Above listed Messages are sended to CU all the time to make decision Which bay is

connected to which bus. (CU also reflect this info on its SLD)

7601 > Isolator position-1 closed 7621 > Circuit breaker failure start 3-pole
7602 > Isolator position-1 open 7620 > Bay out of service
7603 > Isolator position-2 closed 7618 > Circuit breaker manual close
7604 > Isolator position-2 open
7623 > Circuit breaker closed
7624 > Circuit breaker open
7619 > Circuit breaker not ready

BU-1 BU-3 BU-5

BU-2 BU-4
Following Messages are sended to BU in case of BB or BF

7631 Busbar protection:Trip in phase L123


CENTRAL UNIT( CU) 7632 CBF protection:Trip repeat phase L123
7639 Busbar protection:Intertrip
7643 CBF protection :Trip L123
7644 End fault protection:Trip phase L123 (Only Line

BU-5 BU-7 BU-9

BU-6 BU-8 BU-10


ded to BU in case of BB or BF trip by CU.

phase L123
at phase L123
rip
3
phase L123 (Only Line

BU-11

BU-10
Bay-1(LINE 1) Bay-2(TRAN.1) Bay-3(LINE2) Bay-4(TRAN.2)
BB-1A

DS.1 DS.1 DS.1 DS.1

DS.2 DS.2 DS.2 DS.2


BB-2A

CB CB CB

CT CT CT
Bay-5A(BC) Bay-5B(BC) Bay-6A(BS) Bay-6B(BS) Bay-7A(BC)
CB
CT CT
DS.
CT

CB
CT
DS.

CB DS.1 DS.2

CT
Bay-7A(BC) Bay-7B(BC) Bay-8(LINE 3) Bay-9(Line 4)) Bay-10(TRAN.3)

DS. DS.1 DS.1 DS.1


CT

CB

DS. DS.2 DS.2 DS.2

CB CB

CT CT
Bay-11(LINE 5)
BB-1B

DS.1

DS.2
BB-2B

CB CB

CT CT
BU-1(LINE 1) BU-2(TRAN.1) BU-3(LINE2) BU-4(TRAN.2) BU-5(BC) BU-6(BC)
BB-1A

DS.1 DS.1 DS.1 DS.1 DS.


CT

CB
CT
DS.2 DS.2 DS.2 DS.2 DS.
BB-2A

CB CB CB CB

CT CT CT CT
Following listed Messages are sended to CU all the time to make decision Which bay is connected to
which bus. (CU also reflect this info on its SLD)

7601 > Isolator position-1 closed 7603 > Isolator position-2 closed 7621 > Circuit breaker failure start 3-pole
7602 > Isolator position-1 open 7604 > Isolator position-2 open 7624 > Circuit breaker open
7623 > Circuit breaker closed 7624 > Circuit breaker open 7618 > Circuit breaker manual close

BB-1A
BB-2A
BB-1B
BB-2B

BU-1 BU-3 BU-5

BU-2 BU-4 BU-6


BU-7(BS) BU-8(BS) BU-9(BC) BU-10(BC) BU-11(LINE 3) BU-12(TRAN.3)) BU-13(LINE 4)
CB
CT CT
DS. DS.1 DS.1
CT

CB

DS. DS.2 DS.2

CB CB

CT CT
CENTRAL UNIT( CU)
Following Messages are sended to BU in case of BB or BF trip by CU.

7620 > Bay out of service 7631 Busbar protection:Trip in phase L123 7639 Busbar protection:Intertrip
7632 CBF protection:Trip repeat phase L123 7643 CBF protection :Trip L123
7644 End fault protection:Trip phase L123 (Only Line Bays)

BU-7 BU-9 BU-11 BU-3

BU-8 BU-10 BU-2


BU-13(LINE 4) BU-14(LINE 5)
BB-!B

DS.1 DS.1

DS.2 DS.2
BB-2B

CB CB

CT CT
Check Zone
ip by CU.
protection:Intertrip IDIFF IBIAS Check Zone Will
Take all CTs Except
otection :Trip L123 BC CTs
Discimination
Zone
I DIFF I BIAS Decision
BB-1A Trip
BB-2A Trip
BB-1B Trip
BB-2B Trip

