Electricity Grid Modernization Project
BIDDING DOCUMENT
FOR
(Procurement of Plant)
Single-Stage, Two-Envelope
Bidding Procedure
Transmission Line
Total
SPARE PARTS
Galvanized steel tower with required extension
4.0
including Stubs
4.1 Tower type DA+9 0 nos.
4.2 Tower type DB+9 1 nos.
4.3 Tower type DC+9 1 nos.
4.4 Tower type DD/DDES+9 1 nos.
4.5 Tower type DF+9 1 nos.
SPARE PARTS
Galvanized steel tower with required extension
4.0
including Stubs
4.1 Tower type DA+9 0 nos.
4.2 Tower type DB+9 1 nos.
4.3 Tower type DC+9 1 nos.
4.4 Tower type DD/DDES+9 1 nos.
4.5 Tower type DF+9 1 nos.
Check survey and review of profile including L/R profile in undulation, tower spotting, staking
a 39.00 Km.
of tower locations and survey on tower location where required.
2 Soil Investigation
a All kinds of Soils except fissured rock & hard rock 35 Loc.
b Fissured Rock (Both dry and wet) 45 Loc.
c Hard Rock 15 Loc.
d River Crossing 5 Loc.
e Furnishing Bore Log Data 28 Loc.
f Measurement of ground resistance 128 Loc.
3 Benching
a Normal Soil 10000 Cum.
b Fissured Rock 7000 Cum.
c Hard Rock 500 Cum.
Erection of towers & its body extensions (Complete) including bolts & nuts, tack welding
4
and supply and application of enamel & zinc rich paint
4.1 Tower Type DB
a Stub 176 No.
b Basic Body 44 No.
d DB -3M Leg Extension. 2 No.
e DB -1.5M Leg Extension. 2 No.
f DB +/-0M Leg Extension. 20 No.
g DB +1.5M Leg Extension. 4 No.
h DB +3M Leg Extension. 16 No.
i DB +4.5M Leg Extension. 4 No.
j DB +6M Leg Extension. 40 No.
k DB+7.5M Leg Extension. 8 No.
l DB+9 M Leg Extension. 80 No.
4.2 Tower Type DC
a Stub 112 No.
b Basic Body 28 No.
d DC -3M Leg Extension. 4 No.
e DC -1.5M Leg Extension. 4 No.
f DC +/-0M Leg Extension. 20 No.
g DC +1.5M Leg Extension. 4 No.
h DC +3M Leg Extension. 8 No.
i DC +4.5M Leg Extension. 4 No.
j DC +6M Leg Extension. 28 No.
k DC+7.5M Leg Extension. 8 No.
l DC+9 M Leg Extension. 32 No.
4.3 Tower Type DD/DDES
a Stub 216 No.
5.5 Raised chimney type foundation installation for all type of tower locations all complete.
a M20 Conc. Nominal Mix 1:1.5:3 for raised chimney work. 150 CUM
b Reinforcement Bars for raised chimney foundation 50 tons
6.0 Installation of Tower Accessories & Earthing
6.1 Tower Accessories
a Danger Plate 128 No.
b Number Plate 128 No.
c Anti-Climbing Device 128 Sets
d Phase Plate (set of 3) 128 Sets
e Circuit Plate (set of 3) 128 Sets
f Bird Guards 768 Sets
f Aviation signal 30 Sets
6.2 Installation of Tower Earthing Material
a Pipe Type 128 sets
b Counterpoise Type
i) Counterpoise Type - 25 m 28 sets
ii) Counterpoise Type - 50 m 40 sets
iii) Counterpoise Type - 100 m 60 sets
7.0 Installation of Line Materials
7.1 Stringing of Conductor and Groundwire
Stringing of 39 km, 132 kV double circuit transmission line ACSR conductor, code name
a 39 km
"Cardinal" with armour rod, mid span compression joints, repair sleeves etc to complete the job
Stringing of 39 km, steel ground wire with optical fiber (24-fiber) including intermediate splice
b 39 km
boxes and necessary terminal splice boxes, etc.
