Professional Documents
Culture Documents
Technology
Department of Agricultural and Biosystems
Engineering
Visca, Baybay City, Leyte, PHILIPPINES
Telephone: (053) 525-0140 local 1015
Email: dabe@vsu.edu.ph
Website: www.vsu.edu.ph
ABEn 154
AB Electrification and Control Systems
2nd Semester SY 2020-2021
Submitted by:
Waren R. Cañete
BSABE Student
Submitted to:
July 2021
ABEn 154. Final Course Project Report
In the figure below presents the first sheet of the engineering plans containing the three
structural plans namely:
a. Exterior perspective
b. Location Map, and
c. Site development plan.
In the same sheet, the following important columns with their specific contents are also
include:
Column 1 the title of the project, the name of the student, the name of the professor in
this subject and the date submitted
Column 2 represent your structural plan of your project
The other structural drawings such as front elevation (A-05), right side elevation (A06), and the left
side elevation (A-07), the cross section (A-08) and longitudinal section (A-09) and the back view (A-
10) are shown below:
This figure below shows the floor plan and the foundation plan of the building
`
The floor plan and foundation plan of the building.
The sample calculation of computing the demand load of the swine growing to finishing
building is shown below with the assumed equipment to be installed in the building.
Based on the loads listed above, the following are the information in terms full-load
currents from the breeding station structural farm building.
In getting the capacity of the main service equipment, using the load in the farms without
diversity include the feed storage auger, exhaust fans, water pump, convenience outlets
and one-half of the lightning outlets
Note that 100 A is chosen because the actual demand load is 62.025 A rated at 240
V and the next size to be chosen should be at least with additional 50 % to have spare for
additional equipment that may take place in the future for expansion purposes. Therefore,
the recommended rated size of the Service Entrance Switch of 100 A is acceptable.
Applying the recommended number of outlets to be served using the 15-A or 20-A branch
circuits in alternatives is computed below.
48 lightings∧outlets
No .of 15−A circuits= =4.8∨5 minimum circuits
Option 1: outlets
10
circuit
48 lightings∧outlets
No .of 20−A circuits= =4 minimum circuits
Option 2: outlets
12
circuit
The remaining assumed loads without diversity are feed storage auger motor, (2)
exhaust fans, and water pump with each has each own branch circuits. Therefore, the
total number of branch circuits is 12 in the main service entrance including a one space
for spare. The data were listed or summarize in a tabular method form
Sizing the branch circuits for an electric range presents a special situation. Minimum
wire sizes required in each of the different parts in the wiring system contain the wire size
requirement of the main feeder for the overcurrent protection of service entrance, branch
circuits and different loads. It is determined through the assume allowable voltage drop to
be 2% of 240 V of source
The following are the information in the computation of the wire sizes required in each
branch circuits.
1. The type of wire is TW stranded copper wire with 7 strands
2. The distance specified in the computations is the distance possible path of the
conduit raceway from the panel board to the farthest component of the CKT
3. Allowable Voltage Drop (ED) and voltage of the source are, ED = 2%, V=240
The continuous demand load on the panel board is 62.025 A. According to NEC
(2002), the feeder overcurrent protection device should be sized with not less than the
125% of the continuous demand load on the panel board. Using this formula, we can get
the ampere of the main feeder:
From Table A.5, select No. 4 TW wire with a rating of 75 A at 90ºC. At 90ºC, the ampacity
correction factor for a 2-wire TW wire is 0.41. Therefore, you should use 4 No. 4 T85
aluminum or copper clad aluminum type with 2 No. 2 ITW wire at protection rating of 75
A.
Wire sizes for the branch circuits for the lighting outlet are computed using the two
formulas as follows:
ED
RA= , where ED = voltage drop = 0.02 x 240 v = 4.8 ohms
I
RA E D × 1000
= , where D=is the lengthof the wire within the circuit
1000 m 2× D
a. Branch Circuit 1
Assumption: I = 1 A, D= 30 m
ED 0.02 x 240
RA= = =4.8 ohms
I 1
RA 4.8 ×1000
= =¿
1000 m 2 ×30
a. Identify the number of Branch Circuits that will include the following:
Branch Circuits for lighting fixtures
Branch Circuits for convenience outlets
Branch Circuits for specific purpose
Branch Circuits for special purpose
b. Compute the capacity of each branch circuit
Discuss and present the formula
c. Compute the wire size for each branch circuit
Discuss and present the formula
d. Summary listing of the branch circuits with capacity ratings
III.1 Determination of the number and types of luminaires for the building
The lights needed for this structure is that it should have at least 40 lux/sq. meter.
