I/O MODULES

SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 1/21
Form 1144-050721 Part Numbers Description Pages

SNAP-OAC5 SNAP 4-channel 12–250 VAC output, 5 VDC logic 2, 4


Description SNAP-OAC5MA* SNAP 4-channel isolated 12–250 VAC output, 5 VDC logic 2, 5
with manual/auto switches

Opto 22 SNAP digital output modules are designed SNAP-OAC5FM SNAP 4-channel 12–250 VAC output, 5 VDC logic 3, 4
to work with SNAP D-series or SNAP B-series racks. SNAP-OAC5-i* SNAP 4-channel isolated 12–250 VAC output, 5 VDC logic 2, 6
These modules are also compatible with SNAP Ultimate, SNAP-OAC5-iFM SNAP 4-channel isolated 12–250 VAC output, 5 VDC logic 3, 6
SNAP Ethernet, and SNAP Simple I/O. Customers can SNAP-ODC5SRC SNAP 4-channel 5–60 VDC output, 5 VDC logic source 7, 11
choose from AC or DC models. SNAP digital’s 4-channel-
SNAP-ODC5SRCFM SNAP 4-channel 5–60 VDC output, 5 VDC logic source 9, 11
per-module packaging delivers high density. All solid-
SNAP-ODC5SNK SNAP 4-channel 5–60 VDC output, 5 VDC logic sink 7, 12
state modules provide 4,000 volts of optical isolation
from the field side to the logic side. SNAP-ODC5SNKFM SNAP 4-channel 5–60 VDC output, 5 VDC logic sink 9, 12

All SNAP digital modules have removable top- SNAP-ODC5R** SNAP 4-channel dry contact output, normally open 7, 13

mounted connectors to provide easy access for field SNAP-ODC5RFM** SNAP 4-channel dry contact output, normally open 9, 13
wiring. All operate on 5 VDC control logic. Each digital SNAP-ODC5R5** SNAP 4-channel dry contact output, normally closed 7, 13
module features integral channel-specific LEDs for SNAP-ODC5R5FM** SNAP 4-channel dry contact output, normally closed 9, 13
convenient troubleshooting and maintenance. SNAP SNAP 4-channel isolated 5–60 VDC output, 5 VDC logic
SNAP-ODC5MA* 8, 14
digital I/O is 200 percent factory-tested, and most with manual/auto switches

modules are UL and CE approved. In addition, part SNAP-ODC5-i SNAP 4-channel isolated 5–60 VDC output, 5 VDC logic 8, 15
numbers ending in FM are Factory Mutual approved. SNAP-ODC5-iFM SNAP 4-channel isolated 5–60 VDC output, 5 VDC logic 10, 15
SNAP output modules are used to switch up to four SNAP-ODC5A-i* SNAP 4-channel isolated 5–200 VDC output, 5 VDC logic 8, 15
separate AC or DC loads. Output modules that are fused SNAP-ODC5A-iFM SNAP 4-channel isolated 5–200 VDC output, 5 VDC logic 10, 15
use a standard fuse with a convenient handle for easy
SNAP-ODC5ASNK* SNAP 4-channel 5–200 VDC output, 5 VDC logic sink 8, 12
replacement. DC outputs are available in either a source
SNAP-RETN4 SNAP 4-module retention rail (OEM) --------
or sink configuration. AC outputs are zero voltage turn on
and zero current turn off for transient-free switching. The SNAP-RETN4B SNAP 4-module retention rail, 25-pack (OEM) --------

dry contact modules allow switching of low power signals SNAP-RETN6 SNAP 6-module retention rail (OEM) --------