Insulator strings with insulators, attachment assemblies and arcing horns all complete for
7.2
ACSR "Cardinal" conductor and attachment assemblies all complete for OPGW
Single suspension with 1 composite long rod insulator complete for "Cardinal" conductor
a 0 Set
suitable for altitude above 1,000 m
Double suspension with 2x1 composite long rod insulator complete for "Cardinal" conductor
b 0 Set
suitable for altitude above 1,000 m
Single tension with 1 composite long rod insulator complete for "Cardinal" conductor suitable
c 1200 Set
for altitude above 1,000 m
Double tension with 2x1 composite long rod insulator complete for "Cardinal" conductor
d 336 Set
suitable for altitude above 1,000 m
Jumper set with pilot insulators, armour rod & suitable counter weight complete with all
e 128 Set
accessories for one tower
f OPGW suspension preformed assembly complete for one tower 0 Set
g OPGW tension preformed assembly complete for one tower (one set/tower) 40 Set
7.3 Installation of Preformed fittings for OPGW
a Optical approach cable for Khungri and Ghorahi Substation. 2 Km
Optical Distribution Frames and other accessories required for connection with Multiplexer of
b 1 Lot
Khungri and Ghorahi Substation.
7.4 Installation of Vibration Dampers 0
a Vibration Dampers for ACSR "CARDINAL" 1536 set
b Vibration Dampers for OPGW 256 set
a Random rubble stone masonry including excavation (1:4 cement: sand) 4000 CUM
b Stone bound in galvanizing wire netting including excavation (Gabion box protection) 12000 CUM
Price Schedule for Schedule No. 4(c) : Training Charges for training to be imparted to Employer's Personnel by Bidder's Instructor in Nepal
1 NOT APPLICABLE
1 NOT APPLICABLE
Total of Schedule No.4 (d). to Grand Summary)
Khungri Substation
Unit Rate
Amount US$
US$
(1) (2) (3) (4) = (2) x (3)
A) ELECTRICAL WORKS
a) POWER TRANSFORMER
30 MVA, 132/33 kV, three phase, power transformer complete
with on load tap changer (OLTC), RTCC facility with Tank
1.0 no 1
Mounted LA at LV side and Bushing CT on both sides
,Star/star complete with all accessories
b) LT TRANSFORMER
250 kVA, 33/0.4 kV station service transformer as per
1.0 no 1
technical specification and drawings
145 kV, 2000 A, 31.5 kA, 1 sec, 3 phase, SF6 circuit breaker
1.0 sets 1
complete with all accessories (for bus coupler)
145 kV, 1250 A, 31.5 kA, 1 sec, 3 phase, SF6 circuit breaker
2.0 complete with all accessories (for 132 kV side of power sets 5
transformer & 132 kV lines)
36 kV, 2000 A, 25 kA, 1 sec, 3 phase, Vacuum circuit breaker
3.0 for 33 kV side of power transformer complete with all sets 1
accessories
36 kV, 1250 A, 25 kA, 1 sec, 3 phase, vacuum circuit breaker
4.0 sets 6
complete with all accessories
d) DISCONNECTING SWITCHES:
145 kV, 1250 A, 3 phase center break disconnecting switch
1.0 with grounding switch complete with all accessories as per sets 4
specification.
145 kV, 2000 A, 3 phase center break disconnecting switch
2.0 without grounding switch complete with all accessories as per sets 2
specification.
145 kV, 1250 A, 3 phase center break disconnecting switch
3.0 without grounding switch complete with all accessories as per sets 10
specification.
36 kV, 1250 A, 3 phase disconnecting switch with grounding
4.0 sets 5
switch complete with all accessories as per specification.
36 kV, 2000 A, 3 phase disconnecting switch without
5.0 grounding switch complete with all accessories as per sets 1
specification.
36 kV, 1250 A, 3 phase disconnecting switch without
6.0 grounding switch complete with all accessories as per sets 6
specification.
