You are on page 1of 15

Legionella Pneumophila in an

Ammonia Plant Cooling Tower


An outbreak of Legionella pneumophtta bacterial infection that claimed the lives of 30 people in
Bovenkaspel, The Netherlands in 1999 prompted KemiraAgro Rozenburg to sample its cooling
tower water at regular intervals to determine the presence of Legionella bacteria. Results were
consistently negative until a sudden outbreak was detected in the spring of 2000. Safety measures
were implemented immediately, the cause of the outbreak was discovered, and measures were
subsequently taken to prevent a reoccurrence.

W. D. Verduijn
Kemira Agro Rozenburg B.V., Rozenburg, The Netherlands

Introduction wt. % FeC13 solution).

E
emira is a multinational company with its
headquarters in Helsinki, Finland. Active in World Record Ammonia Production
various branches of the chemical industry,
Kemira Agro Oyj is its largest subsidiary and responsi- Rozenburg's ammonia plant was designed by C.F.
ble for about 35% of the turnover. Braun and Co. of Alhambra, CA, now Kellogg Brown
Kemira Agro Oyj affiliate Kemira Agro Rozenburg and Root (see Figure 1). Design capacity was 1,350 tpd
B.V. in Rozenburg, The Netherlands, operated until (1,500 stpd). The first ammonia was produced in late
recently a 1,700 metric ton per day ammonia plant. The 1968.
same site encompassed a 1,200 tpd (100%) nitric acid The plant, at that tune owned by Exxon Chemicals,
plant, a 700 tpd urea plant, a 1,600 tpd CAN plant, a was opened in 1969 by H.R.H. Prince Bernhard of the
800 tpd UAN plant, a 60 tpd liquid fertilizer specialties Netherlands (see Figure 2). Kemira took over in 1985.
plant, and a 300 tpd liquid CO2 plant. All these plants In the period 1969-1990 the plant produced altogeth-
were closed in December 2000 due to overproduction er 10 million metric tons of ammonia. This turned out
on the European market. to be an officially recognized world record for a single
Kemira continues operation on the Rozenburg site train ammonia plant: see Figure 3 (Fertilizer
with a 60 tpd hydrogen peroxide plant and a facility for International, 1990). On October 3, 2000, the 15 mil-
the production of 400 tpd water treating chemicals (40 lionth ton was produced. We believe this is a world

AMMONIA TECHNICAL MANUAL 130 2002


Figure 1. Rozenburg ammonia plant.

Figure 2. H.R.H. The Prince of the Netherlands officially


opens the plant in 1969.

AMMONIA TECHNICAL MANUAL 131 2002


record as well for a single train ammonia plant. It has a concrete basin which both serves for retaining and
been officially recognized as such by Guinness in storing the cooled water. The basin is subdivided by
London (see Figure 4), and we challenge the world internal partitions into nine compartments. Each of
ammonia industry herewith to refute and beat it. these compartments can be isolated and drained while
As mentioned before, the plant was closed in the others are in operation. Finally, the cooled cooling
December 2000. That tragic event is shown in Figure 5. water is pumped to the process plants again.
The cooling tower is shown in Figure 8.