where signal integrity must be maintained, or where zero SNAP-RETN6B SNAP 6-module retention rail, 25-pack (OEM) --------
leakage current is a requirement. SNAP-FUSE4AB SNAP 4-amp fuse, 25-pack --------
SNAP-OAC5MA and SNAP-ODC5MA are special SNAP-MODFUSEH SNAP digital output module fuse holder, 10-pack --------
modules featuring manual-on/manual-off/automatic
* UL approval pending
switches, ideal for diagnostic testing of control applications. ** Not UL approved
The switches override output from the application, so you
can quickly check field device wiring. These modules each
Features
contain four isolated channels.
The SNAP-OAC5-i, SNAP-ODC5-i, and • Four channels per module
SNAP-ODC5A-i modules provide four isolated output • Convenient pluggable wiring terminals
channels. • Powered by a single 5-volt supply
Dry contact modules are not solid-state devices. They • Channel-specific LEDs
use reed relays, which are electro mechanical devices. • Operating temperature: 0° to 70° C
These modules do not provide optical isolation. Current • UL and CE approved (most modules)
rating for dry contact modules depends on the voltage • Accepts up to 14 AWG wire
they are used with, as shown in the graph on page 10. • Factory Mutual approved
(part numbers ending in FM)

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 2/21
Form 1144-050721
Specifications
AC Output Modules

SNAP-OAC5 SNAP-OAC5MA SNAP-OAC5-i


AC OUTPUT MODULE

Key Feature -- Diagnostic switches Four isolated channels


Four isolated channels

Field Side Ratings (each channel)

Line Voltage - Maximum 250 VAC 250 VAC 250 VAC

Line Voltage - Nominal 120/240 VAC 120/240 VAC 120/240 VAC

Current Rating 3 amps per module 3 amps per module 3 amps per module
0°C to 70°C Ambient

One Cycle Surge 80 amps peak (50/60Hz) 80 amps peak (50/60Hz) 80 amps peak (50/60Hz)

Minimum Load Current 20 mA 20 mA 20 mA

Output Voltage Drop 1.6 volts maximum @ 0.75 amps 1.6 volts maximum @ 0.75 amps 1.6 volts maximum @ 0.75 amps

Off-state Leakage at 2.5 mA @ 240 VAC 2.5 mA @ 240 VAC 2.5 mA @ 240 VAC
Nominal Voltage - 60 Hz 1.25 mA @ 120 VAC 1.25 mA @ 120 VAC 1.25 mA @ 120 VAC

Peak Blocking Voltage 500 volts 500 volts 500 volts

Operating Frequency 25-65 Hz 25-65 Hz 25-65 Hz

dV/ dt - Off-state 200 volts/msec 200 volts/msec 200 volts/msec

dV/ dt - Commutating Snubbed for rated 0.5 power Snubbed for rated 0.5 power Snubbed for rated 0.5 power
factor load factor load factor load

Fuse 250 VAC - 4A 5x20 mm Fast-acting Has four isolated channels. User Has four isolated channels. User
(Common to all Channels) Bell Fuse Part No. BEL 5HF4 must provide own fusing. must provide own fusing.
Opto 22 Part No. SNAP-4A

Channel-to-channel Isolation Not applicable 300 VAC (1500 V transient) 300 VAC (1500 V transient)

Logic Side Ratings

Pickup Voltage 4 VDC @ 5.5 mA 4 VDC @ 5.5 mA 4 VDC @ 5.5 mA

Dropout Voltage 1 VDC @ <500 mA 1 VDC @ <500 mA 1 VDC @ <500 mA

Control Resistance 220 ohms 220 ohms 220 ohms

Logic Supply Voltage 5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC

Logic Supply Current 50 mA maximum 50 mA maximum 50 mA maximum

Module Ratings

Number of Channels Per Module 4 4 4

Turn-on Time 1/2 cycle maximum 1/2 cycle maximum 1/2 cycle maximum
(zero volts crossover) (zero volts crossover) (Zero Volts Crossover)

Turn-off Time 1/2 cycle maximum 1/2 cycle maximum 1/2 cycle maximum
(zero current crossover) (zero current crossover) (zero current crossover)

Isolation 4,000 volts (transient) 4,000 volts (transient) 4,000 volts (transient)
(Field Side to Logic Side)

Temperature 0° to 70°C, operating 0° to 70°C, operating 0° to 70°C, operating


-30° to 85°C, storage -30° to 85°C, storage -30° to 85°C, storage

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 3/21
Form 1144-050721
Specifications
AC Output Modules - Factor y Mutual Approved

