technical manual
molded case
circuit breakers
400 - 1200 A
g MERLIN GERIN
mastering electric ! power
*
CROUPE SCHNEIDER
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
table of contents
page
dimensions 28
appendix
UL 489 test procedures 36
routine maintenance guidelines 38
international standards 39
Courtesy
Merlin Germ
of NationalSwitchgear.com
Compact CK circuit breakers
introduction, advantages
standard compliance
CK breakers are built in accordance with
Underwriters Laboratories standard UL 489
and CSA C22-2 no.5. The circuit breaker
and its accessories, except when noted are CK 400N-CK 400NN 400 200 to 400 65,000 50,000 35,000
listed under UL File CK 800N-CK 800NN 800 400 to 800 65,000 50,000 35,000
-t1636&. - i
*-r frta y y
CK 1200N-CK 1200NN 1200 600 to 1200 65,000 50,000 35,000
mi ifel
additional tests -
CK 400H CK 400HH 400 200 to 400 100,000 65,000 42,000
In addition to standard tests and as indicated CK 800H-CK 800HH 800 400 to 800 100,000 65,000 42,000
in the table, CK breakers meet CK 1000HL 150,000
1000 500 to 1000 150 0Q0 65,000
UL 489 standard optional requirements
t
(high available fault current). CK 1200H-CK 1200HH 1200 600 to 1200 100,000 65,000 42,000
WMsSi
wmm.
* mmim m
compliance with CK 1000L 1000 500 to 1000 150,000 150,000
international standards
In addition to UL489 and CSA C 22- 2 no.5 ratings
the Compact CK has been designed to n three maximum continuous ratings
comply also with the international standard 400, 800 and 1200A rating are available with
IEC 947-2 as well as with the major different basic breakers. In addition, rating CK 400N 400 400
standards : plugs are provided to set the maximum
NEMAAB1, current setting at a value equal or lower than CK 400H 400 400
British BS 4752, the basic breaker selected, CK SOON 800 800
German VDE 660, a 100% rated circuit breakers CK 800H 800 800
a French NF C63-120, can be used for continuous operation at CK 1000HL 1000 800
Australian AS 1930- 100% of their rating as permitted by
CK 1000L 1000 800
Compact circuit breakers have been National Electrical Code, paragraph 210-22
roved for marine application by American
, ( c) exception no. 2 and 220- 10 (b) excep- CK 1200N 1200 1000
„ureau of Shipping, Bureau Veritas, Lloyd's tion, when used in an enclosure described in CK 1200H 1200 1000
Register of Shipping, Registro Italiano msmH
ji
<£ > load monitoring option R
is communication option C
—
I
^ ^
=“3 instant.
override, this trip unit covers distribution, With the STR 55UP trip unit these values
selective, generator and motor protection can be adjusted down to 2 times current
current
applications. sensor.
D for all trip units, the instantaneous override
m STR 25DP for general purpose. is automatically set at different values field interchangeable rating
STR 45SP for selective applications and according to the circuit breaker type and
generator applications. rating.
plug
Hme current characteristic curves include All solid state trip units have a field
djustable time delays for both long time
and short time protections.
iSimBBBg installable rating plug located on the front
face. The interchangeability makes rating
CK 400N/H 15 times current sensor
STR 55UP for any type of application. CK 800N/H 15 times current sensor changes simple. To avoid inadvertent errors,
Thanks to a completely adjustable protection frames and rating plugs are keyed together
curve, including an adjustable instantaneous CK 1200N/H 12 times current sensor and are not interchangeable with CJ and
CK 1000L 8 times current sensor Masterpact rating plugs.
2 Merlin Gerin
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
advantages
isolation function
The operating handle is representative of the
position of the main contacts The OFF
position can be reached only when the main
contacts are fully opened.
The handle will reach the OFF position only
if the pin A can be engaged into the slot B of
the operating mechanism.
In case of unbreakable welding of any mam
contact due to non correct application of the
circuit breaker, the mechanism will bump on
this pm.
Merlin Garin 3
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
description
7 9 10
M
11
15 14 13
interrupting rating
circuit breakers
CK molded case circuit breakers are
designed to connect a load to an electrical
supply and to provide tripping under
overcurrent and ground fault conditions.
They consist of :
1 three-pole high strength glass polyester
casing
2 front accessory cover
-
3 qutck make/quick -break mechanism
4 handle with three positions
-
ON TRIPPED OFF -
5 solid state trip unit containing a current
sensor powered solid state logic unit with
rotary adjustment switches for up to five
functions (see description page 7,8 and 9)
6 test receptacle for use with the test kit
7 line and load terminal covers
-
8 push-to trip button
9 shunt trip or undervoltage trip
10 auxiliary and alarm switches
4 Marlin Garin
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
description
current limiting the current to be interrupted Arc quenching due to the design and
J the basic circuit breaker interrupts
|
materials of the arc chute, a magnetic force
circuit breakers currents of up to 8 x current sensors rating, F draws the arc into the V-shaped plates
In order to compatibilize simplicity of design over this value both devices operate .
