You are on page 1of 8

10100 W.

Linne Road
Tracy, CA 95377
Telephone: (209)666-8958

DESIGN CALCULATIONS FOR:

30” and 36” DIAMETER CONCRETE PRESSURE


PIPE, BAR-WRAPPED, STEEL CYLINDER
TYPE AWWA C303-17
OUTLET REINFORCEMENT CALCULATIONS

PROJECT:
Caltrans Contract No. 03-4E62U2
El Dorado Irrigation District

CONTRACTOR: Security Paving Company Inc

Sept 04-2020

Page 1
Outlet Reinforcement Design Calculation
Per AWWA Manual M9 - Chapter 8
36" MAINLINE WITH 36" RADIAL BRANCH

Project: Caltrans Contract No. 03-4E62U4

Mainline Pipe
Nominal diameter: 36 in
Cylinder outside diameter: 37.875 in D yo
Cylinder thickness: 0.375 in ty

Branch Pipe
Nominal diameter: 36 in
Cylinder outside diameter: 37.875 in d yo
Cylinder Thickness: 0.375 in Ty
Branch type: Radial
Deflection angle: 90 degrees 

Design pressure: 133 psi Pw


Allowable steel stress: 16500 psi fs

Pressure Diameter Value 5037 PDV


1.000 d/D

Reinforcment type: Not required

Multiplier Factor: 1.259 M-factor


Required mainline cylinder thickness: 0.150 in tr
Required branch cylinder thickness: 0.150 in Tr
Required area of outlet reinforcment: 6.995 in² Ar
Excess steel area in main cylinder: 8.705 in² A1
Excess steel area in branch wall: 0.423 in² A2
Area available: 9.128 in² A 1 +A 2
Additional area required: -2.132 in² Aw
Minimum reinforcment thickness: -0.056 in T(min)
Minimum allowable width: 12.625 in w (min)
Width to use: 12.625 in w (use)
Maximum allowable width: 18.938 in w (max)

OUTLET SELF REINFORCED

9/3/2020 Page 1 of 1
W:\ENG\Job Folders\TR-20-065 CALTRANS CONTRACT No 03-4E62U4\Calculations\36 x 36 tee M9 outlet reinforcing design
Outlet Reinforcement Design Calculation
Per AWWA Manual M9 - Chapter 8
36" MAINLINE WITH 12" RADIAL BRANCH

Project: Caltrans Contract No. 03-4E62U4

Mainline Pipe
Nominal diameter: 36 in
Cylinder outside diameter: 37.875 in D yo
Cylinder thickness: 0.188 in ty

Branch Pipe
Nominal diameter: 12 in
Cylinder outside diameter: 12.75 in d yo
Cylinder Thickness: 0.375 in Ty
Branch type: Radial
Deflection angle: 90 degrees 

Design pressure: 133 psi Pw


Allowable steel stress: 16500 psi fs

Pressure Diameter Value 571 PDV


0.337 d/D

Reinforcment type: Collar

Multiplier Factor: 1.000 M-factor


Required mainline cylinder thickness: 0.151 in tr
Required branch cylinder thickness: 0.048 in Tr
Required area of outlet reinforcment: 1.814 in² Ar
Excess steel area in main cylinder: 0.498 in² A1
Excess steel area in branch wall: 0.612 in² A2
Area available: 1.110 in² A 1 +A 2
Additional area required: 0.703 in² Aw
Minimum reinforcment thickness: 0.055 in T(min)
Minimum allowable width: 4.250 in w (min)
Width to use: 4.250 in w (use)
Maximum allowable width: 6.375 in w (max)

3/16" THICK BY 21.50" WIDE BY 22.00" LONG COLLAR


Note: Required width/length dimensions rounded up to the nearest 1/2"

9/4/2020 Page 1 of 1
W:\ENG\Job Folders\TR-20-065 CALTRANS CONTRACT No 03-4E62U4\Calculations\12in OT on 36in Pipe
Outlet Reinforcement Design Calculation
Per AWWA Manual M9 - Chapter 8
36" MAINLINE WITH 4" RADIAL BRANCH

