You are on page 1of 19

Bay-1(LINE 1) Bay-2(TRAN.

1)
BB-1A

DS.1

DS.2
BB-2A

CB

CT

Q9

BB-1A Main BB-1A


Relay
Ds.1/ NO contact

Ds.2/ NO
BB-2A Main BB-2A contact
Check Zone Protection
(Main Relay) Relay

Check Zone Take all the CTs


Except Bus Coupler and Bus
Section CTs. BB Tripping will Trip Bus +ve
be Done only if Check Zone
and any Bus Zone is INI.+VE
operated .If Zone operated
and Check zone is not 62 ART
operated ,this will be 86BB Reset +VE
considered relay senced
fault due to switching of cts
(due to DS, open /close )
,not actual fault. BB-1B
BB-1B Main Relay
BB-2B

BB-2B Main Relay

Bus-Bar Protection Panel


86BB

Diode cbf.optd

86CBF

Bay 1 (Line 1)
Protection Panel
Bay-2(TRAN.1) Bay-3(LINE2) Bay-4(TRAN.2) Bay-5(BC)

DS.1 DS.1 DS.1 DS.


CT

CB
CT
DS.2 DS.2 DS.2 DS.

CB CB CB

CT CT CT

Q9 Q9 Q9

Ds.1/ NO contact Ds.1/ NO contact Ds.1 / NO contact

Ds.2/ NO Ds.2/ NO Ds.2/ NO


contact contact contact
86BB

86BB 86BB 86BB 86BB

Diode cbf.optd Diode cbf.optd Diode cbf.optd Diode cbf.optd

86CBF 86CBF 86CBF 86CBF

Bay 2 (Tran.1) Bay 3 (Line 2) Bay 4 (Tran.2)


Protection Panel Protection Panel Protection Panel Bay 5 (BC-A) Protection Panel
Bay-6(BS-A uper) Bay-7A(BC) Bay-7B(BC) Bay-8(LINE 3)
CB
CT CT
DS.
CT

CB

Bay-6(BS-B Lower) DS.

DS.1 DS.2

BB Trip Relay Auto Reset Timer INI.+VE

86BB Reset OR Auto Reset +VE

Ds.1/ NO Ds.2/ NO
contact contact
Ds.1/ NO Ds.2/ NO
contact contact

86BB

86BB 86BB 86BB


Bay 5 (BS-B
Diode cbf.optd Lower)) Diode cbf.optd

86CBF 86CBF

Bay 5 (BS-A Upper))


Bay 7(BC-B) Protection Panel
Bus Section Protection Panel
Bay-8(LINE 3) Bay-9(Line 4)) Bay-10(TRAN.3) Bay-11(LINE 5)
BB-1B

DS.1 DS.1 DS.1 DS.1

DS.2 DS.2 DS.2 DS.2


BB-2B

CB CB CB CB

CT CT CT CT

Q9 Q9 Q9 Q9

Example : How Tim


initiation and Reset Schem
done and work.In all Bays s
scheme is implemented f
timer intiation and reset in
of BB Protection Operate

Ds.1 / NO contact Ds.1 / NO contact Ds.1 / NO contact Ds.1 / NO contact 86BB /NO Contact

Ds.2/ NO Ds.2/ NO Ds.2/ NO Ds.2/ NO


contact contact contact contact
Ds.2/ NO Ds.2/ NO Ds.2/ NO Ds.2/ NO
contact contact contact contact

86BB 86BB 86BB 86BB

Diode cbf.optd Diode cbf.optd Diode cbf.optd Diode cbf.optd


Rest.Coil
86CBF 86CBF 86CBF 86CBF 86BB

Bay 11 (Line 5)
Bay 8 (Line 3) Bay 9 (Line 4) Bay 10 (Tran.3) Protection Panel
Protection Panel Protection Panel Protection Panel
Example : How Timer
nitiation and Reset Scheme is
one and work.In all Bays same
scheme is implemented for
mer intiation and reset in case
of BB Protection Operate .

