You are on page 1of 42

Safe power distribution,

intelligent data and process


management
Totally Integrated Power – ­
SIVACON S8 low-voltage switchboard

siemens.com/sivacon-S8
Contents
Totally Integrated Power 2 Application examples 18
SIVACON S8 low-voltage switchboard – 3 Frame, enclosure, and busbars 20
safe and intelligent power distribution
Circuit-breaker design 22
System overview 4
Universal mounting design 24
SIVACON S8 – standard-compliant, 10
Fixed-mounted design with front covers 28
design verified low-voltage switchboard
In-line design, plug-in 30
Solutions for high seismic requirements 11
and vibrations In-line design, fixed-mounted 32

Safety as an integral part – 12 Reactive power compensation 34


arc resistance Support 36
SIMARIS control – solution for uniform operation 14 Technical data 38
and monitoring
Project checklist 40
Connection to energy management, 16
control, or automation systems with SIVACON S8

Totally Integrated Power


Industries, buildings, and facilities all depend on electrical
power. To ensure that power makes its way in a reliable,
safe, and efficient manner  in increasingly complex distribu-
tion environments, automation and digitalisation need
to work hand-in-hand. Totally Integrated Power (TIP) is
Siemens’ unique approach portfolio for all power supply
applications in every voltage level that enables accurate
and individual solutions that meet these demands –
for any industry. TIP offers specifically customised solutions
for the automotive, chemical, construction, oil and gas,
and mining industries as well as data centers, harbors, and
buildings of all sizes. Of course Siemens has the right
TIP solution that fits to the specific demands for other
markets, too.

SIVACON S8 – Intelligent power distribution for TIP


SIVACON S8 sets standards as a power distribution board or design, offers a wide range of possible uses. Thanks to the
Motor Control Center (MCC) for industrial applications or in modular design, the switchboard can be optimally adapted
the infrastructure. The switchboard system for the simple to every requirement when designing the complete system.
and consistent distribution of power allows a high level of Combining a high level of safety with a modern design and
personnel and switchboard safety and, due to its optimal the SIMARIS control HMI, the switchboard provides an
efficient solution.

2
­ IVACON S8 low-voltage switchboard –
S
safe and intelligent power distribution

Tested safety
SIVACON S8 stands for safety at a high level. The low-voltage
switchboard is a design verified power switchgear and
controlgear assembly; the design is verified by tests accord-
ing to IEC 61439-2. Its physical properties have been verified
at the testing laboratory for both operation and failure
situations. Personnel safety is furthermore ensured by
verification of the test under conditions of arcing in accord-
ance with IEC/TR 61641.

Flexible solutions
SIVACON S8 offers intelligent solutions which can be
adapted to match your requirements. Different mounting
designs can be combined in one cubicle with ease. The
flexible modules allow for the simple exchange or addition
of functional units. The SIVACON S8 modules undergo
a continuous innovation process, thereby ensuring the
technical progress for the overall system.
Your benefits at a glance
Intelligent switchboard
• High level of safety for personnel and switchboard by Using the SIMARIS control visualisation application, all
means of design verification according to IEC 61439-2 communication-capable switching devices of the SIVACON S8
• Personnel and switchboard safety in case of internal low-voltage switchboard can be operated and monitored
arcing proven by means of testing according to IEC/TR uniformly. Status information and measured values of
61641
devices are displayed comprehensively and clearly.
• High flexibility due to innovative modular design Detailed warnings and error messages enable simple and
• Integration in energy management solutions via fast diagnostics of the cause of the fault. The data can be
communication-capable switching and measuring connected with higher level automation or energy manage-
devices
ment systems. This provides a high level of switchboard
• Clear display of extensive measured values, status, availability and transparency of the power flows.
and diagnostics information
• Preventive maintenance supported by diagnostics
information
• Consistently design verified connection to SIVACON 8PS
busbar trunking systems

3
SIVACON S8 –
system overview
Cubicle design

Circuit-breaker design Universal mounting design Fixed-mounted


design
Mounting design • Fixed-mounted design • Withdrawable design • Fixed-mounted
• Withdrawable design • Fixed-mounted design with design with
compartment doors front covers
• Plug-in design

Functions • Incoming feeder • Cable feeders • Cable feeders


• Outgoing feeder • Motor feeders (MCC)
• Bus coupler

Rated values • up to 6,300 A • up to 630 A • up to 630 A


• up to 250 kW

Type of connection front or rear front or rear front

Cubicle width (mm) 400, 600, 800, 1,000, 1,400 600, 1,000, 1,200 1,000, 1,200

Internal separation Form 1, 2b, 3a, 4b, Form 3b, 4a, 4b, Form 1, 2b, 3b, 4a, 4b
4 type 7 (BS) 4 type 7 (BS)

Busbar position top, rear top, rear top, rear

Human-Machine Interface (HMI) SIMARIS control (option) SIMARIS control (option) SIMARIS control
(option)

4
In-line design, In-line design, Reactive power compensation
plug-in fixed-mounted
• Plug-in design • Fixed-mounted • Fixed-mounted design
design

• Cable feeders • Cable feeders • Central compensation


of reactive power

• up to 630 A • up to 630 A • unchoked up to 600 kvar


• choked up to 500 kvar

front front front

1,000, 1,200 600, 800, 1,000 800

Form 3b, 4b Form 1, 2b Form 1, 2b

top, rear rear without, top, rear

SIMARIS control (option) – –

5
Highlights

Tested safety

Design verification by means of Lockable disconnected position


tests according to IEC 61439-2, for safe commissioning and
arc resistance by means of tests maintenance
according to IEC 61641, earth-
quake upgrade, certification
for application on ships and
offshore platforms according to
DNV and GL

Arc-resistant distribution busbar Patented low-wear with-


embedding drawable unit contact system
for long service life

Shutter with double-action for Mechanical coding of


normal and small withdrawable withdrawable units and
units compartments with up to
9,216 possibilities

Operating-error-proof and Consistently design verified


uniform operating concept connection to SIVACON 8PS
throughout all sizes of busbar trunking systems
withdrawable units

6
SIVACON S8 –
system overview
Cubicle design

Circuit-breaker design Universal mounting design Fixed-mounted


design
Mounting design • Fixed-mounted design • Withdrawable design • Fixed-mounted
• Withdrawable design • Fixed-mounted design with design with
compartment doors front covers
• Plug-in design

Functions • Incoming feeder • Cable feeders • Cable feeders


• Outgoing feeder • Motor feeders (MCC)
• Bus coupler

Rated values • up to 6,300 A • up to 630 A • up to 630 A


• up to 250 kW

Type of connection front or rear front or rear front

Cubicle width (mm) 400, 600, 800, 1,000, 1,400 600, 1,000, 1,200 1,000, 1,200

Internal separation Form 1, 2b, 3a, 4b, Form 3b, 4a, 4b, Form 1, 2b, 3b, 4a, 4b
4 type 7 (BS) 4 type 7 (BS)

