 / 31.6 0.03 106 0.000 0.000 0
C2-19 Water Feature Pump 1.0 20.8 / 24.5 0.02 259 0.000 0.000 0
C3-28 Ventilation Room 2.3 20.7 / 27.3 0.05 317 0.000 0.000 0
C3-01 Ventilation Room 1.6 20.8 / 25.1 0.03 339 0.000 0.000 0
C3-04 Outdoor Pool 2.2 20.9 / 25.6 0.05 413 0.000 0.000 0
C3-05 Ventilation Room 1.6 20.8 / 25.2 0.03 336 0.000 0.000 0
C3-09 Ventilation Room 1.3 20.7 / 24.5 0.03 309 0.000 0.000 0
C3-15 Pump Room 2.2 20.9 / 24.4 0.05 566 0.000 0.000 0
C3-18 AHU Room 4.4 20.2 / 31.3 0.10 364 0.000 0.000 0
C3-26 Mech Room 2.6 20.2 / 32.9 0.06 188 0.000 0.000 0
C3-31 AHU Room 2.4 20.1 / 31.9 0.05 183 0.000 0.000 0
C3-29 Mech Room 2.8 20.2 / 32.2 0.06 213 0.000 0.000 0
C3-25 AHURoom 1.8 20.2 / 32.7 0.04 129 0.000 0.000 0
C3-12 Mech Room 1.8 20.2 / 32.8 0.04 131 0.000 0.000 0
C4-26 Ventilation Room 2.1 20.5 / 26.4 0.04 317 0.000 0.000 0
C4-06 Ventilation Room 1.5 20.9 / 25.1 0.03 316 0.000 0.000 0
C4-10 Irrigation Pump 1.1 20.8 / 25.5 0.02 211 0.000 0.000 0
C4-12 Ventilation Room 1.2 20.6 / 24.1 0.03 314 0.000 0.000 0
GF-48 Mech Room 3.1 20.2 / 32.4 0.07 230 0.000 0.000 0
C4-01 Ventilation Room 1.3 20.8 / 24.8 0.03 305 0.000 0.000 0
C2-05 Water Feature BP 1.7 20.7 / 25.9 0.04 298 0.000 0.000 0
C1-134 - Water Feature 1.3 20.9 / 25.1 0.03 279 0.000 0.000 0

Space Loads and Airflows

Hourly Analysis Program v4.80 Page 209 of 773


Zone Sizing Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
C1-132 Mech Room
M-C1-132 Mech. Room 1 3.9 Jul 1600 314 3.7 102.0 3.08
C2-34 Ventilation Room
M-C2-34 Ventilation 1 4.0 Jul 1700 321 2.7 60.0 5.35
C2-01 Mech Room
M-C2-01 Mech Room 1 4.7 Jul 1700 380 2.9 71.0 5.35
C2-42 AHU Room
M-C2-42 AHU room 1 7.2 Jul 1700 582 5.2 186.0 3.13
C2-04 AHU Room
M-C2-04 AHU room 1 2.1 Jul 1700 173 2.3 69.0 2.51
C2-07 Ventilation Room
M-C2-07 Ventilation Rm 1 4.1 Jul 1700 336 1.3 27.0 12.45
C2-08 Indoor Swimming
M-C2-08 Indoor Swimming 1 4.7 Jul 1700 381 2.3 52.0 7.32
C2-20 Mech Room
M-C2-20 Mech. Room 1 1.5 Jul 1700 121 1.4 71.4 1.70
C2-15 Pump Room
M-C2-15 Pump Room 1 6.5 Jul 1700 530 2.2 77.0 6.88
C2-28 Mech Room
M-C2-28 Mech Room 1 1.3 Jul 1700 106 1.5 39.0 2.71
C2-19 Water Feature Pump
M-C2-19 Water Feature P 1 3.2 Jul 1700 259 1.0 35.0 7.39
C3-28 Ventilation Room
M-C3-28 Ventilation Rm 1 3.9 Jul 1700 317 2.3 69.0 4.59
C3-01 Ventilation Room
M-C3-01 Ventilation Rm 1 4.2 Jul 1700 339 1.6 42.0 8.07
C3-04 Outdoor Pool
M-C3-04 Outdoor Pool 1 5.1 Jul 1700 413 2.2 39.0 10.60
C3-05 Ventilation Room
M-C3-05 Ventilation Rm 1 4.1 Jul 1700 336 1.6 39.0 8.61
C3-09 Ventilation Room
M-C3-09 Ventilation Rm 1 3.8 Jul 1700 309 1.3 26.0 11.87
C3-15 Pump Room
M-C3-15 Pump Room 1 7.0 Jul 1700 566 2.2 78.0 7.26
C3-18 AHU Room
M-C3-18 AHU Room 1 4.5 Jul 1700 364 4.8 151.0 2.41
C3-26 Mech Room
M-C3-26 AHU Room 1 2.3 Jul 1700 188 2.8 50.0 3.75
C3-31 AHU Room
M-C3-31 AHU Room 1 2.3 Jul 1700 183 2.6 60.0 3.04
C3-29 Mech Room
M-C3-29 Mech. Room 1 2.6 Jul 1700 213 3.0 73.0 2.92
C3-25 AHURoom
M-C3-25 AHU Room 1 1.6 Jul 1700 129 1.9 38.0 3.40
C3-12 Mech Room
M-C3-12 Mech Room 1 1.6 Jul 1700 131 2.0 35.0 3.74
C4-26 Ventilation Room
M-C4-26 Ventilation Rm 1 3.9 Jul 1700 317 2.2 77.0 4.11
C4-06 Ventilation Room
M-C4-06 Ventilation Rm 1 3.9 Jul 1700 316 1.5 36.0 8.78
C4-10 Irrigation Pump
M-C4-10 Irrigation Pump 1 2.6 Jul 1700 211 1.1 26.0 8.11
C4-12 Ventilation Room
M-C4-12 Ventilation Rm 1 3.9 Jul 1700 314 1.3 25.0 12.56
GF-48 Mech Room
M-GF-48 Mech Room 1 2.8 Aug 1700 230 3.3 38.0 6.06
C4-01 Ventilation Room
M-C4-01 Ventilation Rm 1 3.8 Jul 1700 305 1.3 34.5 8.84
C2-05 Water Feature BP
M-C2-05 Water Feature P 1 3.7 Jul 1700 298 1.7 37.0 8.06
C1-134 - Water Feature
M-C1-134 Water Feature 1 3.4 Jul 1600 279 1.3 26.0 10.74

Hourly Analysis Program v4.80 Page 210 of 773


Zone Sizing Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:57PM

Hourly Analysis Program v4.80 Page 211 of 773


Ventilation Sizing Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
C1-132 Mech Room
M-C1-132 Mech. Room 1 102.0 0.0 313.8 0.00 0.00 0.0 0.0 0.0
C2-34 Ventilation Room
M-C2-34 Ventilation 1 60.0 0.0 320.9 0.00 0.00 0.0 0.0 0.0
C2-01 Mech Room
M-C2-01 Mech Room 1 71.0 0.0 380.1 0.00 0.00 0.0 0.0 0.0
C2-42 AHU Room
M-C2-42 AHU room 1 186.0 0.0 582.3 0.00 0.00 0.0 0.0 0.0
C2-04 AHU Room
M-C2-04 AHU room 1 69.0 0.0 173.4 0.00 0.00 0.0 0.0 0.0
C2-07 Ventilation Room
M-C2-07 Ventilation Rm 1 27.0 0.0 336.1 0.00 0.00 0.0 0.0 0.0
C2-08 Indoor Swimming
M-C2-08 Indoor Swimming 1 52.0 0.0 380.9 0.00 0.00 0.0 0.0 0.0
C2-20 Mech Room
M-C2-20 Mech. Room 1 71.4 0.0 121.5 0.00 0.00 0.0 0.0 0.0
C2-15 Pump Room
M-C2-15 Pump Room 1 77.0 0.0 530.1 0.00 0.00 0.0 0.0 0.0
C2-28 Mech Room
M-C2-28 Mech Room 1 39.0 0.0 105.6 0.00 0.00 0.0 0.0 0.0
C2-19 Water Feature Pump
M-C2-19 Water Feature P 1 35.0 0.0 258.7 0.00 0.00 0.0 0.0 0.0
C3-28 Ventilation Room
M-C3-28 Ventilation Rm 1 69.0 0.0 316.9 0.00 0.00 0.0 0.0 0.0
C3-01 Ventilation Room
M-C3-01 Ventilation Rm 1 42.0 0.0 338.9 0.00 0.00 0.0 0.0 0.0
C3-04 Outdoor Pool
M-C3-04 Outdoor Pool 1 39.0 0.0 413.2 0.00 0.00 0.0 0.0 0.0
C3-05 Ventilation Room
M-C3-05 Ventilation Rm 1 39.0 0.0 335.8 0.00 0.00 0.0 0.0 0.0
C3-09 Ventilation Room
M-C3-09 Ventilation Rm 1 26.0 0.0 308.7 0.00 0.00 0.0 0.0 0.0
C3-15 Pump Room
M-C3-15 Pump Room 1 78.0 0.0 566.5 0.00 0.00 0.0 0.0 0.0
C3-18 AHU Room
M-C3-18 AHU Room 1 151.0 0.0 363.6 0.00 0.00 0.0 0.0 0.0

Hourly Analysis Program v4.80 Page 212 of 773


Ventilation Sizing Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C3-26 Mech Room


M-C3-26 AHU Room 1 50.0 0.0 187.6 0.00 0.00 0.0 0.0 0.0
C3-31 AHU Room
M-C3-31 AHU Room 1 60.0 0.0 182.7 0.00 0.00 0.0 0.0 0.0
C3-29 Mech Room
M-C3-29 Mech. Room 1 73.0 0.0 213.4 0.00 0.00 0.0 0.0 0.0
C3-25 AHURoom
M-C3-25 AHU Room 1 38.0 0.0 129.2 0.00 0.00 0.0 0.0 0.0
C3-12 Mech Room
M-C3-12 Mech Room 1 35.0 0.0 130.7 0.00 0.00 0.0 0.0 0.0
C4-26 Ventilation Room
M-C4-26 Ventilation Rm 1 77.0 0.0 316.7 0.00 0.00 0.0 0.0 0.0
C4-06 Ventilation Room
M-C4-06 Ventilation Rm 1 36.0 0.0 316.0 0.00 0.00 0.0 0.0 0.0
C4-10 Irrigation Pump
M-C4-10 Irrigation Pump 1 26.0 0.0 210.8 0.00 0.00 0.0 0.0 0.0
C4-12 Ventilation Room
M-C4-12 Ventilation Rm 1 25.0 0.0 313.9 0.00 0.00 0.0 0.0 0.0
GF-48 Mech Room
M-GF-48 Mech Room 1 38.0 0.0 230.2 0.00 0.00 0.0 0.0 0.0
C4-01 Ventilation Room
M-C4-01 Ventilation Rm 1 34.5 0.0 305.0 0.00 0.00 0.0 0.0 0.0
C2-05 Water Feature BP
M-C2-05 Water Feature P 1 37.0 0.0 298.3 0.00 0.00 0.0 0.0 0.0
C1-134 - Water Feature
M-C1-134 Water Feature 1 26.0 0.0 279.4 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 9261.0 0.0

Hourly Analysis Program v4.80 Page 213 of 773


Air System Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 28 m² 375 - 28 m² 219 -
Roof Transmission 108 m² 1009 - 108 m² 545 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1216 m² 3781 - 1216 m² 5634 -
Partitions 2852 m² 36250 - 2852 m² 54194 -
Ceiling 313 m² 1256 - 313 m² 1878 -
Overhead Lighting 13238 W 13237 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 47523 0 - 0 0
Safety Factor 10% / 10% 10343 0 10% 6247 0
>> Total Zone Loads - 113775 0 - 68717 0
Zone Conditioning - 107382 0 - 65685 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 107382 0 - 65685 0
Terminal Unit Cooling - 107382 0 - 0 0
Terminal Unit Heating - 0 - - 65685 -
>> Total Conditioning - 107382 0 - 65685 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 214 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C1-132 Mech Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 82 m² 765 - 82 m² 413 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 102 m² 411 - 102 m² 612 -
Partitions 125 m² 1586 - 125 m² 2371 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 755 W 755 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 352 0 10% 340 0
>> Total Zone Loads - 3868 0 - 3736 0

C2-34 Ventilation Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 116 m² 1480 - 116 m² 2195 -
Ceiling 40 m² 162 - 40 m² 240 -
Overhead Lighting 444 W 444 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1511 0 - 0 0
Safety Factor 10% / 10% 360 0 10% 243 0
>> Total Zone Loads - 3956 0 - 2678 0

Hourly Analysis Program v4.80 Page 215 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C2-01 Mech Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 52 m² 211 - 52 m² 312 -
Partitions 116 m² 1486 - 116 m² 2204 -
Ceiling 13 m² 53 - 13 m² 78 -
Overhead Lighting 525 W 525 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1984 0 - 0 0
Safety Factor 10% / 10% 426 0 10% 259 0
>> Total Zone Loads - 4685 0 - 2853 0

C2-42 AHU Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 102 m² 414 - 102 m² 612 -
Partitions 215 m² 2754 - 215 m² 4085 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1376 W 1376 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1981 0 - 0 0
Safety Factor 10% / 10% 653 0 10% 470 0
>> Total Zone Loads - 7178 0 - 5167 0

Hourly Analysis Program v4.80 Page 216 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C2-04 AHU Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 69 m² 280 - 69 m² 414 -
Partitions 90 m² 1153 - 90 m² 1710 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 511 W 511 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 194 0 10% 212 0
>> Total Zone Loads - 2138 0 - 2336 0

C2-07 Ventilation Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 63 m² 807 - 63 m² 1197 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2759 0 - 0 0
Safety Factor 10% / 10% 377 0 10% 120 0
>> Total Zone Loads - 4142 0 - 1317 0

Hourly Analysis Program v4.80 Page 217 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C2-08 Indoor Swimming DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 52 m² 211 - 52 m² 312 -
Partitions 92 m² 1172 - 92 m² 1739 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 385 W 385 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2500 0 - 0 0
Safety Factor 10% / 10% 427 0 10% 205 0
>> Total Zone Loads - 4695 0 - 2256 0

C2-20 Mech Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 65 m² 833 - 65 m² 1235 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 528 W 528 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 136 0 10% 124 0
>> Total Zone Loads - 1497 0 - 1359 0

Hourly Analysis Program v4.80 Page 218 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C2-15 Pump Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 107 m² 1371 - 107 m² 2033 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 570 W 570 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4000 0 - 0 0
Safety Factor 10% / 10% 594 0 10% 203 0
>> Total Zone Loads - 6535 0 - 2236 0

