Professional Documents
Culture Documents
REPORT
1. INTRODUCTION
2. OVERVIEW AND HISTORY
3. MECHANICAL, ELECTRICAL AND PLUMBING
MECHANICAL SYSTEM
HEATING VENTILATION AND AIR CONDITIONING
BASIC HVAC EQUIPMENT
BASIC REFRIGERATION CYCLE
ECONOMIZER
AIR DISTIBUTION IN HVAC
PSYCHROMETRIC CHART
LOAD CALCULATION
AIR CONDITIONING
4. ELECTRICAL SYSTEM
5. PLUMBING SYSTEM
6. FIRE FIGHTING
7. DUCT
AIR HANDLING UNIT
VOLUME CONTROL DUCT
FIRE DAMPER
VENTILLATION
8. PROJECT ON SCHOOL BUILDING
EDUCATION BUILDING PLAN
EDUCATION BUILDING ELEVATION AND SECTION
EDUCATION BUILDING FURNITURE LAYOUT
CALCULATION OF GROUND FLOOR AND FIRST
FLOOR OF SCHOOL BUILDING
9. ENVIRONMENTAL MANAGEMENT
10. SAFETY AND RESCUE
11. CONCLUSION
01. INTRODUCTION
The three major functions of heating, ventilation, and air conditioning are interrelated,
especially with the need to provide thermal comfort and acceptable indoor air quality within
reasonable installation, operation, and maintenance costs. HVAC systems can be used in both
domestic and commercial environments. HVAC systems can provide ventilation, and
maintain pressure relationships between spaces. The means of air delivery and removal from
spaces is known as room air distribution.
HISTORY
HVAC SYSTEMS
03.4 ECONOMISER
1. Economizers reduce air conditioning costs by using outside air (OSA) for free
cooling causing the compressor to run less. Air (OSA) for free cooling causing the
compressor to run less.
2. OSA dampers switch over to minimum OSA when free cooling is not available.
3. Economizer dampers switch to minimum ventilation position when OSA conditions are not
favourable for cooling.
4. The outside air sensor for economizers must be installed The outside air sensor for
economizers must be installed properly and sense the true outside air stream temperature to
be effective.
5. Eliminate outside air for ventilation during unoccupied periods by closing OSA dampers.
Periods by closing OSA dampers.
6. OSA damper operation should be monitored and recorded to verify actual operation of
economizer.
7. Percent OSA can be used to verify that the economizer is properly operating.
8. Percent of OSA is calculated using a formula or graph (to be Percent of OSA is calculated
using a formula or graph (to be covered later).
• Ductwork
– Metal
– Flexible
– Duct board
• Grilles, Louvers, & Registers
• Dampers
– Shut off
– Fire
– Smoke
• Sealants
• Supports
03.6 PSYCHROMETRIC CHART
A psychrometric chart can be used in two different ways. The first is done by plotting
multiple data points, that represent the air conditions at a specific time, on the chart. Then,
overlaying an area that identifies the “comfort zone.” The comfort zone is defined as the
range within occupants are satisfied with the surrounding thermal conditions. After plotting
the air conditions and overlaying the comfort zone, it becomes possible to see how passive
design strategies can extend the comfort zone.
03.7 LOAD CALCULATION
• Heating and Cooling
• Accuracy important
• Design conditions
• Building shell load
• R, U value
• Internal load
• Ventilation load
• Infiltration
The selection of an energy source for equipment depends on its application, each having its
own merits and demerits, but for an HVAC system or typical building services, we are
concerned with AC voltage.
Industrial AC voltage levels are roughly defined as LV (low voltage) and HV (high voltage)
with frequency of 50 to 60 Hz. An electrical circuit has the following three basic components
irrespective of its electrical energy form:
1. Voltage (V) is defined as the electrical potential difference that causes electrons to flow.
2. Current (I) is defined as the flow of electrons and is measured in amperes.
3. Resistance (R) is defined as the opposition to the flow of electrons and is measured in
ohms.
CIRCUITS
In order to flow, electricity must have a continuous, closed path from start to finish;
like a circle.
The word “circuit” refers to the entire course an electric current travels, from the source of
power, through an electrical device, and back to the source. Every circuit is comprised of
three major components:
1. A conductive "path," such as a wire, or printed etches on a circuit board.
2. A "source" of electrical power, such as a battery or household wall outlet.
3. A "load" that needs electrical power to operate, such as a lamp. The current flows to the
devices (called loads) through a “hot” wire and returns via a “neutral” wire because under
normal conditions it’s maintained at zero volts, or what is referred to as ground potential.