Sharing the Experience with AlChE


Chemical Treatment of Cooling Water
Both Exxon and Kemira have always been support- (before 1993)
ive of sharing relevant technical and safety experience
with the world ammonia industry. In most cases that In the early decades of the site, chemical treatment of
was done via articles presented at the AIChE Symposia the cooling water was as follows:
on Safety in Ammonia Plants and Related facilities Sulfuric acid was added to adjust the pH to 6.8-7.0.
(Ruziska, 1972; Osman, 1975; van Eijk,1975; The ami was to minimize deposition of calcium car-
Verduijn, 1979, 1983, 1993, 1996, 2000; Mertens and bonate scale on the waterside of the cooling water heat
Kolff, 1984; Kolff, 1986; Mertens, 1990; Song et al, exchangers.
1992). Polyphosphate and zinc chloride were added to min-
imize corrosion of the cooling water heat exchangers.
Rozenburg's Cooling Tower Chlorine, and later sodium hypochlorite, was added
to counteract the formation of any biological growth
The cooling water system of the Rozenburg fertilizer (bacteria, slime and algae) that can cause fouling,
complex is shown in Figure 6. obstruction, or damage in the cooling water system.
Some 18,000 m3/h treated cooling water with a tem- A nonoxidizing biocide, finally, was also added to
perature of typically 21°C (70°F) is pumped from the counteract biological growth.
basin of the cooling tower to the various plants on the
site. The ammonia plant takes the majority of the cool- Chemical Treatment of Cooling Water
ing water capacity. The warm cooling water, with a typ- (after 1993)
ical temperature of 38°C (100°F), is subsequently
divided into 9 more or less equal streams. Each of these As use of zinc chloride came under environmental
warm streams flows via a riser to the top of two of the pressure, it was decided to switch to Nalco's All
18 cooling tower cells that are arranged in two rows of Organic Program in 1993.
nine.
Figure 7 shows that each cell is equipped with a dis- No acid addition
tribution system that takes care of a proper water flow
division across the horizontal surface area of that cell. Acid is no longer added. Instead, the treatment pro-
The incoming water is directed by main gutters to open gram leads to a relatively high pH of about 8.9 in the
distribution gutters. Further flow division is realized by hot return cooling water; this pH is controlled by the
means of numerous sprayheads in the bottom of these purge flow.
distribution gutters. Each sprayhead drops its water on
splash plates. The warm water droplets subsequently Corrosion protection
cascade down the wooden tower with timbered and
plastic internals, where they meet the countercurrent Zinc chloride is no longer added either. Instead, a
flow of cold air. A small part of each droplet evapo- mix of various predominantly organic chemicals is
rates. The required heat of evaporation cools that used: Nalco 23210 (a mix of certain chemicals to pre-
droplet down. The thus cooled cooling water falls into

AMMONIA TECHNICAL MANUAL 132 2002


K!-X;oki> BOKR
GUINNESS
WORLD RECORDS
i » «.H- V *faTiad. il BiljJ* «il
;ilth dig 1 1 K isioMr I Ir>x1 1 * rMw«

As at 3 October 200Q,
the ammonia plant of
Kemira Agro Rozenburg B. V.
in Rozenburg, Netherlands
produced a world record
15 millions tonnes of ammonia

*&Zv?vfsX£vtïîï:

Figure 3.10 million metric tons of ammonia produced Figure 4.15 million metric tons of ammonia produced
Nov. 14,1990. Oct. 3,2000.

Figure 5. Final shutdown of the ammonia plant on Dec. 18,2000.

AMMONIA TECHNICAL MANUAL 133 2002


hot return

-38 t L-Q-180 Gcal/h — Q-120


plume

COOLING TOWER HN03 PLANT


9x2-18 cells CAN PLANT
Moke-up water NH3 PLANT UREA PLANT
duty 300 Gcal/h L-C02 PLANT
700 m3/h UTIL PLANT

air • • air * leak *

150 m3/h
-21 °C
118000 m3/M
purge

cooled cooling water


-H-*

pump

Figure 6. Rozenburg's cooling water system.

AMMONIA TECHNICAL MANUAL 134 2002


to atmosphère

plastic
dropte«
separators

spray head

fffffffftff
fffffffffff > «_ -. • - ^ -
fffffffffff spmnpHn
timbered \fffffffffff
or plastic internals

variable M«t vanes

cold

basin
«tor
slide valve

Figure 7. One of the 18 cooling tower cells.

AMMONIA TECHNICAL MANUAL 135 2002


vent formation of notably inorganic deposits), Nalco overall bacteria concentration in cooling water in
7348 (biodispersant; a "detergent" to prevent slime for- February 1999 smaller than the detection limit of
mation), and Nalco 73136 (polyphosphate, for addi- 1,000 cfu/mL. That is a typical figure for our cooling
tional corrosion protection, if necessary). water. In other words: the overall bacteria population as
measurable with the above sampling technique was at
Sodium hypochlorite (NaOCI) that time well under control.