It is then split and cooled until extinction
and efficient methods, some of the principles simultaneously . This mutual assistance
used to provide a fast contact opening are noticeably reduces contact wear
described as follows :
In senes association of the basic circuit These performances are obtained by
breaker and of a limiting compartment combination of the following techniques in
equipped with an original system enables the current limiting block
outstanding performances to be obtained contact repulsion
very high interrupting capability, enhancement of induced magnetic field.
specialization of the devices according to arc quenching .
Contact repulsion
Electrodynamic forces are generated by the
current flowing in parallel conductors
The moving contact is blown-off by the
repulsive forces, which appear on a short
circuit current
Merlin Germ
5
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
description
max prospective -
00 00
conditions .
This is illustrated by limitation curves which
BC
70 peak current : Z: +
i tl 00
70
give 60 /& 60
the limited peak let- through current in 50 50
relation to the RMS sym value of the
prospective short -circuit current ( the ia 40 40
equipment ) ;
the limited let- through energy ( thermal • - . •
»
Ics peak B / a
444
/
/ ' \
\
B
/
/
444
- 6
^
5 5
/ prospective Ics / * .
/ \
/ \ 3
/
limited Isc peak V
v limited Isc \
\ 2
2 5 I 7 5 I 10 20 30 40 50 60 70 00 » 100 200
2
I
4 5 ti 7 fl 9 10 20 30 4C 50 60 7U 80 90 100 200 4
2 2
I 10«
i
E
5 5
3 3
2 2
10» 10"
3 3
1
2 « 5 6 7 8 0 10 20 30 40 50 60 70 80 00 100 200
« prospective short circuit current INA RMS sym!
*
6 Merlin Gerin
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers STR 25 DP for general
application
trip units
1 rating plug
2 long time current setting
3 alarm indicator indicates 90 % load with
a fixed light and over 105 % ( the lower limit
of tnpping) with a flashing light
4 instantaneous pickup STR 25DP
u 90
5 test receptacle I
long time
time lo = 1200 A i
long time lost lur set = lr
•nnimetarCK ' XO
long time 1 2
CJl .
IV 38336
.
1IW IJIOO
A 'C a
- t?
nstantaneous
O t
\ instantaneous
5
: T:
instantaneous -
CK 400 - CK 800 CK 1200 : 1.5 to 10 times current setting
CK 1000 1.5 to 10 times current setting with a max of 8 times
test receptacle for overcurrent testing
fault indicators
local by trip indication of the operating handle
remote by alarm and overcurrent trip switch, see page18
Merlin Genn 7
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers STR 45 SP for selective and
generator applications
trip units
1 rating plug
2 long time current setting
3 alarm indicator indicates 90 % load with
a fixed light and over 105 % ( the lower limit 2 13 4
of tripping) with a flashing light
4 short time pickup STR 45 SP
5 short time delay
6 long time delay
7 test receptabie lo = 1200A I
tong tune
II
lest ""•T-* " ""'
Oil -MU It
e
p*Oup
*
1
time
A I l ng time
° •
1 Wirt
'?fs MC
L- instant I I
t5
Sir .»
delay delay
short time 7 6 5
L. mstantaneous
8 Merlin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers STR 55 UP for all types of
applications
trip units
1 rating plug
2 long time pickup
3 alarm indicator indicates 90 % load with
a fixed light and over 105 % ( the lower limit 2 8 13 14 15
of tripping) with a flashing light
4 short time pickup
STR 55UP 6
5 instantaneous pickup
6 local fault and load indicators: .. tong tme •tlm
non grm«J
l i lll
*
they consist in built -in light emitting diodes
fault indicators that discriminate the 3
lo = 1200 A
WP
*« iuo tm Crn »
bod
1 i ifTHU'
tong tuTui
w
tesi . cur ref =ir
9 « nl
aiqtuir pICKup
5 ft I . 7
1 /
causes of topping overload short circuit
and ground faulf if any
,
MeMin Gent -
Courtesy of NationalSwitchgear.com
9
neutral sensor
Compact CK circuit breakers zone selective interlocking
trip units
Fault 1
Circuit breaker A will clear the fault within
the minimum time delay regardless of its
time delay setting.
Fault 2
Circuit breaker B will inform the upstream
circuit breaker A that it is clearing the fault
and will prevent it from tripping instanta-
neously
As a safety feature , the breaker A will trip at
the end of its time delay setting If the fault is
not cleared during this time.
Note :
circuit breaker terminals are delivered with
"in" terminals jumpered Remove the jumber
when interlocking with a downstream
breaker .
Compact CK type molded case circuit
breakers may be also interlocked with
Masterpact circuit breaker with ZSI option
do not ground.
.
Merlin Germ
10 Courtesy of NationalSwitchgear.com
Compact CK circuit breakers load monitoring,
fault and load indicators
trip units
communication
( option C)
. .