Busbar position top, rear top, rear top, rear

Human-Machine Interface (HMI) SIMARIS control (option) SIMARIS control (option) SIMARIS control
(option)

7
In-line design, In-line design, Reactive power compensation
plug-in fixed-mounted
• Plug-in design • Fixed-mounted • Fixed-mounted design
design

• Cable feeders • Cable feeders • Central compensation


of reactive power

• up to 630 A • up to 630 A • unchoked up to 600 kvar


• choked up to 500 kvar

front front front

1,000, 1,200 600, 800, 1,000 800

Form 3b, 4b Form 1, 2b Form 1, 2b

top, rear rear without, top, rear

SIMARIS control (option) – –

8
Highlights

Flexible solutions

Variable busbar positions Normal withdrawable units


(top, rear) with rated current up to 630 A and small with-
up to 7,000 A drawable units up to 63 A

Installation of two independent High packing density with up


main busbar runs possible in one to 48 feeders in withdrawable
switchboard (up to 4,000 A) design in one outgoing feeder
cubicle

Innovative mounting design Innovative locking system


with multiple designs allows
• Combination of different
to change the door hinge at
mounting designs (fixed-
any time
mounted feeders, plug-in
design, withdrawable design)
• Easy exchange or addition
of functional units

Two standard heights and two base heights permit


optimum adaptation to structural conditions

Intelligent switchboard

SIMARIS control – solution for Integration in energy


uniform operation and monitor- management solutions via
ing of intelligent switchboards, communication-capable
as well as possible connection to switching and measuring
a higher-level control system devices, communication
connection

9
Your benefit

• Safety for personnel and switchboard thanks


to design verification with tests according to
IEC 61439-2
• Quality assurance through design verifications and
routine verifications
• Systematic tests always carried out with devices

SIVACON S8: Safe power supply with design verification

SIVACON S8 –
standard-compliant, design verified
low-voltage switchboard
Low-voltage switchboards are developed, manufactured, and tested following
the specifications of IEC 61439-2 for power switchgear and controlgear assemblies.

Requirement of the IEC 61439-2 standard Design verification with tests


In order to provide evidence that the switchboard is fit The SIVACON S8 switchboard offers safety for personnel
for purpose, this standard requires two main forms of and switchboard by means of design verification with tests
verification – design verifications and routine verifications. according to IEC 61439-2.
Design verifications are tests carried out during the devel-
The physical properties are dimensioned and verified at the
opment process and are the responsibility of the original
testing laboratory for both operation and failure situations.
manufacturer (developer). Routine verifications must be
Design verifications as well as routine verifications are
performed by the manufacturer of the power switchgear
a decisive part of quality assurance, and the prerequisite
and controlgear assembly on every manufactured switch-
for CE marking according to the EC guidelines and laws.
board prior to delivery.

10
Solution for high seismic
requirements and vibrations

Your benefit

• Safety for personnel and


switchboard by means of tests
according to IEC 61439-2
• Safe power supply with
earthquake-tested version
SIVACON S8 switchboards offer a safe solution even for for seismic requirements
regions at risk from earthquakes, or areas of application with • Certifications for application
high mechanical stress, e.g. due to large (ship) drives. on ships and offshore
platforms

Earthquake upgrade Certifications for application


In the earthquake-tested version, on ships and offshore platforms
SIVACON S8 is available for seismic The conditions of application on the
requirements. During the test, the high seas are a special challenge for
functionality and stability after and switchboards: Besides the saline
during the earthquake are checked. atmosphere with a high air humidity,
this is particularly due to enhanced
The results of the seismic tests are
mechanical stress. SIVACON S8 switch-
divided into three categories:
boards are perfectly set to meet these
1: Functionality challenges. For application on ships
during the earthquake and offshore platforms, SIVACON S8
was given the necessary certifications
2: Functionality
from renowned international classifi-
after the earthquake
cation societies under hand and seal.
3: Stability Safe power supply even under high seismic
requirements

11
Your benefit

• Personnel safety by testing the switchboard under


conditions of arcing
• Switchboard safety by limiting the effects of inter-
nal arcing faults inside the switchboard
• Reliability thanks to extensive systematic check

Tests under conditions of arcing in accordance with IEC/TR 61641

Safety as an integral part –


arc resistance
Besides the reliability of power supply,
a high level of personnel protection plays a central part.

Protection for personnel and switchboard Safety as the primary objective


An arc is one of the most dangerous faults, associated with Preventive protection measures such as the high-quality
the most serious consequences which can occur inside insulation of live parts (for example, busbars), uniform and
a switchboard, and it can also damage adjacent feeders, simple operation, integrated operating error protection,
cubicles, or the entire switchboard. Arcing can be caused by and reliable switchboard dimensions prevent arcing, and
incorrect dimensioning and reductions in insulation due to thus injuries of personnel.
pollution, etc., but it can also be the result of handling
errors.
The effects, resulting from high pressure and extremely
high temperatures, can have fatal consequences for the
operator, the switchboard, and even the building. Testing
of low-voltage switchboards under conditions of arcing is
a special test in accordance with IEC/TR 61641. SIVACON S8
offers the verification of personnel safety by testing under
conditions of arcing. Furthermore, SIVACON S8 has passed
the more severe test according to AS/NZS 3439.1
(Australian / New Zealand standard).

12
The arc barrier restricts the effects to one cubicle Insulated main busbars prevent the occurrence
in case of arcing. of arcing.

In addition, SIVACON S8 can be equipped with an arc Arc protection levels


detection system and a quenching device. For this purpose, For SIVACON S8 with requirements concerning the arc
sensors are installed for optical detection, whose signals resistance, Siemens has developed a level concept.
are assessed in an evaluation unit in combination with a The arc protection levels describe the limitation of the
current detection system. If an internal arc is detected, this effects of an arc on the entire switchboard or parts thereof.
evaluation unit activates a quenching device which extin-
guishes the arc within a few milliseconds. These very short Level 1 Level 2
reaction times prevent damages to the switchboard.
With SIVACON S8, Siemens offers an innovative solution
that can be used several times without replacing compo-
nents. Thus, the switchboard remains fully protected after
an internal arcing event without the need of replacement Personnel safety without exten- Personnel safety with limitation
measures. sive limitation of the arcing fault of the arcing fault effects to one
effects inside the switchboard. cubicle or double-front unit.
Moreover, reactive protective measures limit the effects
of an arc. They include: arc-resistant hinge and locking
Level 3 Level 4
systems, safe operation of withdrawable units or circuit
breakers behind a closed door, and protective measures on
ventilation openings at the front, arc barriers, or an arc
detection system combined with the rapid quenching of
arcs. The functionality of the measures described has been
proven by numerous, comprehensive arcing tests under Personnel safety with limitation Personnel safety with limitation
of the arcing fault effects to the of the arcing fault effects to the
“worst-case” conditions, performed on a wide variety of
main busbar compartment, place of origin.
cubicle types and functional units. to the device compartment,
or to the cable compartment in
one cubicle or double-front unit.

