1.0 INTRODUCTION
1.1 GENERAL
This design report is for the foundation design for Prefabricated Data Storage
containers. There are three number of containers of size 40'x23', each will be
equipped with module of weight 24 ton. These container will rest on concrete
pedestals and will be tied with anchor bolts. The concrete pedestals will be
supported on a MAT foundation as per requirement and recommendations of
provided soil report. Below sections give the details of loading on each
pedestal. The MAT foundation was modeled on SAFE to check the bearing
pressure, punching & beam shear and design reinforcement.
Allowable Bearing Capacity at 5 feet from Ground Level = 0.8 tsf = 1.76 ksf
Soil report recommends provision of 18 inch MAT foundation
3.0 DURABILITY
RC Beams 1.50 in
Foundations 2.00 in
Slab
Top 0.75 in
Bottom 1.0 in
DATA CONTAINER FOUNDATION
ANALYSIS ON SAFE
The 18 inch MAT foundation was modeled on on SAFE. Input model, input tables,
analysis results and design tables are shown below.
1. SAFE INPUT MODEL
Figure 1 3 D View
17 SOIL
33 SOIL
MAT SOIL
DATA CONTAINER FOUNDATION
2. ANALYSIS RESULTS
Shear capacity = 0.85x2x(f'c)1/2x bxd = 16.74 kips >> Maximum Shear (5 kips)
DATA CONTAINER FOUNDATION