Transmitting data concerning 11, 12 13 Imax,
all settings of the trip unit, identification of
plug, load monitoring operations, fault
indications level of thermal memory, internal
temperature warning ,
Courtesy
Merlin Germ
of NationalSwitchgear.com 11
mini test kit
Compact CK circuit breakers portable test kit
trip units
Merlin Gerin
12
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
time current curves
100 10Q
90 90
80
70 70
60 60
SO SO
43 40
- . 30
20 20
/:
o
c
is 10
6
K>\ - -4 -
-
to
9
6
o
E
— 6 - 6
- . \ ' *
—H- f
— 10\
*
2
T 1 instantaneous
It = ’ 5 . 10 « current setting ( lr )
.
I
- 1
9
- *
- 8
7
e 6
,
4 4
——
i 1-4-
•
i
— f 3
H-4
i
09 09
08 oe
07 V 07
06 »36
05 ~ 05
(V
* .. - -
04
.
03 03
. i
02 02
\
*
>
ot 01
5 6 7 8 9 t I2 15 2 3 4 5 6 7 8 910 20 30 40 SO 60 6 £ £8
multiple of current setting ( lr >
l S i § § £!§! i I |
Courtesy
Morim Genn
of NationalSwitchgear.com 13
Compact CK circuit breakers
time current curves
14 Martin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
time current curves
200
i -
- 200
too
9D
80
— ..
*
-
100
90
BO
70
8C 70
60
5L
40
* *
- W
- 40
30
30
.
20
20
4)
tJ
C
o
S 10
9 - to
£ 9
E
a
- 8
6
e
-
*
— . t 5
- 4
3
:
2 f
Rt ON
t 4 .
. -
t
v
5
kl - -- • •
*
8
6
4 4 4 4
-
- 7
5 U k \V • • 6
4
. i \ . 0.4 *
-
t -4— .
4
.3
44-4-4- .. 3
0.3
2
- 2
*
V 0.2
| :
i
08 1 1 OFF *
* : 0.1 —
1 ^ 09
06
07
H
*
07
06
06
OS
08
J4
*
03
tr 04
02
.
-
—4 -
*
03
02
. .
..
'
T 01
01
SS £ 8$ i 4 5 5 7 8 9 1 1 2 *
5 2 3 4 5 C 7 89 0
' 20 30 40 50 60 S 8 3
^ § 8 i s seas
multiple of current setting lr ) <
Merlin Genri
15
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
time current curves
16 Merlin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers terminals
shunt trip
terminals
Accessory terminals are standard and
located within the breaker behind the front
,
cover
Two types are provided
field installable accessories
terminals are directly mounted on the
accessory Each terminal may be connected
by one or two stranded copper wires 18 to
14 AWG
Tightening torque 12. lb in
Cable strip length 3 8 ' approximate
'
factory mounted accessories
pressure type terminals secured by a screw
on the breaker Each terminal may be
connected by one stranded copper wire 18
to 14 AWG
Cable strip length 3/8 " approximate
In the factory these terminals are facing
towards the top of circuit breaker ( see
gutters on wiring diagram page 24 ) For his
convenience the end user may direct them
to the side of the breaker This can be done
easily on sue
1 remove terminal using a scewdnver
2 break the knock -out for the wire exit
3 replace terminal
Caution :
open circuit breaker and disconnect
control power before removing this front
cover .
i
I
vf .
coil Clearing sw icn
Merlin Genr 17
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers undervoltage trip device
auxiliary and alarm switches
overcurrent trip switch
position switches
-OJ.
information , When the breaker is reset , the h2 14 22 „24 32 „34 J 9? .
.94 J
O O O O—t
' a ' contact ( a <
arm ) is open , and the " b '
contact ( lockout ) is closed
This SPDT sw tch is operated when the b a b a b c; b a
breaker is tripped by the trip unit, shunt trip
or undervoltage trip device or "push- to - trip '
button.
2 auxiliary switches
cal. no.
36404
•-
21
. 31
i
91
1 aux . f 1 alarm switch 36405 voltage (V ) 2 auxiliary 1 auxiliary + 1 alarm 3 auxiliary + 1 alarm
3 aux . + 1 alarm switch 36402 auxiliary alarm auxiliary alarm
50/60 Hz 240 6A 6A 5A 6A 5A
480 6A 6A 5A
600 3A 3A 3A
DC 125 10.5A 0.5A 0.5 A 0.5 A 0.5 A
250 0.25A 0.25 A 0.25 A 0.25A 0.25 A
overcurrent trip switch control voltage
voltage (V) current (A)
50 /60 Hz 240
The auxi lary switch consists of a SPDT
The "a" contact closes when the breaker
t DC 125
2
0.1
operates through the trip unit ( overcurrent or
ground fault ). It does not operate if tr pping
(82)
9184 fault Note : type a switch is delivered as standard Or
’equest type b Is available
is by shunt trip undervo tage trip device or
,
--
i
operated c ose to the connected or j connectedj 600 3
disconnected position .
connected position 46963
91314 a 312 1 324 322 352
¥354~
1
~
¥
362 1364
DC 125
250
0.5
0.25
disconnected position 46964
*
18 Merm Garir
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers motor operator
•i-
reset
% 15 t 152
motor overcurrent
operator trip switch -
i
6vy :c> s o <5 Q 6-
i caution control diagram shall be designed to
a 11 “CD ^ b "Ta "
interlock remote on and off O'ders
? overcurrent trip switch is recommended tc lock
'
- iPlET II
remote resetting after an electrical fault CS . cs L
C1 limit switch
CV locking switch opens when CV
L
n"
b ll CV
1"
b
the breaker is manually operated
• the breaker is padlocked
Mprlm Geon 19
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers motor operator
mechanical interlock
Mounted on the two operators, the interlock
prevents the two breakers from being
simultaneously closed Breakers can be both
or individually opened
In addition to the mechanical interlock , an
electrical interlock is mandatory between the
two operators
Factory mounted
switching time : 0.9 sec
number of switching operations : 10.000.
