Professional Documents
Culture Documents
a r t i c l e in fo abstract
Article history: This paper presents statistical analysis of the behaviour of the electrical performance of commercial
Received 23 March 2007 crystalline silicon photovoltaic (PV) modules tested in the Solar Test Installation of the European
Received in revised form Commission’s Joint Research Centre from 1990 up to 2006 to the IEC Standard 61215 and its direct
14 July 2008
predecessor CEC Specification 503. A strong correlation between different test results was not observed,
Accepted 15 July 2008
Available online 20 August 2008
indicating that the standard is a set of different, generally independent stress factors. The results
confirm the appropriateness of the testing scheme to reveal different module design problems related
Keywords: rather to the production quality control than material weakness in commercial PV modules.
PV modules qualification tests & 2008 Elsevier B.V. All rights reserved.
PV modules reliability
PV modules stability
0927-0248/$ - see front matter & 2008 Elsevier B.V. All rights reserved.
doi:10.1016/j.solmat.2008.07.008
ARTICLE IN PRESS
1594 A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604
Initial Visual Inspection (VI) / Performan ce Measurement (PS) / Insulation Test (IN)
NOCT VI / PS / IN VI / PS / IN VI / PS / IN
Performance VI / PS / IN VI / PS / IN
at Low Irrad.
Sequence 1 (SEQ1)
Outdoor
Humidity Freeze
Exposure
VI / PS / IN VI / PS / IN
VI / PS / IN VI / PS / IN
Fig. 1. The diagram of the IEC 61215 ed. 1 (1993) module qualification test sequence. Abbreviations: NOCT: performance at nominal operating cell temperature; VI: visual
inspection; PS: performance at standard test conditions; IN: insulation test.
Table 1
The summary of test levels included in the IEC 61215 edition 1 test sequence
UVEa UV test Exposure to UV irradiation of total of 15 kWh m2. The UV wavelength range from 280 to 385 nm,
with 5 kWh m2 in the wavelength range from 280 to 320 nm
HSP Hot-spot test 5 h exposure to 1000 W m2 irradiance in the worst-case hot-spot conditions
TC50 and TC200 Thermal cycling test 50 and 200 thermal cycles from 40 to +85 1C
HUF Humidity freeze test 10 cycles from +85 1C, 85% RH to 40 1C
ROB Robustness of termination test Determination of terminations’ capability to withstand appropriate mechanical stress
MEL Mechanical load test 2.4 kPa uniform load applied for 1 h to front and back surface in turn
HAR Hail test 25 mm diameter ice ball at 23 m s1, directed at 11 impact locations
a
Under consideration in the IEC 61215 second edition.
2. Measurements repeatability and uncertainty that specific module type. A total of 813 control measurements
have been performed. The standard deviation for each module
Repeated performance measurements made on the control type was calculated for Pmax, Isc and Voc. The dependence
module selected from each series of module types is used to of standard deviations on the test year, module Pmax, Isc and Voc
determine the measurement repeatability of the laboratory for and the number of repeated measurements is presented in Fig. 2.
ARTICLE IN PRESS
A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604 1595
Fig. 2. The dependence of standard deviations of modules’ Pmax, Isc and Voc on the test year and module size (Pmax).
It can be concluded that although the standard deviation of the assuming that all components have negligible covariance. For PV
control module measurements varies from 0% to about 2.5% for modules smaller than 2.20 m 1.80 m, the uncertainty with a
Pmax, 2.0% for Isc, and 1.5% for Voc, in the majority of cases the coverage factor of k ¼ 2 are for power (P) 71.5%, voltage (V)
values lie much below this level and are practically independent 70.3%, current (I) 71.3% and fill factor (FF) 70.72% .
of year.
