You are on page 1of 10

POWER FACTOR CORRECTION AND LOAD

BALANCING IN THREE-PHASE
DISTRIBUTION SYSTEMS
*Bh SIX&, Anuradha Saxena and D.P.Kothari
Center for Energy Studies
*Department of Electrical Engineering
IIT, Hauz khas, New Delhi-110 016, INDIA

ABSTRACT - This papr deals with the different methods for currents but only with arc-furnace as a load by Cox and Mihod
compensating unbalanced three phase loah. Compensation of [101. Sumi et al [111 have described the system outline and
grounded, ungrounded star connected and delta connected three operating results of 20 MVA static Var Generator. An analysis
phase unbalanced load has been camed out. Three schemes haw to determine the response of the STATCON in transmission line
been proposed for neutral current compensatfon. A common
is provided by Schauder and Mehta [12]. Kearly et al have
approach has been folbwed fir power factor correction and load
bahcing. Simulated resulrs ma1 that aper covnsmon all three worked on microprocessor controlled model construction
supply currents are in phme with their respectiw phase wltages with network for dism'bution feeder [131. Ng et al [141 have used
equal magnitude resulting in a balanced load on supply system. fuzzy approach for placing the capacitors in distribution system.
The vast majority of the work is restricted to single phase line
L INTRODUCTION to line loads, thrwphase, three-wire loads. However, this paper
In recent years, there has been greatly increased demand for is an attempt to compensate all kinds of three-phase unbalanced
controllable var sources to compensate large industrial loads loads i.e. grounded load, ungrounded star connected and delta
such as electric arc fiunaces, electric traction, commercial connected unbalanced loads. In a three-phase, four-wire system
li&ting, air conditioning etc. If not compensated, these loads under normal operating condition with the loads reasonably
create system unbalance and lead to wide ffuctuations in the balanced, the current in the neutral is expected to be small,
supply voltages. Such supply system can not be used to feed typically not more than 20 percent of the normal load current in
sensitive loads like computers, electronic equipment etc. the phases. However, excessive neutral current phenomenon
Tbe importance of balanced load on the supply system has arises, especially in unbalariced circuits such as fluorescent
already been felt by power experts a long back [1-21. The lighting loads. This type of system in particular, results in
presence of unbalanced load results in reactive power burden excessive neutral current, which can potentially af€ect both the
and excessive neutral current, which in turn results in low system neutral conductor and the transfonner to which it is connected.
efficiency, poor power factor and disturbance to other The objective of this paper is to balance a three-phase, four-
consumers. Innumerable control methods have been proposed to Wire system feedig a three-phase, four-wire unbalanced load
draw balanced supply currents if reactive load is fed fiom and thee-phase, three-wire unbalanced load. Three schemes
balanced supply system. Gyugyi [3] discussed few basic have been presented for neutral current compensation. Each
theoretical concepts for reactive power generation including scheme suggests selection of different reactive elements for
control aspects. Impedance and phase balancing of induction making the load balanced and resistive at supply end. It also
a r c - - and siigle phase electric traction as a load have proposes the selection of optimized set out of three
been presented by Tremayne [4] and Knechke [5], respectively. compensation methods according to nature of load. The basis of
A very conceptual approach for realizing balanced load while forming three sets lies on the selection of phases for neutral
feeding single phase R-L load is reported by Kern et al [6] and current compensation namely a-b, b-c and c-a Thereby forming
three phase load by Sadek [7l. However, a new criterion based three solutions for one instant in case of three phase grounded
on optimization of the nns values of line currents is used fir unbalanced load (Fig. l(a)). Moreover, a uni6ed approach is
evaluating the reactive elements required for compensation in devised for compensation of three phase, three wire load.
threephase threemire system by Vasu et al [8] and minimization
of power line loss for optimal reactive power compensator has IL SYSTEM DESCRIPTION
been discussed by Lin e4 al [SI. Further, the idea of electronic System considered consists of a balanced three phase supply
compensator has been introduced to compensate the reactive feeding the unbalanced loads. Fig. l shows the line diagram

