Professional Documents
Culture Documents
SECTION 16450 Panelboards Rev 0
SECTION 16450 Panelboards Rev 0
RESIDENTIAL PANELBOARDS
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................ 1
1.04 REFERENCES..................................................................................................... 1
1.05 DEFINITIONS....................................................................................................... 2
1.06 SUBMITTALS....................................................................................................... 3
PART 1 GENERAL
A. Construction of Panelboards
B. Circuit Breakers
E. Nameplates
1.04 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials, products and workmanship. In case of conflict between these
standards and the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred Codes and Standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment, materials and
1.05 DEFINITIONS
A. dead front: Equipment without live parts, exposed to a person on the operating side
of a panelboards.
E. panelboard: A single panel or group of panel units designed for assembly in the
form of a single panel, including buses and automatic over-current devices, and
equipped with or without switches for the control of light, heat or power circuits,
designed to be placed in a cabinet or cut-out boxes placed in or against wall, partition
or other support and accessible only from the front.
1.06 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
Work:
a) Legend Drawing
1) A drawing showing Legend, Symbols and specialized terminology
used in Shop Drawings.
c) Part List.
B. The Contractor shall submit Field Test Report after completion of testing and
commissioning.
A. The Contractor shall be responsible for the quality of work and shall develop and
propose programs and methods of construction and testing to achieve the specified
quality to the approval of the Royal Commission in accordance with
SECTION 01450.
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
A. The Panelboard shall be tested at the factory in accordance with latest applicable
codes and standards as specified in 1.04. All type tests shall be performed on first
unit of every new design, as per applicable codes and standards. The Contractor
shall notify the Royal Commission in writing not less than 30 days prior to the
scheduled starting date of the factory tests.
B. The Royal Commission reserves the right of deputing their representative for
witnessing the factory tests.
C. Upon completion of factory tests, and before shipment of the equipment or materials,
the Contractor shall submit 5 certified copies of the test reports not later than 10 days
after completion of all factory tests, for review and approval of the Royal
Commission.
A. Panelboards installed indoor shall be suitable for continuous operation under the
following conditions:
a) A maximum of 40°C.
b) A minimum of 0°C.
B. Panelboards installed outdoor shall be suitable for continuous operation under the
following conditions.
a) A maximum of 50°C.
b) A minimum of 0°C.
A. The Contractor shall deliver, handle and store equipment and material units in
accordance with SECTIONS 01650 and 01660, and the following requirements:
each unit securely wrapped, crated and wrapped or packaged, and listed for
safe handling in shipment and to avoid damage.
3. Store equipment in secure and dry storage facility, close to operating condition
and as recommended by manufacturer.
4. Protect the equipment from physical damage from work of other trades.
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods and products
manufactured out-of-Kingdom must be approved by the Royal Commission.
B. All parts and material shall be new, good quality, and shall be selected to perform as
specified herein.
D. Items and component of the equipment not specifically covered herein shall be in
accordance with latest edition of the referenced codes and standards.
E. The components of the assembled unit shall meet the requirement of standard listed
in par. 1.04, or approved by testing laboratory acceptable to the Royal Commission.
2.02 PANELBOARDS
A. General
3. Panelboards shall have rating not less than the minimum feeder capacity
required for the load, as computed in Article 220 of NEC.
4. Panelboard shall be durably marked by the manufacturer with the voltage and
current rating, and the number of phases for which they are designed and with
the manufacturer’s name and trademark. These markings shall be visible after
installation, without disturbing the interior parts or wiring.
B. Construction of Panelboards
2. The Panelboard shall be dead front type with rigid self-supporting structures,
with suitable structural galvanized steel reinforcement, stiffening and bracing.
The Panelboard shall be tamperproof.
3. When the structures are assembled, the surfaces shall be flat and smooth and
shall have ample strength to withstand all stresses encountered in shipping,
installation and operation without any malfunctioning, vibration or other
damage.
6. The front door of the Panelboard shall be provided with concealed hinges. All
door locks shall be corrosion proof with retractable latches. All door locks shall
be keyed for a single key.
C. Circuit Breakers
1. All circuit breakers shall meet the requirement of standard listed in par. 1.04,
and shall have trip rating as indicated on the Contract Drawing.
3. Molded Case Circuit Breaker (MCCB) shall be bolt-on type. Miniature Circuit
Breaker (MCB) used on 120/240 V circuit shall be plug-in or bolt-on type as
specified on the Contract Drawing. MCB used on 277/480 V shall be bolt-on
type only.
4. Two or 3-pole circuit breaker shall have internal common trip cross bar for
simultaneous tripping of each pole.
5. Circuit Breaker shall have standard ON/OFF escutcheon marking. All breaker
handles and face plates shall indicate rated ampacity.
1. The bus bars shall be tin-plated, except where joints are overlapping surface
that shall be silver plated.
3. The bus bars shall be so located, as to be free from physical damage, and
shall be held firmly in place.
4. The arrangement of the bus bars shall be such as to avoid overheating due to
inductive effect. The bus bar bracing shall comply with the Contract
Drawings/Documents.
5. A neutral bus bar of the same rating as that of phase bus shall be provided,
and shall have numbered terminals for connection of neutral wires.
2. The enclosure of the Panelboard shall have top and bottom wire bending
spaces sized in accordance with NEC Table 312.6(B), for the largest
conductor entering or leaving the enclosure. The side wire bending space shall
be in accordance with NEC Table 312.6(A), for the largest conductor to be
terminated in that space.
4. The neutral and ground bus bar shall have minimum number of cable
terminations equal to that of the number of individual circuits that the
Panelboard has been designed to take.
F. Nameplates
PART 3 EXECUTION
3.01 GENERAL
A. The Contractor shall provide all materials, equipment and labor as deemed
necessary for complete and proper execution of the work.
B. After the installation is completed and properly adjusted, the Contractor shall conduct
operating tests. The various equipment and systems shall be demonstrated to
operate in accordance with the requirements of the specifications. Tests shall be
performed in the presence of the Royal Commission’s representative. The Contractor
shall provide electrical power, instruments and personnel necessary for performing
the various tests.
3.02 INSTALLATIONS
A. General
2. All facilities required for transportation of electrical equipment from store to the
site, such as vehicles and competent manpower, shall be supplied by the
Contractor.
3. All equipment moved to the site shall be inspected for damage or deterioration
during storage. Tag numbers and nameplates shall be verified with the details
given on the Contract Drawings.
B. Installation of Panelboards
3. The Contractor shall mount Panel on wall, or flush in wall, or as shown on the
Contract Drawing.
A. General
1. The Contractor shall carry out all site tests in accordance with approved test
procedure, to ensure that the equipment and materials comply with the
specifications and operational requirements. All tests are subject to witnessing
by the Royal Commission’s representatives.
2. 4 weeks prior to scheduled tests, the Contractor shall submit to the Royal
Commission the outline of the plan and procedures to be used in performing
site inspection and site tests. The outline shall include a brief description of the
test equipment, connection diagrams, proposed tests and procedures, test
sheets, reference drawings and minimum/maximum test and performance
values, in conformance with the specification and acceptability of the
equipment and installation.
END OF SECTION