You are on page 1of 9

Doc. N.

R0316-RPT-ME-00-004
DATA SHEET FOR DIESEL Rev. A
GENERATOR Page 1 / 6

DATA SHEET FOR DIESEL GENERATOR

TRANSPORT COMPANY BY PIPE-LINES TO SAHARA (TRAPSA)

A First issue 01/03/2017 AMG/NJ ELA MMH

REV DESCRIPTION DATE BY CHECKED APPROV. CLIENT


DATASHEET FOR POWER Doc. N.
Rev.
R0316-RPT-ME-00-004
A
GENERATOR Page 2 /6
DIAGNOSIS MISSION OF THE FACILITIES OF THE PETROLEUM TERMINAL OF TRAPSA IN SKHIRA
PROJECT:
LOCATION: TUNISIA / SKHIRA
SERVICE:
ITEM: DIESEL GENERATOR
NO. OF UNITS: 1
TAG NO.: -
SITE: -
CUSTOMER: TRANSPORT COMPANY BY PIPE-LINES TO SAHARA (TRAPSA)
MANUFACTURER: -

DESIGN DATA
A SERVICE / SITE CONDITION
1 SERVICE/APPLICATION CONTINUOUS POWER GENERATION
2 MAXIMUM AMBIENT TEMPERATURE 50ºC/0ºC
3 MAX RELATIVE HUMIDITY 76%
4 LOCATION ( INDOOR / OUTDOOR ) INDOOR

B DIESEL GENERATOR SET


1 POWER RATING AT SITE CONDITIONS 625 KVA
2 NET POWER OUTPUT AT ALTERNATOR 625KVA @ 0.8 PF
3 DUTY TYPE INTERMITTENT
4 DRIVE DIRECT
5 TURBO-CHARGER REQUIRED
6 AFTER-COOLER REQUIRED
7 No. OF STROKES FOUR
8 EXHAUST MANIFOLD AIR COOLED
9 REMOTE SPEED RAISE & LOWER FACILTY REQUIRED
10 AUTO ENGINE SHUTDOWN (10-15 MIN AFTER POWER RES) REQUIRED
11 COMBINED CHASSIS BASEPLATE REQUIRED
12 ENGINE PROTECTION SYSTEM REQUIRED
13 ENGINE CONTROL PANEL REQUIRED
14 COMBUSTION AIR INTAKE SYSTEM REQUIRED
15 ENGINE EXHAUST SYSTEM REQUIRED
16 FUEL SUPPLY PIPING REQUIRED
17 FUEL DAY TANK REQUIRED
18 TYPE OF COUPLING (ENGINE/GEN SET) FLEXIBLE
19 ENGINE AUXILLIARY SYSTEM
20 GOVERNOR TYPE ELECTRONIC
21 TYPE OF AIR INLET FILTER DRY
22 LUBE OIL SYSTEM SINGLE
23 SPARK ARRESTER SILENCER REQUIRED
24 PRIMING PUMP SELF PRIMING
25 FUEL STRAINER REQUIRED
26 NOISE LEVEL LIMIT 85 dB AT A DISTANCE OF 1MTR
27 AUTOMATIC TRANSFER SCHEME (ATS) REQUIRED (LOGIC TO BE IMPLEMENTED IN RELAY)
TIME REQUIRED TO CARRY FULL LOAD AFTER ACTUATION OF
28 35 TIMESTART SIGNAL < 30 SEC

C ALTERNATOR
1 OUTPUT VOLTAGE ADJUSTMENT RANGE ±5% CONTINUOUSLY ADJUSTABLE TYPE
2 OUTPUT VOLTAGE 5,5KV
3 OUTPUT FREQUENCY 50Hz
4 No. OF PHASES 3 PHASES 4 WIRES
5 SYSTEM GROUNDING SOLID
6 RATED POWER FACTOR 0.8
7 POWER RATING 625 KVA
8 PHASE SEQUENCE R-Y-B
DATASHEET FOR POWER Doc. N.
Rev.
R0316-RPT-ME-00-004
A
GENERATOR Page 3 /6

DESIGN DATA
9 INSULATION CLASS CLASS F
10 TEMPERATURE RISE EQUIVALENT TO CLASS B
11 STATOR RTDS 2 NOS. / PHASE, 100 OHMS PLATINUM
12 BEARING RTDS 1 NOS. / BEARING, 100 OHMS PLATINUM
13 VOLTAGE RATING OF SPACE HEATER 220 V, 1-PHASE, 50Hz
14 CURRENT TRANSFORMER
14.1 MOUNTED ON NEUTRAL AFTER FORMATION OF STAR POINT ONE FOR STANDBY EARTH FAULT
14.2 RATIO VTA
14.3 ACCURACY CLASS CL-5P20
14.4 VA BURDEN 10VA
14.5 LOCATION ON NEUTRAL TERMINAL BOX
15 GENERATOR CONTROL AND AMF PANEL REQUIRED
16 METHOD OF COOLING (*)
17 DEGREE OF INGRESS PROTECTION IP65
18 PAINTING SPECIFICATION (*)
19 NOISE LIMITATION 85 dB AT A DISTANCE OF 1 METER
20 ACOUSTIC ENCLOSURE NO
21 EXCITER TYPE BRUSHLESS TYPE
22 TERMINAL BOX
22.1 POWER CABLE SIZE AND RUNS AS PER CABLE SCHEDULE
22.2 APPROX OD AS PER CABLE MR
22.3 CABLE ENTRY TYPE GLAND
23 INSPECTION & TESTING
23.1 TYPE TESTS CERTIFICATE
23.2 ROUTINE TESTS AS PER IEC60034 AND BS 4999
23.3 FAT AND SAT REQUIRED
24 AUXILIARY PANELS SCOPE OF SUPPLY
24.1 LOCAL ENGINE PANEL YES
24.2 SYNCHRONIZATION PANEL YES
24.3 PROTECTION RELAY PANEL YES
24.4 OTHERS VENDOR TO SPECIFY (DC SUPPLY TO BATTERY
CHARGING AT STAND BY OF DG
D STARTING SYSTEM
1 METHOD OF STARTING BATTERY
2 NO OF BATTERY SET (*)
3 NO OF 15 SEC STARTS (*)
4 BATTERY TYPE 12V NiCd
5 STARTING TIME 10 Sec AT NO LOAD