Not UL listed.
catalog number 35680
electrical interlock
*i -- r-
•
i. oft i_Lon
normal
f 1 normal ' r •' normal
standby L Af +onstandby i. ofl
' | standby
•with a minimum
time celay of 1 sec
between off and on
.
| with a minimum
time aeiay of I sec
between off and on
orders orders
.
I
A i AAAA
rt
I A A
A?
A
A? B4 B4
I 12 14 12 14
9 9 II 9 ? II
_
—
44
TA
111 =U"
CA' CAT »
> " "b
II• - Pic
1 “ CD
* b a
l I «
"
’ ey cs It
"
’ cv cs II
II’ II
, ,
A l N 152 \ 151
O
11 A 1 \ / ' 5? v / 151
Y Y Y. i ’ ? Y Y.
i
i i
i
L .
i J
I
1
motor auxiliary motor auxiliary
operator switch operator switch
20 Merlin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers rotary operating handle
Directly mounted
This handle is directly mounted on the circuit
breaker It accomodates as standard up to
three padlocks to ock the handle in the OFF
position However , a knockout tab can be
removed to allow the locking of the handle in
the ON position. Due to the trip free
mechanism, padlocking in such a position
will not prevent the circuit breake' from
tripping under overcurrent conditions.
The padlocked handle will continue to
indicate ON.
Padlock shackle diameter 1 /4 to 5/ 16
Note :
A mechanical interlock (cat no 44946) links
two rotary handles and constitues a manual
source changeover This device is only
available for direct rotary handies.
Simultaneous closing of the two breakers is
prevented but simultaeous opening is
possible. The breakers are norma ly f xed on
a panel or on rails.
catalog number 46933
Note :
Door interlock can be disabled or defeated
by turning the defeating screw located on
the front face
It accomodates as standard up to three
padlocks to lock the handle < n th OFF or ON
i by removing a knockout ) position
Padlocking is possible only if the coupling of
the extension shaft and the door mounted
mechanism is correct.
catalog number 46933 42897
UL listed under UL file E 107821.
Courtesy
Wortin Genr of NationalSwitchgear.com 21
Compact CK circuit breakers
wiring diagrams
I I
CK open
I I I I
I
I I
,I 314312 4 3
I
^^^^^ . I I
0% » A?2 l# x
[ 311 M32?
’”
)
r6 in — v ——— —— 0~i .82
[uv or ST ©
I4$ o—O —-O1
151 152
”
V \
V' '' '
-O-21 O — O' -
’Vi
"
jAl 11 [ 31 41 C1
+ 9 9 9 9
22 Merlin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
wiring diagrams
3 auxiliary
1 alarm switch
cat no - 36402
ground load local fault commumca - 3 auxiliary switches
fault ZSI monitoring indications tions 11 12- 14 ?i 22 24 .
r i r i r 31 32 3*1
T t alarm switch
9 - 92- 94
'
2 auxiliary switches
external -
cat no 36404
CT
Ic
external neutral -
11- 12- 14 31 32 34
* sensor 1 auxiliary
n Ic2
tem'inalTt T 2
zone selective
interloktng
1 alarm switch
auxiliary
-
cat no 36405
31 32 - 34
switch
input terminal .
alarm 5* v tch
91 92 94
upstream Z21- Z22
I
brea er
* | .
outpi t lerrmna overcurrent
*I 211 212
or
trip switch
•ermma 81 84
'
_
4
.RUH oe-V£ load monitoring — fault
^ ^ 11.211 2 3 ' indicators
“
terminal H3- R 4 control power
terminal Fn 1? -
load monitoring
A—A ~A 7\~
shunt trip
A A Irrmina R 1 -H2
A A A A A A terminal C 1 C:’
or
undervoltage trip
communication
-
terminal D1 D2
iemimai r
- c -
rV —Cn r C - —Cm
option T option Z -IR -L option F option C possible wire exits
- —Q-
O 1 possible International gutters
VL V^ - y y y y
drawout mounting
Pz22 >R2 ?R 4 9 9,
Z2
1
^
!—
§ 1
downstream
« I
^ ^
24 to 250V
breaker AC or DC secondary
disconnecting
blocks
o o
und » -
MHtk motoi if
'* | *I-II*n»
I
•' MI
" *Jj
M
Or
lii >
II 11 u a .
• marr Mu> I - - «.
