88 10/09/20 Page 1/5

Grid-Connected System: Simulation parameters


Project : SuoiNgo_TanChau
Geographical Site Ấp Hai Country Vietnam
Situation Latitude 11.61° N Longitude 106.31° E
Time defined as Legal Time Time zone UT+7 Altitude 54 m
Albedo 0.20
Meteo data: Ấp Hai Meteonorm 7.2 (1991-2010), Sat=100% - Synthetic

PVsyst TRIAL
Simulation variant :

Simulation parameters
Collector Plane Orientation
8 nos BP 92 vs JA 405 (112 string 20)
Simulation date

System type
Tilt
10/09/20 22h26

No 3D scene defined, no shadings


15° Azimuth 0°
Models used Transposition Perez Diffuse Perez, Meteonorm
Horizon Free Horizon
Near Shadings No Shadings
User's needs : Unlimited load (grid)

PVsyst TRIAL
PV Array Characteristics
PV module Si-mono Model JAM72S10-405/MR/1500V
Custom parameters definition Manufacturer JA Solar
Number of PV modules In series 20 modules In parallel 112 strings
Total number of PV modules Nb. modules 2240 Unit Nom. Power 405 Wp
Array global power Nominal (STC) 907 kWp At operating cond. 811 kWp (55°C)
Array operating characteristics (50°C) U mpp 731 V I mpp 1110 A
Total area Module area 4496 m² Cell area 4038 m²

Inverter Model blueplanet 92.0 TL3-INT


Custom parameters definition Manufacturer Kaco (a Siemens Company)
Characteristics Operating Voltage 591-1300 V Unit Nom. Power 92 kWac
Inverter pack Nb. of inverters 8 units Total Power 736 kWac

PVsyst TRIAL
Pnom ratio 1.23

PV Array loss factors


Thermal Loss factor Uc (const) 20.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Global array res. 11 mOhm Loss Fraction 1.5 % at STC
Module Quality Loss Loss Fraction -0.3 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Strings Mismatch loss Loss Fraction 0.10 %
Incidence effect (IAM): User defined profile
0° 30° 50° 60° 70° 80° 90°
1.000 1.000 1.000 1.000 0.950 0.760 0.000

PVsyst TRIAL
PVsyst Evaluation mode
PVSYST V6.88 10/09/20 Page 2/5

Grid-Connected System: Main results


Project : SuoiNgo_TanChau
Simulation variant : 8 nos BP 92 vs JA 405 (112 string 20)
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 15° azimuth 0°
PV modules Model JAM72S10-405/MR/1500V Pnom 405 Wp
PV Array Nb. of modules 2240 Pnom total 907 kWp
Inverter Model blueplanet 92.0 TL3-INT Pnom 92.0 kW ac

PVsyst TRIAL
Inverter pack Nb. of units 8.0 Pnom total 736 kW ac
User's needs Unlimited load (grid)

Main simulation results


System Production Produced Energy 1493 MWh/year Specific prod. 1646 kWh/kWp/year
Performance Ratio PR 84.96 %

Normalized productions (per installed kWp): Nominal power 907 kWp Performance Ratio PR

7 1.0
Lc : Collection Loss (PV-array losses) 0.71 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.850
0.9
Ls : System Loss (inverter, ...) 0.09 kWh/kWp/day
6
Yf : Produced useful energy (inverter output) 4.51 kWh/kWp/day
0.8
[kWh/kWp/day]

5 0.7
Performance Ratio PR

PVsyst TRIAL
0.6
4
Energy

0.5

3
0.4
Normalized

2 0.3

0.2
1
0.1

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

8 nos BP 92 vs JA 405 (112 string 20)


Balances and main results

PVsyst TRIAL January


February
March
April
GlobHor
kWh/m²
162.1
150.1
172.0
154.0
DiffHor
kWh/m²
57.75
66.57
78.01
71.56
T_Amb
°C
26.42
27.40
28.81
29.42
GlobInc
kWh/m²
184.6
162.4
176.2
150.3
GlobEff
kWh/m²
183.0
160.8
174.0
148.1
EArray
MWh
144.9
127.2
136.8
116.8
E_Grid
MWh
141.9
124.5
134.0
114.5
PR

0.847
0.845
0.838
0.839
May 172.2 84.14 28.99 160.9 158.3 126.2 123.7 0.847
June 171.7 81.50 28.08 156.5 153.8 123.8 121.4 0.855
July 174.6 84.33 27.93 160.8 158.1 127.2 124.7 0.855
August 166.3 84.81 27.69 158.8 156.2 125.6 123.1 0.855
September 138.8 71.95 26.97 139.7 137.8 110.3 108.0 0.852
October 148.7 75.34 27.06 157.8 155.9 124.8 122.3 0.854
November 147.7 66.08 26.53 164.5 162.7 130.1 127.5 0.854

