Project Part

of Structure Proj. No.


Al‐Zor
Calculated by Date Sheet

Checked by Date Rev.

Ref. Calculations Output


Check of connection capacity:

T (MAX HORIZONTAL FORCE CARRIED BY CONNECTION)  = 0.59 KN
N (MAX VERTICAL FORCE CARRIED BY CONNECTION)  = 1.22 KN
Angle Section Properties:
A = 50 mm
B = 120 mm
L = 50 mm
t = 10 mm
Lb = 60 mm
Fy = 235 MPa
Fu = 400 MPa

Stiffener properties:
ts = 0 mm
Lh  = 25 mm
Lv = 110 mm
a (stiffener critical width at sec Y) =  0 mm
Fy = 235 Mpa

Check of Section Y:
slot width = 0 mm
My = (T*Lb)‐(N*Lh) = 0.01 KN.M
y" = ‐5.000 mm
Iy = 4167 mm^4
Zy = Iy/(a‐y") = 833.33 mm^3
(F1‐1) Mn = Fy*Z = 0.20 KN.M
AISC LRFD  φ = 0.9
1999 φ Mn = 0.18 KN.M

(D1-1, D1-2) Ae = 500 mm^2 Ag = 500 mm^2


Project Part of Structure Proj. No.
Al‐Zor
Calculated by Date Sheet

Checked by Date Rev.

Ref. Calculations Output


AISC LRFD  φPn = 0.75 Fu Ae = 150.00 KN OR  φPn = 0.90 Fy Ag = 106 KN
1999 Then  φPn =  105.75 KN

(F2‐1) φ = 0.9


AISC LRFD  φ Vn = φ 0.6 Fy Ae = 63.45 KN
1999
N/φPn+T/φVn+My/φMn = 0.078 < 1 [safe]