A decrease in the standard deviation can be noticed from
2000 onwards especially for Voc values, which reflects the 3. Change in module performance following applied tests
implementation of an improved temperature control system
(Voc has a stronger temperature dependence than other para- A total of 1782 different tests have been executed on 199
meters). The standard deviation seems to depend on module different module types (174 commercial products, 25 different
Pmax (related to module area). Smaller values (below 0.5%) can project and experimental modules), 1181 individual modules, with
be observed for modules larger than 200Wp, but the reason could the individual tests numbers presented in Table 2.
be that 5 of the 7 large modules were measured over the last One of the most important pass/fail criteria of each module,
3 years, during which time the general repeatability has been following a stress test, is the loss in maximum power output. The
improved. absolute numbers and percentage of modules with maximum
The stability of the results confirms the high reproducibility of power loss 45% following applied stress tests, average power
the test methodology used at the ESTI Laboratory. The average losses and the associated standard deviations are presented in
value of standard deviation (1s) of all performed measurements is Table 3. Since module qualification test failure occurs if maximum
70.74% of the Pmax. Similar or even smaller standard deviations power loss exceeds 5% plus repeatability for a given type of
were determined for other electric parameters, namely: Voc module or due to the presence of a major physical defect or due to
70.31%, Isc 70.5% and FF 70.41%. a failure of modules insulation, the data collected in this table do
These values are in quite good agreement with the estimates not correspond to the actual number of rejected module types; it
for the uncertainty components which have been made following gives an indication on results spread and power loss levels caused
the ISO ‘‘Guide to the expression of uncertainty in measurement’’ by individual tests.
ARTICLE IN PRESS
1596 A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604
Table 2
Numbers of individual tests
OE HSP UVE Subtotal TC50 HUF TC200 DAH Subtotal ROB TW MEL HAR Subtotal
irrad. environ. mech.
tests tests tests
Tests of commercial modules 114 128 203 445 178 156 282 216 832 72 73 103 91 339
Tests of project modules 1 2 30 33 28 28 28 29 113 5 5 5 5 20
Total 115 130 233 478 206 184 310 245 945 77 78 108 96 359
Table 3
Numbers and percentage of modules with maximum power loss 45%, mean power losses and standard deviations values after individual qualification tests
Test TC200 UVE DAH OE HUF TC50 HAR MEL HSP ROB TW
Commercial modules
Average Pmax loss (%) 3.9 2.0 0.7 2.3 0.2 0.6 1.0 0.7 0.1 0.2 0.1
Standard deviation (%) 12.5 2.1 4.0 1.5 2.2 5.3 1.3 1.5 1.2 1.1 0.7
No. of Pmax losses 45% 29 19 11 4 3 3 1 1 0 0 0
Pmax losses 45% (%) 10.3 9.4 5.1 3.5 1.9 1.7 1.1 1.0 0.0 0.0 0.0
Project modules
Average Pmax loss (%) 1.7 5.7 4.6 5.5 4.3 3.6 7.5 1.3 3.8 0.4 0.3
Standard deviation (%) 2.1 15.3 4.8 - 5.7 3.4 14.3 1.6 4.2 1.4 0.4
No. of Pmax losses 45% 2 3 10 1 6 7 1 0 1 0 0
Pmax losses 45% (%) 7.1 10.0 34.5 100.0 21.4 25.0 20.0 0.0 50.0 0.0 0.0
Analysis of the percentage of modules exhibiting a power loss deviation among these tests. The greatest numbers of strongly
greater than 5% revealed that the most severe tests are the TC200, affected modules can be observed for the TC200, DAH, HUF and
UVE and DAH followed by OE, HUF and TC50. One should note that the UVE tests, where more than 5% of modules exhibit more than
19 commercial modules (11 different module types) exhibiting 6% loss in Pmax.
greater than 5% power loss following the UVE were mono-
crystalline silicon modules which had not undergone initial light
soaking prior to the UVE test (as is now foreseen in the revised IEC
4. Analysis of the results of the module pairs tests
61215 ed. 2 [3]). It must also be stressed that none of the
commercial modules following the UVE test suffered power loss
As mentioned in the introduction, most tests are conducted on
greater than 10%. None of the commercial modules suffered power
the pairs of modules. Tests conducted on two modules of the same
loss greater than 5% following the ROB, TW and HSP tests and only
type are expected to produce similar results (nearly identical
one failed the MEL and HAR test. For project modules (among
percentage loss in a given parameter), giving data points
which experimental prototypes can be found) also the TC50 and
distributed along the diagonal line on the scatter plot (Fig. 4).
