Professional Documents
Culture Documents
Contents
1. Description.................................................................................................. 2
1.1 Features................................................................................................ 2
1.2 Application ............................................................................................ 2
1.3 Input description ................................................................................... 2
2. Description of operation............................................................................ 3
2.1 General ................................................................................................. 3
2.2 How to use ............................................................................................ 3
1. Description
1.1 Features
1.2 Application
2
Distribution Automation EVENT230
2. Description of operation
2.1 General
The “FALSE -> TRUE” input (IN) signal transition signifies an activating event
occurrence (odd event codes), whereas the “TRUE -> FALSE” input (IN) signal
transition signifies a deactivating event occurrence (even event codes).
Each edge occurrence causes an event generation with an event code and a time stamp.
The event code is internally selected based on the IEC_ADDR input. For selecting the
IEC address, see the events table below. Optionally, one data value may be passed
with the event.
Events to be generated with these functions are found in the local MMI event list.
Note that if the event is masked, it will not be shown in the MMI event list.
This function can be instantiated 32 times per single relay configuration at the
maximum. Each instance should have a unique IEC address. The software does not
check the amount of instances or uniqueness of the IEC addresses.
Assign the desired IEC address as a constant (integer in range 0…31) into the input
IEC_ADDR. If this input is left unconnected, no events are sent. Do not add any
selection logic to change the value of this input during run-time operation.
This function can be freely assigned to any task cycle desired. Still, be careful not to
generate excessive amounts of events since this may cause event buffer overflow
situations. If the event buffer overflows, no events will be sent until the overflow
situation repeals. Note that EVENT230 will not try to re-send any events it failed to
send due to buffer overflow.
If the input IN is active during the relay start-up (or restart due to configuration
download), EVENT230 will not send the activating event. It will only memorize the
initial state of IN. Only real signal edges generate events.
For example, the following function block diagram can be used to send status of one
relay binary input to the IEC address 12:
3
EVENT230 Distribution Automation
One floating point data may be sent to SCADA with the EVENT230. This is useful for
example in reporting the power factor calculated by the MEPE7 function block. In the
example below, standard timers TON and TP are used to trigger the EVENT230 every
10 seconds. The local feedback variable should have an initial value FALSE.
4
Distribution Automation EVENT230
3. Setting values
5
EVENT230 Distribution Automation
4. Measurement values
4.1 Events
Note that in the tables below, the data in columns “Default” and “Event reason” is the
same for all events.
Events 0...31:
6
Distribution Automation EVENT230
Events 32…63:
7
EVENT230 Distribution Automation
5. Technical data
Technical revision history
Technical revision Change
B Inputs DATA and IEC_ADDR added; ECODE removed