C2-28 Mech Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 39 m² 158 - 39 m² 234 -
Partitions 58 m² 737 - 58 m² 1093 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 289 W 289 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 118 0 10% 133 0
>> Total Zone Loads - 1302 0 - 1459 0

Hourly Analysis Program v4.80 Page 219 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C2-19 Water Feature Pump DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 50 m² 641 - 50 m² 950 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2000 0 - 0 0
Safety Factor 10% / 10% 290 0 10% 95 0
>> Total Zone Loads - 3189 0 - 1045 0

C3-28 Ventilation Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 112 m² 1430 - 112 m² 2120 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 511 W 511 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1611 0 - 0 0
Safety Factor 10% / 10% 355 0 10% 212 0
>> Total Zone Loads - 3906 0 - 2332 0

Hourly Analysis Program v4.80 Page 220 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C3-01 Ventilation Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 78 m² 999 - 78 m² 1482 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 311 W 311 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2488 0 - 0 0
Safety Factor 10% / 10% 380 0 10% 148 0
>> Total Zone Loads - 4178 0 - 1630 0

C3-04 Outdoor Pool DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 39 m² 158 - 39 m² 234 -
Partitions 92 m² 1184 - 92 m² 1756 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 289 W 289 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3000 0 - 0 0
Safety Factor 10% / 10% 463 0 10% 199 0
>> Total Zone Loads - 5094 0 - 2189 0

Hourly Analysis Program v4.80 Page 221 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C3-05 Ventilation Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 77 m² 986 - 77 m² 1463 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 289 W 289 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2488 0 - 0 0
Safety Factor 10% / 10% 376 0 10% 146 0
>> Total Zone Loads - 4139 0 - 1609 0

C3-09 Ventilation Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 63 m² 807 - 63 m² 1197 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 192 W 192 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2460 0 - 0 0
Safety Factor 10% / 10% 346 0 10% 120 0
>> Total Zone Loads - 3805 0 - 1317 0

Hourly Analysis Program v4.80 Page 222 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C3-15 Pump Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 78 m² 0 - 78 m² 0 -
Partitions 107 m² 1371 - 107 m² 2033 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 577 W 577 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4400 0 - 0 0
Safety Factor 10% / 10% 635 0 10% 203 0
>> Total Zone Loads - 6983 0 - 2236 0

C3-18 AHU Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 151 m² 613 - 151 m² 906 -
Partitions 183 m² 2344 - 183 m² 3477 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1117 W 1117 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 407 0 10% 438 0
>> Total Zone Loads - 4482 0 - 4821 0

Hourly Analysis Program v4.80 Page 223 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C3-26 Mech Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 50 m² 203 - 50 m² 300 -
Partitions 104 m² 1327 - 104 m² 1968 -
Ceiling 50 m² 202 - 50 m² 300 -
Overhead Lighting 370 W 370 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 210 0 10% 257 0
>> Total Zone Loads - 2313 0 - 2825 0

C3-31 AHU Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 36 m² 146 - 36 m² 216 -
Partitions 95 m² 1214 - 95 m² 1801 -
Ceiling 60 m² 243 - 60 m² 360 -
Overhead Lighting 444 W 444 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 205 0 10% 238 0
>> Total Zone Loads - 2252 0 - 2615 0

Hourly Analysis Program v4.80 Page 224 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C3-29 Mech Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 73 m² 296 - 73 m² 438 -
Partitions 105 m² 1345 - 105 m² 1995 -
Ceiling 52 m² 210 - 52 m² 312 -
Overhead Lighting 540 W 540 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 239 0 10% 275 0
>> Total Zone Loads - 2631 0 - 3020 0

C3-25 AHURoom DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 38 m² 154 - 38 m² 228 -
Partitions 79 m² 1012 - 79 m² 1501 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 281 W 281 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 145 0 10% 173 0
>> Total Zone Loads - 1592 0 - 1902 0

Hourly Analysis Program v4.80 Page 225 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C3-12 Mech Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 35 m² 142 - 35 m² 210 -
Partitions 72 m² 922 - 72 m² 1368 -
Ceiling 35 m² 142 - 35 m² 210 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 146 0 10% 179 0
>> Total Zone Loads - 1611 0 - 1967 0

C4-26 Ventilation Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 77 m² 0 - 77 m² 0 -
Partitions 107 m² 1368 - 107 m² 2029 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 570 W 570 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1611 0 - 0 0
Safety Factor 10% / 10% 355 0 10% 203 0
>> Total Zone Loads - 3904 0 - 2232 0

Hourly Analysis Program v4.80 Page 226 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C4-06 Ventilation Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 36 m² 0 - 36 m² 0 -
Partitions 72 m² 922 - 72 m² 1368 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 266 W 266 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2352 0 - 0 0
Safety Factor 10% / 10% 354 0 10% 137 0
>> Total Zone Loads - 3895 0 - 1505 0

C4-10 Irrigation Pump DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 0 - 26 m² 0 -
Partitions 44 m² 565 - 44 m² 838 -
Ceiling 26 m² 105 - 26 m² 156 -
Overhead Lighting 192 W 192 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 10% / 10% 236 0 10% 99 0
>> Total Zone Loads - 2599 0 - 1093 0

Hourly Analysis Program v4.80 Page 227 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C4-12 Ventilation Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 25 m² 0 - 25 m² 0 -
Partitions 63 m² 807 - 63 m² 1197 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 185 W 185 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2526 0 - 0 0
Safety Factor 10% / 10% 352 0 10% 120 0
>> Total Zone Loads - 3870 0 - 1317 0

GF-48 Mech Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 28 m² 415 - 28 m² 219 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 38 m² 154 - 38 m² 228 -
Partitions 135 m² 1729 - 135 m² 2565 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 281 W 281 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 258 0 10% 301 0
>> Total Zone Loads - 2837 0 - 3313 0

Hourly Analysis Program v4.80 Page 228 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C4-01 Ventilation Room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 35 m² 0 - 35 m² 0 -
Partitions 63 m² 811 - 63 m² 1203 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 255 W 255 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2352 0 - 0 0
Safety Factor 10% / 10% 342 0 10% 120 0
>> Total Zone Loads - 3760 0 - 1323 0

C2-05 Water Feature BP DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 37 m² 150 - 37 m² 222 -
Partitions 60 m² 769 - 60 m² 1140 -
Ceiling 37 m² 150 - 37 m² 222 -
Overhead Lighting 274 W 274 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2000 0 - 0 0
Safety Factor 10% / 10% 334 0 10% 158 0
>> Total Zone Loads - 3676 0 - 1742 0

Hourly Analysis Program v4.80 Page 229 of 773


Zone Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 06:58PM

C1-134 - Water Feature DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 26 m² 244 - 26 m² 132 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 105 - 26 m² 156 -
Partitions 46 m² 590 - 46 m² 882 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 192 W 192 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2000 0 - 0 0
Safety Factor 10% / 10% 313 0 10% 117 0
>> Total Zone Loads - 3444 0 - 1286 0

Hourly Analysis Program v4.80 Page 230 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' M-C1-132 Mech. Room '' IN ZONE '' C1-132 Mech Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 82 m² 765 - 82 m² 413 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 102 m² 411 - 102 m² 612 -
Partitions 125 m² 1586 - 125 m² 2371 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 755 W 755 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 352 0 10% 340 0
>> Total Zone Loads - 3868 0 - 3736 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' M-C1-132 Mech. Room '' IN ZONE '' C1-132 Mech Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 82 0.232 - 765 - 413

Hourly Analysis Program v4.80 Page 231 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' M-C2-34 Ventilation '' IN ZONE '' C2-34 Ventilation Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 116 m² 1480 - 116 m² 2195 -
Ceiling 40 m² 162 - 40 m² 240 -
Overhead Lighting 444 W 444 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1511 0 - 0 0
Safety Factor 10% / 10% 360 0 10% 243 0
>> Total Zone Loads - 3956 0 - 2678 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-34 Ventilation '' IN ZONE '' C2-34 Ventilation Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 232 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' M-C2-01 Mech Room '' IN ZONE '' C2-01 Mech Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 52 m² 211 - 52 m² 312 -
Partitions 116 m² 1486 - 116 m² 2204 -
Ceiling 13 m² 53 - 13 m² 78 -
Overhead Lighting 525 W 525 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1984 0 - 0 0
Safety Factor 10% / 10% 426 0 10% 259 0
>> Total Zone Loads - 4685 0 - 2853 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-01 Mech Room '' IN ZONE '' C2-01 Mech Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 233 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' M-C2-42 AHU room '' IN ZONE '' C2-42 AHU Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 102 m² 414 - 102 m² 612 -
Partitions 215 m² 2754 - 215 m² 4085 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1376 W 1376 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1981 0 - 0 0
Safety Factor 10% / 10% 653 0 10% 470 0
>> Total Zone Loads - 7178 0 - 5167 0

TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-42 AHU room '' IN ZONE '' C2-42 AHU Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 234 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' M-C2-04 AHU room '' IN ZONE '' C2-04 AHU Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 69 m² 280 - 69 m² 414 -
Partitions 90 m² 1153 - 90 m² 1710 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 511 W 511 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 194 0 10% 212 0
>> Total Zone Loads - 2138 0 - 2336 0

TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-04 AHU room '' IN ZONE '' C2-04 AHU Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 235 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' M-C2-07 Ventilation Rm '' IN ZONE '' C2-07 Ventilation Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 63 m² 807 - 63 m² 1197 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2759 0 - 0 0
Safety Factor 10% / 10% 377 0 10% 120 0
>> Total Zone Loads - 4142 0 - 1317 0

TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-07 Ventilation Rm '' IN ZONE '' C2-07 Ventilation Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 236 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' M-C2-08 Indoor Swimming '' IN ZONE '' C2-08 Indoor Swimming ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 52 m² 211 - 52 m² 312 -
Partitions 92 m² 1172 - 92 m² 1739 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 385 W 385 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2500 0 - 0 0
Safety Factor 10% / 10% 427 0 10% 205 0
>> Total Zone Loads - 4695 0 - 2256 0

TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-08 Indoor Swimming '' IN ZONE '' C2-08 Indoor Swimming ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 237 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' M-C2-20 Mech. Room '' IN ZONE '' C2-20 Mech Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 65 m² 833 - 65 m² 1235 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 528 W 528 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 136 0 10% 124 0
>> Total Zone Loads - 1497 0 - 1359 0

TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-20 Mech. Room '' IN ZONE '' C2-20 Mech Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 238 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' M-C2-15 Pump Room '' IN ZONE '' C2-15 Pump Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 107 m² 1371 - 107 m² 2033 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 570 W 570 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4000 0 - 0 0
Safety Factor 10% / 10% 594 0 10% 203 0
>> Total Zone Loads - 6535 0 - 2236 0

TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-15 Pump Room '' IN ZONE '' C2-15 Pump Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 239 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 10.1.A. COMPONENT LOADS FOR SPACE '' M-C2-28 Mech Room '' IN ZONE '' C2-28 Mech Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 39 m² 158 - 39 m² 234 -
Partitions 58 m² 737 - 58 m² 1093 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 289 W 289 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 118 0 10% 133 0
>> Total Zone Loads - 1302 0 - 1459 0

TABLE 10.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-28 Mech Room '' IN ZONE '' C2-28 Mech Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 240 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 11.1.A. COMPONENT LOADS FOR SPACE '' M-C2-19 Water Feature P '' IN ZONE '' C2-19 Water Feature Pump ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 50 m² 641 - 50 m² 950 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2000 0 - 0 0
Safety Factor 10% / 10% 290 0 10% 95 0
>> Total Zone Loads - 3189 0 - 1045 0

TABLE 11.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-19 Water Feature P '' IN ZONE '' C2-19 Water Feature Pump ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 241 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 12.1.A. COMPONENT LOADS FOR SPACE '' M-C3-28 Ventilation Rm '' IN ZONE '' C3-28 Ventilation Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 112 m² 1430 - 112 m² 2120 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 511 W 511 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1611 0 - 0 0
Safety Factor 10% / 10% 355 0 10% 212 0
>> Total Zone Loads - 3906 0 - 2332 0

TABLE 12.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-28 Ventilation Rm '' IN ZONE '' C3-28 Ventilation Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 242 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 13.1.A. COMPONENT LOADS FOR SPACE '' M-C3-01 Ventilation Rm '' IN ZONE '' C3-01 Ventilation Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 78 m² 999 - 78 m² 1482 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 311 W 311 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2488 0 - 0 0
Safety Factor 10% / 10% 380 0 10% 148 0
>> Total Zone Loads - 4178 0 - 1630 0

TABLE 13.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-01 Ventilation Rm '' IN ZONE '' C3-01 Ventilation Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 243 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 14.1.A. COMPONENT LOADS FOR SPACE '' M-C3-04 Outdoor Pool '' IN ZONE '' C3-04 Outdoor Pool ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 39 m² 158 - 39 m² 234 -
Partitions 92 m² 1184 - 92 m² 1756 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 289 W 289 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3000 0 - 0 0
Safety Factor 10% / 10% 463 0 10% 199 0
>> Total Zone Loads - 5094 0 - 2189 0

TABLE 14.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-04 Outdoor Pool '' IN ZONE '' C3-04 Outdoor Pool ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 244 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 15.1.A. COMPONENT LOADS FOR SPACE '' M-C3-05 Ventilation Rm '' IN ZONE '' C3-05 Ventilation Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 77 m² 986 - 77 m² 1463 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 289 W 289 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2488 0 - 0 0
Safety Factor 10% / 10% 376 0 10% 146 0
>> Total Zone Loads - 4139 0 - 1609 0

TABLE 15.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-05 Ventilation Rm '' IN ZONE '' C3-05 Ventilation Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 245 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 16.1.A. COMPONENT LOADS FOR SPACE '' M-C3-09 Ventilation Rm '' IN ZONE '' C3-09 Ventilation Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 63 m² 807 - 63 m² 1197 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 192 W 192 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2460 0 - 0 0
Safety Factor 10% / 10% 346 0 10% 120 0
>> Total Zone Loads - 3805 0 - 1317 0

TABLE 16.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-09 Ventilation Rm '' IN ZONE '' C3-09 Ventilation Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 246 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 17.1.A. COMPONENT LOADS FOR SPACE '' M-C3-15 Pump Room '' IN ZONE '' C3-15 Pump Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 78 m² 0 - 78 m² 0 -
Partitions 107 m² 1371 - 107 m² 2033 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 577 W 577 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4400 0 - 0 0
Safety Factor 10% / 10% 635 0 10% 203 0
>> Total Zone Loads - 6983 0 - 2236 0

TABLE 17.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-15 Pump Room '' IN ZONE '' C3-15 Pump Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 247 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 18.1.A. COMPONENT LOADS FOR SPACE '' M-C3-18 AHU Room '' IN ZONE '' C3-18 AHU Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 151 m² 613 - 151 m² 906 -
Partitions 183 m² 2344 - 183 m² 3477 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1117 W 1117 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 407 0 10% 438 0
>> Total Zone Loads - 4482 0 - 4821 0