SNAP-OAC5-FM SNAP-OAC5-i-FM
AC OUTPUT MODULE

Key Feature Factory Mutual approved Four isolated channels


Factory Mutual approved

Field Side Ratings (each channel)

Line Voltage - Maximum 250 VAC 250 VAC

Line Voltage - Nominal 120/240 VAC 120/240 VAC

Current Rating 3 amps per module 3 amps per module


0°C to 70°C Ambient

One Cycle Surge 80 amps peak (50/60Hz) 80 amps peak (50/60Hz)

Minimum Load Current 20 mA 20 mA

Output Voltage Drop 1.6 volts maximum @ 0.75 amps 1.6 volts maximum @ 0.75 amps

Off-state Leakage at 2.5 mA @ 240 VAC 2.5 mA @ 240 VAC


Nominal Voltage - 60 Hz 1.25 mA @ 120 VAC 1.25 mA @ 120 VAC

Peak Blocking Voltage 500 volts 500 volts

Operating Frequency 25-65 Hz 25-65 Hz

dV/ dt - Off-state 200 volts/msec 200 volts/msec

dV/ dt - Commutating Snubbed for rated 0.5 power factor Snubbed for rated 0.5 power
load factor load

Fuse 250 VAC - 4A 5x20 mm Fast-acting Has four isolated channels. User
(Common to all Channels) Bell Fuse Part No. BEL 5HF4 must provide own fusing.
Opto 22 Part No. SNAP-4A

Channel-to-channel Isolation Not applicable 300 VAC (1500 V transient)

Logic Side Ratings

Pickup Voltage 4 VDC @ 5.5 mA 4 VDC @ 5.5 mA

Dropout Voltage 1 VDC @ <500 mA 1 VDC @ <500 mA

Control Resistance 220 ohms 220 ohms

Logic Supply Voltage 5VDC ± 0.25 VDC 5VDC ± 0.25 VDC

Logic Supply Current 50 mA maximum 50 mA maximum

Module Ratings

Number of Channels per Module 4 4

Turn-on Time 1/2 cycle maximum 1/2 cycle maximum


(zero volts crossover) (zero volts crossover)

Turn-off Time 1/2 cycle maximum 1/2 cycle maximum


(zero current crossover) (zero current crossover)

Isolation 4,000 volts (transient) 4,000 volts (transient)


(Field Side to Logic Side)

Temperature 0° to 70°C, operating 0° to 70°C, operating


-30° to 85°C, storage -30° to 85°C, storage

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 4/21
Form 1144-050721 Part Number Description
SNAP-OAC5 4-channel AC output 12–250 VAC 5 VDC logic
Schematics
4-channel AC output 12–250 VAC 5 VDC logic,
SNAP-OAC5FM
SNAP-OAC5 Output Module Factory Mutual approved

NOTE: See page 16 for FM modification.

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 5/21
Form 1144-050721 Part Number Description

Schematics
4-channel isolated AC output 12–250 VAC,
SNAP-OAC5MA
5 VDC logic, with manual/auto switch
SNAP-OAC5MA Output Module
With Manual/Auto Switches

NOTE: User must provide own fusing.

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 6/21
Form 1144-050721 Part Number Description
4-channel isolated AC output 12–250 VAC,
Schematics SNAP-OAC5-i 5 VDC logic
SNAP-OAC5-i Isolated Output Module SNAP-OAC5-iFM 4-channel isolated AC output 12–250 VAC,
5 VDC logic, Factory Mutual approved

NOTE: See page 16 for FM modification.

NOTE: User must provide own fusing.

