Professional Documents
Culture Documents
, 'H, ~\
4..b6...J\~w
.. .~..c:t\ C""""
. L\Y'"'.J
_..:t\ ~ "LiJ! ill~\ <..::.Jli...o\
- _t\
Y*'
SECTION 16410:
KINGDOM
OFSAUDIARABIA
~~tfUJl4J.}!J1~I
forJubail&Yanbu
RoyalCommission ~4 ~ A#J.oJI
~I
SECTION 16410
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................... 1
1. 04 REFERENCES..................................................................................................... 2
1. 05 DEFINITIONS....................................................................................................... 4
1. 06 SUBMITTALS....................................................................................................... 5
1. 10 SERVICE CONDITIONS...................................................................................... 6
1. 11 ENCLOSURES .................................................................................................... 7
2. 01 GENERAL ............................................................................................................ 9
3. 01 GENERAL .......................................................................................................... 24
PART 1 GENERAL
1. 01 DESCRIPTION OF WORK
A. This Section specifies the minimum technical requirements for design engineering,
furnishing, manpower, installing and supervision, of enclosed switches and circuit
breakers as per the Contract Documents.
B. The Contractor shall, as part of his full responsibility scope, check the enclosed
switches and circuit breakers as specified in the Contract Drawings/Documents.
When this check indicates that the specified enclose switches and circuit breakers
are not adequate, then the Contractor shall notify the Royal Commission and take the
necessary action/changes with approval by the Royal Commission.
C. The Contractor shall also check and verify every requirements, aspect and detail
necessary for coordinating with new or existing systems of enclosed switches and
circuit breakers.
1. 02 SECTION INCLUDES
A. This Section specifies design, furnishing, installing, testing and commissioning of Low
Voltage Enclosed Switches and Circuit Breakers as per The Contract Document.
1. 03 RELATED SECTIONS
1. 04 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials and products. In case of conflict between these standards and
the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment conforming to
one group of codes and standards.
1. 05 DEFINITIONS
A. air circuit breaker: The medium in which circuit interruption is performed may be
designated by suitable prefix, that is air circuit breaker.
C. enclosed switches: Switches designed for service within a housing, restricting heat
transfer to the external medium.
E. isolating switch or knife switch: A form of switch in which the moving element,
usually a hinged blade, enters or embraces the stationary contact clips.
F. low voltage: Means a voltage level of less than 1000 V. For this equipment in the
intended application “Low Voltage” shall be limited to 600 V.
G. miniature circuit breaker: A small trip switch operated by an overload and used to
protect an electric circuit.
1. 06 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
Work:
1. All vendor drawings and products data including schematics and wiring
diagrams shall be generally provided as defined in the SECTION 16055 are
required, and as listed below:
a) List of manufacturers.
h) Certificates of compliance.
B. The Contractor shall submit field test reports after the completion of Testing and
Commissioning.
1. 07 QUALITY CONTROL
A. The Contractor shall be responsible for the quality of Work and shall develop and
propose programs and methods of construction and testing such as to achieve the
specified quality to the approval of the Royal Commission in accordance with
SECTION 01450.
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
1. 09 FACTORY TESTING
A. General
1. All the equipment/material shall be tested at the factory. The Contractor shall
notify the Royal Commission in writing not less than 30 days prior to the
scheduled starting date of the factory tests.
2. The Royal Commission reserves the right of deputing their representative for
witnessing the factory tests.
1. 10 SERVICE CONDITIONS
A. All the enclosed switches and circuit breakers installed indoors shall be suitable for
continuous operation under the following service conditions:
a) A maximum of 40°C.
b) A minimum of 0°C.
B. All the enclosed switches and circuit breakers installed outdoor shall be suitable for
continuous operation under the following service conditions:
a) A maximum of 50°C.
C. All the enclosed switches and circuit breakers to be installed in classified areas as
indicated on the Contract Drawings shall be suitable for such installation as per NEC
Article 500 or other relevant standards as specified in par. 1.04.
D. The Equipment shall be labeled, listed or certified by at least one of these standards
UL, NEMA or IEC.