TABLE 18.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-18 AHU Room '' IN ZONE '' C3-18 AHU Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 248 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 19.1.A. COMPONENT LOADS FOR SPACE '' M-C3-26 AHU Room '' IN ZONE '' C3-26 Mech Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 50 m² 203 - 50 m² 300 -
Partitions 104 m² 1327 - 104 m² 1968 -
Ceiling 50 m² 202 - 50 m² 300 -
Overhead Lighting 370 W 370 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 210 0 10% 257 0
>> Total Zone Loads - 2313 0 - 2825 0

TABLE 19.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-26 AHU Room '' IN ZONE '' C3-26 Mech Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 249 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 20.1.A. COMPONENT LOADS FOR SPACE '' M-C3-31 AHU Room '' IN ZONE '' C3-31 AHU Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 36 m² 146 - 36 m² 216 -
Partitions 95 m² 1214 - 95 m² 1801 -
Ceiling 60 m² 243 - 60 m² 360 -
Overhead Lighting 444 W 444 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 205 0 10% 238 0
>> Total Zone Loads - 2252 0 - 2615 0

TABLE 20.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-31 AHU Room '' IN ZONE '' C3-31 AHU Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 250 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 21.1.A. COMPONENT LOADS FOR SPACE '' M-C3-29 Mech. Room '' IN ZONE '' C3-29 Mech Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 73 m² 296 - 73 m² 438 -
Partitions 105 m² 1345 - 105 m² 1995 -
Ceiling 52 m² 210 - 52 m² 312 -
Overhead Lighting 540 W 540 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 239 0 10% 275 0
>> Total Zone Loads - 2631 0 - 3020 0

TABLE 21.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-29 Mech. Room '' IN ZONE '' C3-29 Mech Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 251 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 22.1.A. COMPONENT LOADS FOR SPACE '' M-C3-25 AHU Room '' IN ZONE '' C3-25 AHURoom ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 38 m² 154 - 38 m² 228 -
Partitions 79 m² 1012 - 79 m² 1501 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 281 W 281 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 145 0 10% 173 0
>> Total Zone Loads - 1592 0 - 1902 0

TABLE 22.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-25 AHU Room '' IN ZONE '' C3-25 AHURoom ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 252 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 23.1.A. COMPONENT LOADS FOR SPACE '' M-C3-12 Mech Room '' IN ZONE '' C3-12 Mech Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 35 m² 142 - 35 m² 210 -
Partitions 72 m² 922 - 72 m² 1368 -
Ceiling 35 m² 142 - 35 m² 210 -
Overhead Lighting 259 W 259 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 146 0 10% 179 0
>> Total Zone Loads - 1611 0 - 1967 0

TABLE 23.1.B. ENVELOPE LOADS FOR SPACE '' M-C3-12 Mech Room '' IN ZONE '' C3-12 Mech Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 253 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 24.1.A. COMPONENT LOADS FOR SPACE '' M-C4-26 Ventilation Rm '' IN ZONE '' C4-26 Ventilation Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 77 m² 0 - 77 m² 0 -
Partitions 107 m² 1368 - 107 m² 2029 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 570 W 570 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1611 0 - 0 0
Safety Factor 10% / 10% 355 0 10% 203 0
>> Total Zone Loads - 3904 0 - 2232 0

TABLE 24.1.B. ENVELOPE LOADS FOR SPACE '' M-C4-26 Ventilation Rm '' IN ZONE '' C4-26 Ventilation Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 254 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 25.1.A. COMPONENT LOADS FOR SPACE '' M-C4-06 Ventilation Rm '' IN ZONE '' C4-06 Ventilation Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 36 m² 0 - 36 m² 0 -
Partitions 72 m² 922 - 72 m² 1368 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 266 W 266 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2352 0 - 0 0
Safety Factor 10% / 10% 354 0 10% 137 0
>> Total Zone Loads - 3895 0 - 1505 0

TABLE 25.1.B. ENVELOPE LOADS FOR SPACE '' M-C4-06 Ventilation Rm '' IN ZONE '' C4-06 Ventilation Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 255 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 26.1.A. COMPONENT LOADS FOR SPACE '' M-C4-10 Irrigation Pump '' IN ZONE '' C4-10 Irrigation Pump ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 0 - 26 m² 0 -
Partitions 44 m² 565 - 44 m² 838 -
Ceiling 26 m² 105 - 26 m² 156 -
Overhead Lighting 192 W 192 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 10% / 10% 236 0 10% 99 0
>> Total Zone Loads - 2599 0 - 1093 0

TABLE 26.1.B. ENVELOPE LOADS FOR SPACE '' M-C4-10 Irrigation Pump '' IN ZONE '' C4-10 Irrigation Pump ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 256 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 27.1.A. COMPONENT LOADS FOR SPACE '' M-C4-12 Ventilation Rm '' IN ZONE '' C4-12 Ventilation Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 25 m² 0 - 25 m² 0 -
Partitions 63 m² 807 - 63 m² 1197 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 185 W 185 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2526 0 - 0 0
Safety Factor 10% / 10% 352 0 10% 120 0
>> Total Zone Loads - 3870 0 - 1317 0

TABLE 27.1.B. ENVELOPE LOADS FOR SPACE '' M-C4-12 Ventilation Rm '' IN ZONE '' C4-12 Ventilation Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 257 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 28.1.A. COMPONENT LOADS FOR SPACE '' M-GF-48 Mech Room '' IN ZONE '' GF-48 Mech Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 28 m² 415 - 28 m² 219 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 38 m² 154 - 38 m² 228 -
Partitions 135 m² 1729 - 135 m² 2565 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 281 W 281 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 258 0 10% 301 0
>> Total Zone Loads - 2837 0 - 3313 0

TABLE 28.1.B. ENVELOPE LOADS FOR SPACE '' M-GF-48 Mech Room '' IN ZONE '' GF-48 Mech Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 28 0.365 - 415 - 219

Hourly Analysis Program v4.80 Page 258 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 29.1.A. COMPONENT LOADS FOR SPACE '' M-C4-01 Ventilation Rm '' IN ZONE '' C4-01 Ventilation Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 35 m² 0 - 35 m² 0 -
Partitions 63 m² 811 - 63 m² 1203 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 255 W 255 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2352 0 - 0 0
Safety Factor 10% / 10% 342 0 10% 120 0
>> Total Zone Loads - 3760 0 - 1323 0

TABLE 29.1.B. ENVELOPE LOADS FOR SPACE '' M-C4-01 Ventilation Rm '' IN ZONE '' C4-01 Ventilation Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 259 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 30.1.A. COMPONENT LOADS FOR SPACE '' M-C2-05 Water Feature P '' IN ZONE '' C2-05 Water Feature BP ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 35.9 °C / 21.7 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 37 m² 150 - 37 m² 222 -
Partitions 60 m² 769 - 60 m² 1140 -
Ceiling 37 m² 150 - 37 m² 222 -
Overhead Lighting 274 W 274 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2000 0 - 0 0
Safety Factor 10% / 10% 334 0 10% 158 0
>> Total Zone Loads - 3676 0 - 1742 0

TABLE 30.1.B. ENVELOPE LOADS FOR SPACE '' M-C2-05 Water Feature P '' IN ZONE '' C2-05 Water Feature BP ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)

Hourly Analysis Program v4.80 Page 260 of 773


Space Design Load Summary for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:01PM

TABLE 31.1.A. COMPONENT LOADS FOR SPACE '' M-C1-134 Water Feature '' IN ZONE '' C1-134 - Water Feature ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.7 °C / 21.9 °C HEATING OA DB / WB -0.8 °C / -2.5 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 26 m² 244 - 26 m² 132 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 105 - 26 m² 156 -
Partitions 46 m² 590 - 46 m² 882 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 192 W 192 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 2000 0 - 0 0
Safety Factor 10% / 10% 313 0 10% 117 0
>> Total Zone Loads - 3444 0 - 1286 0

TABLE 31.1.B. ENVELOPE LOADS FOR SPACE '' M-C1-134 Water Feature '' IN ZONE '' C1-134 - Water Feature ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 26 0.232 - 244 - 132

Hourly Analysis Program v4.80 Page 261 of 773


Hourly Air System Design Day Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:05PM

DESIGN MONTH: JULY


COMMON CENTRAL CENTRAL CENTRAL VENT VENT ZONE
OA VENT COOLING COOLING HEATING COOLING HEATING TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.7 0 0.0 0.0 0.0 0.0 0.0 90.2 0.0 0.0
0100 27.2 0 0.0 0.0 0.0 0.0 0.0 88.5 0.0 0.0
0200 26.6 0 0.0 0.0 0.0 0.0 0.0 86.7 0.0 0.0
0300 26.2 0 0.0 0.0 0.0 0.0 0.0 85.6 0.0 0.0
0400 25.8 0 0.0 0.0 0.0 0.0 0.0 84.6 0.0 0.0
0500 25.7 0 0.0 0.0 0.0 0.0 0.0 83.8 0.0 0.0
0600 25.9 0 0.0 0.0 0.0 0.0 0.0 84.1 0.0 0.0
0700 26.5 0 0.0 0.0 0.0 0.0 0.0 85.2 0.0 0.0
0800 27.5 0 0.0 0.0 0.0 0.0 0.0 87.3 0.0 0.0
0900 29.0 0 0.0 0.0 0.0 0.0 0.0 90.7 0.0 0.0
1000 30.7 0 0.0 0.0 0.0 0.0 0.0 94.4 0.0 0.0
1100 32.6 0 0.0 0.0 0.0 0.0 0.0 98.6 0.0 0.0
1200 34.4 0 0.0 0.0 0.0 0.0 0.0 103.1 0.0 0.0
1300 35.8 0 0.0 0.0 0.0 0.0 0.0 105.4 0.0 0.0
1400 36.7 0 0.0 0.0 0.0 0.0 0.0 105.9 0.0 0.0
1500 37.0 0 0.0 0.0 0.0 0.0 0.0 106.3 0.0 0.0
1600 36.7 0 0.0 0.0 0.0 0.0 0.0 107.4 0.0 0.0
1700 35.9 0 0.0 0.0 0.0 0.0 0.0 107.3 0.0 0.0
1800 34.6 0 0.0 0.0 0.0 0.0 0.0 106.5 0.0 0.0
1900 33.2 0 0.0 0.0 0.0 0.0 0.0 103.4 0.0 0.0
2000 31.7 0 0.0 0.0 0.0 0.0 0.0 100.0 0.0 0.0
2100 30.4 0 0.0 0.0 0.0 0.0 0.0 97.1 0.0 0.0
2200 29.3 0 0.0 0.0 0.0 0.0 0.0 94.5 0.0 0.0
2300 28.4 0 0.0 0.0 0.0 0.0 0.0 91.9 0.0 0.0

Hourly Analysis Program v4.80 Page 262 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C1-132 Mech Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 - 313.8 2365.5 2309.3 2309.3 0.0 0.0
0100 27.2 24.6 - 313.8 2243.4 2171.3 2171.3 0.0 0.0
0200 26.6 24.6 - 313.8 2126.0 2044.7 2044.7 0.0 0.0
0300 26.2 24.5 - 313.8 2026.3 2017.9 2017.9 0.0 0.0
0400 25.8 24.5 - 313.8 1943.7 1915.7 1915.7 0.0 0.0
0500 25.7 24.5 - 313.8 1892.8 1851.3 1851.3 0.0 0.0
0600 25.9 24.5 - 313.8 1895.7 1842.6 1842.6 0.0 0.0
0700 26.5 24.4 - 313.8 1973.9 1977.4 1977.4 0.0 0.0
0800 27.5 24.5 - 313.8 2154.9 2133.8 2133.8 0.0 0.0
0900 29.0 24.5 - 313.8 2431.3 2305.7 2305.7 0.0 0.0
1000 30.7 24.5 - 313.8 2761.8 2628.1 2628.1 0.0 0.0
1100 32.6 24.6 - 313.8 3133.5 2851.6 2851.6 0.0 0.0
1200 34.4 24.7 - 313.8 3491.4 3119.8 3119.8 0.0 0.0
1300 35.8 24.7 - 313.8 3704.4 3350.3 3350.3 0.0 0.0
1400 36.7 24.8 - 313.8 3795.9 3372.9 3372.9 0.0 0.0
1500 37.0 24.8 - 313.8 3852.0 3383.0 3383.0 0.0 0.0
1600 36.7 24.8 - 313.8 3868.5 3461.6 3461.6 0.0 0.0
1700 35.9 24.8 - 313.8 3844.1 3465.0 3465.0 0.0 0.0
1800 34.6 24.8 - 313.8 3713.0 3343.2 3343.2 0.0 0.0
1900 33.2 24.8 - 313.8 3433.1 3082.6 3082.6 0.0 0.0
2000 31.7 24.7 - 313.8 3146.8 2906.6 2906.6 0.0 0.0
2100 30.4 24.7 - 313.8 2902.6 2665.8 2665.8 0.0 0.0
2200 29.3 24.6 - 313.8 2686.2 2555.4 2555.4 0.0 0.0
2300 28.4 24.6 - 313.8 2508.0 2368.8 2368.8 0.0 0.0

ZONE: C2-34 Ventilation Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 - 320.9 3189.5 2987.6 2987.6 0.0 0.0
0100 27.2 24.6 - 320.9 3119.7 3061.0 3061.0 0.0 0.0
0200 26.6 24.7 - 320.9 3048.8 2939.6 2939.6 0.0 0.0
0300 26.2 24.7 - 320.9 2988.7 2881.6 2881.6 0.0 0.0
0400 25.8 24.6 - 320.9 2939.7 2839.1 2839.1 0.0 0.0
0500 25.7 24.7 - 320.9 2914.1 2784.8 2784.8 0.0 0.0
0600 25.9 24.7 - 320.9 2924.1 2751.3 2751.3 0.0 0.0
0700 26.5 24.7 - 320.9 2971.0 2836.2 2836.2 0.0 0.0
0800 27.5 24.6 - 320.9 3067.4 2978.6 2978.6 0.0 0.0
0900 29.0 24.7 - 320.9 3214.6 3050.6 3050.6 0.0 0.0
1000 30.7 24.7 - 320.9 3390.3 3194.1 3194.1 0.0 0.0
1100 32.6 24.8 - 320.9 3595.0 3367.8 3367.8 0.0 0.0
1200 34.4 24.8 - 320.9 3793.7 3538.6 3538.6 0.0 0.0
1300 35.8 24.8 - 320.9 3892.6 3624.9 3624.9 0.0 0.0
1400 36.7 24.8 - 320.9 3910.1 3678.8 3678.8 0.0 0.0
1500 37.0 24.8 - 320.9 3926.5 3664.1 3664.1 0.0 0.0
1600 36.7 24.7 - 320.9 3941.8 3783.2 3783.2 0.0 0.0
1700 35.9 25.0 - 320.9 3956.0 3590.0 3590.0 0.0 0.0
1800 34.6 24.8 - 320.9 3909.9 3734.9 3734.9 0.0 0.0
1900 33.2 24.8 - 320.9 3767.9 3551.5 3551.5 0.0 0.0
2000 31.7 24.9 - 320.9 3620.6 3368.5 3368.5 0.0 0.0
2100 30.4 24.8 - 320.9 3491.7 3304.9 3304.9 0.0 0.0
2200 29.3 24.8 - 320.9 3370.6 3209.8 3209.8 0.0 0.0
2300 28.4 24.7 - 320.9 3269.5 3124.7 3124.7 0.0 0.0