479
representation of loads where supply voltages are: On solving above equations for lIhpl and l&l :
v , = IvI LOO; v ba = JVIL120"; v , = IVIL240" I~l=~Im~sin(24O°ty-~)/sin(12Oo+y-p);
For three-phase unbalanwd grounded load as shown in Fig. 1 (a),
three schemes have been presented and then three-phase three-
wire unbalanced load has been compensated using a common
scheme. First scheme considers phases b and c vig.2(a)), second The corresponding susceptances are :
scheme selects phases a and b (Fig.2(b)) and third scheme
chooses phases a and c (Fig.2(c)) for neutral current By putting these susceptances in b and c phases, neutral
compensation. Suppose P, Pb and Po are three loads of lagging
grounded star connected system can be made equivalent to
power factor cos@, cos% and cos@, respectively fed from
ungrounded star co~ected system and supply neutral current is
balanced supply. The current carried away by neutral U is given
by summation of b, Ihl and I^j (load currents). I,, can be zero a s :
t + I, =o.o
neutralized by injecting a current I, equal in & t u d e and 180"
out of phase fiom z. L current stands for neutral compensation And, neutral compensated load becomes equivalent to :
current and 8 is the neutral current compensating angle.
B. Second Scheme
After neutral curreat compensation the load becomes equivalent This scheme provides neutral current compensation in phases a
to three-phase three-wire unbalanced load (Fig.l(b)), this is and b for a three-phase four-wire unbalanced load. For
transformed to equivalent delta connected load (Fig.(c)). Three compensation of neutral m e n t reactive elements will be placed
phase unbalanced delta co~ected load is cornpensated by two in phases a and b. The arrangement of this scheme is shown in
sets of lossless elements (susceptances) one for power factor Fig 2(b). Nature of reactive elements will be reflected by angles
correction (B*,, Bboi and B ml ) and other for line currents a and p. The angle a is an angle of lossless reactive elements
balancing (Bsb2, kZ and B d ) as shown in Fig.3. c~~ected across phase a for neutral compensation and may be
either +90° or -90". Angles a and p will change as 8 value
EL NEUTRAL CURRENT COMPENSATION changes.
Neutral current compensation can be achieved by any one of the For 3 0 " q W ; w W 0 ; p= -90"
following three schemes. For 90°<8<2100; a=+90°; fk +!N°
For 210°<8 <270°; a=-Wo; f3= +!N°
A. First Scheme For 27O°<8<36o0; cr--90°; j3= -90"
This scheme realizes the b a l a n d operation by providing neutral If angle a or p is+ve then capacitor if-ve then inductor will be
current compensation in phases b and c, for three-phase four- connected in the respective phases. These reactive elements set
wire load as shown in Fig.2(a). The nature of passive lossless for neutral current compensation will cany phase currents I,
compensating elements will depend on angle of neutral and IbDe m phases a and b respe&vely. On decomposing L and
compensation current L i.e. 8. Reactive elements chosen for b IbDD in phase and guadrature axis of phase voltage V,. (Refer
and c phases will be decided by angles P and 7. The angles p and Fig.4(b)).
7 are the angles of compensating elements Z, and Z , . These
|Ucos(eHU|cos(a)+|I 1 Jcos(120 o +P);
two impedances being lossless reactive elements (either
capacitive or inductive) thus, these angles (B and 7) will be SO". Distribution of nd current in compensating phases a and b
If angle is -909 then selected element will be an inductor, i f *
is given by L and W On solving above equations for the same:
then it will be a capacitor:
pPpl=~lsi(I20°+ey~;l(12o o +p-a);l
For 3O°<0<15OO; (5 =-90°; y=-90°
Ll=ILlsin(a-O)/sin(a-fI-120');
For i50°~8<2i0°;p =WO;r; ' - - 9 0 °
For 2lO°<eCj3O0;p =eoo; R ; + 9
For 33O°<8<36O0 and O°<8<300;p =-!N°; r = O
Amount of neutral current shared by two phases is equal to 1^ The corresponding susceptances are :
and I-. Where & is the current carried by reactance placed in B mc =II ~l iin(a)/lVl; L =lI ~ lsin(B)/lVl
phase b and I, is the current carried by reactance placed in The above values of 2, and Z, in phases a and b make the
phase c for neutral current compensation as shown in Fig.2(a). system equivalent to three phase ungrounded star co~ected.
On decomposing L and I, along in phase and quadrature axis Thus supply neutral current is zero as :
of phase voltage V, and equating them to corresponding r, + I , + W l«c + E = 0.0
components of I, (Refer to Fig.4(a) for a typical case): Neutral compensated load becomes equivalent to :
IIJcoiKeHIfcJcosO 20°+P)+|I011c|cos(240o-Hy) Zbn=ZwZbM/(Ztal+ZblB); Zal=ZMl

