Professional Documents
Culture Documents
Series Connection
Connection Guide
Guide
Step 1 Checking the Equipment Required for Connection Supported units (PLC)
* If you are using the vision system monitor function, update this unit’s firmware to version 3.2 or later. If you are not using this function, version 2.0 or later of the
firmware is sufficient.
Connection diagram Connect the KV-7500 to the CV-X200/X100 Series as shown below.
KV-7500 CV-X200/X100 Series
STP/UTP cable
One point
You can use an Ethernet switch to connect multiple CV-X200/X100 Series units.
CV-X200/X100 Series
NE-Q05(P)
KV-7500
CV-X200/X100 Series
CV-X200/X100 Series
2
CV-X200/X100 Series Connection Guide
Connection diagram
When using the VT5-W07(M) or when connecting multiple CV-X200/X100 Series units
VT5-W07(M) KV-7500 CV-X200/X100 Series CV-X200/X100 Series
NE-Q05(P)
One point
Connecting the CV-X200/X100 Series to the VT5 Series enables the following functions.
3
CV-X200/X100 Series Connection Guide
1 On the setup screen of the CV-X100 Series, select [Global], [Communications & I/O], and then
[EtherNet/IP].
4
CV-X200/X100 Series Connection Guide
2 On the setup screen of the CV-X100 Series, select [Global], [Communications & I/O], and then [Network].
Configure the CV-X100 Series network settings.
IP Address 192.168.000.020 (Ensure that the IP address is not the same as that of the KV-7500.)
Delimiter CR (default)
3 After you finish configuring the settings, restart the CV-X100 Series.
When the CV-X100 Series restarts, the settings changed in steps 1 and 2 are applied.
One point
Changes to the [EtherNet/IP] and [Network] settings will be applied after the CV-X200/X100 Series restarts.
5
CV-X200/X100 Series Connection Guide
1 Select [Add Tools] for the CV-X100 Series, and then use the [Tool Catalog] to set the measurement
conditions.
When setting the measurement method to “Edge Width”
2 Use [Output Settings] for the CV-X100 Series to set the output.
6
CV-X200/X100 Series Connection Guide
1 Under [All Programs], click [KEYENCE KV STUDIO Ver.8G (or later)], start [KV STUDIO Ver.8G (or
later)], and then select the KV-7500 for the corresponding PLC.
When connecting the KV-7500 and the CV-X100 Series via EtherNet/IP™, use KV STUDIO version 8 or later.
2 On the [Tool(T)] menu, click [Unit Editor(U)] to open the Unit Editor.
One point
When connecting through the KV-EP21V/NC1EP, add the EtherNet/IP unit (KV-EP21V/NC1EP) to the unit
configuration on the [Select unit(1)] tab. For the KV-7500/5500, this operation is not necessary.
7
CV-X200/X100 Series Connection Guide
Ethernet • Ensure that the IP address is not the same as that of the CV-X100 Series.
setting precautions • Enter the same subnet mask setting as that on the CV-X100 Series.
Click this.
8
CV-X200/X100 Series Connection Guide
6 The [Initial adapter settings] dialogue box is displayed. Enter the IP address, and then click [OK].
7 Save and close the EtherNet/IP settings and the Unit Editor.
One point
You can use the following procedure to automatically register the comments for the devices related to
communication with the CV-X200/X100 Series, which greatly reduces the man-hours spent entering comments.
9
CV-X200/X100 Series Connection Guide
List of mnemonics
❶ LDP @MR000
MOV #1 W0F4
❷ LDP @MR000
AND B02
OR B060
ANB B00
❸ ANB B01
OUT B060
❹ LDP B03
MOV.L W012 DM0
LD B03
OUT B063
One point
When writing a ladder program, you can intuitively make inputs using the RT edit function.
RT edit: During key input, the items that can be selected will be searched for and displayed automatically when
device comments are entered directly.
Example) Inputting the CV-X100 Series[1]. Cmd ready (B02) normally open contact
10
CV-X200/X100 Series Connection Guide
* T he above table refers to the case when the leading devices of the CV-X100 Series are set to B00 and W00 in KV STUDIO.
If the leading devices are changed, the assigned device numbers will be changed accordingly.
One point
Store a communication command number for control (see page 16) in the W0F4 (CV-X100 Series[1]. Cmd
number) command input area to control the CV-X100 Series.
One point
Data will also be stored in the W012 (CV-X100 Series[1]. InDat(0048)) result data area when an I/O terminal or
an operating panel is used to perform triggering.
In this case, no program (steps ➊ and ➋) for generating the triggers of the above ladder program (see page
10) is necessary.
11
CV-X200/X100 Series Connection Guide
STP/UTP cable
2 Check that the “NS” and “LINK” LEDs of the KV-7500 are lit or flashing in green.
One point
The following are possible causes of the KV-7500 “NS” and “LINK” LEDs not being lit in green.
If the “NS” LED is not lit in green
• A setting is incorrect Alternatively, the settings were not transferred correctly.
