62305-1
General Principles
62305-2
Risk Management
62305-3 62305-4
Physical damage Electrical- and
and life hazard electronic systems
• According to the ABI figures the UK Insurance Industry pays out on average
£8.65 Billion a year in Commercial & Domestic claims (2007-2015)
• There is no reason to assume the UK differs that greatly from the EU figures
so 31% of this can be ‘assumed’ to lightning & surge related
Risk
Analyse risks
Quantify risks
Total risks
Control risk Accept
risk
Prevent Reduce Insure
(take protection
measures)
Source of
damage
Type of Type of
loss damage
BS EN 62305-2
Source of
Lightning current is the primary source of damage. damage
BS EN 62305-2
Types of damage which may occur as a result of lightning strikes: Source of
damage
Type of
D1: Injury to living beings damage
LEMP
D3: Failure of electrical and electronic systems due to LEMP
BS EN 62305-2
“Each type of damage, alone or in combination with others, Source of
may produce a different consequential loss in the object to damage
regarded as loss of
Water
Gas
Risk
Risk Types
BS EN 62305-2
10-4
gas
Risk
Risk Types
Risk components
Risk
Current
Water
Gas
R1 R2 R3 R4
Each risk consists of several risk components
= = = =
R1 = RA+ RB+ RC R2 = RB+ RC+ R3 = RB+ RV R4 = RA+ RB+ RC
+ RM+ RU+ RM+ RV + + RM+ RU+
RV+ RW+ RZ RW+RZ RV+ RW+ RZ
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 13
Overview of risk component RX
LEMP
RA RB RC
S1
RZ S4 RM
Rx S2
LEMP
S3
RW RV RU
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 14
Risk component RB - Fire
Source of damage S1
S1
RB =fire
Physical damage due to
dangerous sparking inside
the structure causing fire
and explosion.
RM=overvoltage
(LEMP)
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 16 30.09.08 / S6215e
Risk component RV - Fire
Source of damage S3
RV = fire
Physical damage due to
lightning current injected
in supply lines entering
the structure.
S3
Possible types of loss:
L1: Loss of human life
L2: Service to the
public
L3: Cultural heritage
L4: Economic loss
RZ = overvoltage
Failure of internal systems
caused by overvoltages
induced on incoming lines
and transmitted to the
structure.
S4
Possible types of loss:
L1: Loss of human life
(structures with
risk of explosion,
hospitals)
L2: Service to the
public
L4: Economic loss
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 18 30.09.08 / S6219e
Risk composition
Risk
Risk types
Risk components
Risk of damage
RX = NX • PX • LX
NX PX LX
Number of dangerous Probability of Consequent loss
events damage
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 20 30.09.08 / S6220e
Lightning Ground Flash Density (NG)
per square kilometre per year
No
R > RT Structure protected
Yes
Yes Yes
LPS installed? SPM installed?
Calculate new values
of risk components No
No No
RA+B+U+V > RT
Yes
Install relevant Install relevant Install other
type of LPS SPM protection
measures