HUF tests caused considerable degradation.
The results of the pairs tests are presented in the form of scatter
It can be observed that for commercial modules the TC200 test
plots of the percentage change of Pmax, vertical and horizontal
exhibits the largest variation of module behaviour with standard
axes represent results obtained from each of the modules pairs.
deviation values exceeding 12%. More coherent results are
For the sake of legibility, the most distinct results are outlined
obtained from the DAH and the TC50 tests with standard
with a contour. It can be observed from the scatter plots in the
deviation of about 4–5%. The HUF, UVE and OE tests seem to
figure given below that all tests produce slightly different scatter
produce much more coherent results with standard deviations of
type, although in all cases the majority of results are grouped
2.2%, 2.1% and 1.5%, respectively. The statistics for the project
within a similar range.
modules is slightly distorted but the main reason for that is the
In order to quantify different test results the average of
very limited number of tested module types and the fact that only
differences from the absolute value was calculated as follows:
4 out of all 25 project module types were experimental prototypes
utilizing novel materials (encapsulants, front/back substrate or 1X
framing structure), which degraded considerably during qualifica- DTest ¼ jTest1 Test2 j (1)
n n
tion tests.
More information concerning the spread of performance where Test1 and Test2 are the results for each module in the pair
losses, following the main environmental and irradiation tests, following a specific test and n is the total number of pairs. This
can be graphically presented in the form of bin plots—histograms parameter can be used as a measure of the scatter in the results
of the results (Fig. 3). The bar height represents the percentages of obtained. The total numbers of pairs tested, the average of
modules with a maximum power loss within the specified range. absolute differences and percentage of module pairs revealing
It can be observed that the majority of tests reveal a Gaussian-like difference 45% are presented in Table 4 for each test and for the
distribution with mean values close to those previously presented main electrical parameters.
in Table 3, slightly shifted because of the presence of the peak at The parameters presented in Table 4 give a rough indication
the ‘‘black’’ bin, representing module power loss greater than 6%. how strongly data are scattered in relation to the ideal case;
This peak is almost not present in the OE, HSP, MEL and the HAR values of DTest closer to zero represent more consistent behaviour
plots, which exhibit the smallest calculated value of standard of module pairs following an applied test.
ARTICLE IN PRESS
A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604 1597
Fig. 3. Histograms of qualification tests’ results (percentages of maximum power losses following the given tests).
The smallest values of both DTest and standard deviation of nificant degradation from the UVE test has been reflected in the
almost all electric parameters can be observed for the UVE test, second edition of the IEC 61215 standard [2] where the UVE has
followed by the sequence of (UVE, TC50, HUF), then HUF and DAH been classified as preconditioning test. The UVE test results also
tests. The UVE test yields the most uniform results of module seem to dominate in the results of the sequence of UVE, TC50 and
degradation (ultraviolet light affects the whole area of the HUF tests. Although the number of pairs, which were subjected to
module, causing the degradation of silicon proprieties and/or the test sequence, is limited (44 pairs were UVE tested only), the
encapsulating browning), resulting in rather small, but uniform, scatter type and values of calculated parameters are similar. The
power losses. Only 2 pairs out of 114 differ more than 5% in other environmental tests, such as the DAH and HUF, exhibit a
maximum power loss. One of these pairs was a prototype module similar behaviour to each other, causing 4 and 5 cases of a 45%
in which the UVE test caused severe delamination. (This module loss in maximum power, respectively. Results from the HUF test
type also failed in other tests.) The fact that the vast majority of are more consistent than DAH, revealing a slightly smaller value of
contemporary crystalline silicon modules did not exhibit sig- DTest and considerably smaller values of standard deviation.
