Compact CK

technical manual

molded case
circuit breakers
400 - 1200 A

g MERLIN GERIN
mastering electric ! power
*
CROUPE SCHNEIDER

Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
table of contents

page

molded case circuit breakers


introduction 2
standard compliance 2
additional tests 2
ratings 2
interrupting capability 2
advantages 2
description
standard and high interrupting rating circuit breakers 4
current limiting circuit breakers 5
Ip and l2t curves 6
trip unit characteristics
STR 25DP 7
STR 45SP 0
STR 55UP 9
neutral sensor 10
zone selective interlocking 10
load monitoring 11
fault and alarm indicators 11
mini test kit * portable test kit 12
time current curves
STR 25DP (overcurrent protection) 13
STR 45SP (overcurrent protection) 14
STR 55UP (overcurrent protection) 14
option T ( ground fault protection) 15
option R (load monitonng) 16
accessories
terminals 17
location 17
shunt trip 17
undervoltage trip device 18
auxiliary and alarm switches 18
overcurrent trip switch 18
position switches 18
motor operator 20
rotary operating handle 21
padlock adaptator 24
door escutcheon 24
label holder 24
wiring diagrams 22
main connections
front connection 25
rear connection 25
drawout mounting 26

molded case switch 27

dimensions 28

appendix
UL 489 test procedures 36
routine maintenance guidelines 38
international standards 39

Courtesy
Merlin Germ
of NationalSwitchgear.com
Compact CK circuit breakers
introduction, advantages

standard compliance
CK breakers are built in accordance with
Underwriters Laboratories standard UL 489
and CSA C22-2 no.5. The circuit breaker
and its accessories, except when noted are CK 400N-CK 400NN 400 200 to 400 65,000 50,000 35,000
listed under UL File CK 800N-CK 800NN 800 400 to 800 65,000 50,000 35,000
-t1636&. - i
*-r frta y y
CK 1200N-CK 1200NN 1200 600 to 1200 65,000 50,000 35,000
mi ifel
additional tests -
CK 400H CK 400HH 400 200 to 400 100,000 65,000 42,000
In addition to standard tests and as indicated CK 800H-CK 800HH 800 400 to 800 100,000 65,000 42,000
in the table, CK breakers meet CK 1000HL 150,000
1000 500 to 1000 150 0Q0 65,000
UL 489 standard optional requirements
t

(high available fault current). CK 1200H-CK 1200HH 1200 600 to 1200 100,000 65,000 42,000
WMsSi
wmm.
* mmim m
compliance with CK 1000L 1000 500 to 1000 150,000 150,000

international standards
In addition to UL489 and CSA C 22- 2 no.5 ratings
the Compact CK has been designed to n three maximum continuous ratings
comply also with the international standard 400, 800 and 1200A rating are available with
IEC 947-2 as well as with the major different basic breakers. In addition, rating CK 400N 400 400
standards : plugs are provided to set the maximum
NEMAAB1, current setting at a value equal or lower than CK 400H 400 400
British BS 4752, the basic breaker selected, CK SOON 800 800
German VDE 660, a 100% rated circuit breakers CK 800H 800 800
a French NF C63-120, can be used for continuous operation at CK 1000HL 1000 800
Australian AS 1930- 100% of their rating as permitted by
CK 1000L 1000 800
Compact circuit breakers have been National Electrical Code, paragraph 210-22
roved for marine application by American
, ( c) exception no. 2 and 220- 10 (b) excep- CK 1200N 1200 1000
„ureau of Shipping, Bureau Veritas, Lloyd's tion, when used in an enclosure described in CK 1200H 1200 1000
Register of Shipping, Registro Italiano msmH

Navale, Germanische Lloyd's, Det Norske


page 28 with size and ventilation and
Canadian Electrical Code part 1 C22-1-1986
.
ST

CK 400NN 400 400


Veritas and Nippon Kaiji Kyokai. section 8.
CK 400HH 400 400
CK 800NN 800 800
CK 800HH 800 800
CK 1200NN 1200<D
© only with edgewise rear connections
CK 1200HH 1200©

3 types of trip units to meet HHH


specific needs S
long time
time » long time delay I fixed
1long time
load short time
monitor
short time delay
O II instantaneous fixed
1
:

;! fault indication option F


; ground
ground fault protection option T
short time zone selective Interlocking option Z

ji
<£ > load monitoring option R
is communication option C

I
^ ^
=“3 instant.
override, this trip unit covers distribution, With the STR 55UP trip unit these values
selective, generator and motor protection can be adjusted down to 2 times current
current
applications. sensor.
D for all trip units, the instantaneous override
m STR 25DP for general purpose. is automatically set at different values field interchangeable rating
STR 45SP for selective applications and according to the circuit breaker type and
generator applications. rating.
plug
Hme current characteristic curves include All solid state trip units have a field
djustable time delays for both long time
and short time protections.
iSimBBBg installable rating plug located on the front
face. The interchangeability makes rating
CK 400N/H 15 times current sensor
STR 55UP for any type of application. CK 800N/H 15 times current sensor changes simple. To avoid inadvertent errors,
Thanks to a completely adjustable protection frames and rating plugs are keyed together
curve, including an adjustable instantaneous CK 1200N/H 12 times current sensor and are not interchangeable with CJ and
CK 1000L 8 times current sensor Masterpact rating plugs.

2 Merlin Gerin
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
advantages

isolation function
The operating handle is representative of the
position of the main contacts The OFF
position can be reached only when the main
contacts are fully opened.
The handle will reach the OFF position only
if the pin A can be engaged into the slot B of
the operating mechanism.
In case of unbreakable welding of any mam
contact due to non correct application of the
circuit breaker, the mechanism will bump on
this pm.

easy installation reinforced insulation disconnecting interlock


reverse feeding Two insulation barriers separate the front .
As a safety feature In the event of
common depth face of the circuit breaker from the main disconnecting a closed drawout breaker, a
All standard and high interrupting Compact contacts (4000 volts dielectric test between mechanical interlock will trip the breaker
circuit breakers from 250 to 1200A have a main contacts and front cover). before the separation of the main
common depth of 4 1/2". This reinforced insulation allows a safe disconnects.
connection operation and safe installation of the
Cu- AL pressure terminals are listed per electrical auxiliaries. The casing in which
UL file E107821 and can be either factory or they are installed is independant from the
field installed. casing of the main contacts.
-
built in terminal blocks are provided with
the accessories, consequently intermediate integral partitioning
terminals are not required for the connection
of control wiring. They are located behind an Once the front cover has been removed, to
accessory front cover Removing this cover give access to the auxiliary compartments,
gives no access to direct access to live the main circuits remain fully insulated.
parts. Internal accessories are UL listed and Furthermore, interphase partitioning allows
are field installable. full installation between each pole even if the
front cover has been removed.

Merlin Garin 3

Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
description

7 9 10

M
11

15 14 13

CK circuit breakers exist in two different 11 rotary operating handle


physical sizes, one tor the standard and high 12 motor operator
interrupting type , and another one for the 13 racking handle
current limiting type. 14 connected position switches
15 universal drawout assembly
standard and high 16 secondary disconnects ( fixed part)

interrupting rating
circuit breakers
CK molded case circuit breakers are
designed to connect a load to an electrical
supply and to provide tripping under
overcurrent and ground fault conditions.
They consist of :
1 three-pole high strength glass polyester
casing
2 front accessory cover
-
3 qutck make/quick -break mechanism
4 handle with three positions
-
ON TRIPPED OFF -
5 solid state trip unit containing a current
sensor powered solid state logic unit with
rotary adjustment switches for up to five
functions (see description page 7,8 and 9)
6 test receptacle for use with the test kit
7 line and load terminal covers
-
8 push-to trip button
9 shunt trip or undervoltage trip
10 auxiliary and alarm switches

4 Marlin Garin

Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
description

current limiting the current to be interrupted Arc quenching due to the design and
J the basic circuit breaker interrupts
|
materials of the arc chute, a magnetic force
circuit breakers currents of up to 8 x current sensors rating, F draws the arc into the V-shaped plates
In order to compatibilize simplicity of design over this value both devices operate .
It is then split and cooled until extinction
and efficient methods, some of the principles simultaneously . This mutual assistance
used to provide a fast contact opening are noticeably reduces contact wear
described as follows :
In senes association of the basic circuit These performances are obtained by
breaker and of a limiting compartment combination of the following techniques in
equipped with an original system enables the current limiting block
outstanding performances to be obtained contact repulsion
very high interrupting capability, enhancement of induced magnetic field.
specialization of the devices according to arc quenching .