480
C. Third Scheme The m l t i n g taistiVe network becomes balanced load when one
This scheme selects phases a and c for compensation (Fig.2(c)). more set of reactive components B a . B^ and B d is connected
According to neutral compensating current angle compensating across respeaive phases. Assuming connection of B&, B^g and
reactive elements for phases a and c will be selected. B d makes aurents ~ u a l .
For 330°<8<3600 and O°<8<900; a 4 " ; y= +90° I,= I LO"; Ib= I L120", L= I L240"
For !30°<8<1 50'; a=+90°; y= -90" From Fig.3, according to ohm's Law, we can write:
For 15O°<W27Oo; u=-90°; y= -90" I*=CV.-V hll XG lb +jB iM );
For 270'4K330'; a=-W0; y= +90"
The vector decomposition of currents carried by neutral
compensating reactive elements, along in phase and quadrature On applying Kirchoffs current law at nodes a, b and c
axis of phase voltage V, results in (Refer Fig.4(c)). respectively. We have:
|IJcos e=|Iraclcos(a)+|Iaio|cos(240o-f7) (1)
,lsin(a)+ l IJsin(240 ° + r ) (2)
(3)
From above equations, I, and Ico are solved as : On solving Equations (I), (2) and (3) after separating real and
~I,c~=~~~sin(2400+r-8)/sin(2400+r~); imaginary parts of three line currents:

BD=-I/(D3IV1)+2GJD3+GJD3
The corresponding sosceptances are : Bbo2=-I/(2V3|V|)+V3Gcl/2-Bcij/2
These equations give the d u e s of susceptances required for
Connection of these two susceptances makes the system current magnitude equallzation. Elements so obtained are
equivalent to three phase ungrounded star connected, thus connected in p d e l with B h l , B M and B W1 as shown in Fig.3
supply neutral current is as: to make the system totally balanced. Total susceptances in lines
for power factor correction and load balancing will be:
Neutral compensated load becomes equivalent to:
Fig.3 shows the equivalent balanced represenmion of load on
the supply end. Figs. q a ) , 4@), 4(c), 4(d) and 4(e) are the
IV. POWER FACTOR CORRECTION AND phasor dmgrams of tidy compensated loads. Figs,4(a), 4@) and
BALANCING OF UNBALANCED LOAD 4(c) correspond to three phase pounded loads, which have been
Neutral current compensated load now becomes equivalent to compensated by three schemes. Figs.4(d) and * e ) are for three
three phase unbalanced ungrounded star connected load, which phase ungrounded star co~ected and delta connected load
is the second category of loads as shown in Fig. I(%). Star-Delta respectiveb.
transformation of equivalent star co~ected load will be:
Ya=z V. RESULTS AND DISCUSSION
A comparative analysis of all three schemes for three phase
z , + z , Zd unbalanced grounded load is shown in Table 1 for the three
This @ v a l e n t delta-connected load is similar to third category phase unbalanced load (15kW 0.8pf laggins 20kW unity power
of load (unbalanced delta connected load refer Fig. l(c)). Thus, factor, 25kW 0.85pf lagging). For the considered load, first
all kinds of loads either equivalent to delta m ~ e c t e d load or scheme demands an inductor of 10.3mH in phase b and capacitor
delta connected loads are compensated in the following manner of 205.3pF in phase c. Second scheme requires inductors of
for the reactive power compensation and load balancing. values 49.3mH and 8.51mH in phases a and b respectively and
The power factor 'df each phase is corrected by adding a set of third scheme needs capacitors of 982.2pF and 1188.9pF in
susceptances B*l & , , B,,. On separating real and imaginaty phases a and c for neutral current compensation. Power factor
parts of admittances Y*, Ybo and Y , : correction requires three capacitors of values, 2 5 7 . 6 $ , 290.7pF
and 150.7pF ( u i i g first scheme) and 328.6pF, 355.9pF and
%=Re(Ybo);G,=Rfl,) 219.9pF using second scheme in phase a-b, b-c and ea
Susceptanm Bdl, hl and B,, are co~ected across lines a-b, respectively. However, third scheme uses three inductors of
b-c and c-a to realize the reactive part of the respective 153.5mH, 471.2mH and 51.41mH in phases a-b, b-c and o a .
susceptances of Y& Yb and Y, Now, the three equivalent load For load balancing capacitors of 69.7pF and 37.9pF in between
elements become resistive ones of conductances G& Gbc and phases a-b, b-c and inductance of 9 4 . W in between c and a are
G , , respectively. needed by the fist scheme. Second scheme also requires two
capacitors and an inductor of values 67.2pF, 41.2pF and