e) INSTRUMENT TRANSFORMERS:
f) LIGHTNING ARRESTORS:
i) Grounding
Galvanized E.H.S. steel wires of size 7/3.35 for lightning
1.0 shield wire in take-off and internal structures complete with all LS 1
accessories
Lightning protection system with lightning mast, copper
2.0 conductor, electrodes complete with all accessories for control LS 1
building
Earthing of substation with conductors, electrode, grounding
3.0 materials complete with all accessories LS 1
o) Illumination System
Lighting system for outdoor Switchyard, Substation area,
1.0 Entrance & Internal Road, Boundary wall periphery (with LS 1
support if necessary ) as per technical specification
2.0 Emergency DC lighting system complete for switchyard Nos 12
C) CIVIL WORKS
D) SPARE PARTS
1.0 Transformer
a) 132/33 kV Transformer:
1.0 OLTC motor with contactor sets 1
2.0 Cooler Fan with motor nos 1
Local & Remote WTI and OTI with sensing device & contact
3.0 sets 1
(each type)
4.0 Buchholz relay complete with contacts (Main tank) sets 1
5.0 Magnetic oil level gauge nos 1
Starters, contactors, switches & relays for electrical control
6.0 sets 1
panels (one set of each type)
7.0 Complete set of pressure relief device set 1
8.0 145 kV Bushing with metal parts and gaskets and lifting tools nos 1
9.0 36 kV Bushing with metal parts and gaskets and lifting tools nos 1
Spare insulating oil to be handed over to NEA after
10.0 KL 15
commissioning for O&M requirement including tank
b) 33/ 11 kV Transformer
1.0 OLTC motor with contactor sets 1
Local & Remote WTI and OTI with sensing device & contact
2.0 sets 1
(each type)
3.0 Buchholz relay complete with contacts (Main tank) sets 1
5.0 33 KV ISOLATORS :
5.1 Porcelain insulators nos 3
5.2 Main contact assemblies (one assembly) sets 3
5.3 Auxiliary contact assemblies (one assembly) sets 3
5.4 Interlocking coil sets 2
Push button switch - (1 No. of each type & rating) as
5.5 sets 1
applicable
Limit switch and Aux. Switches for complete 3 phase
5.6
equipment
5.6.1 For isolator sets 1
5.6.2 For earth switch sets 1
12.5.2 Ground Fault Relay, for 33 kV side, one of each type nos 1
13.5.1 3 phase Overcurrent Relay, for 11 kV side one of each type nos 1
13.5.2 Ground Fault Relay, for 11 kV side, one of each type nos 1
16.0 Miscellaneous:
16.1 Tonge tester as per specification nos 1
TOTAL OF SCHEDULE 1
A) ELECTRICAL WORKS
a) POWER TRANSFORMER
30 MVA, 132/33 kV, three phase, power transformer
complete with on load tap changer (OLTC), RTCC facility
1.0 no 1
with Tank Mounted LA at LV side and Bushing CT on both
sides ,Star/star complete with all accessories
b) LT TRANSFORMER
250 kVA, 33/0.4 kV station service transformer as per
1.0 no 1
technical specification and drawings
145 kV, 2000 A, 31.5 kA, 1 sec, 3 phase, SF6 circuit breaker
1.0 sets 1
complete with all accessories (for bus coupler)
145 kV, 1250 A, 31.5 kA, 1 sec, 3 phase, SF6 circuit breaker
2.0 complete with all accessories (for 132 kV side of power sets 5
transformer & 132 kV lines)
36 kV, 2000 A, 25 kA, 1 sec, 3 phase, vacuum circuit breaker
3.0 for 33 kV side of power transformer complete with all sets 1
accessories
36 kV, 1250 A, 25 kA, 1 sec, 3 phase, vacuum circuit breaker
4.0 sets 6
complete with all accessories
d) DISCONNECTING SWITCHES:
145 kV, 1250 A, 3 phase center break disconnecting switch
1.0 with grounding switch complete with all accessories as per sets 4
specification.
145 kV, 2000 A, 3 phase center break disconnecting switch
2.0 without grounding switch complete with all accessories as per sets 2
specification.
145 kV, 1250 A, 3 phase center break disconnecting switch
3.0 without grounding switch complete with all accessories as sets 10
per specification.
36 kV, 1250 A, 3 phase disconnecting switch with grounding
4.0 sets 5
switch complete with all accessories as per specification.
36 kV, 2000 A, 3 phase disconnecting switch without
5.0 grounding switch complete with all accessories as per sets 1
specification.
36 kV, 1250 A, 3 phase disconnecting switch without
6.0 grounding switch complete with all accessories as per sets 6
specification.