ARTICLE IN PRESS
1598 A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604
Fig. 4. Scatter plots of percentage change of Pmax of module pairs (modules in pairs are labelled as ‘‘_1’’ and ‘‘_2’’) following the UVE, HUF, DAH, TC50, TC200 tests and the
SEQ1 sequence.
It can be observed from Table 4 that for the TC50, DAH, HUF scattered, with an increased number of cases, when only one of
and SEQ1 calculated values of DTest for different electrical the two tested modules suffered large power losses, while the
parameters have a similar order. The largest value of the DTest other in the pair still performed fairly well. As an example of such
occurs for the Pmax, followed by FF, Isc and Voc. A similar order can behaviour, I–V curves of two modules are presented in Fig. 5. It
be observed for the UVE test, but in this case the DTest value for FF can be observed that one module suffered power loss of 38.8%
is slightly higher than for Pmax. (TC200 caused loss of a substring) while the other displayed
The results of the TC200 test exhibit a slightly distorted order. almost no change.
Although the Pmax exhibits the largest value of DTest, it is followed The two thermal cycling tests, TC50 and TC200, differ only in
by Voc, Isc and FF. The results of this test are considerably more the number of cycles. The TC50, as can be expected, produces
ARTICLE IN PRESS
A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604 1599
more coherent results, with only 3 pairs differing by more than 5. Correlations between module test results
5%, while TC200 induces the greatest frequency of severe module
degradation—12 cases. Both tests seem to have greater impact on One of the aims of this analysis was the determination of any
point failures of cell strings or sub-strings within the module, relationship between different test results. Since the IEC 61215
rather than the whole area. Standard is designed as a set of different, generally separately
acting stress factors (although, for example, both the DAH and
Table 4 HUF combine the impact of high temperature and humidity), real-
Total numbers of pairs tested, the average of absolute differences and percentage life module operation is in the vast majority of cases a
of modules pairs revealing difference 45%
combination of a larger number of stress factors. In order to
Test UVE SEQ1 HUF DAH TC50 TC200 determine any possible cross-reference in test results, the
correlation (r) matrixes between losses in the main electric para-
No. of pairs 114 71 90 118 101 148 meters: Pmax, Isc, Voc and FF, individually for each test (Table 5),
Pmax and correlation matrixes between all tests for losses in the main
DTest 0.9 0.9 1.1 1.3 1.6 3.3 electric parameters were calculated (Table 6).
s 2.4 1.3 1.8 3.3 6.5 10.2 Correlation values larger than 0.7, indicating possible relation,
% 1.7 2.8 4.4 3.4 3.0 8.1
are marked in bold. Names of the columns and the rows ending
Isc with ‘‘_2’’ stand for the test of the second module in the pair of
DTest 0.6 0.6 0.6 0.8 0.7 1.9 modules.
s 0.8 0.6 1.1 2.7 1.5 9.9 Analysis of the results presented in Table 5 reveals that the
% 0.0 0.0 1.1 1.7 2.0 4.0
SEQ1 and the UVE test produce the most consistent results and
Voc correlation between the results of pairs of modules of the same
DTest 0.3 0.4 0.3 0.3 0.8 2.3 type can be observed for all electric parameters. For both SEQ1
s 0.7 0.8 0.3 0.3 4.6 9.9
and UVE tests, losses in Pmax are strongly correlated with losses in
% 0.9 1.4 0.0 0.0 1.0 4.7
Isc and Voc for each of the two modules. Results from the SEQ1
FF exhibit a higher degree of correlation in comparison to the UVE
DTest 1.0 0.8 1.0 0.9 1.5 1.8
test. However, this may only reflect the lower number of samples
s 3.9 0.7 2.0 1.4 4.7 8.0
% 2.6 0.0 4.4 3.4 4.0 6.0 tested through SEQ1 in comparison to the UVE and the fact that
the most distinct results were observed on a few modules that
DTest—average of absolute differences values (%); s—standard deviation of were UVE tested only. In the case of SEQ1 all losses are strongly
absolute differences (%); %—percentage of modules pairs revealing losses 45%. correlated with each other. For the other tests, correlation
Fig. 5. I–V curves of two modules of the same type before and following the TC200 test.