BU-3

BU-4
BU-1(LINE 1) BU-2(TRAN.1) BU-3(LINE2) BU-4(TRAN.2)
BB-1A

DS.1 DS.1 DS.1 DS.1

DS.2 DS.2 DS.2 DS.2


BB-2A

CB CB CB

CT CT CT
Following listed Messages are sended to CU all the time to make decision Which bay is connected to which bus(c
input contacts). CU also reflect this info on its SLD

7601 > Isolator position-1 closed 7603 > Isolator position-2 closed 7621 > Circuit breaker failure sta
7602 > Isolator position-1 open 7604 > Isolator position-2 open 7624 > Circuit breaker open
7623 > Circuit breaker closed 7624 > Circuit breaker open 7618 > Circuit breaker manual clo
BB-1A
BB-2A
BB-1B
BB-2B

BU-1
BU-3
Inputs
Inputs

BU-2 BU-4

Inputs Inputs

Outputs Outputs

Outputs Outputs
BU-5(BC) BU-6(BC) BU-7(BS) BU-8(BS) BU-9(BC)
CB
CT CT
DS. DS.
CT CT

CB
CT
DS. DS.

CB DS.1 DS.2

CT
bay is connected to which bus(configured IN BU for CENTRAL UNIT( CU)
on its SLD Following Messages are sended to BU in case

7621 > Circuit breaker failure start 3-pole 7620 > Bay out of service 7631 Busbar protection:Trip in phase L
7624 > Circuit breaker open 7632 CBF protection:Trip repeat phase
7618 > Circuit breaker manual close 7644 End fault protection:Trip phase L

BU-5 BU-7 BU-9

Inputs Inputs Inputs

BU-6 BU-8

Inputs Inputs

Outputs Outputs Outputs

Outputs Outputs
BU-10(BC) BU-11(LINE 3) BU-12(Line 4) BU-13(TRAN.3) BU-14(LINE 5)

DS.1 DS.1 DS.1 DS.1

CB

DS.2 DS.2 DS.2 DS.2

CB CB CB

CT CT CT
Check Zone
ages are sended to BU in case of BB or BF trip by CU(Configured IN BU for output contacts )
bar protection:Trip in phase L123 7639 Busbar protection:Intertrip IDIFF IBIAS
protection:Trip repeat phase L123 7643 CBF protection :Trip L123
fault protection:Trip phase L123 (Only Line Bays)

BU-11 BU-13

Inputs Inputs

BU-10 BU-12 BU-14

Inputs Inputs Inputs

Outputs Outputs

Outputs Outputs Outputs


s
BB-!B

BB-2B

CB

CT

Check Zone Will


Take all CTs Except
BC CTs
Discimination Zone
Decision
I DIFF I BIAS BB-1A Trip
BB-2A Trip
BB-1B Trip
BB-2B Trip

s
BU-1(LINE 1) BU-2(TRAN.1) BU-3(LINE2) BU-4(TRAN.2)
BB-1A

DS.1 DS.1 DS.1 DS.1

DS.2 DS.2 DS.2 DS.2


BB-2A

CB CB CB

CT CT CT
Following listed Messages are sended to CU all the time to make decision Which
which bus. (CU also reflect this info on its SLD)
7601 > Isolator position-1 closed 7621 > Circuit breaker failure sta
7602 > Isolator position-1 open 7620 > Bay out of service
7603 > Isolator position-2 closed 7618 > Circuit breaker manual cl
7604 > Isolator position-2 open 7619 > Circuit breaker not ready
7623 > Circuit breaker closed 7624 > Circuit breaker open
BB-1A
BB-2A
BB-1B
BB-2B
BB Trip BB Trip BB Trip BB Trip
CBF-1 DS.1 CL CBF-1 DS.1 CL CBF-1 DS.1 CL CBF-1 DS.1 CL
Intertrip DS.1 OP Intertrip DS.1 OP Intertrip DS.1 OP Intertrip DS.1 OP
CBF-2 DS.2 CL CBF-2 DS.2 CL CBF-2 DS.2 CL CBF-2 DS.2 CL
End Ft. DS.2 OP End Ft. DS.2 OP End Ft. DS.2 OP End Ft. DS.2 OP
CB.OP CB.OP CB.OP CB.OP
CB.CL CB.CL CB.CL CB.CL
BFI BFI BFI BFI
CB.NR CB.NR CB.NR CB.NR
BOS BOS BOS BOS
CMC CMC CMC CMC
CB.F CB.F CB.F CB.F
CT Value CT Value CT Value CT Value
BU-2 BU-4

