PT PJB UNIT PELAYANAN PEMELIHARAAN WILAYAH TIMUR No. Dok.

:
FMH-04.3.7.685

PJB INTEGRATED MANAGEMENT SYSTEM Tgl. Terbit: 27 OKT 2016

FORM UJI Revisi : 00


UPHT
GENERATOR TRANSFORMATOR Halaman :

SITE : PLTU PAITON MANUFACTURE : BAODING TANWEI TAHUN QP No. P-01-3-1801 FU No.
UNIT : UNIT 9 INSPECTION : MEDIUM INSPECTION (ME) 2021 OEM Doc. No. :

SPESIFIKASI PERALATAN
NAMA PERALATAN : GENERATOR TRANSFORMATOR
TEGANGAN : 20 / 525 KV
DAYA : 800 MVA
VECTOR GROUP : YNd1
FREKUENSI : 50 HZ

GT MECHANICAL PROTECTION (Trip)


NO TEST CIRCUIT INDICATION RESULT
Relay Bucholz PROTECTION ROOM Trp_HvyGas_MT (PHA_MR5)
1 Terminal : 3J (39-41) CCR/ DCS ROOM GE-TR BUCHOLZ TRIP OK
Location : tekan penuh
Pressure Relief valve 1 PROTECTION ROOM Trp_PresRlf_MT (PHA_MR7)
2 Terminal Number : 3J (17-19) CCR/ DCS ROOM GE-TR PT RELIEF TRIP OK
Location : tarik tuas test
Pressure Relief valve 2 PROTECTION ROOM Trp_PresRlf_MT (PHA_MR7)
3 Terminal Number : 3J (25 - 27) CCR/ DCS ROOM GE-TR PT RELIEF TRIP OK
Location : tarik tuas test
Pressure Relief valve 3 PROTECTION ROOM Trp_PresRlf_MT (PHA_MR7)
4 Terminal Number : 3J (47 - 49) CCR/ DCS ROOM GE-TR PT RELIEF TRIP OK
Location : tarik tuas test
Oil Temperature 1 PROTECTION ROOM Trp_OilTemp_MT (PHA_MR9)
5 Terminal Number : 3J (5 - 7) CCR/ DCS ROOM GE-TR OIL TEMP HIGH TRIP (98°C) OK
Location : putar dial - 98
Oil Temperature 2 PROTECTION ROOM To PLC control cooling system Auto Trip
6 Terminal Number : 3J (9 - 11) CCR/ DCS ROOM OK
Location : putar dial - 98
Winding Temperature PROTECTION ROOM
7 Terminal Number : 3J (13 - 15) CCR/ DCS ROOM GE-TR WINDING TEMP HIGH TRIP (136°C) OK
Location : putar dial - 136

GT MECHANICAL PROTECTION (Alarm)


NO TEST CIRCUIT INDICATION RESULT
Relay Bucholz PROTECTION ROOM Alm_LvyGas_MT (PHA_MR15)
1 Terminal : 2J (1-2) CCR/ DCS ROOM GE-TR BUCHOLZ OK
Location : tekan setengah
Oil Level Low PROTECTION ROOM Alm_OilLev_MT (PHA_MR16)
2 Terminal Number : 2J (3-4) CCR/ DCS ROOM GE-TR OIL LEVEL ABNORMAL OK
Location : jumper terminal
Oil Level High PROTECTION ROOM Alm_OilLev_MT (PHA_MR16)
3 Terminal Number : 2J (3-5) CCR/ DCS ROOM GE-TR OIL LEVEL ABNORMAL OK
Location : jumper terminal
Pressure Relay PROTECTION ROOM Alm_Pressure_MT (PHA_MR11)
4 Terminal Number : 2J (9 - 10) CCR/ DCS ROOM GE-TR OIL PRESS OP OK
Location : jumper terminal
Oil Temperature 1 PROTECTION ROOM Alm_OilTemp_MT (PHA_MR14)
5 Terminal Number : 2J (12 - 13) CCR/ DCS ROOM GE-TR OIL TEMP HIGH (88°C) OK
Location : putar dial - 88
Oil Temperature 2 PROTECTION ROOM Alm_OilTemp_MT (PHA_MR14)
6 Terminal Number : 2J (14 - 15) CCR/ DCS ROOM GE-TR OIL TEMP HIGH (88°C) OK
Location : putar dial - 88
Winding Temperature PROTECTION ROOM Alm_ WdgTemp_MT (PHA_MR14)
7 Terminal Number : 2J (16 - 17) CCR/ DCS ROOM GE-TR WINDING TEMP HIGH (126°C) OK
Location : putar dial - 126

ACCEPTED/REWORK/REPLACE
RECOMMENDATION
(by Quality Control)

