kW kVAR

Generator Rating 1500 929.6

Motor Rating 220 118.7


Generator Peak Load 1223 264.8
Generaotor before MS 1003
### 146.1
Motor during MS 206.3895 1011.1

Gen demand 1157

Generator Terninal Voltage / Phase, Vp = 254.04157


Generator SubTransient Reactance, X" ( % ) = 15.6
Generator SubTransient Reactance, X" ( ohm ) = 0.0171142
Generator X/R ratio 15.46
Generator Resistant, R ( ohm ) = 0.001107

E, before Motor start >> 254.04157

Vp before Motor start =

sq E = sq (Vp.Cos@ + Irun.Rt) + sq (Vp.Sin@ + Irun.Xt) 67463.532


Erun = 259.73743

E, at Motor start >> 259.73743

Est = Erun

sq Est = sq (Vp.Cos@ + Ist.Rt) + sq (Vp.Sin@ + Ist.Xt) Vp at 67463.532


Motor start will change and given by >>
0 = a. Vp.Vp + b. Vp + c, where

a=
1

b = 55.786591
c = -65999.517
Vp = (-b+/-Sqrt(b.b-4.a.c)) / 2.a = 230.52023 taking + value
Voltage at Gen terminals, Vl-l = 399.2841
Internal Vd, V = 40.715901
Internal Vd, % = 9.2536139 Ex

Voltage Drop < 10% YES


kVA PF Eff Current Voltage
1764.7 0.85 0.97 2389.59 440

250 0.88 0.97 338.52 440


1251.3 0.98

1013.5848 0.9896 1329.985171


1031.947557 0.2 1354.08

2045.5324 0.825 2684.065171

67464.5865255929

259.739458930662

259.739458930662

67464.5865255929
1a
56.8735681642177 b
-65345.6762056551 c
228.768050426474 Vp_during start
25.2735195735259 vd

9.94857635839911 %vd