Table 5
Correlation matrixes of the main electric parameters for HUF, DAH, TC50, TC200, UVE tests and SEQ1 sequence
Pmax Pmax_2 Isc Isc_2 Voc Voc_2 FF FF_2 Pmax Pmax_2 Isc Isc_2 Voc Voc_2 FF FF 2 Pmax Pmax_2 Isc Isc_2 Voc Voc_2 FF FF_2
Pmax 0.7 0.5 0.5 0.7 0.3 1.0 0.5 0.2 0.4 0.3 1.0 0.9 1.0 0.1 1.0 1.0 1.0 1.0 0.8 1.0 1.0
Pmax 2 0.8 0.8 0.9 0.2 0.6 0.7 0.9 0.6 0.7 0.9 0.5 0.4 0.2 0.7 1.0 1.0 1.0 0.9 0.8 1.0 1.0
Isc 0.6 0.8 1.0 0.3 0.4 0.4 0.8 0.7 0.7 0.6 0.2 0.3 0.2 0.7 1.0 0.9 1.0 0.9 0.8 1.0 1.0
Isc 2 0.4 0.9 0.8 0.2 0.4 0.4 0.8 0.3 0.4 0.5 0.8 0.2 0.1 0.4 1.0 1.0 1.0 0.9 0.8 1.0 1.0
Voc 0.4 0.3 0.2 0.1 0.3 0.4 0.7 0.9 0.3 0.5 0 0.9 1.0 0.5 0.9 0.9 0.9 0.8 0.8 0.9 0.9
Voc 2 0.3 0.3 0.3 0.2 0.7 0.2 0.3 0.4 0.9 0.5 0 0.3 0.3 0.6 0.7 0.8 0.7 0.7 0.8 0.8 0.8
FF 0.9 0.4 0.1 0.0 0.2 0.1 0.6 0.6 0.4 0.4 0.1 0.3 0.2 0.9 0.9 0.9 0.9 0.8 0.9 0.7 1.0
FF 2 0.7 0.6 0.9 0.1 0.3 0.3 0.8 0.4 0.7 0.5 0.4 0.1 0.3 0.7 0.6 0.6 0.4 0.4 0.6 0.5 0.7
DAH TC200 UVE
ARTICLE IN PRESS
1600 A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604
DAH_2
between losses in different electric parameters is not so
0.9
0.2
0.5
0.2
0.4
0.3
0.0
0.0
0.1
0.1
0.1
straightforward.