Contact repulsion
Electrodynamic forces are generated by the
current flowing in parallel conductors
The moving contact is blown-off by the
repulsive forces, which appear on a short
circuit current

Merlin Germ
5
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
description

Ip and l*t curves 200 i . 4 5 b 7 « 9 10 20 JO 40 50 60 70 80 BO 100

The limitation capability of a circuit breaker


is that characteristic whereby only a current — 480 V
less than the prospective fault current is
allowed to flow under short circuit - 100
T"* - t 600V 100

max prospective -
00 00
conditions .
This is illustrated by limitation curves which
BC
70 peak current : Z: +
i tl 00
70
give 60 /& 60
the limited peak let- through current in 50 50
relation to the RMS sym value of the
prospective short -circuit current ( the ia 40 40

short -circuit current that would flow *> I


M 30 30
continuously in the absence of protective C

equipment ) ;
the limited let- through energy ( thermal • - . •
»

stress ) In relation to the RMS sym . value of


I 20 20

the prospective short -circuit current.


o
£
5
X
«
& I
Ics
4 prospective
1 J
10

Ics peak B / a
444
/
/ ' \
\
B
/
/
444
- 6

^
5 5
/ prospective Ics / * .
/ \
/ \ 3
/
limited Isc peak V
v limited Isc \
\ 2
2 5 I 7 5 I 10 20 30 40 50 60 70 00 » 100 200
2

\\ + - prospective short circuit currant (kA RMS sym)

I
4 5 ti 7 fl 9 10 20 30 4C 50 60 7U 80 90 100 200 4

Installation of current limiting circuit 2 2


breakers offers several advantages
Better protection 10« 10«
Current limiting circuit breakers considerably
reduce the undesirable effects of
short -circuit currents in an installation 5 b
-
Reduced mechanical effects
Electrodynamic forces are reduced, thus
2 2
electrical contacts are less likely to be
deformed or broken .
Reduced electromagnetic effects 10»
10
'
Measuring equipment situated near an
electrical circuit is less affected. ?
5

2 2

I 10«
i
E
5 5

3 3

2 2

10» 10"

3 3

1
2 « 5 6 7 8 0 10 20 30 40 50 60 70 80 00 100 200
« prospective short circuit current INA RMS sym!
*
6 Merlin Gerin
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers STR 25 DP for general
application
trip units

1 rating plug
2 long time current setting
3 alarm indicator indicates 90 % load with
a fixed light and over 105 % ( the lower limit
of tnpping) with a flashing light
4 instantaneous pickup STR 25DP
u 90
5 test receptacle I
long time

time lo = 1200 A i
long time lost lur set = lr
•nnimetarCK ' XO
long time 1 2
CJl .
IV 38336

.
1IW IJIOO
A 'C a
- t?
nstantaneous

O t

\ instantaneous
5
: T:

current overcurrent RMS protection


rating plug breaker sensor plug rating
CK 400 400A 200- 225- 250-300-350 400A -
CK 800 800A 400 500-600-700-800A -
CK 1000 1000A 500-600-700-800- 1000 A
CK 1200 1200 A 600- 700-800-900 1000- 1200A -
long time current setting 0 8 to 1 x plug rating
delay at 1.5 x current setting : min 96 sec • max, 120 sec
-
at 6 x current setting ; min , 6.0 sec. max . 7.5 sec.
at 7.2 x current setting mm 4.2 sec . - max. 5.2 sec.
off long time off with rating plug cat no. 35300 ,

instantaneous -
CK 400 - CK 800 CK 1200 : 1.5 to 10 times current setting
CK 1000 1.5 to 10 times current setting with a max of 8 times
test receptacle for overcurrent testing
fault indicators
local by trip indication of the operating handle
remote by alarm and overcurrent trip switch, see page18

Merlin Genn 7
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers STR 45 SP for selective and
generator applications
trip units

1 rating plug
2 long time current setting
3 alarm indicator indicates 90 % load with
a fixed light and over 105 % ( the lower limit 2 13 4
of tripping) with a flashing light
4 short time pickup STR 45 SP
5 short time delay
6 long time delay
7 test receptabie lo = 1200A I
tong tune
II
lest ""•T-* " ""'
Oil -MU It
e
p*Oup

*
1
time
A I l ng time
° •
1 Wirt
'?fs MC

L- instant I I
t5
Sir .»
delay delay

short time 7 6 5

L. mstantaneous

overcurrent RMS protection


current rating plug breaker sensor plug rating
CK 400 400 A 200 -225- 250-300 -350- 400A
CK 800 800A 400 -500 - 600-700-800A
CK tOOO 1000A 500-600*700-800- 1000A
CK 1200 1200A 600-700 -800-900-1000- 1200 A
long time current setting 0 8 to 1 x plug rating
delay delay band 15 30 60 120 240 480
at 1 5 x cur . set . mm. 12 24 48 96 192 384
max . 15 30 60 120 240 480
at 6 x cur set min. 0.75 1 50 3.00 6.0 12 24
max 0.94 1.88 3.75 7.5 15 30
at 7.2 x cur . set . min. 0.52 1.04 2.08 4.2 8.3 16.7
max . 0.65 1.30 2.60 5.2 10.4 20.8
off long time off with rating plug cat no 35300
short time pickup 1.5 to 10 x current setting
delay bands -
0 0.1 0.2 0.3 - -
Instantaneous -
CK 400 CK 800 : override at 15 times current sensors
CK 1200 override at 12 times current sensors
CK 1000 : override at 8 times current sensors
test receptacle for overcurrent testing
fault indicators
local by tnp indication of the operating handle
remote by alarm and overcurrent trip switch see page 18

8 Merlin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers STR 55 UP for all types of
applications
trip units

1 rating plug
2 long time pickup
3 alarm indicator indicates 90 % load with
a fixed light and over 105 % ( the lower limit 2 8 13 14 15
of tripping) with a flashing light
4 short time pickup
STR 55UP 6
5 instantaneous pickup
6 local fault and load indicators: .. tong tme •tlm
non grm«J
l i lll
*
they consist in built -in light emitting diodes
fault indicators that discriminate the 3
lo = 1200 A
WP
*« iuo tm Crn »
bod
1 i ifTHU'
tong tuTui
w
tesi . cur ref =ir
9 « nl
aiqtuir pICKup
5 ft I . 7
1 /
causes of topping overload short circuit
and ground faulf if any
,

bargraph indicating the load in steps of 60.


*
w 1200
A
-*
to
. JM

(
0
3U
wiviurtj
-' J qfnuod shon lirni fr
’ff
w
3 .) a
.
J
i
,„‘
4
8
.
70 80 % of the current setting
7 ground fault pickup
*
'
.
4 It Ot »
| rtfl
8 ground fault time delay or second load TFR grcuml tadmrftx
monitoring pickup
9 load monitoring pickup
10 short time delay 12 11 10 9
11 long time delay
12 test receptacle
Overcurrent protection

time i load overcurrent RMS protection


k long time
monitor rating plug breaker sensor plug rating
CK 400 400 A 200 ’ - 225 ? 250 i -300 -350 400A - -
CK 800 800A 400 1 5007 -600-700-800 A -
CK 1000 1000 A 500 ! -6002 - 700 -800-1000 A
CK 1200 1200A 600' v -700® -800-900-1000- 1200 A
snort nme long time current setting 0 8 to 1 x plug rating
delay delay band 15 30 60 120 240 480
5 x CU set min 12 24 48 96 192 384
instant
at 6 x cur set .
max 15 30 60 120 240 480
min 0.75 1 50 3.00 6.Q 12 24
max. 0.94 1 ,88 3,75 7.5 15 30
current at 7.2 x cur set min. 0.52 104 2.08 4 2 8.3 167
max. 0.65 1.30 2.60 5.2 10.4 20.8
Ground fault protection short time pickup t 5 to 10 x current setting
time delay bands -
0 0.1 * 0.2 0.3 -
instantaneous -
CK 400 CK 800 2 to 15 times the current sensors
CK 1200 2 to 12 times the current sensors
ground
CK 1000 2 to 8 times the current sensors
test receptacle for overcurrent and ground fault testing
ground fault protection (option T) 3
pickup 0.2 to 0 6 times the current sensors
O delay band 0.1 - 0 . 2 - 0 . 3 - 0 . 4
zone selective interlocking (option Z )
for short time and ground fault protection - see page 10
load monitoring (option R )
current inverse time pickup Ic 1 = 0 8 to 1 x current setting
t 1he lowest pickup setting ot the inverse time alarm Ic2 4 = o,5 to 1 x current setting
alarm Ic2 may not work properly if the long time closing tr 1 = tr /2 ( tr - long time delay )
current sotting and/ or me toad decreases below
80 % n this plug rating
time delay -
tr2 tr /4 ( tr ^ long time delay)
opening fixed at 10 sec.
plugrating min Ic2 pickup setting
time deiay &
'.1 0.8 to 1 x current setting
<2 0 6 to 1 x current setting fault and load indicators
3 option T residual scheme, option W ; not discriminated local by tnp indication of the operating handle
source ground return The maximum ground fault
pickup meets ^ 991 National Etecincal Code remote by alarm and overcurrent tnp switch see page 18
paragraph 230-95{ a) (not exceed 1200AJ discriminated local with option F see page 11 _ -
•i not available with ground fault protection remote with option C (communication )
(option T)
5 see time -current curve page 16

MeMin Gent -
Courtesy of NationalSwitchgear.com
9
neutral sensor
Compact CK circuit breakers zone selective interlocking
trip units

neutral sensor location


cable size 18- 14 AWG/1.5mm*
main max , length 50 feet/ 15m
Ground fault protection may be applied on
breaker wiring twisted or not
304W or 303W circuits. On 304W an
external neutral sensor must be used.
This neutral current sensor shall have the <n>
same ampere rating as the breaker.
<0>
The following are current sensors for use
with CK breakers equipped with
STR 55UP trip units with option T.
rating
400 A
for
CK 400
cat. no.
35700
~
o o
800 A CK 800 35701 T1 T2
1000 A CK 1000L 35702
1200A CK 1200 35703 S1 S2
Wiring neutral
T
It shall be as indicated in opposite fig. and
on the neutral sensor label Observe control
-
wiring ( terminal S1 S2. T1-T 2) .
ground fault
t S1
— o
_ T1
feeder
Terminals neutral C T' s breaker
j
~
terminals S1- S2 (neutral sensor) are of S2 J2
"quick -connect " type (1/ 4" female tab socket
are supplied with current sensors) .
terminals T 1-T2 (circuit breaker) are
pressure type terminal blocks. These
terminals are intended for use with 18 to 14
AWG stranded copper wire

zone selective interlocking


( option Z )
Option Z provides selectivity and reduces
the duration of fault compared to traditional
time-delayed selectivity . By interconnecting
several trip units, it locates the ground fault
or short-circuit and allows the upstream
circuit breaker to trip at the minimum time
regardless of the time delay setting of this
breaker.

Fault 1
Circuit breaker A will clear the fault within
the minimum time delay regardless of its
time delay setting.