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 7/21
Form 1144-050721

Specifications
DC Output Modules

SNAP DIGITAL DC
SNAP-ODC5SRC SNAP-ODC5SNK SNAP-ODC5R SNAP-ODC5R5
SOURCE AND SINK

Key Feature Load sourcing Load sinking Dry contact Dry contact
Normally open Normally closed

Field Side Ratings (each channel)

Line Voltage - Range 5–60 VDC 5–60 VDC 0–100 VDC 0–100 VDC
0–130 VAC* 0–130 VAC*

Line Voltage - Nominal 5–48 VDC 5–48 VDC -- --

Current Rating 3 amps per module 3 amps per module 0.5 amps switching* 0.5 amps switching*
0°C to 70°C Ambient

Surge Current 5 amps peak for 1 second 5 amps peak for 1 second 1.5 amps carry @ 6.6 volts 1.5 amps carry @ 6.6 volts

Minimum Load 20 mA 20 mA 0 mA 0 mA

Output Voltage Drop 1.6 volts maximum @ 0.75 1.6 volts maximum @ 0.75 0 volts 0 volts
amps amps

Off-state Leakage 1 mA @ 60 VDC 1 mA @ 60 VDC 0 mA 0 mA

Peak Blocking Voltage 60 VDC 60 VDC 100 VDC / 130 VAC 100 VDC / 130 VAC

Fuse 250 VAC - 4A 5x20 mm 250 VAC - 4A 5x20 mm Has four isolated channels. Has four isolated channels.
(Common to all Channels) Fast-acting Fast-acting User must provide own User must provide own
Bell Fuse Part No. BEL 5HF4 Bell Fuse Part No. BEL 5HF4 fusing. fusing.
Opto 22 Part No. SNAP-4A Opto 22 Part No. SNAP-4A

Channel-to-channel Isolation Not applicable Not applicable 300 VAC (1500 V transient) 300 VAC (1500 V transient)

Logic Side Ratings

Pickup Voltage 4 V @ 5.5 mA 4 V @ 5.5 mA 4 V @ 5.5 mA 4 V @ 5.5 mA

Dropout Voltage 1 VDC 1 VDC 1 VDC 1 VDC

Control Resistance 220 ohms 220 ohms 220 ohms 220 ohms

Logic Supply Voltage 5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC

Logic Supply Current 50 mA maximum 50 mA maximum 50 mA maximum 50 mA maximum

Module Ratings

Number of Channels Per 4 4 4 4


Module

Turn-on Time 50 µsec 50 µsec 500 µsec 500 µsec

Turn-off Time 100 µsec 100 µsec 500 µsec 500 µsec

Isolation 4,000 volts (transient) 4,000 volts (transient) 1,500 volts (transient) 1,500 volts (transient)
(Field Side to Logic Side)

Temperature 0° to 70°C, operating 0° to 70°C, operating 0° to 70°C, operating 0° to 70°C, operating


-30° to 85°C, storage -30° to 85°C, storage -30° to 85°C, storage -30° to 85°C, storage

* The power rating of the dry contact module must not exceed 10 VA under steady state or momentary in-rush conditions.
For voltages at or below 20 volts, the current limit is 0.5 amps. For voltages above 20 volts, the maximum allowable current is determined by the following
equation: 10 VA = Current maximum. See rating curve on page 13.
Voltage

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 8/21
Form 1144-050721

Specifications
DC Output Modules

SNAP DIGITAL DC
OUTPUT—LOGIC SNAP-ODC5MA SNAP-ODC5-i SNAP-ODC5A-i SNAP-ODC5ASNK
SOURCE AND SINK

iDiagnostic switches
iKey Feature iFour isolated channels iFour isolated channels Load sinking
iFour isolated channels

iFIELD SIDE RATINGS (each channel)

iLine Voltage - Range i5–60 VDC i5–60 VDC i5–200 VDC 5–200 VDC

iLine Voltage - Nominal i5–48 VDC i5–48 VDC i5–200 VDC 5–200 VDC

iCurrent Rating i2 Amps per Module i3 Amps per Module i3 Amps per Module 3 amps per module
i0°C to 70°C Ambient i0.5 Amps per Channel i i

iSurge Current i1.5 Amps peak for 1 isecond i5 Amps peak for 1 second i5 Amps peak for 1 second 5 amps peak for 1 second