E COOLING
1 METHOD OF COOLING RADIATOR
2 RADIATOR MOUNTING SKID
3 COOLING WATER/GLYCOL REQUIREMENT AIR COOLED

F INSPECTION & TESTING


1 TYPE TESTS CERTIFICATES TO BE SUBMITTED
2 ROUTINE TESTS AS PER IEC 60034 AND BS 5514
3 FAT AND SAT REQUIRED
DATASHEET FOR POWER Doc. N.
Rev.
R0316-RPT-ME-00-004
A
GENERATOR Page 4 /6

DATA SUPPLIED BY VENDOR


A DIESEL ENGINE SET
1 MANUFACTURER (*)
2 COUNTRY OF ORIGIN (*)
3 MODEL NO. (*)
4 MANUFACTURING STANDARD (*)
5 SPEED (*) RPM
6 CYLINDER ARRANGEMENT (*)
7 NO. OF CYLINDERS (*)
8 BORE (*) mm
9 STROKE (*) mm
10 DISPLACEMENT / COMPRESSION RATIO (*) litres
11 PISTON SPEED (*) m/sec

B GOVERNOR :
1 MAKE (*)
2 MODEL No. (*)
3 SIGNAL RANGE & SPEED RANGE (*)

C AIR INLET FILTER :


1 MAKE (*)
2 MODEL No. (*)
3 MOUNTING (*)

D LUBE OIL FILTER :


1 MAKE (*)
2 MODEL No. (*)
3 TYPE (*)

E SPARK ARRESTING EXHAUST SILENCER :


1 MAKE (*)
2 MODEL No. (*)
3 TYPE (*)
4 RAIN COVER NOT REQUIRED
5 CYLINDER ARRANGEMENT (*)
6 EXTENSION PIECE LENGTH (*) Mtrs.

F STARTING SYSTEM :
1 MAKE (*)
2 MODEL No. (*)
3 BATTERY TYPE & SIZE (*)
4 BATTERY CHARGER RATING (*) Amps

G DIESEL OIL :
1 TANK CAPACITY (*)Ltrs
2 FUEL PIPE SIZE (*)Inch
3 FUEL PIPE MATERIAL (*)
4 FUEL OIL CONSUMPTION AT
i) 100% LOAD (*)Ltr/Hr
ii) 75% LOAD (*)Ltr/Hr
iii) 50% LOAD (*)Ltr/Hr
5 ACOUSTIC ENCLOSURE / DG SET LOCATION (*)
6 DEGREE OF ENCLOSURE (*)
7 INLET & OUTLET AIR DAMPERS (*)
DATASHEET FOR POWER Doc. N.
Rev.
R0316-RPT-ME-00-004
A
GENERATOR Page 5 /6

DATA SUPPLIED BY VENDOR


H ALTERNATOR
1 MODEL NO. (*)
2 MANUFACTURING STANDARD (*)
3 VOLTAGE & FREQUENCY OUTPUT (*)
i) AT 50% STEP LOAD
i) AT 75% STEP LOAD
i) AT 100% STEP LOAD
4 POWER RATING, NO OF PHASE AND RATED POWER FACTOR (*)
5 NAMEPLATE RATING (*)
6 SITE RATING - STANDBY AND PRIME (*)
7 CURRENT TRANSFORMER RATING (*)
8 GUARANTEED EFFICIENCY (125 / 130 oC TEMPERATURE RATING):
i) AT 25% LOAD (*)
ii) AT 50% LOAD (*)
iii) AT 75% LOAD (*)
iv) AT 100% LOAD (*)
9 SHORT CIRCUIT RATIO (*)
10 OVERSPEED CAPABILITY (*)
11 SHORT CIRCUIT WITHSTAND CAPABILITY (*)
12 MOMENTARY OVERLOAD CAPABILITY (*)
11 GENERATOR INDUCED SHAFT VOLTAGE (*)
13 MIN. AIR CLEARANCE BETWEEN PHASE TO PHASE (*)
AS WELL AS BETWEEN PHASE TO EARTH IN MAIN (*)
TERMINAL BOX (*)

14 EXCITATION SYSTEM :
14.1 MAKE (*)
14.2 MODEL No. (*)
14.3 TYPE (*)
14.4 PARALLEL FUSED DIODES (*)
14.5 SHORT CIRCUIT CAPABILITY (*)
14.6 PILOT EXCITER (*)
14.7 EXCITATION CURRENT
a) (*)
b) (*)
15 SPACE HEATER VOLTAGE AND RATING (*)
DATASHEET FOR POWER Doc. N.
Rev.
R0316-RPT-ME-00-004
A
GENERATOR Page 6 /6

NOTES

NOTES
1 VENDOR shall fully comply with all the data sheet requirements and/or otherwise provide list of deviation, if any.
2 VENDOR shall provide all calculations, graphs, charts, performance report and updated specification in soft and hard copies.
3 Operating software should be provided by VENDOR.
4 Normal identification labels shall be black background with white letters.
5 Warning and Danger label shall be red background with white letter , bilingual English and Arabic.