Hourly Analysis Program v4.80 Page 263 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C2-01 Mech Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 - 380.1 3870.3 3732.8 3732.8 0.0 0.0
0100 27.2 24.7 - 380.1 3795.9 3642.9 3642.9 0.0 0.0
0200 26.6 24.8 - 380.1 3720.4 3502.4 3502.4 0.0 0.0
0300 26.2 24.6 - 380.1 3656.3 3617.5 3617.5 0.0 0.0
0400 25.8 24.7 - 380.1 3604.1 3407.2 3407.2 0.0 0.0
0500 25.7 24.7 - 380.1 3576.7 3434.8 3434.8 0.0 0.0
0600 25.9 24.7 - 380.1 3587.5 3386.6 3386.6 0.0 0.0
0700 26.5 24.7 - 380.1 3637.5 3484.2 3484.2 0.0 0.0
0800 27.5 24.7 - 380.1 3740.3 3586.5 3586.5 0.0 0.0
0900 29.0 24.7 - 380.1 3897.3 3719.0 3719.0 0.0 0.0
1000 30.7 24.7 - 380.1 4084.6 3878.3 3878.3 0.0 0.0
1100 32.6 24.8 - 380.1 4302.8 4065.4 4065.4 0.0 0.0
1200 34.4 24.8 - 380.1 4514.7 4248.0 4248.0 0.0 0.0
1300 35.8 24.8 - 380.1 4617.5 4336.5 4336.5 0.0 0.0
1400 36.7 24.8 - 380.1 4636.1 4401.4 4401.4 0.0 0.0
1500 37.0 24.9 - 380.1 4653.5 4352.4 4352.4 0.0 0.0
1600 36.7 25.0 - 380.1 4669.7 4275.2 4275.2 0.0 0.0
1700 35.9 24.8 - 380.1 4684.9 4522.2 4522.2 0.0 0.0
1800 34.6 24.9 - 380.1 4638.3 4366.4 4366.4 0.0 0.0
1900 33.2 24.8 - 380.1 4487.0 4246.3 4246.3 0.0 0.0
2000 31.7 24.8 - 380.1 4329.9 4115.6 4115.6 0.0 0.0
2100 30.4 24.8 - 380.1 4192.5 4000.6 4000.6 0.0 0.0
2200 29.3 24.8 - 380.1 4063.4 3890.7 3890.7 0.0 0.0
2300 28.4 24.8 - 380.1 3955.7 3797.9 3797.9 0.0 0.0

ZONE: C2-42 AHU Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 - 582.3 5703.4 5347.1 5347.1 0.0 0.0
0100 27.2 24.8 - 582.3 5568.7 5235.0 5235.0 0.0 0.0
0200 26.6 24.8 - 582.3 5431.9 5119.3 5119.3 0.0 0.0
0300 26.2 24.7 - 582.3 5315.9 5022.7 5022.7 0.0 0.0
0400 25.8 24.7 - 582.3 5221.4 4945.5 4945.5 0.0 0.0
0500 25.7 24.7 - 582.3 5171.8 4910.2 4910.2 0.0 0.0
0600 25.9 24.7 - 582.3 5191.3 4939.7 4939.7 0.0 0.0
0700 26.5 24.7 - 582.3 5281.8 5034.9 5034.9 0.0 0.0
0800 27.5 24.7 - 582.3 5468.0 5321.9 5321.9 0.0 0.0
0900 29.0 24.7 - 582.3 5752.2 5455.9 5455.9 0.0 0.0
1000 30.7 24.7 - 582.3 6091.5 5823.1 5823.1 0.0 0.0
1100 32.6 24.7 - 582.3 6486.6 6189.6 6189.6 0.0 0.0
1200 34.4 24.9 - 582.3 6870.3 6202.6 6202.6 0.0 0.0
1300 35.8 24.8 - 582.3 7056.1 6543.6 6543.6 0.0 0.0
1400 36.7 24.8 - 582.3 7089.8 6615.3 6615.3 0.0 0.0
1500 37.0 24.9 - 582.3 7121.2 6554.5 6554.5 0.0 0.0
1600 36.7 24.8 - 582.3 7150.6 6660.6 6660.6 0.0 0.0
1700 35.9 24.8 - 582.3 7178.0 6727.8 6727.8 0.0 0.0
1800 34.6 24.8 - 582.3 7094.0 6686.6 6686.6 0.0 0.0
1900 33.2 24.8 - 582.3 6820.0 6545.5 6545.5 0.0 0.0
2000 31.7 24.8 - 582.3 6535.6 6125.0 6125.0 0.0 0.0
2100 30.4 24.8 - 582.3 6286.8 6006.8 6006.8 0.0 0.0
2200 29.3 24.8 - 582.3 6053.0 5644.1 5644.1 0.0 0.0
2300 28.4 24.8 - 582.3 5858.0 5479.3 5479.3 0.0 0.0

Hourly Analysis Program v4.80 Page 264 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C2-04 AHU Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 - 173.4 1472.0 1457.6 1457.6 0.0 0.0
0100 27.2 24.6 - 173.4 1411.1 1306.0 1306.0 0.0 0.0
0200 26.6 24.6 - 173.4 1349.2 1257.1 1257.1 0.0 0.0
0300 26.2 24.6 - 173.4 1296.7 1213.7 1213.7 0.0 0.0
0400 25.8 24.6 - 173.4 1254.0 1179.1 1179.1 0.0 0.0
0500 25.7 24.6 - 173.4 1231.6 1163.0 1163.0 0.0 0.0
0600 25.9 24.6 - 173.4 1240.4 1174.7 1174.7 0.0 0.0
0700 26.5 24.5 - 173.4 1281.4 1283.3 1283.3 0.0 0.0
0800 27.5 24.5 - 173.4 1365.6 1337.2 1337.2 0.0 0.0
0900 29.0 24.6 - 173.4 1494.2 1339.2 1339.2 0.0 0.0
1000 30.7 24.6 - 173.4 1647.6 1538.4 1538.4 0.0 0.0
1100 32.6 24.7 - 173.4 1826.4 1573.8 1573.8 0.0 0.0
1200 34.4 24.7 - 173.4 1999.9 1762.8 1762.8 0.0 0.0
1300 35.8 24.7 - 173.4 2082.8 1847.4 1847.4 0.0 0.0
1400 36.7 24.8 - 173.4 2098.0 1864.4 1864.4 0.0 0.0
1500 37.0 24.8 - 173.4 2112.2 1880.2 1880.2 0.0 0.0
1600 36.7 24.8 - 173.4 2125.5 1851.8 1851.8 0.0 0.0
1700 35.9 24.8 - 173.4 2137.8 1899.7 1899.7 0.0 0.0
1800 34.6 24.8 - 173.4 2101.0 1854.9 1854.9 0.0 0.0
1900 33.2 24.8 - 173.4 1977.1 1750.3 1750.3 0.0 0.0
2000 31.7 24.8 - 173.4 1848.4 1643.4 1643.4 0.0 0.0
2100 30.4 24.7 - 173.4 1735.9 1649.9 1649.9 0.0 0.0
2200 29.3 24.7 - 173.4 1630.1 1540.9 1540.9 0.0 0.0
2300 28.4 24.6 - 173.4 1541.9 1504.8 1504.8 0.0 0.0

ZONE: C2-07 Ventilation Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 - 336.1 3765.5 3704.7 3704.7 0.0 0.0
0100 27.2 24.9 - 336.1 3731.2 3624.6 3624.6 0.0 0.0
0200 26.6 24.9 - 336.1 3696.4 3589.1 3589.1 0.0 0.0
0300 26.2 24.9 - 336.1 3666.8 3557.4 3557.4 0.0 0.0
0400 25.8 24.9 - 336.1 3642.7 3530.9 3530.9 0.0 0.0
0500 25.7 24.9 - 336.1 3630.1 3515.8 3515.8 0.0 0.0
0600 25.9 24.9 - 336.1 3635.1 3518.3 3518.3 0.0 0.0
0700 26.5 24.9 - 336.1 3658.1 3539.0 3539.0 0.0 0.0
0800 27.5 24.9 - 336.1 3705.5 3584.2 3584.2 0.0 0.0
0900 29.0 24.9 - 336.1 3777.9 3654.7 3654.7 0.0 0.0
1000 30.7 24.9 - 336.1 3864.3 3739.6 3739.6 0.0 0.0
1100 32.6 24.9 - 336.1 3964.9 3839.3 3839.3 0.0 0.0
1200 34.4 25.0 - 336.1 4062.6 3936.5 3936.5 0.0 0.0
1300 35.8 25.0 - 336.1 4111.3 3984.7 3984.7 0.0 0.0
1400 36.7 25.0 - 336.1 4119.9 3992.8 3992.8 0.0 0.0
1500 37.0 25.0 - 336.1 4127.9 4000.2 4000.2 0.0 0.0
1600 36.7 25.0 - 336.1 4135.4 4006.9 4006.9 0.0 0.0
1700 35.9 25.0 - 336.1 4142.4 4013.0 4013.0 0.0 0.0
1800 34.6 25.0 - 336.1 4119.7 3989.1 3989.1 0.0 0.0
1900 33.2 25.0 - 336.1 4049.9 3917.5 3917.5 0.0 0.0
2000 31.7 24.9 - 336.1 3977.5 3899.7 3899.7 0.0 0.0
2100 30.4 25.0 - 336.1 3914.1 3771.0 3771.0 0.0 0.0
2200 29.3 24.8 - 336.1 3854.6 3797.2 3797.2 0.0 0.0
2300 28.4 24.6 - 336.1 3804.9 3806.4 3806.4 0.0 0.0

Hourly Analysis Program v4.80 Page 265 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C2-08 Indoor Swimming


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 - 380.9 4051.3 3875.2 3875.2 0.0 0.0
0100 27.2 24.9 - 380.9 3992.5 3826.3 3826.3 0.0 0.0
0200 26.6 24.8 - 380.9 3932.8 3775.3 3775.3 0.0 0.0
0300 26.2 24.8 - 380.9 3882.1 3732.1 3732.1 0.0 0.0
0400 25.8 24.7 - 380.9 3840.9 3771.2 3771.2 0.0 0.0
0500 25.7 24.6 - 380.9 3819.2 3790.4 3790.4 0.0 0.0
0600 25.9 24.7 - 380.9 3827.7 3733.3 3733.3 0.0 0.0
0700 26.5 24.7 - 380.9 3867.3 3768.9 3768.9 0.0 0.0
0800 27.5 24.7 - 380.9 3948.6 3845.8 3845.8 0.0 0.0
0900 29.0 24.9 - 380.9 4072.6 3858.4 3858.4 0.0 0.0
1000 30.7 24.7 - 380.9 4220.8 4119.7 4119.7 0.0 0.0
1100 32.6 24.8 - 380.9 4393.3 4189.7 4189.7 0.0 0.0
1200 34.4 24.8 - 380.9 4560.8 4426.1 4426.1 0.0 0.0
1300 35.8 24.9 - 380.9 4641.6 4365.9 4365.9 0.0 0.0
1400 36.7 24.8 - 380.9 4656.2 4519.1 4519.1 0.0 0.0
1500 37.0 25.0 - 380.9 4669.9 4386.4 4386.4 0.0 0.0
1600 36.7 24.9 - 380.9 4682.8 4489.6 4489.6 0.0 0.0
1700 35.9 24.9 - 380.9 4694.7 4502.4 4502.4 0.0 0.0
1800 34.6 24.8 - 380.9 4658.4 4526.7 4526.7 0.0 0.0
1900 33.2 24.8 - 380.9 4538.8 4379.4 4379.4 0.0 0.0
2000 31.7 24.8 - 380.9 4414.7 4256.2 4256.2 0.0 0.0
2100 30.4 24.8 - 380.9 4306.0 4130.2 4130.2 0.0 0.0
2200 29.3 24.8 - 380.9 4203.9 4027.7 4027.7 0.0 0.0
2300 28.4 24.7 - 380.9 4118.8 4038.8 4038.8 0.0 0.0

ZONE: C2-20 Mech Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 - 121.5 1108.2 1072.5 1072.5 0.0 0.0
0100 27.2 24.7 - 121.5 1072.8 1045.9 1045.9 0.0 0.0
0200 26.6 24.6 - 121.5 1036.9 1017.5 1017.5 0.0 0.0
0300 26.2 24.6 - 121.5 1006.4 992.8 992.8 0.0 0.0
0400 25.8 24.6 - 121.5 981.5 971.7 971.7 0.0 0.0
0500 25.7 24.6 - 121.5 968.5 929.9 929.9 0.0 0.0
0600 25.9 24.6 - 121.5 973.6 986.1 986.1 0.0 0.0
0700 26.5 24.6 - 121.5 997.4 982.2 982.2 0.0 0.0
0800 27.5 24.6 - 121.5 1046.3 1009.6 1009.6 0.0 0.0
0900 29.0 24.7 - 121.5 1121.0 1027.0 1027.0 0.0 0.0
1000 30.7 24.6 - 121.5 1210.1 1135.7 1135.7 0.0 0.0
1100 32.6 24.8 - 121.5 1313.9 1137.3 1137.3 0.0 0.0
1200 34.4 24.8 - 121.5 1414.7 1246.1 1246.1 0.0 0.0
1300 35.8 24.7 - 121.5 1464.9 1327.6 1327.6 0.0 0.0
1400 36.7 24.8 - 121.5 1473.8 1273.3 1273.3 0.0 0.0
1500 37.0 24.8 - 121.5 1482.1 1307.4 1307.4 0.0 0.0
1600 36.7 24.8 - 121.5 1489.9 1326.2 1326.2 0.0 0.0
1700 35.9 24.8 - 121.5 1497.1 1325.7 1325.7 0.0 0.0
1800 34.6 24.9 - 121.5 1473.7 1293.4 1293.4 0.0 0.0
1900 33.2 24.8 - 121.5 1401.7 1317.3 1317.3 0.0 0.0
2000 31.7 24.8 - 121.5 1326.9 1227.6 1227.6 0.0 0.0
2100 30.4 24.7 - 121.5 1261.6 1180.8 1180.8 0.0 0.0
2200 29.3 24.7 - 121.5 1200.1 1137.5 1137.5 0.0 0.0
2300 28.4 24.7 - 121.5 1148.9 1101.6 1101.6 0.0 0.0