MEASURING TOOLS AVO METER

DESCRIPTION TESTED BY COORDINATOR QUALITY CONTROL WITNESS

SUBAGIO

BAHRUDDIN RIF'I A F
NAME DEDI TRICAHYONO MUJIANTO
HADYAN P PUTRA

FATHOL ARIFIN

SIGNATURE

DATE
PT PJB UNIT PELAYANAN PEMELIHARAAN WILAYAH TIMUR No. Dok.
:
FMH-04.3.7.685

PJB INTEGRATED MANAGEMENT SYSTEM Tgl. Terbit: 27 OKT 2016

FORM UJI Revisi : 00


UPHT
GENERATOR TRANSFORMATOR Halaman :

SITE : PLTU PAITON MANUFACTURE : XI'AN XD TRANSFORMER TAHUN QP No. P-01-3-1801 FU No.
UNIT : UNIT 9 INSPECTION : MEDIUM INSPECTION (ME) 2021 OEM Doc. No. :

SPESIFIKASI PERALATAN
NAMA PERALATAN : UNIT AUXILIARY TRANSFORMATOR
TEGANGAN : 20 / 6.3 KV
DAYA : 40 MVA
VECTOR GROUP : Dyn11yn11
FREKUENSI : 50 HZ

GT MECHANICAL PROTECTION (Trip)


NO TEST CIRCUIT INDICATION RESULT
Relay Bucholz PROTECTION ROOM Trp_HvyGas_MT (PHB_MR5)
1 Terminal : 3J (1-3)/(5-7) CCR/ DCS ROOM UAT BUCHOLZ TRIP OK
Location : tekan penuh
Pressure Relief valve 1 PROTECTION ROOM Trp_PresRlf_MT (PHB_MR6)
2 Terminal Number : 3J (9-11) CCR/ DCS ROOM UAT PT RELIEF TRIP OK
Location : tarik tuas test
Pressure Relief valve 2 PROTECTION ROOM Trp_PresRlf_MT (PHB_MR6)
3 Terminal Number : 3J (13 - 15) CCR/ DCS ROOM UAT PT RELIEF TRIP OK
Location : tarik tuas test
Oil Temperature 1 PROTECTION ROOM Trp_OilTemp_MT (PHB_MR8)
4 Terminal Number : 3J (17 - 19) CCR/ DCS ROOM UAT PT RELIEF TRIP OK
Location : putar dial - 105
Oil Temperature 2 PROTECTION ROOM Trp_OilTemp_MT (PHB_MR8)
5 Terminal Number : 3J (21 - 23) CCR/ DCS ROOM GE-TR OIL TEMP HIGH TRIP (105°C) OK
Location : putar dial - 105
Winding Temperature PROTECTION ROOM Trp_WdgTemp_MT (PHB_MR7)
6 Terminal Number : 3J (25 - 27) CCR/ DCS ROOM GE-TR OIL TEMP HIGH TRIP (115°C) OK
Location : putar dial - 115

GT MECHANICAL PROTECTION (Alarm)


NO TEST CIRCUIT INDICATION RESULT
Relay Bucholz PROTECTION ROOM Alm_LvyGas_ST (PHB_MR15)
1 Terminal : 2J (1-2) CCR/ DCS ROOM UAT BUCHOLZ OK
Location : tekan setengah
Oil Level Low PROTECTION ROOM Alm_OilLev_ST (PHB_MR18)
2 Terminal Number : 2J (3-4) CCR/ DCS ROOM UAT OIL LEVEL ABNORMAL OK
Location : jumper terminal
Oil Level High PROTECTION ROOM Alm_OilLev_ST (PHB_MR18)
3 Terminal Number : 2J (5-6) CCR/ DCS ROOM UAT OIL LEVEL ABNORMAL OK
Location : jumper terminal
Pressure Relay PROTECTION ROOM Alm_Pressure_ST (PHB_MR10)
4 Terminal Number : 2J (6- 7) CCR/ DCS ROOM UAT OIL PRESS OP OK
Location : jumper terminal
Oil Temperature 1 PROTECTION ROOM Alm_OilTemp_ST (PHB_MR16)
5 Terminal Number : 2J (11 - 12) CCR/ DCS ROOM UAT OIL TEMP HIGH (95°C) OK
Location : putar dial - 95
Oil Temperature 2 PROTECTION ROOM Alm_OilTemp_ST (PHA_MR16)
6 Terminal Number : 2J (12 - 13) CCR/ DCS ROOM UAT OIL TEMP HIGH (95°C) OK
Location : putar dial - 95
Winding Temperature PROTECTION ROOM Alm_ WdgTemp_ST (PHB_MR17)
7 Terminal Number : 2J (13 - 14) CCR/ DCS ROOM UAT WINDING TEMP HIGH (105°C) OK
Location : putar dial - 105

ACCEPTED/REWORK/REPLACE
RECOMMENDATION
(by Quality Control)

MEASURING TOOLS AVO METER

DESCRIPTION TESTED BY COORDINATOR QUALITY CONTROL WITNESS

SUBAGIO

BAHRUDDIN RIF'I A F
NAME DEDI TRICAHYONO MUJIANTO
HADYAN P PUTRA

FATHOL ARIFIN

SIGNATURE

DATE