Project: Caltrans Contract No. 03-4E62U4

Mainline Pipe
Nominal diameter: 36 in
Cylinder outside diameter: 37.875 in D yo
Cylinder thickness: 0.188 in ty

Branch Pipe
Nominal diameter: 4 in
Cylinder outside diameter: 4.5 in d yo
Cylinder Thickness: 0.237 in Ty
Branch type: Radial
Deflection angle: 90 degrees 

Design pressure: 133 psi Pw


Allowable steel stress: 16500 psi fs

Pressure Diameter Value 71 PDV


0.119 d/D

Reinforcment type: Collar

Multiplier Factor: 1.000 M-factor


Required mainline cylinder thickness: 0.151 in tr
Required branch cylinder thickness: 0.016 in Tr
Required area of outlet reinforcment: 0.608 in² Ar
Excess steel area in main cylinder: 0.183 in² A1
Excess steel area in branch wall: 0.262 in² A2
Area available: 0.445 in² A 1 +A 2
Additional area required: 0.163 in² Aw
Minimum reinforcment thickness: 0.036 in T(min)
Minimum allowable width: 1.500 in w (min)
Width to use: 1.500 in w (use)
Maximum allowable width: 2.250 in w (max)

3/16" THICK BY 7.50" WIDE BY 8.00" LONG COLLAR


Note: Required width/length dimensions rounded up to the nearest 1/2"

9/3/2020 Page 1 of 1
W:\ENG\Job Folders\TR-20-065 CALTRANS CONTRACT No 03-4E62U4\Calculations\4in OT on 36in Pipe
Outlet Reinforcement Design Calculation
Per AWWA Manual M9 - Chapter 8
36" MAINLINE WITH 4" TANGENT BRANCH

Project: Caltrans Contract No. 03-4E62U4

Mainline Pipe
Nominal diameter: 36 in
Cylinder outside diameter: 37.875 in D yo
Cylinder thickness: 0.188 in ty

Branch Pipe
Nominal diameter: 4 in
Cylinder outside diameter: 4.5 in d yo
Cylinder Thickness: 0.237 in Ty
Branch type: Tangent
Deflection angle: 90 degrees 

Design pressure: 133 psi Pw


Allowable steel stress: 16500 psi fs

Pressure Diameter Value 71 PDV


0.119 d/D

Reinforcment type: Collar

Multiplier Factor: 1.000 M-factor


Required mainline cylinder thickness: 0.151 in tr
Required branch cylinder thickness: 0.016 in Tr
Required area of outlet reinforcment: 0.608 in² Ar
Excess steel area in main cylinder: 0.183 in² A1
Excess steel area in branch wall: 0.262 in² A2
Area available: 0.445 in² A 1 +A 2
Additional area required: 0.163 in² Aw
Minimum reinforcment thickness: 0.036 in T(min)
Minimum allowable width: 1.500 in w (min)
Width to use: 1.500 in w (use)
Maximum allowable width: 2.250 in w (max)

3/16" THICK BY 7.50" WIDE BY 16.50" LONG COLLAR


Note: Required width/length dimensions rounded up to the nearest 1/2"

9/3/2020 Page 1 of 1
W:\ENG\Job Folders\TR-20-065 CALTRANS CONTRACT No 03-4E62U4\Calculations\4in BO on 36in Pipe
Outlet Reinforcement Design Calculation
Per AWWA Manual M9 - Chapter 8
30" MAINLINE WITH 30" RADIAL BRANCH

Project: Caltrans Contract No. 03-4E62U4

Mainline Pipe
Nominal diameter: 30 in
Cylinder outside diameter: 31.875 in D yo
Cylinder thickness: 0.375 in ty

Branch Pipe
Nominal diameter: 30 in
Cylinder outside diameter: 31.875 in d yo
Cylinder Thickness: 0.375 in Ty
Branch type: Radial
Deflection angle: 90 degrees 