Hourly Analysis Program v4.80 Page 266 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C2-15 Pump Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 - 530.1 5894.4 5701.5 5701.5 0.0 0.0
0100 27.2 24.7 - 530.1 5836.1 5749.9 5749.9 0.0 0.0
0200 26.6 24.9 - 530.1 5776.9 5555.8 5555.8 0.0 0.0
0300 26.2 24.8 - 530.1 5726.7 5605.9 5605.9 0.0 0.0
0400 25.8 24.7 - 530.1 5685.8 5649.8 5649.8 0.0 0.0
0500 25.7 24.7 - 530.1 5664.4 5611.8 5611.8 0.0 0.0
0600 25.9 24.7 - 530.1 5672.8 5607.3 5607.3 0.0 0.0
0700 26.5 24.7 - 530.1 5712.0 5637.1 5637.1 0.0 0.0
0800 27.5 24.7 - 530.1 5792.5 5663.4 5663.4 0.0 0.0
0900 29.0 24.7 - 530.1 5915.4 5813.3 5813.3 0.0 0.0
1000 30.7 24.7 - 530.1 6062.1 5951.9 5951.9 0.0 0.0
1100 32.6 24.9 - 530.1 6233.0 5910.6 5910.6 0.0 0.0
1200 34.4 24.8 - 530.1 6398.9 6219.7 6219.8 0.0 0.0
1300 35.8 24.9 - 530.1 6481.6 6207.0 6207.0 0.0 0.0
1400 36.7 25.0 - 530.1 6496.2 6083.4 6083.4 0.0 0.0
1500 37.0 24.9 - 530.1 6509.9 6303.7 6303.7 0.0 0.0
1600 36.7 24.8 - 530.1 6522.6 6416.9 6416.9 0.0 0.0
1700 35.9 24.9 - 530.1 6534.5 6282.8 6282.8 0.0 0.0
1800 34.6 25.0 - 530.1 6496.0 6162.2 6162.2 0.0 0.0
1900 33.2 24.9 - 530.1 6377.4 6208.1 6208.1 0.0 0.0
2000 31.7 24.9 - 530.1 6254.4 6064.3 6064.3 0.0 0.0
2100 30.4 24.9 - 530.1 6146.8 5954.5 5954.5 0.0 0.0
2200 29.3 24.8 - 530.1 6045.6 5959.3 5959.3 0.0 0.0
2300 28.4 25.0 - 530.1 5961.3 5673.9 5673.9 0.0 0.0

ZONE: C2-28 Mech Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 - 105.6 885.8 822.1 822.1 0.0 0.0
0100 27.2 24.6 - 105.6 847.7 808.0 808.0 0.0 0.0
0200 26.6 24.6 - 105.6 809.1 763.4 763.4 0.0 0.0
0300 26.2 24.6 - 105.6 776.3 726.4 726.4 0.0 0.0
0400 25.8 24.5 - 105.6 749.6 725.6 725.6 0.0 0.0
0500 25.7 24.5 - 105.6 735.6 704.4 704.4 0.0 0.0
0600 25.9 24.5 - 105.6 741.1 704.6 704.6 0.0 0.0
0700 26.5 24.5 - 105.6 766.7 725.6 725.6 0.0 0.0
0800 27.5 24.6 - 105.6 819.3 764.6 764.6 0.0 0.0
0900 29.0 24.6 - 105.6 899.6 842.8 842.8 0.0 0.0
1000 30.7 24.6 - 105.6 995.4 906.1 906.1 0.0 0.0
1100 32.6 24.7 - 105.6 1107.1 988.8 988.8 0.0 0.0
1200 34.4 24.7 - 105.6 1215.4 1071.1 1071.1 0.0 0.0
1300 35.8 24.7 - 105.6 1267.4 1130.3 1130.3 0.0 0.0
1400 36.7 24.7 - 105.6 1276.9 1145.0 1145.0 0.0 0.0
1500 37.0 24.7 - 105.6 1285.8 1158.5 1158.5 0.0 0.0
1600 36.7 24.8 - 105.6 1294.0 1142.6 1142.6 0.0 0.0
1700 35.9 24.8 - 105.6 1301.8 1157.5 1157.5 0.0 0.0
1800 34.6 24.7 - 105.6 1278.6 1165.7 1165.7 0.0 0.0
1900 33.2 24.7 - 105.6 1201.2 1089.5 1089.5 0.0 0.0
2000 31.7 24.8 - 105.6 1120.8 988.5 988.5 0.0 0.0
2100 30.4 24.7 - 105.6 1050.6 958.8 958.8 0.0 0.0
2200 29.3 24.7 - 105.6 984.5 891.3 891.3 0.0 0.0
2300 28.4 24.6 - 105.6 929.4 870.3 870.3 0.0 0.0

Hourly Analysis Program v4.80 Page 267 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C2-19 Water Feature Pump


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 25.0 - 258.7 2890.3 2769.8 2769.8 0.0 0.0
0100 27.2 24.8 - 258.7 2863.1 2816.6 2816.6 0.0 0.0
0200 26.6 24.9 - 258.7 2835.4 2732.8 2732.8 0.0 0.0
0300 26.2 24.8 - 258.7 2812.0 2768.9 2768.9 0.0 0.0
0400 25.8 24.8 - 258.7 2792.9 2754.4 2754.4 0.0 0.0
0500 25.7 24.7 - 258.7 2782.9 2782.5 2782.5 0.0 0.0
0600 25.9 24.7 - 258.7 2786.8 2752.4 2752.4 0.0 0.0
0700 26.5 24.9 - 258.7 2805.1 2667.5 2667.5 0.0 0.0
0800 27.5 24.8 - 258.7 2842.7 2783.1 2783.1 0.0 0.0
0900 29.0 24.7 - 258.7 2900.1 2880.5 2880.5 0.0 0.0
1000 30.7 24.9 - 258.7 2968.7 2869.4 2869.4 0.0 0.0
1100 32.6 25.0 - 258.7 3048.6 2893.4 2893.4 0.0 0.0
1200 34.4 24.9 - 258.7 3126.1 3035.9 3035.9 0.0 0.0
1300 35.8 24.8 - 258.7 3164.7 3105.8 3105.8 0.0 0.0
1400 36.7 25.0 - 258.7 3171.5 3018.3 3018.3 0.0 0.0
1500 37.0 24.9 - 258.7 3177.9 3087.3 3087.3 0.0 0.0
1600 36.7 24.9 - 258.7 3183.9 3084.8 3084.8 0.0 0.0
1700 35.9 25.0 - 258.7 3189.5 3060.4 3060.4 0.0 0.0
1800 34.6 24.9 - 258.7 3171.4 3087.5 3087.5 0.0 0.0
1900 33.2 25.0 - 258.7 3116.1 2994.2 2994.2 0.0 0.0
2000 31.7 24.9 - 258.7 3058.6 2991.2 2991.2 0.0 0.0
2100 30.4 24.9 - 258.7 3008.3 2903.9 2903.9 0.0 0.0
2200 29.3 24.8 - 258.7 2961.0 2904.5 2904.5 0.0 0.0
2300 28.4 24.9 - 258.7 2921.6 2833.7 2833.7 0.0 0.0

ZONE: C3-28 Ventilation Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 - 316.9 3238.7 3123.9 3123.9 0.0 0.0
0100 27.2 24.8 - 316.9 3177.9 3020.0 3020.0 0.0 0.0
0200 26.6 24.7 - 316.9 3116.2 3017.5 3017.5 0.0 0.0
0300 26.2 24.7 - 316.9 3063.8 2924.4 2924.4 0.0 0.0
0400 25.8 24.7 - 316.9 3021.2 2931.4 2931.4 0.0 0.0
0500 25.7 24.8 - 316.9 2998.8 2825.6 2825.6 0.0 0.0
0600 25.9 24.7 - 316.9 3007.6 2914.2 2914.2 0.0 0.0
0700 26.5 24.7 - 316.9 3048.4 2942.0 2942.0 0.0 0.0
0800 27.5 24.7 - 316.9 3132.4 3045.8 3045.8 0.0 0.0
0900 29.0 24.7 - 316.9 3260.6 3111.6 3111.6 0.0 0.0
1000 30.7 24.8 - 316.9 3413.6 3236.8 3236.8 0.0 0.0
1100 32.6 24.8 - 316.9 3591.9 3386.0 3386.0 0.0 0.0
1200 34.4 24.8 - 316.9 3764.9 3533.2 3533.2 0.0 0.0
1300 35.8 24.8 - 316.9 3851.1 3669.0 3669.0 0.0 0.0
1400 36.7 24.8 - 316.9 3866.4 3659.3 3659.3 0.0 0.0
1500 37.0 24.9 - 316.9 3880.6 3640.6 3640.6 0.0 0.0
1600 36.7 24.8 - 316.9 3893.9 3716.6 3716.6 0.0 0.0
1700 35.9 24.8 - 316.9 3906.3 3693.9 3693.9 0.0 0.0
1800 34.6 24.8 - 316.9 3866.1 3706.6 3706.6 0.0 0.0
1900 33.2 24.8 - 316.9 3742.5 3537.1 3537.1 0.0 0.0
2000 31.7 24.9 - 316.9 3614.2 3372.1 3372.1 0.0 0.0
2100 30.4 24.8 - 316.9 3501.9 3343.7 3343.7 0.0 0.0
2200 29.3 24.8 - 316.9 3396.4 3257.1 3257.1 0.0 0.0
2300 28.4 24.8 - 316.9 3308.4 3126.3 3126.4 0.0 0.0

Hourly Analysis Program v4.80 Page 268 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C3-01 Ventilation Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 - 338.9 3711.2 3553.2 3553.2 0.0 0.0
0100 27.2 24.8 - 338.9 3668.7 3585.1 3585.1 0.0 0.0
0200 26.6 24.9 - 338.9 3625.5 3479.5 3479.5 0.0 0.0
0300 26.2 24.8 - 338.9 3588.9 3511.8 3511.8 0.0 0.0
0400 25.8 24.9 - 338.9 3559.1 3429.8 3429.8 0.0 0.0
0500 25.7 24.8 - 338.9 3543.5 3467.5 3467.5 0.0 0.0
0600 25.9 24.7 - 338.9 3549.6 3479.4 3479.4 0.0 0.0
0700 26.5 24.7 - 338.9 3578.2 3508.9 3508.9 0.0 0.0
0800 27.5 24.8 - 338.9 3636.9 3500.7 3500.7 0.0 0.0
0900 29.0 24.7 - 338.9 3726.5 3656.5 3656.5 0.0 0.0
1000 30.7 24.7 - 338.9 3833.4 3752.7 3752.7 0.0 0.0
1100 32.6 24.8 - 338.9 3958.0 3810.1 3810.1 0.0 0.0
1200 34.4 24.7 - 338.9 4079.0 3993.1 3993.1 0.0 0.0
1300 35.8 24.9 - 338.9 4139.2 3978.5 3978.5 0.0 0.0
1400 36.7 24.7 - 338.9 4149.9 4074.8 4074.8 0.0 0.0
1500 37.0 24.8 - 338.9 4159.8 4042.0 4042.0 0.0 0.0
1600 36.7 25.0 - 338.9 4169.1 3927.3 3927.3 0.0 0.0
1700 35.9 24.9 - 338.9 4177.8 4022.3 4022.3 0.0 0.0
1800 34.6 25.0 - 338.9 4149.7 3957.1 3957.1 0.0 0.0
1900 33.2 24.9 - 338.9 4063.3 3929.0 3929.0 0.0 0.0
2000 31.7 24.9 - 338.9 3973.6 3832.0 3832.0 0.0 0.0
2100 30.4 24.8 - 338.9 3895.1 3822.3 3822.3 0.0 0.0
2200 29.3 24.9 - 338.9 3821.4 3633.8 3633.8 0.0 0.0
2300 28.4 24.8 - 338.9 3759.9 3661.3 3661.3 0.0 0.0

ZONE: C3-04 Outdoor Pool


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 - 413.2 4468.8 4314.0 4314.0 0.0 0.0
0100 27.2 24.7 - 413.2 4411.7 4329.9 4329.9 0.0 0.0
0200 26.6 24.9 - 413.2 4353.8 4160.3 4160.3 0.0 0.0
0300 26.2 24.8 - 413.2 4304.6 4155.3 4155.3 0.0 0.0
0400 25.8 24.7 - 413.2 4264.6 4195.2 4195.2 0.0 0.0
0500 25.7 24.8 - 413.2 4243.6 4065.8 4065.8 0.0 0.0
0600 25.9 24.8 - 413.2 4251.9 4107.5 4107.5 0.0 0.0
0700 26.5 24.8 - 413.2 4290.2 4119.1 4119.1 0.0 0.0
0800 27.5 24.7 - 413.2 4369.1 4284.6 4284.6 0.0 0.0
0900 29.0 24.7 - 413.2 4489.4 4395.7 4395.7 0.0 0.0
1000 30.7 24.8 - 413.2 4633.2 4455.5 4455.5 0.0 0.0
1100 32.6 24.8 - 413.2 4800.5 4640.3 4640.3 0.0 0.0
1200 34.4 24.8 - 413.2 4963.0 4796.7 4796.7 0.0 0.0
1300 35.8 25.0 - 413.2 5041.9 4777.8 4777.8 0.0 0.0
1400 36.7 24.9 - 413.2 5056.2 4834.4 4834.4 0.0 0.0
1500 37.0 24.8 - 413.2 5069.5 4904.9 4904.9 0.0 0.0
1600 36.7 24.9 - 413.2 5081.9 4858.7 4858.7 0.0 0.0
1700 35.9 24.8 - 413.2 5093.6 4933.0 4933.0 0.0 0.0
1800 34.6 24.8 - 413.2 5057.8 4926.5 4926.5 0.0 0.0
1900 33.2 24.8 - 413.2 4941.7 4768.9 4768.9 0.0 0.0
2000 31.7 24.8 - 413.2 4821.3 4658.0 4658.0 0.0 0.0
2100 30.4 25.0 - 413.2 4715.9 4465.2 4465.2 0.0 0.0
2200 29.3 24.7 - 413.2 4616.8 4518.7 4518.7 0.0 0.0
2300 28.4 24.9 - 413.2 4534.2 4337.1 4337.1 0.0 0.0