iMinimum Load i20 mA i20 mA i20 mA 20 mA

i1.6 V max. @ .75 iAmps 1.6 volts maximum @ 0.75


iOutput Voltage Drop i1.6 V max. @ .75 iAmps i1.6 V max. @ .75 iAmps
amps

iOff-State Leakage i1 mA @ 60 VDC i1 mA @ 60 VDC i1 mA @ 200 VDC 1 mA @ 200 VDC

iPeak Blocking Voltage i60 VDC i60 VDC i200 VDC 200 VDC

250 VAC - 4A 5x20 mm


iHas four isolated channels. iHas four isolated channels. iHas four isolated channels.
iFuse (common to all Fast-acting
iUser must provide own iUser must provide own iUser must provide own
ichannels) Bell Fuse Part No. BEL 5HF4
ifusing. ifusing. ifusing.
Opto 22 Part No. SNAP-4A

iChannel-to-channel i300 VAC i300 VAC i300 VAC


Not applicable
iIsolaton i(1500 V transient) i(1500 V transient) i(1500 V transient)

iLOGIC SIDE RATINGS

iPickup Voltage i4 V @ 5.5 mA i4 V @ 5.5 mA i4 V @ 5.5 mA 4 V @ 5.5 mA

iDropout Voltage i1 VDC i1 VDC i1 VDC i1 VDC

iControl Resistance i220 ohms i220 ohms i220 ohms 220 ohms

iLogic Supply Voltage i5 VDC ± 0.25 VDC i5 VDC ± 0.25 VDC i5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC

iLogic Supply Current i50 mA maximum i50 mA maximum i50 mA maximum i50 mA maximum

iMODULE RATINGS

iNumber of Channels iper


i4 i4 i4 i4
iModule

iTurn On Time i50 µsec i50 µsec i100 µsec i100 µsec

iTurn Off Time i100 µsec i100 µsec i750 µsec i750 µsec

iIsolation
i4,000 Volts (transient) i4,000 Volts (transient) i4,000 Volts (transient) i4,000 Volts (transient)
i(Field Side to Logic Side)

i0°C to 70°C, operating i0°C to 70°C, operating i0°C to 70°C, operating i0°C to 70°C, operating
iTemperature
i-30°C to 85°C, storage i-30°C to 85°C, storage i-30°C to 85°C, storage i-30°C to 85°C, storage

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 9/21
Form 1144-050721

Specifications
DC Output Modules (FM Models)

OUTPUT–LOGIC SNAP-ODC5SRCFM SNAP-ODC5SNKFM SNAP-ODC5RFM SNAP-ODC5R5FM


SOURCE AND SINK

Key Feature Load sourcing Load sinking Dry contact Dry contact
Factory Mutual approved Factory Mutual approved Normally open Normally closed
Factory Mutual approved Factory Mutual approved

Field Side Ratings (each channel)

Line Voltage - Range 5–60 VDC 5–60 VDC 0–100 VDC 0–100 VDC
0–130 VAC* 0–130 VAC*

Line Voltage - Nominal 5–48 VDC 5–48 VDC -- --

Current Rating 3 amps per module 3 amps per module 0.5 amps switching* 0.5 amps switching*
0°C to 70°C Ambient

Surge Current 5 amps peak for 1 second 5 amps peak for 1 second 1.5 amps carry @ 6.6 volts 1.5 amps carry @ 6.6 volts

Minimum Load 20 mA 20 mA 0 mA 0 mA

Output Voltage Drop 1.6 volts max.@ 0.75 amps 1.6 volts max.@ 0.75 amps 0 volts 0 volts

Off-state Leakage 1 mA @ 60 VDC 1 mA @ 60 VDC 0 mA 0 mA

Peak Blocking Voltage 60 VDC 60 VDC 100 VDC / 130 VAC 100 VDC / 130 VAC

Fuse 250 VAC - 4A 5x20 mm 250 VAC - 4A 5x20 mm Has four isolated channels. Has four isolated channels.
(Common to all Channels) Fast-acting Fast-acting User must provide own User must provide own
Bell Fuse Part No. BEL 5HF4 Bell Fuse Part No. BEL 5HF4 fusing. fusing.
Opto 22 Part No. SNAP-4A Opto 22 Part No. SNAP-4A

