General Data
kg
Wind pressure wp 60
2
m
Profile Geometry
width bp 10cm
kg
bending stress fy 2400
2
cm
kg
elasticity Es 2100000
2
cm
I 3
Modulus section z 36.542 cm
0.5 hp
2 2 2
Area of profile a hp ( hp 2 tp) 11.64 cm
Mmax 62174kg cm
δm 1.2cm
Mmax
ratio 0.886 1 Ok
Mn 0.8
2. Check Horizontal Frame Hollow 100x50x2.7mm
kg
wind pressure wp 60
2
m
Profile Geometry
width wh 10cm
kg
bending stress fy 2400
2
cm
kg
elasticity Es 2100000
2
cm
Ih 3
Modulus section zh 7.488 cm
0.5 wh
2 2 2
Area of profile a hp ( hp 2 tp) 5.64 cm
2
wlt ws 3
Mtmax 6.48 10 kg cm
8
Momen capacity Mtu fy zh 0.8 143.767 kg m
Mtmax
Ratio 0.451 1 Ok
Mtu
4
5 wlt ws ws
Deflection δt 0.495 cm 1.371 cm Ok
384 Es Ih 175
3. Check Frame Hollow 38x38x1,1mm
kg
wind pressure wp 60
2
m
Profile Geometry
width wa 3.8cm
kg
bending stress Pb 1100
2
cm
kg
elasticity Es 700000
2
cm
Ih 3
Modulus section zh 3.031 cm
0.5 wh
2 2 2
Area of profile a hp ( hp 2 tp) 2.152 cm
2
wlt ws
Mtmax 3456 kg cm
12
Mtmax
Ratio 1 1 Ok
Mtu
4
wlt ws ws
Deflection δt 1.876 cm 2.667 cm Ok
120 Es Ih 90
4. Check Vertical Frame Mullion 53x40 Allumunium
kg
wind pressure wp 60
2
m
width span hs 120cm
Profile Geometry
width wh 4cm
kg
bending stress Pb 1100
2
cm
kg
elasticity Ea 700000
2
cm
4
Inertia profile Im 9.74cm
Ih 3
Modulus section zm 5.719 cm
2.65cm
Mn Pb z 40196 kg cm
2
wlt vsm
Mtmax 2025 kg cm
8
Mtmax
Ratio 0.759 1 Ok
Mtu
4
5 wlt vsm ws
Deflection δt 0.447 cm 1.371 cm Ok
384 Ea Ih 175
kg
wind pressure wp 60
2
m
tg 1cm
Width span m 120cm
Transom properties
high of transom ht
cx 2.46cm
cy 2.1cm
kg
wind load wlt 72
m
kg
weight of glass wg hg m tg 0.0025 45 kg
3
cm
wg m
Muty 675 kg cm due weight of glass
2 4
4
wlt m
δtx 0.649 cm
120 Ea Iy
m
Deflection limit δax 0.686 cm δtx 0.649 cm Ok
175
m
δay 0.4 cm δty 0.265 cm Ok
300
7 Check Single Glas Unit
kg
Wind pressure wp 60
2
m
General Properties
Length of edge a 278cm
Shorter of edge b 120cm
outer panel sg 1cm
Load factor γL 1.2
kg
Elasticity Glass Eg 700000
2
cm
Allowable stress of Annealed Glass
kg
σac 250
2
cm
a
Ratio 2.317
b
β 0.75
α 0.1421
SAP2000 v16.0.0 - File:CW - Frame Span Loads (WIND) (As Defined) - Kgf, cm, C Units
SAP2000 6/1/21 5:20:37
SAP2000 v16.0.0 - File:CW - Steel P-M Interaction Ratios (AISC 360-10) - Kgf, cm, C Units
SAP2000 5/28/21 15:31:33
1 Input data
Anchor type and diameter: HSA NG M12 hnom1
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 50 mm, hnom = 64 mm
Material:
Evaluation Service Report: ETA 11/0374
Issued I Valid: 8/8/2016 | -
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0 mm (no stand-off); t = 10 mm
Anchor plate: lx x ly x t = 150 mm x 210 mm x 10 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: uncracked concrete, C25/30, fc,cyl = 25.00 N/mm2; h = 120 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
with longitudinal edge reinforcement d >= 12 + close mesh (stirrups, hangers) s <=
Reinforcement to control splitting according to fib (07/2011), 10.1.5.2 present
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.5
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 5/25/2021
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.5
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 5/25/2021
E-Mail:
5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.111 0.064 2.000 2 OK
concrete 0.429 0.232 1.500 40 OK
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.5
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 5/25/2021
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Your design has selected filled holes. Please ensure that there is a proper method to fill the annular gap between the fixture and HSA NG
M12 hnom1, and contact Hilti in case of any questions.
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.5
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 5/25/2021
E-Mail:
8 Installation data
Anchor plate, steel: - Anchor type and diameter: HSA NG M12 hnom1
Profile: no profile Installation torque: 0.050 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 10 mm Hole depth in the base material: 72 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
75 75
40
3 4
105
130
x
105
1 2
40
31 90 30
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com Profis Anchor 2.7.5
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 5/25/2021
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan