ACCEPTANCE CRITERIA
Engine Generator
Ground bus(ses) have been installed and terminated to
1 DATE APPROVED
ground grid system
Permanent labels for bus, section, breakers and devices
2 DATE APPROVED
installed
10 Engine lube oil system is fully operational and free of leaks DATE APPROVED
11 Engine coolant system is fully operational and free of leaks DATE APPROVED
12 Fuel supply system tank is full and ready for operation DATE APPROVED
14 Engine exhaust has rain cap installed at exterior outlet DATE APPROVED
Engine
Generator
Service Area All
Contractor Notes
ACCEPTANCE CRITERIA
Generator remote E-stop is remotely installed, electrically
18 connected and fully operational to comply with NFPA 110, DATE APPROVED
Level 1 system
21 Utility Power is available and connected for system operation DATE APPROVED
Automatic
Transfer Switch
Service Area All
Contractor Notes
ACCEPTANCE CRITERIA
Automatic Transfer Switch
10 All enclosure panels and doors in place, fitted, undamaged DATE APPROVED
Passed 0
Tested 0 Pass?
Initial Test Date ?
Retest 1 ?
Retest 2 ?
VAV 0-067 VAV 1-025 VAV 1-061
Room(s) Served
Max Cooling CFM 2,400 1,100 2,400
Min Cooling CFM 1,200 1,050 1,200
Max Heating CFM 2,400 1,100 2,400
Min Heating CFM 1,200 1,050 1,200
Occupied Space Temperature Cooling Setpoint
Occupied Space Temperature Heating Setpoint
Notes
ACTION ACCEPTANCE CRITERIA
DEVICE LOCATIONS
Removable without removing
1 Observe VAV box Pass? Pass? Pass?
ductwork or piping.
Re-heat coil removable without
2 Observe reheat coil location. Pass? Pass? Pass?
removing ductwork or piping.
Observe reheat hot water valve Accessible for maintenance or
3 Pass? Pass? Pass?
location replacement
Observe perimeter radiation hot Accessible for maintenance or
4 Pass? Pass? Pass?
water valve location replacement
5 Observe temperature sensor location Temporary location Pass? Pass? Pass?
TEST INITIATION
Space temperature setpoint Insert Value Insert Value Insert Value
Space temperature Insert Value Insert Value Insert Value
VAV discharge temperature Insert Value Insert Value Insert Value
Record Initial Performance Supply airflow setpoint Insert Value Insert Value Insert Value
6
Parameters Supply airflow Insert Value Insert Value Insert Value
Damper position Insert Value Insert Value Insert Value
Reheat valve position Insert Value Insert Value Insert Value
Perimeter heating valve position Insert Value Insert Value Insert Value
OCCUPIED COOLING
Passed 0
Tested 0 Pass?
Initial Test Date ?
Retest 1 ?
Retest 2 ?
VAV 0-067 VAV 1-025 VAV 1-061
Room(s) Served
Max Cooling CFM 2,400 1,100 2,400
Min Cooling CFM 1,200 1,050 1,200
Max Heating CFM 2,400 1,100 2,400
Min Heating CFM 1,200 1,050 1,200
Occupied Space Temperature Cooling Setpoint
Occupied Space Temperature Heating Setpoint
Notes
ACTION ACCEPTANCE CRITERIA
OCCUPIED HEATING
Airflow at heating CFM. Pass? Pass? Pass?
Reheat valve opens to100%
before the perimeter heating
Pass? Pass? Pass?
Override the space temperature to: valve opens? Sequence of
heating setpoint minus 4 F. (Or operation is not clear.
adjust control setpoints to achieve the Perimeter heating valve opens to
Pass? Pass? Pass?
9 same system reaction.) Override the 100%.
outside air temperature to 39 F (or
Discharge air temperature
change perimeter heating lock-out Pass? Pass? Pass?
increases
setpoint).
Record airflow Insert Value Insert Value Insert Value
Record damper position Insert Value Insert Value Insert Value
Record VAV discharge
Insert Value Insert Value Insert Value
temperature
Perimeter heating valve position. Insert Value Insert Value Insert Value
Check the lighting circuit breakers to ensure that Circuit breaker shall be rated for switching
1.3 a Pass?
they are duty rated. functions “SWD”
6.2 Verify ON operation of ON/OFF digital switches a Pressing switch turns lighting ON. Pass?
Note that sensors can be set to shorter
Light fixtures will blink after __ minutes (5 minute timeout settings for these tests (greater
6.3 Verify OFF operation of room lighting control a "blink warn") and then will turn OFF automatically Pass? than 5 minute blink warn), but must be set
after 5 minutes. back to original setting - see ON/OFF
Worksheet
After lighting has turned OFF, turn on again with
6.4 a Pressing switch turns lighting ON. Pass?
ON/OFF digital switch.
Lighting remains ON for an additional ___ minutes
After "blink warn" has occurred, but before 5
6.5 a before turning OFF automatically. Confirm that 5 Pass?
minutes are up, press digital switch
minute "blink warn" again initiates.
Return all changed control parameters and
6.6 a OFF timeout delays are returned to initial settings. Pass?
conditions to their pre-set values.