This is to certify the subject product which is in conformity with the standard ISO9001 passed
IEC61869-2:2012 and its technical specifications.

Quality Certificate of Current Transformer

Tested

Approved
Dalian No.1 Instrument Transformer Co.,Ltd.
Date 2020-12-19 The People’s Republic of China
、Specifications
I、
7.V-A performance test
Type LZZBJ9-36/250W3h Current ratio 1500,2000,2500/1/1/1 A I (A) 0.025 0.050 0.075 0.100 0.150
2S1,2S2
Accuracy classes 0.5/5P20/5P20 U (V) 372 390 400 409 419
Insulation level 40.5/70/170 kV Equipment type Indoor I (A) 0.025 0.050 0.075 0.100 0.150
2S1,2S3
Rated output 10/15/15 VA Frequency 50 Hz U (V) 510 533 547 555 567
Ith. 25/1 kA/s Polarity Negative I (A) 0.025 0.050 0.075 0.100 0.150
2S1,2S4
Serial No. 9120119789 Matched V-A No. / U (V) 652 677 692 704 718
Order No. 4507217641 Altitude / meters. I (A) 0.025 0.050 0.075 0.100 0.150
3S1,3S2
U (V) 394 414 423 430 438
、Test results
II、
I (A) 0.025 0.050 0.075 0.100 0.150
3S1,3S3
(Indoor temperature: 19 ℃ Relative humidity:49 %) U (V) 542 562 575 582 593
I (A) 0.025 0.050 0.075 0.100 0.150
3S1,3S4
1. DC resistance measurement. U (V) 688 713 727 737 750
DC resistance measurement of primary winding R1= 7 µΩ. I (A)
DC resistance measurement of secondary winding U (V)
Sec. markings 1S1,1S2 1S1,1S3 1S1,1S4 2S1,2S2 2S1,2S3 2S1,2S4 3S1,3S2 3S1,3S3 I (A)
R2(Ω) 5.808 6.985 8.990 5.184 7.133 9.187 5.123 7.100 U (V)
I (A)
Sec. markings 3S1,3S4 / / / / / / / U (V)
R2(Ω) 9.140 / / / / / / / I (A)
2. Measurement of winding insulation resistance. U (V)
Pri.-sec.& ground: ≥ 2500 MΩ. I (A)
Sec.-sec.& sec.-ground: ≥ 1000 MΩ. U (V)
3. Short time power frequency withstand voltage test. I (A)
Pri-sec.& ground: 70 kV, 5 min, passed. U (V)
Sec.-sec.& sec.-ground: 3 kV, 60
s, passed. I (A)
4. Induced over -voltage withstand test≤4.5 kV(peak voltage), 1 min. U (V)
5. Measurement of partial discharge. I (A)
Pre-set applied voltage: 56 kV, test voltage(1.2Um&1.2Um/√3): 48.6/28.1 kV U (V)
apparent discharge level: 26/4 pC. I (A)
6. Verification of terminal markings: correct. U (V)
I (A)
U (V)
8. Error test (cosφ= 0.8 ) When the burden is less than 5VA,cosφ=1.0

Sec I1/In (%) I1/In (%)


Current Burden Current Accuracy Sec Burden
Accurac marking Error Error
ratio (VA) ratio class markings (VA)
y class s 1 5 20 100 120 1 5 20 100 120
f (%) -0.10 -0.10 -0.05 -0.05 f (%) 0.10
10 15
δ( ' ) 8.3 7.3 6.2 6.2 δ( ' ) 2.2
1500/1 0.5 1S1,1S2 2500/1 5P20 3S1,3S4
f (%) 0.05 0.10 0.10 0.10 f (%)
2.5
δ( ' ) 6.5 5.0 4.0 4.0 δ( ' )
f (%) -0.05 0.00 0.00 0.00 f (%)
10
δ( ' ) 5.8 4.1 4.1 4.1 δ( ' )
2000/1 0.5 1S1,1S3
f (%) 0.05 0.05 0.05 0.05 f (%)
2.5
δ( ' ) 5.2 3.3 3.3 3.3 δ( ' )
f (%) 0.00 0.05 0.05 0.05 f (%)
10
δ( ' ) 2.0 1.2 1.2 1.2 δ( ' )
2500/1 0.5 1S1,1S4
f (%) 0.05 0.05 0.05 0.05 f (%)
2.5
δ( ' ) 1.8 1.0 1.0 1.0 δ( ' )
f (%) 0.30 f (%)
15
δ( ' ) 2.6 δ( ' )
1500/1 5P20 2S1,2S2
f (%) f (%)
δ( ' ) δ( ' )
f (%) 0.25 f (%)
15
δ( ' ) 2.1 δ( ' )
2000/1 5P20 2S1,2S3
f (%) f (%)
δ( ' ) δ( ' )
f (%) 0.20 f (%)
15
δ( ' ) 1.8 δ( ' )
2500/1 5P20 2S1,2S4
f (%) f (%)
δ( ' ) δ( ' )
f (%) 0.05 f (%)
15
δ( ' ) 3.7 δ( ' )
1500/1 5P20 3S1,3S2
f (%) f (%)
δ( ' ) δ( ' )
f (%) 0.10 f (%)
15
δ( ' ) 3.0 δ( ' )
2000/1 5P20 3S1,3S3
f (%) f (%)
δ( ' ) δ( ' )