There are also two optional components that can be included in an electrical circuit. These are
control devices and protective devices. Control and protective devices, however, are not
required for a circuit to function. They are optional.
For example, a circuit that switches on an air conditioner when the temperature is too high
would contain the following components:
• A source of electrical energy, in this case, simple household current.
• A protective device that senses current flow on the circuit, the circuit breaker in the panel
box.
• A control device that redirects the current, the switch in the thermostat.
• A load such as an air conditioner that cools the space down until the circuit opens shutting
the air conditioner off.
The building is served by a 1-1/4” diameter water service. The existing toilets
observed, are the “tank” type toilets requiring the minimal pipe size. The men’s room at the
ground floor had both urinals and toilets.
The sanitary for the building is connected to the toilets throughout the building. There area
men’s room and women’s room located and the ground floor. There is also a small
kitchenette in the computer room office which has a small sink. The first floor has a
handicapped toilet at the east end of the building and the second floor has a men’s room at the
west and a women’s room at the east end of the building. There is also a small sink in the
lounge on the east end of the second floor.
The domestic hot water for the toilets is served by electric water heaters. The water heater at
the ground floor serves the toilet rooms and the service sink. The heater is 9years old and is
located in the boiler room. The domestic hot water serving the toilets on the first floor and the
second floors is also electric. The heater is located in the lounge area at the second floor. The
heater is 4 years old. The roof drainage for the building consisted of gutters and down spouts.
STANDARD AND CODES OF PLUMBING SYSTEM
Engineers concerned with smoke control often specify the use of the building HVAC
system in a special mode of operation for controlling smoke. However, depending on the type
of system and its set of components and controls, HVAC systems may be easy or difficult to
adapt for use in controlling smoke. The various types of HVAC systems such as multi zone
systems, induction unit systems, fan coil systems, VAV, etc. are described relative to their
ease of adaptability for controlling smoke. Also, the role of system components and controls
in HVAC system operation and adaptability of the system as a smoke control system are
described.
07. DUCT
FLEXIBLE DUCT
07.2 VOLUME CONTROL DUCT
07.4 VENTILATION
Natural ventilation is the ventilation of a building with outside air without using fans
or other mechanical systems. It can be via operable windows, louvers, or trickle vents when
spaces are small and the architecture permits. In more complex schemes, warm air is allowed
to rise and flow out high building openings to the outside (stack effect), causing cool outside
air to be drawn into low building openings. Natural ventilation schemes can use very little
energy, but care must be taken to ensure comfort. In warm or humid climates, maintaining
thermal comfort solely via natural ventilation might not be possible. Air conditioning systems
are used, either as backups or supplements. Air-side economizers also use outside air to
condition spaces, but do so using fans, ducts, dampers, and control systems to introduce and
distribute cool outdoor air when appropriate.
An important component of natural ventilation is air change rate or air changes per hour: the
hourly rate of ventilation divided by the volume of the space. For example, six air changes
per hour means an amount of new air, equal to the volume of the space, is added every ten
minutes. For human comfort, a minimum of four air changes per hour is typical, though
warehouses might have only two. Too high of an air change rate may be uncomfortable, akin
to a wind tunnel which have thousands of changes per hour. The highest air change rates are
for crowded spaces, bars, night clubs, commercial kitchens at around 30 to 50 air changes per
hour.
Room pressure can be either positive or negative with respect to outside the room. Positive
pressure occurs when there is more air being supplied than exhausted, and is common to
reduce the infiltration of outside contaminants.
TYPES OF CALUCULATION IN HVAC SYSTEM
MANUAL METHOD
SOFTWARE METHOD
AUTOCADD
HAP
DUCT SIZER
08. PROJECT ON SCHOOL BUILDING
Older chillers can be retrofitted to utilize replacement refrigerants that are more ozone
friendly. HCFC-123 is the current choice to replace CFC-11, while HFC-134a (hydro
fluorocarbon) is the current choice to replace CFC-12. HCFC-123 is an interim solution, and
is currently scheduled to be phased out starting in 2010.There is no compelling reason to
retrofit a chiller with a new refrigerant unless major work is to be done on the unit. On the
other hand, it may be more cost effective to replace the equipment if it is old and near the end
of its useful life. Reciprocating chillers and direct-expansion systems generally utilize HCFC-
22, which also is scheduled to be phased out starting in 2010. Several alternative replacement
refrigerants are currently undergoing testing, but no manufacturer has yet settled on a
replacement.
