Document Title: 120V AC POSITIVE IQ REMOTE CONTROL CIRCUITRY - MODULATING (24VDC)

THE INFRA RED SETTING TOOL ENABLES ALL CONFIGURABLE NOTE:


ACTUATOR SETTINGS TO BE MADE. ACTUATOR REMOTE CONTROL SIGNALS MAY BE INTERNALLY OR
EXTERNALLY SUPPLIED.
BEFORE PUTTING THE ACTUATOR INTO SERVICE, IT MUST BE INTERNALLY SUPPLIED:
INSTALLED AND COMMISSIONED IN ACCORDANCE WITH FIT LINK '#' AS SHOWN AND CONNECT REMOTE CONTROL
PUBLICATION E170E : IQ INSTALLATION AND MAINTENANCE # CONTACTS TO INTERNAL SUPPLY ON TERMINAL 5.
INSTRUCTIONS. EXTERNALLY SUPPLIED:
UNLESS SPECIFIED WITH ORDER, THE ACTUATOR IS CONNECT CONTROL CONTACTS TO EXTERNAL SUPPLY LIVE/+VE.
DESPATCHED WITH DEFAULT SETTINGS AS LISTED IN CONNECT SUPPLY ZERO/-VE AS FOLLOWS:-
PUBLICATION E170E. TO TERMINAL 36 & 31 FOR SUPPLIES UP TO 60VAC or DC
TO TERMINAL 40 & 32 FOR SUPPLIES UP TO 120VAC
FOR IQ CONTROL AND MONITORING FACILITIES, REFER TO
PUBLICATION E120E. FOR CONTROL FORMS D & E, LINK '#' MUST BE FITTED.
CONNECT ZERO/-VE AS INDICATED ABOVE.

N
OW
CUSTOMER CONNECTION FOR

OR P T OTE

TO TE
REMOTE CONTROL

TD
AC LS U EM

V A LS 6 EM
Y

Y
DC O

HU
PL

+V PPL
60V TRO OR R

120 TRO OR R

LE

LE
0V

YS
UP

DC L SU
AB

AB
LS

NC
E
F

EN

EN

AIN
CO ON

CO ON
-VE RNA

24V RNA

GE
C

E
MM

MM

I NT

ER
EN
AK

AK

OS
E

E
N

N
INT

INT

EM
CO

CO

MA

OP
BR

BR

CL
4 36 40 33 34 35 5 25
FORM A #
OPEN/CLOSE PUSH TO RUN CONTROL Close Open
(LOCAL CONTROL REMAINS SELF MAINTAINED)
To external supply or terminal 5
(see 'Note:' above)

4 36 40 33 34 35 5 25
#
FORM B
Close Open
OPEN/CLOSE MAINTAINED CONTROL
WITH MID TRAVEL REVERSAL To external supply or terminal 5
(see Note:' above)

4 36 40 33 34 35 5 25
# To external supply or
FORM C terminal 5 (see 'Note:'
OPEN/STOP/CLOSE MAINTAINED CONTROL above)
Close Open Stop

4 36 40 33 34 35 5 25
FORM D #
TWO WIRE CONTROL, ENERGISE TO OPEN
DE-ENERGIZE TO CLOSE. Close Open
(CONFIGURE FOR OPEN PRIORITY)
CUSTOMER TO LINK 5 - 33 To external supply or terminal 5
(see 'Note:' above)

4 36 40 33 34 35 5 25
FORM E #
TWO WIRE CONTROL, ENERGISE TO CLOSE
DE-ENERGIZE TO OPEN Open Close
(CONFIGURE FOR CLOSE PRIORITY)
CUSTOMER TO LINK 5 - 35 To external supply or terminal 5
(see 'Note:' above)

4 31 32 33 34 35 5 25
FORM F # ESD
EMERGENCY SHUT-DOWN CIRCUIT. switch
THE ESD CIRCUIT CAN BE ADDED TO ANY OF THE CONTROL
CIRCUITS SHOWN ABOVE. (stayput)
AN ESD SIGNAL APPLIED TO THE ACTUATOR WILL OVERRIDE
To external supply or terminal 5
ANY EXISTING OPEN OR CLOSE CONTROL SIGNAL.
(see 'Note:' above)
THE DEFAULT ESD CONFIGURATION IS "STAY PUT", DERIVED
FROM A N/O CONTACT (SIGNAL APPLIED).
FOR OTHER CONFIGURABLE ESD SETTING OPTIONS, REFER TO
PUBLICATION E170E INSTALLATION AND MAINTENANCE
INSTRUCTIONS.

BRAKE ENABLE CONNECTIONS


4 24 30 5

ROTORK CONTROLS LTD ROTORK CONTROLS INC Document No Issue No


This is an Associative Document that needs to be read in
www. .com BATH, BA1 3JQ ROCHESTER
conjunction with the appropriate Rotork Wiring Diagram. RWS511 1
ENGLAND NY 14624, USA

A4