You are on page 1of 8

ARTICLE NH-6000

NH-6100 General Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65


NH-6110 Scope of Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
NH-6111 General Hydrostatic and Pneumatic Test Media . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
NH-6112 Pressure Testing of Components and Appurtenances . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
NH-6113 Pressure Testing of Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
NH-6115 Time of Pressure Test and Stamping of Components and Appurtenances . . . . . . . . . 65
NH-6116 Machining of Local Areas After Static Pressure Testing . . . . . . . . . . . . . . . . . . . . . . . . 66
NH-6117 Alternative Tests of Closure Welds and Access Hatches . . . . . . . . . . . . . . . . . . . . . . . . 66
NH-6118 Alternative Tests at Specially Designed Welded Seals . . . . . . . . . . . . . . . . . . . . . . . . . . 66
NH-6120 Preparation for Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
NH-6121 Exposure of Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
NH-6122 Addition of Temporary Supports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
NH-6123 Restraint or Isolation of Expansion Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
NH-6124 Isolation of Equipment Not Subjected to Pressure Test . . . . . . . . . . . . . . . . . . . . . . . . . 67
NH-6125 Treatment of Flanged Joints Containing Blinds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
NH-6126 Precautions Against Test Medium Expansion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

NH-6200 Hydrostatic Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67


NH-6210 Hydrostatic Testing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
NH-6211 Provision of Air Vents at High Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
NH-6212 Test Medium and Test Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
NH-6213 Check of Test Equipment Before Applying Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
NH-6215 Examination for Leakage After Application of Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 67
NH-6220 Hydrostatic Test Pressure Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
NH-6221 Minimum Required System Hydrostatic Test Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . 68
NH-6222 Maximum Permissible Hydrostatic Test Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
NH-6223 Hydrostatic Test Pressure for Valves, Pumps, and for Components and
Appurtenances Containing Brazed Joints. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
NH-6224 Hydrostatic Test Pressure Holding Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

NH-6300 Pneumatic Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68


NH-6310 Pneumatic Testing Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
NH-6311 General Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
NH-6312 Test Medium and Test Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
NH-6313 Check of Test Equipment Before Applying Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
NH-6314 Procedure for Applying Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
NH-6315 Examination for Leakage After Application of Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 69
NH-6320 Pneumatic Test Pressure Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
NH-6321 Minimum Required System Pneumatic Test Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

63
NH-6322 Maximum Permissible Pneumatic Test Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
NH-6323 Pneumatic Test Pressure for Valves, Pumps, and for Components and
Appurtenances Containing Brazed Joints. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
NH-6324 Pneumatic Test Pressure Holding Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

