1MRS752349-MUM COCBDIR

Issued: 10/1997 Direct Open for CBs via MMI


Version: E/23.6.2005
Data subject to change without notice

Contents
1. Introduction ................................................................................................ 2
1.1 Features................................................................................................ 2
1.2 Application ............................................................................................ 2
1.3 Output description................................................................................. 2

2. Description of operation............................................................................ 3
2.1 Configuration ........................................................................................ 3
2.2 Operation criteria .................................................................................. 3

3. Parameters and events .............................................................................. 4


3.1 General ................................................................................................. 4
3.2 Setting values ....................................................................................... 5
3.2.1 Actual settings ............................................................................. 5
3.2.2 Control settings............................................................................ 5
3.3 Events ................................................................................................... 5

4. Technical data ............................................................................................ 6


COCBDIR Distribution Automation

1. Introduction

1.1 Features

• Provides a user-defined open pulse via the MMI push-button combination “up-
arrow” and “0”
• Can also be controlled remotely

1.2 Application

This document specifies the function of the COCBDIR function block used in
products based on the RED 500 Platform. The function block is mainly designed for
the direct open of the circuit breaker.

Table 1 . Protection diagram symbols used in the relay terminal

ABB IEC ANSI

COCBDIR CBDIR COCBDIR

Figure 1. Function block symbol for the direct open of the circuit breaker

1.3 Output description

Name Type Description


OPEN Digital signal (BOOL, active high) Direct open pulse

2
Distribution Automation COCBDIR

2. Description of operation

2.1 Configuration

The OPEN signal can be connected directly to the relay output signal or to the
OPENDIR input of the function block COCB1 or COCB2.

2.2 Operation criteria

Pressing a certain button combination will cause an OPEN pulse, the duration of
which can be defined by the user.

3
COCBDIR Distribution Automation

3. Parameters and events

3.1 General

• Each function block has a specific channel number for serial communication
parameters and events. The channel for COCBDIR is 141.

• The data direction of the parameters defines the use of each parameter as follows:
Data direction Description
R, R/M Read only
W Write only
R/W Read and write

• The different event mask parameters (see section “Control settings”) affect the
visibility of events on the MMI or on serial communication (LON or SPA) as
follows:
Event mask 1 (FxxxV101/102) SPA / MMI (LON)
Event mask 2 (FxxxV103/104) LON
Event mask 3 (FxxxV105/106) LON
Event mask 4 (FxxxV107/108) LON

For example, if only the events E3, E4 and E5 are to be seen on the MMI of the
relay terminal, the event mask value 56 (8 + 16 + 32) is written to the “Event mask
1” parameter (FxxxV101).
In case a function block includes more than 32 events, there are two parameters
instead of e.g. the “Event mask 1” parameter: the parameter “Event mask 1A”
(FxxxV101) covers the events 0...31 and “Event mask 1B”(FxxxV102) the events
32...63.

4
Distribution Automation COCBDIR

3.2 Setting values

3.2.1 Actual settings

Parameter Code Values Unit Default Data Explanation


direction
Pulse width S1 0.1...300.0 s 0.1 R/W Output pulse width

3.2.2 Control settings

Parameter Code Values Unit Default Data Explanation


direction
Output pulse V1 1=Activate - 0 W Remote trigger for output pulse

Event mask 1 V101 0...3 - 2 R/W Event mask 1 for event transmission
(E0 ... E1)

Event mask 2 V103 0...3 - 2 R/W Event mask 2 for event transmission
(E0 ... E1)

Event mask 3 V105 0...3 - 2 R/W Event mask 3 for event transmission
(E0 ... E1)

Event mask 4 V107 0...3 - 2 R/W Event mask 4 for event transmission
(E0 ... E1)

3.3 Events

Code Weighting Default Event reason Event state


coefficient mask
E0 1 0 Breaker direct open command Deactivated

E1 2 1 Breaker direct open command Activated

5
COCBDIR Distribution Automation

4. Technical data
Operation accuracies Pulse width accuracy:

The accuracies depend on the function block execution interval (that


can be selected) and the pulse width setting value, i.e. whether the
setting value is a multiple of the execution interval or not. The symbol
“Tex” denotes the execution interval in ms.

Open pulse width:

± 2% of set value or ±10 ms (if the pulse width is a multiple of the


execution interval)

± 2% of set value or 0...Tex±10 ms (if the pulse width is not a


multiple of the execution interval)

Configuration data Task execution interval (Relay Configuration Tool): 20 ms


at the rated frequency fn = 50 Hz

Technical revision history


Technical revision Change
B Corrected: MMI indications could not be cleared with the C button in revision A

C Event reason text changed