481
93.4mH in phases a-b, b-c and c-a, respectively. Third scheme balancing and at any instant, is the sum of i*b -Ui> i,t, and -&.
uses two capacitors of 65.58pF and 21.91pF and an inductor of Fig.qc) shows the balanced load currents i, & and i, after
115.7mH in phases a-b, b-c and c-a respectively. After compensation Fig.7(a) presents the load aments L, ,,i and L
compensation all currents are in phase with their respective in case of three phase delta connected load. Fig.7(b) shows the
voltages and power consumed per phase is equal as given in balanced phase current i, which at any instant is the sum of i d ,
Table 1. - L , U and - b . Where ia and b. are the currents flowing in
Table 2 presents the compensation results for three phase star susceptances placed for unity power factor correction and load
~ ~ e c t e d ungrounded load. For the given load specifications, balancing in phases a-b and cia. Lastly, Fig.7(c) shows the
capacitors of 380.8pF. 59.65pF and 290.8pF are needed in voltage v, and three balanced supply currents i, 4 and b drawn
between phases a-b, b-c and c-a respectively for reactive by load thereby presenting balanced load to the supply system.
power/power factor compensation. Further, load balancing
requires two capacitors of 82.54pF, 11.62pF in phases a-b, b-c VI. CONCLUSIONS
and one inductor of 107.6mH in phase oa Last column of table Three different compensation schemes for unbalanced three
shows per phase current and per phase power after phase four wire load have been investigated. All the three
compensation. Table 3 shows the results corresponding to three schemes are able to make the system perfectly balanced. A
phase unbalanced delta connected load. For the given load common scheme for three-phase three-wire unbalanced load
values, two capacitances of values 184.9pF, and 254.6pF are (either star connected or delta c~~ected) has been adyzed and
needed in phases a-b and c-a fbr power fkctor correction and no found to balance the load completely. These schemes can be
capacitive or inductive element in phase b-c for power factor realized by variable lossless impedance compensators using
correction is needed. Load balancing requires an inductor of elements which may knction as variable reactances. Results
213.3mH in phase a-b, a capacitor of 94.89pF in phase b-c and may be utilized for the proper design of a controller for
an inductor of 213.4mH in phase e a . Last column shows that balancing the loads in three phase ac system.
equivalent balanced per phase power is 19.99kW and current is
78.7A.
VlL ACKNOWLEDGEMENT
Relevant waveforms for three phase grounded star connected The fitst author gratefblly acknowledges the "Council of
unbalanced load, three phase ungrounded star connected Scientific and Industrial Research, INDIA" for the financial
u n b d d load and three phase delta connected load have also support receiving under the Senior Research Fellowship scheme,
been devised. Fig. 5 shows the results corresponding to a load Award No. 9/143(285)/94-EMR-I, because of which this work
of 15kW 0.8pf lagging, 20kW unity pf and 25kW 0.85pf lagging reported in this paper was possible.
in three phase grounded star connected load configuration (as
shown in Fig. l(a)). FigS(a) indicates the load currents id it^ REFERENCES
and L and neutral current i,. Figs. 5(b), 5(c) and 5(d) depict the 1. L.Gyugyi, R.AOtto and T.H.Putman, "Principles and
neutral current compensation by the three schemes. It has been application of static thyristor-conuolled shunt
clearly shown in Fig.S@) that at any instant sum of i b , i, and compensators", IEEE Trans. on PAS, vo1.97, no. 5, pp
i, is zero, which effectively represents the neutral current 1935-1942, 1978.
elimination by the first scheme. Fig.S(c) shows the neutral 2. L. Gyugyi,"Reactive power generation and control by
current compensation by second scheme and at any instant the thyristor circuits", EEE Trans. on Ind. Appl., v01.M-
sum of w, ihoc and i,, is zero. In FigS ( d ) according to the third lS,no.S,pp 521-531, 1979.
scheme, neutral current compensation is carried out in phases a 3. L.Gyugyi,"Power electronics in electric utilities: static var
and c and i n is neutralized by i, and w Figs. 5 (0, 5 (g) and compensators", Proc. IEEE, vol.76, no.4, pp 483494,
5(h) give the detailed description of balanced load current i, 1988.
when balancing is done by the three schemes. F i g . 5 0 shows 4. J.F.Tremayne,"Impedance and phase balancing of mains-
that current i, is equal to sum of id, i* and -i, which is fiequency induction fiirnaces", EE Proc., vol.130, pt.B,
expected according to the first scheme. Similarly Figs S (g) and n0.3, pp 161-170, 1983.
5 0 ) indicate that sum of idi, , i& and -i is equal to i. Finally, 5. T.AKneschke,"Control of utility system unbalance caused
FigS(e) shows the voltage v, and the three balanced supply by single-phase electric traction", IEEE Trans. on Ind.
currents 4, & and h obtained after compensation by all the three Appl., v01.21, n0.6, pp 1559-1570, 1985.
schemes.
6. k K e m and G.Schroder,"A n o d approach to power fkcm
Fig.6 gives the appropriate waveforms for three phase control and balancing problems", Proc. of Cod. JEEE-
ungrounded star connected unbalanced load and Fig.7 for three IECON Record, pp 428-433, 1994.
phase delta co~ected unbalanced load. Fig.Ci(a) shows the 7. M.Z.E1 Sadek., "Balancing of unbalanced loads using static
equivalent load current w &, &.i in case of three phase var compensators", Electr. Pow. Syst. Res., vol.12, pp
ungrounded star connected load. Fig.6(b) produces i current 137-148,1987.

