Professional Documents
Culture Documents
SECTION 16440 Switchboards, Panelboards & Control Centers Rev 0
SECTION 16440 Switchboards, Panelboards & Control Centers Rev 0
~I
-<- ~'I ~:<1JAJ c;.J~
r-- . --:11
wb YJ
_I ~ "liJl wb -11~.L.bjl w~1
Y'"
--II
Y'"'
SECTION 16440:
KINGDOM
OFSAUDIARABIA ~~~I ~}iJ1~I
forJubail&Yanbu
RoyalCommission ~ 1~ 4#J.oJ I 44fJ 1
SECTION 16440
SWITCHBOARDS, PANELBOARDS & CONTROL CENTERS
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................... 1
1.05 DEFINITIONS....................................................................................................... 3
1.06 SUBMITTALS....................................................................................................... 4
2.02 SWITCHBOARDS................................................................................................ 8
PART 1 GENERAL
A. Switchboards
B. Panelboards
C. Control Center
1.04 REFERENCE
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials and products. In case of conflict between these standards and
the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment conforming to
one group of codes and standards.
1.05 DEFINITIONS
C. dead front: Equipment without live parts exposed to a person on the operating side
of the equipment.
F. low voltage: A voltage level of less than 1000 V. In this section, the intended
application “low voltage” shall be up to 600 V.
supporting and enclosing housing of insulating material designed to open and close a
circuit by non-automatic means and to open the circuit automatically on a
predetermined over-current without injury to self when properly applied within its
rating.
I. panelboard: A single panel or group of panel units designed for assembly in the form
of a single panel, including buses and automatic over-current devices, and equipped
with or without switches for the control of light, heat or power circuits designed to be
placed in a cabinet or cut-out boxes placed in or against a wall, partition or other
support and accessible only from the front.
1.06 SUBMITTALS
A. The Contractor shall submit to the Royal Commission under the provision of
SECTION 01330, the following items for their review and/or approval before
commencing work:
B. The Contractor shall submit Field Test Report after completion of testing and
commissioning.
A. The Contractor shall be responsible for the quality of work and shall develop and
propose programs and methods of construction and testing such as to achieve the
specified quality to the approval of the Royal Commission in accordance with
SECTION 01450.
3. Contractor
a) Health and Safety Standards and System as accepted by the Royal
Commission.
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
A. All equipment and materials shall be tested at the factory in accordance with latest
applicable codes and standard. All type of tests as per applicable codes and
standards shall be performed on first unit of every new design. The Contractor shall
notify the Royal Commission in writing not less than 30 days prior to the scheduled
starting date of the factory tests.
B. The Royal Commission reserves the right of deputing their representative for
witnessing the factory tests.
C. Upon completion of factory test and before shipment of the equipment or material,
the Contractor shall submit 5 certified copies of the test reports not latter than
10 days after completion of all factory test for review and approval of the Royal
Commission.
A. Switchboards, Panelboards and Control Centers installed indoors shall be suitable for
continuous operation under the following service conditions:
a) A maximum of 40°C.
b) A minimum of 0°C.
c) Average temperature measured over a period of 1 month is 35°C.
1.11 ENCLOSURES
A. The Switchboards, Panelboards and Control Centers shall meet relevant standards,
listed in par. 1.04, for enclosure requirements.
A. The Contractor shall deliver, handle and store equipment and material units in
accordance with SECTIONS 01650 and 01660, as well as the following
requirements:
2. Ship each unit securely wrapped, crated and wrapped or packaged and
labeled for safe handling in shipment and to avoid damage or distortion.
4. Lift the equipment using eyes, yokes, and skids provided for the purpose by
manufacturer.
5. Store all indoor units protected from weather and protect all units from physical
damage from work of other trades.
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods manufactured
out-of-Kingdom shall be approved by the Royal Commission.
2.02 SWITCHBOARDS
A. Construction of Switchboards
4. The switchboard shall have frame structure of 2.5 mm minimum thick formed
steel channels with welded sub-frames bolted to longitudinal members and
reinforced at corners. Side, top and rear covers (panels) shall have minimum
thickness of 1.5 mm or code-gage steel, bolted to the switchboard structure.