13
Solution for uniform operation and
monitoring of intelligent switchboards

Your benefit

• Central switchboard operating


station for all local communi-
cation-capable switching
devices; remote access possible
• Clear display of all switching As a permanent diagnostics station, SIMARIS control supports
states, extensive measured reliable operation.
values, status and diagnostics
information Modern low-voltage switchboards, The individual devices use different
• Fast diagnostics by means of especially Motor Control Centers, use software tools here.
structured and detailed fault intelligent protection, switching, and
For better local visualisation and control
information control devices almost exclusively.
of the communication-capable switch-
These devices have extensive diagnos-
• Preventive maintenance due ing devices installed, SIMARIS control
tics, status, measuring, statistical, and
to diagnostics information offers an optimum solution.
service data. The use and display of
• Transfer of relevant data this data in the control system for
Clear display,
and display to higher-level process automation comes down to
safe and easy operation
automation system a few items of status information and
With SIMARIS control, all the informa-
individual measured values as well
tion of the communication-capable
as the control function. Signalling and
switching, protection, and measuring
control on the switchboard using
devices used in SIVACON S8 is dis-
indicator lights, pushbuttons, or
played clearly and in a structured,
device-specific operator panels is
requirement-oriented form. The current
extremely limited regarding extent
diagnostics information of the individ-
and clarity. Comprehensive and clear
ual devices is recorded in a centralised
presentation of all device information
message list for the complete
is often only possible with a PC and
switchboard.
the appropriate software.

14
Operation of SIMARIS control is touch-screen-optimised. High level of switchboard availability supported by
Navigation through the switchboard structure is clear preventive maintenance and energy management
and intuitive. With just a few operation steps, extensive With SIMARIS control, operational diagnostics can thus be
feeder-specific detailed information can be displayed from carried out faster, more flexibly, and more simply.
a general overview.
Comprehensive display of all measured values, status
Appropriate authorisations are defined in individual user signals, and statistical data enables a high degree of trans-
groups to avoid operating errors. Users of the “Guest” parency right down to the individual feeder. Statistical data
group, for example, have no switching authorisation and such as switching frequencies, runtimes, etc. support
also cannot make any changes in SIMARIS control. optimisation and planning of maintenance measures.
Sensor data (e.g. for temperatures) can also be displayed
Autonomous software
in the visualisation system for the purpose of monitoring
SIMARIS control is a PC-based software application that is
relevant status information of a switchboard. This helps
integrated into the communication system as a permanent
reduce downtimes and increase switchboard availability.
diagnostics station, independently of a higher-level auto-
Moreover, the power demand of the switchboard can be
mation system. In doing so, SIMARIS control uses the avail-
analysed and optimised using the consumption values of
able switchboard communication system.
the feeders.
The hardware of SIMARIS control can be integrated into
existing IT structures via the integrated LAN interfaces. Technical features
Functions such as remote access/monitoring are thus also • Windows PC / industrial PC system with optimised
possible as an alternative to centralised operation on the operation for touch screen
on-site panel PC of the switchboard. • Interfaces for PROFIBUS, PROFINET, Modbus, Ethernet,
and others
Easy commissioning and flexible operation
• Several operator stations possible
Individual operating parameters like current settings can be
modified without parameterisation software, thus simplify- • Operation possible via web client
ing the commissioning of SIMOCODE motor feeders, for • Structured representation of alarms and faults /
example. Furthermore, SIMARIS control allows changes message list
during runtime. Feeder names and comments can be freely • Integral user group administration with differentiated
modified. Adjustments to the switchboard structure result- authorisations
ing, for example, from moving, adding, or removing feed-
• Configuration changes during operation possible
ers can be carried out in SIMARIS control by users them-
(changes to number and positioning of feeders,
selves.
adaptation of feeder names and descriptions)

1 1 General overview with cubicle arrangement and


group information
2 2 Cubicle overview with feeder information

3 Feeder overview

4 Detailed feeder information


3
(measured values, status signals, statistical data, and much more)
4 5 Central message list

15
Connection to energy management,
control, or automation systems
with SIVACON S8

Switchboards must operate cost-efficiently. Consequently,


Your benefit downtimes must be avoided, and their utilisation must be
constantly optimised. The ISO 50001 standard supports com-
• Simple integration of the panies with a specific process description when an operation-
communication-capable al energy management system is introduced. A standard-
measuring devices and circuit based energy management optimises the use of energy and
breakers increases the energy efficiency constantly.
• Identification of saving
potentials thanks to Consistently well informed They record precise and reliable
transparency of power flows Anybody who wants to reduce energy measurements of the energy values
• Reliable recording and display costs on a long-term basis, firstly for electrical feeders or individual
of consumption data requires a clear overview of power consumer loads. In addition to this,
consumption and power flows. the devices provide you – via standard-
• Improved switchboard The 7KT/7KM PAC measuring devices, ised bus systems – with important
availability through 3WL/3VA circuit breakers or intelligent measured values for the assessment of
continuous monitoring motor management systems such as the switchboard state and the network
SIMOCODE pro, which are integrated quality. Furthermore, high failure
in the switchboard, can help you to safety is supported by redundant
achieve this. communication up to the with-
drawable unit.

16
powermanager –
power monitoring software

7KM PAC4200
measuring device

7KM PAC3200 7KM PAC3100


Communication-capable measuring measuring device measuring device
and switching devices

3VA molded case


circuit breaker
incl. measuring
function

3VA molded case 3NP1 fuse switch


circuit breaker disconnector

Innovative devices of the SENTRON family for The basis of energy management is transparency:
recording and supplying consumption data and Integrated solution for smart power distribution
electrical parameters

Simple evaluation of data The PC-based power monitoring software powermanager


For the further processing of measured data, the devices from Siemens analyses and documents the data from
can be very easily integrated into higher-level automation measuring devices and circuit breakers, and produces load
and energy management systems, thanks to the wide profile curves and trend analyses, extending to the visuali-
variety of communication options they offer. The communi- sation of switching states.
cation-capable measuring devices and circuit breakers
therefore provide the ideal basis for cost-efficient power
monitoring with the SIVACON S8 switchboard.