This is used to counteract the formation of biological


growth (bacteria, slime, algae), and enhanced by the The Legionella Pneumophila Bacterium
addition of Nalco 1338 which contains bromine. Both
are added in the suction of the circulation pumps. Although'not many people were aware of it in 1999,
A typical chemical analysis of the makeup water and cooling water can also contain a bacterium named
the hot return water to the Rozenburg cooling tower in Legionella. This bacterium can cause the so-called
February 1999 is shown in Figure 9. Note that the tar- Legionnaire's disease, an infection of the lungs that is
get concentration of free chlorine is 0.1-0.3 ppmwt in a form of pneumonia. There are over 30 different
the hot return flow. The use of NaOCI is limited by species of Legionella bacteria. Legionella pneumophi-
Rozenburg's operating permit to a certain quantity per la is the most common species that causes the disease.
year. Infection is caused by inhaling water in the form of an
aerosol contaminated with Legionella pneumophila
bacteria. Legionella pneumophila bacteria exist in 14
Cooling Water Bacteria in Genera! different sero-types, of which sero-type 1 is probably
responsible for 80% and sero-type 6 probably respon-
As stated above, addition of sodium hypochlorite to sible for the remaining 20% of the disease cases. The
cooling water is aimed at combating bacterial growth. other sero-types are believed to be far less dangerous.
Due to the favorable temperature of cooling water, bac-
teria in there namely tend to multiply easily, which is Symptoms
undesirable from a standpoint of system efficiency
(slime causes heat-transfer reduction of exchangers), Incubation time is 2-10 days. Symptoms of the dis-
corrosion protection (under slime), and health (possible ease in its initial stage are much like those of the flu.
infection). There are many types of bacteria present in After one or two days, though, pneumonia-like symp-
cooling water. toms may appear. Some individuals may only have
flu-like symptoms, while with others the disease can
Sampling for bacteria in general be fatal.

The presence of these bacteria is determined by Who are at risk?


measuring their overall concentration. This is a practice
that has been in use for decades, and is applied by Many people appear to be resistant to the disease.
every industrial cooling tower operator. This determi- Some have a lower resistance. The risk of developing
nation, via a dip slide at 37°C (99°F) on-site, takes the illness is increased by factors like underlying med-
about 2 days. The thus measured concentration is ical problems (respiratory diseases, diabetes and so
expressed in colony forming units per milliliter on), heavy smoking, heavy drinking, and age (older
(cfu/mL). Detection limit is 1,000 cfu/mL; the problem persons are more likely to get the disease).
limit 10,000 to 100,000 cfu/mL.
Pontiac fever
Typical analysis
The same bacterium can also cause the flu-like dis-
The typical analyses of Figure 9 shows a measured ease Pontiac fever. Full recovery of Pontiac fever with-

AMMONIA TECHNICAL MANUAL 136 2002


Figure 8. Rozenburg's cooling tower.
make up water hot return (actual) hot return (target)

PH 7.9 8.6 8.8 - 9.0


conductivity (25 °C) uS/cm 670 2060
calcium hardness ppmCaCOS 180 540
free chlorine ppmCl2 - 0.13 0.1-0.3
free bromine ppmBr2 - 0.09
chloride ppmCl 90 380
iron ppmFe 0.05 0.33 <0.5
concentration factor . - 3.0 3.3
bacteria count (37 °C) cfu/ml - <1000 <1000

Figure 9. Typical analysis of the cooling tower.

Figure 10. Dimensions of the cooling tower plume can be substantial.