1. 11 ENCLOSURES
B. Enclosures shall bear labels from a testing laboratory (i.e. UL, IEC or approved
equal) indicating that they are designed, constructed and tested to the applicable
standards referenced within this Specification.
A. The Contractor shall deliver, handle and store material and equipment in accordance
with SECTIONS 01650 and 01660, as well as the following requirements:
PART 2 PRODUCTS
2. 01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods and products
manufactured out-of-Kingdom must be approved by the Royal Commission.
A. General
1. All enclosed switches shall be general or heavy duty, single or double throw
type with Ampere and Voltage rating, number of poles, fusible or non-fusible as
indicated on the Contract Drawings.
a) General duty switches are from 30 to 1200 A ratings are intended for
light service when usual load prevail in systems not exceeding 240 V AC
and are for use with Class H fuses.
b) Heavy-duty switches are from 30 to 1200 A ratings and are intended for
systems not exceeding 600 V AC and also suitable for 600 V DC.
5. Enclosed switches shall have defeatable door interlocks that prevent the door
from opening when the operating handle is in the ‘ON’ position. The handle
shall be capable of being padlocked in the ‘OFF’ position.
7. The enclosure shall be totally enclosed type, made of heavy gage sheet steel,
and finished enamel to comply with ANSI Z55-1. An earthing terminal shall be
provided. The enclosure shall be suitable for conduit, trunking and armored
cable entries and also for connection to busbar chamber from top or bottom.
Enclosures shall be as specified in par. 1.11.
1. Molded case switches shall be as specified in par. 1.04. The molded case
switch is virtually identical in construction to the molded case circuit breaker,
except that they shall be operated manually, and non-automatic quick-make
and quick-break type, without any overload or over-current protection features.
2. Casing shall be molded from a strong heat resistant resin. Fitted with
padlocking facilities so that they can be padlocked in either “ON” or “OFF”
position, and they shall be 2 or 3-pole with the provisions for bolt on
connection.
3. The switch shall carry a short-circuit current for 1 second duration. These
switches are not designed to make or break the short-circuit.
2. Isolating switches rated at over 1200 A at 250 V or less, and at over 600 A at
251 to 600 V, shall be used only as isolating switches and shall not be opened
under load.
A. General
1. This Section covers the general requirements of ACB, ICCB, MCCB, MCB,
and RCCB. Additional requirements relevant to a particular type of circuit
breakers are as indicated below.
2. Circuit Breakers shall comply with either standard listed in par. 1.04. Circuit
3. Circuit breakers shall have multi-pole contacts such as 4-pole (with switch
neutral), 3-pole, 2-pole and one-pole. ACB or power circuit breakers normally
have 3-pole or 4-pole contacts, or as indicated on the drawings. The operating
mechanism shall be entirely trip-free so that the contacts cannot be held
closed against an abnormal over-current or short-circuit conditions.
5. Circuit breakers shall be encased within rigid, non-metallic housing and vary in
sizes and rating. They shall be tested for overload, endurance and short-circuit
by international approved laboratory or institution.
8. The circuit breakers shall have the following minimum RMS symmetrical
interrupting capacity:
9. Bolted type circuit breakers shall be suitable for mounting and operating in any
position
10. Facility for padlocking circuit breakers in “OFF” position shall be provided.
11. The circuit breakers shall be suitable for continuous operation at rated current
under the service condition as specified in pars. 1.10 and 1.11, as indicated
above.
a) General
6) The circuit breakers shall be rated for ranges 400 to 4000 A. The
ranges shall have 2 frame sizes (in 3 or 4-pole configuration) with
each range having common height and depth.
11) The protection feature for ACB, which shall be fixed mounted type
or unless otherwise indicated, used as feeder protection of a
branch feeder shall be from pars. 2.03 B.10.a to n of the above
features for main ACB.
b) Performance Characteristic
d) Racking Gear
1) The enclosure of the draw-out type ACB shall be fitted with a set
of racking gears that shall lock the ACB to the runner rails in
3 distinct positions, i.e. “CONNECTED,” “TEST” and
“DISCONNECTED.” The ACB can only be closed fully when it is
in the “CONNECTED” position. In the “TEST” position, it shall be
possible to operate the ACB (for ACB with motorized charging
spring only) to close and test the secondary and auxiliary
contacts, but not the main isolating contacts.