Correlation values presented in Table 6 indicated rather weak
0.8
0.3
0.4
0.2
0.4
0.3
0.2
0.0
0.1
0.1
0.1
DAH
0.2
correlations are presented in the form of scatter plots. Since even
0.5
0.0
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
the behaviour of two modules of the same type, following one test
such as the HUF, TC50, TC200 or DAH, does not often demonstrate
TC200
0.7
0.2
0.0
0.0
0.0
0.0
0.0
0.1
0.1
0.1
0.1
0.7
0.5
0.3
0.3
0.4
0.2
0.2
0.2
0.1
0.1
0.1
cross-dependence of performance loss. The significant, but still
very low values of correlations can be noticed for the pairs of tests
(data presented in Table 6)
0.7
0.5
0.3
0.3
0.2
0.3
0.0
0.1
0.1
0.1
HUF
OE and UVE for Isc (r ¼ 0.6 for both modules), Pmax (r ¼ 0.5
TC50_2
0.4
0.5
0.5
0.2
0.0
0.1
0.1
0.1
0.1
0.1
0.1
and 0.4);
TC50 and UVE for Isc (r ¼ 0.5 for both modules), Pmax
(r ¼ 0.5 and 0.4); and
TC50
0.3
0.3
0.3
0.4
0.4
0.4
0.1
0.1
0.1
0.1
0
0.7
0.7
0.3
0.2
0.2
0.3
0.0
0.0
0.1
0.1
0.1
0.4
0.5
0.2
0.0
0.1
0.1
0.1
0.1
UVE
0.2
0.2
0.2
0.0
0.0
0.1
0.1
0.1
0.1
HSP
0.2
0.2
0.2
0.2
0.1
0.1
0.1
0.1
Voc
0
OE
FF
0.2
0.2
0.5
0.1
0.1
0.1
the plot with the UV source distinction. The majority of UVE tests
were carried out using a chamber equipped with high-intensity
0.9
0.4
0.2
0.3
0.3
0.2
0.4
0.6
0.1
0.1
DAH
0.0
0.1
0.1
0.1
0.1
0.1
0.2
0.3
0.3
0.5
0.0
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.2
0.2
0.0
0.1
0.1
0.2
0.2
0.0
0.1
0.1
0.1
0.1
0.1
HUF
0.2
0.2
0.4
0.5
0.6
0.4
0.2
0.2
0.2
0.1
0.1
0.2
0.5
0.4
0.6
0.2
0.2
0.3
0.2
0.0
0.0
0.0
carried out following the UVE can cause some recovery of module
performance (Fig. 8). This is why some negative correlation can be
UVE_2
0.9
0.6
0.4
0.4
0.3
0.3
0.2
0.2
observed between the UVE and the TC50. Similarly to the UVE–OE
0.1
0.1
0.1
0.5
0.4
0.3
0.3
0.2
0.0
0.1
0.1
0.1
UVE
technology.
The weakest correlation among the previously mentioned
0.2
0.3
0.3
0.2
0.2
0.2
0.0
0.1
0.1
0.1
0.1
HSP
0.3
0.2
0.2
0.3
0.3
0.0
0.0
0.0
0.1
Pmax
Isc
TC50_2
DAH_2
HUF_2
UVE_2
TC200
DAH
HUF
UVE
HSP
OE
A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604 1601
Fig. 6. Scatter plots of relative change of Pmax following the UVE and OE tests with Fig. 8. Scatter plots of relative change of Pmax following the UVE and TC50 tests
regard to module type (open circle—monocrystalline, filled circle—polycrystal- with regard to module type (open circle—monocrystalline, filled circle—polycrys-
line). talline).
Fig. 7. Scatter plots of relative change of Pmax following the UVE versus the OE Fig. 9. Scatter plots of relative change of Pmax following the TC200 and DAH tests.
tests with regard to light source (open square—fluorescent, filled square—HID
mercury).
1602 A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604
Fig. 10. Scatter plots of relative change of Pmax and relative changes of Voc, Isc, Imp and FF following the UVE test.
results are much more scattered. One of the reasons is that sequences and test levels are identical, apart from the UVE test,
failures do not have such a uniform impact on the whole module which was not included in the IEC standard. The ESTI laboratory,
area, such as in the case of the UVE. There are cases of substring however, performed the UVE test as a part of its type approval
failure (for multi-string constructions), single cell damage, testing procedure for each full test sequence. In 1998 the
interconnection problems due to cell dislocation, etc., which can complementary IEC 61345 [11] standard ‘‘UV test for PV modules’’
be attributed generally to quality control problems during the was published, detailing the UVE test. (The UVE test was
production process. The scatter plots of electrical parameters incorporated latter as a part of IEC 61215 ed. 2 [3].) Results
change following the most severe test: the TC200, which thermo- presented in Table 7 differ slightly from those previously
mechanically stresses cells’ interconnections, are presented in presented in Table 3 (because as stated in the introduction a
Fig. 11. The degradation of interconnections resulting in FF loss in failure according to the IEC 61215 is deemed to have occurred
the aftermath of series resistance increase can be observed as if the loss in maximum power following a single test is greater
correlation between relative FF and Pmax change. than 5%+the repeatability of the power measurement of the
control module), but similar conclusions can be drawn. The great
majority of failures occur following the environmental tests. The
6. Failure summary reasons of failure can be broadly shared between power loss and
major visual defect, insulation failure occurred only once. The
As mentioned in the introduction, the classification of major high failure rate following the TC200 indicates high fatigue, which
defects in tested PV modules is related to either visual, loss of is not observed to the same extent in the case of the TC50.
