Trip Circuit Supervision
Trip Circuit Supervision
Supervision
current
Mechanical
Command
Disappearance
of supervision
current
mechanical
Tripping circuit Command
interruption
Alarm
mechanical
Command
+ +
Relay
Advantages
Relay
2 cables only between
relay and circuit breaker
- -
Alarm Alarm
Circuit Breaker
Disadvantages
Circuit Breaker
Contct position
when equipment
energised
Relay
Advantages
2 cables only between
relay and circuit breaker.
Circuit Breaker
Disadvantages
Circuit Breaker
(1)
No trip circuit control if
CB open
52b
52b
52a
52a
Requires additional
resistance into the CB
Contct position control box (1)
when equipment
energised
(1) Avoid a Battery short circuit when the CB is already open but trip
order still present.
14 > Title of presentation - Date - References 14
Trip Circuit Supervision
Scheme n° 3
+ +
Advantages
Relay
Relay
- -
Alarm Alarm
Disadvantages
Requires 3 wires
Circuit Breaker
Circuit Breaker
52b
52a
52a
Relay
Advantages
The trip coil is controlled
whatever the CB position
- -
Disadvantages
Circuit Breaker
Circuit Breaker
Requires 3 wires
between relay and CB.
52a
52a
+ +
Advantages
Relay
Relay
- -
Relay
Relay
Advantages
2 cables only between
relay and circuit breaker.
Triping contact
CB Tripping coil
Logic Input
controlled whatever the
(Opto)
- - CB position
(1)
Disadvantages
52b
52b
52a
52a
Requires installation of
additional resistance into
the CB control box (1)
Contct position
when equipment
energised (1) avoid any damage of the tripping coil when trip order still present and circuit
breaker already open.
Opto
ET Alarm trip
& circuit faulty
Trip contact
energised
+
Relay
Trip coil
52a
+
Relay
-
Overcurrent relay
Alarme
Circuit Breaker
+
Relay
Logical input
-
Overcurrent relay
Alarme
Circuit Breaker
Resistance
Trip coil
52a
52b
Alarm
Disjoncteur
Release timer
52a
52b
Contct position
when equipment
energised
¾MVAX 91
connection
diagram :