Hourly Analysis Program v4.80 Page 269 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C3-05 Ventilation Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 - 335.8 3678.6 3658.9 3658.9 0.0 0.0
0100 27.2 24.8 - 335.8 3636.7 3491.6 3491.6 0.0 0.0
0200 26.6 24.7 - 335.8 3594.1 3538.3 3538.3 0.0 0.0
0300 26.2 24.8 - 335.8 3558.0 3448.2 3448.2 0.0 0.0
0400 25.8 24.8 - 335.8 3528.5 3384.5 3384.5 0.0 0.0
0500 25.7 24.8 - 335.8 3513.1 3408.4 3408.4 0.0 0.0
0600 25.9 24.8 - 335.8 3519.2 3370.6 3370.6 0.0 0.0
0700 26.5 24.8 - 335.8 3547.3 3440.7 3440.7 0.0 0.0
0800 27.5 24.8 - 335.8 3605.3 3500.8 3500.8 0.0 0.0
0900 29.0 24.8 - 335.8 3693.7 3597.2 3597.2 0.0 0.0
1000 30.7 24.8 - 335.8 3799.3 3669.9 3669.9 0.0 0.0
1100 32.6 24.8 - 335.8 3922.3 3806.8 3806.8 0.0 0.0
1200 34.4 24.8 - 335.8 4041.7 3899.7 3899.7 0.0 0.0
1300 35.8 24.9 - 335.8 4101.2 3948.1 3948.1 0.0 0.0
1400 36.7 24.8 - 335.8 4111.7 4019.2 4019.2 0.0 0.0
1500 37.0 24.9 - 335.8 4121.5 3962.5 3962.5 0.0 0.0
1600 36.7 24.7 - 335.8 4130.7 4069.0 4069.0 0.0 0.0
1700 35.9 24.8 - 335.8 4139.3 3994.2 3994.2 0.0 0.0
1800 34.6 25.0 - 335.8 4111.5 3892.1 3892.1 0.0 0.0
1900 33.2 24.9 - 335.8 4026.2 3877.5 3877.5 0.0 0.0
2000 31.7 24.8 - 335.8 3937.7 3838.0 3838.0 0.0 0.0
2100 30.4 24.8 - 335.8 3860.3 3770.7 3770.7 0.0 0.0
2200 29.3 24.9 - 335.8 3787.5 3627.9 3627.9 0.0 0.0
2300 28.4 24.8 - 335.8 3726.7 3613.3 3613.3 0.0 0.0

ZONE: C3-09 Ventilation Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 - 308.7 3428.5 3325.6 3325.6 0.0 0.0
0100 27.2 24.9 - 308.7 3394.2 3294.6 3294.6 0.0 0.0
0200 26.6 24.9 - 308.7 3359.3 3262.6 3262.6 0.0 0.0
0300 26.2 24.9 - 308.7 3329.8 3235.6 3235.6 0.0 0.0
0400 25.8 24.9 - 308.7 3305.7 3213.7 3213.7 0.0 0.0
0500 25.7 24.8 - 308.7 3293.1 3202.9 3202.9 0.0 0.0
0600 25.9 24.8 - 308.7 3298.0 3209.2 3209.2 0.0 0.0
0700 26.5 24.7 - 308.7 3321.1 3274.5 3274.5 0.0 0.0
0800 27.5 24.8 - 308.7 3368.5 3287.2 3287.2 0.0 0.0
0900 29.0 24.7 - 308.7 3440.9 3408.1 3408.1 0.0 0.0
1000 30.7 25.0 - 308.7 3527.3 3342.8 3342.8 0.0 0.0
1100 32.6 24.8 - 308.7 3627.9 3536.6 3536.6 0.0 0.0
1200 34.4 24.9 - 308.7 3725.6 3618.0 3618.0 0.0 0.0
1300 35.8 24.8 - 308.7 3774.2 3681.6 3681.6 0.0 0.0
1400 36.7 25.0 - 308.7 3782.8 3639.7 3639.7 0.0 0.0
1500 37.0 24.9 - 308.7 3790.9 3656.0 3656.0 0.0 0.0
1600 36.7 24.8 - 308.7 3798.4 3714.4 3714.4 0.0 0.0
1700 35.9 25.0 - 308.7 3805.4 3644.6 3644.6 0.0 0.0
1800 34.6 25.0 - 308.7 3782.7 3639.2 3639.2 0.0 0.0
1900 33.2 25.0 - 308.7 3712.9 3577.4 3577.4 0.0 0.0
2000 31.7 25.0 - 308.7 3640.5 3512.4 3512.4 0.0 0.0
2100 30.4 24.9 - 308.7 3577.1 3455.7 3455.7 0.0 0.0
2200 29.3 24.9 - 308.7 3517.5 3402.2 3402.2 0.0 0.0
2300 28.4 24.9 - 308.7 3467.9 3357.8 3357.8 0.0 0.0

Hourly Analysis Program v4.80 Page 270 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C3-15 Pump Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 - 566.5 6342.5 6220.7 6220.7 0.0 0.0
0100 27.2 24.8 - 566.5 6284.3 6168.3 6168.3 0.0 0.0
0200 26.6 24.7 - 566.5 6225.1 6201.7 6201.7 0.0 0.0
0300 26.2 24.7 - 566.5 6174.9 6110.4 6110.4 0.0 0.0
0400 25.8 24.8 - 566.5 6134.0 5999.4 5999.4 0.0 0.0
0500 25.7 24.7 - 566.5 6112.5 6076.1 6076.1 0.0 0.0
0600 25.9 24.7 - 566.5 6120.9 6034.5 6034.5 0.0 0.0
0700 26.5 24.8 - 566.5 6160.1 5981.9 5981.9 0.0 0.0
0800 27.5 24.8 - 566.5 6240.6 6072.4 6072.4 0.0 0.0
0900 29.0 24.7 - 566.5 6363.5 6307.3 6307.3 0.0 0.0
1000 30.7 24.9 - 566.5 6510.3 6194.9 6194.9 0.0 0.0
1100 32.6 24.8 - 566.5 6681.2 6470.2 6470.2 0.0 0.0
1200 34.4 24.8 - 566.5 6847.1 6646.9 6646.9 0.0 0.0
1300 35.8 24.9 - 566.5 6929.7 6689.7 6689.7 0.0 0.0
1400 36.7 24.9 - 566.5 6944.3 6711.5 6711.5 0.0 0.0
1500 37.0 24.9 - 566.5 6958.0 6729.0 6729.0 0.0 0.0
1600 36.7 24.9 - 566.5 6970.7 6749.8 6749.8 0.0 0.0
1700 35.9 24.9 - 566.5 6982.7 6749.4 6749.4 0.0 0.0
1800 34.6 25.0 - 566.5 6944.1 6609.5 6609.5 0.0 0.0
1900 33.2 24.9 - 566.5 6825.6 6653.9 6653.9 0.0 0.0
2000 31.7 24.9 - 566.5 6702.6 6462.2 6462.2 0.0 0.0
2100 30.4 24.8 - 566.5 6594.9 6451.4 6451.4 0.0 0.0
2200 29.3 24.9 - 566.5 6493.8 6286.0 6286.0 0.0 0.0
2300 28.4 24.8 - 566.5 6409.4 6285.8 6285.8 0.0 0.0

ZONE: C3-18 AHU Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 - 363.6 3108.2 2880.0 2880.0 0.0 0.0
0100 27.2 24.6 - 363.6 2982.5 2786.9 2786.9 0.0 0.0
0200 26.6 24.6 - 363.6 2854.8 2688.4 2688.4 0.0 0.0
0300 26.2 24.6 - 363.6 2746.5 2604.9 2604.9 0.0 0.0
0400 25.8 24.6 - 363.6 2658.3 2536.5 2536.5 0.0 0.0
0500 25.7 24.6 - 363.6 2612.0 2502.8 2502.8 0.0 0.0
0600 25.9 24.5 - 363.6 2630.2 2662.3 2662.3 0.0 0.0
0700 26.5 24.5 - 363.6 2714.8 2673.7 2673.7 0.0 0.0
0800 27.5 24.5 - 363.6 2888.6 2787.1 2787.1 0.0 0.0
0900 29.0 24.5 - 363.6 3153.9 2987.8 2987.8 0.0 0.0
1000 30.7 24.6 - 363.6 3470.7 3135.3 3135.3 0.0 0.0
1100 32.6 24.6 - 363.6 3839.5 3471.8 3471.8 0.0 0.0
1200 34.4 24.7 - 363.6 4197.7 3672.2 3672.2 0.0 0.0
1300 35.8 24.7 - 363.6 4368.3 3845.8 3845.8 0.0 0.0
1400 36.7 24.8 - 363.6 4399.7 3706.4 3706.4 0.0 0.0
1500 37.0 24.8 - 363.6 4428.9 3816.2 3816.2 0.0 0.0
1600 36.7 24.8 - 363.6 4456.3 3997.2 3997.2 0.0 0.0
1700 35.9 24.8 - 363.6 4481.8 3919.2 3919.2 0.0 0.0
1800 34.6 24.8 - 363.6 4406.2 3984.5 3984.5 0.0 0.0
1900 33.2 24.8 - 363.6 4150.5 3749.9 3749.9 0.0 0.0
2000 31.7 24.7 - 363.6 3885.0 3658.6 3658.6 0.0 0.0
2100 30.4 24.6 - 363.6 3652.8 3484.2 3484.2 0.0 0.0
2200 29.3 24.6 - 363.6 3434.5 3333.2 3333.2 0.0 0.0
2300 28.4 24.7 - 363.6 3252.4 2979.1 2979.1 0.0 0.0

Hourly Analysis Program v4.80 Page 271 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C3-26 Mech Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 - 187.6 1506.0 1373.2 1373.2 0.0 0.0
0100 27.2 24.6 - 187.6 1432.3 1349.3 1349.3 0.0 0.0
0200 26.6 24.6 - 187.6 1357.5 1269.1 1269.1 0.0 0.0
0300 26.2 24.6 - 187.6 1294.1 1204.0 1204.0 0.0 0.0
0400 25.8 24.5 - 187.6 1242.4 1152.0 1152.0 0.0 0.0
0500 25.7 24.5 - 187.6 1215.3 1125.0 1125.0 0.0 0.0
0600 25.9 24.5 - 187.6 1225.9 1135.2 1135.2 0.0 0.0
0700 26.5 24.5 - 187.6 1275.4 1182.7 1182.7 0.0 0.0
0800 27.5 24.6 - 187.6 1377.2 1235.5 1235.5 0.0 0.0
0900 29.0 24.6 - 187.6 1532.6 1381.1 1381.1 0.0 0.0
1000 30.7 24.6 - 187.6 1718.1 1577.2 1577.2 0.0 0.0
1100 32.6 24.7 - 187.6 1934.2 1734.1 1734.1 0.0 0.0
1200 34.4 24.7 - 187.6 2143.9 1941.8 1941.8 0.0 0.0
1300 35.8 24.8 - 187.6 2245.9 1907.6 1907.6 0.0 0.0
1400 36.7 24.8 - 187.6 2264.3 1950.8 1950.8 0.0 0.0
1500 37.0 24.8 - 187.6 2281.5 2024.8 2024.8 0.0 0.0
1600 36.7 24.8 - 187.6 2297.5 2057.4 2057.4 0.0 0.0
1700 35.9 24.8 - 187.6 2312.5 2032.8 2032.8 0.0 0.0
1800 34.6 24.8 - 187.6 2266.3 1983.9 1983.9 0.0 0.0
1900 33.2 24.8 - 187.6 2116.5 1850.5 1850.5 0.0 0.0
2000 31.7 24.7 - 187.6 1961.0 1771.3 1771.3 0.0 0.0
2100 30.4 24.7 - 187.6 1825.0 1639.4 1639.4 0.0 0.0
2200 29.3 24.7 - 187.6 1697.1 1570.5 1570.5 0.0 0.0
2300 28.4 24.7 - 187.6 1590.4 1461.9 1461.9 0.0 0.0

ZONE: C3-31 AHU Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 - 182.7 1505.0 1392.3 1392.3 0.0 0.0
0100 27.2 24.6 - 182.7 1436.8 1320.1 1320.1 0.0 0.0
0200 26.6 24.6 - 182.7 1367.6 1304.5 1304.5 0.0 0.0
0300 26.2 24.6 - 182.7 1308.9 1235.3 1235.3 0.0 0.0
0400 25.8 24.6 - 182.7 1261.0 1180.3 1180.3 0.0 0.0
0500 25.7 24.6 - 182.7 1235.9 1149.1 1149.1 0.0 0.0
0600 25.9 24.6 - 182.7 1245.8 1153.7 1153.7 0.0 0.0
0700 26.5 24.6 - 182.7 1291.6 1194.8 1194.8 0.0 0.0
0800 27.5 24.6 - 182.7 1385.8 1279.4 1279.4 0.0 0.0
0900 29.0 24.5 - 182.7 1529.6 1448.8 1448.8 0.0 0.0
1000 30.7 24.6 - 182.7 1701.3 1554.7 1554.7 0.0 0.0
1100 32.6 24.7 - 182.7 1901.2 1703.0 1703.0 0.0 0.0
1200 34.4 24.7 - 182.7 2095.3 1851.6 1851.6 0.0 0.0
1300 35.8 24.7 - 182.7 2190.2 1956.7 1956.7 0.0 0.0
1400 36.7 24.7 - 182.7 2207.2 1981.0 1981.0 0.0 0.0
1500 37.0 24.7 - 182.7 2223.1 2003.1 2003.1 0.0 0.0
1600 36.7 24.7 - 182.7 2238.0 2023.2 2023.2 0.0 0.0
1700 35.9 24.8 - 182.7 2251.9 1994.0 1994.0 0.0 0.0
1800 34.6 24.7 - 182.7 2208.6 1992.9 1992.9 0.0 0.0
1900 33.2 24.8 - 182.7 2070.0 1841.4 1841.4 0.0 0.0
2000 31.7 24.8 - 182.7 1926.1 1704.6 1704.6 0.0 0.0
2100 30.4 24.7 - 182.7 1800.2 1640.9 1640.9 0.0 0.0
2200 29.3 24.7 - 182.7 1681.8 1520.5 1520.5 0.0 0.0
2300 28.4 24.6 - 182.7 1583.2 1477.6 1477.6 0.0 0.0

