Professional Documents
Culture Documents
Exergy and Cost Optimization of A Two-Stage Refrigeration System Using Refrigerant R32 and R410A
Exergy and Cost Optimization of A Two-Stage Refrigeration System Using Refrigerant R32 and R410A
Ranendra Roy
Department of Mechanical Engineering,
Two-Stage Refrigeration System
IIEST Shibpur,
Howrah 711103, West Bengal, India
e-mail: ranendraroy2009@gmail.com
Using Refrigerant R32 and R410A
An attempt has been made to investigate numerically a two-stage refrigeration system with
Arup Jyoti Bhowal flash intercooler of 50 kW cooling capacity using refrigerant R410A and its possible alter-
Introduction Payne and Domanski [17], and Calm and Domanski [18] also sug-
gested R410A to be a promising replacement for R22 in air condi-
Refrigeration is the process of transferring heat from low temper-
tioners and heat pump applications. Though several studies
ature to high temperature with the expense of work [1]. The widely
recommended R410A to be a better alternative to R22, different
used system for any refrigeration process is the simple vapor com-
researchers are recently looking for some other alternatives of
pression refrigeration system (VCRS). But this system is effective
R410A as it is having higher global warming potential (GWP)
when the pressure ratio between evaporator and condenser is
value of 2000 [14] as suggested in the recent Kigali amendment
below 5 [2]. In case of higher pressure ratios, compressor power
[19] in 2016. Xu et al. [20] experimentally found an increase in
requirement increases and co-efficient of performance (COP) of
COP and capacity by 9% and 10%, respectively, using R32
the system decreases. In such cases, a multi stage vapor compres-
instead of R410A the refrigerant in a vapor-injected heat pump
sion refrigeration system is recommended for better performance.
system. Tu et al. [21] carried out a numerical study and also con-
Several numerical and experimental works have been conducted
ducted an experiment on a residential heat pump unit using R32
to assess the performance of refrigeration system. Sarbu [3],
and R410A. The numerical results showed that the cooling COP
Qureshi and Zubair [4], Best and Rivera [5], and Anand et al. [6]
obtained with R32 was 6% higher than the COP using R410A.
reviewed different systems and identified several strategies for
They also found a 2% improvement in heating COP from the exper-
future development of the existing system for the improvement in
imentation. In et al. [22], Piao et al. [23], Alabdulkarem et al. [24],
thermodynamic performances. Some previous work on refrigerants
and Yao et al. [25] also identified R32 to be the best replacement for
and their possible alternatives had also been reviewed by Mohanraj
R410A from their experimental study on a heat pump unit. Ust et al.
et al. [7] and Emani et al. [8]. Ahamed et al. [9] presented a review
[26] also recommended refrigerant R32 for its better performances
work on exergy analysis of a simple vapor compression refrigera-
over R410A for vapor compression refrigeration systems. Though
tion system. Chowdhury et al. [10] presented a review work on
several researchers recommended refrigerant R32 over R410A, it
energy and exergy analysis of a two-stage vapor compression refrig-
has the limitation of higher discharge temperature. Barve and Cre-
eration system. In another numerical study, Ahamed et al. [11] found
maschi [27] and Zilio et al. [28] found that the capacity obtained
an improvement in the exergetic performance of a single-stage
with R32 was always higher compared with R410A, but the dis-
vapor compression system using R600a over R134a. Gill et al.
charge temperature with R32 was always higher than that of R410A.
[12] and Abraham et al. [13] obtained better performances using
It has now been established that the multi-stage refrigeration
R450A and R430A, respectively, over refrigerant R134a.
system gives better performance when the pressure ratio and
The Montreal protocol and the subsequent amendments have put
hence the temperature lift is high. Nikolaidis and Probert [29]
restriction on the production and use of some of the most thermody-
carried out exergy analysis on a two-stage vapor compression
namically efficient chlorofluorocarbon (CFC) and hydrochlorofluo-
refrigeration system using R22 as refrigerant. They reported that
rocarbon (HCFC) refrigerants due to their direct involvement in the
any reduction in exergy loss in evaporator or condenser resulted
depletion of stratospheric ozone layer. Calm and Hourahan [14] pre-
in decrease in overall plant irreversibility by 2.87 times or 2.40
sented refrigerants data summary and identified that refrigerant
times, respectively. Tiedeman and Sherif [30] showed that signifi-
R410A had thermophysical properties similar to those of R22.
cant error would occur if the intermediate pressure is taken as the
Spatz and Yana Motta [15], Yana Motta and Domanski [16],
geometric mean of the condenser and the evaporator pressure.
Ouadha et al. [31] concluded from their numerical study that signif-
1 icant exergy losses occurred mainly in compressor, expansion
Corresponding author.