482
8. E.Vasu, V.V.B.Rao, P.Sankaran,"An optimization criterion
for three phase reactive power compensation", EEE
Trans. on PAS, ~01.104, no.11, pp 3216-3220, 1985.
9. C.E. Lit& T.C.Chen and C.L.Huang,"A real time calculation
method for optimal reactive power compensator", IEEE
Trans. On Pow. Syst., vo1.4, n0.2, pp 443-652, 1989.
10. MD.Cox, AMirbod," A new static var compensator for an
arcifinace", IEEE Trans. on Pow. Syst. voI.PWRS-1,
110.3,pp 110-119,1986.
11. Y.Sumi,Y.Harumoto,T.Hasegawa,M.YanoandK.Ikeda,"
New static VAR control using force-commutated
inverters", IEEE Trans. on Pow. App. and syst., vol. PAS-
100, no.9, pp 4216-4224, 1981.
12. C.Schauder and H.Mehta, "Vector analysis and control of
advanced static VAR compensators", IEE Proc.-C,
~01.140, pp 299-306, 1993.
13. J.K&y, AY.Chilchani, RHackam, M.M.A.Salama and
V.H. Quhana," Microprocessor controlled reactive power
compensator for loss reduction in radial distribution
feeders", IEEE Trans. on Pow. Del., vo1.6, no.4, pp 1848-
1855,1991.
14. H.N.Ng, M.M.A.Salama and AY.Ch&hani," Capacitor
placement in distribution systems using fuzzy technique",
IEZE Canadian Conference on Elecuical and Computer
Engineering pp 790-793, 1996.

483
TABLE 3.1: Compensation of three-phase unbalanced grounded load
Load Specifications : ( 15kW 0.8 pf, 20kW unity pf, 25kW 0.85 pf)
For neutral For power factor/ Load balancing
Schemes current reactive power
compensation compensation Compensating I Per phase power
Elements (kW) & Current(A)
First Lbnc=10.3mH b,=257.6pF C a ,=69.7 p F poh= 19.99; I,=78.7L0"
Cte2=37.9^F ^=78.72; 1^78.7/120°
Scheme C c ,=205.3 pF Cbcl=290.7^F 13,-78.7/240°
C^ISO^F Lca2=94.0mH *"
Second L,=49.3np Cabl=328.6pF Ca,,=67.2pF ? , = 19.99; I,=78.7L0"
Scheme &=8.51mH cl=355.9pF C k2 =41.2 p f L=78.72; Isb=78.7L 120"
C a ,=219.9 p F L 4 ~ 93.4mH 1, = 78.7L240"
Third C,=982.2 p F Labl = 153.5& CaU=65.58pF k = 19.99; I,=78.7L0"
Scheme C,, = 1188.9pF L l =471.2mH Cbc2=21.91pF bz78.72; ISb=78.7L 120"
L,,=51.41mH L d = 115.7mH 1 ,=78.7L240"