86BB /NO Contact


Trp Coming as per
B B protection

Opt. Coil
86BB
UG Line Set 1 Protection Main Relay CBF-Trip
21-Z1/87L/Aided Trip/DEF Inst.Trip 21-Z2,Z3,Z4/SOTFT/BackUp OC&EF(Delayed Trip Inter Trip Rec.2
For 94L-1 to trip CB
94L-1 86L-1 through PSE From R
Trip Tc2 Trip Tc2
CBFI to SET 1 CB Close Block
CBFI to SET 2 CB Close Block (BCU) Inter Trip Rec.2
AR INI SET 1 CBFI to SET 1 For tripping Remote
AR INI SET 2 CBFI to SET 2 through PSE From L
AR Block SET 1
AR Block SET 2

We use 85DTTS.BF.1&2 Aux


are Configuring main relay c
we will not use these.we
BB-1A
BB-2A
BB-1B
BB-2B

86 CBF
85DTTR.BF.1 85DTTR.BF.2 CBF-Trip Over Head Li
Inter Trip Rec.1 21-Z1/87L/DEF/Aided Trip(Inst.Trip.)
For 94L-1 to trip CB comming For 94L-2 to trip CB comming through
through PSE From Remote end PSE From Remote end 94L-2
Trip Tc2
85DTTS.BF.1 85DTTS.BF.2 CBFI to SET 1
Inter Trip Rec.1 CBFI to SET 2
For tripping Remote CB Sending For tripping Remote CB Sending AR INI SET 1
through PSE From Local end through PSE From Local end AR INI SET 2

Note:

use 85DTTS.BF.1&2 Auxilary relay to send trip to remote end through PSE only ,when we
onfiguring main relay contact for intertrip Function(in case of CBF optd.) .in Present case
we will not use these.we use 86 CBF contcact to send trip to remote end through PSE

Q 1 Status O/C

Diode 86 BB
CB Close Block Trip TC1
CB Close Block (BCU) Trip TC2
Save Trip TC1 Close Block CB
Save Trip TC2 Close Block CB ( BCU)
AR Block SET-1 AR Block SET-1
AR Block SET-2 AR Block SET-2
InterTrip Send-1 CBFI to SET 1
InterTrip Send-2 CBFI to SET 2
Over Head Line Set 2Protection Main Relay
ded Trip(Inst.Trip.) 21-Z2,Z3,Z4/SOTFT/BackUp OC&EF(Delayed Trip)

86L-2
Trip Tc2
CB Close Block
CB Close Block (BCU)
CBFI to SET 1
CBFI to SET 2
AR Block SET 1
AR Block SET 2

Q 2 Status O/C

Block CB ( BCU)
UG Line Set 1 Protection Main Relay CBF-Trip
21-Z1/87L/Aided Trip/DEF Inst.Trip 21-Z2,Z3,Z4/SOTFT/BackUp OC&EF delayed trip Inter Trip Rec.2

94L-1 86L-1
Trip Tc2 CB Close Block
CBFI to SET 1 CB Close Block (BCU)
CBFI to SET 2 CBFI to SET 1 Inter Trip Rec.2
CBFI to SET 2

We use 85DTTS.BF.1&2 Auxil


are Configuring main relay
case we will not use these.w
BB-1A
BB-2A
BB-1B
BB-2B

86 CBF
85DTTR.BF.1 85DTTR.BF.2 CBF-Trip
Inter Trip Rec.2 Inter Trip Rec.1 21-Z1/87L/DEF/Aided Trip(Inst.Trip.)
For 94L-1 to trip CB comming For 94L-2 to trip CB comming through
through PSE From Remote end PSE From Remote end 94L-2

85DTTS.BF.1 85DTTS.BF.2
Inter Trip Rec.2 Inter Trip Rec.1
For tripping Remote CB Sending For tripping Remote CB Sending
through PSE From Local end through PSE From Local end

Note:

We use 85DTTS.BF.1&2 Auxilary relay to send trip to remote end through PSE only ,when we
are Configuring main relay contact for intertrip Function(in case of CBF optd.) .in Present
case we will not use these.we use 86 CBF contcact to send trip to remote end through PSE