5. The removable rear access panels shall be of the concealed hinged type, or
screw-on type. The front shall be completely enclosed with hinged panels
covering each breaker, metering or blank compartment.
6. The hinged covers shall be provided with concealed hinges, latches, and cut-
outs where necessary for ventilation, operating mechanism, mechanical trip
and position indication.
7. Adequate ventilating louvers shall be provided only in the hinged panels where
required to limit the temperature rise of current-carrying-parts, including
contacts, to values specified in IEEE standard rules for enclosed equipment.
8. All openings shall be protected against entrance of falling dirt, water or other
foreign matter. Filters are not required for indoor assemblies. Each
switchboard shall be mounted on a 100 mm concrete pad and anchored to two
100 mm channel iron sills by tack welding or bolting.
9. Sills shall be furnished by the Contractor to suit the switchboard and shall be
leveled and grouted flush into the concrete pad by the Contractor.
10. Where space for future is indicated, all necessary buses and straps shall be
provided.
13. Each switchboard shall have an engraved nameplate fixed by stainless steel
screws. The nameplate shall indicate a facsimile of the switchboard bussing
and switch device arrangement, both in English and Arabic.
14. Each switch shall be equipped with a nameplate which indicates the name of
the equipment to which the feeder conductors are connected. Feeder numbers
used on the drawings shall be applied on the switch nameplates.
15. All devices located within a switchboard shall be provided with suitable
nameplates to identify item and function. The nameplates of protective devices
shall indicate ANSI device number.
17. All enclosure parts shall be thoroughly cleaned, degreased and given a
phosphatizing treatment to inhibit rust and to prime the metal for the finish
coating. A 5 micron (0.2 mil) thick electrostatic powder paint coat shall be
applied to all surfaces. The paint type and process shall meet UL 1332 for
electrical equipment steel enclosures. All exterior enclosure covers and doors
shall be painted ANSI Z55.1 No. 61 gray (Munsel 8.3/G.10/0.54).
b) All mechanical and electrical connection shall be made from the front.
a) Designed to be free-standing.
d) All normal maintenance in the main bus shall be performed from the
rear.
e) All line and load connections for branch devices are made from the
front.
f) Cross bus is located behind the branch devices and is available only
from the rear.
a) Designed to be free-standing.
d) All normal maintenance in the main bus shall be performed from the
rear.
e) All line and load connections for branch devices are made from the rear.
f) All cross bus and line and load connections branch devices accessible
only from the rear.
21. Sub-main, tie and feeder devices shall be individually mounted and arranged
for stationary (dead-bolt plug in) mounting, unless otherwise indicated. Also,
they shall be arranged to be individually removable from the front of the
switchboard.
22. Main devices shall be individually mounted and arranged for stationary (draw-
out) mounting, unless otherwise indicated.
23. Main device shall be completely isolated from the feeder sections of the
switchboard both in the device section and the cable section of the cubicle.
The cable section shall also be isolated from the main horizontal bus bar.
c) Fusible switches.
d) Motor starters.
25. All feeder device line and load connection straps shall be rated to carry the full
continuous current rating of the device frame (not trip rating). The load
connection straps shall be insulated and extended beyond the main bus.
26. Switchboard standardized to IEC rated 400 A and below shall be acceptable
as low voltage switchboards.
1. All bus bars shall conform to ASTM B187M, 98% conductivity copper with
silver plated contact surfaces. In no case shall dimensions be such that at
rated load the current density in any copper bus bar exceeds 1,000 A per
645 mm2 of cross-section.
2. The bus bars shall be braced to withstand or exceed the short circuit rating of
the switchboard as indicated on the Contract Drawings for the service
conditions as specified in par. 1.11.
3. All buses shall be rigidly held by bus supports which have high and indefinitely
long lasting dielectric qualities, are moisture resistant, non-carbonizing, non-
tracking and have vertical creepage surface to prevent faults due to build up of
conductive dirt. Bus bar spacing shall not be less than and spacing of bus
fastening point shall not be more than those specified in UL 891.
4. The bus bars shall run continuously through all sections of switchboards, with
provision made for extension at either end for future expansion.