power or insulation failures can have a different nature. Table 7 The DAH test still provokes many failures, although encapsula-
summarises major defect types provoked during the years tion system seems to be quite mature in contemporary modules.
1990–2006 per Module Qualification Test procedure of commer- The UVE test provoked much smaller number of failures than the
cial modules conducted for clients seeking IEC 61215 type DAH test. Many module types suffered power loss following the
approval testing for their products. The total number of module UVE test of just greater than 5%, which is classified as a
types tested was 174. Out of those 130 module types (74.7%) successful result when the repeatability of the control module is
passed certification procedure, 27 (15.5%) passed after successful added to the 5% power limit. The effect of initial photon
retest and 17 types (9.7%) were rejected. degradation should be eliminated in the IEC 61215 ed. 2, which
From 1990 to 1995 tests were conducted according to the CEC incorporates an initial modules preconditioning. (Before begin-
Specification 503 [3]; the tests conducted from 1995 onwards are ning the testing, all modules, including control, shall be exposed
based on the first edition of the IEC 61215 [2]. Test results can be to sunlight, either real or simulated, to an irradiation level of
considered as fully comparable since in both cases the test 5–5.5 kWh/m2.)
ARTICLE IN PRESS
A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604 1603
Fig. 11. Scatter plots of relative change of Pmax and relative changes of Voc, Isc and FF following the TC200 test.
Table 7
Distribution of major defects of commercial modules provoked per Qualification Tests performed between 1990 and 2006
OE HSP UVE Total TC50 HUF TC200 DAH Total ROB MEL HAR TW Total
irrad. envir. mech.
tests tests tests
All failures
Visual defect 0 1 1 2 6 5 17 11 39 0 1 0 0 1
Power loss 1 0 3 4 3 3 18 4 28 0 1 0 0 1
Visual defect and power loss 0 0 0 0 2 0 7 1 10 0 0 0 0 0
Mechanical tests provoked very few failures since the correlation between different tests was not observed, validating
mechanical features of the modules are generally well under- the concept that the IEC 61215 standard is designed as a set of
stood; however, these tests can be fatal for non-standard modules different, generally separately acting stress factors. The selection
such as non-glass and pole mounted types. of tests ensures that different failure mechanisms are provoked,
revealing different design/material weaknesses.
The approach of executing environmental tests on modules
7. Conclusions pairs, used in the IEC 61215 standard, helps to indicate produc-
tion/quality control issues as well as overall design problems. The
The analysis of data from module tests based on the IEC 61215 results from pairs of modules tested can reveal significant
Standard confirms the ability of the module testing scheme to differences in behaviour of modules of the same type. The test
show design problems in commercial PV modules. Strong which produces the most scattered results is the TC200 test. For
ARTICLE IN PRESS
1604 A. Skoczek et al. / Solar Energy Materials & Solar Cells 92 (2008) 1593–1604
this test, the approach of measuring two different modules of a The publication of a revised standard in April 2005 has
given type increases significantly the failure detection rate. As included two new tests, the Wet Leakage Current Test and the
many as 8% of modules behaved differently (12 modules pairs out Bypass Diode Thermal Test, together with small modifications to
of 149). Other tests produce considerably more consistent some of the existing tests (TC200, HSP, etc.). The impact of these
behaviour. The TC200 is followed by the other environmental new tests shall be monitored to assess the failure rates and failure
tests: the HUF, which produces a difference of 4.4%, and the DAH, mechanisms.