AMMONIA TECHNICAL MANUAL 137 2002


out antibiotics occurs in two to five days. held in February of that year. Cause turned out to be
contamination with the bacterium Legionella pneu-
Multiplication conditions mophila, reportedly as a result of a whirlpool demon-
stration.
Warm stagnant water of a pH between 5 and 9 pro- This tragedy urged Kemira Agro Rozenburg to sam-
vides ideal conditions for growth of the organism. ple its water systems for the presence of the bacterium.
Multiplication is possible between 20 and 50°C (68 and The necessity was further supported by a Legionella
122°F), and optimal between 32 and 40°C (90 and incident at a neighboring industry, and by an article in
105°F). The presence of rust, scale, slime and algae can Chemical Engineering during that same period
promote that growth (Nalco Bulletin; National Center (Chemical Engineering, 1999; Huysmans, 1999) men-
for Genome Resources, 1998; Huysmans, 1999). tioning that at least 14% of the cooling towers in the
U.S. contain the bacterium, that the fatality rate of
Standard test for Legionella bacteria infected people is 10-20%, and that 1,000 of the
15,000 infections per year in the U.S. end in death.
The general alimentary medium used to determine
the overall bacteria concentration in cooling water (see
above) is not suitable for Legionella bacteria: they do Safety Showers Sampled in 1999
not grow on this medium. Therefore, their isolation and
determination requires a special technique. This tech- One of the first actions was sampling the water in the
nique, in an outside microbiological laboratory, safety showers of Kemira Agro Rozenburg for the pres-
involves incubation and produces preliminary results ence of Legionella bacteria.
after 3, 5 and 7 days, followed by a final result after 10
days. The detection limit of the technique for both city Method of sampling
water and cooling water is 25 cfu/L (per liter, not per
milliliter, as in the case of bacteria in general). The A sampling method adopted by Nalco was applied,
legal safe limit for city water in the Netherlands is 50 which requires a defined (1 min. long) water purge
cfu/L, irrespective of the Legionella type. There is no before sampling. The standard sampling test described
legal safe limit for cooling water in The Netherlands above was used. As mentioned before, its detection
yet; some suggest 100 cfu/L (Huysmans, 1999), but limit in city water is 25 cfu/L, whereas 50 cfu/L is the
the discussion on this subject has not been finalized legal safe limit in city water.
yet.
A rapid Legionella test is also available. It is based Result
on a colorimetric determination of certain chemicals
specific in Legionella bacteria. The test requires 8 h, Much to our dismay, we found that those safety
(24 h including shipment of the sample to a foreign showers located inside buildings showed unacceptably
laboratory), but its detection limit is only 600 cfu/L in high concentrations of Legionella of the dangerous two
clean water and only 2,100 cfu/L in turbid water. Also, sero-groups 1 and 6. One of these showers was the lab-
this test measures the total of dead and viable oratory safety shower. We could have predicted that:
Legionella bacteria, whereas the standard test measures the laboratory sometimes is at, and sometimes is above,
viable Legionella bacteria only. room temperature, and the safety shower is seldom or
never used. The measured concentration of sero-groups
1 and 6 together of about 3,000 cfu/L was characterized
Tragedy in Bovenkarspel as "moderately unsafe", and was also unlawful. The
other (four) safety showers were located inside the
CAN production building. Temperatures there usually
In 1999 about 30 people died after attending a flower run well over 20°C (68°F), and sometimes up to 40°C
fair in Bovenkarspel, The Netherlands. The fair was (104°F). Also, these showers are seldom or never used.

AMMONIA TECHNICAL MANUAL 138 2002


Only sero-group 6 was found here: the measured con- April 2000 event
centrations at all four places in the CAN building, rang-
ing from 9,000 to 11,000 cfu/L, were characterized as On March 28, a sample was taken from the cold sup-
"moderately to highly unsafe"; of course, they were ply and hot return of the cooling water during full plant
also unlawful. operation. During the evening of April 4 (after 7 days),
the preliminary analyses results came in: 10,000 cfu/L
Corrective action of sero-type 1 ! Consternation all over! How could this
happen? Given the high analyses figure, there was no
All safety shower water systems running the risk of doubt in our minds that we had a problem. We also
(temporary) operation at temperatures over 20°C were realized that the plume of the cooling tower had been
systematically purged and sampled, until the discharging appreciable flows of aerosol into the
Legionella bacteria level was below 25 cfu/L. One atmosphere containing the dangerous Legionella sero-
shower showed in March 2000 still persistently 125 type 1 bacteria, and probably was still doing so. It was
cfu/L of sero-type 6. All of its many dead end parts not unlikely that employees had inhaled the aerosol:
were cut off. Thermal disinfecting (purging at a tem- the discharge point of the cooling tower fans is at a rel-
perature over 60°C) and chemical disinfecting (I atively low elevation, and, under certain weather con-
believe with NaOCl or H2O2) were necessary to get the ditions, the dimensions of the plume can be quite con-
Legionella bacteria in this specific shower finally siderable (see Figure 10).
under control. Other city water systems were investi-
gated as well. Finally, a weekly purging and monthly Operators inside
sampling program was set up.
The on-site operators that evening were immediately
Conclusion informed and retracted within the overpressurized main
control room as much as possible. Also, we realized
Despite their name, safety showers can turn out to be that, on that same day, the four Northern cells of the
deadly traps if they are seldom used and located in cooling tower were being cleaned; a check revealed
environments with temperatures well over 20°C. that this work had fortunately just been finalized.