NH-6400 Pressure Test Gages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

64
ARTICLE NH-6000
TESTING

NH-6100 GENERAL REQUIREMENTS (c) A static pressure test of each line valve and
pump with inlet piping connections of 4 in. nominal
Testing of Section III, Division I, Class 1 components
pipe size and smaller shall be performed by the Manu-
when metal temperatures exceed those for which allow-
facturer and so noted on the Data Report Form; however,
able stress values are given in Section II, Part D, shall
this static pressure test need not be witnessed by the
be in accordance with the rules of this Subsection.
Inspector. The Inspector’s review of the Manufacturer’s
test records will be his authority to sign the report.
This takes precedence over NCA-5280.
NH-6110 SCOPE OF TESTING (d) Under the special conditions of NH-6117 and
NH-6111 General Hydrostatic and Pneumatic NH-6118, a helium mass spectrometer leak test (plus
Test Media other tests) may replace the static pressure test required
in (a) above.
(a) The selection of a particular test medium may (e) The requirements of (a) above are met by meeting
depend upon considerations in (b), (c), and (d) below. the requirement of NH-6113(a).
For some items, a combination of gaseous and liquid (f) The component or appurtenance pressure test,
test media may be desirable. when conducted in accordance with the rules of NH-
(b) Compared to pressurized liquids, gas under a 6221 or NH-6321, shall be acceptable as a pressure
similar pressure has a greater potential energy release. test for parts and piping subassemblies.
It is therefore recommended that special precautions (g) For components and appurtenances which will
for protection of personnel be taken when a gas under be subjected to external pressure loads in service, the
pressure is used as a test medium. pressure test requirement in (a) above may be performed
(c) Some components, appurtenances, or systems are on the basis of an internal pressure test using the rules
not designed to support the liquid weight required in of NH-6221 or NH-6321. The Design Specifications
a hydrotest. Pneumatic tests should be considered for may require further tests to demonstrate structural integ-
such components. rity under external pressure loading.
(d) The use of liquids for testing often results in
traces of the liquid left in hard-to-clean places in the
system, and these residues may be harmful to the NH-6113 Pressure Testing of Systems
structural material because of reactions involving the
residues and the system coolant. Pneumatic tests should (a) Prior to initial operation, the installed Class 1
be considered under these circumstances. system shall be static pressure tested in the presence
of the Inspector.
(b) Under the special restrictions of NH-6117 and
NH-6112 Pressure Testing of Components and NH-6118, a helium mass spectrometer leak test may
Appurtenances replace the static pressure test in (a) above.
(a) Except as noted in (b) and (c) below, all compo-
nents and appurtenances for elevated temperature service
NH-6115 Time of Pressure Test and Stamping
shall be static pressure tested in the presence of the
of Components and Appurtenances
Inspector.
(b) Nuts, bolts, studs, and gaskets are exempt from (a) The pressure tests of components and appurte-
the rules of this Subsection. nances required by NH-6112(a) shall be performed

65
NH-6115 1998 SECTION III, DIVISION 1 — NH NH-6122

prior to installation in the system as specified in NH- T is the nominal thickness of the thicker material
6221(a) or NH-6321(a). adjacent to the weld;
(b) The pressure tests of components and appurte- (3) The alternative test procedure in (b) below is
nances required by NH-6112(a) may be performed after specified for the closure welds; and
installation if the system pressure test is used under (4) The closure welds to which the alternative
the provisions of NH-6221(c) or NH-6321(c). tests shall be applied, and the alternative test procedure
(c) The Data Report Form shall not be completed shall be included in the Design Specification. The
nor signed by the Inspector and the components shall closure welds to which the alternative test procedure
not be stamped until the component Manufacturer has has been applied shall be identified on the Data Report.
conducted the static pressure test. (b) As an alternative to the pressure test procedure,
(d) Specially designed welded seals,1 which are iden- closure welds may be tested by a mass spectrometer
tified on the Data Report Form as being welded by helium leak test.
the Installer under the rules of NH-6118, need not be
tested prior to the stamping of the component.
(e) Appurtenances containing brazed joints, pumps NH-6118 Alternative Tests at Specially
not designed by detailed analysis,1 and valves shall be Designed Welded Seals
static pressure tested prior to installation in a system.
(a) Specially designed welded seals, such as omega
and canopy seals, need not meet the pressure test
NH-6116 Machining of Local Areas After Static requirements of NH-6112 and NH-6113 when:
Pressure Testing (1) The final weld cannot be completed until after
(a) In local regions of the pressure boundary where the hydrostatic or pneumatic test because the system
tight tolerances are required for proper component test pressure would exceed the limit specified for any
functioning, extra wall thickness is permitted during system component; and
pressure testing. If extra wall thickness is provided (2) The seal is subjected to a leak test at the
during fabrication, the excess material may be machined maximum normal operating pressure.
to critical dimensions and tolerances after completion (b) Welds of specially designed welded seals may
of the static pressure test. be tested by a helium leak test in lieu of the pressure
(b) The extra wall thickness permitted during pressure test requirements of NH-6112 and NH-6113 provided:
testing in (a) above shall not exceed 10% of the final (1) The welds of the seal, and the welds joining
wall thickness or 3⁄8 in. (10 mm), whichever is less. the seal to the component or supporting structure, cannot
(c) The final wall thickness, after machining to criti- be visually examined during testing due to access
cal dimensions and tolerances, shall comply with the restrictions; and
minimum wall thickness requirements defined in the (2) The welds and the alternative test procedures
rules for design of Class 1 components for elevated have been mutually agreed to by the Owner and Manu-
temperature service. facturer, and the requirements appear in the Design
Specifications and in the Installer’s Data Report Forms.
NH-6117 Alternative Tests of Closure Welds
and Access Hatches
(a) Closure welds for access hatches in vessels and NH-6120 PREPARATION FOR TESTING
closure welds for connecting piping subassemblies may
be tested by an alternative procedure for the pressure NH-6121 Exposure of Joints
test requirements of NH-6112 and NH-6113 provided All mechanical and welded joints, including welds,
the conditions of (1) through (4) below are met: shall be left uninsulated and exposed for examination
(1) If hydrotesting were to be used, residues from during the test.
the hydrotest liquid could be deleterious to the service;
(2) Closure welds are located at least 3√RT from
major structural discontinuities such as flanges, large
NH-6122 Addition of Temporary Supports
nozzles, pumps, or valves. R is the mean radius and
Components designed for vapor or gas may be pro-
1 Definitions
are contained in the rules governing the design of Class vided with additional temporary supports, if necessary,
1 components in elevated temperature service. to support the weight of the test liquid.

