PVSYST V6.

43 Moslem Moradbazofti 30/12/17 Page 1/3

MAN & TO

Grid-Connected System: Simulation parameters

Project : Grid-Connected Project at Shahrak bozorg isfahan


Geographical Site Shahrak bozorg isfahan Country Iran
Situation Latitude 33.0°N Longitude 51.4°E
Time defined as Legal Time Time zone UT+3.5 Altitude 1960 m
Albedo 0.20
Meteo data: Shahrak bozorg isfahan NASA-SSE - Synthetic

Simulation variant : New simulation variant


Simulation date 30/12/17 00h21

Simulation parameters
2 orientations Tilts/Azimuths 10°/-87° and 10°/-90°
Models used Transposition Perez Diffuse Perez, Meteonorm
Horizon Free Horizon
Near Shadings No Shadings

PV Array Characteristics
PV module Si-poly Model YL260P-29b
Original PVsyst database Manufacturer Yingli Solar
Number of PV modules In series 23 modules In parallel 3 strings
Total number of PV modules Nb. modules 69 Unit Nom. Power 260 Wp
Array global power Nominal (STC) 17.94 kWp At operating cond. 16.03 kWp (50°C)
Array operating characteristics (50°C) U mpp 631 V I mpp 25 A
Total area Module area 112 m² Cell area 101 m²

Inverter Model Sunny Tripower 20000TLEE-JP


Original PVsyst database Manufacturer SMA
Characteristics Operating Voltage 580-800 V Unit Nom. Power 20.0 kWac
Inverter pack Nb. of inverters 1 units Total Power 20 kWac

PV Array loss factors


Array Soiling Losses Loss Fraction 2.0 %
Thermal Loss factor Uc (const) 29.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Global array res. 43 mOhm Loss Fraction 0.2 % at STC
Serie Diode Loss Voltage Drop 0.7 V Loss Fraction 0.1 % at STC
LID - Light Induced Degradation Loss Fraction 1.3 %
Module Quality Loss Loss Fraction -0.8 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Incidence effect, ASHRAE parametrization IAM = 1 - bo (1/cos i - 1) bo Param. 0.05

System loss factors


AC loss, transfo to injection Grid Voltage 20 kV
Wires: 3x150.0 mm² 100 m Loss Fraction 0.0 % at STC
External transformer Iron loss (24H connexion) 18 W Loss Fraction 0.1 % at STC
Resistive/Inductive losses 294214.1 mOhm Loss Fraction 1.3 % at STC

User's needs : Unlimited load (grid)


PVSYST V6.43 Moslem Moradbazofti 30/12/17 Page 2/3

MAN & TO

Grid-Connected System: Main results


Project : Grid-Connected Project at Shahrak bozorg isfahan
Simulation variant : New simulation variant
Main system parameters System type Grid-Connected
PV Field Orientation 2 orientations Tilt/Azimuth = 10°/-87° and 10°/-90°
PV modules Model YL260P-29b Pnom 260 Wp
PV Array Nb. of modules 69 Pnom total 17.94 kWp
Inverter Model Sunny Tripower 20000TLEE-JP 20.00 kW ac
User's needs Unlimited load (grid)

Main simulation results


System Production Produced Energy 29787 kWh/year Specific prod. 1660 kWh/kWp/year
Performance Ratio PR 85.3 %

Normalized productions (per installed kWp): Nominal power 17.94 kWp Performance Ratio PR
10 1.0
PR : Performance Ratio (Yf / Yr) : 0.853
Lc : Collection Loss (PV-array losses) 0.65 kWh/kWp/day
Ls : System Loss (inverter, ...) 0.14 kWh/kWp/day
Yf : Produced useful energy (inverter output) 4.55 kWh/kWp/day

8 0.8

6 0.6

4 0.4

2 0.2

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

New simulation variant


Balances and main results

GlobHor T Amb GlobInc GlobEff EArray E_Grid EffArrR EffSysR


kWh/m² °C kWh/m² kWh/m² kWh kWh % %
January 100.8 0.80 99.3 91.9 1662 1608 14.93 14.45
February 122.6 2.10 122.7 114.7 2062 2002 14.99 14.56
March 157.8 6.00 156.7 147.9 2591 2513 14.76 14.32
April 179.4 12.80 180.4 171.1 2885 2799 14.28 13.85
May 212.3 18.40 212.5 202.4 3307 3211 13.89 13.49
June 225.0 23.20 224.8 214.2 3424 3327 13.60 13.21
July 219.2 25.90 216.7 206.4 3260 3166 13.43 13.04
August 208.9 25.00 209.5 199.2 3167 3075 13.49 13.10
September 179.4 20.60 181.8 172.2 2797 2717 13.73 13.34
October 144.8 14.50 143.6 134.8 2273 2205 14.13 13.71
November 105.0 7.80 106.1 98.5 1732 1679 14.58 14.13
December 92.7 2.80 92.6 85.3 1534 1484 14.79 14.31

Year 1947.9 13.39 1946.6 1838.6 30693 29787 14.07 13.66

Legends: GlobHor Horizontal global irradiation EArray Effective energy at the output of the array
T Amb Ambient Temperature E_Grid Energy injected into grid
GlobInc Global incident in coll. plane EffArrR Effic. Eout array / rough area
GlobEff Effective Global, corr. for IAM and shadings EffSysR Effic. Eout system / rough area
PVSYST V6.43 Moslem Moradbazofti 30/12/17 Page 3/3

MAN & TO

Grid-Connected System: Loss diagram


Project : Grid-Connected Project at Shahrak bozorg isfahan
Simulation variant : New simulation variant
Main system parameters System type Grid-Connected
PV Field Orientation 2 orientations Tilt/Azimuth = 10°/-87° and 10°/-90°
PV modules Model YL260P-29b Pnom 260 Wp
PV Array Nb. of modules 69 Pnom total 17.94 kWp
Inverter Model Sunny Tripower 20000TLEE-JP 20.00 kW ac
User's needs Unlimited load (grid)

Loss diagram over the whole year

1948 kWh/m² Horizontal global irradiation

-0.07% Global incident in coll. plane


-3.62% IAM factor on global
-2.00% Soiling loss factor

1839 kWh/m² * 112 m² coll. Effective irradiance on collectors


efficiency at STC = 16.02% PV conversion

32990 kWh Array nominal energy (at STC effic.)


-0.35% PV loss due to irradiance level
-4.99% PV loss due to temperature
+0.75% Module quality loss

-1.30% LID - Light induced degradation


-1.00% Module array mismatch loss
-0.21% Ohmic wiring loss
0.00% Mixed orientation mismatch loss
30698 kWh Array virtual energy at MPP

-1.72% Inverter Loss during operation (efficiency)


0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss over nominal inv. voltage
-0.02% Inverter Loss due to voltage threshold
30165 kWh Available Energy at Inverter Output

0.00% AC ohmic loss


-1.25% External transfo loss

29787 kWh Energy injected into grid