17
Application examples

Cost-efficient low-voltage power distribution Smart low-voltage power distribution


for the oil & gas industry for data centers

Requirement Requirement
• Safety for personnel and switchboard • High level of safety for personnel
• Reliable power supply • Uninterrupted power supply with minimum failure risk
• Minimisation of failure risk • High reliability of supply for the information and communication
technology (ICT) as well as for infrastructure systems
• Customer-specific, flexible and extendable solutions
• High level of cost-efficiency

Solution Solution
The cubicles in universal mounting design are perfectly suitable for Motor A SIVACON S8 switchboard as a double-fronted switchboard, connected
Control Centers. The withdrawable design combines a high level of through SIVACON 8PS busbar trunking systems with standard connection
personnel and operating safety with flexibility for changing requirements. components in order to reduce the fault rate and effects to a minimum.
Communication-capable devices establish the link to higher-level
The universal mounting design allows to combine various mounting
automation and energy management systems. With SIMARIS control,
designs in one cubicle as a cost-efficient solution for different
a clear visualisation and control of SIVACON S8 is ensured even in
requirements.
complex plants and distribution systems.

Added value / result Added value / result


• Safety for personnel and switchboard by means • Safety for personnel and switchboard by means
of design verification acc. to IEC 61439-2 of design verification acc. to IEC 61439-2
• Personnel and switchboard safety in case of arcing • Personnel and switchboard safety in case of arcing
• Certification by renowned classification societies available for • Cost-efficient, flexible, and modularly extendable
offshore applications and for earthquake-tested design switchboard with space-optimised installation
• Cost-efficient, flexible, and modularly extendable switchboard • Consistent, reliable power distribution with
links to energy management systems
• Consistent, reliable power distribution with links
to automation and energy management

18
Safe and compact low-voltage power distribution Cost-efficient low-voltage power distribution
for high-rise buildings and infrastructure for chemical plants

Requirement Requirement
• High level of safety for personnel • Safety for personnel and switchboard
• Reliable power supply • Reliable and flexible power supply
• High level of cost-efficiency • Minimisation of failure risk
• Minimum maintenance requirements • Customer-specific, flexible, and extendable solutions

Solution Solution
A SIVACON S8 switchboard with design verified connection to SIVACON S8 with design verified connection to SIVACON 8PS busbar
SIVACON 8PS busbar trunking systems ensures safe power transmission trunking systems transports the power from the transformer through the
from the transformer to the main distribution board and up to the floor main distribution board to the production facilities and factory buildings
distribution boards. around the clock in flexible, reliable, and safe manner.
The cubicles in fixed-mounted and in-line design are efficient and Thanks to the withdrawable design, MCC cubicles in universal mounting
economical; the link to the energy management system is established design are safe for people and operation, and flexible. SIMOCODE pro,
through communication-capable devices. among others, provides for the intelligent link between the automation
system and the motor feeder.

Added value / result Added value / result


• Safety for personnel and switchboard by means • Safety for personnel and switchboard by means
of design verification acc. to IEC 61439-2 of design verification acc. to IEC 61439-2
• Personnel and switchboard safety in case of arcing • Personnel and switchboard safety in case of arcing
• Earthquake-tested version available • Earthquake-tested version available
• Cost-efficient, space-saving switchboard • Cost-efficient, flexible, and modularly extendable switchboard
• Modular construction with high level of flexibility and extensibility • Consistent, reliable power distribution with links
to automation and energy management
• Consistent and reliable power distribution

19
Frame, enclosure,
and busbars

Your benefit

• Personnel safety thanks to the


patented door locking system
Variable busbar positions (rear or top)
• Arrangement of busbar
positions suitable for the
application
• High level of flexibility thanks
to variable busbar systems
The SIVACON S8 switchboard offers a perfect combination of
a cost-efficient structure and high quality. The target is clear:
a perfect equipment for all of your demands – versatile, safe,
user-friendly, and easy to operate. The intelligent design of
SIVACON S8 is our answer to these requirements.

Safety with functionality frame components, rear walls, and


Locking system for simple or central locking
The frame and all of the bearing floor plates are sendzimir-galvanised.
components of the cubicle are made Doors, side walls, and covers are
from stable, screw-fastened sheet powder-coated or painted.
steel profiles. Circumferential rows of
holes allow for individual expansion. Systematic flexibility
The patented door locking system with The well thought-out design of the
universal door hinge allows for the switchboard allows it to be integrated
hinge side to be changed with ease. perfectly into a modern room concept.
The doors are available with either The cubicles, either single- or double-
simple or central locking (door locks or fronted, can be installed with a com-
rotary handle systems). The roof plates mon main busbar system (MBB system),
feature pressure relief for additional or back-to-back with separate MBB
safety. Cubicle-to-cubicle separation is systems.
Flexible framework for high stability,
corrosion protection and safe earthing
provided as standard. The surfaces of

20
Enclosure Cubicle in universal mounting design
1 Roof plate 6 Base
2 Rear wall 7 Base compartment cover,
ventilated
3 Design side wall 8 Cubicle door, ventilated
4 Frame 9 Compartment door
5 Base cover 10 Head compartment door 1

11
2
Busbars 21

11 Main busbar (L1 ... L3, N) – top 10

12 Main busbar (L1 ... L3, N) – rear top


13 Main busbar (L1 ... L3, N) – rear bottom 9 12

14 Main busbar (PE) – bottom


15 Distribution busbar (L1 ... L3, N) – device compartment
17
16 Distribution busbar (PE) – cable compartment 20
17 Distribution busbar (N) - cable compartment 16
19 13 3
18
8 15

Internal separation
18 Device compartment / 20 Compartment to 14
busbar compartment compartment 4

19 Cubicle to cubicle 21 Cross-wiring compartment 7 6

Technical data

Frame

Door opening angle 125°, 180° with stand-alone


installation

Frame height 2,000, 2,200 mm


(without base)

Base height (optional) 100, 200 mm

The busbars can be positioned at either the top or the rear Degree of protection in accordance with IEC 60529:
and, if required, two busbar systems can also be integrated IP30, IP31, IP40, IP41, IP43,
in one switchboard, thus providing a high level of flexibility. IP54
The busbar connections are maintenance-free. The trans-
port joints are easily accessible from the front or the top. Main busbars

Rated currents up to 7,000 A

Rated peak up to 330 kA


withstand current Ipk

Rated short-time up to 150 kA


withstand current Icw

21
Circuit-breaker design

Your benefit

• Safety by connected, test, and


disconnected position with the
door closed High switchboard safety for all requirements Compact cubicles with circuit-breaker design
in functional buildings
• Optimum cubicle width for
every circuit breaker size
• Ideal space conditions for cable
connection, for every size
• Design verified connection to Where more current is needed, e.g. in incoming feeder
SIVACON 8PS busbar trunking cubicles or for high-power consumer loads, the circuit-breaker
systems design offers a powerful, compact solution.