Global warming also is becoming a concern, and agreements may be adopted to reduce
carbon dioxide emissions by reducing the burning of fossil fuels. Refrigerants have a direct
global-warming impact, as well as an indirect impact because of the energy their systems
consume. Thus, any overall system efficiency improvement also will reduce carbon dioxide
emissions. There are several choices for new or replacement chillers. Centrifugal and rotary
screw chillers utilizing HCFC-123 or HCFC-22 are available from several manufacturers.
Another option is to utilize double-effect absorption chillers, either steam or gas-fired. These
units use water and lithium bromide and have no ozone-depletion or global-warming
potential. The double-effect absorbers are much more efficient than the old-fashioned single-
effect absorbers.
1) Protective Gear
Any time you’re exposed to contaminants like dust, gases and other debris, you will
need a respirator to avoid breathing in any harmful particles. If the respirator lacks eye
protection, it’s necessary to wear either goggles or a face shield to keep your eyes safe from
contact with liquids or flying particles. Gloves and arm protectors need to be worn when
handling anything that could lacerate you such as sheet metal and glass.
Slip resistant shoes should ensure that you maintain steady footing, which is important when
dealing with potential leaks and slippery floors. If you’re in an environment where objects
may fall from above, a hardhat or some type of helmet is a good idea. Also, earplugs should
be worn whenever you’re in a loud environment for an extended period of time.
Part of being a professional HVAC technician is using the right HVAC tools for the
specific job at hand. Before starting out on jobs, you will need to have acquired an assortment
of tools like wrenches, wire strippers, an anemometer, clamp meter and vacuum gauge. With
the ever-present threat of gas and radiation leaks, having a leak detector is also important.
Keeping everything in working condition through routine maintenance is critical for staying
safe on the job.
3) Identifying Hazards
Before jumping right into a task, it’s critical to take the time to make an assessment
and know exactly what you’re up against. When you’re new to this profession, you should
identify any potential hazards on each job site and take the proper safety precautions before
going forth. It’s better to take a bit more time to get the job done right and stay safe than rush
it and wind up seriously injured. The Centres for Disease Control and Prevention also
suggests that it’s smart to participate in “additional electrical safety training to those workers
working with or around electrical current, including proper rescue procedures.” If electrical
safety isn’t part of on-the-job training, one could consider taking a short 3-month electrician
training program.
4) Chemical Safety
On a daily basis, you’re likely to encounter a range of chemicals that can pose a
serious threat to your health. Everything from refrigerants and cleaning liquids to solvents
and detergents can be problematic if handled incorrectly. In some cases, certain combustible
chemicals can explode and cause major injury. That’s why you should always wear protective
gloves when handling chemicals that can cause skin burns.
You should always follow proper procedures when transporting and storing chemicals. In
some cases, newer technicians will lack in-depth knowledge on certain chemicals, so extra
precaution is needed during your learning curve. If you’re at all unsure about a particular
substance, you should familiarize yourself with it or ask an expert before handling it. It’s
better to be safe than sorry.
5) Avoiding Shock
Because you’re often dealing with electrical equipment that you may not be fully
familiar with when starting out, you should be cautious and take preventative steps to
minimize your risk of shock or electrocution. This can be especially problematic whenever
there is a water leak within an HVAC system. As water drips onto the electrical parts, it’s the
perfect recipe for equipment failure and shock. Typically, the best way to stay safe is to turn
off main circuit breakers beforehand. Not only should this eliminate the threat of
electrocution, but it should prevent any expensive equipment from being damaged as well.
11. CONCLUSION
Surely HVAC system has become a necessity for Human, the report elaborates the
usage of water as a coolant for the centralized HVAC system. The design of a centralized
chilled water air-conditioning system for the Corporate Office building done as per the
standards of ASHRAE will be submitted for approval from the sponsored authority. The
project report concludes that;
The concept of chiller water system is clearly explained with the importance of the
system in HVAC Industry & Application.
The main motive of design of an HVAC system for the building industry purely
depends on the Human comfort values, should be maintained irrespective of location
of the project.
The Heat Load Estimated provides the requirement of cooling for the project,
provides a guideline for the Selection of Machines.
The final layouts for the piping and equipment are submitted for final approval, for
the site Installation.
Thus the Project Report clearly identifies the requirements of the project and provides an
effective way of Air-Conditioning to achieve Human effort for the occupants. The design and
drawings as approved will be sent to the site installation process. Therefore the project
defines the requirement and process of achieving the Human Comfort and Environment.