Design pressure: 133 psi Pw


Allowable steel stress: 16500 psi fs

Pressure Diameter Value 4239 PDV


1.000 d/D

Reinforcment type: Not required

Multiplier Factor: 1.060 M-factor


Required mainline cylinder thickness: 0.125 in tr
Required branch cylinder thickness: 0.125 in Tr
Required area of outlet reinforcment: 4.138 in² Ar
Excess steel area in main cylinder: 8.142 in² A1
Excess steel area in branch wall: 0.468 in² A2
Area available: 8.610 in² A 1 +A 2
Additional area required: -4.472 in² Aw
Minimum reinforcment thickness: -0.140 in T(min)
Minimum allowable width: 10.625 in w (min)
Width to use: 10.625 in w (use)
Maximum allowable width: 15.938 in w (max)

OUTLET SELF REINFORCED

9/3/2020 Page 1 of 1
W:\ENG\Job Folders\TR-20-065 CALTRANS CONTRACT No 03-4E62U4\Calculations\30 x 30 tee M9 outlet reinforcing design
Outlet Reinforcement Design Calculation
Per AWWA Manual M9 - Chapter 8
30" MAINLINE WITH 4" TANGENT BRANCH

Project: Caltrans Contract No. 03-4E62U4

Mainline Pipe
Nominal diameter: 30 in
Cylinder outside diameter: 31.875 in D yo
Cylinder thickness: 0.188 in ty

Branch Pipe
Nominal diameter: 4 in
Cylinder outside diameter: 4.5 in d yo
Cylinder Thickness: 0.237 in Ty
Branch type: Tangent
Deflection angle: 90 degrees D

Design pressure: 133 psi Pw


Allowable steel stress: 16500 psi fs

Pressure Diameter Value 84 PDV


0.141 d/D

Reinforcment type: Not required

Multiplier Factor: 1.000 M-factor


Required mainline cylinder thickness: 0.127 in tr
Required branch cylinder thickness: 0.016 in Tr
Required area of outlet reinforcment: 0.511 in² Ar
Excess steel area in main cylinder: 0.304 in² A1
Excess steel area in branch wall: 0.262 in² A2
Area available: 0.565 in² A 1 +A 2
Additional area required: -0.054 in² Aw
Minimum reinforcment thickness: -0.012 in T(min)
Minimum allowable width: 1.500 in w (min)
Width to use: 1.500 in w (use)
Maximum allowable width: 2.250 in w (max)

OUTLET SELF REINFORCED

9/3/2020 Page 1 of 1
W:\ENG\Job Folders\TR-20-065 CALTRANS CONTRACT No 03-4E62U4\Calculations\4in BO on 30in Pipe
Outlet Reinforcement Design Calculation
Per AWWA Manual M9 - Chapter 8
30" MAINLINE WITH 4" RADIAL BRANCH

Project: Caltrans Contract No. 03-4E62U4

Mainline Pipe
Nominal diameter: 30 in
Cylinder outside diameter: 31.875 in D yo
Cylinder thickness: 0.188 in ty

Branch Pipe
Nominal diameter: 4 in
Cylinder outside diameter: 4.5 in d yo
Cylinder Thickness: 0.237 in Ty
Branch type: Radial
Deflection angle: 90 degrees 

Design pressure: 133 psi Pw


Allowable steel stress: 16500 psi fs

Pressure Diameter Value 84 PDV


0.141 d/D

Reinforcment type: Not required

Multiplier Factor: 1.000 M-factor


Required mainline cylinder thickness: 0.127 in tr
Required branch cylinder thickness: 0.016 in Tr
Required area of outlet reinforcment: 0.511 in² Ar
Excess steel area in main cylinder: 0.304 in² A1
Excess steel area in branch wall: 0.262 in² A2
Area available: 0.565 in² A 1 +A 2
Additional area required: -0.054 in² Aw
Minimum reinforcment thickness: -0.012 in T(min)
Minimum allowable width: 1.500 in w (min)
Width to use: 1.500 in w (use)
Maximum allowable width: 2.250 in w (max)

OUTLET SELF REINFORCED

9/4/2020 Page 1 of 1
W:\ENG\Job Folders\TR-20-065 CALTRANS CONTRACT No 03-4E62U4\Calculations\4in OT on 30in Pipe