You are on page 1of 3

POINT LOAD = 163.

3 kg
POINT LOAD = 398.9 kg
POINT LOAD LAYOUT PLAN POINT LOAD = 303.6 kg
1:400@A3

TAKACHIHO
FIRE, SECURITY & SERVICES (THAILAND) LTD.
H1
H1

H1

H1

H1

POINT LOAD (H1) = DEAD LOAD + LIVE LOAD (Ref NFPA 13)
DEAD LOAD = WEIGHT OF WATER FILLED PIPE 3"
= 16.10 kg/m X 3m =48.3kg
LIVE LOAD = 115 kg
POINT LOAD (H1) = 163.3 kg

POINT LOAD - H1
1:50@A3

TAKACHIHO
FIRE, SECURITY & SERVICES (THAILAND) LTD.
H3 H3

POINT LOAD (H2, H3) = DEAD LOAD + LIVE LOAD (Ref NFPA 13)
POINT LOAD - H2,H3 DEAD LOAD = WEIGHT OF WATER FILLED PIPE 8"
1:50@A3 = 70.98 kg/m X 4m =283.9kg
LIVE LOAD = 115 kg
POINT LOAD (H1) = 398.9 kg

POINT LOAD (H2a, H3a) = DEAD LOAD + LIVE LOAD (Ref NFPA 13)
DEAD LOAD = WEIGHT OF WATER FILLED PIPE 6"
= 47.15 kg/m X 4m =188.6kg
LIVE LOAD = 115 kg
POINT LOAD (H1) = 303.6 kg