Fault 2
Circuit breaker B will inform the upstream
circuit breaker A that it is clearing the fault
and will prevent it from tripping instanta-
neously
As a safety feature , the breaker A will trip at
the end of its time delay setting If the fault is
not cleared during this time.
Note :
circuit breaker terminals are delivered with
"in" terminals jumpered Remove the jumber
when interlocking with a downstream
breaker .
Compact CK type molded case circuit
breakers may be also interlocked with
Masterpact circuit breaker with ZSI option
do not ground.
.

Merlin Germ
10 Courtesy of NationalSwitchgear.com
Compact CK circuit breakers load monitoring,
fault and load indicators
trip units

load monitoring if the trip unit is equipped with option C


(communication) there is only one pickup
(option R ) .
limit (Id ) Furthermore there is no static
The option R provides 2 independent static contact integrated in the trip unit Instead a
contacts which operates when the current load monitoring signal is sent via the
exceeds adjustable pickup limits ( two communication output to a separate relaying
independent limits Ic 1 and Ic2 adjustable unit with 5 A contacts,
from 0 8 and 0.5 to 1 x the long time current wiring diagram page 23
setting.
when the current exceeds the limit Ic1 (or
Ic2) the contact R 1 -R 2 (or R 3-R 4) closes,
following an inverse time characteristics a ,

when the current drops below the limit Id


(or Ic2) the contact R 1 -R 2 (or R 3-R 4) opens
with constant time delay ( 10 seconds) b
These contacts can be used for load
shedding, alarms, indications, etc...
output 240V AC max
0 1 A triac-optodecoupled
input self powered provided a
minimum of 0.22 x In through
the breaker sensors.

fault and load indicators A separate 24 to 250 V AC or DC control


source is required. Fault indications are
( option F) maintened as long as the control voltage is
Fault indications differentiate the 3 causes provided When the control voltage is
of tripping : overload, short circuit and considered as unreliable, auxiliary power
ground fault if any. module (AD) and battery pack module (BAT)
Option F provides LED indicators located on may be added to preserve memory .
the front face of the trip unit.
input voltages available for the module
Alarm indicaton indicates 90 % load with (AD):
a fixed light and over 105 % ( the lower limit DC : 24 - 4 8 - 125V
of tripping) with a flashing light. consumption : 10W
60Hz 120 V
Bargraph indicating the load in steps of 60 . consumption : 10VA
70, 80 % of the current setting.
Safeguard period of the battery pack
module (BAT) :
approximately 12 hours .

communication
( option C)
. .
Transmitting data concerning 11, 12 13 Imax,
all settings of the trip unit, identification of
plug, load monitoring operations, fault
indications level of thermal memory, internal
temperature warning ,

Courtesy
Merlin Germ
of NationalSwitchgear.com 11
mini test kit
Compact CK circuit breakers portable test kit
trip units

Every trip unit is equipped with a test


receptacle that can be used with a test kit.
This particular design allows a safe and
simple testing.
Tests performed by test kits are only
functional tests designed to electrically test
the operating integrity of the trip unit, the flux
shifter and the mechanical operation of the
breaker . Tests are not designed to calibrate
the breaker .
Calibration can best be done at the factory.
cat. no.
mini test kit 43362
portable test kit 55651
STR adapter 46900

long time : Caution :


mini test kit test leads shall be connected according to when breaker trips release the test switch
Overcurrent protection test proceedure
1 operate on " OFF load" conditions
-
“+ overcurrent " markings (on trip unit ) . immediatly.
set current selector K of test kit at trip unit Under no circumstances, should this switch
2 record the short time or instantaneous
pickup setting and set the trip unit to the
.
long time setting ( see table 1 ) be in the “ON" position for more than 120 %
move Ir switch The breaker will trip in the of the expected maximum tripping time.
minimum setting following tripping time :
3 close the circuit breaker - STR 25DP : 50 < t < 70 sec. short time or instantaneous :
4 connect the two + and * test leads into -
- STR 45SP STR 55UP : j tests leads shall be connected according
trip unit test receptacle, observing the
delay band tripping time
-
to V overcurrent " markings (on trip unit),
- overcurrent ” markings. J move pickup switch for one second max
5 press the test kit push button, the circuit 15 5 < t < 9 sec. to trip breaker
breaker will trip. 30 10 < t < 15 sec
6 return to initial setting.
60 20 < t < 35 sec . ground fault ( residual scheme) :
Caution :
Batteries 120 50 < t < 70 sec.
test leads shall be connected according
The mini test kit requires five 9 Volt batteries. 240 100 < t < 150 sec to " + - ground" markings ( on trip unit). Move
Alkaline batteries are recommended. 480 200 < t < 350 sec pickup switch for one second max to trip the
breaker.
Dimensions : 5 1/2 x 3 x 1 1/ 2
table 1 : value of K
type plug rating ( A ) trip unit long time set at :
portable test kit 1.00 0.90 0.60
Warning : touching test plug pins may CK 400 200 0.50 0.45 0.40
cause electrical shock when power cord 225 0.55 0.50 0.45
is connected. Power switch should never
be in the ON position unless test plug is 250 0.65 0.55 0.50
connected. 300 0.75 0.65 0.60
350 0.90 0.80 0.70
prior testing : 400 1 00 0.90 0.80
1 operate on "off load" conditions.
CK 800 400 0.50 0.45 0.40
2 set control voltage selector located at the
back of test kit to proper voltage. 500 0.65 0.55 0.50
3 switch for control power has to be in the 600 0.75 0.65 0.60
OFF position. 700 090 0.80 0.70
4 remove the transparent trip unit cover 0.80
800 1.00 0.90
and connect test leads according to
0.50 0.45 0.40
-
" + overcurrent " markings. CK 1000L 500
0.60 0.55 0.50
5 plug in the power cord 600
6 turn control power switch ON . The 700 0.70 0.65 0.55
.
"power on' lamp should light . If not check 800 080 0.70 0.65
the source, then the test kit fuse ( 1 A fuse).
1000 1 00 0.90 0.80
7 close the breaker.
CK 1200 600 050 0.45 0.40
700 0.60 0.50 0.45
800 070 0.60 0.50
900 075 0.70 0.60
1000 080 0.75 060
1200 1.00 0.90 0.80

Merlin Gerin
12
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
time current curves

overcurrent protection STR 25 DP trip unit


g
» 0000 5 8 . 7 8 9 1 1 2 1 5 2 3 4 5 6 7 8 9 1 0 20 30 40 SOdD
^ gS - I
4 8000 3000 - brocket current rating plug
type sensor
7000
6000
CK 400 400A 200 225, 250 300 350 400
5000 current setting ~T » T - CK 600
CK » 000
eooA
1QOQA
400
500
500 600 700 600
600 7Q0 800 1 Q0Q
4000 It * 0 8 t iplug rating ( lot
I
CK 1200
breaker
1200A 600 700 800 900 1000 1230
Interrupting ratings
-
3000
.
.
typ« RMS symmetrical Amps
240V 4fl0V 600V
2300 -
CK 4DON CK 40DNN 65.000 50.000 35 000
I CK BOON CK 900NN 65.000 50.000 35.000
CK 1200N CK 12O0NN 65.QOC 50.000 35 000
1000 CK 400H CK DO
4 MR 100.0CC 65.000 42 000
900 CK BOOM CK BOOHH 100 000 65.003 42 000
800
r• 00 CK tOOOHL 150 000 150.000 65.000
600 . CK 120OH CK 1200HM 100.000 65.000 42 000
S30
t
- 150.000 150.000
400
. -
XX) 300
.
230 - 20Q

100 10Q
90 90
80
70 70
60 60
SO SO
43 40

- . 30

20 20

/:
o
c

is 10

6
K>\ - -4 -
-
to
9
6
o
E
— 6 - 6

- . \ ' *
—H- f

— 10\
*
2
T 1 instantaneous
It = ’ 5 . 10 « current setting ( lr )
.
I
- 1
9
- *
- 8
7
e 6

,
4 4

——
i 1-4-

i
— f 3

H-4
i
09 09
08 oe
07 V 07
06 »36
05 ~ 05

(V
* .. - -
04
.
03 03
. i

02 02
\
*
>
ot 01
5 6 7 8 9 t I2 15 2 3 4 5 6 7 8 910 20 30 40 SO 60 6 £ £8
multiple of current setting ( lr >
l S i § § £!§! i I |

Courtesy
Morim Genn
of NationalSwitchgear.com 13
Compact CK circuit breakers
time current curves

overcurrent protection STR 45 SP and STR 55UP unit

14 Martin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
time current curves

ground fault protection (for STR 55UP trip unit)


4 5 « 789112 t5 2 3
* 5 6 7 0 910 20
A '9000
0000
8000 :4 - breaker currant rating plug
7000 * *
YP
CK 400 400A .
200, 225 250, 300. 350, 400
woo
I
CK 800 BOOA .
400, 500 600 700. 600
4000 CK « 000 1000 A 600 600 700 800, 1000
: CK « 200 1200A 600, 700, 800 900 1000 1200
300 -
. type RMS symmetrical Amps
200C 240V 480V 600 V
CK 400N CK 400NN 65.000 60.000 35.000
-
CK BOON CK 800NN 65.000 50 000 35.000
CK 1200N CK 1200NN 65000 _ 50,000 35 ,000
11XXJ
• 00
- - CK 400H CK OOHH
* 100.000 65 000 42.000
BCG
700
son
- — CK 0OOH CK 800HH
CK 1000HL
100.000
150.000
65 000
150.000
42.000
65.000
CK 1200H CK 1200HH 100 000 65 000 42.000
500
pickup : CK 10001 150.000 150 000
0.2 0.6 11 » = 0 2 0 6
* current sensor ( In)
IOC
-
.
300
' I
300

200

i -
- 200

too
9D
80
— ..
*
-
100
90
BO
70
8C 70
60
5L
40
* *
- W
- 40
30
30
.
20
20
4)
tJ
C
o
S 10
9 - to
£ 9
E
a
- 8
6
e
-
*
— . t 5
- 4

3
:
2 f
Rt ON
t 4 .