5. Bus bars shall be uniformly arranged to provide A-B-C sequence left to right
(from front), front to rear and top to bottom. The bus bar shall be accessible
6. Bus bars shall be so mounted on the switchboard that no current carrying part
(bus bar, nuts, bolts, connectors, switch parts, etc.), is less than 25 mm from
grounded parts of the switchboard.
7. The vertical bus in main and feeder sections shall be insulated and isolated
from main horizontal bus.
8. Each phase of the main horizontal bus shall be insulated/isolated from each
other and device load lugs (taping is not acceptable). Bus joints shall be
insulated with removable caps to allow maintenance without removal of the
barriers or tape.
9. If neutral bus is required, the bus rating shall be equal to phase bus.
10. A ground bus of minimum half the size of the phase bus bar, shall be provided
running the full length of the switchboard, bolted to each vertical section. The
internal ground bus of the service bus duct servicing the switchboard shall be
bonded to the above grounding bus in a manner meeting all code
requirements.
C. Wiring
1. Wiring shall meet relevant standards as specified in par. 1.04. All conductors
shall be copper materials, except conductors that are internal to pre-
manufactured devices, integral parts or components of manufactured
equipment, and plating of the copper, silver or copper/silver alloy base
conductor materials.
2. Control and secondary wiring shall be 2.5 mm2 stranded copper conductors
only.
3. Each wire shall be identified with thermo-plastic, slip-on wire markers with
permanently printed characters. Snap-on or adhesive type markers are
prohibited.
D. Terminal
2. All connection points between assembly devices and field wiring shall be made
with terminal blocks. 20% spare terminal block points shall be provided.
3. Terminal blocks shall be one piece, phenolic, barrier type, rated 20 A, 600 V
minimum with numbered marking strips and suitable for two terminations per
point. A maximum of 2 wires per point is permitted.
4. Current transformer circuits shall use ring tongue terminals. Shorting terminal
blocks shall be provided for current transformer circuits.
d) The breaker shall be equipped with adjustable long time, short time and
instantaneous trip elements. The breaker shall employ a spring-
operated, stored-energy mechanism that assures high-speed closing of
the breaker contacts, independent of the operating force.
a) The branch circuit breakers shall be the same type as the main circuit
breaker except for frame and over-current trip ratings. Those shall be as
shown on the Contract Drawings.
3. Monitoring Panel
a) The monitor panel shall be a flush mounted unit rated at 120 V. The
panel shall allow testing of the system with or without tripping the main
circuit breaker. A pilot light shall be provided to indicate presence of
control power.
b) The panel shall be provided with an alarm and annunciator circuit. The
multiple alarm units shall have common test, acknowledge and reset
push buttons. The red push button shall be marked "TEST" and the
yellow push button shall be marked "RESET." The acknowledge push
button shall be green in color. Annunciators shall be in energized mode
for normal conditions. Under fault conditions, annunciators shall flash
and an audible horn shall be energized. When the alarm is
acknowledged, the horn shall be silenced and annunciators shall
continue flashing until circuit is reset.
c) A red colored ground fault lamp shall light to show that the “Ground
Break” relay has operated to trip the main breaker. The reset button
must be pushed to reset the relay after the fault has been located and
before the breaker can be closed.
2.03 PANELBOARDS
A. Construction of Panelboards
1. General
e) Panelboards shall have bolt-on MCCBs, either with electronic trip units
or just normal thermal-magnetic trip units, or as indicated on the
Contract Drawings. Refer to SECTION 16410 for the specification of
enclosed switches and circuit breakers.
3. The breaker shall have trip ratings as indicated on the Contract Drawings or in
the panelboard schedules. Breakers shall have a minimum interrupting
capacity of 10,000 A symmetrical at 240 V. A magnetic armature shall also be
provided to trip the breaker instantaneously for short circuit current above the
overload range. The magnetic trip devices shall be adjusted at the factory to
"low" trip setting ampere values.
a) These panels shall have more than 10% of the over-current devices
rated 30 A or less, for which neutral connections are provided.
b) Not more than 42 over-current devices (other than those provided for
the mains) of lighting and appliance branch-circuit panelboards shall be
installed in any one cabinet. For this purpose, a 2-pole circuit breaker
shall be considered as 2 over-current devices and 3-pole circuit breaker
shall be considered as 3 over-current devices.
a) This type includes all other panelboards not defined as lighting and
appliance panelboards. The 42-over-current protective device limitation
does not apply.
b) The size shall not exceed practical and physical limitations, such as the
standard box height and widths available.
a) This type includes small number of motor starters grouped together into
a panelboard. This panel is not applicable for the grouping of a large
number of motors to be controlled from one location, rather use MCC.
d) Terminal blocks shall be furnished near each unit when external control
wiring required in not combined units.