Manuscript received October 29, 2019; final manuscript received January 24, 2020; valve, and condenser. They also found the optimum inter-stage
published online February 5, 2020. Assoc. Editor: Cheng-Xian Lin. pressure to be close to the arithmetic mean of the evaporator and
Journal of Thermal Science and Engineering Applications JUNE 2020, Vol. 12 / 031024-1
Copyright © 2020 by ASME
the condenser pressure. Zubair et al. [32] simulated a two-stage in cascade refrigeration system. Some optimization studies had
refrigeration system and found that maximum exergy loss was also been conducted on thermal energy storage system for air condi-
due to low compressor efficiency. They also reported a similar tioning applications by Sanaye and Shirazi [42], Sanaye and Shirazi
trend in optimum intermediate pressure as reported by Ouadha [43], and Navidbakhsh et al. [44]. Baakeem et al. [2] also carried out
et al. [31]. Röyttä et al. [33] discussed about the optimization of a thermo-economic analysis as well as single-objective optimization
two-stage refrigeration system with flash intercooler using R134a for maximizing COP using conjugate directions method available
and R245fa as refrigerants to obtain maximum COP. Agrawal in engineering equation solver [45].
and Bhattacharyya [34] simulated a two-stage transcritical carbon Though a huge number of papers are available on vapor compres-
dioxide heat pump system with flash intercooler and concluded sion refrigeration system, few problems still need attentions. There
that flash intercooling arrangement was not economical when are very less amount of work available on multi-stage refrigeration
R744 was used as refrigerant. Shuxue and Guoyuan [35] experi- system using flash intercooler. The impact of some environment
mentally investigated on a two-stage compression refrigeration/ friendly refrigerants on the performance of multi-stage refrigeration
Fig. 1 (a) Schematic diagram and (b) P–h plot of a two-stage refrigeration system with flash intercooler
Ẇ total = Ẇ LP + Ẇ HP (6)
Refrigerant Properties Next, applying first law of thermodynamics to condenser, the
Energy and Exergy Analysis. The optimal intermediate pres- Ẇ total − δtotal
ηex = (12)
sure (Pi) for the two-stage compression refrigeration system can Ẇ total
be taken following Arora [46] and Purohit et al. [47] as:
Pi = Peva × Pcond (1) Economic Analysis. Economic analysis of any plant focuses on
three maincost components,
namely, total capital and maintenance
where Peva is the evaporator pressure and Pcond is the condenser cost rate CRk , operational cost rate (CROP) and CO2 penalty
pressure. Now, applying first law of thermodynamics to the evapo-
cost rate (CRenv) of the plant. The total plant cost rate (CRtotal) is
rator, cooling load (Q̇eva ) can be expressed following Baakeem et al. the sum of these three cost components and can be expressed as:
[2] as:
CRtotal = CRk + CROP + CRenv (13)
Q̇eva = ṁLP (h1 − h8 ) (2)
where ṁLP is the mass flow rate in the low pressure (LP) side. Power
requirement by LP compressor (Ẇ LP ) and high pressure (HP) com- Table 2 Exergy destruction in different components
pressor (Ẇ HP ) can be written as:
Component Exergy destruction equation
ṁLP (h2 − h1 )
Ẇ LP = (3) δeva = Ex8 − Ex1 + Q̇eva (1 − T0 /Teva )
ηs × ηm × ηel Evaporator
LP compressor δLP,comp = Ex1 − Ex2 + Ẇ LP
HP compressor δHP,comp = Ex3 − Ex4 + Ẇ HP
ṁHP (h4 − h3 ) Condenser δcond = Ex4 − Ex5 − Q̇cond (1 − T0 /Tcond )
Ẇ HP = (4)
ηs × ηm × ηel HP throttle valve δHP,TV = Ex5 − Ex6
LP throttle valve δLP,TV = Ex7 − Ex8
where ṁHP is the mass flow rate in the HP side, ηel is the electrical Flash tank δFT = Ex2 − Ex3 + Ex6 − Ex7
efficiency of the motor and ηm is mechanical efficiency of the
Journal of Thermal Science and Engineering Applications JUNE 2020, Vol. 12 / 031024-3
Capital investment and maintenance cost rate of individual com- System Optimization
ponent is given by
Objective Function. In this paper, four parameters including
CRk = Ck × φ × CRF (14) exergetic efficiency, plant cost rate, and two compressors discharge
temperatures have been selected as objective functions where exer-
where Ck is the capital cost component of individual components, φ getic efficiency should be maximized and other three functions
is the maintenance factor, and CRF is the capital recovery factor. should be minimized for the system using refrigerant R32. In case
The capital cost of different components of the two-stage refrigera- of the R410A based system, only two parameters, namely, exergetic
tion system can be estimated using the cost functions as given by efficiency and plant cost rate have been chosen as objective func-
Mosaffa et al. [48]. These cost functions are presented in Table 3. tions. Several researchers identified the problem of high compressor
Capital recovery factor (CRF) can be calculated from the follow- discharge temperature using R32 in the system. However, this
ing Dincer et al. [52] as: problem does not exist in case of the R410A. This motivated
Fig. 2 (a) Variation of COP with evaporator temperature and (b) variation of exergetic efficiency with evaporator temperature
Journal of Thermal Science and Engineering Applications JUNE 2020, Vol. 12 / 031024-5
Downloaded from http://asmedigitalcollection.asme.org/thermalscienceapplication/article-pdf/12/3/031024/6489164/tsea_12_3_031024.pdf by Suny At Buffalo user on 02 February 2021
Fig. 3 (a) Variation of COP with condenser temperature and (b) variation of exergetic efficiency with condenser temperature
alternative R32 to compare the thermo-economic performances. COP with the R32-based system is comparable with R410A
A computer-based model has been developed to carry out the system throughout the evaporator temperature range. However,
simulation. the COP of R32 system at evaporator temperature of −50 °C is
found to be 0.27% less than that of R410A system. The correspond-
ing value at −25 °C evaporator temperature is 0.32% higher.