. -
t
v
5
kl - -- • •
*
8
6
4 4 4 4
-
- 7

5 U k \V • • 6
4
. i \ . 0.4 *
-
t -4— .
4
.3
44-4-4- .. 3
0.3
2
- 2

*
V 0.2
| :

i
08 1 1 OFF *
* : 0.1 —
1 ^ 09
06
07
H
*

07
06
06
OS
08
J4
*
03
tr 04

02
.
-
—4 -

*
03

02
. .
..
'

T 01
01
SS £ 8$ i 4 5 5 7 8 9 1 1 2 *
5 2 3 4 5 C 7 89 0
' 20 30 40 50 60 S 8 3
^ § 8 i s seas
multiple of current setting lr ) <

Merlin Genri
15
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
time current curves

load monitoring (for STR 55UP trip units )

16 Merlin Genn

Courtesy of NationalSwitchgear.com
Compact CK circuit breakers terminals
shunt trip

Internal accessories comply with


requirements of Underwriters Laboratones
Standard UL 489 and CSA 022 2 no 5
Most of them as noted below are listed for
tield installation per UL file -fr107(KH E103955
Installation
shunt trip field installable
undervoltage tnp field installable
2 auxiliary switches field installable
1 aux 4 1 alarm switches field installable
3 aux * 1alarm switches field installable
motor operator field installable
overcurrenl trip switch factory mounted
position switches factory mounted

terminals
Accessory terminals are standard and
located within the breaker behind the front
,

cover
Two types are provided
field installable accessories
terminals are directly mounted on the
accessory Each terminal may be connected
by one or two stranded copper wires 18 to
14 AWG
Tightening torque 12. lb in
Cable strip length 3 8 ' approximate
'
factory mounted accessories
pressure type terminals secured by a screw
on the breaker Each terminal may be
connected by one stranded copper wire 18
to 14 AWG
Cable strip length 3/8 " approximate
In the factory these terminals are facing
towards the top of circuit breaker ( see
gutters on wiring diagram page 24 ) For his
convenience the end user may direct them
to the side of the breaker This can be done
easily on sue
1 remove terminal using a scewdnver
2 break the knock -out for the wire exit
3 replace terminal
Caution :
open circuit breaker and disconnect
control power before removing this front
cover .

shunt trip rated inrush ( * ) cal. no.


The shunt trip is mtermitently rated with a control voltage voltage ( V ) current ( A )
series normally open contact 60 Hz 120 2.5 36437
AC shunt trips can be operated at 240 03 36446
55 percent of their rated voltage making
,
* Lt"P 480 05 36446
them suitable for use with ground fault
protection devices.
rI button 600 1 36447
Minimum operating voltage : DC 12 68 36434
AC 55 % of rated voltage 24 3.0 36435
DC 75 % of rated voltage 48 1 1 36436
125 0.4 36437
( •) during 50 ms max

i
I

vf .
coil Clearing sw icn

Merlin Genr 17
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers undervoltage trip device
auxiliary and alarm switches
overcurrent trip switch
position switches

undervoltage trip device rated sealed-in cat. no.


Undervoltage trip devices may be used as control voltage voltage (V ) current (A)
circuit interlocks . T 60 Hz 120 0.050 36418
If an undervoltage condition exists , opera -
tion of the closing mechanism of the circuit
breaker will not permit the main contacts to
touch , even momentarily .
£ trip
button
240
480
600
0.020
0.014
0.010
36419
36420
36421
Dropout : 35 - 70 % ol rated voltage DC 24 0.037 36410
Pickup : 85 % of rated voltage 48 0 022 36411
125 0.014 36412

auxiliary and alarm switches control voltage control voltage


Auxiliary switches consist of SPDT switcnes T t t —
— falarm m -t- t— T
and provide remote information of the I of * | on lock i | ott | on lock I alarm
breaker status.
A arm switch provides alarm / lockout
n
T T
out w

-OJ.
information , When the breaker is reset , the h2 14 22 „24 32 „34 J 9? .
.94 J
O O O O—t
' a ' contact ( a <
arm ) is open , and the " b '
contact ( lockout ) is closed
This SPDT sw tch is operated when the b a b a b c; b a
breaker is tripped by the trip unit, shunt trip
or undervoltage trip device or "push- to - trip '
button.

2 auxiliary switches
cal. no.
36404
•-
21
. 31
i
91

1 aux . f 1 alarm switch 36405 voltage (V ) 2 auxiliary 1 auxiliary + 1 alarm 3 auxiliary + 1 alarm
3 aux . + 1 alarm switch 36402 auxiliary alarm auxiliary alarm
50/60 Hz 240 6A 6A 5A 6A 5A
480 6A 6A 5A
600 3A 3A 3A
DC 125 10.5A 0.5A 0.5 A 0.5 A 0.5 A
250 0.25A 0.25 A 0.25 A 0.25A 0.25 A
overcurrent trip switch control voltage
voltage (V) current (A)
50 /60 Hz 240
The auxi lary switch consists of a SPDT
The "a" contact closes when the breaker
t DC 125
2
0.1
operates through the trip unit ( overcurrent or
ground fault ). It does not operate if tr pping
(82)
9184 fault Note : type a switch is delivered as standard Or
’equest type b Is available
is by shunt trip undervo tage trip device or
,

push - to- trip button. ' ( terminal 82 instead of 84 )


Not available on m c s.

The b" contact is used as interlock when


resetting of the breaker is done remotely or
automatically .
catalog number 36403
81
i
position switches r f T- voltage (V) current (A)
On drawout mecnanism SPDT switches are disconnected 50/60 Hz 480 6

--
i
operated c ose to the connected or j connectedj 600 3
disconnected position .
connected position 46963
91314 a 312 1 324 322 352
¥354~
1
~
¥
362 1364
DC 125
250
0.5
0.25
disconnected position 46964

| 311 , 321 [ 351 [ 361

*
18 Merm Garir
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers motor operator

motor operator rated inrush fuse


voltage ( V ) current ( A ) amps ( A )
The motor operator remotely operates the
circuit breaker Besides, a toggle remains 50/60 Hz 120 6 10
accessible to open and close the breaker 240 4 10
locally DC 24 15 15
ON. TRIPPED and OFF positions are clearly 48 11 10
indicated by the operating handle
Provision for padlocking is provided as 125 6 10
standard to lock the toggle in the OFF Operating voltage 85 -110° r of rated
position . When locked manual or remote voltage
closing is mpossioie Max . operation frequency 2 per minute
Interlock switches electrically disconnect the Closing time 400 ms
motor operator when the front transparent Opening time 500 ms
cover is open for local operation or padloc - Minimum operating order 100 ms
king and when the complete mechanism is
rocked for connecting internal accessories
( shunt trip , undervoltage trip device auxiliary
switches or motor operator )

Under fault conditions the operating handle


will indicate the tripped position of the
breaker Depending on the wiring resetting
,

can be done locally, remotely or


automatically ( see wiring diagrams ) manual resetting remote resetting using
Field installable. ( standard scheme) a resetting push button

Note : using an overcurrent trip switch


t - T- T —
T—T -T t
.
i cat no 36403 ) automatic resetting is not
possible after an overcurrent i e short h°ni :liotl
b
V"! IK
T "
*

•i-
reset

circuit or overload, but possible after a 1B4 1A« ! 8'


voiontary iripp ng. local or remote oA 2 0 0
9”
voltage (V)
50/60 H7 120
240
cat . no.
35678
35679
o
Xf
_
Tc /X-
TCD
LP2E"
DC 24 35670
48 35671 cst b
125 35672 CV

% 15 t 152

motor overcurrent
operator trip switch -

automatic resetting remote resetting during


after tripping opening sequence
rrr T n
A| nj li-<
T ° i •I *
1

i
6vy :c> s o <5 Q 6-
i caution control diagram shall be designed to
a 11 “CD ^ b "Ta "
interlock remote on and off O'ders
? overcurrent trip switch is recommended tc lock
'

- iPlET II
remote resetting after an electrical fault CS . cs L
C1 limit switch
CV locking switch opens when CV
L
n"
b ll CV
1"
b
the breaker is manually operated
• the breaker is padlocked

- the motor operator is rocked


CDbuilt-m alarm switch, operates when breaker
f I
. 0 $ - , 0152L _ y
° A V
trips by an electrical fault or opening coils. I
CA self feeding switch i l
CS electrical interlock switch delivered with motor overcurrent auxiliary motor overcurrent
automatic source changeover operator trip switch 2 switch operator trip switch t
M motor

Mprlm Geon 19
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers motor operator

mechanical interlock
Mounted on the two operators, the interlock
prevents the two breakers from being
simultaneously closed Breakers can be both
or individually opened
In addition to the mechanical interlock , an
electrical interlock is mandatory between the
two operators
Factory mounted
switching time : 0.9 sec
number of switching operations : 10.000.
Not UL listed.
catalog number 35680

electrical interlock

*i -- r-

i. oft i_Lon
normal
f 1 normal ' r •' normal
standby L Af +onstandby i. ofl
' | standby
•with a minimum
time celay of 1 sec
between off and on
.
| with a minimum
time aeiay of I sec
between off and on
orders orders

.
I
A i AAAA
rt
I A A
A?
A
A? B4 B4
I 12 14 12 14

9 9 II 9 ? II
_

44

TA
111 =U"
CA' CAT »
> " "b
II• - Pic
1 “ CD
* b a

l I «

"
’ ey cs It
"
’ cv cs II
II’ II
, ,
A l N 152 \ 151
O
11 A 1 \ / ' 5? v / 151

Y Y Y. i ’ ? Y Y.
i
i i
i
L .
i J
I

1
motor auxiliary motor auxiliary
operator switch operator switch

normal source standby source

20 Merlin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers rotary operating handle

rotary operating handle


Two versions are available :

Directly mounted
This handle is directly mounted on the circuit
breaker It accomodates as standard up to
three padlocks to ock the handle in the OFF
position However , a knockout tab can be
removed to allow the locking of the handle in
the ON position. Due to the trip free
mechanism, padlocking in such a position
will not prevent the circuit breake' from
tripping under overcurrent conditions.
The padlocked handle will continue to
indicate ON.
Padlock shackle diameter 1 /4 to 5/ 16

Note :
A mechanical interlock (cat no 44946) links
two rotary handles and constitues a manual
source changeover This device is only
available for direct rotary handies.
Simultaneous closing of the two breakers is
prevented but simultaeous opening is
possible. The breakers are norma ly f xed on
a panel or on rails.
catalog number 46933

Door -mounted type


The handle s removable and can be fitted
on a door - mounted mechanism . A 16 long
shaft extension is supplied ana can be cut to
a suitable length. A cutting and drilling jig is
provided
The mechanism has the same features as
the directly mounted type and provides door
interlocking preventing the door from being
opened when the breaker is closed .
The handle mechanism can be used in
NEMA 3 R and 12 enclosure applications

Note :
Door interlock can be disabled or defeated
by turning the defeating screw located on
the front face
It accomodates as standard up to three
padlocks to lock the handle < n th OFF or ON
i by removing a knockout ) position
Padlocking is possible only if the coupling of
the extension shaft and the door mounted
mechanism is correct.
catalog number 46933 42897
UL listed under UL file E 107821.