7. Multi-Section Panelboards
1. The bus bars shall be tin-plated, except where joints are overlapping or mating
surfaces that shall be silver plated or copper with 98% conductivity as per
relevant standards listed in par. 1.04.
3. The bus bars shall be so located as to be free from physical damage and shall
be held firmly in place.
5. A neutral bus bar of the same rating as that of phase bus shall be provided
and shall have numbered terminals for connection of neutral wires.
C. Wiring
2. The enclosure for a panelboard shall have the top and bottom wire bending
space sized in accordance with NEC Table 312.6(B) for the largest conductor
entering or leaving the enclosure. The side wire bending space shall be in
accordance with NEC Table 312.6(A) for the largest conductor to be
terminated in that space.
D. Terminal Blocks
2. All wire and cable connections to the main circuit bus system shall be
terminated using 2-hole compression connectors.
3. All wires and cables 95 mm2 (4/0 AWG) and larger shall be terminated using
compression connectors.
A. Motor starters and motor control centers are covered under control centers.
3. The control center shall be equipped, unless otherwise indicated, with a main
over-current device, motor starters, motor contactors, overload protection
device and necessary interconnections, instrumentation and control wiring.
B. Motor Starters
b) Control connection shall be clearly marked “L” for line, “C” for closing,
and “O” for opening. Remote control switches with protection shall be as
per standards.
3. Motor starters shall be rated for continuous current suitable for the associated
motor in accordance with related standards specified in par. 1.04 and as
shown on the Contract Drawings. Minimum size of a starter shall be NEMA 1
size.
4. All starters must be equipped with thermal overload relays in each ungrounded
conductor as per NEC Article 430.32 and shall be sized in accordance with
nameplate rating of motor supplied.
5. If starters are provided with disconnect switches or motor circuit protector type
circuit breaker as the main disconnecting device, the motor circuit protector
shall be an adjustable instantaneous only type. The handle mechanism used
to operate the circuit breaker shall be labeled with ‘ON,’ ‘OFF’ and ‘TRIP’
positions; and that of the disconnect switch with ‘ON’ and ‘OFF’ positions.
a) Across the line manual starters for all motors of rating ½ HP and below
shall be operable on 127 V, single phase, 60 Hz supply.
b) Across the line magnetic starters for all motors above ½ HP and up to
200 HP shall be operable on 380 V (or voltage level as indicated on the
Contract Drawings), 3-phase, 60 Hz supply.
c) Combination starters for all motors where overload relays and other
devices for motor overload protection that are not capable of opening
short-circuits or ground faults, shall be protected by fuses or circuit
breakers with ratings or settings in accordance with Section 430-52 of
NEC.
8. Manual Starters
9. Magnetic Starters
a) The reduced voltage starter shall be considered for what it is used for to
ensure efficient operation, especially in larger motor sizes. Starters that
reduce in rush current each have unique characteristic, and are as
follows:
1) Autotransformer Reduced Voltage Starters
(a) They shall be used for the applications where highest
starting torque is required for reduced starting current of the
motor. During starting of motor, autotransformer reduced
voltage starters shall provide reduced current with a
minimum sacrifice of starting torque. Autotransformers shall
have adjustable taps to reduce starting voltage to 50, 65, or
80% of full-line voltage.
2) Part Winding Reduced Voltage Starters
(a) Part-winding reduced voltage starters shall be provided on
motors with 2 separate parallel windings on the starter. The
windings used during start shall draw about 65 to 80% of
the rated locked rotor current. During running, each winding
shall carry approximately 50% of the load current.