Effect of Evaporator Temperature on COP. Figure 4 shows
the variations of COP of the investigated system with the evaporator
temperature keeping the condenser temperature fixed at 40 °C for Evaporator Temperature on Exergetic Efficiency. The varia-
both R410A and R32 refrigerants. It can be seen from the figure tions of exergetic efficiency of the system with the evaporator tem-
that the COP of the system increases with the increase in evaporator perature have been plotted in Fig. 5. Condenser temperature has
temperature. As evaporator temperature increases, pressure ratios in been kept fixed at 40 °C. The figure shows that exergetic efficiency
both stages decrease which causes a decrease in the compressor increases with the increase in evaporator temperature. This can be
power for the system. The decrease in compressor power conse- explained from the fact that as evaporator temperature increases,
quently results in increase in COP of the system. Similar trends the intermediate temperature increases. This leads to decrease in
are noted for both the investigated refrigerants. Results show that the pressure ratios in both the stages which finally causes a decrease
Fig. 4 Variation of COP of the system with evaporator Fig. 5 Variation of exergetic efficiency with evaporator
temperature temperature
Teva
Refrigerant (°C) δcond δeva δFT δHP Comp δLP Comp δLP,TV δHP,TV
Fig. 6 Influence of evaporator temperature on total plant cost Fig. 8 Variations of different cost components of the plant with
rate evaporator temperature using R410A
Journal of Thermal Science and Engineering Applications JUNE 2020, Vol. 12 / 031024-7
Downloaded from http://asmedigitalcollection.asme.org/thermalscienceapplication/article-pdf/12/3/031024/6489164/tsea_12_3_031024.pdf by Suny At Buffalo user on 02 February 2021
Fig. 9 Variations of components cost rates with evaporator tem-
perature for R32 based system Fig. 11 Variation of exergetic efficiency of the system with con-
denser temperature
Tcond
Refrigerant (°C) δcond δeva δFT δHP Comp δLP Comp δLP,TV δHP,TV
efficiency decreases from 55.55% to 51.15% when the condenser leads to an increase in operational cost and CO2 penalty cost rate
temperature is increased from 40 °C to 55 °C for R32 system. The for both R32 and R410A based system. But, the increase in con-
decrease in exergetic efficiency is found to be slightly more with denser temperature results in decrease in the total capital and main-
R410A. It changes from 55.49% to 49.62% for the same increase tenance cost of the system due to the decrease in capital and
of condenser temperature. maintenance cost rate of condenser as shown in Fig. 15 due to
decrease in heat exchanger area. Initially, the decrease in capital
and maintenance cost is more than the increase in operational and
Condenser Temperature on Total Plant Cost Rate. Influences CO2 penalty cost which leads to decrease in the total plant cost.