Note : door interlock can be disabled or position or ON ( by removing a knockout ).


defeated by turning tne defeating screw Padlocking is possible only if the coupling of
located on the front face. the extension shaft and the door mounted
It accomodates as standard up to three mechanism is correctly done
padlocks to lock the handle in the OFF

Courtesy
Wortin Genr of NationalSwitchgear.com 21
Compact CK circuit breakers
wiring diagrams

drawout position switches auxiliary switches remote operation

overcurrent auxiliary and shunt undervoltage motor


trip switch alarm switches trip or trip device operator X
-f r i r i r i r
? t 1 r1 t -r r —Tt -.- t - 9
lock I I I I
I I fault out I I
I I
# ifr -
‘h :M !h
I I closed I I ON i I OFF
connected disconnected
i i i l ! I button

I I
CK open

I I I I
I
I I
,I 314312 4 3
I

^^^^^ . I I

0% » A?2 l# x

[ 311 M32?
’”

^ 351 > 361


- —
^
A ' -fir A— A—A:“A • A~ A A
A / V

)
r6 in — v ——— —— 0~i .82
[uv or ST ©
I4$ o—O —-O1

151 152

V \
V' '' '

-O-21 O — O' -
’Vi
"
jAl 11 [ 31 41 C1

+ 9 9 9 9

CD see page 19 for other winng diagrams


\
1
type a switch is delivered as standard On request type b can be available ( terminal 82 instead of 84) Not available on m.c .s
• coil clearing switch
@ zone selective interlocking with an upstream circuit breaker. Remove the lumper.
5 zone selective interlocking with a downstream circuit breaker. Remove the jumper.
« for ( 2) auxiliary switches (cat 36404) terminal designations are 11. 12. 14 and 21.22. 24.
Note : contacts are shown with the breaker in the open and reset position

22 Merlin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
wiring diagrams

trip unit options fixed mounting

3 auxiliary
1 alarm switch
cat no - 36402
ground load local fault commumca - 3 auxiliary switches
fault ZSI monitoring indications tions 11 12- 14 ?i 22 24 .
r i r i r 31 32 3*1
T t alarm switch
9 - 92- 94
'
2 auxiliary switches
external -
cat no 36404
CT
Ic
external neutral -
11- 12- 14 31 32 34
* sensor 1 auxiliary

n Ic2
tem'inalTt T 2

zone selective
interloktng
1 alarm switch

auxiliary
-
cat no 36405

31 32 - 34
switch
input terminal .
alarm 5* v tch
91 92 94
upstream Z21- Z22
I
brea er
* | .
outpi t lerrmna overcurrent

*I 211 212
or
trip switch
•ermma 81 84
'
_
4
.RUH oe-V£ load monitoring — fault
^ ^ 11.211 2 3 ' indicators

terminal H3- R 4 control power
terminal Fn 1? -
load monitoring
A—A ~A 7\~
shunt trip
A A Irrmina R 1 -H2
A A A A A A terminal C 1 C:’
or
undervoltage trip
communication
-
terminal D1 D2
iemimai r
- c -

rV —Cn r C - —Cm
option T option Z -IR -L option F option C possible wire exits

- —Q-
O 1 possible International gutters

knock - outs Break only these required dipending


of the desired direction of wiring

VL V^ - y y y y
drawout mounting

Pz22 >R2 ?R 4 9 9,
Z2
1
^
!—
§ 1

downstream
« I
^ ^
24 to 250V
breaker AC or DC secondary
disconnecting
blocks
o o
und » -
MHtk motoi if
'* | *I-II*n»
I
•' MI
" *Jj
M

Or

lii >
II 11 u a .
• marr Mu> I - - «.
Wow 11

4
P
^ i

or
*
trip unit options

T1
or
R 1 IZ 111 Z2 IFt 11 R 3
i
e- T2
or or
R 2 IZt 2lZl 2 lZ22l R -
V rlir Genti
^ PR
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers padlock adaptator
door escutcheon
label holder
kirk key lock
boot

padlock adaptator door escutcheon label holder


A padlock adaptator is available to padlock A door escutcheon provides better A label holder can be clipped onto the front
the circuit breaker in the OFF position It is appearance of the door cutout cover It permits an easy circuit breaker
similar to the one used on CE.CF and CJ identification
type , catalog number 44938
The adaptator accomodates up to 3 catalog number 42976
padlocks.
Padlock shackle diameter : 1 /4 to 5/ 16
catalog number 44936

Kirk key lock boot


A K rk key lock is used to lock the circuit The boot provides a light seal when a
breaker m the OFF position breaker is used behind a panel or door with
The deadbolt of the lock prevents the circuit cutout The square part fits over the breaker
breaker handle from being moved . The key cover and the middle provides a rubber
is removable when the deadbolt is extended cover for the toggle, improving protection to
It is provided as standard mounted on the NEMA 3R
right - pole position but can be mounted on
reouest on the left pole position Mounting catalog number 44965
screws can be sealed The assembly
comprises mounting plate and screws. It
doesn' t nclude K rk key lock and wire seal ,
Installable on CK CE CF and CJ frame ( not
UL listed - not CSA ) .
catalog number 35636

24 Memn Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
main connections

CK circuit breakers may be connected with Complete instructions are given with tne set
bus bars or cables on both line and load of pressure type terminals and in the
sides. installation instructions proviaed with the
The type of connections should be specified breaker.
when ordenng Caution : modification of terminals requires
A field modification is possible to e ther removing of a front and back
mount or remove the pressure type terminal cover . When the modification is
terminals. completed , this cover must be replaced.

front connection with bus bars .


Note : for voltages above 240 V insulation
around bus bars may be required to meet
CK circuit breaker may be connected with
one to three copper or aluminium bus bars
spacmgs between phases required by the
2 x 1/4 or 1 3/4 x 1/4
H NEC
possible msultation
Terminal cover when 2' bars
The short terminal cover ( 1 11/16" height ) is are used
provided. However , the long terminal cover
( 3 1/ 16“ height ) normally supplied with
pressure type terminals may be used

Tightening
The bus bars shall be secured by two bolts. 7 16" dia
011
; 2 ) holes
IV "
<50

with cables
Copper or aluminium cables may be
connected by pressure type connectors w th
a capacity of :
rating 800 Amp.
cat . no 46961
1 to 2 cables 2'0 to 400 MCM Cu
or 1 to 3 cables 2 0 to 300 MCM Cu
or 1 to 3 cables 4 0 to 400 MCM Al
cable strip length : 1 1/ 4 .
rating 1200 Amp.
cat no 46960
1 to 4 cables 3/0 to 500 MCM Cu
1 to 4 cables 4/0 to 500 MCM Al
cat . no 46966
t to 3 cables 250 to 600 MCM Cu or Al

Cable strip lengths : 1 1 / 4“ ( front holes) and


2 1 /4 " ( back holes ) .
Cables shall be torqued at 375 ib.in (3/8
alien wrench ).
The connectors are secured on breaker by
screws tightened at 400 lb. m .
Caution : connectors are plated for
reliable electrical contact .
Do not abrase them.

rear connection
Rear bus bar connections are used for
switchboard mounting According to the way
of mounting the rear connections, they
provide on N and H type breakers vertical or
edgewise connection possibilities

cat, no. (each)


CK 400 CK 800 - CK 1200 46958
CK 1000HL - CK 1000L
Hat 46916
edgewise 46913

Merlin Genu 25
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
main connections

universal drawout assembly door interlock position switches


This lock prevents the compartment door see page ! 8
from being opened when the breaker is in
connected position 46963
the connected " position. If the breaker is out
into the 'connected" position with the door disconnected position 46964
open the latter can be closed without
disconnecting the breaker. door cutout
Note : Escutcheon can be provided to allow to have
tor more safety this interlock may be used
,
access to
with racking interlock below
cat. no.
catalog number 46834 handle trip unit 46831
rot op . handle + tnp unit 46832
racking interlock racking mechanism 46830
This lock prevents racking in tne breaker
when the door is open
.
( Insertion of the breaker rack ng crank is not
possible when the compartment door is
open ) .