3) Star-Delta Reduced Voltage Starter
(a) Star-delta reduced-voltage starters shall be provided on the
motors having stator windings not connected internally and
all 6 motor leads available for connection. During starting,
the motor shall be connected in star configuration to draw
reduced starting line current. The motor shall be
reconfigured to a delta connection for running condition.
4) Primary Resistance Reduced Voltage Starter
(a) Primary resistance reduced voltage starters are provided
on motors used for belt-driven or gear-driven equipment.
During starting, the motor shall be energized through a
resistor in each of the 3 incoming lines. Part of the voltage
shall be dropped through the resistors. The motor shall
receive 70 to 80% of the full-line voltage. As the motor
picks up speed, a time-delay relay shall close a separate
set of contacts, shorting out the resistors and applying full
voltage to the motor.
5) Solid State Reduced Voltage Controllers
(a) These are more advanced starters and shall be used where
greater control of starting, running and stopping of motor is
required. Solid-state reduced voltage controllers shall apply
voltage gradually from some low initial value to 100%
voltage resulting in reduced in rush current and smooth
acceleration of the motor.
a) The Contractor shall supply reversing starters for motors used for
various applications such as the opening or closing of valves. The
direction of rotation of the motor shall be changed by changing the
direction of current flow through the winding. This shall be achieved by
interchanging supply between phase A and C of 3-phase motors.
i) Provide identification labels for each motor starter indicating the motor
or device controlled. Device, such as meters, circuit breakers, and
fuses; and each compartment, the enclosing devices, or the operational
parts. The nameplate shall be bolted or riveted by stainless steel bolts or
non-corrosive materials; shall be of laminated plastic materials with
white background and with 5 mm high black cut-in letters.
j) Provide openings, bus stubs with jointing materials and accessories for
future motor control expansion.
k) Provide spare parts such as entire starters, circuit breakers and fuses (if
specified protective device or parts thereof) that are subject to periodic
replacement.
m) All circuit components within each unit shall be factory wired. The type
of wiring requirement shall meet relevant standards.
a) General
1) Each vertical section shall be provided with a main 3-phase
insulated horizontal bus at the top, and with a 3-phase insulated
vertical bus to distribute power to the combination starters and
feeder units in the vertical section. A full neutral copper bus bar
shall be provided as specified on the Contract Drawings. A
continuous bare copper ground bus shall be provided throughout
the length of the control center.
2) All bus bars shall conform to ASTM B187M, 98% conductivity
copper with silver plated contact surfaces. Horizontal and vertical
buses shall be tin or silver plated and shall be braced to withstand
the minimum RMS symmetrical fault current of 32 kA at a
utilization voltage of 380 V, or as specified on the drawings. Bus
ratings shall be based on 50°C rise over a 40°C ambient.
3) All buses shall be rigidly held by bus supports which have high
and indefinitely long lasting dielectric qualities, are moisture
resistant, non-carbonizing, non-tracking and have a vertical
creepage surface to prevent faults due to build up of conductive
dirt. Bus bar spacing shall not be less than and spacing of bus
fastening point and shall not be more than those specified in
UL 845.
4) The phase arrangement on 3-phase horizontal common power
and vertical buses shall be A, B, C from front to back, top to
bottom, or left to right, as viewed from the front of the Motor
Control Center.
4. Wiring
a) All equipment shall be completely wired within the control center for
control and operation. Wiring shall be in accordance with NEMA Class II
Type B.
c) All internal wiring shall be identified with slip-on wire markers. Wiring
requiring external connections shall be brought to terminal blocks for
attachment of external leads. All external wiring shall be identified with
duplicate cable tags. One tag, with black lettering on white, shall be
applied by use of a heat-shrinkable sleeve, fire retardant, resistant to
industrial solvents, contaminants and sunlight. The second tag shall be
metallic, corrosion resistant and shall be installed by use of cable ties
resistant to industrial solvents, contaminants and sunlight. The cable
shall be identified as per wiring drawings with the service number (i.e.
motor no., panel etc.). The cable identification shall also show the
source equipment (MCC, switchgear no. etc.). Wires shall be terminated
with full-ring, insulated, compression connectors.
f) Control and feeder power cables will enter the motor control center
assembly either from the top and/or bottom. Suitable supports shall be
provided within the motor control center housing for power and control
cables.
g) The motor space heater circuit shall be factory wired from the heater
circuit breaker in the distribution panel board to the terminal block in
each starter compartment for remote connection. The motor space
heater circuit shall be wired through a normally closed auxiliary contact
of starter for automatic energizing of space heater when motor is
stopped. One branch circuit breaker shall be provided in the motor
control center space heaters for manual switching of heaters.