Channel-to-channel Isolation Not applicable Not applicable 300 VAC (1500 V transient) 300 VAC (1500 V transient)

Logic Side Ratings

Pickup Voltage 4 V @ 5.5 mA 4 V @ 5.5 mA 4 V @ 5.5 mA 4 V @ 5.5 mA

Dropout Voltage 1 VDC 1 VDC 1 VDC 1 VDC

Control Resistance 220 ohms 220 ohms 220 ohms 220 ohms

Logic Supply Voltage 5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC

Logic Supply Current 50 mA maximum 50 mA maximum 50 mA maximum 50 mA maximum

Module Ratings

Number of Channels Per 4 4 4 4


Module

Turn-on Time 50 µsec 50 µsec 500 µsec 500 µsec

Turn-off Time 100 µsec 100 µsec 500 µsec 500 µsec

Isolation 4,000 volts (transient) 4,000 volts (transient) 1,500 volts (transient) 1,500 volts (transient)
(Field Side to Logic Side)

Temperature 0° to 70°C, operating 0° to 70°C, operating 0° to 70°C, operating 0° to 70°C, operating


-30° to 85°C, storage -30° to 85°C, storage -30° to 85°C, storage -30° to 85°C, storage

* The power rating of the dry contact module must not exceed 10 VA under steady state or momentary in-rush conditions.
For voltages at or below 20 volts, the current limit is 0.5 amps. For voltages above 20 volts, the maximum allowable current is determined by the following
equation: 10 VA = Current maximum. See rating curve on page 13.
Voltage

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 10/21
Form 1144-050721

Specifications
DC Output Modules (FM Models)

SNAP DIGITAL DC
SNAP-ODC5-iFM SNAP-ODC5A-iFM
SOURCE AND SINK

Key Feature Four isolated channels Four isolated channels


Factory Mutual approved Factory Mutual approved

Field Side Ratings (each channel)

Line Voltage - Range 5–60 VDC 5–200 VDC

Line Voltage - Nominal 5–48 VDC 5–200 VDC

Current Rating 3 amps per module 3 amps per module


0°C to 70°C Ambient

Surge Current 5 amps peak for 1 second 5 amps peak for 1 second

Minimum Load 20 mA 20 mA

Output Voltage Drop 1.6 volts max.@ 0.75 amps 1.6 volts max.@ 0.75 amps

Off-state Leakage 1 mA @ 60 VDC 1 mA @ 200 VDC

Peak Blocking Voltage 60 VDC 200 VDC

Fuse Has four isolated channels. User Has four isolated channels. User
(Common to all Channels) must provide own fusing. must provide own fusing.

Channel-to-channel Isolation 300 VAC (1500 V transient) 300 VAC (1500 V transient)

Logic Side Ratings

Pickup Voltage 4 V @ 5.5 mA 4 V @ 5.5 mA

Dropout Voltage 1 VDC 1 VDC

Control Resistance 220 ohms 220 ohms

Logic Supply Voltage 5 VDC ± 0.25 VDC 5 VDC ± 0.25 VDC

Logic Supply Current 50 mA maximum 50 mA maximum

Module Ratings

Number of Channels Per 4 4


Module

Turn-on Time 50 µsec 100 µsec

Turn-off Time 100 µsec 750 µsec

Isolation 4,000 volts (transient) 4,000 volts (transient)


(Field Side to Logic Side)

Temperature 0° to 70°C, operating 0° to 70°C, operating


-30° to 85°C, storage -30° to 85°C, storage

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 11/21
Form 1144-050721 Part Number Description

Schematics SNAP-ODC5SRC 4-channel DC output 5–60 VDC logic


source
SNAP-ODC5SRC 4-channel DC output 5–60 VDC logic
SNAP-ODC5SRCFM source, Factory Mutual approved
Output Module - Sourcing

NOTE: See page 16 for FM modification.