catalog number 46835

disconnected position
locking
The breaker can be locked in the
" disconnected" position by the means of 1 to
3 padlocks (padlocks not provided) or 1 Kirk
When the breaker is in the connected
key lock Factory mounted
position , Ihe primary voltage is fed through
Mounted on the stationary assembly and
the breaker by means of multiple finger
accessible with the cubicle door locked
disconnects A racking handle permanently
located on the stationary assembly is used Note :
to connect and disconnect ' he breaker thru keylock is of the captive key type tree
the door As a safety feature in the event of when locked .
disconnecting a closed breaker a on special order , locking may be possible
mechanical interlock will tnp the breaker on disconnected an connected positions
before the separation of the mam padlocking device standard
disconnects
Control voltage is provided through provisior for Kirk key lock 46836
secondary disconnects in the connected Kirk key lock 35635
position only See page 22 for the number of
secondary disconnects required
UL listed under file E 116305
cat. no. standard drawout assembly This version provides in a smaller volume
the same disconnecting / connecting and
fixed part
safety features
CK 400 - CK 800 - CK 1200 46820
CK 1000HL - CK 1000L i
' 46822 cat. no .
rear connections complete assembly
flat leach ) 46990 -
CK 400 CK 800 CK 1200
' 46851
Hal « edgewise connector i. each ) 46988 CK 1000HL - CK 1000L :’ 46852
moving part rear connections
moving assembly 46824 flat ( each ) 46990
flat disconnecting terminal (per pole) flat + edgewise connector ( each) 46988
CK 400 - CK 800 CK 1200

46896 flat disconnecting terminal (per pole)
CK 1000HL - CK I 000L 46915 CK 400 - CK 800 - CK 1200 46896
secondary disconnects CK 1000HL - CK 1000L 46915
moving block 3 wires 36693 secondary disconnects
6 wires 36696 moving block 3 wires 36693
10 wires consult us 6 wires 36696
fixed block 3 wires 42940 10 wires consult us
6 wires 42941 fixed block 3 wires 42940
10 wires consult us 6 wires 42941
with a max rating plug jf 1000A 10 wires consult us
: with a max rating plug jf 800A optional door cutout
UL listed under tile E116305 access to op. handle only 46977
Verlm Gerin
26
Courtesy of NationalSwitchgear.com
Compact CK switches

m.c.s. when protected by Merlin Gerin CB's


600V CK 800N CK 800H CK1000HL

-
CK 800NA Msss. -
maximum rating
CK 1200N

800A
CK 1200H

800A
CK1000L

800A
nm%m

suitable for use on a circuit at 240 V 65,000 100,000 150,000


(max RMS Sym. Amps) at 480 V 50,000 65,000 150,000
at 600V 35,000 42,000 65,000
CK 1200NA
maximum rating
jjllSRlfj
1200A 1200A
mw&
1200A
suitable for use on a circuit at 240V 65,000 100,000 150 ,000
(max RMS Sym. Amps) at 480V 50,000 65,000 150 ,000
at 600 V 35 ,000 42,000 65,000
-
iA < £ *' U t e
*
accessories £ i <> 3 s ss dimensions - installation -
construction The following accessories of the CK circuit connections
breaker may be used with the CK molded
CK molded case switches are designed Molded case switch dimensions, installation
case switch.
identically to CK molded case circuit and connections are identical to those of the
breakers, except that they are not equipped corresponding circuit breaker. See page 28
with trip unit and sensors. shunt trip 17 to 35.
UL listed under UL file-E e?8£2: <" c ; ‘5 4. undervoltage
*
U i- r t ’ l l L
/v\ v. trip devices
2 auxiliary switches
18
18
Caution : 1 auxiliary + alarm switch 18
molded case switches do not provide 3 aux. switches + 1 alarm switch 18
overcurrent protection. position switches 18
Molded case switches can be protected by a motor operator 19
CK circuit breaker. rotary operating handle 21
padlock adaptor 24
door escutcheon 24
label holder 24

© ratings apply for both standard and 100% rated


breakers
Merlin Gerin
Courtesy of NationalSwitchgear.com 27
CK 400 - CK 800 - CK 1200
Compact CK circuit breakers fixed mouting
dimensions front or rear connection
inch/ mm

with bus bar terminals with pressure terminals 1200 A

_ ^
2.75
70
2.75 _ __1.37
or pressure terminals 800 A
.98 l
J 2.7535 25
2.75
70
1 rh

2.75
70
1
70
^I "
* ' 1
r
* t
1.37
35
i
I
2.16
k '
O ii c oi ! i i
tr"
-w
( 4 ) mounting
holes
— *- H
i -
M
I
- tr.
3.34
85
55
f m ...

® --
9.44 T
ON
i
240
100 5°— 7 15.74
3.77 13.38 f TRIPPED 400

^Pt
96 340 *
p \ 18 ° 2.06
! '

— U ~* 52,5
20°
I >OFF 4.09
7 04
CK 1200- 100% rated only
2.83 with edgewise rear connections
RESET
72 I (as an option on CK 400 and CK 800)

f - 1
2.44
62
I

1 .39 \ M10 .67*


77
t -4
2.95
75
f 1
a
.19 L
5
L 177
45 —
25 * "" 10
7.87
200 8.26
screws
. 19
5
4.33
7 70 4.52

4.80 115
~
210 122
6.77
172
with bus bar terminals Cutting and drilling for attachement to panel
front connection rear connection
6.81
2.75 2.75 2.75 173
~ 70 * 70 * 70 ""
r optional cutout
M10 ! 2.87 for secondary
screws \ 3.34 73 disconnecting
85 i blocks
± I i
\ 10.31 4.11
9.44 7 04.5
J .77^ ~1.77
45 ^
1.77
~ .98 240 262
45

with CK 1200-100% rated edgewise


45
25 I l
rear connections J I L
(as an option ! 2.95
I! i
75 .27 dia
on CK 400 and CK 800)| I
t » 07
( 4 holes)
i n .19 7.87 .19
5 200 5
210
Door cutout
1.06
handle •jB) handle and nameplate
27.37
j 95
,

t t -
i
IT 44 dia
1
i

.37 * 25
.96 J' 7i^,44
.39
70
t -f” 1 fi
I
—1 2.71
69
1
i
i

9.5
/i r
standard rated circuit breakers
CK 1200N HI '1 CK 120GH equipped wilt ISMKJ plug in - 120CA are suitable Icr use in a
'
minimum cubicle space of H51 *JV W21 by Di 3 inches ( 1300 bv 550 by 350 mm)
\
I
r — £ ==*
I
I /
4.09
104
I
i

1
5 +
!*
\
with a mif 'inur ventilation of 60 square inches ; 4 am | both at top and bottom / i i i
100so rated circuit breakers ( type NN or HH )
are suitable for continuous operation a 00 pe cent of rating only if used in a minimum
''
1
t
L_ _ 1 iJ
cubicle space of /
CK 400 CK 800 • 40 by W21 by 09 inches 1030 bv 550 bv 230 mmi

without venli ation
;CK 800 wiring wlh Of C wires based un 75 C rated corouctors!
CK 1200 H51 by W? 1 by D13 inches / 1300 by 550 by 350 mm without ventilation - 2.91,
74
2.48
63

Merlin Genn
28
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers CK 400 - CK 800 - CK 1200
drawout mouting
dimensions ( universal drawout assembly )
inch/ mm

7.94 5.23

;
2.75 2.75 3.03
70 + 7 0 + 7 7

( 4 ) holes
J3- L
-
1.69

._
202 133
. 39
10

r ]
y~ for mounting disconnecting
on a panel position \ 63
16

+
13.39
340
7.17 18.16
182 5

. 32 dia
+ + 23 8 ,2
optional sleeve
for operating
( 4 ) holes thru door n
6.20 / for mounting
/

sp
157 , 5 on a base plate i

Uf
1.53
ingwiBiM:(a
8.49 1.53
I Oo

39 r 216 39
10.22
260 U 2.36
60 * ^
3.69
94
: 2.99 :
.67 9.37
17 238

Cutting and drilling for attachement


on base plate to panel

2.60

2.05 ^
52

13.36 4.33
340 8.74 110
222

3.94
100
i
J L
d T
3.34
85
k 2.60
optional cutout
^ for secondary
disconnecting

1.38
l
l
SW
2.17 2.75 2.75
2.71 3.69 2.99 i
69 94 76 26 dia
06.5
(4holes )
66

8.11
blocks

35 55 70 70 ^ 206

Door cutout with optional


sleeve and door escutcheon - 39 6 x . 20 dia
10 6 . ’5

9.25 4.35
235
ref . 2 | 770.5
1.77

3.56
90.5

100% rated circuit breakers ( CK 400 - CK 800) rl . 96


are suitable tor continuous operation at 100 per .08 •l 24.5 .96
cent of rating only if used in a minimum cubicle 2 24.5
space of H4C by W 21 by D9 inches ( 1030 by 550 breaker ret . 1 — [
by 230 mm) without ventilation. basis .67
-
CK 800NN CK 800HH winng with 90 C wires
based on 75 C rated conductors .
.22 9.84
17
.22
5.5 250 5 ,5

Merlin Genn 29
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers CK 400 - CK 800 - CK 1200
drawout mounting
dimensions ( standard drawout assembly )
inch/ mm

2.75 2.75 3.68


^
70 T 70 93.5

( 4 ) holes
for mounting disconnecting

»
on a panel position

i r 13.39
340

16.34
]
:
9.84 1.38
250 415
35
. 63

3.25
+
-
t
82.5 1.731
44
i
4 13
105
3.68
93.5
»
11.50
292

Cutting and drilling for attachement


to panel
3.65
93.5

1.57
40
?
r [ i 4.33
- fin 10.79
274
110

3.94
100
3.25
62 5
1.38
35
optional cutout
T for secondary
|o o| |o o| 7.32 disconnecting
ri 2.17 186 ^ blocks
2.75 2.75 .26 dia f
£ 6.5 8.11
55 70 70 700
( 4 holes )

Door cutout with optional sleeve


and door escutcheon

.75
19

\
5.78 4.29
\ 5.39
137
147 109

i
7.24
100% rated circuit breakers (CK 400 - CK BOO) 184
are suitable for continuous operation at 100 per
cent of rating only it used in a minimum cubicle .15 dia / 4- I
space of H40 by W? 1 by D9 inches ( 1030 by 550 04
by 230 mm ) without ventilation
CK 800NN - CK 800HH wiring with 90 C wires 120 24
based on 75 C rated conductors
'