Cooling Tower Sampled in 1999 and 2000 Legionella Crisis: Shutdown all Plants?

The cooling tower water was also sampled in 1999 All plants?
for the presence of Legionella bacteria. Again, the stan-
dard test described above was used for the determina- We seriously considered shutting down the ammonia
tion of the cfu/liter figure. plant, as well as the other plants on-site, with the objec-
tive of eliminating the plume of the cooling tower. This
Result in 1999 option would also permit us to thoroughly clean and
disinfect the cooling tower and cooling water system.
The first sample of cold supply and hot return was
taken March 25, 1999. Measured concentrations of Some plants?
Legionella bacteria were nil (or rather below the detec-
tion limit of 25 cfu/L). It was concluded that Legionella We also considered shutting down a number of plants
bacteria were absent. As from that date, the analyses on the site in order to reduce the cooling tower plume
were repeated each three months. None of these quar- and therefore the risk area.
terly checks revealed a problem.

AMMONIA TECHNICAL MANUAL 139 2002


Neither of the two Neighbors

It was finally decided to not execute any shutdown Neighboring companies were informed as well. A
for the following reasons. Firstly, the full plume reduc- press release was issued to make sure that involved
ing effect would only be reached after 24 h. Secondly, individuals who possibly had not been informed could
operators would have to carry out shutdown work in be informed via that message. It was felt that neighbor-
the plume. Thirdly, the effect of the Legionella com- ing communities were not at risk since they were locat-
bating actions mentioned below would, we hoped, be ed much further away from the cooling tower than 250
visible within 24 h. meters (275 yards); 250 meters is considered the max-
imum length the plume can reach under the worst cli-
matic conditions.
Legionella Combating Actions
Restricted area
Within 2 h from the receipt of above analysis result
of 10,000 cfu/L, the following actions were taken. The Northern wind sent the plume southbound. The
area covered by the plume was fenced off up to 250
Increased purge flow meters from the cooling tower, and was declared for-
bidden for personnel. This area included most of the
Firstly, the cooling water purge flow to the cold sea major plants, including the ammonia plant.
water canal, normally 150 m3/h, was increased to Special filter masks, the so-called P3SL filters, were
1,000 m3/h for a period of 12 h. This was realized brought in for those operators who had to enter the
under simultaneous increase of the makeup flow. As operating plants from time to time. These special
the volume of the circulating cooling water is approxi- mouth and nose masks effectively absorb aerosols.
mately 5,600 m3, this was an effective way to rapidly
purge the bacteria out of the system.
Information to the Authorities
More hypochlorite
The authorities were informed as well. It was obvi-
Hypochlorite solution addition to the system was ous that the incident, so short a time after the
increased from the regular 1.5 tpd to the maximum Bovenkarspel tragedy, caused considerable public
capability of the system of 4.0 tpd. After the purge flow commotion.
had been reduced again to the regular value of 150 First of all, it was emphasized to the authorities that
m3/h, this resulted in a free chlorine level of 2.0 ppm, the surrounding communities were not at risk. Also,
vs. a regular level of 0.1-0.3 ppm (see again Figure 9). our action plan was discussed with them. Thereafter,
on April 6, a joint press release on the situation was
issued by Kemira and the authorities (see above).
Actions with Respect to Health Finally, a member of Rozenburg's management team
appeared that evening together with a representative of
Information the authorities on local TV to assure the public that
they had nothing to fear. This step effectively eased the
Employees were informed the next morning (April 5) commotion.
via a bulletin of the situation and its possible risk. We have again concluded that a good relationship
Other personnel that had been on-site during the period with the authorities and the press is vital in times of cri-
from March 20 were informed as well. Kemira's med- sis.
ical service approached the employees who reported
sick during this period for an additional diagnosis.