User-friendly with safety Moving to the connected, test, or


The cubicles for 3WL/3VA circuit disconnected position with the 3WL air
breakers cater for personnel safety and circuit breaker takes place with the
long-term operational reliability. The door closed. Design verification by
incoming feeder, outgoing feeder and tests in accordance with IEC 61439-2
coupling cubicles in circuit-breaker also allows a high level of safety for all
design are fitted with 3WL air circuit sizes.
breakers in withdrawable or fixed-
mounted design or, alternatively, with Cost-efficient solutions
3VA molded case circuit breakers. As a compact version with a cubicle
width of just 400 mm, the cubicle
Continuous power supply by means of design Since there are generally many con-
with 3WL air circuit breaker is perfectly
verified connection to SIVACON 8PS busbar sumer loads downstream from these
trunking systems
suitable for current ratings up to
cubicles, the personnel safety and
2,000 A. For a cost-efficient installa-
operational reliability of these is of
tion, the circuit-breaker cubicle with
particular importance. SIVACON S8,
a width of 600 mm offers enough
with its components of the circuit-
space for up to three circuit breakers.
breaker design, meets all these
In this version, the connection is made
requirements in compact and safe
at the rear.
manner.

22
Cooling system with fans underneath
the 3WL circuit breaker

Inspection of the 3WL air circuit breaker possible without removal

Cubicles in circuit-breaker design can be equipped with Technical data


forced cooling. The use of fans considerably reduces the
circuit breaker derating caused by operational power loss. Mounting design Fixed-mounted design,
Cubicle properties such as degree of protection or a high withdrawable design

form of internal separation are not restricted thereby. Functions Incoming feeder, outgoing feeder,
transversal or longitudinal coupler
Flexible for individual requirements
Rated current In up to 6,300 A
The cubicles consist of separate functional compartments. of the circuit breaker
In the cable or busbar connection compartment, the circuit-
breaker design offers optimal connection conditions for Type of connection front or rear
every size. Cubicle width (mm) 400, 600, 800, 1,000, 1,400

There, cables or SIVACON 8PS busbar trunking systems can Internal separation Form 1, 2b, 3a, 4b, 4 type 7 (BS)
be connected through a design verified connection.
Busbar position top, rear top
The auxiliary device compartment offers ideal space and/or rear bottom
conditions for the switching devices provided for control
and monitoring. Depending on the position of the cable
or busbar connection compartment, the auxiliary device
holder can be installed at the top or bottom.

23
Universal mounting design

Your benefit

• High level of flexibility and


efficiency by functional
assemblies which can be High level of availability of the Motor Control Combination of withdrawable design, fixed-
combined as required in Center even in a harsh industrial environment mounted design, and switch disconnectors
space-optimised modular with fuses

design
• Personnel safety, even in the
event of a fault, thanks to
closed front doors in all
If there is little space available, the universal mounting design
withdrawable unit positions offers a safe, flexible, and cost-efficient solution. It allows to
(connected, test, disconnected combine different mounting designs – withdrawable, fixed-
positions) mounted with compartment doors, plug-in – in one cubicle.
• Long service life thanks to As a version in withdrawable design, it is the ideal solution for
patented low-wear contact Motor Control Centers in industrial plants, where a high avail-
system
ability of feeders and quick adjustments of the power supply
system are required.

Flexible and space-saving


The functional assemblies can be unnecessary, thus reducing the cubicle
combined at will, allowing for a space- width to 600 mm. The vertical distri-
saving installation of your switch- bution busbars are arranged at the
board. The 400 mm or 600 mm wide rear left in the cubicle. The profile
cable compartment on the right side busbar or flat copper design allows
of the cubicle offers cable brackets for for tap-offs in the smallest of grids.
propping up the cables. In universal Cables, wires, or busbars can also be
mounting design, the cables can also connected without any need for drill-
Flexible withdrawable design with normal and be connected at the rear, which makes ing or punching – optimal flexibility
small withdrawable units for high packing the lateral cable compartment for later extensions.
densities

24
Wide cable connection duct for
easy installation

Forced ventilation to install withdrawable units with frequency converters

Extended mounting options Technical data


Cubicles in universal mounting design can be provided
with forced ventilation to enable the installation of devices Mounting design Withdrawable design, fixed-mounted
with extremely high power loss in withdrawable design. design with compartment doors,
plug-in design
The heat is dissipated by fans via a separate air duct. The
fans are sized so that heat removal of the withdrawable Functions Cable feeders up to 630 A
unit is ensured even if one of the fans fails. Motor feeders up to 250 kW
(at 400 V)

Communication Type of connection front and rear


Communication via PROFIBUS DP, PROFINET, or Modbus
Cubicle width (mm) 600, 1,000, 1,200
offers all the benefits of extensive control functions and
analysis options. Internal separation Form 3b, 4a, 4b, 4 type 7 (BS)

Busbar position top, rear top


and/or rear bottom

25
Fixed-mounted design – Plug-in design – Withdrawable design –
modular and cost-efficient flexible modifications ergonomic and compact

Fixed-mounted design with 3VA circuit Plug-in design with 3NJ62 switch Simple and safe operation of the withdrawable
breaker disconnectors with fuses units with the doors closed

The fixed-mounted switching 3NJ62 or SASILplus (JEAN MÜLLER) When requirements are frequently
devices are installed on modular switch disconnectors with fuses can changing, e.g. modifications in motor
device holders. These can be be installed in the bottom 600 mm rating or the connection of new con-
equipped with circuit breakers or of the device compartment. They sumer loads, the withdrawable design
switch disconnectors with fuses. are equipped with a plug-in contact offers the flexibility needed. With-
on the supply/line side. This means drawable units can be modified or
Cable connection is made directly
that the switch disconnector can retrofitted with ease, and without
at the device or, in cases of higher
be replaced or retrofitted without de-energising the cubicle.
requirements, at special connection
de-energising the cubicle.
terminals in the cable compart- Regardless of whether small or normal
ment. For individual equipping, withdrawable units are used, the size
the system offers freely assignable is optimally adapted to the required
device holders. power rating, thus allowing to reduce
the size of the switchboard to a mini-
mum. The compact small withdrawable
units are particularly useful here.
With small withdrawable units of size
1/4 (up to four withdrawable units per
compartment) and 1/2 (up to two
withdrawable units per compartment),
as well as with normal withdrawable
units with heights starting from
100 mm, very high packing densities
can be achieved, with up to 48 with-
drawable units per cubicle for space-
optimised installation.