à Check steps 2 to 4 again.
• IP addresses are duplicated.
àC heck whether the set IP address is a duplicate of another IP address. If using an
Ethernet switch or a similar device, check whether other equipment with the same
IP address exists.
12
CV-X200/X100 Series Connection Guide
If DM0 is updated each time @MR0 changes from off to on, communication is being performed normally.
If “Decimal Point” is set to “Fixed-point” in the [Global] settings (see page 4), the CV-X100 will multiply the measured value by
1000 before sending the data. In the above example, the actual measured value is 306.012.
13
CV-X200/X100 Series Connection Guide
14
CV-X200/X100 Series Connection Guide
If the amount of measured data of the CV-X200/X100 Series increases and the size of the data transferred to the KV-7500 becomes larger (496 bytes or
more), you can change the size of the data to transfer during cyclic communication.
* The cyclic communication data size can be changed to a setting between 248 and 1436 bytes (default: 496 bytes).
15
CV-X200/X100 Series Connection Guide
The following commands can be used to switch the trigger input and run state of the CV-X100 Series.
To use the above command numbers, enter them into CV-X100 Series[1]. Cmd number.
One point
For commands that require the command number and parameters such as the switch inspection setting
command, enter the parameters starting with CV-X100 Series[1]. Cmd param1.
In addition, for commands that have multiple return values such as the read inspection settings command,
the result will be output starting at CV-X100 Series[1]. InDat(0048).
One point
There is a command that stops the CV-X200/X100 Series from capturing images.
Pay attention to this fact when using commands from external equipment on a high-speed production line.
16
CV-X200/X100 Series Connection Guide
By connecting to a VT5 Series unit, you can display images that have been captured by the vision system controller.
You can also connect a mouse to the USB port on the front of the VT5 Series to check and change the vision system settings.
Connection diagram
Mouse VT5-W10 NE-Q05(P) KV-7500 CV-X200/X100 Series
USB connection
Ethernet connection
When using the vision system monitor function, check that the CV-X200/X100 firmware is version 3.2 or later.
2 Select the “Display area size” and the “Display mode,” and then click “Vision system monitor setting.”
You can select the “Display area size” from the options shown below.
• 800 × 600
• 640 × 480
• 400 × 300
• 320 × 240
* “800 × 600” cannot be used on the VT5-W07(M).
Select this check box when you are connecting a mouse to the VT5 Series to operate the CV-X200/
X100 Series. (This is only enabled when the “Display area size” is “800 × 600” or “640 × 480.”)
17
CV-X200/X100 Series Connection Guide
3 Enter the IP address of the CV-X200/X100 Series that you will connect and the monitor number of
the vision system monitor display that you will use.
Sensor 0 settings
IP address 192.168.0.20
4 Connect the USB cable or the LAN cable to the VT5 Series. Then, select [Send Screen Data from PC
to VT(S)] on the [Communication(C)] menu to transfer the screen data.
One point
The vision system monitor’s dedicated system screen supports the following functions with a dedicated operation panel.
■ Operation panel area ... The following operations, such as switching the screen’s display, are possible.
(1) Connection destination information ... IP address of the vision system whose image is displayed
■ Remote desktop area
(2) Connection destination selection ... Select the connection destination from the vision systems
... Displays the vision system’s monitor
that have been registered for monitoring.
screen or setup screen
(3) Screen display selection ... Switch between the one-screen and four-screen displays.
(4) Search ... Switch to the screen for searching for vision systems connected via Ethernet.
(5) Save Image ... Save an image of the remote desktop area.
You can use the following methods to display the vision system monitor’s dedicated system screen.
A Place a switch to which the “Call up system screen” B Click [Tool] under [System Mode], and then click [Vision
function has been assigned. System Monitoring].
Double-click this.
18
CV-X200/X100 Series Connection Guide
By using a USB cable to connect the touch panel display VT5 Series and the PC, you can send and receive the CV-X200/X100 Series
setting data through the VT5 Series.
Connection diagram
USB connection
1 Turn on the CV-X200/X100 Series, and then switch the VT5 Series to Run mode.
2 In VT STUDIO, click [Remote Ethernet Tool(E)] on the [Tool(T)] menu to start the remote Ethernet
tool.
3 In the CV-X Series simulator, set the leading byte of the communication destination’s IP address to
“127” and the last three bytes to the actual IP address of the vision system.
Example) If the IP address of the CV-X200/X100 Series is “192.168.0.20,” set the IP address in the simulator to “127.168.0.20.”
4 Send and receive the setting data in the CV-X Series simulator.
One point
• You cannot start two or more remote Ethernet tools at the same time. Also, you can only connect one
VT5 Series unit and the setting software at the same time.
• Use a USB cable to connect the VT5 Series and the PC.
19
www.keyence.com
Copyright (c) 2016 KEYENCE CORPORATION. All rights reserved. KVCVX2/1Setting-WW-AG-GB 1066-1 600J08