PVsyst TRIAL December


Year

Legends: GlobHor
DiffHor
T_Amb
145.1
1903.3
63.98
886.03

Horizontal global irradiation


Horizontal diffuse irradiation
T amb.
26.41
27.64
165.1
1937.6
163.5
1912.4

GlobEff
EArray
E_Grid
130.6
1524.3
127.9
1493.4
0.854
0.850

Effective Global, corr. for IAM and shadings


Effective energy at the output of the array
Energy injected into grid
GlobInc Global incident in coll. plane PR Performance Ratio

PVsyst Evaluation mode


PVSYST V6.88 10/09/20 Page 3/5

Grid-Connected System: Special graphs


Project : SuoiNgo_TanChau
Simulation variant : 8 nos BP 92 vs JA 405 (112 string 20)
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 15° azimuth 0°
PV modules Model JAM72S10-405/MR/1500V Pnom 405 Wp
PV Array Nb. of modules 2240 Pnom total 907 kWp
Inverter Model blueplanet 92.0 TL3-INT Pnom 92.0 kW ac

PVsyst TRIAL
Inverter pack Nb. of units 8.0 Pnom total 736 kW ac
User's needs Unlimited load (grid)

Daily Input/Output diagram

6000
Values from 01/01 to 31/12

5000
Energy injected into grid [kWh/day]

4000

PVsyst TRIAL 3000

2000

1000

0
0 2 4 6 8 10
Global incident in coll. plane [kWh/m².day]

PVsyst TRIAL
System Output Power Distribution

50000
Values from 01/01 to 31/12
Energy injected into grid [kWh / Bin]

40000

30000

20000

PVsyst TRIAL 10000

0
0 200 400 600 800
Power injected into grid [kW]

PVsyst Evaluation mode


PVSYST V6.88 10/09/20 Page 4/5

Grid-Connected System: Loss diagram


Project : SuoiNgo_TanChau
Simulation variant : 8 nos BP 92 vs JA 405 (112 string 20)
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 15° azimuth 0°
PV modules Model JAM72S10-405/MR/1500V Pnom 405 Wp
PV Array Nb. of modules 2240 Pnom total 907 kWp
Inverter Model blueplanet 92.0 TL3-INT Pnom 92.0 kW ac

PVsyst TRIAL
Inverter pack Nb. of units 8.0 Pnom total 736 kW ac
User's needs Unlimited load (grid)

Loss diagram over the whole year

1903 kWh/m² Horizontal global irradiation


+1.8% Global incident in coll. plane

-1.30% IAM factor on global

1912 kWh/m² * 4496 m² coll. Effective irradiation on collectors


efficiency at STC = 20.22% PV conversion

PVsyst TRIAL 1738 MWh Array nominal energy (at STC effic.)
-0.18% PV loss due to irradiance level

-10.42% PV loss due to temperature

+0.31%

-1.10%
Module quality loss

Mismatch loss, modules and strings


-1.08% Ohmic wiring loss
1525 MWh Array virtual energy at MPP

-2.00% Inverter Loss during operation (efficiency)


-0.05% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage

PVsyst TRIAL
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
-0.02% Night consumption
1493 MWh Available Energy at Inverter Output
1493 MWh Energy injected into grid

PVsyst TRIAL
PVsyst Evaluation mode
PVSYST V6.88 10/09/20 Page 5/5

Grid-Connected System: P50 - P90 evaluation


Project : SuoiNgo_TanChau
Simulation variant : 8 nos BP 92 vs JA 405 (112 string 20)
Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation tilt 15° azimuth 0°
PV modules Model JAM72S10-405/MR/1500V Pnom 405 Wp
PV Array Nb. of modules 2240 Pnom total 907 kWp
Inverter Model blueplanet 92.0 TL3-INT Pnom 92.0 kW ac

PVsyst TRIAL
Inverter pack Nb. of units 8.0 Pnom total 736 kW ac
User's needs Unlimited load (grid)

Evaluation of the Production probability forecast


The probability distribution of the system production forecast for different years is mainly dependent
on the meteo data used for the simulation, and depends on the following choices:
Meteo data source Meteonorm 7.2 (1991-2010), Sat=100%
Meteo data Kind Not defined Year 1995
Specified Deviation Year deviation from aver. 3%
Year-to-year variability Variance 2.0 %

The probability distribution variance is also depending on some system parameters uncertainties

PVsyst TRIAL
Specified Deviation PV module modelling/parameters 1.0 %
Inverter efficiency uncertainty 0.5 %
Soiling and mismatch uncertainties 1.0 %
Degradation uncertainty 1.0 %
Global variability (meteo + system) Variance 2.7 % (quadratic sum)

Annual production probability Variability 40 MWh


P50 1493 MWh
P90 1442 MWh
P95 1427 MWh

Probability distribution

PVsyst TRIAL
0.50

0.45
P50 = 1493407 kWh
0.40 E_Grid simul = 1493407 kWh

0.35

0.30
Probability

0.25

0.20
P90 = 1441845 kWh
0.15

0.10 P95 = 1427337 kWh

0.05

PVsyst TRIAL
0.00
1350000 1400000 1450000 1500000 1550000 1600000 1650000
E_Grid system production kWh

PVsyst Evaluation mode