Professional Documents
Culture Documents
~\
~~\tl ~~ wIJ~\t W~I w\.i ::aI~1
SECTION 16140:
KINGDOM
OFSAUDIARABIA
~~~1 ~f!J1~I
lorJubail&Yanbu
RoyalCommission cw. 4~ 46.4J I44+JI
SECTION 16140
WIRING DEVICES
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................ 1
1.04 REFERENCES..................................................................................................... 1
1.05 DEFINITIONS....................................................................................................... 3
1.06 SUBMITTALS....................................................................................................... 3
1.09 TESTING.............................................................................................................. 4
2.03 RECEPTACLES................................................................................................... 9
3.03 TESTING............................................................................................................ 16
PART 1 GENERAL
A. Switches
B. Receptacles
C. Wall Plates
D. Boxes
1.04 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials and products. In case of conflict between these standards and
the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment conforming to
one group of codes and standards.
1. SASO 444 Plugs and Socket Outlets for Household and Similar
General Use
6. IEC 60884 Plugs and Socket Outlets for Household and Similar
Purposes
1.05 DEFINITIONS
A. device: A unit of an electrical system that is intended to carry but not utilize electric
energy.
B. electrical box: A square, octagonal, or rectangular plastic or metal box that fastens
to framing and houses wires, and/or receptacles and/or switches.
D. receptacle: A receptacle is a contact device installed at the outlet for the connection
of an attachment plug. A single receptacle is a single contact device with no other
contact device on the same yoke. A multiple receptacle is two or more contact
devices on the same yoke.
1.06 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provision of
SECTION 01330. the following items for review and approval before commencing
Work:
2. List of manufacturers.
B. The Contractor shall submit Field Test Report after completion of testing and
commissioning.
A. The Contractor shall be responsible for the quality of Work and shall develop and
propose programs and methods for construction and testing such as to achieve the
specified quality to the approval if the Royal Commission in accordance with
SECTION 01450.
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
1.09 TESTING
A. All equipment shall be tested in factory in accordance with the latest applicable
Codes and Standard. All type tests as per applicable Codes and Standards shall be
performed on first unit of every new design. The Contractor shall notify to the Royal
Commission in writing not less than 30 days prior to the scheduled starting date of
B. The Royal Commission reserves the right of deputing their representative for
witnessing the factory test.
C. Upon completion of factory test and before shipment of the equipment/material, the
Contractor shall submit 5 certified copies of test reports not latter than 10 days after
completion of all factory test for review/approval by the Royal Commission.
A. Wiring Devices installed indoors shall be suitable for continuous operation under the
following service conditions:
B. Wiring Devices installed outdoors shall be suitable for continuous operation under the
following service conditions:
1.11 ENCLOSURES
A. The Contractor shall manufacture enclosures of devices as per NEMA 250, IEC
A. The Contractor shall deliver, handle and store product units in accordance with
SECTIONS 01650 and 01660, as well as the following requirements:
2. Ship each unit securely wrapped, crated or packaged and labeled for safe
handling in shipment and to avoid damage or distortion.
5. Store all indoor units protected from weather and protect all units from physical
damage from work of other trades.
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods manufactured
out-of-Kingdom shall be approved by the Royal Commission.
2.02 SWITCHES
A. Lighting Switches
3. The switches shall have butt contacts made of silver alloy toggle type handles.
5. The switches shall be rated for 20 A at 120 to 277 V AC. They shall be single
or double pole and 2-way, 3-way or 4-way type as indicated on the Contract
Drawing.
6. The toggle switches shall be totally enclosed tumbler type with body made of
fire resistant, non-absorptive thermosetting phenolic compound or approved
equal.
7. The switches shall be color coded for current rating as listed by Underwriters
Laboratories and meeting the requirements of NEMA WD1 and UL 20.
9. The switches shall have an integral self-grounding mounting strap with break-
off plaster ears and provision for back wiring with separate metal wiring clamps
and side wiring with a binding screw. The terminals of the switches shall be
screw or combination screw-clamp type capable of receiving and holding
4 mm² wire size.
1. All Switches shall be heavy-duty type with electrical ratings as shown on the
drawings or as required by the application. Switches for motors shall be horse-
power rated. Indoor enclosures shall be NEMA 12 for non-hazardous areas
and NEMA 4X for outdoor installations.