3.4%. The other thermal cycling test, namely the TC50, differs from
the TC200 only by number of cycles. Reducing the number of References
cycles also reduced the number of differently behaving module
pairs, falling from 8% for the TC200 to 3% for the TC50. The most [1] J.H. Wohlgemuth, D.W. Cunningham, P. Monus, J. Miller, A. Nguyen, Long term
coherent results are produced by the test sequence 1 (SEQ1) and reliability of photovoltaic modules, Conference Record of the 2006 IEEE
Fourth World Conference on Photovoltaic Energy Conversion, vol. 2, 7–12 May
UVE tests. Results of these tests are not only the most coherent in
2006, Waikoloa, HI, USA, 2006, pp. 2050–2053.
terms of Pmax but strong correlation can also be found for all [2] IEC Central Office, IEC 61215: Crystalline silicon terrestrial photovoltaic (PV)
combinations of main electric parameters. modules—design qualification and type approval, 1993.
The analysis of many years of test results indicates no [3] IEC Central Office, IEC 61215 the second edition, Crystalline silicon terrestrial
photovoltaic modules—design qualification and type approval, 2005.
noticeable difference between modules incorporating polycrystal- [4] European Commission, CEC-Specification No. 501, EUR Report 7545 EN, 1981.
line or monocrystalline cells. The results confirm the appropriate- [5] J. Bishop, H.A. Ossenbrink, Results of four years of module qualification
ness of the testing scheme to reveal different module design testing to CEC Specification 503, in: Proceedings of the 13th European
Photovoltaic Solar Energy Conference, 23–27 October 1995, Nice, France,
problems related rather to either production quality control or 1995, pp. 2104–2109.
material weakness in commercial PV modules. Results from [6] H. Ossenbrink, T. Sample, Results of 12 years of module qualification to the
modules originating from different manufacturers but essentially IEC 61215 standard and CEC specification 503, in: Proceedings of the Third
World Conference on Photovoltaic Energy Conversion, vol. 2, Osaka, Japan,
produced from the same commercially available cells, encapsu-
2003, pp. 1882–1887.
lant and backsheet can exhibit different behaviour. This fact [7] E.D. Dunlop, D. Halton, The performance of crystalline silicon photovoltaic
leads to the conclusion that quality control during of the solar modules after 22 years of continuous outdoor exposure, Prog. Photovolt.
production process plays a crucial role in the behaviour of the 14 (1) (2005) 53.
[8] E.D. Dunlop, Lifetime performance of crystalline silicon PV modules, in:
final product. Proceedings of the Third Word Conference on Photovoltaic Energy Conver-
It can also be concluded that environmental tests like thermal sion, vol. 2, Osaka, Japan, 2003, pp. 2927–2930.
cycling (TC50 and TC200) cause thermo-mechanical fatigue to the [9] T. Sample, A. Skoczek, E.D. Dunlop, H.A. Ossenbrink, Data analysis of electrical
performance measurements from 15 years of module qualification tests, in:
interconnections, contributing to series resistance increase and Proceedings of the Fourth World Conference on Photovoltaic Energy
hence decreasing FF, while irradiation tests like the UVE test affect Conversion, vol. 2, 7–12 May 2006, Waikoloa, HI, USA, pp. 2042–2045.
the optical properties of the module, resulting in the lower Isc. [10] J. Knobloch, S.W. Glunz, V. Henniger, W. Warta, W. Wettling, Solar cells with
efficiencies above 21% processed from Czochralski grown silicon, in:
While the first type of losses is rather connected to quality control
Conference Record of the 2006 25th IEEE Photovoltaic Specialists Conference,
problems during the production process, the second type is 13–17 May 1996, Washington, DC, USA, 1996, pp. 405–408.
attributed to material weakness. [11] IEC Central Office, IEC 61345: UV test for photovoltaic (PV) modules, 1998.