Fluorescent lamp is used and suggested by BPEX, it is a practical guide for lighting for
pig units.
PAES (2001) recommended that the required number of lamps per sq. m. for lighting
intensity equal to 50 lux for an a 20W fluorescent lamp is 0.068.
Based on the area presented above, the number of luminaires required per section is
computed using the formula:
No .of luminaire=number of lamps per sq . meter ×area of pens
b. Security Room:
The recommendation illumination for the pens is 500 lux. Using a 20 W of fluorescent
lamp that is equivalent to 0.068.
Solution:
Number of luminaire: = No. of lamps required/ m 2 x area of pens
= 0.068 x 5 m 2
= 0.34 lamp
Use: 1 - 20 W fluorescent luminaire
c. Office Room
The recommendation illumination for the pens is 500 lux. Using a 20 W of fluorescent
lamp that is equivalent to 0.068.
Solution:
Number of luminaire: = No. of lamps required/ m 2 x area of pens
= 0.068 x 68.25 m 2
= 4.641 lamps or 5 lamps
Use: 5 - 20 W fluorescent luminaire
d. Equipment Room
The recommendation illumination for the pens is 100 lux. Using a 20 W of fluorescent
lamp that is equivalent to 0.068.
Solution:
Number of luminaire: = No. of lamps required/ m 2 x area of pens
= 0.068 x 142.8 m 2
= 9.71 lamps or 10 lamps
Use: 10 - 20 W fluorescent luminaires
e. Storage Room
The recommendation illumination for the pens is 100 lux. Using a 20 W of fluorescent
lamp that is equivalent to 0.068.
Solution:
Number of luminaire: = No. of lamps required/ m 2 x area of pens
= 0.068 x 50 m 2
= 3.4 lamps or 4 lamps
Use: 4 - 20 W fluorescent luminaire
f. Farrowing Pen
The recommendation illumination for the pens is 200 lux. Using a 20 W of fluorescent
lamp that is equivalent to 0.068.
Solution:
ABEn 154. Final Course Project Report
g. Piglet Area
The recommendation illumination for the pens is 200 lux. Using a 20 W of fluorescent
lamp that is equivalent to 0.068.
Solution:
Number of luminaire: = No. of lamps required/ m 2 x area of pens
= 0.068 x 137.6 m 2
= 9.356 lamps or 10 lamps
Use: 10 - 20 W fluorescent luminaire
h. Boar Pen
The recommendation illumination for the pens is 50 lux. Using a 20 W of fluorescent
lamp that is equivalent to 0.068.
Solution:
Number of luminaire: = No. of lamps required/ m 2 x area of pens
= 0.068 x 63.44 m 2
= 4.3139 lamps or 5 lamps
Use: 5 - 20 W fluorescent luminaire
i. Mating Area/Pen
The recommendation illumination for the pens is 300 lux. Using a 20 W of fluorescent
lamp that is equivalent to 0.068.
Solution:
Number of luminaire: = No. of lamps required/ m 2 x area of pens
= 0.068 x 85.5 m 2
= 5.814 lamps or 6 lamps
Use: 6 - 20 W fluorescent luminaire
Therefore, the total luminaire requirements for the 50-head Capacity Gestation
Sow for Breeding Station Farm Structure Building:
Solution:
Total Number of Luminaires = No of luminaires for ((mating, boar, gestation, farrowing
pens) + office + security room + feed storage + equipment room + piglet area)
= (6+5+58+4) +5+1+4+10+10
=103 - 20 W fluorescent luminaires
For the exterior lighting, it should be at least four (4) 18 W LED bulb can be used,
thus:
Use: 4 – 18 W LED bulbs
Therefore, the total luminaire requirements for the 50-head Capacity Sow in Breeding
Station Farm Structure Building:
For this project report, the electrical layout of the 50-head Capacity of Sow for
Breeding Station Building is presented as a whole that combines the three (3)
major components.
The electrical layout of the 50-head capacity of Sow on a Breeding Station Building
3.8 Preparation of the Bill of Material
A bill of materials or structure product is a list of the raw materials, sub-assemblies,
intermediate assemblies, sub-components, parts and the quantities of each needed to
construct or build a new product. It is the quantities required of each component and their
cost
V. LIFELONG LEARNINGS