Wow 11
4
P
^ i
or
*
trip unit options
T1
or
R 1 IZ 111 Z2 IFt 11 R 3
i
e- T2
or or
R 2 IZt 2lZl 2 lZ22l R -
V rlir Genti
^ PR
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers padlock adaptator
door escutcheon
label holder
kirk key lock
boot
24 Memn Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
main connections
CK circuit breakers may be connected with Complete instructions are given with tne set
bus bars or cables on both line and load of pressure type terminals and in the
sides. installation instructions proviaed with the
The type of connections should be specified breaker.
when ordenng Caution : modification of terminals requires
A field modification is possible to e ther removing of a front and back
mount or remove the pressure type terminal cover . When the modification is
terminals. completed , this cover must be replaced.
Tightening
The bus bars shall be secured by two bolts. 7 16" dia
011
; 2 ) holes
IV "
<50
with cables
Copper or aluminium cables may be
connected by pressure type connectors w th
a capacity of :
rating 800 Amp.
cat . no 46961
1 to 2 cables 2'0 to 400 MCM Cu
or 1 to 3 cables 2 0 to 300 MCM Cu
or 1 to 3 cables 4 0 to 400 MCM Al
cable strip length : 1 1/ 4 .
rating 1200 Amp.
cat no 46960
1 to 4 cables 3/0 to 500 MCM Cu
1 to 4 cables 4/0 to 500 MCM Al
cat . no 46966
t to 3 cables 250 to 600 MCM Cu or Al
rear connection
Rear bus bar connections are used for
switchboard mounting According to the way
of mounting the rear connections, they
provide on N and H type breakers vertical or
edgewise connection possibilities
Merlin Genu 25
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
main connections
disconnected position
locking
The breaker can be locked in the
" disconnected" position by the means of 1 to
3 padlocks (padlocks not provided) or 1 Kirk
When the breaker is in the connected
key lock Factory mounted
position , Ihe primary voltage is fed through
Mounted on the stationary assembly and
the breaker by means of multiple finger
accessible with the cubicle door locked
disconnects A racking handle permanently
located on the stationary assembly is used Note :
to connect and disconnect ' he breaker thru keylock is of the captive key type tree
the door As a safety feature in the event of when locked .
disconnecting a closed breaker a on special order , locking may be possible
mechanical interlock will tnp the breaker on disconnected an connected positions
before the separation of the mam padlocking device standard
disconnects
Control voltage is provided through provisior for Kirk key lock 46836
secondary disconnects in the connected Kirk key lock 35635
position only See page 22 for the number of
secondary disconnects required
UL listed under file E 116305
cat. no. standard drawout assembly This version provides in a smaller volume
the same disconnecting / connecting and
fixed part
safety features
CK 400 - CK 800 - CK 1200 46820
CK 1000HL - CK 1000L i
' 46822 cat. no .
rear connections complete assembly
flat leach ) 46990 -
CK 400 CK 800 CK 1200
' 46851
Hal « edgewise connector i. each ) 46988 CK 1000HL - CK 1000L :’ 46852
moving part rear connections
moving assembly 46824 flat ( each ) 46990
flat disconnecting terminal (per pole) flat + edgewise connector ( each) 46988
CK 400 - CK 800 CK 1200
•
46896 flat disconnecting terminal (per pole)
CK 1000HL - CK I 000L 46915 CK 400 - CK 800 - CK 1200 46896
secondary disconnects CK 1000HL - CK 1000L 46915
moving block 3 wires 36693 secondary disconnects
6 wires 36696 moving block 3 wires 36693
10 wires consult us 6 wires 36696
fixed block 3 wires 42940 10 wires consult us
6 wires 42941 fixed block 3 wires 42940
10 wires consult us 6 wires 42941
with a max rating plug jf 1000A 10 wires consult us
: with a max rating plug jf 800A optional door cutout
UL listed under tile E116305 access to op. handle only 46977
Verlm Gerin
26
Courtesy of NationalSwitchgear.com
Compact CK switches
-
CK 800NA Msss. -
maximum rating
CK 1200N
800A
CK 1200H
800A
CK1000L
800A
nm%m
_ ^
2.75
70
2.75 _ __1.37
or pressure terminals 800 A
.98 l
J 2.7535 25
2.75
70
1 rh
•
2.75
70
1
70
^I "
* ' 1
r
* t
1.37
35
i
I
2.16
k '
O ii c oi ! i i
tr"
-w
( 4 ) mounting
holes
— *- H
i -
M
I
- tr.
3.34
85
55
f m ...