e) INSTRUMENT TRANSFORMERS:
f) LIGHTNING ARRESTORS:
i) Grounding
Galvanized E.H.S. steel wires of size 7/3.35 for lightning
1.0 shield wire in take-off and internal structures complete with LS 1
all accessories
Lightning protection system with lightning mast, copper
2.0 conductor, electrodes complete with all accessories for LS 1
control building
Earthing of substation with conductors, electrode, grounding
3.0 materials complete with all accessories LS 1
o) Illumination System
Lighting system for outdoor Switchyard, Substation area,
1.0 Entrance & Internal Road, Boundary wall periphery (with LS 1
support if necessary ) as per technical specification
2.0 Emergency DC lighting system complete for switchyard Nos 12
C) CIVIL WORKS
D) SPARE PARTS
1.0 Transformer
a) 132/33 kV Transformer:
1.0 OLTC motor with contactor sets 1
2.0 Cooler Fan with motor nos 1
Local & Remote WTI and OTI with sensing device & contact
3.0 sets 1
(each type)
4.0 Buchholz relay complete with contacts (Main tank) sets 1
5.0 Magnetic oil level gauge nos 1
Starters, contactors, switches & relays for electrical control
6.0 sets 1
panels (one set of each type)
7.0 Complete set of pressure relief device set 1
8.0 145 kV Bushing with metal parts and gaskets and lifting tools nos 1
9.0 36 kV Bushing with metal parts and gaskets and lifting tools nos 1
Spare insulating oil to be handed over to NEA after
10.0 KL 15
commissioning for O&M requirement including tank
b) 33/ 11 kV Transformer
1.0 OLTC motor with contactor sets 1
Local & Remote WTI and OTI with sensing device & contact
2.0 sets 1
(each type)
3.0 Buchholz relay complete with contacts (Main tank) sets 1
5.0 33 KV ISOLATORS :
5.1 Porcelain insulators nos 3
5.2 Main contact assemblies (one assembly) sets 3
5.3 Auxiliary contact assemblies (one assembly) sets 3
5.4 Interlocking coil sets 2
Push button switch - (1 No. of each type & rating) as
5.5 sets 1
applicable
Limit switch and Aux. Switches for complete 3 phase
5.6
equipment
5.6.1 For isolator sets 1
5.6.2 For earth switch sets 1
12.5.2 Ground Fault Relay, for 33 kV side, one of each type nos 1
13.5.1 3 phase Overcurrent Relay, for 11 kV side one of each type nos 1
13.5.2 Ground Fault Relay, for 11 kV side, one of each type nos 1
16.0 Miscellaneous:
16.1 Tonge tester as per specification nos 1
TOTAL OF SCHEDULE 2
A NOT APPLICABLE
Total
b) LT TRANSFORMER
d) DISCONNECTING SWITCHES:
e) INSTRUMENT TRANSFORMERS:
145 kV, 50 VA, 132/√3/110/√3 kV, Class 0.2/3P Voltage
1.0 nos 18
Transformer complete with all accessories as per specification
145 kV, 30 VA 5 core current transformer for Line & Bus
2.0 nos 15
coupler complete with all accessories as per specification
145 kV, 30 VA 5 core current transformer for power transformer
3.0 nos 3
complete with all accessories as per specification
36 kV, 50 VA, 33/√3/110/√3 V potential transformer complete
4.0 nos 18
with all accessories as per specification
f) LIGHTNING ARRESTORS:
120 kV, 10 kA Surge arrester (1 phase) including discharge
1.0 nos 15
counter
30 kV, 10 kA Surge arrester (1 phase) including discharge
2.0 nos 21
counter
3.0 9 kV Surge arrester (1 phase) including discharge counter nos 6
i) Grounding
Galvanized E.H.S. steel wires of size 7/3.35 for lightning shield
1.0 wire in take-off and internal structures complete with all LS 1
accessories
Lightning protection system with lightning mast, copper
2.0 conductor, electrodes complete with all accessories for control Ls 1
building
o) Illumination System
Lighting system for outdoor Switchyard, Substation area,
1.0 Entrance & Internal Road, Boundary wall periphery (with LS 1
support if necessary ) as per technical specification
2.0 Emergency DC lighting system for switchyard Nos 12
SUB TOTAL OF ELECTRICAL WORKS
SUBSTATION AUTOMATION/ COMMUNICATION/
B)
SCADA (Based on IEC 61850)
a) SUBSTATION AUTOMATION SYSTEM:
Complete Substation automation system including hardware
and software for the substation & remote control stations
1.0
alongwith associated equipments for the followings as per
Technical Specification.