Hourly Analysis Program v4.80 Page 272 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C3-29 Mech Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 - 213.4 1769.8 1673.8 1673.8 0.0 0.0
0100 27.2 24.6 - 213.4 1691.1 1584.0 1584.0 0.0 0.0
0200 26.6 24.6 - 213.4 1611.2 1496.5 1496.5 0.0 0.0
0300 26.2 24.5 - 213.4 1543.3 1486.5 1486.5 0.0 0.0
0400 25.8 24.5 - 213.4 1488.1 1417.2 1417.2 0.0 0.0
0500 25.7 24.5 - 213.4 1459.1 1378.2 1378.2 0.0 0.0
0600 25.9 24.5 - 213.4 1470.5 1380.9 1380.9 0.0 0.0
0700 26.5 24.5 - 213.4 1523.5 1426.1 1426.1 0.0 0.0
0800 27.5 24.6 - 213.4 1632.3 1491.4 1491.4 0.0 0.0
0900 29.0 24.6 - 213.4 1798.4 1668.8 1668.8 0.0 0.0
1000 30.7 24.6 - 213.4 1996.7 1862.8 1862.8 0.0 0.0
1100 32.6 24.7 - 213.4 2227.7 2002.3 2002.3 0.0 0.0
1200 34.4 24.7 - 213.4 2451.9 2166.9 2166.9 0.0 0.0
1300 35.8 24.7 - 213.4 2559.9 2287.9 2287.9 0.0 0.0
1400 36.7 24.7 - 213.4 2579.5 2316.7 2316.7 0.0 0.0
1500 37.0 24.7 - 213.4 2597.9 2342.9 2342.9 0.0 0.0
1600 36.7 24.8 - 213.4 2615.0 2311.1 2311.1 0.0 0.0
1700 35.9 24.8 - 213.4 2631.0 2344.4 2344.4 0.0 0.0
1800 34.6 24.8 - 213.4 2582.6 2308.2 2308.2 0.0 0.0
1900 33.2 24.8 - 213.4 2422.5 2101.2 2101.2 0.0 0.0
2000 31.7 24.7 - 213.4 2256.2 2031.4 2031.4 0.0 0.0
2100 30.4 24.7 - 213.4 2110.8 1886.3 1886.3 0.0 0.0
2200 29.3 24.7 - 213.4 1974.1 1827.8 1827.8 0.0 0.0
2300 28.4 24.7 - 213.4 1860.2 1706.7 1706.7 0.0 0.0

ZONE: C3-25 AHURoom


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 - 129.2 1049.4 958.5 958.5 0.0 0.0
0100 27.2 24.6 - 129.2 999.8 909.2 909.2 0.0 0.0
0200 26.6 24.5 - 129.2 949.4 891.3 891.3 0.0 0.0
0300 26.2 24.5 - 129.2 906.7 844.2 844.2 0.0 0.0
0400 25.8 24.5 - 129.2 871.9 807.1 807.1 0.0 0.0
0500 25.7 24.5 - 129.2 853.7 787.1 787.1 0.0 0.0
0600 25.9 24.5 - 129.2 860.8 792.6 792.6 0.0 0.0
0700 26.5 24.5 - 129.2 894.2 824.1 824.1 0.0 0.0
0800 27.5 24.6 - 129.2 962.7 862.7 862.7 0.0 0.0
0900 29.0 24.6 - 129.2 1067.3 936.2 936.2 0.0 0.0
1000 30.7 24.7 - 129.2 1192.2 1031.2 1031.2 0.0 0.0
1100 32.6 24.7 - 129.2 1337.7 1163.4 1163.4 0.0 0.0
1200 34.4 24.7 - 129.2 1478.9 1316.5 1316.5 0.0 0.0
1300 35.8 24.7 - 129.2 1547.3 1387.8 1387.8 0.0 0.0
1400 36.7 24.7 - 129.2 1559.7 1402.8 1402.8 0.0 0.0
1500 37.0 24.7 - 129.2 1571.2 1416.4 1416.4 0.0 0.0
1600 36.7 24.7 - 129.2 1582.0 1428.8 1428.8 0.0 0.0
1700 35.9 24.7 - 129.2 1592.1 1440.2 1440.2 0.0 0.0
1800 34.6 24.7 - 129.2 1561.2 1410.8 1410.8 0.0 0.0
1900 33.2 24.7 - 129.2 1460.4 1341.2 1341.2 0.0 0.0
2000 31.7 24.7 - 129.2 1355.7 1239.5 1239.5 0.0 0.0
2100 30.4 24.7 - 129.2 1264.1 1143.7 1143.7 0.0 0.0
2200 29.3 24.7 - 129.2 1178.0 1059.7 1059.7 0.0 0.0
2300 28.4 24.6 - 129.2 1106.2 1024.6 1024.6 0.0 0.0

Hourly Analysis Program v4.80 Page 273 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C3-12 Mech Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.6 - 130.7 1050.0 956.4 956.4 0.0 0.0
0100 27.2 24.6 - 130.7 998.7 940.1 940.1 0.0 0.0
0200 26.6 24.6 - 130.7 946.6 884.3 884.3 0.0 0.0
0300 26.2 24.6 - 130.7 902.4 839.0 839.0 0.0 0.0
0400 25.8 24.5 - 130.7 866.5 802.8 802.8 0.0 0.0
0500 25.7 24.5 - 130.7 847.6 784.0 784.0 0.0 0.0
0600 25.9 24.5 - 130.7 855.0 791.1 791.1 0.0 0.0
0700 26.5 24.5 - 130.7 889.5 824.2 824.2 0.0 0.0
0800 27.5 24.6 - 130.7 960.3 859.0 859.0 0.0 0.0
0900 29.0 24.6 - 130.7 1068.5 959.4 959.4 0.0 0.0
1000 30.7 24.6 - 130.7 1197.7 1094.0 1094.0 0.0 0.0
1100 32.6 24.6 - 130.7 1348.1 1238.7 1238.7 0.0 0.0
1200 34.4 24.8 - 130.7 1494.1 1280.9 1280.9 0.0 0.0
1300 35.8 24.9 - 130.7 1565.0 1331.9 1331.9 0.0 0.0
1400 36.7 24.8 - 130.7 1577.8 1359.8 1359.8 0.0 0.0
1500 37.0 24.8 - 130.7 1589.8 1383.1 1383.1 0.0 0.0
1600 36.7 24.8 - 130.7 1601.0 1426.4 1426.4 0.0 0.0
1700 35.9 24.8 - 130.7 1611.4 1446.4 1446.4 0.0 0.0
1800 34.6 24.8 - 130.7 1579.3 1423.0 1423.0 0.0 0.0
1900 33.2 24.8 - 130.7 1475.0 1315.5 1315.5 0.0 0.0
2000 31.7 24.8 - 130.7 1366.7 1214.2 1214.2 0.0 0.0
2100 30.4 24.7 - 130.7 1272.0 1163.2 1163.2 0.0 0.0
2200 29.3 24.7 - 130.7 1183.0 1074.9 1074.9 0.0 0.0
2300 28.4 24.6 - 130.7 1108.8 1035.8 1035.8 0.0 0.0

ZONE: C4-26 Ventilation Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 - 316.7 3264.9 3161.2 3161.2 0.0 0.0
0100 27.2 24.8 - 316.7 3206.7 3026.2 3026.2 0.0 0.0
0200 26.6 24.7 - 316.7 3147.6 3066.2 3066.2 0.0 0.0
0300 26.2 24.7 - 316.7 3097.5 3026.9 3026.9 0.0 0.0
0400 25.8 24.6 - 316.7 3056.7 3028.4 3028.4 0.0 0.0
0500 25.7 24.7 - 316.7 3035.3 2936.2 2936.2 0.0 0.0
0600 25.9 24.7 - 316.7 3043.7 2951.2 2951.2 0.0 0.0
0700 26.5 24.7 - 316.7 3082.8 3008.3 3008.3 0.0 0.0
0800 27.5 24.7 - 316.7 3163.1 3024.8 3024.9 0.0 0.0
0900 29.0 24.7 - 316.7 3285.8 3183.9 3183.9 0.0 0.0
1000 30.7 24.8 - 316.7 3432.3 3235.4 3235.4 0.0 0.0
1100 32.6 24.8 - 316.7 3602.9 3385.8 3385.8 0.0 0.0
1200 34.4 24.8 - 316.7 3768.5 3526.3 3526.3 0.0 0.0
1300 35.8 24.8 - 316.7 3851.0 3647.1 3647.1 0.0 0.0
1400 36.7 24.9 - 316.7 3865.6 3616.1 3616.1 0.0 0.0
1500 37.0 24.9 - 316.7 3879.2 3635.0 3635.0 0.0 0.0
1600 36.7 24.9 - 316.7 3891.9 3659.3 3659.3 0.0 0.0
1700 35.9 24.9 - 316.7 3903.8 3657.7 3657.7 0.0 0.0
1800 34.6 24.9 - 316.7 3865.3 3591.4 3591.4 0.0 0.0
1900 33.2 24.8 - 316.7 3747.0 3569.6 3569.6 0.0 0.0
2000 31.7 24.9 - 316.7 3624.2 3412.5 3412.5 0.0 0.0
2100 30.4 24.8 - 316.7 3516.8 3385.7 3385.6 0.0 0.0
2200 29.3 24.8 - 316.7 3415.8 3250.6 3250.6 0.0 0.0
2300 28.4 24.8 - 316.7 3331.6 3230.3 3230.3 0.0 0.0

Hourly Analysis Program v4.80 Page 274 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C4-06 Ventilation Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.7 - 316.0 3464.1 3444.2 3444.2 0.0 0.0
0100 27.2 24.9 - 316.0 3424.9 3254.1 3254.1 0.0 0.0
0200 26.6 24.6 - 316.0 3385.0 3376.1 3376.1 0.0 0.0
0300 26.2 24.9 - 316.0 3351.2 3201.0 3201.0 0.0 0.0
0400 25.8 24.7 - 316.0 3323.7 3298.8 3298.8 0.0 0.0
0500 25.7 24.6 - 316.0 3309.3 3280.9 3280.9 0.0 0.0
0600 25.9 24.7 - 316.0 3315.0 3255.1 3255.1 0.0 0.0
0700 26.5 24.8 - 316.0 3341.3 3240.5 3240.5 0.0 0.0
0800 27.5 24.6 - 316.0 3395.5 3352.3 3352.3 0.0 0.0
0900 29.0 24.8 - 316.0 3478.2 3328.5 3328.5 0.0 0.0
1000 30.7 24.9 - 316.0 3576.9 3423.6 3423.6 0.0 0.0
1100 32.6 24.9 - 316.0 3691.9 3533.3 3533.3 0.0 0.0
1200 34.4 24.9 - 316.0 3803.6 3641.7 3641.7 0.0 0.0
1300 35.8 24.9 - 316.0 3859.2 3692.7 3692.7 0.0 0.0
1400 36.7 24.8 - 316.0 3869.0 3758.7 3758.7 0.0 0.0
1500 37.0 24.9 - 316.0 3878.2 3701.5 3701.5 0.0 0.0
1600 36.7 24.8 - 316.0 3886.8 3796.0 3796.0 0.0 0.0
1700 35.9 25.0 - 316.0 3894.8 3701.6 3701.6 0.0 0.0
1800 34.6 24.9 - 316.0 3868.9 3729.7 3729.7 0.0 0.0
1900 33.2 24.8 - 316.0 3789.1 3695.4 3695.4 0.0 0.0
2000 31.7 24.8 - 316.0 3706.3 3621.9 3621.9 0.0 0.0
2100 30.4 24.9 - 316.0 3633.9 3486.4 3486.4 0.0 0.0
2200 29.3 24.8 - 316.0 3565.8 3459.4 3459.4 0.0 0.0
2300 28.4 24.9 - 316.0 3509.1 3388.9 3388.9 0.0 0.0

ZONE: C4-10 Irrigation Pump


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 - 210.8 2285.8 2190.3 2190.3 0.0 0.0
0100 27.2 24.7 - 210.8 2257.3 2223.4 2223.4 0.0 0.0
0200 26.6 24.8 - 210.8 2228.4 2152.0 2152.0 0.0 0.0
0300 26.2 24.8 - 210.8 2203.8 2124.8 2124.8 0.0 0.0
0400 25.8 24.7 - 210.8 2183.9 2139.5 2139.5 0.0 0.0
0500 25.7 24.8 - 210.8 2173.4 2079.2 2079.2 0.0 0.0
0600 25.9 24.6 - 210.8 2177.5 2150.1 2150.1 0.0 0.0
0700 26.5 24.6 - 210.8 2196.6 2166.6 2166.6 0.0 0.0
0800 27.5 24.7 - 210.8 2236.0 2168.8 2168.8 0.0 0.0
0900 29.0 24.9 - 210.8 2296.1 2178.2 2178.2 0.0 0.0
1000 30.7 24.7 - 210.8 2367.8 2306.8 2306.8 0.0 0.0
1100 32.6 24.8 - 210.8 2451.4 2343.0 2343.0 0.0 0.0
1200 34.4 24.8 - 210.8 2532.5 2459.6 2459.6 0.0 0.0
1300 35.8 24.9 - 210.8 2572.9 2429.5 2429.5 0.0 0.0
1400 36.7 24.8 - 210.8 2580.0 2511.6 2511.6 0.0 0.0
1500 37.0 25.0 - 210.8 2586.7 2414.8 2414.8 0.0 0.0
1600 36.7 24.9 - 210.8 2592.9 2491.5 2491.5 0.0 0.0
1700 35.9 24.9 - 210.8 2598.8 2495.2 2495.2 0.0 0.0
1800 34.6 24.9 - 210.8 2579.9 2456.1 2456.1 0.0 0.0
1900 33.2 24.9 - 210.8 2522.0 2434.6 2434.6 0.0 0.0
2000 31.7 24.9 - 210.8 2461.8 2370.4 2370.4 0.0 0.0
2100 30.4 24.8 - 210.8 2409.2 2358.6 2358.6 0.0 0.0
2200 29.3 24.9 - 210.8 2359.7 2258.9 2258.9 0.0 0.0
2300 28.4 24.8 - 210.8 2318.5 2253.2 2253.2 0.0 0.0