® --
9.44 T
ON
i
240
100 5°— 7 15.74
3.77 13.38 f TRIPPED 400
^Pt
96 340 *
p \ 18 ° 2.06
! '
— U ~* 52,5
20°
I >OFF 4.09
7 04
CK 1200- 100% rated only
2.83 with edgewise rear connections
RESET
72 I (as an option on CK 400 and CK 800)
f - 1
2.44
62
I
4.80 115
~
210 122
6.77
172
with bus bar terminals Cutting and drilling for attachement to panel
front connection rear connection
6.81
2.75 2.75 2.75 173
~ 70 * 70 * 70 ""
r optional cutout
M10 ! 2.87 for secondary
screws \ 3.34 73 disconnecting
85 i blocks
± I i
\ 10.31 4.11
9.44 7 04.5
J .77^ ~1.77
45 ^
1.77
~ .98 240 262
45
t t -
i
IT 44 dia
1
i
.37 * 25
.96 J' 7i^,44
.39
70
t -f” 1 fi
I
—1 2.71
69
1
i
i
9.5
/i r
standard rated circuit breakers
CK 1200N HI '1 CK 120GH equipped wilt ISMKJ plug in - 120CA are suitable Icr use in a
'
minimum cubicle space of H51 *JV W21 by Di 3 inches ( 1300 bv 550 by 350 mm)
\
I
r — £ ==*
I
I /
4.09
104
I
i
1
5 +
!*
\
with a mif 'inur ventilation of 60 square inches ; 4 am | both at top and bottom / i i i
100so rated circuit breakers ( type NN or HH )
are suitable for continuous operation a 00 pe cent of rating only if used in a minimum
''
1
t
L_ _ 1 iJ
cubicle space of /
CK 400 CK 800 • 40 by W21 by 09 inches 1030 bv 550 bv 230 mmi
’
without venli ation
;CK 800 wiring wlh Of C wires based un 75 C rated corouctors!
CK 1200 H51 by W? 1 by D13 inches / 1300 by 550 by 350 mm without ventilation - 2.91,
74
2.48
63
Merlin Genn
28
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers CK 400 - CK 800 - CK 1200
drawout mouting
dimensions ( universal drawout assembly )
inch/ mm
7.94 5.23
;
2.75 2.75 3.03
70 + 7 0 + 7 7
( 4 ) holes
J3- L
-
1.69
._
202 133
. 39
10
r ]
y~ for mounting disconnecting
on a panel position \ 63
16
+
13.39
340
7.17 18.16
182 5
. 32 dia
+ + 23 8 ,2
optional sleeve
for operating
( 4 ) holes thru door n
6.20 / for mounting
/
sp
157 , 5 on a base plate i
Uf
1.53
ingwiBiM:(a
8.49 1.53
I Oo
39 r 216 39
10.22
260 U 2.36
60 * ^
3.69
94
: 2.99 :
.67 9.37
17 238
2.60
2.05 ^
52
13.36 4.33
340 8.74 110
222
3.94
100
i
J L
d T
3.34
85
k 2.60
optional cutout
^ for secondary
disconnecting
1.38
l
l
SW
2.17 2.75 2.75
2.71 3.69 2.99 i
69 94 76 26 dia
06.5
(4holes )
66
8.11
blocks
35 55 70 70 ^ 206
9.25 4.35
235
ref . 2 | 770.5
1.77
3.56
90.5
Merlin Genn 29
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers CK 400 - CK 800 - CK 1200
drawout mounting
dimensions ( standard drawout assembly )
inch/ mm
( 4 ) holes
for mounting disconnecting
»
on a panel position
i r 13.39
340
16.34
]
:
9.84 1.38
250 415
35
. 63
3.25
+
-
t
82.5 1.731
44
i
4 13
105
3.68
93.5
»
11.50
292
1.57
40
?
r [ i 4.33
- fin 10.79
274
110
3.94
100
3.25
62 5
1.38
35
optional cutout
T for secondary
|o o| |o o| 7.32 disconnecting
ri 2.17 186 ^ blocks
2.75 2.75 .26 dia f
£ 6.5 8.11
55 70 70 700
( 4 holes )
.75
19
\
5.78 4.29
\ 5.39
137
147 109
i
7.24
100% rated circuit breakers (CK 400 - CK BOO) 184
are suitable for continuous operation at 100 per
cent of rating only it used in a minimum cubicle .15 dia / 4- I
space of H40 by W? 1 by D9 inches ( 1030 by 550 04
by 230 mm ) without ventilation
CK 800NN - CK 800HH wiring with 90 C wires 120 24
based on 75 C rated conductors
'
30 Merlin Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers CK 1000HL - CK 1000L
fixed mounting
dimensions front or rear connection
inch/mm
r —r
70
—i
^ 70
-X—
^
ir
115
11
4
1.37
35
f1
OHhlO t 0 ' HO
' ' $4 - Cc = a ~-A 3.35
*
2.16
55
4
( 4 ) mounting
holes
L r* - 85
f- W '
L
( A) -
ON J
9.44
18! ° °
240 5 ni: 15.74
3.77 13.38 fTRIPPED. . 400
96 i
340
: -ir_2.60 „ 2.64
20 °
'
< OFF
8°
- I
5.90
750
4.09
2.83 nit iiuir gg :TTTin 67 4
.. r 704
V: RESET
72 I with rear connections
f -1-
2.44 rmnr n:::: mu
“
i
T
2.95
62
t $ _ f J LMJ i
l
<
x* r .