30 Merlin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers CK 1000HL - CK 1000L
fixed mounting
dimensions front or rear connection
inch/mm

with bus bar terminals with pressure terminals 1200 A


or pressure terminals 800 A
2.75 2.75 1.37
70 ^ 4.53
j 2.7535
- 2.75
70
T rri
2.75

r —r
70
—i
^ 70
-X—
^

ir
115
11
4
1.37
35
f1
OHhlO t 0 ' HO
' ' $4 - Cc = a ~-A 3.35
*
2.16
55
4
( 4 ) mounting
holes
L r* - 85

f- W '
L
( A) -
ON J
9.44
18! ° °
240 5 ni: 15.74
3.77 13.38 fTRIPPED. . 400
96 i
340

: -ir_2.60 „ 2.64
20 °
'

< OFF

- I
5.90
750
4.09
2.83 nit iiuir gg :TTTin 67 4
.. r 704
V: RESET
72 I with rear connections
f -1-
2.44 rmnr n:::: mu

i
T
2.95
62
t $ _ f J LMJ i
l
<
x* r .
75
» i
.39
- 254
T
1 . 39
70
M10
screws
67
77 7.87
200
J TO

.19
i
177
45
- 7.87
t

. 19
8.07
205 When equipped with rating ptug In = I 00QA use a
5 5 8.34 minimum cubiclespace ot H51 by W 21 by 013 inches
200 6.26
270 10.31212 11300 by 550 by 350 mm ) with a minimum ventilation
262 ol 60 square inches ( 4 dm* ) both al top and bottom
with bus bar terminals
Cutting and drilling for attachement to panel
front connection rear connection
6 81
2.75 2.75 2.75
t ]
70 * 70 * 70
M10
screws optional cutout
!
V 3.34 for secondary
J- 3 i I disconnecting
I X 85 blocks

4.53 J
775 ! \ 10.31 4.11
' 9.44 704.5
I
240 262

45 45
_
J 77 ^1 77 L1 7? ,
45
. - i
i

2.95 l-

with rear connections . 19


\: ~ ~
r
7.87
p .19
n
i
.27 dia
<? 7
2.87
73
i
5 200 5

Door cutout
£) handle B handle and nameplate

r r \
I


i
1—H ? i
!
2.71
J
I
I * + I

f
I
r~
B= t 4.09

T id

T\
'
4
I f I
i
1.1037
28 9.5
I t 1 i
It
I
\ L -1
V
s-t+s- x 5
'
.44 dia
011
2.91 #
74
2.48
63

Merlin Germ 31
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers CK 1000HL - CK1000L
drawout mounting
dimensions ( universel drawout assembly )
inchfmm

11.48 5.23
292 133
1.69 .39
2.75 2.75 3.03 43 10
70 + 70 ^ 77 ^

( 4 ) holes
for mounting
on a panel
disconnecting
position \
© Fi .63
16
_
1
1

I 4'- 13.39

7.17
I voE
/A

1.38
340
18.16
462
182.5
1 35
.63
16
.32 dia .98
- + + 06,2
optional sleeve |
for operating — 25

. :-•
r ( 4) holes thru door l
3i A
v
1.73
6.20 r for mounting • «t
f «*
44
157 5 on a base plate •j

i laBijiliaMMTa
3.35
.37 35
f 95 I
8.49 1.53
10.22
260
216
1
39

.67
2.36
60
! 3.69
94
2.99

12.91
17 328
Cutting and drilling for attachement
on base plate to panel

2.60
66

1 ]
rp
t 2.05
52

13.36 4.33
340 8.74 HO
222
t
f
i 3.34 optional cutout
3.94
WO L
J 1
85
1
for secondary
2.60 disconnecting

1.38
35
i
-
Sir
2.17 _ 2.75
55 ^ 70
2.75
70
2.711 3.69 i 2.99 3.85
69 94 76 98 .26 dia
66

0 6,5 - /
( 4 holes )
7.32
186
8.11
blocks

206

Door cutout with optional


sleeve and door escutcheon .39 6 X.20 dia
10

!
9.25 ref . 2
235 | . 110.5
1.77
t
3.56 4= !
45

-
90.5 x n
1 Hn
.08
T . 96
24,5
A
.96
24.5
When equipped with rating plug In = 1000A use 2
a minimum cubicle space of H51 by W 21 by D13 breaker ref .
mcnes ( 1300 by 550 by 350 mm ) with a minimum basis
venlilation of 60 square inches ( 4 dm" ) both
at top and bottom .

32
.22
5.5
9.84
250
17

-Uff Merlin Gorin


Courtesy of NationalSwitchgear.com
CK 1000HL - CK 1000L
Compact CK circuit breakers drawout mounting
dimensions ( standard drawout assembly )
inch/ mm

Merlin Gerin 33
Courtesy of NationalSwitchgear.com
door escutcheon
Compact CK circuit breakers door interlock
dimensions external neutral sensor
inch/mm

door escutcheon
fixed mounting

drawout mounting
with operating handle with rotary operating drilling of the door
handle 217
55
.39 8 x . 20 dia
10
805
I ref. 2 :
when
mounting
on a panel
9.25 .35 4.35
235
ref. 2
V
|» 9 1W 5

1.77
45
! Da
-Hi*
3.56
90.5 \
coi
- --

‘ 2
breaker
basis
.08

ref 1—
.67
T

]
.96
24 5
i
.96
24.5
ref. 1 »
when mounting
on a base plate

1
.22 9.84 .22
5.5 250 5.5

door interlock external neutral sensor

< .15
4 r 20
-
.79 v
- (
.15
4
.59
15
-
39
10
_ — —
~

T l
1.77
45
i
| 25 ;
"

( 4 ) holes
3.15
59

.44 dia
+ + ii
O 11
»
-r i
.7 3.74 1.77 4.92
95 45 725
19 ^ I
S
i
+

.5 9 ?i
*

.31
^
3.54 1.26
15 ^ 90 ^ 32 8

34 Mertir Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers motor operator
rotary operating handle
dimensions
inch/mm

motor operator with mechanical interlock

.19 1.18 11.26 3.23


5 30 286 82

i
3
i
. y
t

T
I-*- 1 n I
tt == ±J
I r
i
1 i i

6.88 N *' r 8.42


\ 'r
' srr
175 *
\ 214 15.75 si

] m 400
13.78 1
2.08

r -i
53
350

V 7 2
(3 ) mounting
2.44
62
1 12.951L.
NH : 9.25 / L :
8.26
~

~ holes T 235 325 -
2 )0 24.60 NH : 9.72 / L : 13.26
1.45 625 247 337
25.78 NH = 10.39 / 1: 13 93
37 •5
15
? U 655 264 354

rotary operating handle


directly mounted flush / surface / directly mounted
N, H HL, L
© © © surface A mm 10.82 275 14.37 / 365
mounting A max 20.66 525 24.21 / 615
flush B mm 12.40 315 15.94 / 405
mounting B max 22.24 565 25.78 / 655
t flush mounted

rT_
2 surface mounted

E
J i directly mounted
4.84
+ 4 breaker mounting hole
T 123
4.38
111 , 5
\
? 5 drawout assembly mounting hole

Note : shaft can be cut to required length

f-
1.87
47,5
6.83 A (*)
173,5
8.26 .31
B (* )
210 8
door cutout
directly mounted
O add 3.54 / 90 for current lin tmg b ' ock
door mounted
- door mounted door mounted
fixed mounting fixed mounting drawout mounting drawout mounting
on base plate to panel

( 3 ) holes
. 22 dia
06
handle handle
1.37
axis Bxis

I
4 38 38 , 5 3.20
1.37 111 ,5
35 9.50 81.5
T 241 ,5 t
I l 2.70
0 68 - H' T)
t
r <D
.25 dia / 0 6 26 , 73 5 i.es .25 dia / 0 6 .25 dia / 0 6

-
' 6.16
for flush 47 for flush for flush
156,5
mounting mounting mounting
8.60 5.65
only only only ^
218, 5

Courtesy
Merlin Germ
of NationalSwitchgear.com 35
Compact CK circuit breakers UL 489 test procedures
( abstract from UL 489 with revisions
appendix through April 6th. 1987 )

test sequence
standard tests X Y Z
For solid state trip breaker , and 200% calibration at 25 C ( 77 F)
uncompensated thermal breaker rated
40 C , the test sequences are 135% calibration at 25 C ( 77 F)
calibration of adjust instant trip
overload
tungsten lamp load
i calibration at 40 C ( 104 F) Q)
temperature and 100% calibration at 25 C ( 77 F)
endurance
200%. calibration at 25 C ( 77 F) repeated
135% calibration at 25 C ( 77 F) repeated
interrupting ability ( Y sequence )
interrupting ability (Z sequence)
200% trip out at 25°C (77aF)
dielectric voltage withstand
1 Applies only (or D'eakersrated 55 A or less . 125 or 125 / 250V cr less
7 Applies only 1or thermal breakers '•ated 40 C.