26
Mechanical coding of the withdrawable unit to prevent mix-up
of withdrawable units of the same size

Safe operation of the withdrawable units


Withdrawable units of all sizes are equipped with integrated
operating error protection and a uniform, clear indication
of the withdrawable unit positions. Moving to the test,
disconnected, or connected position takes place with the Integrated full motor protection, including communication
door closed and without eliminating the degree of protection. for intelligent linking to the control level

In addition to the main switch, the disconnected position


of the withdrawable units can also be locked for additional
safety. A coding of the withdrawable unit prevents any Motor management and motor control devices
mix-up of withdrawable units of the same size. SIMOCODE pro
The patented withdrawable unit contact system has been SIMOCODE pro is a flexible, modular motor management
conceived to be user-friendly and particularly wear-resistant. system for motors in the low-voltage range. It optimises the
In order to protect against damage, in the disconnected link between control system and motor feeder, increases
position all parts of the withdrawable units are located switchboard availability, and offers at the same time con-
within the contours of the withdrawable units. siderable savings during construction, commissioning,
No connection work is required inside the withdrawable operation, and maintenance of a switchboard.
unit compartments. • Extensive protection, monitoring, safety, and control
functions between the motor feeder and the automation
system in just one compact system
• Functions independently of the controller
In the connected position, both power and
I control contacts are closed. • Scalable, flexible solutions for all system configurations
• Detailed operating, service, and diagnostic data for
increased transparency throughout your switchboard
• Connection to process control systems using the
Withdrawable units in disconnected position most important communication protocols: PROFIBUS,
have maximum isolating distances on the PROFINET, Modbus RTU, and OPC UA
0 incoming, outgoing, and control sides. • Simple configuration and fast commissioning

The test position allows for no-load testing


Test of the withdrawable units.

Moving to the withdrawable unit positions behind closed door

27
Fixed-mounted design with front covers

Your benefit

• Cost-efficient arrangement of
devices as single or multiple
feeders Safe and cost-efficient construction in Easy installation of front covers and uniform
fixed-mounted design with front covers front level in the fixed-mounted design cubicle
• More safety thanks to design
verified standard modules
• High level of flexibility through
the combination of high-rating
outgoing feeders and modular If the replacement of components under operating conditions
installation devices is not required, or if short downtimes are acceptable, then the
fixed-mounted design with front covers offers a safe and
cost-efficient solution.

Safe and cost-efficient Flexible and space-saving


Individual functional assemblies can The vertical distribution busbars are
be combined in modular design as arranged at the rear left in the cubicle.
desired, therefore offering you all the The profile busbar or flat copper design
flexibility that you need. allows for tap-offs in the smallest of
grids. Connections to the distribution
Additive modules enable functional
busbars by means of cables, wires, or
compartments to be subdivided as
busbars are also possible without any
required (up to form 4b). The cables
need for drilling or punching. This
are routed at the right side of the
allows maximum flexibility, even for
cubicle in a cable compartment with
later extensions.
a choice of width of either 400 mm or
600 mm. Cable brackets are provided
here to prop up the cables.

Installation of fuse switch disconnectors,


circuit breakers, or modular installation
devices

28
The multi-profile busbar allows for easy mounting of modular installation devices.

Multifunctional modules Technical data


The switching devices are installed on modular device
holders of graduated depth. These can be equipped with Mounting design Fixed-mounted design
circuit breakers, switch disconnectors with fuses, or modu- with front covers

lar installation devices. They are attached to the device Functions Cable feeders up to 630 A
holder and directly connected to the distribution busbar.
Type of connection front
The cable connection is made directly at the device or,
in cases of higher requirements, at special connection Cubicle width (mm) 1,000, 1,200
terminals. Thanks to the cover, simple operation is possible
Internal separation Form 1, 2b, 3b, 4a, 4b
directly at the device. The cubicle can be optionally closed
with a glass door. Busbar position top, rear top
and/or rear bottom

29
In-line design, plug-in

Your benefit

• High level of switchboard


availability thanks to
modification or replacement In-line design for applications with numerous Up to 35 outgoing feeders per cubicle for
under operating conditions cable feeders in a very confined space 3NJ62 switch disconnectors with fuses

• Simple and cost-efficient


mounting due to plug-in
contact on the supply/line side
• High packing density with up In-line switching devices with a plug-in contact on the supply/
to 35 feeders per cubicle line side offer a cost-efficient alternative to the withdrawable
design and, thanks to their modular design, allow for quick
and easy modification or replacement under operating
conditions.

Variable with plug-in design Safe and flexible


The in-line 3NJ62 switch disconnectors The distribution busbar system is
with fuses are suitable for cable feeders arranged at the rear of the in-line
up to 630 A. design cubicle. It offers test finger
safety (IP20B) to live parts.
Alternatively, SASILplus (JEAN MÜLLER)
The tap-off openings are arranged
switch disconnectors with fuses can be
in a 50 mm modular grid. This allows
used. With up to 35 feeders per cubicle,
3NJ62 switch disconnectors with fuses feature maximum flexibility, even for later
the switching devices achieve a high
single or double breaking as standard. extensions.
packing density.
The cables are routed upwards at the
right side of the cubicle in a cable
compartment with a choice of width
of either 400 mm or 600 mm. Cable
brackets are provided here to prop up
the cables.

30
Plug-in busbar system, with test finger safety cover

Compact with high functionality Technical data


The cable is connected directly at the device. The device
forms the front closure. The plug-in in-line switch discon- Mounting design Plug-in design
nectors are operated directly at the device. Up to three Functions Cable feeders up to 630 A
required current transformers can be installed in the in-line
system within the device contours. Auxiliary switches and Type of connection front
measuring devices can be integrated in the in-line system. Cubicle width (mm) 1,000, 1,200
Device compartments are available for individual equipping.
Internal separation Form 3b, 4b

Busbar position top, rear top


and/or rear bottom

31
In-line design, fixed-mounted

Your benefit

• Space-saving thanks to
the compact design with
up to 18 feeders per cubicle Space-saving and cost-efficient switchboard Up to 18 outgoing feeders per cubicle with
installation in office complexes fixed-mounted 3NJ4 fuse switch disconnectors
• Consequent,
cost-efficient installation
• Optional installation of freely
assignable device holders or
ALPHA small distribution boards If the replacement of components under operating conditions
for modular installation devices is not required, or if short downtimes are acceptable, then the
fixed-mounted in-line fuse switch disconnectors offer a safe
and cost-efficient solution.