AMMONIA TECHNICAL MANUAL 140 2002


Result of Legionella Combating Actions Standard test April 5

Rapid test April 5 How wrong we were! Of course, part of the cooling
water sample for the rapid test of April 5 was, as a cross
About 24 h after the start of the Legionella combat- check, also subjected to the accurate and more sensitive
ing actions, namely on April 5, a rapid Legionella test standard test. The result came in 10 days later: 38,000
as described above was executed to obtain an impres- cfu/L of the sero-types 1 and 10! Remember that this
sion of the result of these actions. The more sensitive sample was taken after cleaning of the four Northern
and accurate standard test would of course have been cells, after one day of increased purge flow, and after
preferable, but there was obviously no time to wait 10 one day of increased hypochlorite addition. We had
days for its result. The rapid test result, available April therefore to conclude in mid-April that the Legionella
6, showed that the Legionella concentration in cooling crisis had not been under control at all by the end of
water was still "positive". Kemira interpreted that out- April 5! On the contrary, it reached there its height!
come as 600 cfu/L (which was later found to be a not Finally, we confronted the laboratory executing the
fully correct interpretation). Apparently we started to rapid test with the big difference between their result
get the crisis under control! and the result of the standard test. They answered that
the detection limit of the rapid test is a function of the
Hypochlorite dosing turbidity of the cooling water, and that the outcome is
an indication only. We therefore also concluded in mid-
It was therefore decided to reduce the free chlorine April that there is an urgent need for a Legionella
level from the crisis value of 2.0 ppm to a medium analysis method that is both fast and accurate.
level of 0.5 ppm (the level before the crisis was 0.1-0.3
ppm).
Further Sampling Results
Rapid test April 6
Fortunately, the sample results via the standard
On April 6, another sample was subjected to the rapid method that arrived in subsequent days showed that the
test. The result, on April 7, was that the Legionella con- measures taken had nevertheless led to the desired
centration had dropped to below the detection limit of result (see Table 1).
the rapid test (usually 600 cfu/L). Apparently, the situ- After two months, no presence of Legionella bacteria
ation was under control. That same day, April 7, fenc- could be demonstrated anymore with the standard test,
ing was removed and a message was released that that has a detection level of 25 cfu/L. Note also that the
wearing P3SL filters in the area in question was no dangerous sero-type 1 was killed off effectively by the
longer necessary. We felt the crisis was over. measures taken. The increased free chlorine level of 0.5
ppm was maintained until June, after which it was
reduced gradually to the target value of 0.3 in

Table 1. Test Results

Sample Taken Rapid Test Result Result Standard Test Result Result Sero-type

Mar. 28, 2000 no yes Apr. 4 10 000 cfu/L 1


Apr. 5, 2000 yes Apr. 7 detected yes Apr. 15 38 000 cfu/L 1 +10
Apr. 6, 2000 yes Apr. 8 not detected yes Apr. 16 2 100 cfu/L 10
Apr. 7, 2000 yes Apr. 8 not detected yes Apr. 17 1 900 cfu/L 8 + 10
Apr. 13, 2000 yes Apr. 23 750 cfu/L 8

AMMONIA TECHNICAL MANUAL 141 2002


December. Legionella bacteria enter into the atmosphere in aerosol
form via the plume. This hypothesis of the probable
Cause of the Outbreak cause is strengthened by the phenomenon of high con-
centration of Legionella bacteria found in the sample
Initiation date taken on April 5: remember that on this day the four
Northern (windward) cells were cleaned.
The first sign of Legionella outbreak was found in
the cooling water sample taken March 28, 2000. The Cause
previous sample analyzed for Legionella was taken
three months earlier, and had shown the regular value Therefore, we believe that it is highly likely that our
of less than 25 cfu/L. It was therefore likely that the Legionella incident was caused by cooling tower clean-
problem had initiated between January 1 and March 28. ing.