2. Switches shall have defeatable door interlocks that prevent the door from
opening when operating handle is in ‘ON’ position. The handle shall be
capable of being padlocked in ‘OFF position.
C. Dimmer Switches
b) Dimmers shall have low and high intensity adjustment, built-in transient
voltage protection and fuses on the load side. All remote mounted units
shall be completely enclosed in integral metal housing.
b) All wall mounted incandescent lamp load dimmers shall be of the same
manufacturer.
b) Dimmers shall have low end intensity adjustment and maintain full load
rating even when two or more units are installed adjacent to one
another.
c) Dimming ballast shall be provided for each F32 rapid start lamp or pair
of lamps. Dimmers shall have adequate capacity for the load served and
the environment in which installed.
2.03 RECEPTACLES
B. Receptacle which are not listed as hospital grade but are listed by UL in their
respective categories shall be used only if indicated on the drawings as “not hospital
grade.”
C. Receptacles shall be listed for the purpose and marked with the manufacturer’s
name or identification and voltage and ampere ratings. Receptacles and cord
connectors shall be rated not less than 20 A, 125 V or 20 A, 250 V, as shown on the
Contract Drawings.
E. Mounting straps shall be plated steel, with beak-off plaster ears and shall include a
self-grounding feature. Terminal screws shall be brass, brass plated or a copper alloy
metal.
F. Receptacles shall have provisions for back wiring with minimum 4 separate metal
clamp type terminals and side wiring from 4 binding screws.
G. 20, 30 and 50 A, 250V receptacle shall be complete with appropriate cord grip plug.
Devices shall meet UL 231.
H. Receptacles installed in hazardous areas shall have their enclosures suitable for
such installations conforming to the requirements of IEC 60079.
I. Duplex Receptacles
2. Switched duplex receptacles shall be wired so that only the top receptacle is
switched. The remaining receptacle shall be unswitched.
1. Ground fault interrupter duplex receptacles shall be an integral unit suitable for
mounting in a standard outlet box.
2. Ground fault interrupter shall be hospital grade and consist of a solid state
4. The devices shall have a minimum nominal tripping time of 30 ms. Devices
shall meet UL 943.
2. Devices shall be hospital grade, except that the rating shall be 15 A with the
following additional requirements:
a) Shall permit current to flow only while a standard plug is in the proper
position in the receptacle.
b) Screws exposed while the wall plates are in place shall be of the
tamperproof type.
a) Psychiatric rooms and wards, where psychiatric patients are not under
constant supervision.
2. The weatherproof integrity shall not be affected when heavy duty specification
or hospital grade attachment plug caps are inserted.
3. Cover plates on outlet boxes mounted flush with the wall shall be gasketed to
the wall in a watertight manner.
N. Lamp Receptacles
2. Keyless, porcelain body and skirt supporting a medium screw shell socket, and
integral 3-wire grounding receptacle shall have screw terminals and a
minimum rating of 600 W.
O. Computer Receptacles
2. The receptacle shall be isolated grounding type with orange triangle on its face
plate.
P. Industrial Receptacles
2. The receptacle used in Industrial areas shall be heavy duty type with enclosure
confirming to IP 44 of IEC 60529.
B. Wall plates for switches and receptacles shall be ASTM A167 Type 304 stainless
steel, bronze M32 medium satin finish or smooth nylon plates as specified. Oversize
plates will not be acceptable.
D. Metal faceplates shall be of ferrous metal not less than 0.76 mm in thickness or of
non-ferrous metal not less than 1.02 mm in thickness. Metal faceplates shall be
grounded.
E. Faceplates of insulating material shall be noncombustible and not less than 2.54 mm
in thickness but shall be permitted to be less than 2.54 mm in thickness if formed or
reinforced to provide adequate mechanical strength.
F. For receptacles or switches mounted adjacent to each other, wall plates shall be
common for each group of receptacles or switches.
G. In psychiatric areas, wall plates shall have tamperproof screws and beveled edges.
H. Each separately mounted bedroom telephone outlet shall have a wall plate to match
the receptacle wall plates but with openings to receive telephone jacks as approved
by Royal Commission.
2.05 BOXES
A. General
B. Floor Boxes
1. Floor Boxes shall be adjustable and shall consist of a cast metal body with
adjustable ring, flange ring and cover plate and threaded openings for
conduits.
