Professional Documents
Culture Documents
Abstract— Symmetrical component distance relay (SCDR) was protection and SCDR, since both of them uses only one
introduced by A.G Phadke, M. Ibrahim and T. Hilbka in-order equation to estimate the positive sequence impedance and FL
to reduce the computational burden in conventional numerical of the protected line respectively, but the main difference
distance relay (CNDR) where all the six elements, each arises from the fact that SCDR does not receive the selected
represented by one equation simultaneously estimates the
voltage and current phasor pairs as done in switched numerical
positive sequence impedance of the protected line for all kinds of
faults. SCDR uses only one equation to estimate the fault location distance protection, where these phasors are selected and
(FL) for all kinds of faults. Even-though the field tests are delivered to the impedance estimation algorithm by fault
successful, the performance equation of SCDR fails to survive as classification algorithms e.g. SIEMENS 7SA511 distance
an algorithm in relay industry. This paper investigates the relay [2]. Even though field tests on 765 KV line [5], [6] show
performance of SCDR for different fault types, location, source satisfactory results from algorithm point of view when SCDR
to line reach impedance (SIR) and for different loading is digitally implemented, relay manufacturers have not
conditions. The results obtained are compared with CNDR (non- incorporated this SCDR algorithm in numerical distance relay.
switched type).
1
B. Operating Principle Of SCDR
where,
SCDR uses only one performance equation, using
Z Z L1
k E L0 (1) which it estimates the FL in per unit for all fault types [4].
3Z L1 The performance equation is given by equation (3), if the
fault resistance R f is assumed to be zero.
kE residual compensation factor
k1 k 2 k 2' k o k0'
Z L0 zero sequence impedance of the protected line k (3)
1 k0' k 2' kl
Z L1 positive sequence impedance of the protected line
V r , y ,b voltage phasors where,
Ex
I r , y ,b current phasors kx (4)
E x
I0 zero sequence current phasor
E0 j (0 1 )
k 0' e (5)
These six elements estimates the positive sequence impedance E1
of the protected line simultaneously and the tripping decision
is made based on the angle criterion [7] as shown in Figure 1 k 2' 1 if E0 E1 (6)
and Figure 2 where, Z R is the impedance of the protected = 0 otherwise
transmission line referred to secondary of CT and CVT and Z1 I 1
Z r r is the estimated positive sequence impedance. kl (7)
E1
where,
x=0 zero sequence
x=1 positive sequence
x=2 negative sequence
90 ang (S1' ) ang (S2' ) 90 (2) Figure 3. Test system
2
Power system shown in Figure 3 is subjected to 600 different IV. PERFORMANCE ANALYSIS
conditions like,
A. Speed
s 0,10,20,30
Speed is one of the prime requirements for any protection
10 different kinds of faults device. An increase in relay operating time may lead to
single phase to ground fault (SPGF) equipment or plant damage, raises safety issues and it may
phase to phase fault (PPF) lead to an unstable system. SCDR and CNDR operating time
phase to phase and ground fault (PPGF) for different types of faults at 50km and 100km are obtained
3 phase fault (3PF) by using the test method as shown in Figure 4 of previous
SIR = 1,5,10,20,30 section. Since the fault location lies within the zone 1 reach
FL = 50km, 100km, 200km setting of both SCDR and CNDR, zone 1 element of both the
relays are expected to assert trip signal. Figure 5, Figure 6,
The manner in which the simulation is carried out to Figure 7 and Figure 8 show the actual operating times of
investigate the performance of SCDR is shown in Figure 4. SCDR and CNDR for SPGF, PPF, PPGF and 3PF
respectively.
Figure 4 . Test method used to analyze the performance of SCDR with CNDR
B. Selectivity
Relay Maloperation
(%)
CNDR 54
Figure 8. Relay operating time for 3PF SCDR 46.5
4
Investigation shows that, mal-operation occurs only during
high SIR conditions and this can be tackled in CNDR by using
a security counter to assist the trip decision to increase
selectivity.
C. Reliability
5
Investigation on speed requirement, particularly for
SPGF and 3PF shows that SCDR relay operating
times is relatively high for most cases.
Investigation on selectivity requirement shows that
SCDR performs better than CNDR.
APPENDIX A
REFERENCES
[1] S. Horowitz and A.Phadke, Power system relaying, 3rd
ed. England: Wiley, 2008.
[2] G. Ziegler, Numerical Distance Protection: principles
and applications, 3rd ed. Erlangen: Wiley, 2008.
[3] M. Adamiak, G. Alexander, and W. Premerlani,”
Advancements in adaptive algorithms for secure high
speed distance protection,” in 23rd Annual Western
Protective Relaying Conference, 1996.
[4] A. Phadke, M. Ibrahim and T. Hlibka, “Fundamental
basis for distance relaying with symmetrical
components,” IEEE Trans. on Power Apparatus and
Systems,. Vol.96, no 2, pp.635-646, Apr.1977.
[5] M. Adamiak and J. Jauch, “Field experience with the
Figure 16. Estimated FL by SCDR for PPGF at 50% of line length
AEP digital relay,” IEEE Trans.on Power Del., vol. 1,
no 4, pp.91-98 Oct. 1986.
[6] A. Phadke, T. Hlibkka, M. Adamiak, M. Ibrahim, and J.
Thorp, “A microcomputer based ultra-high-speed
distance relay: Field tests,” IEEE Trans. on Power
Apparatus and Systems, vol.100, No. 4, pp 2026-2036,
Apr. 1981
[7] V. Cook, Analysis of distance protection. NY: Research
Studies Press, 1985.
[8] R. B. Laughlin (2009, Aug.) Standard parameters of 800
KV class transmission systems in INDIA[Online].
Available:
http://large.stanford.edu/publications/coal/references/cea
/.
[9] L.Hewitson, M. Brown, and R. Balakrishnan, Practical
power system protection. MA: Newnes, 2005.
[10] E. T. Association et al.,Power System Protection:
Principles and components. UK: Institution of Elec.
Figure 17. Estimated FL by SCDR for 3PF at 50% of line length Engineers, 1995.
[11] G. Benmoyal, “ Removal of dc-offset in current
V. CONCLUSION
waveforms using digital mimic filtering,” IEEE Trans.
Power. Del., vol.10, no 2, pp. 621-630, Apr.1995.
Investigation on reliability shows that SCDR fails to [12] M. Dadash Zadeh, T. Sidhu, and A. Klimek,”FPAA-
meet the performance requirement since it fails to based mho distance relay considering CVT transient
meet the dependability requirement. It is also supervision,” Generation, Transmission and Distribution,
observed that this occurs only at high SIR i.e. when IET, vol.3, no.7, pp-616-627, 2009.
SIR is 30.
6
Venkatesh C received B.E. degree in
electrical and electronics engineering
from the Madras University, India, in
2004, Post Graduation Diploma in
Thermal Power Plant Engineering from
National Power Training Institute,
Neyveli, Ministry of Power, India, in
2005 and the M.Tech. degree in energy
from the Indian Institute of Technology Delhi, New Delhi,
India, in 2010. He worked in Delhi Discom for five years
where he handled protection, SCADA, commissioning and O
& M. He is currently a Research Scholar with the Department
of Electrical Engineering, Indian Institute of Technology
Madras. His research interest includes Power System
Protection, SCADA testing and condition monitoring of
Power Transformers and Circuit Breakers.