Cell cleaning
Past Cooling Tower Cleanings
Investigation showed also that there was cleaning
work started in the cooling tower on March 20. This Personnel
cleaning work is part of a yearly spring program, cov-
ering cleaning all cells successively. The cleaning work As mentioned before, the cooling tower was cleaned
that started March 20 was executed in a few cells in the tens of times following the above procedure. It is there-
middle to northern section of the tower. To that end, the fore very likely that we have had temporary high con-
section in question was isolated from the rest of the centrations of Legionella bacteria in the cooling water
tower and shut down. Cleaning was necessary as slime before. To the best of our knowledge, that has never
and deposits had been building up in the water distri- lead to a case of Legionnaire's disease among our per-
bution system of the cooling tower top, giving rise to sonnel, although we do not rule out that it may have led
water maldistribution across the cell. The cleaning to cases of the less severe Pontiac fever.
operation was executed with waterhoses. Access to the The cleaning crew is a contractor crew. Although
area in question was achieved via the top of the tower they enter the cooling tower during cleaning, they do
by removing the droplet separators. The slime and not come in contact with the plume. However, their
deposits, loosened by the water jet, fall down into the cleaning jets bring other types of aerosols into the ah" in
basin, where they are removed every four years during which Legionella bacteria may be present. The crew
a scheduled cooling tower stop. As mentioned before, did not wear any protective face mask. As far as we
this cleaning operation is routine and takes place every know, none of the crew members has ever developed
spring. Legionnaire's disease. It was not investigated whether
the crew members are young or belong to other groups
Hypothesis that have a decreased probability of developing
Legionnaire's disease.
Although the free chlorine concentration in the cool-
ing water adequately kills the Legionella bacterium,
some local areas underneath the slime and deposit lay- Future Cooling Tower Cleanings
ers in the tower top can be shielded off effectively from
the water: Legionella concentrations can therefore eas- Monthly samplings
ily develop behind that layer. When removing the lay-
ers with a waterhose, these concentrations come loose From last year's incident on, cooling tower water
and enter the cooling water, where it takes a while will be analyzed for the presence of Legionella bacte-
before the Legionella bacteria are killed by the free ria monthly (quarterly since March 1999).
chlorine. During that time, certain quantities of