86 CBF 86 BB
CB Close Block
CB Close Block (BCU)
Save Trip TC1
Save Trip TC2
InterTrip Send-1
InterTrip Send-2
Over Head Line Set 2Protection Main Relay
1-Z1/87L/DEF/Aided Trip(Inst.Trip.) 21-Z2,Z3,Z4/SOTFT/BackUp OC&EF(Delayed Trip)

86L-2
Trip Tc2 CB Close Block
CBFI to SET 1 CB Close Block (BCU)
CBFI to SET 2 CBFI to SET 1
CBFI to SET 2

Q 1 Status O/C Q 2 Status O/C

Trip TC1
Trip TC2
Close Block CB
Close Block CB ( BCU)
CBFI to SET 1
CBFI to SET 2
TRANSFORMER Set-1 Protection Main Relay HV CBF-Trip
LV CBF-Trip Buchlz Trip
For 86T-1 & 86T-2 to trip LB and M
94T-1 86T-1 Relay (Main Tank & OLTC)
Trip Tc 1 LV CB Trip Tc1 HV CB
CBFI to SET 1 LV CB HV CB Close Block
CBFI to SET 2 LV CB HV CB Close Block (BCU) Oil Tem.Trip
LV CB close Block For 86T-1 & 86T-2 to trip LB and M
CBFI to SET 1 HV Temp. Relay (Main Tank)
CBFI to SET 2 HV
ABTS
ACCS Oil Low Level Trip
For 86T-1 & 86T-2 to trip LB and M
Level (Main Tank&and OLTC)
BB-1A
BB-2A
BB-1B
BB-2B

86CBF-LV 86 CBF-HV
Trip TC1 HV CB
Trip TC2 HV CB
Save Trip TC1 LV CB
Save Trip TC2 LV CB
HV CB Close Block
HV CB Close Block BCU
LV CB Close Block
CBFI to SET 1 HV
CBFI to SET 2 HV
Buchlz Relay Winding Temp. HV CBF-Trip
Buchlz Trip Winding Temp Trip LV CBF-Trip
For 86T-1 & 86T-2 to trip LB and MB.Buchlz For 86T-1 & 86T-2 to trip LB and
Relay (Main Tank & OLTC) MB.Buchlz Relay (Main Tank) 94T-2

Oil Temp. Pressure Releif Device


Oil Tem.Trip PRD Trip
For 86T-1 & 86T-2 to trip LB and MB.Oil For 86T-1 & 86T-2 to trip LB and MB.
Temp. Relay (Main Tank) Pressure Releif Device (MainTank &
OLTC)
Oil Low Level Oil High Level
Oil Low Level Trip Oil high Level Trip
For 86T-1 & 86T-2 to trip LB and MB.Oil Low For 86T-1 & 86T-2 to trip LB and MB.Oil
Level (Main Tank&and OLTC) High Level (Main Tank& OLTC

86 CBF-HV 86 BB
Trip TC1 LV CB
Trip TC2 LV CB
Save Trip TC1 HV CB
Save Trip TC2 HV CB
HV CB Close Block
HV CB Close Block BCU
LV CB Close Block BCU
LV CB Close Block
CBFI to SET 1 LV
CBFI to SET 2 LV
Block ABTS
TRANSFORMER Set-2Protection Main Relay

86T-2
Trip Tc2 LV CB Trip Tc2 HV CB
CBFI to SET 1 HV CB Close Block
CBFI to SET 2 HV CB Close Block (BCU)
LV CB close Block
CBFI to SET 1 HV
CBFI to SET 2 HV
ABTS
ACCS

Q 1 Status O/C Q 2 Status O/C

Trip TC1 HV CB
Trip TC2 HV CB

HV CB Close Block
HV CB Close Block BCU
LV CB Close Block BCU
LV CB Close Block
CBFI to SET 1 HV
CBFI to SET 2 HV
CBFI to SET 1 LV
CBFI to SET 2 LV
Block ABTS

You might also like