You are on page 1of 4

POWER SOURCE LOSS MONITORING

RUT4 RELAY

4 CO CONTACTS POWER SOURCE


VOLTAGE MONITORING RELAY WITH DIP
ENHANCED UNSENSITIVITY

APPLICATIONS MAIN FEATURES


> 150 ms fixed dip unsensitivity > Designed to allow continuous operation even in
> Homogeneous with other field coils. high temperature ambient, within the whole
> Durability and long lifespan.. voltage range..
> AC or DC monitoring depending on the model.. > Self-cleaning contacts.
> Overvoltage and/or undervoltage in Substation > High level of electrical insulation between
auxiliary power services. circuits.
> Triggering of automatic line transfer automation > Tested to comply highest requesting
Standards; IEC, EN, IEEE and CE.
> Tested to comply highest requesting
Standards; IEC, EN, IEEE and CE.)
> Sturdy design.
> High protection degree (IP40), with transparent
cover, making them suitable for use in salty and
tropical atmospheres.
> Wide range of auxiliary/monitoring voltage
levels (Vdc and Vac).
> Versatile installation (plug-in relays in a wide
range of sockets with different installation
configurations).
Substations, Power plants and Industry > The ruggedness of the output contacts makes
possible direct action on HV and MV switchgear,
> Critical process automation. as their making/breaking capacities, continuous
> Command and Control. through-current and overvoltage capacity
> Alarm signaling and filtering. guarantee very high insulation.
> Monitors the level of its coil's rated voltage
> OP and OP2 signals the correct level of the
power source with a green LED. OP2,
additionally, signals wrong condition with a red
LED

1 www.arteche.com MONITORING RELAYS


V1.0
Breaking Curves for SY models

48 Vdc 125Vdc
Resistive load:
L/R = 0 ms
Inductive load:
L/R = 20 ms
Highly inductive load:
L/R = 40 ms

RELAY DIMENSIONS

6 www.arteche.com MONITORING RELAYS


V1.0
SOCKETS AND RETAINING CLIP
The dimensional and format of the sockets for the relay RUT4 are “F” type. Please refer to the document
“MU_BASES_RELES_EN” for further and more precise details. The sockets & clips available for this model are:

Sockets

FN DE IP10
FN DE2C IP10

FN DE IP20
JN DE2C IP21

FN TR OP
JN TR2C OP

FN DE CL IP20

FN EMP OP

Clips

OPTIONS FOR THIS RELAY

7 www.arteche.com MONITORING RELAYS


V1.0
This relay must be ordered indication the chosen options
RUT4 24/48/72/110/125/220 Vdc Op:--/2*
RUT4 SY 63.5/110/127/230 Vac(*) Op:--/2
(*) OP2 versions only in Vdc up to 125 volts.

8 www.arteche.com MONITORING RELAYS