5. Terminal Blocks
a) Terminal blocks shall be provided for all secondary and control wiring
requiring external connections. The terminal block shall be front
mounted with minimum rating of 10 A, and shall be provided with marker
strips. The contractor shall supply 20% spare terminals.
b) All control devices such as oil tight ‘ON’ - ‘OFF’ or ‘OPEN’ – ‘CLOSE‘
push buttons, ‘H-O-A’ selector switches, ‘ON,’ ‘OFF,’ ‘TRIP’ and
annunciation indicating lamps and all control circuit elements as well as
protection and metering devices such as ammeters, voltmeters, watt
meters and power factor meters shall be provided as shown on the
Contract Drawings when conventional controls are used.
PART 3 EXECUTION
3.01 GENERAL
A. The Contractor shall provide all materials, equipment and labor as deemed
necessary for complete and proper execution of the work.
B. After the installation is complete and properly adjusted, the Contractor shall conduct
operating tests. The various equipment and systems shall be demonstrated to
operate in accordance with the requirements of the specifications. Tests shall be
performed in the presence of the Royal Commission's representative. The Contractor
shall provide electric power, instruments and personnel necessary for performing the
various tests.
A. General
2. All buildings and rooms for the installation of the equipment shall be ready,
complete and clean. All embedded channels and anchor bolts shall be in place
as per the layout drawings. The clearances around the equipment shall be as
per Article 110.26 of NEC.
3. All the facilities required for transportation of electrical equipment from store to
site such as competent manpower, crane and trucks of adequate capacities
shall be supplied by Contractor.
4. All equipment moved to the site shall be inspected for damage or deterioration
during storage. Tag numbers and nameplates shall be verified with the details
given on the Contract Drawings.
3. All bus bars of the shipping sections shall be connected together by stainless
steel nut and bolts as per manufacturer’s instructions. The torque applied on
nuts and bolts shall be as recommended by manufacturer.
4. All power and control wiring shall be completed as per the Contract Drawings.
5. Ground complete switchboard and motor control center and motor starters as
specified in SECTION 16060.
C. Installation of Panelboard
2. The Contractor shall mount panel on wall or flush in walls. Wall mounted
panels shall be securely fastened to the wall utilizing expansion bolts or
mounting channels. The panels shall be mounted square to the building lines;
the mounting height of the center line of the top protective device shall not be
greater than 1800 mm above finished floor.
A. General
1. The Contractor shall carry out all site tests in accordance with approved test
procedure to ensure that the equipment and materials comply with the
specifications and operational requirements. All tests are subject to witnessing
by the Royal Commission’s representatives.
2. At least 4 weeks prior to scheduled tests, the Contractor shall submit to the
Royal Commission an outline of the plan and procedures to be used in
performing the site inspection and site tests. This outline shall include a brief
description of the test equipment, connection diagrams, proposed tests and
procedures, test sheets, calculations, reference drawings and minimum/
maximum test and performance values in conformance with applicable
standards which will be used to determine conformance with the specification
and acceptability of the equipment and installation.
1. Check ground bus bar continuity and connection to plant ground grid. The
grounding resistance shall comply with recommendations of IEEE 142.
2. Check that all connections and identifications are made in accordance with the
relevant schemes. Check all connections for tightness.
3. Perform insulation resistance test on power and control wiring and verify that
the insulation resistance of ungrounded conductor to ground is a minimum of
10 Mgohms.
7. Set and test all overload relays and protective devices as per relay
coordination study data sheets.
3. Test circuits for connections in accordance with the wiring diagram. Check all
connections for tightness.
4. Test operation of circuits and controls. When testing, operate each control a
minimum of 10 times and each circuit continuously for a minimum of ½ hour.
END OF SECTION