Hourly Analysis Program v4.80 Page 275 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C4-12 Ventilation Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 - 313.9 3493.0 3432.4 3432.4 0.0 0.0
0100 27.2 24.6 - 313.9 3458.6 3448.5 3448.5 0.0 0.0
0200 26.6 24.9 - 313.9 3423.8 3315.9 3315.9 0.0 0.0
0300 26.2 24.9 - 313.9 3394.2 3288.4 3288.4 0.0 0.0
0400 25.8 24.9 - 313.9 3370.2 3263.3 3263.3 0.0 0.0
0500 25.7 24.9 - 313.9 3357.5 3249.7 3249.7 0.0 0.0
0600 25.9 24.9 - 313.9 3362.5 3253.7 3253.7 0.0 0.0
0700 26.5 24.9 - 313.9 3385.5 3275.9 3275.9 0.0 0.0
0800 27.5 24.9 - 313.9 3432.9 3322.6 3322.6 0.0 0.0
0900 29.0 24.9 - 313.9 3505.3 3394.5 3394.5 0.0 0.0
1000 30.7 24.9 - 313.9 3591.7 3480.6 3480.6 0.0 0.0
1100 32.6 24.8 - 313.9 3692.3 3618.0 3618.0 0.0 0.0
1200 34.4 25.0 - 313.9 3790.0 3641.3 3641.3 0.0 0.0
1300 35.8 25.0 - 313.9 3838.7 3694.8 3694.8 0.0 0.0
1400 36.7 25.0 - 313.9 3847.3 3705.5 3705.5 0.0 0.0
1500 37.0 25.0 - 313.9 3855.3 3715.3 3715.3 0.0 0.0
1600 36.7 25.0 - 313.9 3862.8 3724.3 3724.3 0.0 0.0
1700 35.9 25.0 - 313.9 3869.8 3733.7 3733.7 0.0 0.0
1800 34.6 25.0 - 313.9 3847.1 3713.1 3713.1 0.0 0.0
1900 33.2 25.0 - 313.9 3777.4 3644.9 3644.9 0.0 0.0
2000 31.7 24.9 - 313.9 3704.9 3629.8 3629.8 0.0 0.0
2100 30.4 25.0 - 313.9 3641.6 3520.5 3520.5 0.0 0.0
2200 29.3 24.8 - 313.9 3582.0 3513.8 3513.8 0.0 0.0
2300 28.4 25.0 - 313.9 3532.3 3380.2 3380.2 0.0 0.0

ZONE: GF-48 Mech Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.5 - 230.2 1638.6 1545.7 1545.7 0.0 0.0
0100 27.2 24.5 - 230.2 1544.2 1462.4 1462.4 0.0 0.0
0200 26.6 24.4 - 230.2 1451.0 1379.8 1379.8 0.0 0.0
0300 26.2 24.5 - 230.2 1371.8 1258.2 1258.2 0.0 0.0
0400 25.8 24.4 - 230.2 1306.5 1250.9 1250.9 0.0 0.0
0500 25.7 24.4 - 230.2 1269.6 1182.6 1182.6 0.0 0.0
0600 25.9 24.4 - 230.2 1279.0 1217.5 1217.5 0.0 0.0
0700 26.5 24.4 - 230.2 1338.8 1287.4 1287.4 0.0 0.0
0800 27.5 24.4 - 230.2 1461.1 1356.6 1356.6 0.0 0.0
0900 29.0 24.5 - 230.2 1645.2 1505.7 1505.7 0.0 0.0
1000 30.7 24.5 - 230.2 1864.7 1686.4 1686.4 0.0 0.0
1100 32.6 24.6 - 230.2 2121.7 1900.4 1900.4 0.0 0.0
1200 34.4 24.7 - 230.2 2388.3 2124.7 2124.7 0.0 0.0
1300 35.8 24.7 - 230.2 2558.9 2272.0 2272.0 0.0 0.0
1400 36.7 24.8 - 230.2 2645.4 2351.1 2351.1 0.0 0.0
1500 37.0 24.7 - 230.2 2722.5 2472.6 2472.6 0.0 0.0
1600 36.7 24.7 - 230.2 2777.6 2508.4 2508.4 0.0 0.0
1700 35.9 24.8 - 230.2 2800.2 2497.3 2497.3 0.0 0.0
1800 34.6 24.8 - 230.2 2714.4 2395.7 2395.7 0.0 0.0
1900 33.2 24.7 - 230.2 2479.7 2247.7 2247.7 0.0 0.0
2000 31.7 24.7 - 230.2 2247.3 2058.8 2058.8 0.0 0.0
2100 30.4 24.6 - 230.2 2056.2 1901.0 1901.0 0.0 0.0
2200 29.3 24.6 - 230.2 1886.9 1759.1 1759.1 0.0 0.0
2300 28.4 24.5 - 230.2 1748.3 1641.0 1641.0 0.0 0.0

Hourly Analysis Program v4.80 Page 276 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C4-01 Ventilation Room


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 - 305.0 3381.3 3304.6 3304.6 0.0 0.0
0100 27.2 24.7 - 305.0 3346.8 3282.5 3282.5 0.0 0.0
0200 26.6 24.9 - 305.0 3311.8 3181.4 3181.4 0.0 0.0
0300 26.2 24.7 - 305.0 3282.1 3248.7 3248.7 0.0 0.0
0400 25.8 24.7 - 305.0 3257.9 3218.7 3218.7 0.0 0.0
0500 25.7 24.7 - 305.0 3245.2 3201.4 3201.4 0.0 0.0
0600 25.9 24.7 - 305.0 3250.2 3199.2 3199.2 0.0 0.0
0700 26.5 24.7 - 305.0 3273.4 3214.2 3214.2 0.0 0.0
0800 27.5 24.7 - 305.0 3321.0 3245.5 3245.5 0.0 0.0
0900 29.0 24.7 - 305.0 3393.7 3314.5 3314.5 0.0 0.0
1000 30.7 24.8 - 305.0 3480.5 3358.6 3358.6 0.0 0.0
1100 32.6 24.8 - 305.0 3581.6 3469.7 3469.7 0.0 0.0
1200 34.4 24.8 - 305.0 3679.8 3550.1 3550.1 0.0 0.0
1300 35.8 24.9 - 305.0 3728.7 3583.4 3583.4 0.0 0.0
1400 36.7 24.9 - 305.0 3737.3 3590.9 3590.9 0.0 0.0
1500 37.0 25.0 - 305.0 3745.4 3572.0 3572.0 0.0 0.0
1600 36.7 24.9 - 305.0 3752.9 3613.9 3613.9 0.0 0.0
1700 35.9 25.0 - 305.0 3760.0 3562.7 3562.7 0.0 0.0
1800 34.6 24.7 - 305.0 3737.2 3689.8 3689.8 0.0 0.0
1900 33.2 24.8 - 305.0 3667.1 3559.4 3559.4 0.0 0.0
2000 31.7 24.9 - 305.0 3594.3 3479.2 3479.2 0.0 0.0
2100 30.4 24.9 - 305.0 3530.6 3404.2 3404.2 0.0 0.0
2200 29.3 24.7 - 305.0 3470.8 3426.4 3426.4 0.0 0.0
2300 28.4 24.7 - 305.0 3420.9 3368.1 3368.1 0.0 0.0

ZONE: C2-05 Water Feature BP


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.8 - 298.3 3179.3 3075.2 3075.2 0.0 0.0
0100 27.2 24.9 - 298.3 3133.9 2953.3 2953.3 0.0 0.0
0200 26.6 24.7 - 298.3 3087.7 3005.1 3005.1 0.0 0.0
0300 26.2 24.7 - 298.3 3048.6 2954.9 2954.9 0.0 0.0
0400 25.8 24.8 - 298.3 3016.7 2877.8 2877.8 0.0 0.0
0500 25.7 24.7 - 298.3 3000.0 2918.4 2918.4 0.0 0.0
0600 25.9 24.6 - 298.3 3006.6 2984.2 2984.2 0.0 0.0
0700 26.5 24.8 - 298.3 3037.1 2915.4 2915.4 0.0 0.0
0800 27.5 24.9 - 298.3 3099.9 2929.8 2929.8 0.0 0.0
0900 29.0 24.8 - 298.3 3195.8 3083.2 3083.2 0.0 0.0
1000 30.7 24.8 - 298.3 3310.2 3200.2 3200.2 0.0 0.0
1100 32.6 24.7 - 298.3 3443.4 3373.5 3373.5 0.0 0.0
1200 34.4 24.8 - 298.3 3572.8 3446.9 3446.9 0.0 0.0
1300 35.8 24.9 - 298.3 3635.4 3445.8 3445.8 0.0 0.0
1400 36.7 24.9 - 298.3 3646.7 3461.7 3461.7 0.0 0.0
1500 37.0 24.9 - 298.3 3657.3 3473.6 3473.6 0.0 0.0
1600 36.7 24.9 - 298.3 3667.2 3483.8 3483.8 0.0 0.0
1700 35.9 24.9 - 298.3 3676.5 3491.9 3491.9 0.0 0.0
1800 34.6 24.8 - 298.3 3648.2 3539.5 3539.5 0.0 0.0
1900 33.2 24.8 - 298.3 3555.9 3465.4 3465.4 0.0 0.0
2000 31.7 24.8 - 298.3 3459.9 3359.9 3359.9 0.0 0.0
2100 30.4 24.9 - 298.3 3376.0 3206.3 3206.3 0.0 0.0
2200 29.3 24.8 - 298.3 3297.2 3186.9 3186.9 0.0 0.0
2300 28.4 24.9 - 298.3 3231.4 3040.3 3040.3 0.0 0.0

Hourly Analysis Program v4.80 Page 277 of 773


Hourly Zone Loads for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:06PM

ZONE: C1-134 - Water Feature


DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.7 24.9 - 279.4 2937.6 2830.4 2830.4 0.0 0.0
0100 27.2 24.8 - 279.4 2896.2 2808.2 2808.2 0.0 0.0
0200 26.6 24.8 - 279.4 2856.3 2778.9 2778.9 0.0 0.0
0300 26.2 24.8 - 279.4 2822.3 2751.9 2751.9 0.0 0.0
0400 25.8 24.7 - 279.4 2794.3 2765.5 2765.5 0.0 0.0
0500 25.7 24.8 - 279.4 2777.2 2687.1 2687.1 0.0 0.0
0600 25.9 24.8 - 279.4 2778.4 2701.1 2701.1 0.0 0.0
0700 26.5 24.7 - 279.4 2805.0 2767.8 2767.8 0.0 0.0
0800 27.5 24.9 - 279.4 2866.1 2718.4 2718.4 0.0 0.0
0900 29.0 24.8 - 279.4 2959.4 2892.2 2892.2 0.0 0.0
1000 30.7 24.8 - 279.4 3071.0 2967.7 2967.7 0.0 0.0
1100 32.6 25.0 - 279.4 3196.8 3042.2 3042.2 0.0 0.0
1200 34.4 24.9 - 279.4 3317.9 3187.3 3187.3 0.0 0.0
1300 35.8 24.8 - 279.4 3389.6 3317.1 3317.1 0.0 0.0
1400 36.7 25.0 - 279.4 3419.4 3252.1 3252.1 0.0 0.0
1500 37.0 25.0 - 279.4 3437.8 3308.6 3308.6 0.0 0.0
1600 36.7 24.9 - 279.4 3443.7 3325.8 3325.8 0.0 0.0
1700 35.9 24.8 - 279.4 3436.4 3360.7 3360.7 0.0 0.0
1800 34.6 24.7 - 279.4 3392.7 3349.7 3349.7 0.0 0.0
1900 33.2 25.0 - 279.4 3298.4 3154.0 3154.0 0.0 0.0
2000 31.7 24.8 - 279.4 3201.9 3140.7 3140.7 0.0 0.0
2100 30.4 24.8 - 279.4 3119.5 3066.5 3066.5 0.0 0.0
2200 29.3 24.8 - 279.4 3046.2 2953.2 2953.2 0.0 0.0
2300 28.4 24.8 - 279.4 2985.9 2902.7 2902.7 0.0 0.0

Hourly Analysis Program v4.80 Page 278 of 773


System Psychrometrics for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:12PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 37.0 0.01203 0 400 0 0
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 24.9 0.00000 9261 0 106293 0
Return Plenum Outlet -17.8 0.00000 9261 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.101 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2687.3 W/(L/s)
Site Altitude = 773.0 m

Hourly Analysis Program v4.80 Page 279 of 773


System Psychrometrics for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:12PM

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
C1-132 Mech Room ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24.8 0.00002 314 0 - -
Cooling Coil Outlet - 15.0 0.00002 314 0 3383 0
Heating Coil Inlet - 15.0 0.00002 314 0 - -
Heating Coil Outlet - 15.0 0.00002 314 0 0 -
Zone Air - 24.8 0.00002 314 0 3383 -
C2-34 Ventilation Room (
Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24.8 0.00002 321 0 - -
Cooling Coil Outlet - 14.5 0.00002 321 0 3664 0
Heating Coil Inlet - 14.5 0.00002 321 0 - -
Heating Coil Outlet - 14.5 0.00002 321 0 0 -
Zone Air - 24.8 0.00002 321 0 3664 -
C2-01 Mech Room ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24.9 0.00002 380 0 - -
Cooling Coil Outlet - 14.5 0.00002 380 0 4352 0
Heating Coil Inlet - 14.5 0.00002 380 0 - -
Heating Coil Outlet - 14.5 0.00002 380 0 0 -
Zone Air - 24.9 0.00002 380 0 4352 -
C2-42 AHU Room ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24.9 0.00002 582 0 - -
Cooling Coil Outlet - 14.6 0.00002 582 0 6555 0
Heating Coil Inlet - 14.6 0.00002 582 0 - -
Heating Coil Outlet - 14.6 0.00002 582 0 0 -
Zone Air - 24.9 0.00002 582 0 6555 -
C2-04 AHU Room ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24.8 0.00002 173 0 - -
Cooling Coil Outlet - 14.9 0.00002 173 0 1880 0
Heating Coil Inlet - 14.9 0.00002 173 0 - -
Heating Coil Outlet - 14.9 0.00002 173 0 0 -
Zone Air - 24.8 0.00002 173 0 1880 -
C2-07 Ventilation Room (
Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 25.0 0.00002 336 0 - -
Cooling Coil Outlet - 14.2 0.00002 336 0 4000 0
Heating Coil Inlet - 14.2 0.00002 336 0 - -
Heating Coil Outlet - 14.2 0.00002 336 0 0 -
Zone Air - 25.0 0.00002 336 0 4000 -
C2-08 Indoor Swimming (
Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 25.0 0.00002 381 0 - -
Cooling Coil Outlet - 14.5 0.00002 381 0 4386 0
Heating Coil Inlet - 14.5 0.00002 381 0 - -
Heating Coil Outlet - 14.5 0.00002 381 0 0 -
Zone Air - 25.0 0.00002 381 0 4386 -
C2-20 Mech Room ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24.8 0.00002 121 0 - -
Cooling Coil Outlet - 15.0 0.00002 121 0 1307 0
Heating Coil Inlet - 15.0 0.00002 121 0 - -
Heating Coil Outlet - 15.0 0.00002 121 0 0 -
Zone Air - 24.8 0.00002 121 0 1307 -
C2-15 Pump Room ( Cooling )
Ventilation Air - - - 0 - - -

Hourly Analysis Program v4.80 Page 280 of 773


System Psychrometrics for FCU - Mechanical Rooms
Project Name: J17006-0100D FD REV2 11/19/2018
Prepared by: dar 07:12PM

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Cooling Coil Inlet - 24.9 0.00002 530 0 - -
Cooling Coil Outlet - 14.1 0.00002 530 0 6304 0
Heating Coil Inlet - 14.1 0.00002 530 0 - -
Heating Coil Outlet - 14.1 0.00002 530