2. Boxes for use with under-floor ducts shall be made of cast metal or heavy duty
plastic and shall be of the same manufacturer and range as the ducts. Gaskets
shall be used to ensure watertight installation. Trim shall suit the selected type
of surface.
PART 3 EXECUTION
3.01 GENERAL
A. The Contractor shall provide all material, equipment and labor as deemed necessary
for complete and proper execution of work.
C. Install devices plumb and level. Install securely in neat and workmanlike manner as
specified in NECA-1.
D. Adjust the location of devices to accommodate the work in accordance with field
conditions encountered and as directed by the Royal Commission.
F. Provide plates on all switches and receptacle outlets, and blank plates on all unused
boxes. Decorative types of plates shall be installed in finished area.
G. Protect devices and assemblies during painting. Install wall plates when painting is
completed.
A. Installation of Switches
1. Switches shall be mounted in an enclosure listed for the intended use. The
minimum wire bending space at terminals provided in a switch shall be as
specified in NEC Article 312.6.
2. Enclosure of the switches shall not be used as junction boxes, auxiliary gutters
or raceways for the conductors feeding through or tapping off to other switches
or overcurrent devices, unless the enclosure complies with NEC Article 312.8.
4. Light switches shall be flush or surface mounted. Dimmer and lighting switches
for domestic and similar purposes shall be mounted at a height of 1200 mm
above finished floor level.
5. When light switches are mounted adjacent to one another, they shall be
grouped in a single enclosure (multi-gang box) and shall share a common
switch plate, subject to a maximum of 3 switches per single-gang plate.
6. Where 3 or more switches are ganged, identify each switch with approved
legend engraved on wall plate.
7. Identify circuit number and panel number on the wires connected to switch
terminals.
8. Light switches installed adjacent to a door shall be located on the handle side
of the door, and shall be as near to the door as practicable.
10. Switches shall not be installed within wet locations in tub or shower spaces.
13. Install wall dimmer switches to achieve full rating specified and indicated after
de-rating for ganging as instructed by manufacturer.
14. The neutral conductor on the load side of dimmer switches shall not be shared.
15. The 3-way and 4-way switches shall be wired so that all switching is done only
in the ungrounded circuit conductor.
16. Switches shall not disconnect the grounded and neutral conductors of the
circuit.
17. Faceplates provided for switches mounted in boxes and other enclosures shall
be installed so as to completely cover the opening and, where the switch is
flush mounted, seat against the finished surface.
B. Installation of Receptacles
2. Before installing receptacles in the boxes, clean electrical boxes of dirt and
debris.
3. Receptacles mounted in boxes that are either flush with the wall surface or
projecting from it, shall be installed so that the mounting yoke or strap of the
receptacle is held rigidly against the box or raised box cover.
4. Receptacles mounted to and supported by the box cover shall be held rigidly
against the cover by more than one screw.
10. No receptacle shall be installed within 2 m of any tap, sink or basin in kitchen
or cloakroom.
14. Ground receptacles with an insulated green ground wire from device ground
screw to a bolted outlet box connection. Route a continuous green equipment
grounding conductor with branch circuit conductor serving isolated ground
receptacle. Terminate the equipment ground on the ground bus in the
panelboard.
16. The Contractor shall identify the panelboard and circuit number from which
receptacles are supplied on the wires connected to receptacle terminals
C. Installation of Boxes
1. General
2. Floor Boxes
3.03 TESTING
A. General
1. The Contractor shall carry out all field tests in accordance with approved test
procedure to ensure that the equipment and materials comply with the
specifications and operational requirements. All tests are subject to witnessing
by the Royal Commission representatives.
2. At least 4 weeks prior to scheduled tests, the Contractor shall submit to the
Royal Commission an outline of the plan and procedures to be used in
performing the site inspection and site tests. The outline shall include a brief
description of the test equipment, connection diagrams, proposed tests and
procedures, test sheets, calculations, reference drawings and
minimum/maximum test and performance values in conformance with
applicable standards which will be used to determine conformance with the
specification and acceptability of the equipment and installation.
7. Wring devices shall be tested for proper polarity and ground continuity,
operating each device at least 6 times.
8. GFCI operation shall be tested with both and local and remote fault simulations
according to manufacturer’s written instructions.
9. Each wiring device shall be inspected for defects and, damaged and defective
components replaced.
END OF SECTION