Professional Documents
Culture Documents
Table 2.1 Partial safety factors for loads, gf for limit state
Durability Considerations
The following factors affect the durability of a steel structure:
(a) Environment
(b) Degree of exposure
(c) Shape of the member and the structural detail
(d) Protective measures
(e) Ease of maintenance
A designer should refer to the IS code provisions given in section 15 of IS 800-2007
and also to specialised literature on durability.
Fire Resistance
A steel structure should have sufficient fire resistance level (FRL) specified in terms of
minutes depending upon the purpose for which the structure is used and the time
taken to evacuate in case of fire. For detailed specifications a designer may refer to
section 16 of IS 800-2007 along with IS 1641, IS 1642, IS 1643 and any other specialised
literature on fire resistance.
STABILITY CHECKS
After designing a structure for strength, it should be checked for instability due to
overturning, uplift or sliding under factored loads. In checking for instability
disturbing forces should be taken as design loads and stabilising forces may be taken
as design loads (factored loads) with lesser factor of safety (0.9) as specified
A structure should be adequately stiff against sway and fatigue also. In the chapters to
follow now onwards, design principles are made clear from the point of limit states of
strength and deflections. In most of the buildings these are the predominant limit
states, but in all important and special buildings, a designer has to ensure that other
limit states are not exceeded.
Load factor means how efficiently we use energy. It is the measure of the utilisation of
electrical energy during a given period to the maximum energy which would have
been utilised in that period. The load factor plays an important role in the cost of
generation per unit (kWh). The higher the load factor the smaller will be the
generation cost for the same maximum demands. Load factor regarding energy,
Characteristic load is that value of load which has a 95 percent probability of not
being exceeded during the lifetime of the structure. In absence of any data, loads
given in various standards shall be assumed as the characteristic loads
Nominal Cover Nominal cover is the design depth of concrete cover to all steel
reinforcements, including links. It is the dimension used in design and indicated in
the drawings. It shall be not less than the diameter of the bar.
Nominal Cover to Meet Durability Requirement
Minimum values for the nominal cover of normal weight aggregate concrete which
should be provided to all reinforcement, including links depending on the condition
of exposure.
However for a longitudinal reinforcing bar in a column nominal cover shall in any case
not be less than 40 mm, or less than the diameter of such a bar. In the case of columns
of minimum dimension of 200 mm or under, whose reinforcing bars do not exceed
12mm, a nominal cover of 25 mm may be used.
The deflection of a structure or part thereof shall not adversely affect the appearance
or efficiency of the structure or finishes or partitions. The deflection shall generally be
limited to the following:
a) The final deflection due to all loads including the effect of temperature, creep and
shrinkage and measured from the as-cast level of the supports of floors, roofs and all
other horizontal members, should not normally exceed span/250.
b) The deflection including the effects of temperature, creep and shrinkage occurring
after erection of partitions and the application of finishes should not normally exceed
span/350 or 20 mm whichever is less.
The vertical deflection limits may, generally be assumed to be satisfied provided that
the span to depth ratios are not greater than the values obtained as below:
a) Basic values of span to effective depth ratios for spans up to 10m: Cantilever 7
Simply supported 20 Continuous 26
b) For spans above 10m, the value sin (a) may be multiplied by 10/span in meters,
except for cantilever in which case deflection calculations should be made.
c) Depending on the area and the stress of steel for tension reinforcement, the values
in(a) or (b) shall be modified by multiplying with the modification factor obtained
5.
6.Slenderness Limits for Columns
The unsupported length between end restraints shall not exceed 60 times the
least lateral dimension of a column.
If, in any given plane, one end of a column is unrestrained, its unsupported
length, it shall not exceed
100b^2/ D
where b = width-of that cross-section,
and D = depth of the cross-section measured in the plane under consideration.
Slab panel is supported on two opposite Slab panel is supported on four sides of
sides in short direction of one-way slab the two-way slab.
One way slab bends or deflect in a direction Two way slabs bend or deflect in both
perpendicular to the supporting edges directions.
Deflected shape of the one way slab is Deflected shape of two way slab is dish-
cylindrical. shaped
One way slab has structural strength in Two way slab has structural strength in
shorter direction the shortest direction
N/mm2 mm mm mm mm mm
9
• Torsion reinforcement shall be provided at any corner where the slab is simply
supported on both edges meeting at that comer. It shall consist of top and
bottom reinforcement, each with layers of bars placed parallel to the sides of
the slab and extending from the edges a minimum distance of one-fifth of the
shorterspan.The area of reinforcement in each of these four layers shall be
three-quarters of the area required for the maximum mid-span moment in the
slab.
• Torsion reinforcement equal to half that described above shall be provided at
a corner contained by an edge over only one of which the slab is continuous.
• Torsion reinforcements need not be provided at any comer contained by edges
over both of which the slab is continuous.
• Torsion ly/lx is greater than 2, the slabs shall be designed as spanning one way.
1. If two adjacent edges are discontinuous
We provide full torsion in both ways( x and y direction)
2. When two adjacent edges are continuous - no torsion should be provided
3. If one edge is discontinuous and other is continuous we provide 50% of torsion
Note : if continuity is there on both sides then no torsion steel is required.
13. A load-bearing structure and frame structure are two methods of building
structural framing. Load bearing structures were popular earlier, but now due to
comparative advantages the frame structure has become obsolete.
Almost all the walls are load-bearing walls. None of the walls are load-bearing.
They serve the same purpose as a
partition or screen.
Almost all should be provided with a None of the walls are provided with
foundation. any type of foundation. Walls do not
go below the plinth beam.
Load-bearing walls are taken deep into the The only column is taken deep into the
subsoil foundation. subsoil and provided with foundation
footing.
Any load-bearing wall should have a minimum Exterior walls subjected to weathering
thickness of 200 mm. elements are generally 200 mm thick.
All other walls can be 100 mm thick or
even thinner.
In a multi-storeyed building the thickness of These walls do not take the load and
the wall increases as we descend from a floor need not be thicker. They may not
above to one below it. even continue on the floor below.
A load-bearing wall once constructed shall The walls of the framed structure can
remain in position and should never be be displaced at will as they are lighter
dismantled in full or part. and non-load bearing.
This type of construction does not favor too The space between columns can
many openings for windows, doors, remain as open space as the case with
ventilation, etc., in the ground floor as multi-storeyed residential flats where
required for the showroom, etc., as the load- the ground floor is left with no walls
bearing length of the wall is considerably for easy parking of the vehicle.
reduced.
In the case of multi–story buildings, the room The thickness of the wall remains
area is reduced as we go down due to thicker uniform, therefore the carpet area on
walls. any floor remains the same.