TABLE 3.2: Compensation of three-phase star connected ungrounded load


1oa Equivalent A- For power Factor/ oa oaaancing
Specifications connected load reactive power
compensation Compensating Per phase power
Elements (kW) & current (A)
2,=3.44 L 36.9" 2,=11.3L12.8"- c abl =380.8 pF C au =82.54pF P,=20.41; 1,=80.4L0"
Z,=3.23L0" Z,=7.21L7.76" C bcl =59.65 p F CbcZ=11.62p [ ,=80.4; 1,=80.4L120"
Z c ,=2.19L31.8" 2,=7.69L44.6" Cc,,=290.8pF Lca=107.6mH 1, = 80.4L240"

TABLE 3.3: Compensation of three-phase unbalanced A-connected load


Load Equivalent A Tor power Xoad Balancing
Specifications connected load factor\ reactive
Power Compensating Per phase power
compensation Elements (kW) & current (A)
Pab= 15kW0.8pf Zab = 10.3 L 36.9" C ab , = 184.9pFLa,=213 L a ,=213.3mH k',,,,=19.99; I,=78.7L0"
Pk=2OkW 1.0 pf Z,=9.68 LO" C bcl =0.00pF Ck2=94.89pF$,=78.72;Is F$,=78.72;Isb=78.7L120"
Pc,=25 kW 0.85 pf Z,,=6.58L31.8" CCa,=254.6pFLC L C a = 2 1 3 . 4 m H Isc=78.7Z240°

484
cnc

c Toil
(a) Grounded star connected (a) First scheme (cornpensation in b
and c phases)

a 'an1
ao
NZonl

bnl

v
cnl
(bl Ungrounded star connected (bf Second scheme (compensation in
a and b phases)

ca

(c) Delta connected (c) Third scheme (compensation in


a and c phases

Fig. 1 Representation of three phase Fig.2 Neutral current compensation


unbalanced load of three phase unbalanced
grounded load

485
BCQ1

Vbn

Fq. 4 (a)Using first scheme for three


Fig. 3 Representation of equivalent balanced phase grounded star connected
load unbalanced load
-Ica
anc

Ibei \ cnc

Figt(c) Using third scheme for three


Fig. 4 (b) Using second scheme for three phase phase grounded star connected
grounded star connected unbalanced unbalanceCI load
load
ad
VQn lab
ab

'be
bn
ca
Fig.4(d)For three phase ungrounded star F;g.L(e) For three phase delta
connected unbalanced load connected unbalanced load

Fig.L Phasor representations for compensations of all kinds of load

486
no. mi"

.•ibnc / ibnc
•• A
EO.M-
t
/ \ / •• // \\'.
.'Y
-ianq
;\;\' / i\ i\ N

vy '>' V
\ /

«,•• «. TirE (SEO

Fig 5(a) Load currents and Fig.5(b) Neutral current Fig.5(c) Neutral current Fig.5(d) Neutral current
neutral current compensation in first scheme compensation by second scheme compensation by third scheme

~zsr
Fig.5(e) Voltage van and three Fig.5(0 Current ia balancing by Fig.5(g) Current ia balancing by Fig.5(h) Current ia balancing by
balanced supply currents tlrst scheme second scheme third scheme

Fig.5. Waveforms lor compensation of three phase grounded load (Load specifications: 15kW 0.8 pf lag, 20kW unity pi, 25 kW 0.85pf lag)
e.ee-

-80.00-)- ,,1,1,
0.00 0.01 0.02 0.03 0.04
TIE (SEC)
Fig 6(a) Load currents in delta equi. Fig 7(a) Load currents when load
of ungrounded star load is delta connected

\ / ^

-100.00-
0.00 0.01 0.02 0.03 0.04 0.00 0. 01 0.02 0.03 0.04
TIE ( SEC1 TIE ( SEC1
Fig 6(b) Current isa balancing Fig 7(b) Current isa balancing

Fig 6(c) Voltage van and three Fig 7(c) Voltage van and three
phase balanced supply currents phase balanced supply currents

Fig 6 Waveforms for compensation of Fig 7 Waveforms for compensation of


three-phase ungrounded S&K connected load three-phase delta connected load

488

You might also like