PVSYST V6.

88 SunSource Energy (United States) 01/04/21 Page 1/6

Grid-Connected System: Simulation parameters


Project : New Project
Geographical Site Beed Country India
Situation Latitude 19.00° N Longitude 75.77° E
Time defined as Legal Time Time zone UT+5.5 Altitude 507 m
Albedo 0.20
Meteo data: Beed SolarGIS Monthly aver. , period not spec. - Synthetic

Simulation variant : New simulation variant


Simulation date 01/04/21 11h19

Simulation parameters System type Unlimited sheds


Collector Plane Orientation Tilt 10° Azimuth 0°
Sheds configuration Nb. of sheds 5 Unlimited sheds
Sheds spacing 6.00 m Collector width 4.40 m
Inactive band Top 0.02 m Bottom 0.02 m
Shading limit angle Limit profile angle 25.0° Ground cov. Ratio (GCR) 73.3 %

Models used Transposition Perez Diffuse Perez, Meteonorm


Horizon Free Horizon
Near Shadings Mutual shadings of sheds
User's needs : Unlimited load (grid)

PV Array Characteristics
PV module Si-mono Model TSM-550DE19
Custom parameters definition Manufacturer Trina Solar
Number of PV modules In series 36 modules In parallel 174 strings
Total number of PV modules Nb. modules 6264 Unit Nom. Power 550 Wp
Array global power Nominal (STC) 3445 kWp At operating cond. 3267 kWp (40°C)
Array operating characteristics (50°C) U mpp 1069 V I mpp 3056 A
Total area Module area 16367 m² Cell area 15193 m²

Inverter Model Solis-250K-EHV-5G(3voltage)


Custom parameters definition Manufacturer Ginlong Technologies
Characteristics Operating Voltage 600-1500 V Unit Nom. Power 220 kWac
Inverter pack Nb. of inverters 12 units Total Power 2640 kWac
Pnom ratio 1.30

PV Array loss factors


Array Soiling Losses Loss Fraction 3.0 %
Thermal Loss factor Uc (const) 29.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Global array res. 7.5 mOhm Loss Fraction 2.0 % at STC
LID - Light Induced Degradation Loss Fraction 2.5 %
Module Quality Loss Loss Fraction 0.0 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Strings Mismatch loss Loss Fraction 0.10 %
Incidence effect (IAM): User defined profile
0° 30° 50° 60° 70° 75° 80° 85° 90°
1.000 1.000 0.999 0.996 0.978 0.944 0.856 0.622 0.000

PVsyst Licensed to SunSource Energy (United States)


PVSYST V6.88 SunSource Energy (United States) 01/04/21 Page 2/6

Grid-Connected System: Simulation parameters

System loss factors


AC wire loss inverter to transfo Inverter voltage 800 Vac tri
Wires: 3x10000.0 mm² 1995 m Loss Fraction 2.0 % at STC
External transformer Iron loss (24H connexion) 3413 W Loss Fraction 0.1 % at STC
Resistive/Inductive losses 1.88 mOhm Loss Fraction 1.0 % at STC
Unavailability of the system 1.8 days, 3 periods Time fraction 0.5 %

Auxiliaries loss Proportionnal to Power 5.0 W/kW ... from Power thresh. 0.0 kW

PVsyst Licensed to SunSource Energy (United States)


PVSYST V6.88 SunSource Energy (United States) 01/04/21 Page 3/6

Grid-Connected System: Main results


Project : New Project
Simulation variant : New simulation variant
Main system parameters System type Unlimited sheds
PV Field Orientation Sheds disposition, tilt 10° azimuth 0°
PV modules Model TSM-550DE19 Pnom 550 Wp
PV Array Nb. of modules 6264 Pnom total 3445 kWp
Inverter Model Solis-250K-EHV-5G(3voltage) 220 kW ac
Inverter pack Nb. of units 12.0 Pnom total 2640 kW ac
User's needs Unlimited load (grid)

Main simulation results


System Production Produced Energy 5605 MWh/year Specific prod. 1627 kWh/kWp/year
Performance Ratio PR 80.05 %

Normalized productions (per installed kWp): Nominal power 3445 kWp Performance Ratio PR

8 1.0
Lc : Collection Loss (PV-array losses) 0.9 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.800
0.9
7 Ls : System Loss (inverter, ...) 0.21 kWh/kWp/day
Yf : Produced useful energy (inverter output) 4.46 kWh/kWp/day
0.8
[kWh/kWp/day]

6
0.7
Performance Ratio PR

5
0.6
Energy

4 0.5

0.4
3
Normalized

0.3
2
0.2

1
0.1

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

New simulation variant


Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² MWh MWh
January 155.0 62.00 21.80 173.7 166.3 511.7 492.2 0.822
February 163.1 63.80 24.50 177.5 170.0 511.8 492.4 0.805
March 202.6 82.50 28.60 212.2 202.9 596.7 574.3 0.786
April 204.1 89.40 32.20 205.8 196.7 572.2 550.3 0.776
May 210.5 94.50 33.00 205.9 196.5 574.8 539.6 0.761
June 152.3 91.80 28.80 147.6 140.3 426.2 410.2 0.807
July 124.0 91.50 25.60 120.9 114.5 355.7 341.9 0.821
August 127.0 89.60 24.40 125.5 119.1 371.8 344.4 0.797
September 147.5 84.90 24.80 150.2 143.0 437.8 408.0 0.789
October 166.7 76.00 24.30 177.9 169.9 516.9 497.3 0.812
November 148.8 61.80 22.30 165.4 158.2 487.9 469.4 0.824
December 149.6 58.60 20.89 169.9 162.6 504.1 484.9 0.828
Year 1951.2 946.39 25.93 2032.4 1940.1 5867.6 5604.8 0.800