66
NH-6123 ARTICLE NH-6000 — TESTING NH-6215

NH-6123 Restraint or Isolation of Expansion (b) No hydrostatic test shall be performed at a temper-
Joints ature which exceeds those for which Sm values are
listed in Tables 2A and 2B of Section II, Part D,
Expansion joints shall be provided with temporary
Subpart 1 for any of the materials used in the pressure
restraint, if required for the additional pressure load
boundaries of components being tested.
under test, or they shall be isolated from the test.
(c) It is recommended that the test be made at a
temperature that will minimize the possibility of brittle
NH-6124 Isolation of Equipment Not Subjected fracture (NB-2330). The test pressure shall not be
to Pressure Test applied until the component, appurtenance or system,
and the pressurizing medium are approximately at the
Equipment that is not to be subject to the pressure same temperature.
test shall be either disconnected from the component (d) For the vessel hydrostatic test before installation,
or system, or isolated by a blank flange or similar it is recommended that the test be made at a temperature
means. Valves may be used if the valve with its closure not lower than [RTNDT + 60°F], (NB-2331).
is suitable for the proposed test pressure.

NH-6125 Treatment of Flanged Joints


Containing Blinds NH-6213 Check of Test Equipment Before
Applying Pressure
Flanged joints at which blinds are inserted to blank
off other equipment during the test need not be tested The test equipment shall be examined before pressure
until the blinds are removed. is applied to ensure that it is tight and that all low
pressure filling lines and other appurtenances that should
not be subjected to the test pressures have been discon-
NH-6126 Precautions Against Test Medium nected or isolated by valves or other suitable means.
Expansion
If a pressure test is to be maintained for a period
of time and the test medium in the system is subject
to thermal expansion, precautions shall be taken to NH-6215 Examination for Leakage After
avoid excessive pressure. A small relief valve set to Application of Pressure
1.33 times the test pressure is recommended during
Following the application of the hydrostatic test
the pressure test.
pressure for a minimum of 10 minutes, as required by
NH-6224, examination for leakage shall be made of
all joints, connections, and of all regions of high stress
NH-6200 HYDROSTATIC TESTS such as regions around openings and thickness transition
sections. Except in the case of pumps and valves,
NH-6210 HYDROSTATIC TESTING which shall be examined while at test pressure, this
PROCEDURE examination shall be made at a pressure equal to the
NH-6211 Provision of Air Vents at High Points greater of the design pressure or three-fourths of the
test pressure and it shall be witnessed by the Inspector.
Vents shall be provided at all high points of the Leakage of temporary gaskets and seals, installed for
component or system in the position in which the test the purpose of conducting the hydrostatic test and which
is to be conducted to purge air pockets while the will be replaced later, may be permitted unless the
component or system is filling. leakage exceeds the capacity to maintain system test
pressure for the required amount of time. Other leaks,
such as from permanent seals, seats, and gasketed joints
NH-6212 Test Medium and Test Temperature
in components, may be permitted when specifically
(a) Any nonhazardous liquid at any temperature be- allowed by the Design Specifications. Leakage from
low its boiling point may be used for the hydrostatic temporary seals or leakage permitted by the Design
test. Combustible liquids having a flash point less than Specifications shall be directed away from the surface
100°F, such as petroleum distillates, may be used only of the component to avoid masking leaks from other
for tests at near atmospheric temperature. joints.