75
» i
.39
- 254
T
1 . 39
70
M10
screws
67
77 7.87
200
J TO
.19
i
177
45
- 7.87
t
. 19
8.07
205 When equipped with rating ptug In = I 00QA use a
5 5 8.34 minimum cubiclespace ot H51 by W 21 by 013 inches
200 6.26
270 10.31212 11300 by 550 by 350 mm ) with a minimum ventilation
262 ol 60 square inches ( 4 dm* ) both al top and bottom
with bus bar terminals
Cutting and drilling for attachement to panel
front connection rear connection
6 81
2.75 2.75 2.75
t ]
70 * 70 * 70
M10
screws optional cutout
!
V 3.34 for secondary
J- 3 i I disconnecting
I X 85 blocks
4.53 J
775 ! \ 10.31 4.11
' 9.44 704.5
I
240 262
45 45
_
J 77 ^1 77 L1 7? ,
45
. - i
i
2.95 l-
Door cutout
£) handle B handle and nameplate
r r \
I
—
i
1—H ? i
!
2.71
J
I
I * + I
f
I
r~
B= t 4.09
T id
T\
'
4
I f I
i
1.1037
28 9.5
I t 1 i
It
I
\ L -1
V
s-t+s- x 5
'
.44 dia
011
2.91 #
74
2.48
63
Merlin Germ 31
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers CK 1000HL - CK1000L
drawout mounting
dimensions ( universel drawout assembly )
inchfmm
11.48 5.23
292 133
1.69 .39
2.75 2.75 3.03 43 10
70 + 70 ^ 77 ^
( 4 ) holes
for mounting
on a panel
disconnecting
position \
© Fi .63
16
_
1
1
I 4'- 13.39
7.17
I voE
/A
1.38
340
18.16
462
182.5
1 35
.63
16
.32 dia .98
- + + 06,2
optional sleeve |
for operating — 25
. :-•
r ( 4) holes thru door l
3i A
v
1.73
6.20 r for mounting • «t
f «*
44
157 5 on a base plate •j
i laBijiliaMMTa
3.35
.37 35
f 95 I
8.49 1.53
10.22
260
216
1
39
.67
2.36
60
! 3.69
94
2.99
12.91
17 328
Cutting and drilling for attachement
on base plate to panel
2.60
66
1 ]
rp
t 2.05
52
13.36 4.33
340 8.74 HO
222
t
f
i 3.34 optional cutout
3.94
WO L
J 1
85
1
for secondary
2.60 disconnecting
1.38
35
i
-
Sir
2.17 _ 2.75
55 ^ 70
2.75
70
2.711 3.69 i 2.99 3.85
69 94 76 98 .26 dia
66
0 6,5 - /
( 4 holes )
7.32
186
8.11
blocks
206
!
9.25 ref . 2
235 | . 110.5
1.77
t
3.56 4= !
45
-
90.5 x n
1 Hn
.08
T . 96
24,5
A
.96
24.5
When equipped with rating plug In = 1000A use 2
a minimum cubicle space of H51 by W 21 by D13 breaker ref .
mcnes ( 1300 by 550 by 350 mm ) with a minimum basis
venlilation of 60 square inches ( 4 dm" ) both
at top and bottom .
32
.22
5.5
9.84
250
17
Merlin Gerin 33
Courtesy of NationalSwitchgear.com
door escutcheon
Compact CK circuit breakers door interlock
dimensions external neutral sensor
inch/mm
door escutcheon
fixed mounting
drawout mounting
with operating handle with rotary operating drilling of the door
handle 217
55
.39 8 x . 20 dia
10
805
I ref. 2 :
when
mounting
on a panel
9.25 .35 4.35
235
ref. 2
V
|» 9 1W 5
1.77
45
! Da
-Hi*
3.56
90.5 \
coi
- --
‘ 2
breaker
basis
.08
ref 1—
.67
T
]
.96
24 5
i
.96
24.5
ref. 1 »
when mounting
on a base plate
1
.22 9.84 .22
5.5 250 5.5
< .15
4 r 20
-
.79 v
- (
.15
4
.59
15
-
39
10
_ — —
~
T l
1.77
45
i
| 25 ;
"
( 4 ) holes
3.15
59
.44 dia
+ + ii
O 11
»
-r i
.7 3.74 1.77 4.92
95 45 725
19 ^ I
S
i
+
.5 9 ?i
*
.31
^
3.54 1.26
15 ^ 90 ^ 32 8
34 Mertir Genn
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers motor operator
rotary operating handle
dimensions
inch/mm
i
3
i
. y
t
T
I-*- 1 n I
tt == ±J
I r
i
1 i i
] m 400
13.78 1
2.08
r -i
53
350
V 7 2
(3 ) mounting
2.44
62
1 12.951L.