Compact and safe Cost-efficient and adaptable


The cubicles for cable feeders in the As a distribution busbar system, vari-
fixed-mounted design up to 630 A are ous cross-sections are available which
equipped with vertically installed 3NJ4 are arranged horizontally at the rear
fuse switch disconnectors. inside the cubicle.
Thanks to their compact design, they The protective conductor, PEN, or
allow for optimal and cost-efficient neutral conductor bars are installed
applications in infrastructure. separately from the phase conductors
in the cable compartment, either at
Depending on the cubicle width,
the top or the bottom of the cubicle,
several switch disconnectors of size 00
depending on the connection.
to 3 can be installed. A mounting plate
can be provided in the cubicle for the
installation of additional auxiliary
devices. Alternatively, an ALPHA small
distribution board can be installed.

32
With a wide range of connection options, the compact devices 3NJ4 fuse switch disconnectors with cable compartment
can be optimally fitted, even where space is limited. for connection from the bottom

Flexible design Technical data


The switch disconnectors are fixed-mounted on the hori-
zontal distribution busbar system. The cable is connected Mounting design Fixed-mounted design
directly at the device. The cables can be routed into the Functions Cable feeders up to 630 A
cubicle from the top or the bottom.
Type of connection front
A cubicle-height door provides the front closure. This door
Cubicle width (mm) 600, 800, 1,000
can be optionally fitted with a cutout area, which allows
to operate the switching devices when the door is closed. Internal separation Form 1, 2b
Operation takes place directly at the device. The switch
Busbar position rear top, and/or
disconnectors can be fitted with up to three current trans-
rear bottom
formers to enable feeder-related measurements.

33
Reactive power compensation

Your benefit

• More cost-efficient thanks to


lower energy costs
Reactive power is caused by inductive loads Cubicle for the central reactive power
• Efficient network dimensioning
such as motors. compensation
thanks to low reactive power
• Design verified integration,
either directly to the switch-
board or as a separate cubicle
Cubicles for the central reactive power compensation relieve
transformers as well as cables, and reduce transmission losses.
In this way, reactive power compensation cubicles enable an
economic power supply with efficient network dimensioning.

Cost-efficient overall system The capacitor assembly (up to


In a network, reactive power is caused 200 kvar) with MKK capacitors has
by inductive, linear consumer loads a fuse switch disconnector, capacitor
such as motors, transformers, or contactors, discharge devices, and
reactors, as well as by inductive, filter reactors. The switch disconnector
non-linear consumer loads such as assembly can optionally be used
converters, welding apparatuses, arc for the central safety isolation of the
furnaces, or UPS systems. Depending integrated capacitor assemblies.
on the consumer load structure, the
reactive power compensation is
equipped with choked or unchoked
capacitor assemblies. The controller
assembly has an electronic reactive
power controller for door installation.
The multifunction display is used to set
the desired target cos phi from 0.8 ind
to 0.8 cap. Network parameters such as
U, l, f, cos phi, P, S, Q, and harmonics
are displayed.

34
The capacitor assemblies can be used in
choked or unchoked version.

Reactive power compensation cubicle for cost-efficient power supply

Flexible design Technical data


The reactive power compensation cubicle can be integrated
into the switchboard directly and with design verification. Mounting design Fixed-mounted design
In this case, additional protection measures and cable Functions Central compensation
connections between the switchboard and the reactive of reactive power
power compensation are not required when these are
Capacitor power unchoked up to 600 kvar,
installed separately. The entire height of the device com-
choked up to 500 kvar
partment is available for the installation of the controller,
capacitor, or group-switch assemblies. The device compart- Degree of chocking without, 5.67 %, 7 %, 14 %
ment is closed by means of a cubicle-height door with Type of connection front
ventilation openings.
Cubicle width (mm) 800

Internal separation Form 1, 2b

Busbar position without, top, rear top


and/or rear bottom

35
Support
Optimise your time with Siemens
as a competent partner at your side

SIMARIS planning tools: siemens.com/simaris

SIVACON S8 low-voltage switchboards


on the Internet
Our website offers you a broad range of promotional
and technical information, as well as helpful tools for SIVACON S8 on the Internet:
the SIVACON S8 low-voltage switchboards.
siemens.com/sivacon-S8
siemens.com/sivacon-S8

Tender specification texts


We offer a comprehensive range of specification texts
Reliable local support
to support you:
Our local experts are there for you around the world, help-
siemens.com/specification ing you to develop solutions for your energy supply, and
providing you with specific expertise on project manage-
ment and financial services. Important aspects of safety,
logistics, and environmental protection are considered.
E-mail: support.energy@siemens.com

36
Technical experts from TIP Consultant Support offer sup-
port, especially for planning and conception of electrical
power distribution systems. The support also includes
planning tools, specification texts, as well as planning and
application manuals.
siemens.com/tip-cs

Efficient planning support


with the SIMARIS software tools
Planning electric power distribution for industrial plants,
infrastructure, and buildings is becoming more and more
complex. To help electrical planning engineers to work
faster and better under existing conditions, the innovative
SIMARIS software tools effectively support the planning
process.
Technical documentation on the Internet
SIMARIS design You will find an overview of the technical documentation
For network calculations and dimensioning, SIMARIS design available for the SIVACON S8 low-voltage switchboard, such
offers a secure solution from the broad product portfolio as the planning manual “SIVACON S8 – Technical Planning
of power distribution, according to recognised rules and Information” on our website (updated daily) at:
standards (VDE, IEC), and specific requirements. The specif-
ic components that are required are selected automatically siemens.com/lowvoltage/product-support
on the basis of the given project structure and the basic
data collected.
Build on a sound basis
siemens.com/simaris Our courses offer you solid foundations for your business
success. Expert lecturers provide you with the necessary
theoretical and practical information relating to our
SIMARIS project SIVACON S8 low-voltage switchboards.
This software tool enables you to create project documents For details of our current range of courses, please visit our
quickly, easily, and clearly to fit the space and budget website at:
requirements of your complete power distribution system.
Based on the switchboards and devices determined, you siemens.com/lowvoltage/training
can also create a list of specifications in GAEB D81 or
RTF format – in German, English, or Italian – at the click
of a button. The relevant specification texts are stored for Support
all the components, configured automatically, and com- For more information, please contact
piled in a project-specific manner. our Customer Support Center.

siemens.com/simarisproject Tel.: +49 (0) 180 524 70 00


Fax: +49 (0) 180 524 24 71
(Charges depending on provider)
E-mail: support.energy@siemens.com

37
Technical data

Standards and approvals

Standards and prescriptions Power switchgear and controlgear IEC 61439-2


assembly (design verification) DIN EN 61439-2
VDE 0660-600-2

Testing under conditions of arcing IEC/TR 61641


due to internal fault DIN EN 61439-2 Supplement 1
VDE 0660-600-2 Supplement 1

Induced vibrations IEC 60068-3-3


IEC 60068-2-6
IEC 60068-2-57
IEC 60980
KTA 2201.4
Uniform Building Code (UBC), Edition 1997 Vol. 2,
Ch. 19, Div. IV