BU-1 BU-3
BU-5(BC) BU-6(BC) BU-7(BS) BU-8(BS) BU-9(BC)
CB
CT CT

CT CT

CB

CT

CB

CT
e time to make decision Which bay is connected to CENTRAL UNIT( CU) Following Messages are sended to BU
flect this info on its SLD)
7621 > Circuit breaker failure start 3-pole 7631 Busbar protection:Trip in phase L
7620 > Bay out of service 7632 CBF protection:Trip repeat phase
7618 > Circuit breaker manual close 7639 Busbar protection:Intertrip
7619 > Circuit breaker not ready 7643 CBF protection :Trip L123
7624 > Circuit breaker open 7644 End fault protection:Trip phase L

BB Trip BB Trip BB Trip BB Trip BB Trip


CBF-1 DS.1 CL CBF-1 DS.1 CL CBF-1 DS.1 CL CBF-1 DS.1 CL CBF-1 DS.1 CL
Intertrip DS.1 OP Intertrip DS.1 OP Intertrip DS.1 OP Intertrip DS.1 OP Intertrip DS.1 OP
CBF-2 DS.2 CL CBF-2 DS.2 CL CBF-2 DS.2 CL CBF-2 DS.2 CL CBF-2 DS.2 CL
End Ft. DS.2 OP End Ft. DS.2 OP End Ft. DS.2 OP End Ft. DS.2 OP End Ft. DS.2 OP
CB.OP CB.OP CB.OP CB.OP CB.OP
CB.CL CB.CL CB.CL CB.CL CB.CL
BFI BFI BFI BFI BFI
CB.NR CB.NR CB.NR CB.NR CB.NR
BOS BOS BOS BOS BOS
CMC CMC CMC CMC CMC
CB.F CB.F CB.F CB.F CB.F
CT Value CT Value CT Value CT Value CT Value
BU-6 BU-8

BU-5 BU-7 BU-9


BU-10(BC) BU-11(LINE 3) BU-12(TRAN.3)) BU-13(LINE 4) BU-14(LINE 5)

DS.1 DS.1 DS.1 DS.1

CB

DS.2 DS.2 DS.2 DS.2

CB CB CB

CT CT CT
Messages are sended to BU in case of BB or BF trip by CU.

bar protection:Trip in phase L123


protection:Trip repeat phase L123
bar protection:Intertrip
protection :Trip L123
fault protection:Trip phase L123 (Only Line Bays)

BB Trip BB Trip BB Trip BB Trip BB Trip


CBF-1 DS.1 CL CBF-1 DS.1 CL CBF-1 DS.1 CL CBF-1 DS.1 CL CBF-1 DS.1 CL
Intertrip DS.1 OP Intertrip DS.1 OP Intertrip DS.1 OP Intertrip DS.1 OP Intertrip DS.1 OP
CBF-2 DS.2 CL CBF-2 DS.2 CL CBF-2 DS.2 CL CBF-2 DS.2 CL CBF-2 DS.2 CL
End Ft. DS.2 OP End Ft. DS.2 OP End Ft. DS.2 OP End Ft. DS.2 OP End Ft. DS.2 OP
CB.OP CB.OP CB.OP CB.OP CB.OP
CB.CL CB.CL CB.CL CB.CL CB.CL
BFI BFI BFI BFI BFI
CB.NR CB.NR CB.NR CB.NR CB.NR
BOS BOS BOS BOS BOS
CMC CMC CMC CMC CMC
CB.F CB.F CB.F CB.F CB.F
CT Value CT Value CT Value CT Value CT Value
BU-10 BU-12 BU-14

BU-11 BU-13
BB-!B

BB-2B

CB

CT

Discimination Zone Check Zone

I DIFF I BIAS IDIFF IBIAS