NH : 9.25 / L :
8.26
~
—
~ holes T 235 325 -
2 )0 24.60 NH : 9.72 / L : 13.26
1.45 625 247 337
25.78 NH = 10.39 / 1: 13 93
37 •5
15
? U 655 264 354
rT_
2 surface mounted
E
J i directly mounted
4.84
+ 4 breaker mounting hole
T 123
4.38
111 , 5
\
? 5 drawout assembly mounting hole
f-
1.87
47,5
6.83 A (*)
173,5
8.26 .31
B (* )
210 8
door cutout
directly mounted
O add 3.54 / 90 for current lin tmg b ' ock
door mounted
- door mounted door mounted
fixed mounting fixed mounting drawout mounting drawout mounting
on base plate to panel
( 3 ) holes
. 22 dia
06
handle handle
1.37
axis Bxis
I
4 38 38 , 5 3.20
1.37 111 ,5
35 9.50 81.5
T 241 ,5 t
I l 2.70
0 68 - H' T)
t
r <D
.25 dia / 0 6 26 , 73 5 i.es .25 dia / 0 6 .25 dia / 0 6
-
' 6.16
for flush 47 for flush for flush
156,5
mounting mounting mounting
8.60 5.65
only only only ^
218, 5
Courtesy
Merlin Germ
of NationalSwitchgear.com 35
Compact CK circuit breakers UL 489 test procedures
( abstract from UL 489 with revisions
appendix through April 6th. 1987 )
test sequence
standard tests X Y Z
For solid state trip breaker , and 200% calibration at 25 C ( 77 F)
uncompensated thermal breaker rated
40 C , the test sequences are 135% calibration at 25 C ( 77 F)
calibration of adjust instant trip
overload
tungsten lamp load
i calibration at 40 C ( 104 F) Q)
temperature and 100% calibration at 25 C ( 77 F)
endurance
200%. calibration at 25 C ( 77 F) repeated
135% calibration at 25 C ( 77 F) repeated
interrupting ability ( Y sequence )
interrupting ability (Z sequence)
200% trip out at 25°C (77aF)
dielectric voltage withstand
1 Applies only (or D'eakersrated 55 A or less . 125 or 125 / 250V cr less
7 Applies only 1or thermal breakers '•ated 40 C.
36 Merlin Germ
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers UL 489 test procedures
( abstract from UL 489 with revisions
appendix through April 6th , 1987 )
100 to 800 A 8.660 10.000 power factor in AC . and non inductive load in
1000 to 1200A 12, 120 14.000 DC for 100% of the number of operations
1600 A 14.000 20 , 000 with current ” for auxiliary switches , and
2000 A 14 , 000 25.000 10% of this number for alarm switches.
3000A 25 , 000 35.000
Motor operator
The motor operator shall perform the
number of " without current " operations
indicated for the breaker endurance tests
The first 25 operations shall be conducted at
85% of the motor operator voltage rating.
The breaker is to be tripped during these
tests.
The next 25 operations shall be conducted
at 110% of the motor operator voltage rating
The balance shall be completed at rated
voltage without tripping the breaker ,
Merlin Germ
Courtesy of NationalSwitchgear.com 37
Compact CK circuit breakers routine and maintenance
guidelines
appendix
Important
recommended inspection insulation resistance tests All tests must be made on circuit
intervals Wnen breakers are subjected to severe breakers which have been de-energized ,
Merlin Germ circuit breakers are designed to operating conditions, insulation resistance and disconnected so as to prevent
test should be performed as indicated in accidental contact with live parts .
be maintenance - free. However , all
NEMA standard publication no AB2 - 1980.
equipment with moving parts requires
periodic inspection to ensure optimum An insulation resistance test is usea to Caution
performance and reliability . We recommend
determine the quality of the insulation Since molded case circuit breakers
between phases and phase to ground The contain factory- sealed and calibrated
that the circuit breakers be routinely
inspected six months after installation ,
resistance test is made with a DC voltage elements, it is essential that the seal be
higher than the rated voltage , to determine not broken and the circuit breaker be not
followed by annual inspection , Intervals can
the actual resistance of the insulation The tampered with.
vary depending on your particular
most common method employs a " megger Molded-case circuit breakers should not
experience
type instrument . A 1000 V instrument will be field adjusted or repaired . In the case
provide a more reliable test because it is of malfunction , the circuit breaker should
inspection of terminals capable ot detecting tracking on insulated be replaced or repaired at the Merlin
connections to circuit breaker terminals surfaces . Resistance values below 1 Gerin factory , or by an authorized
could be inspected II there is discoloration megohm are unsafe and should be investi- representative.
due lo overheating , the joint should be gated An insulation test should be made
disassembled and the surface cleaned between line and load terminals of
before remstallation It is essential that individual poles with the circuit breaker
electrical connections be made carefully in contacts open.
order to prevent overheating. between ad acent poles and from poles to
check for terminal tightness the metallic supporting structure with the
circuit breaker contacts closed The latter
test may be done with the circuit breaker in
cleaning place after the line and load conductors
Remove tne dust and oirt that have have been removed or with the circuit
,
accumulated on the circuit breaker surface breaker bolted to a metallic base which
and terminals. simulates the in- service mounting
38 Merlin Genr
Courtesy of NationalSwitchgear.com
Compact CK circuit breakers
appendix
auxiliary switches,
undervoltage trip device alarm switch,
rated voltage ( V ) overcurrent trip switch
UL 489 listed IEC 947-2
position switches
DC 24 DC 24
IEC 947- 2 characteristics are the same as
48 48 those indicated in page 18
125 125
Merlm Gerin
39
Courtesy of NationalSwitchgear.com
As standards specifications and designs develop from time
,