2) The racking gear shall consist of rollers fitted to the ACB frame.
All parts shall be accurately aligned and adjusted so that the ACB
can be moved freely along the runner rails within the enclosure
between the two extreme positions, i.e. “CONNECTED” and
“DISCONNECTED.” Facilities shall be provided to padlock the
ACB in its “CONNECTED,” “TEST” or “DISCONNECTED”
position.
2) Two sets of safety shutters shall be provided for every ACB, one
for the incoming terminals of the main isolating contacts and the
other for the outgoing terminals. Each set shall be capable of
being operated individually.
g) Contact
2) Main contacts shall be fitted with detachable arc chutes for each
pole. Sufficient auxiliary contacts shall be provided for connection
of secondary wiring. These auxiliary contacts shall remain
engaged when the ACB is in the “TEST” or “CONNECTED”
position and shall be disengaged when the ACB is in the
“DISCONNECTED” position.
a) General
8) Type of MCCBs
(a) Thermal-Magnetic
(i) Employ temperature-sensitive bimetal, which provide
inverse or time delayed tripping on overloads, and
coil or magnet and armature designs for
instantaneous tripping.
(b) Magnetic Only
(i) Employ only instantaneous tripping and are used in
welding or motor circuit application.
(ii) Standards recognize magnetic type only for motor
circuit applications.
(c) Integrally Fused
(i) Specially designed current-limiting fuses are housed
within the molded case for extended short-circuit
application in systems 100 or 200 kA available,
interlocks are provided to ensure that the MCCB trips
when any fuse operates.
(d) Current Limiting
(i) Employs electromagnetic principles to effectively
reduce the let-through magnitudes of current and
energy (I²t).
(ii) Their ratings and number of operations are available
in manufacturer's literature.
(e) High Interrupting Capacity
(i) Employs high stronger, high temperature molded
material, but retain the standard circuit breaker
dimensions.
(ii) Use for application in systems having high fault
current.
b) Operating Characteristic
c) Performance Characteristic
1) The shunt trip release controls the tripping of the circuit breaker
with which it is associated. It shall trip on energisation, equipped
with a contact allowing self-breaking and operate between the
70 to 120% of the supply nominal voltage.
a) General
4) Terminal lugs for MCB rated 0.5 to 63 A shall accept cable sizes
of 1 to 35 mm2 (for load lugs) and 1 to 25 mm2 (for line lugs).
Terminal lugs for MCB rated 80 to 125 A shall accept cable sizes
of not more than 70 mm2 for load/line lugs.
5) The breakers shall be designed for both bus bar and DIN rail
installations. If DIN rail mounted, the MCB shall be easily to
remove and to install.
b) Operating Characteristic
a) General
b) Operation
3) When a neutral pole is built, it has to be closed first and open last,
with respect to other phases, in order to prevent over-voltage.
c) Test Device
5. Fuse
a) General
c) Cartridge Fuse
b) Each switch’s circuit beakers and fuses shall have a label as per
standard or as follows.
5) Rated Ampere.
6) Rated voltage.
9) Serial number.
PART 3 EXECUTION
3. 01 GENERAL
A. The Contractor shall provide all materials, equipment and labor as deemed
necessary for proper execution of the work.
A. General
A. General
1. The Contractor shall carry out all site test in accordance with approved test
procedures that conform to ensure that the equipment and materials comply
with the specifications and operational requirements. All tests are subject to
witnessing by the Royal Commission representatives.
2. At least 4 weeks prior to schedule tests, the Contractor shall submit to the
Royal Commission an outline of the plan and procedures to be used in
performing the site inspection and site tests.
3. This outline shall include a brief description of the test equipment, connection
7. Care shall be taken that the test apparatus does not damage the circuit
breaker during the testing.
3. Test circuits for connections in accordance with the wiring diagram. Check all
connections for tightness.
5. Test operation of circuits and controls. When testing, the Contractor shall
operate each control a minimum of 10 times and each circuit continuously for a
minimum of ½ hour.
END OF SECTION