67
NH-6220 1998 SECTION III, DIVISION 1 — NH NH-6313

NH-6220 HYDROSTATIC TEST PRESSURE appurtenances containing brazed joints shall be hydro-
REQUIREMENTS statically tested at a pressure 1.5 times the system
design pressure.
NH-6221 Minimum Required System
(b) The inlet (primary pressure containing) portion
Hydrostatic Test Pressure
of safety and safety relief valves shall be hydrostatically
(a) Except as may be otherwise required by material tested at a pressure at least 1.5 times the set pressure
specifications and by the requirements of NH-6223, all marked on the valve. For closed system applications,
components and appurtenances shall be subjected to a the outlet portion of safety and safety relief valves
hydrostatic test at a pressure not less than 1.25 times shall be hydrostatically tested to 1.5 times the design
the system design pressure prior to installation in the secondary pressure of the outlet system.
nuclear power system.
(b) All pressure retaining components of the com-
pleted Class 1 system shall be subjected to a system NH-6224 Hydrostatic Test Pressure Holding
hydrostatic test at a pressure not less than 1.25 times Time
the system design pressure unless specifically excepted The hydrostatic test pressure shall be maintained for
under the provisions of NH-6117 and NH-6118. a minimum total time of 10 minutes and for such
(c) The system hydrostatic test of NH-6221(b) may additional time as may be necessary to conduct the
be substituted for a component hydrostatic test of NH- examination for leakage required by NH-6215. When
6221(a) provided: testing pumps, valves, and other components covered
(1) The component can be repaired by welding, by NH-6223, the pressure shall be maintained a mini-
if required, as a result of the system hydrostatic test, mum of 15 minutes for each inch of design minimum
in accordance with the rules of NB-2500; wall thickness, but for not less than 10 minutes.
(2) The component repair can be postweld heat
treated, if required, and nondestructively examined in
accordance with rules of NB-2500, NB-5100, and NB- NH-6300 PNEUMATIC TESTS
5400, as applicable, subsequent to the system hydrostatic
test; and NH-6310 PNEUMATIC TESTING
(3) The component is subjected to the required PROCEDURES
system hydrostatic test following the completion of NH-6311 General Requirements
repair and examination.
When a pneumatic test is performed, it shall be
conducted in accordance with the requirements of NH-
NH-6222 Maximum Permissible Hydrostatic 6300 and NH-6112.
Test Pressure
(a) The stress limits, contained in the rules of NH- NH-6312 Test Medium and Test Temperature
3000, shall be used in determining the permissible
hydrostatic test pressure. In multichamber components, (a) The gas used as the test medium shall be non-
pressure may be simultaneously applied to the appro- flammable;
priate adjacent chamber to meet these stress limits. The (b) It is recommended that the test be made at a
number of test sequences for which the above provisions temperature that will minimize the possibility of brittle
may be considered applicable shall not exceed ten. fracture (NB-2330). The test pressure shall not be
(b) When hydrostatically testing a system, the test applied until the component, appurtenance or system,
pressure shall not exceed the lowest of the maximum and the pressurizing medium are approximately the
test pressures allowed for any of the components in same temperature.
the system.
NH-6313 Check of Test Equipment Before
NH-6223 Hydrostatic Test Pressure for Valves, Applying Pressure
Pumps, and for Components and
The test equipment shall be examined before pressure
Appurtenances Containing Brazed
is applied to ensure that it is tight and that all appurte-
Joints
nances that should not be subjected to the test pressure
(a) Prior to installation, valves, pumps not designed have been disconnected or isolated by valves or other
by detailed stress analysis, and other components and suitable means.