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 12/21
Form 1144-050721 Part Number Description
4-channel DC output 5–60
Schematics SNAP-ODC5SNK
VDC logic sink
SNAP-ODC5SNK and SNAP-ODC5ASNK 4-channel DC output 5–60
Output Module - Sinking SNAP-ODC5SNKFM VDC logic sink, Factory
Mutual approved

SNAP-ODC5ASNK 4-channel DC output 5–200


VDC logic sink

NOTE: See page 16 for FM modification.

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 13/21
Form 1144-050721 Part Number Description
4-channel dry dontact output,
Schematics
SNAP-ODC5R
normally open
4-channel dry contact output,
SNAP-ODC5R Dr y Contact Module SNAP-ODC5R5
normally closed
4-channel dry contact output,
SNAP-ODC5RFM
normally open, Factory Mutual approved
4-channel dry contact output,
SNAP-ODC5R5FM
normally closed, Factory Mutual approved

NOTE: See page 16 for FM modification.

10 VA RATING FOR REED RELAY (DRY CONTACT) MODULES

600
Current Limit
at Key Voltages
500
V mA
5 500
(mA)
Current (mA)

400
Allowable Current

12 500
24 416
MaximumAllowable

300
1
100 100
Maximum

200 120 83
2
130 76
100
Note 1: Maximum DC voltage is 100 VDC.
Note 2: Maximum AC voltage is 130 VAC.
0
0 10 20 30 40 50 60 70 80 90 100 110 120 130
Field Voltage (AC or DC)

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 14/21
Form 1144-050721 Part Number Description
4-channel isolated DC output 5–60 VDC,
Schematics SNAP-ODC5MA
5 VDC logic, with manual/auto switch
SNAP-ODC5MA Output Module With Manual/Auto Switches

NOTE: User must provide own fusing.

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 15/21
Form 1144-050721 Part Number Description
4-channel isolated DC output 5–60 VDC,
Schematics
SNAP-ODC5-i 5 VDC logic
4-channel isolated DC output 5–200 VDC,
SNAP-ODC5-i and SNAP-ODC5A-i SNAP-ODC5A-i 5 VDC logic
Isolated Output Module SNAP-ODC5-iFM 4-channel isolated DC output 5–60 VDC,
5 VDC logic, Factory Mutual approved
4-channel isolated DC output 5–200 VDC,
SNAP-ODC5A-iFM 5 VDC logic, Factory Mutual approved
NOTE: See page 16 for FM modification.

NOTE: User must provide own fusing.

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 16/21
Form 1144-050721

Factory Mutual Modification


All modules with part numbers ending in FM are Factory Mutual approved with the installation of the FM Module Clamp, as
shown below.

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 17/21
Form 1144-050721

Dimensional Drawing
All Models Except MA

Top View of Module

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 18/21
Form 1144-050721

Dimensional Drawing
All MA Models

Top View of MA Module

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 19/21
Form 1144-050721

Dimensional Drawing
All Models

Bottom View of Module Base

IMPORTANT: The mounting rack connector has 24 pins;


the module connector has 20 pins. The extra pins on
the mounting rack connector prevent misalignment
of the module during installation.

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
I/O MODULES
SNAP
DIGITAL OUTPUT MODULES
DATA SHEET page 20/21
Form 1144-050721