Legends: GlobHor Horizontal global irradiation GlobEff Effective Global, corr. for IAM and shadings
DiffHor Horizontal diffuse irradiation EArray Effective energy at the output of the array
T_Amb T amb. E_Grid Energy injected into grid
GlobInc Global incident in coll. plane PR Performance Ratio

PVsyst Licensed to SunSource Energy (United States)


PVSYST V6.88 SunSource Energy (United States) 01/04/21 Page 4/6

Grid-Connected System: Special graphs


Project : New Project
Simulation variant : New simulation variant
Main system parameters System type Unlimited sheds
PV Field Orientation Sheds disposition, tilt 10° azimuth 0°
PV modules Model TSM-550DE19 Pnom 550 Wp
PV Array Nb. of modules 6264 Pnom total 3445 kWp
Inverter Model Solis-250K-EHV-5G(3voltage) 220 kW ac
Inverter pack Nb. of units 12.0 Pnom total 2640 kW ac
User's needs Unlimited load (grid)

Daily Input/Output diagram

25000
Values from 01/01 to 31/12

20000
[kWh/day]

15000
grid
into

10000
injected

5000
Energy

-5000
0 2 4 6 8 10
Global incident in coll. plane [kWh/m².day]

System Output Power Distribution

250000
Values from 01/01 to 31/12
Bin]

200000
/
[kWh

150000
grid
into
injected

100000
Energy

50000

0
0 500 1000 1500 2000 2500
Power injected into grid [kW]

PVsyst Licensed to SunSource Energy (United States)


PVSYST V6.88 SunSource Energy (United States) 01/04/21 Page 5/6

Grid-Connected System: Loss diagram


Project : New Project
Simulation variant : New simulation variant
Main system parameters System type Unlimited sheds
PV Field Orientation Sheds disposition, tilt 10° azimuth 0°
PV modules Model TSM-550DE19 Pnom 550 Wp
PV Array Nb. of modules 6264 Pnom total 3445 kWp
Inverter Model Solis-250K-EHV-5G(3voltage) 220 kW ac
Inverter pack Nb. of units 12.0 Pnom total 2640 kW ac
User's needs Unlimited load (grid)

Loss diagram over the whole year

1951 kWh/m² Horizontal global irradiation


+4.2% Global incident in coll. plane

-0.04% Global incident below threshold


-0.87% Near Shadings: irradiance loss
-0.73% IAM factor on global
-3.00% Soiling loss factor

1940 kWh/m² * 16367 m² coll. Effective irradiation on collectors


efficiency at STC = 21.07% PV conversion

6690 MWh Array nominal energy (at STC effic.)


+0.27% PV loss due to irradiance level

-7.59% PV loss due to temperature

-2.50% LID - Light induced degradation


-1.10% Mismatch loss, modules and strings
-1.41% Ohmic wiring loss
5893 MWh Array virtual energy at MPP

-1.16% Inverter Loss during operation (efficiency)


-0.44% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
-0.01% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
0.00% Night consumption
5799 MWh Available Energy at Inverter Output

-0.50% Auxiliaries (fans, other)


-0.71% System unavailability
-1.10% AC ohmic loss
-1.08% External transfo loss
5605 MWh Energy injected into grid

PVsyst Licensed to SunSource Energy (United States)


PVSYST V6.88 SunSource Energy (United States) 01/04/21 Page 6/6

Grid-Connected System: P50 - P90 evaluation


Project : New Project
Simulation variant : New simulation variant
Main system parameters System type Unlimited sheds
PV Field Orientation Sheds disposition, tilt 10° azimuth 0°
PV modules Model TSM-550DE19 Pnom 550 Wp
PV Array Nb. of modules 6264 Pnom total 3445 kWp
Inverter Model Solis-250K-EHV-5G(3voltage) 220 kW ac
Inverter pack Nb. of units 12.0 Pnom total 2640 kW ac
User's needs Unlimited load (grid)

Evaluation of the Production probability forecast


The probability distribution of the system production forecast for different years is mainly dependent
on the meteo data used for the simulation, and depends on the following choices:
Meteo data source SolarGIS Monthly aver. , period not spec.
Meteo data Kind Not defined Year 1995
Specified Deviation Year deviation from aver. 3%
Year-to-year variability Variance 0.5 %

The probability distribution variance is also depending on some system parameters uncertainties
Specified Deviation PV module modelling/parameters 1.0 %
Inverter efficiency uncertainty 0.5 %
Soiling and mismatch uncertainties 1.0 %
Degradation uncertainty 1.0 %
Global variability (meteo + system) Variance 1.9 % (quadratic sum)

Annual production probability Variability 105 MWh


P50 5605 MWh
P90 5470 MWh
P75 5534 MWh

Probability distribution

0.50

0.45
P50 = 5604824 kWh
0.40 E_Grid simul = 5604824 kWh

0.35
P75 = 5534133 kWh
0.30
Probability

0.25

0.20
P90 = 5470367 kWh
0.15

0.10

0.05

0.00
5300000 5400000 5500000 5600000 5700000 5800000 5900000
E_Grid system production kWh

PVsyst Licensed to SunSource Energy (United States)