of condenser temperature on the plant cost rate and different cost However, the increase in operational and CO2 penalty costs over-
components of the system using refrigerants R32 and R410A sepa- shoots the decrease in capital and maintenance cost rate beyond
rately for a fixed evaporator temperature of −35 °C have been the condenser temperature of 48 °C. As a result, the total plant
shown in Figs. 12–14, respectively. In Fig. 12, the plant cost rate cost rate starts increasing after this. Predicted results show that
first rapidly decreases and again increases with the increase in con- total plant cost of the system using R32 is slightly less than the
denser temperature as shown in the figure. The increase in compres- other system. Minimum cost rates are required when both R32-
sor power requirement with the increase in condenser temperature and R410A-based systems are operated at 49 °C and 47 °C
Fig. 13 Variations of different cost components with condenser Fig. 15 Effect of condenser temperature on component costs of
temperature using refrigerant R32 R32 based system
Journal of Thermal Science and Engineering Applications JUNE 2020, Vol. 12 / 031024-9
Table 9 Variations of quality of vapor with evaporator Table 11 Compressors discharge temperature with evaporator
temperature for Tcond of 40 °C temperature
LPC HPC
Table 10 Variations of quality of vapor with condenser compressor compressor
temperature for Teva of −35 °C discharge discharge
temperature temperatures Refrigerant
R410A R32 (°C) (°C) flowrate (kg/s)
Condenser
Condenser temperature (°C) xLP xHP xLP xHP temperatures (°C) R410A R32 R410A R32 R410A R32
40 0.18 0.32 0.15 0.25 40 31.4 60.3 68.7 90.6 0.39 0.26
43 0.19 0.34 0.15 0.27 43 33.9 63.9 72.7 95.4 0.41 0.27
46 0.19 0.36 0.16 0.28 46 36.4 67.4 76.7 100.3 0.43 0.28
49 0.2 0.38 0.16 0.3 49 38.9 71 80.7 105.1 0.45 0.29
52 0.21 0.4 0.17 0.32 52 41.4 74.6 84.7 110 0.48 0.30
55 0.21 0.43 0.17 0.34 55 44 78.2 88.7 114.9 0.51 0.31
Condenser temperature (°C) Evaporator temperature (°C) ṁLP (kg/s) V̇ eva (m3 /s) ṁHP (kg/s) V̇ HP,comp (m3 /s)
Table 14 Mass flowrate versus volumetric flowrate for different Teva and Tcond = 40 °C using R410A
lower than that using R410A at any evaporator temperature. increased from 53.71% to 58.65%. So, it can be said that a 9.2%
Detailed calculation predict that nearly 23% and 10% less refriger- increase in exergetic efficiency can be achieved at a cost of increase
ant volume flowrates are required for the LP and HP stages, respec- in the plant cost rate by 9.6%. In case of R32 system, the increase in
tively, when R32 is used in the system instead of R410A. plant cost rate is noted to be 12% for an improvement of exergetic
The above results clearly identify that the use of refrigerant efficiency by 8.7%.
R32 is much beneficial for the evaporator temperature ranging Again, any point on the Pareto front is capable to satisfy both the
from −35 °C to −25 °C and condenser temperature ranging from objective functions at a reasonable level. However, the decision
40 °C to 55 °C. Though the compressor discharge temperature is maker has to select only one point among the Pareto optimal solu-
slightly higher in case of R32, it can be a good option as replace- tions for practical reasons and that selection is dependent on the
ment of R410A due to its low GWP value. importance of individual objective functions. Few decision-making
methods are available in the literature for the selection of one
optimum point from Pareto front. In this work, TOPSIS [41]
Optimization Results. Figures 16(a) and 16(b) show the Pareto decision-making method has been employed to select the unique
fronts of the of two-stage refrigeration system working with refrig- solution of the multi-objective optimization problem. Optimum
erants R410A and R32, respectively. The figure clearly depicts the points obtained by TOPSIS method for both systems have been
conflict between the two objectives (exergetic efficiency and plant shown in the figures by an “Asterisk” symbol. The operating param-
cost rate). It can be seen from both the figures that total plant cost eters and optimum performances of the individual systems have
rate increases when exergetic efficiency is increased. Figure 16(a) also been presented in Table 15.
shows that the plant cost rate of the R410A based system increases It can be noted from this table that the operating parameters and
from 64,417 USD to 70,585 USD when exergetic efficiency is most of performance parameters at optimum condition are very
Fig. 16 Pareto optimum solutions for both (a) R410A and (b) R32 based system
Journal of Thermal Science and Engineering Applications JUNE 2020, Vol. 12 / 031024-11
Table 15 Optimum operating condition and performance ex = specific exergy
parameters CR = cost rate
CRF = capital recovery factor
Parameters R410A R32 δ = exergy destruction
−27.2 −28.1
η = efficiency
Evaporator temperature (°C)
μ = emission factor
Condenser temperature (°C) 45.2 44.5
Intermediate pressure (°C) 0.904 0.899 φ = maintenance factor
Compressor discharge temperature (°C) 70.3 89.2
Compressor power (kW) 27.4 27.3
Mass flowrate (kg/s) 0.41 0.26 Subscript
COP 1.824 1.831 comp = compressor
Exergy destruction (kW) 11.88 11.72
cond = condenser
Journal of Thermal Science and Engineering Applications JUNE 2020, Vol. 12 / 031024-13