Protection against electric shock EN 50274 (VDE 0660-514)

Approvals and certifications Europe CE Marking and EC Declaration of Conformity


Russia, Belarus, EAC (Eurasian Conformity)
Kazakhstan
China CCC

Det Norske Veritas DNV GL Type Approval Certificate


Lloyds Register of Shipping LR Type Approval Certificate

Shell Conformity “DEP Shell”

38
Technical data

Rated operational voltage Ue Main circuit up to 690 V (rated frequency fn 50 Hz)

Clearances and creepage distances Rated impulse withstand voltage Uimp 8 kV

Rated insulation voltage Ui 1,000 V

Degree of pollution 3

Main busbars, Rated current up to 7,010 A


horizontal
Rated peak withstand current Ipk up to 330 kA

Rated short-time withstand current Icw up to 150 kA, 1s

Rated currents of devices Circuit breakers up to 6,300 A

Cable feeders up to 630 A

Motor feeders up to 250 kW

Internal separation IEC 61439-2 Form 1 to Form 4

BS EN 61439-2 up to Form 4 type 7

IP degree of protection In accordance with IEC 60529 ventilated up to IP43


non-ventilated IP54

Mechanical strength IEC 62262 up to IK10

Dimensions Height (without base) 2,000, 2,200 mm

Height of base (optional) 100, 200 mm

Panel width 200, 350, 400, 600, 800, 850, 1,000, 1,200, 1,400 mm

Depth (single front) 500, 600, 800, 1,000, 1,200 mm

Installation conditions Indoor installation, ambient air + 35 °C


temperature in the 24-h mean (– 5 °C to + 40 °C)

39
Project checklist – Part 2

Project:

Network data / infeed data

Grid type ☐☐TN-C ☐☐TN-S ☐☐TN-C-S ☐☐IT ☐☐TT

Transformer rated power Sr kVA Rated impedance voltage Uz %

Rated operational voltage Ue V Frequency f Hz

Rated short-time withstand current Icw kA Short-circuit withstand current Ik at DC kA

Design ☐☐L1, L2, L3, PEN ☐☐L1, L2, L3, PE + N ☐☐Others:


of external connection ☐☐ZEP (PEN + PE)

☐☐3-pole switchable ☐☐4-pole switchable

Horizontal busbar system

Position ☐☐top ☐☐rear (top) ☐☐rear (bottom)

Rated current In A A A

Cu surface treatment ☐☐Bare ☐☐Silver-plated ☐☐Tin-plated

Design L1, L2, L3 + … ☐☐PEN ☐☐PE ☐☐N ☐☐PEN, N = 50 % ☐☐PEN, N = 100 %

☐☐Others:

Vertical busbar system / Distribution busbars

Cu surface treatment ☐☐Bare ☐☐Silver- ☐☐Tin-


plated plated

Design L1, L2, L3 + … ☐☐PEN ☐☐PE ☐☐N ☐☐PEN, N = 50 % ☐☐PEN, N = 100 %

Internal separation

Circuit-breaker design ☐☐Form 1 ☐☐Form 2b ☐☐Form 3a ☐☐Form 4b ☐☐Form 4


type 7

Universal mounting design ☐☐Form 3b ☐☐Form 4a ☐☐Form 4b ☐☐Form 4


type 7

Fixed-mounted design ☐☐Form 1 ☐☐Form 2b ☐☐Form 3b ☐☐Form 4a ☐☐Form 4b

In-line design, plug-in ☐☐Form 3b ☐☐Form 4b

In-line design, fixed-mounted ☐☐Form 1 ☐☐Form 2b

Reactive power compensation ☐☐Form 1 ☐☐Form 2b

Notes

41
Project checklist – Part 1

Customer

Author

Project Telephone

Factory ref. no. Fax

Delivery date Date

Standards and prescriptions

IEC 61439-1/2 / EN 61439-1/2 IEC/TR 61641/VDE 0660 Part 500-2, arc resistance
VDE 0660 Part 600-1/2 ☐☐Level 1,personnel safety ☐☐Level 2, limitation to one cubicle
☐☐Level 3, limitation to functional compartment ☐☐Level 4, limitation to the place of origin

☐☐Insulated main busbar ☐☐Arc barrier ☐☐Arc detection system

Environmental conditions

Operating conditions ☐☐Standard ☐☐Special ☐☐Corrosive gases (for example, H2S)


(interior climate 3K4)

Ambient air temperature ☐☐20 °C ☐☐25 °C ☐☐30 °C ☐☐35 °C ☐☐40 °C ☐☐45 °C ☐☐50 °C
(24-h mean)

Site altitude above sea level ☐☐≤ 2,000 m ☐☐Others: m

Adverse operating conditions ☐☐None ☐☐Earthquake-proof ☐☐Ship/Offshore

☐☐Others:

Layout and installation

Type of installation ☐☐Single-fronted ☐☐Back-to-back ☐☐Double-fronted

Connection inside the cubicle ☐☐front ☐☐rear

Restriction of total length ☐☐without ☐☐yes mm

Max. net length per transport unit ☐☐2,400 mm ☐☐Others: mm

Cable/busbar entry

Incoming feeder cubicles ☐☐from bottom ☐☐from top

Outgoing feeder cubicles ☐☐from bottom ☐☐from top

Degree of protection

Ventilated cubicle ☐☐IP30 ☐☐IP31 ☐☐IP40 ☐☐IP41 ☐☐IP43

Non-ventilated cubicle ☐☐IP54

Towards the cable floor ☐☐IP00 ☐☐IP30 ☐☐IP40 ☐☐IP54

☐☐at the factory ☐☐at the building site

40
Published by
Siemens AG 2016
Energy Management Division
Freyeslebenstrasse 1
91058 Erlangen, Germany
For more information, please contact our
Customer Support Center.
Tel.: +49 180 524 70 00
Fax: +49 180 524 24 71
(Charges depending on provider)
E-mail: support.energy@siemens.com
Article No. EMMS-B10040-00-7600
Printed in Germany
Dispo 30407
TH 260-160134 BR 09162.0

Subject to changes and errors.


The information given in this document only contains
general descriptions and/or performance features
which may not always specifically reflect those
described, or which may undergo modification in
the course of further development of the products.
The requested performance features are binding
only when they are expressly agreed upon in the
concluded contract.

SIVACON® und SIMARIS® are registered trademarks


of Siemens AG. Any unauthorized use is prohibited.
All other designations in this document may represent
trademarks whose use by third parties for their own
purposes may violate the proprietary rights of the
owner.

Read the
QR code with
the QR code
reader!

You might also like