Dimensional Drawing
All Models

SNAP Digital Module Mounted on SNAP Rack

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
© 1999–2004 Opto 22. All rights reserved. All trademarks, trade names, logos, and service marks referenced herein belong to their respective companies.
LATEST PRODUCTS
PRODUCT SUPPORT
COMPANY INFORMATION I/O MODULES
SNAP
Products DIGITAL
Opto 22 Software OUTPUT MODULES
DATA
Opto 22 produces aSHEET
broad array of reliable, flexible hardware and Opto 22’s ioProject and FactoryFloor ® page 21/21
software
Formproducts for industrial automation, remote monitoring,
1144-050721 software suites provide full-featured and cost-
enterprise data acquisition, and machine-to-machine (M2M) effective control, HMI, and OPC software to power
applications. your Opto 22 hardware. These software
applications help you develop control automation
SNAP Ethernet Systems solutions, build easy-to-use operator interfaces,
Based on the Internet Protocol (IP), SNAP Ethernet systems offer and expand your manufacturing systems’ connectivity.
flexibility in their network connectivity and in the software applications
they work with. The physical network may be a wired Ethernet network, Quality
a cellular wireless network, or a modem. A wide variety of software In delivering hardware and software solutions for worldwide device
applications can exchange data with SNAP Ethernet systems, including: management and control, Opto 22 retains the highest commitment to
• Opto 22’s own ioProject™ suite of control and HMI software quality. We do no statistical testing; each product is made in the U.S.A.
• Manufacturing resource planning (MRP), enterprise and is tested twice before leaving our 160,000 sq.ft. manufacturing
management, and other enterprise systems facility in Temecula, California. That’s why we can guarantee solid-
• Human-machine interfaces (HMIs) state relays and optically-isolated I/O modules for life.
• Databases
• Email systems Product Support
• OPC client software Opto 22’s Product Support Group offers comprehensive technical
• Custom applications support for Opto 22 products. The staff of support engineers represents
• Modbus/TCP software and hardware. years of training and experience, and can assist with a variety of project
SNAP Ethernet system hardware consists of controllers and I/O units. implementation questions. Product support is available in English and
Controllers provide central control and data distribution. I/O units provide Spanish from Monday through Friday, 7 a.m. to 5 p.m. PST.
local connection to sensors and equipment.
Opto 22 Web Sites
SNAP OEM Systems • www.opto22.com
Opto 22 SNAP OEM I/O systems are highly configurable, pro- • nvio.opto22.com
grammable processors intended for OEMs, IT professionals, and others • www.internetio.com (live Internet I/O demo)
who need to use custom software with Opto 22 SNAP
I/O modules. Other Resources
Linux® applications running on these systems can • OptoInfo CDs
read and write to analog, simple digital, and serial • Custom integration and development
I/O points on SNAP I/O modules using easily • Hands-on customer training classes.
implemented file-based operations. Applications can
be developed using several common development tools About Opto 22
and environments, including C or C++, Java, and shell Opto 22 manufactures and develops hardware and software products
scripts. for industrial automation, remote monitoring, enterprise data acquisition,
and machine-to-machine (M2M) applications. Using standard,
M2M Systems commercially available Internet, networking, and computer technologies,
Machine-to-machine (M2M) systems connect your business computer Opto 22’s input/output and control systems allow customers to monitor,
systems to the machines, devices, and environments you want to monitor, control, and acquire data from all of the mechanical, electrical, and electronic
control, or collect data from. M2M systems often use wireless cellular assets that are key to their business operations. Opto 22’s products and
communications to link remote facilities to central systems over the Internet, services support automation end users, OEMs, and information technology
or to provide monitoring and control capability via a cellular phone. and operations personnel.
Opto 22’s Nvio™ systems include everything you need for M2M— Founded in 1974 and with over 85 million Opto 22-connected devices
interface and communications hardware, data service plan, and Web deployed worldwide, the company has an established reputation for quality
portal—in one easy-to-use package. Visit nvio.opto22.com for more and reliability.
information.

Opto
Opto 22
22••43044
43044Business
BusinessPark
ParkDrive
Drive••Temecula,
Temecula,CA
CA92590-3614
92590-3614••Phone:
Phone:(951)
(951)695-3000
695-3000••(800)
(800)321-OPTO
321-OPTO••Fax:
Fax:(951)
(951)695-3095
695-3095••www.opto22.com
www.opto22.com
Inside Sales:
Inside
(800)Sales:
321-OPTO
(800) 321-OPTO
• Product Support:
• Product(800)
Support:
TEK-OPTO
(800) TEK-OPTO
• (951) 695-3080
• (951)• 695-3080
Fax: (951)• 695-3017
Fax: (951)• 695-3017
Email: sales@opto22.com
• Email: sales@opto22.com
• Form 1335-050601
© 2004-2005 Opto 22. All rights reserved. All trademarks, trade names, logos, and service marks referenced herein belong to their respective companies.

You might also like