You are on page 1of 3

© Grid Solutions SAS 2016. All rights reserved.

Information contained in this document is


indicative only. No representation or warranty is given or should be relied on
that it is complete or correct or will apply to any particular project. This will
depend on the technical and commercial circumstances. It is provided without
liability and is subject to change without notice. Reproduction, use or disclosure
to third parties, without express written authority, is strictly prohibited.

01
02

Rev

Created:

Approved:
Reviewed:
Scale: N/A
EC Number:
N° d'article
Part Number /
F06A790549-02

Date
26/07/2016
10/04/2017

BHTPNJ
A

Rev

B.TREGUIER
J.PERRETON
Unit: mm Format:
Q.Level:
3
A4
FIRST ISSUE
Lot de plaques Poste

UPDATE MASS OF SF6

Sheet:
Local Unit:
D.Authority:

Product:
Texte

1 / 3
BHT
BHT

B105
Description

F06A790549
GIS Nameplate
GIS TYPE B105
GHAZI ROAD - 220kV
3

Page

N°EC

02
Rev:
HE0019330E
Nameplates characteristics

Material : Stainless steel

Treatment : whithout

Resistance : very good resistance to corrosion, for indoor and outdoor use

Colours : stainless steel colour letters on blue RAL 5002 background

Text : engraved

Fastening : by rivets

GIS TYPE

As per IEC 62271-1:2007 (GIS)


The rated voltage is equal to the maximum system voltage for which the
equipment is designed. It indicates the maximum value of the "highest system
voltage" of networks for which the equipment may be used (refer to Clause 9 of
Ur Rated Voltage
IEC 60038). Standard values of rated voltages are given below.
170 kV – 245 kV – 300 kV – 362 kV – 420 kV – 550 kV – 800 kV.
In other words, it means the "design voltage" and not the "operation voltage".

The rated normal current of switchgear and controlgear is the r.m.s. value of the
current which switchgear and controlgear shall be able to carry continuously
under specified conditions of use and behaviour. The values of rated normal
Ir Rated Current
currents should be selected from the R 10 series, specified in IEC 60059.
The R 10 series comprises the numbers 1000 – 1250 – 1600 – 2000 – 2500 –
3150 – 4000 – 5000 – 6300 – 8000.

Up rated lightning impulse withstand voltage


Ud rated power-frequency withstand voltage (rated voltage < 300kV)
Ik rated short-time withstand current
Ip rated peak withstand current
fr rated frequency
tk rated duration of short circuit
Ua Rated supply voltage of auxiliary circuits (and associated frequency)
pre rated filling pressure (density)
pae alarm pressure (density)
pme minimum functional pressure (density)
m Total mass of SF6 contained in the GIS installation

Sheet

2 /3
F06A790549 02
GIS Nameplate

Blank plate F304 928 002

Quantity 2

Type / Standard B105 IEC 62271-203:2003


Job number (Sr No) / Year of manufacture AQ71 / 2017
Rated voltage / Rated frequency Ur / fr 245 kV / 50 Hz
Power-frequency withstand voltage Ud 460 kV
Lightning impulse withstand voltage Up 1050 kV

Rated auxiliary voltage Ua 220 V d.c.


Normal current :
- Busbars and bays (INDOOR) Ir 3150 A
- Line and transformer bays (OUTDOOR) Ir 2000 A
Short-time withstand current / Duration Ik / tk 50 kA / 3 s
Peak withstand current Ip 125 kA
CB SF6 gas pressure : filling/alarm/minimum (at 20°C) Pre / Pae / Pme 6,3 / 5,8 / 5,5 bar
GIS SF6 gas pressure : filling/alarm/minimum (at 20°C) Pre / Pae / Pme 6,3 / 5,8 / 5,5 bar
Total mass of SF6 contained in the GIS installation m 2024 kg