Control Room Column Design & Drawing Doc. No.

Rev. : 00 Date :
Checks for Control Room Column Design & Drawing
Reference 01 : Bureau of Indian Standards ( IS : 456_2000), & Other relavent IS Standards
Reference 02 : Suzlon Technical Specification No.: ENG:PEV:T-012 , CEA Te
Standards for Construction of Electrical Plants and Electric Lines Regulations, 2010.
Sl.No Parameters to be Checked OK NOT OK

A DESIGN UNITS
All Design units are as per Standard International (SI) Metric System
1

B DESIGN ASSUMPTIONS

1 General design Methodology is provided

2 All Design assumptions are clearly described

C DESIGN PARAMETERS

1 Concrete & Reinforcement grades

2 Soil Unit weight is provided

3 Young's modulus is provided

D DESIGN LOADS

1 Design Loads are as per Project Design Basis /IS Codes

2 Dynamic loads are as Per Vendor Data for Heavy Rotating Equipment

3 Thermal loads are as per Project Design Basis


Load combinations for Allowable Stress Design are as per Project Design Basis ,
4 IS Codes
Load combinations for Ultimate Strength Design are as per Project Design
5 Basis , IS Codes

F COLUMN DESIGN
It shall called a column if its effective length will be three
1 times the least lateral dimension.

If the effective length of column is not at least three time its


2 lateral dimension then it is known as Pedestal.

The nominal cover for a longitudinal reinforcement bar in a column should not
3 be less than 40mm or the diameter of the bars.
The diameter of lateral ties should be greater among, (1⁄4)th of the diameter of
4 the largest longitudinal bars. 6 mm
The Pitch or spacing of the lateral ties should not be
greater than the following. Least lateral dimension of the column. 16 times the
5 diameter of the mallest longitudinal bars. 300 mm

Minimum area of cross-section of longitudinal bars must be atleast 0.8% of


6 gross section area of the column.

Maximum area of cross-section of longitudinal bars must not exceed 6% of the


7 gross cross-section area of the column.

8 The bars should not be less than 12mm in diameter.


Minimum number of longitudinal bars must be four in rectangular column and
9 6 in circular column.
Spacing of longitudinal bars measures along the periphery of a column should
10 not exceed 300mm.

It maybe in the form of lateral ties or spirals.


11
G CALCULATION PRESENTATION
Calculations Cover Sheet with Document Number, Project title, Caculation
1 Subject, Date, etc. is provided
Name of calculation originator/Checker on Claculation Sheets
2
Subject of Structural Calculations
3
Reference drawing number,Table of contents , List of appilcable coded,&
4 Standards .
General description of Structure design Methodology/Design Criteria /Primary
5 Loads Definition
Drawings
H
Check North Direction, Check Scale, Check units, Check Grid Dimensions
1
The information within the Title Block of each drawing has been reviewed for
accuracy including the “Designed By”, “Drawn By”, “Checked By” and “File No.”
2 fields.

The Index Sheet has been coordinated with the current list of
3 architectural drawings with respect to drawing number and title.

A drawing has been included to identify abbreviations and symbols utilized on


the project drawings and have been coordinated with the other architectural
4 drawings for compliance.

Loading plans, vertical loads layout


5
Deviations, if any

Verification team
Reviewed & Verfied by Approved & Accepted by
Remarks
Name
Date
Sign.

Prepared by Reviewed by Accepted by


Rupesh Khandekar Swapnil Kauthekar/Pravinkumar Patil/Jagadish G. Pravinkumar Patil
Doc. No.
Rev. : 00 Date :

CEA Technical

Remarks, if any
Approved & Accepted by

Accepted by
Pravinkumar Patil