68
NH-6314 ARTICLE NH-6000 — TESTING NH-6400

NH-6314 Procedure for Applying Pressure (3) The component is subjected to the required
system pressure test following the completion of repair
The pressure in the system shall gradually be in-
and examination.
creased to not more than one-half of the test pressure,
after which the pressure shall be increased in steps of
approximately one-tenth of the test pressure until the NH-6322 Maximum Permissible Pneumatic Test
required test pressure has been reached. The pressure Pressure
shall then be reduced to a value equal to the greater (a) The stress limits contained in the rules of NH-
of the design pressure or three-fourths of the test 3000 shall be used in determining the permissible
pressure and held for a sufficient time to permit examina- pneumatic test pressure. In multichamber components,
tion of the system in accordance with NH-6315. pressure may be simultaneously applied to the appro-
priate adjacent chamber to meet these stress limits. The
number of test sequences for which the above provisions
NH-6315 Examination for Leakage After may be considered applicable shall not exceed ten.
Application of Pressure (b) When pneumatically testing a system, the test
Following the application of pressure for the time pressure shall not exceed the lowest of the maximum
specified in NH-6324, examination of leakage in accord- test pressures allowed for any of the components in
ance with NH-6215 shall be made. the system.

NH-6323 Pneumatic Test Pressure for Valves,


Pumps, and for Components and
NH-6320 PNEUMATIC TEST PRESSURE
Appurtenances Containing Brazed
REQUIREMENTS
Joints
NH-6321 Minimum Required System Pneumatic
(a) Prior to installation, valves, pumps not designed
Test Pressure
by detailed stress analysis, and other components and
(a) Except as may be otherwise required by material appurtenances containing brazed joints shall be pneu-
specifications and by the requirements of NH-6323, all matically tested at a pressure 1.5 times the system
components and appurtenances shall be subjected to a design pressure.
pneumatic test at a pressure not less than 1.20 times (b) The inlet (primary pressure containing) portion
the system design pressure prior to installation in the of safety and safety relief valves shall be pneumatically
nuclear power system. tested at a pressure at least 1.5 times the set pressure
(b) All pressure retaining components of the com- marked on the valve. For closed system applications,
pleted Class 1 system shall be subjected to a system the outlet portion of safety and safety relief valves
pneumatic test at a pressure not less than 1.20 times shall be pneumatically tested to 1.5 times the design
the system design pressure unless specifically excepted secondary pressure of the outlet system.
under the provisions of NH-6117 and NH-6118.
(c) The system pneumatic test of NH-6321(b) may NH-6324 Pneumatic Test Pressure Holding
be substituted for a component pneumatic test of NH- Time
6321(a) provided:
(1) The component can be repaired by welding, The pneumatic test shall be maintained for a minimum
if required as a result of the system pneumatic test, total time of 10 minutes and for such additional time
in accordance with the rules of NB-4400; as may be necessary to conduct the examination for
leakage required by NH-6215.
(2) The component repair can be postweld heat
treated, if required, and nondestructively examined in
accordance with the rules of NB-4400, NB-5100, and
NH-6400 PRESSURE TEST GAGES
NB-5400, as applicable, subsequent to the system pneu-
matic test; and The rules of NB-6400 shall apply.

69

You might also like