Calculation for Duct Static Pressure Loss

FCU Fresh Air Supply Fan

Supply Fan Flow Rate: 2844 CMH

Duct
Equivelant Velocity Duct Loss Hudraulic Absolute Renold Friction Total Pressure
Fitting Airflow Rate Duct size (mm) Velocity Pressure
Duct Element Material Dia. Pressure Length Coefficients ASHRAE Fitting Number Diameter Roughness Number Factor Loss Param
Number Loss
(CMH) Round Rectangular (mm) (m/s) (Pa) (m) (Co) Dh (mm) Re f (Pa/m) (Pa)

1 RA Grille 2844 1250 150 420 5.7 19.6 *f 0 0 2.0


2 DUCT Plenum(1300x250x250) Galvernised Iron 2844 1300 250 578 3.0 5.5 0.3 419 0.09 83893 0.020 0.26 0.1
3 Flexible Duct 948 200 200 200 219 7.0 29.5 3.5 0.41 *f 0 0.00 0 0.000 0.00 12.1
4 DUCT Plenum(850x300x350) Galvernised Iron 2844 850 300 535 3.5 7.4 0.4 443 0.09 103536 0.019 0.32 0.1
5 FCU 3128 200 150 189 31.0 578.0 0 0.00 0 0.000 0.00 0.0
6 DUCT Plenum(850x300x350) Galvernised Iron 3128 850 300 535 3.9 9.0 0.4 443 0.09 113875 0.019 0.39 0.1
7 Flexible Duct 1043 200 200 200 219 7.7 35.6 3.5 0.41 *f 0 0.00 0 0.000 0.00 14.6
8 DUCT Plenum(1300x250x250) Galvernised Iron 3128 1300 250 578 3.3 6.6 0.3 419 0.09 92255 0.020 0.32 0.1
9 SA Grille 3128 1250 150 420 6.3 23.7 *f 0 0.00 0 0.000 0.00 5.0

Total Pressure Loss 0 0.00 0 0.000 0.00 34.1


Safty (10 %) 0 0.00 0 0.000 0.00 37.5
Require Static Pressure For Fan 38.0

*a ASHRAE Hand Book, Fundamentals 2001


*f Based on Manufacturer Data

Required External Static Pressure for PAU Fresh Air Supply Fan with 10% safety Design : 38 Pa
Mfg : Pa
Actual : Pa

1 Supply Air Flow Rate

Required Cooling Capacity = 12553.65 j/s


Specific heat capasity = 1000 j/kg.K
Temp difference = 12 0
C (Supply 12 C & Return 24 C)
=
Mass flow rate = 1.05 kg/s
Air density(20C) = 1.204 kg/m3

Supply Air flo rate = 0.87 m3/s


= 868.88 l/s = 3128 CMH
Supply flow rate from 1 flexible = 289.63 l/s = 1042.7 CMH

Fresh Air flow rate = 78.75 l/s (Calculated data)

Return Flow Rate = 790.13 l/s


Return Flow Rate form 1 flexible = 263.38 l/s

2 Flexible Duct Pressure drop


200 mm flexible duct pressure drop = 0.5 in Aq/100ft (manufactures data)
= 12.5 Pa/100ft
= 0.41 Pa/m
Tota flexible pressure drop(13m) = 2.87 pa
Parameters

790.13 l/s
l/s
l/s