AMMONIA TECHNICAL MANUAL 142 2002


Controlling actions risk.
(5) Despite their name, safety showers can turn out to
At positive results, measures proven to be successful be deadly sources of Legionella contamination if they
have to be launched, such as to maximize purge flow are seldom used and located in environments with tem-
and hypochlorite dosage. peratures well over 20°C (68°F).
(6) In March 2000, Rozenburg's cooling water sud-
Extra entry permit denly and unexpectedly showed a serious outbreak of
Legionella bacteria of the dangerous sero-type 1.
The cooling tower will only be entered after making (7) The spread was effectively suppressed by a com-
sure that the Legionella bacterium is not present in the bination of a very high cooling water purge flow and a
water. That means that cleaning work can only be start- substantially increased hypochlorite dosage to the cir-
ed 10 days after sampling. culating cooling water.
(8) It is likely that the outbreak was caused by the
Stagnant water standard spring cleaning work in the cooling tower. It
has not lead to infections.
Since stagnant water facilitates the growth of (9) A good relationship with authorities and press has
Legionella, all cooling water pumps will be switched again proven to be vital in times of crisis.
on a weekly basis. (10) There is an urgent need for a Legionella analy-
Procedures for the yearly cleaning operation of our sis method that is both fast and accurate. The present
cooling tower internals during operation have been analysis time of 10 days frustrates an adequate deci-
updated. New measures are for instance: no more than sion-making process.
two cells per time, extra free chlorine, and full face
fresh air masks for the crew. Finally, the procedures for Literature Cited
integral cleaning of the cooling tower during a site stop
have been updated from a standpoint of avoiding Chemical Engineering, "Cooling Tower Makers Rally
Legionella contamination; these procedures include Against Legionnaires Disease," Editors page, p. 5
shutdown of the cooling tower, sludge removal from (Mar. 1999).
the basin, and re-startup. Fertilizer International, "Kemira Rozenburg Poses a
Challenge- Is this a Record?," No. 285; p. 37 (May
Observations and Conclusions 1990).
Huysmans, L., "Watersymposium '99: De
(1) The ammonia plant of Kemira Agro Rozenburg, Veteranenziekte," in Dutch, BetzDearborn N.V. (Apr.
started up late 1968 and shut down permanently in 13, 1999).
December 2000, has produced over 15 million metric Kolff, S. W, "Corrosion of a CO2 Absorber Tower,"
tons of ammonia in its lifetime. Ammonia Plant Safety & Related Facilities, Vol. 26,
(2) We believe that to be a world record for a single
AIChE, New York (1986).
train facility, and challenge the ammonia world to Mertens, P. R., and S.W. Kolff, "The Impact of
refute and beat it. Effective Quality Control," Ammonia Plant Safety &
(3) Legionella pneumophila bacteria of sero-types 1 Related Facilities, Vol. 24, AIChE, New York (1984).
and 6 can easily develop in various water systems in Mertens, P. R., "Unexpected Consequences of an
and around ammonia plants. When inhaled, they can Energy Conservation Project," Ammonia Plant Safety
lead to Legionnaire's disease. The fatality rate of & Related Facilities, Vol. 30, AIChE, New York
infected people is 10-20%.
(1990).
(4) Many people are resistant to the bacterium, but Nalco Bulletin, "Legionaires' Disease: Questions and
employees with medical problems (respiratory dis- Answers," 1-95.
eases, diabetes, and so on), heavy smokers or heavy National Center for Genome Resources, "Legionella
drinkers, as well as older employees, are at increased

AMMONIA TECHNICAL MANUAL 143 2002


Pneumophila," available on the Web at (1975).
http://www.ncgr.org/microbe/legionellaptxt.htinl Verduijn, W. D., "Experience with a Cryogenic Syngas
(modified, Oct. 13, 1998). Purifier," Ammonia Plant Safety & Related
Osman, R. M., "Heat Exchanger Problems in a 1500 Facilities, Vol. 19, AIChE, New York (1979).
ST/SD Ammonia Plant," Ammonia Plant Safety & Verduijn, W. D., "Corrosion of a CO2 Absorber Tower
Related Facilities, Vol. 15, AIChE, New York (1975). Wall," Ammonia Plant Safety & Related Facilities,
Ruziska, P. A., "Automatic trip systems" , Ammonia Vol. 23, AIChE, New York (1983).
Plant Safety & Related Facilities, Vol. 12, AIChE, Verduijn, W. D., "Experience with a Prereformer,"
New York (1972). Ammonia Plant Safety & Related Facilities, Vol. 33,
Song, C. C., W. D. Verduijn, et al., "Conversion of a AIChE, New York (1993).
Œ>2 removal system to Flexsorb HP," Ammonia Verduijn, W. D., "Catastrophic Failure of an Ammonia
Plant Safety & Related Facilities, Vol. 32, AIChE, /Air Mixer," Ammonia Plant Safety & Related
New York (1992). Facilities, Vol. 36, AIChE, New York (1996).
van Eijk, F. P., "Instrument Trip System Maintenance Verduijn, W. D., "Catacarb Rich-Reflux Reboiler,"
and Improvement Program," Ammonia Plant Safety Ammonia Plant Safety & Related Facilities, Vol. 40,
& Related Facilities, Vol. 15, AIChE, New York AIChE, New York (2000).

AMMONIA TECHNICAL MANUAL 144 2002

You might also like