IHITC- ANOMALIES IN ENGINEERING WORKS
27 Not Functional
28 Main Control Panel Fitting Required
29 No Ventilation, No Exhaust Fans
30 Hour Meters in AC’s Missing
Incinerator Room
31 Incinerator Incinerators can’t handle more than 50 patients.
Plumbing
Items Observations
Radiology
32 Wash Basin Not OK
Laboratory
33 Washbasin Not Installed (12 in Nos.)
(Hematology)
Unit-4
34 Muslim Shower Missing
35 Muslim Shower Head Missing
Sewerage
36 Sewerage Line No proper Connections
37 Main Sewerage Line No proper connection and slopes
38 Doctors Room 4 Due to the design issues of sewerage system of the hospital, a
blockage has occurred in the Sewerage manhole behind of
doctor’s room 4. Due to this issue washroom of room 4 has
been choked.
44 Handing over and Vacating of Quarters inside STP Premises from residents is
Complete Locking needed to avoid theft risks
Down of STP Premises
45 Wash Rooms/Toilets At several places Muslim showers, cocks are missing. Unit 4,
Missing Items ward B
46 Fire Hydrants: Hose are Hose is missing in Ward A
Missing
47 Fire Hydrants: No Hose No Hose Pipe Cabinet outside of Building
2
IHITC- ANOMALIES IN ENGINEERING WORKS
52 Doctors Room Central Laboratory wastage pipe is passing through sewerage manhole
Space which causes blocking
53 Behind Admin building Sewerage line is leaking
3
IHITC- ANOMALIES IN ENGINEERING WORKS
Security
Observations
Main Gate Fence at the back of the security guard room is missing.
72 CC TV Camera Surveillance There are many blind spots are present in the building. 32
Blind Spots CCTV cameras are required.
Janitorial Services
Observations
74 Hospital Building Separate Bins are required in different colors for Metals, Glass,
Plastics and Paper
Landscaping
4
IHITC- ANOMALIES IN ENGINEERING WORKS
Observations
Electrical
Items Observations
76 Earth leakage Breaker Earth leakage Breaker missing in all DPs.
77 Earth Arresting Module Earth Arresting Module missing
78 Public Address System Not Functioning
79 Electric Distribution Panel Electric Distribution Panel of Heaters are Hidden in Ceiling.
of Heaters Hidden in Once on 13-14th August, its turning on by some FWO/NDMA
Ceiling in minor OT Staff by mistake caused fire/smoke which was suppressed by
Service Square Staff. Those panels should be installed in walls
and clearly visible and accessible to operation and
maintenance staff.
80 Earthling & Grounding Earth Arrester Module is not installed
81 Fire Alarm System Fire Alarm System is not provided with Ring System Wiring.
5
IHITC- ANOMALIES IN ENGINEERING WORKS
86 Electric Control Room Holes at base of wall too big to prevent entry of rodents and
reptiles. They can cause biting of cables and subsequent
malfunctioning
94 Electric Control Room No proper covering and plugging of ducting at base to protect
entry of rodents, reptiles and insects. All animals are
conductor and Can cause short circuiting
6
IHITC- ANOMALIES IN ENGINEERING WORKS
7
IHITC- ANOMALIES IN ENGINEERING WORKS
126 Ward B and Corridor • No dressing, No safety glass, No thimbles, No Spare wire
133 Lighting System Street lights panel lock keys are missing and some panels are
damaged.
137 Ward B DB, Ward A DB, Water Heater breakers are not working
Unit 5 Electrical room,
139 Lighting System Unit 4 electric room ceiling light is not working
140 Fire Alarm System Unit 1 fire alarm glass of MCB is still broken.
8
IHITC- ANOMALIES IN ENGINEERING WORKS
142 Electric Manhole Electric manhole is missing near underground water tank as
wires are naked and short circuit can happen.
143 Ward A, Ward B Joint Electrical Connection of washrooms with room ceiling
lights. When room light is turned off, washroom light also
turns off.
144 Ward A, Ward B, Light plug electrical supply issue.
145 Electrical Connection Light plug and light issues in Biomedical Electrical bed panels
inside wards, rooms, and ICUs.
148 AC panel issues Variable Frequency Drive panels are manual drive. They should
be auto drive.
150 Trane Unit Stairs for Packaged air conditioning units have blocked end
151 Building Stairs No safety railing for stairs and walking platform for PACUs.
152 Building Stairs Stairs are straight and dangerous for moving equipment.
153 PACU Unit 3 Unit 5 Automatic Modular of Unit 3 euro Aire and Unit 5 euro Aire
not functional
154 Unit 1 SKM PACU SKM PACU of unit 1 thermostat not working and
155 Unit 2 SKM PACU Compressor trips after heating(becomes out of service)
9
IHITC- ANOMALIES IN ENGINEERING WORKS
156 Control Room UPS room UPS room split ac refrigerant issue and remote missing
General
S.N Item/Location Description
o
Radiology
S.N
Description Location IP
o Feedback
net port not working, NO
162 Computer MRI Room 192.168.100.101
POWER OUTLET
Control net port not working, NO
163 Computer 192.168.100.102
Room POWER OUTLET
net port Not functional , NO
164 Computer CT Scan 192.168.100.103
POWER OUTLET
165 Computer Office 192.168.100.104 net port not working
Unit: 1
S.No Description Location IP Status
167 Computer ICU Ward 192.168.100.106 Net port Not functional
10
IHITC- ANOMALIES IN ENGINEERING WORKS
Unit: 2
S.N
Description
o Status
168 Cable Bed 203 Damaged Lighting System
169 Cable Bed 228 Damaged
Unit: 5
S.N
Description Location IP
o Feedback
170 Computer ICU Ward 192.168.100.120 Not functional
192.168.2.18 Ext No
171 IP Phone Reception Not functional
1052
Ward: A
S.No Description Location IP Feedback
Not
172 IP Phone Nurses Room 192.168.2.19 Ext No 1053 functional
Minor-OT
S. No Description
IT/NETWORK-General Issues
11
IHITC- ANOMALIES IN ENGINEERING WORKS
179 CCTV cables at main door are exposed, not properly waterproofed. Security point Highly
Risky As shown in the figure No. 3
180 Cables inside building are required to be properly in runway/ducting inside Ceiling
181 All outsides cameras need proper water proofing setup
182 Wires are open in celling
183 Empty Voice Port Minor-OT
184 Nurse Call System setup is not properly tagged and installed
185 Terminals of Nursing Caller System are not properly mounted just hang behind LCD
186 NVR failure there is no alternative for access & backup of camera if one goes down
187 Require backup NVR in case of main NVR failure to recording
188 PTZ camera cables are not safely housed
189 IP telephone are only working on POE no Power adapters
190 HDMI Cables main reception is damaged
191 Routers, Firewall, Wireless Access points are not Available, no internet Access
192 PA system speakers are not located in admin block as per site drawings
193 Fiber Optical cables are exposed without any protection Figure 4
194 Door access systems are required at ICU Units & Wards
196 Manuals and software applications are required for the CCTV, Windows & Nursing system
software etc.
197 Nursing call button Cables on Ward B bed 119, 214, 231 & 241 are damaged. (not
resolved)
12