1.1 132 kV System bays 6
C) CIVIL WORKS
1 2 3 4 5
Training to Owners personnel on i) Control & Protection and
Design , testing and Maintenance aspect 3 5
A Substation Automation System,
as per Section Project, Technical
Specification at manufacturer's works ii)Transformer 3 5
Total for Training Charges
1 2 3 4 5 6 = 3x4x5
A NOT APPLICABLE
Total for Training Charges
Ghorahi Substation
b) DISCONNECTING SWITCHES:
c) INSTRUMENT TRANSFORMERS:
d) LIGHTNING ARRESTORS:
120 kV, 10 kA Surge arrester (1 phase) including discharge
1.0 nos 6.00
counter complete with all accessories as per specification
g) Grounding
Galvanized E.H.S. steel wires of size 7/3.35 for lightning
1.0 shield wire in take-off and internal structures complete with LS 1.00
all accessories
j) Illumination System
Lighting system for outdoor Switchyard, Substation area,
1.0 Entrance & Internal Road, Boundary wall periphery (with LS 1.00
support if necessary ) as per technical specification
C) CIVIL WORKS
Steel structure for post, beam and equipment supporting
1 frame complete with bolts, fastner, pack washer, nuts, guest
paltes and all accessories: (For 132 and 33 kV side)
D) SPARE PARTS
1.0 145 KV SF6 CIRCUIT BREAKER:
5.2.4 Hand reset trip relay (relay of each type) set 1.00
b) DISCONNECTING SWITCHES:
c) INSTRUMENT TRANSFORMERS:
d) LIGHTNING ARRESTORS:
120 kV, 10 kA Surge arrester (1 phase) including discharge
1.0 nos 6.00
counter complete with all accessories as per specification
g) Grounding
Galvanized E.H.S. steel wires of size 7/3.35 for lightning
1.0 shield wire in take-off and internal structures complete with LS 1.00
all accessories
j) Illumination System
Lighting system for outdoor Switchyard, Substation area,
1.0 Entrance & Internal Road, Boundary wall periphery (with LS 1.00
support if necessary ) as per technical specification
C) CIVIL WORKS
Steel structure for post, beam and equipment supporting
1 frame complete with bolts, fastner, pack washer, nuts, guest
plates and all accessories: (For 132 and 33 kV side)
D) SPARE PARTS
1.0 145 KV SF6 CIRCUIT BREAKER:
5.2.4 Hand reset trip relay (relay of each type) set 1.00
1 2 3 5 6 = 3x4x5
A NOT APPLICABLE
Total
145 kV, 1250 A, 31.5 kA, 1 sec, 3 phase, SF6 circuit breaker
1.0 sets 2
complete with all accessories (for 132 kV lines)
b) DISCONNECTING SWITCHES:
c) INSTRUMENT TRANSFORMERS:
145 kV, 50 VA, 132/√3 /110/√3 kV, Class 0.2/3P Voltage
1.0 nos 12
Transformer complete with all accessories as per specification
2.0 145 kV, 30 VA current transformer nos 6
d) LIGHTNING ARRESTORS:
120 kV, 10 kA Surge arrester (1 phase) including discharge counter
1.0 nos 6
with all accessories as per technical specifications
132 kV Bus bar control and relay panel complete with all accessories
1.0 sets 1
as per technical specifications
132 kV line control and relay panel complete with all accessories as
2.0 sets 2
per technical specifications
g) Grounding
Galvanized E.H.S. steel wires of size 7/3.35 for lightning shield wire
1.0 LS 1
in take-off and internal structures complete with all accessories
Lightning protection system with lightning mast, copper conductor,
2.0 Ls 1
electrodes complete with all accessories for control building
Earthing of substation with conductors, electrode, grounding
3.0 LS 1
materials complete with all accessories
j) Illumination System
Lighting system for outdoor Switchyard, Substation area, Entrance
1.0 & Internal Road, Boundary wall periphery (with support if necessary LS 1
) as per technical specification
2.0 Emergency DC lighting system for switchyard Nos 12
SUB TOTAL OF ELECTRICAL WORKS
C) CIVIL WORKS
Steel structure for post, beam and equipment supporting frame
1 complete with bolts, fastner, pack washer, nuts, guest paltes and
all accessories: (For 132 and 33 kV side)
1.1 132 kV take off gantry structures LS 1
3.3 M20 Conc. Nominal Mix 1:1.5:3 for protection work. Cub m 25
1 2 3 4 5 6 = 3x4x5
A NOT APPLICABLE
1 2 3 4 5 6 = 3x4x5
A NOT APPLICABLE
Sl.
Description unit Quantity Total
No. Currency (US $)
NRs
1 2 3 4 = 2*3
A NOT APPLICABLE
Total