standard specifications Temperature Endurance


When connected with specified cables or The breaker must complete an endurance
200% calibration at 25 C bus bars ( see below ) and with its rated test :
The breaker must trip within time limits current , the temperature rises on the breaker operations at 'ated current and rated
which depend on the rating from 3 minutes and at its terminals does not exceed voltage
for a 30 A rated breaker up to 30 minutes specified limits . foiloweo by no load operat on
over 2000 A The power factor shall be 0 75 to 0.80
Examples of specified wires and bus lagging .
135 % calibration at 25 C ‘75 C" copper wire
The breaker must trip within two hours Examples
( for breakers rated more than 50 A ) rating number size
100 A 1 1 AWG ( 60 C ) frame number of cycles of
Calibration of adjustable or 1 3 AWG size operations
instantaneous trip 250 A 1 250 MCM with without total
The breaker must trip within the range of current current
400 A 2 3/0 AWG
80 - 120% of tne maximum marked tripping 100 A 6 000
, 4,000 10 ,000
current and 75- 125% of the minimum 600 A 2 350 MCM
225 A 4.000 4.000 8 , 000
marked tripping current 800 A 3 300 MCM
400 A 1.000 5,000 6 , 000
1000 A 3 400 MCM
Overload 600 A 1 ,000 5.000 6 , 000
1200 A 4 350 MCM
up to 1600 A fifty operations at 600% of 800 A 500 3.000 3, 500
rated current 1200A 500 2.000 2 , 500
cooper bus bar
2000 and 2500 A twenty -five operations
1600A 500 2,000 2 , 500
at 600 % of rated current rating number size
3000 to 6000 A : three operations at 600% 1600 A 2 1 /4 x3 2000A 500 2.000 2 , 500
followed by twenty - five operations at 200 % 2500A 500 2.000 2 , 500
2000 A 2 1 /4 x4
of rated current 3000A 400 1 100 1 , 500
The power faclor snail be from 0.45 to 0 50 2500 A 2 1 /4 x 5
lagging or 4 1 /4 x2
3000 A 4 1 /4 x4
1200 Aoross 1OOC1A in i

36 Merlin Germ
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers UL 489 test procedures
( abstract from UL 489 with revisions
appendix through April 6th , 1987 )

Interrupting ability ( Y sequence) Dielectric


After endurance tests and calibrations After tests , the breaker must withstand
tests on accessories
repeated, the breaker completes an opening for one minute a voltage of 1000 V plus twice Shunt trip and undervoltage trip
followed by a close-open operation the rated voltage between These devices are submitted to temperature
iO-t-CO). with specified current line and load terminals overvoltage, operation , endurance and
terminals of opposite polarity dielectric tests .
Examples for three pole breakers live parts and the overall enclosure overvoltage test
It checks that the device is capable of
frame rating RMS Sym. Amps withstanding 110% of its rated voltage
Optional tests :
(3-pole O- t - CO) contmuously without injury ( this test does not
high available fault current
100A 3.000 apply to a shunt trip with an "a ' contact
Breakers having passed all the standard
225A 3.000 tests may have the UL label applied at
connected * n series).
operation
400 A 5 , 000 higher values than the standard.
The shunt trip must operate at 75% of its
600 A 6 , 000 Test sequence is as follow
rated voltage ( except that shunt trip devices
200 % calibration
800 A 10 ,000 for use with ground fault protection shall
interrupting capacity : an opening
1200 A 14.000 operate at 55%)
operation followed by a close open
The undervoltage trip must trip the
1600 A 20,000 operation ( O- t -CO) on all poles are
breaker when the voltage is between 35
2000 A 25.000 performed on the circuit breaker.
and 70% of its rated voltage and shall seal
The power factor over 20000 A shall be 0.15
3000 A 35.000
to 0.2 lagging
.
(i e. the breaker cannot be turned on ON
I Above 250 V position) when the voltage is at 85% or more
trip out at 250%
of its rated voltage
dielectric at twice the rated test voltage .
Interrupting ability ( Z sequence ) endurance
.
A 3 -pole breaker rated 240 480 or 600V
have to complete ar opening operation and
100% rated
The device must be capable of performing
successfully for 10% of the number of " with
Breakers having passed all the standard current " operations of the breaker
a close - open operation ( O - t - CO) on each tests may have the UL label applied to use
pole , at rated voltage , followed by an tne circuit breaker in an enclosure , when
opening operation ( O ) using all the three Auxiliary and alarm switches
carrying 100% of its maximum rating.
poles for the frame sizes up to 1200 A . an Auxiliary and alarm switches must be
The circuit breaker is submitted to additional
add tional close - open operation on tne three submitted to temperature overload,
temperature tests performed as in Standard
poles is required ). endurance and dielectric tests
tests , except that the breaker is installed in
an enclosure . The dimensions and possible
overload test
Examples for three pole breaker The test consists of fifty operations making
ventilations shall be recorded and shall be and breaking 150% of rated current at rated
frame rating RMS Sym. Amps marked on the breaker
voltage with a 75- 80% power factor in AC
each common and non inuductive load in DC .
pole endurance
O- t- CO o O-t- CO The switch must make and break its rated
current at rated voltage with a 75 -80%
,

100 to 800 A 8.660 10.000 power factor in AC . and non inductive load in
1000 to 1200A 12, 120 14.000 DC for 100% of the number of operations
1600 A 14.000 20 , 000 with current ” for auxiliary switches , and
2000 A 14 , 000 25.000 10% of this number for alarm switches.
3000A 25 , 000 35.000
Motor operator
The motor operator shall perform the
number of " without current " operations
indicated for the breaker endurance tests
The first 25 operations shall be conducted at
85% of the motor operator voltage rating.
The breaker is to be tripped during these
tests.
The next 25 operations shall be conducted
at 110% of the motor operator voltage rating
The balance shall be completed at rated
voltage without tripping the breaker ,

Merlin Germ
Courtesy of NationalSwitchgear.com 37
Compact CK circuit breakers routine and maintenance
guidelines
appendix

Important
recommended inspection insulation resistance tests All tests must be made on circuit
intervals Wnen breakers are subjected to severe breakers which have been de-energized ,
Merlin Germ circuit breakers are designed to operating conditions, insulation resistance and disconnected so as to prevent
test should be performed as indicated in accidental contact with live parts .
be maintenance - free. However , all
NEMA standard publication no AB2 - 1980.
equipment with moving parts requires
periodic inspection to ensure optimum An insulation resistance test is usea to Caution
performance and reliability . We recommend
determine the quality of the insulation Since molded case circuit breakers
between phases and phase to ground The contain factory- sealed and calibrated
that the circuit breakers be routinely
inspected six months after installation ,
resistance test is made with a DC voltage elements, it is essential that the seal be
higher than the rated voltage , to determine not broken and the circuit breaker be not
followed by annual inspection , Intervals can
the actual resistance of the insulation The tampered with.
vary depending on your particular
most common method employs a " megger Molded-case circuit breakers should not
experience
type instrument . A 1000 V instrument will be field adjusted or repaired . In the case
provide a more reliable test because it is of malfunction , the circuit breaker should
inspection of terminals capable ot detecting tracking on insulated be replaced or repaired at the Merlin
connections to circuit breaker terminals surfaces . Resistance values below 1 Gerin factory , or by an authorized
could be inspected II there is discoloration megohm are unsafe and should be investi- representative.
due lo overheating , the joint should be gated An insulation test should be made
disassembled and the surface cleaned between line and load terminals of
before remstallation It is essential that individual poles with the circuit breaker
electrical connections be made carefully in contacts open.
order to prevent overheating. between ad acent poles and from poles to
check for terminal tightness the metallic supporting structure with the
circuit breaker contacts closed The latter
test may be done with the circuit breaker in
cleaning place after the line and load conductors
Remove tne dust and oirt that have have been removed or with the circuit
,

accumulated on the circuit breaker surface breaker bolted to a metallic base which
and terminals. simulates the in- service mounting

mechanical checks electrical tests


Even over long periods circuit breakers are These tests require equipment for conduc -
not often required to operate or overload or ting pole resistance , overcurrent and
short -circuit conditions. Therefore it is instantaneous tripping in accordance with
,

essentia to operate the breaker periodically NEMA standard publication no AB 2 They


To trip the breaker push the push-to- trip are not within the scope of norma * field
button operation

38 Merlin Genr
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
appendix

molded case circuit breaker circuit breakers for


In addition to UL and CSA standards
standard CK breakers comply with I EC 947- 2
compliance with other
standard as per tab ^ e below world standards.
CK type ampere rating ( A ) Where compliance with IEC standards is
interrupting rating
3 -pole required, Merlin Germ offers a versatile
UL 489 - CSA C22- 2 IEC 947- 2
range (not UL listed) of CK circuit breakers
current rating plugs RMS Sym Amps to meet your specific need
sensors 240 V 480 V 600 V 380/415 V 660 V Units include three or four poles voltages up
standard breakers D to 660V , three levels of interrupting
CK 400N 400 200 to 400 65.000 50.000 35.000 50.000 25.000 capabilities up to 660V
CK 800N 800 400 to 800 65.000 An extensive range of accessories
50.000 35.000 50.000 25 ,000
complements the product line
CK 1200N 1200 600 to 1200 65.000 50.000 35.000 50.000 25,000 For further information, please contact your
high interrupting breakers 3> Merlin Gerin representative
CK 400H 400 200 to 400 100, 000 65.000 42.000 i 70.000 40.000
CK 800H 800 400 to 800 100,000 65, 000 42 ,000 70,000 40,000
CK 10Q0HL 1000 500 to 1000 150,000 150.000 65 ,000 150.000 60,000
CK 1200H 1200 600 to 1200 100.000 65,000 42,000 70,000 40,000
current limiting breakers
CK 1000L 1000 500 to 1000 150.000 150.000 150, 000 60,000

shunt trip motor operator


rated voltage ( V ) rated voltage (V )
UL 489 listed IEC 947 - 2 UL 489 listed IEC 947- 2
60Hz 120 50/60HZ 110 - 127 60Hz 120 50/60HZ 110- 127
240 220 - 240 240 220- 240
480 380- 415 DC 24 DC 24
DC 24 DC 24 48 48
48 48 125 125
125 125

auxiliary switches,
undervoltage trip device alarm switch,
rated voltage ( V ) overcurrent trip switch
UL 489 listed IEC 947-2
position switches
DC 24 DC 24
IEC 947- 2 characteristics are the same as
48 48 those indicated in page 18
125 125

ratings apply for both standard and 100% rated breakers

Merlm Gerin
39
Courtesy of NationalSwitchgear.com
As standards specifications and designs develop from time
,

to time always ask for confirmation of ihe formation given


in this publication
^

photos : Merlin Germ, B . Maurice


design by AMEG , Y Marcnand
AC0037/2E IPV 02/92 - pnnted by In